Vous êtes sur la page 1sur 8

12535-Gastite_Underground-Install_Guide

2/3/11

3:08 PM

Page 1

Underground Gas
Polyethylene (PE) Piping
Installation Guide
February, 2011

Featuring the Con-Stab I.D. Seal Fittings


from Continental Industries, Inc.

12535-Gastite_Underground-Install_Guide

2/3/11

3:08 PM

Page 2

ASSEMBLY INSTRUCTIONS: I.D. SEAL CON-STAB

STEP 1
Verify the polyethylene
(P.E.) pipe being
assembled is the
correct size.

STEP 5
Mark the stab depth by
inserting the pipe into
the chamfer tool and
marking the pipe at the
entrance as shown.

STEP 2
Cut pipe ends square.

STEP 6
If using chamfer tool
with ID gauge, check
for proper chamfer by
inserting pipe over
gauge.

STEP 3
Clean piping thoroughly
to assure there is no
dirt, grease or oil in
assembly area.

STEP 7
Stab pipe completely
into fitting entrance.

STEP 4
Chamfer end of pipe
using Continentals
chamfering tool with I.D.
gauge.

STEP 8
Stab pipe completely
into fitting so that the
mark on the pipe is
within 1/8" from the
fitting entrance.

STEP 9
Repeat steps 1 though 4 for all Con-Stab joints.
STEP 10
To assure proper assembly and to comply with 49
CFR 192 Subpart J-Test requirements, the joint shall
be leak tested.

See Technical Bulletins 34-6448-00


& 34-6448-01 for further information
regarding I.D. Seal Con-Stab Fittings.

Each Con-Stab I.D. Seal Fitting


provides the following unique
features:
Two internal seals
Fixed stiffener
Self-locking gripper
Moisture lip
Uni-body construction

Patent #s 5,366,260,5,692,785 & 5,853,272

Gastite Division 1116 Vaughn Parkway Portland, TN 37148

12535-Gastite_Underground-Install_Guide

2/3/11

3:08 PM

Page 3

INSTALLATION GUIDELINES:
1) Polyethylene (PE) gas piping shall be installed outside, underground only. PE is not approved for indoor use
or for encasement in concrete.
2) Underground gas piping shall be installed with sufficient clearance from any other underground structure to
avoid contact, to allow maintenance, and to protect against damage from proximity to other structures. In
addition, underground plastic piping shall be installed with sufficient clearance, or shall be insulated from
any source of heat so as to prevent heat from impairing the serviceability and reliability of the pipe.
3) Careful attention should be paid to layout and routing to prevent excessive stressing of the piping where
there is heavy vehicular traffic, or soil conditions are unstable and setting of piping could occur. ABS or PVC
piping may be used for additional protection.
4) Piping shall be protected from physical damage where it passes through flowerbeds, shrub beds, and any
other cultivated areas where damage is reasonably expected.
5) Polyethylene piping shall be installed so as to minimize thrust forces caused by expansion and contraction of
the piping. Typical polyethylene piping will expand or contract 1 inch for every 10 F temperature change for
every 100 feet of pipe.
6) Piping shall be buried or covered in a manner so as to protect the piping from physical damage and in
accordance with the following guidelines.
a) Cover Requirements Underground piping systems shall be installed with at least 18 inches of coverage.
The cover may be reduced to 12 inches if external damage to the pipe is not likely to result. If a minimum of
12 inches of cover cannot be maintained, the pipe shall be installed in a conduit or otherwise protected or
shielded.
b) Trenches The trench shall be graded so that the pipe has a firm, substantially continuous bearing on the
bottom of the trench. It should also be free of rocks and debris that would abrade the PE piping. This may
require additional material such as loom, topsoil or sand to create a level surface.
c) Backfilling Where flooding of the trench is done to consolidate the backfill, care should be exercised to
see that the pipe is not floated from its firm bearing on the trench bottom.
7) An electrically continuous corrosion-resistant tracer wire (minimum AWG 14) or magnetic tape shall be
buried with the polyethylene pipe to facilitate locating. One end shall be brought above the ground at a
building wall or riser. The wire or tape shall not be in direct contact with the polyethylene pipe.
8) The maximum allowable pressure test shall be 150 psi and the maximum continuous pressure shall be 60 psi.

Note: The techniques outlines in this bulletin are recommended practice for generic applications.
These practices must be reviewed for compliance with all local fuel gas and building codes.
Where a conflict exists between these techniques and local requirements, local requirements will
take precedence.
Con-Stab I.D. Seal System Specifications Meets of Exceeds:
NFPA-58 and NFPA-54
ASTM D-2513, Category 1
ASME B31.8-1995
CAN/CSA-B137.4
Listed with CSA
Listed with IAMPO/UPC
US DOT Part 192.283
ISO 4437
Ph: 1.800.662.0208 Fax: 615.325.9407 Web: www.gastite.com

12535-Gastite_Underground-Install_Guide

2/3/11

3:08 PM

Page 4

NATURAL GAS SIZING TABLES FOR PE PIPE


Maximum Capacity of PE Pipe in Cubic Feet per Hour
with a Gas Pressure of 6.0 in. WC and a Pressure Drop of 0.5 in. WC
(based on a 0.60 specific gravity gas)
Tubing Length (ft)

Tubing
Size

1/2" CTS

110

74

59

50

44

39

33

29

26

24

22

21

3/4" IPS

635

426

338

286

252

227

192

169

152

139

129

120

1" CTS

823

553

438

371

326

294

249

219

197

180

167

156

529

465

419

355

312

281

257

238

10

15

20

25

30

40

50

60

70

80

90

100

125

150

20

17

16

113

100

90

147

129

116

223

209

184

166

1" IPS

1173

787

624

1-1/4" IPS

2108

1415

1121

950

835

752

638

561

505

462

428

400

376

331

298

1-1/2" IPS

2765

1900

1526

1306

1158

1049

898

796

721

663

617

579

547

485

439

2" IPS

5954

3997

3166

2683

2360

2125

1801

1584

1426

1305

1209

1130

1063

935

842

Tubing
Size

200

250

300

400

500

600

700

800

900

1000

1100

1200

1300

1400

1500

1/2" CTS

13

12

10

3/4" IPS

76

67

60

51

45

40

37

34

32

30

29

27

26

25

24

1" CTS

99

87

78

66

58

52

48

44

42

39

37

35

34

32

31

1" IPS

141

124

111

94

83

75

68

63

59

56

53

50

48

46

44

1-1/4" IPS

253

222

200

170

149

134

123

114

106

100

95

90

86

83

79

1-1/2" IPS

376

333

302

258

229

207

191

178

167

157

149

143

137

131

126

2" IPS

714

628

565

479

421

380

347

322

301

283

268

255

243

233

224

Tubing Length (ft)

1000BTUh=1CFH

Maximum Capacity of PE Pipe in Cubic Feet per Hour


with a Gas Pressure of 6.0 to 7.0 in. WC (1/4 psig) and a Pressure Drop of 1.0 in. WC
(based on a 0.60 specific gravity gas)
Tubing Length (ft)

Tubing
Size

10

1/2" CTS

165

111

88

74

65

59

50

44

39

36

33

31

29

26

23

3/4" IPS

947

636

503

427

375

338

286

252

227

208

192

180

169

149

134

1" CTS

1228

824

653

553

487

438

371

327

294

269

249

233

219

193

174

1" IPS

1749

1174

930

788

693

624

529

465

419

384

355

332

312

275

247

1-1/4" IPS

3143

2110

1671

1416

1246

1122

951

836

753

689

638

596

561

494

445

1-1/2" IPS

4023

2765

2221

1900

1684

1526

1306

1158

1049

965

898

842

796

705

639

2" IPS

8878

5960

4720

4001

3519

3169

2686

2362

2127

1947

1803

1685

1586

1395

1256

Tubing
Size

200

250

300

400

500

600

700

800

900

1000

1100

1200

1300

1400

1500

1/2" CTS

20

17

16

13

12

10

10

3/4" IPS

114

100

90

76

67

60

55

51

48

45

43

41

39

37

36

1" CTS

147

129

117

99

87

78

72

66

62

58

55

53

50

48

46

1" IPS

210

184

166

141

124

112

102

95

88

83

79

75

71

69

66

1-1/4" IPS

377

331

298

253

223

200

183

170

159

149

141

135

128

123

118

1-1/2" IPS

547

485

439

376

333

302

278

258

242

229

217

207

199

191

184

2" IPS

1065

936

843

715

629

566

518

480

448

422

399

380

363

348

334

15

20

25

30

40

50

60

70

80

90

100

125

150

Tubing Length (ft)

1000BTUh=1CFH

Gastite Division 1116 Vaughn Parkway Portland, TN 37148

12535-Gastite_Underground-Install_Guide

2/3/11

3:08 PM

Page 5

NATURAL GAS SIZING TABLES FOR PE PIPE


Maximum Capacity of PE Pipe in Cubic Feet per Hour
with a Gas Pressure of 8.0 in. WC and a Pressure Drop of 3.0 in. WC
(based on a 0.60 specific gravity gas)
Tubing
Size

Tubing Length (ft)


5

10

15

20

25

30

40

50

60

70

80

90

100

125

150

1/2" CTS

308

210

166

141

124

111

94

83

75

68

63

59

56

49

44

3/4" IPS

1773

1205

955

809

712

641

543

478

430

394

365

341

321

282

254

1" CTS

2298

1561

1236

1048

921

830

703

619

557

510

472

441

415

365

329

1" IPS

3275

2198

1741

1476

1298

1169

991

871

785

718

665

621

585

514

463

1-1/4" IPS

5885

4002

3170

2686

2363

2128

1803

1586

1428

1307

1211

1131

1065

937

843

1-1/2" IPS

7290

5010

4023

3443

3052

2765

2367

2097

1900

1748

1627

1526

1442

1278

1158

2" IPS

16623

10940

8665

7344

6459

5816

4930

4336

3904

3573

3309

3093

2911

2560

2305

Tubing
Size

200

250

300

400

500

600

700

800

900

1000

1100

1200

1300

1400

1500

1/2" CTS

37

33

30

25

22

20

18

17

16

15

14

13

13

12

12

3/4" IPS

215

189

171

145

127

113

103

96

90

84

80

76

72

69

67

1" CTS

279

245

221

187

165

147

134

124

116

109

103

98

94

90

87

1" IPS

393

345

311

264

232

209

191

177

165

156

147

140

134

128

123

1-1/4" IPS

715

629

566

480

422

375

343

318

297

280

265

252

241

230

222

Tubing Length (ft)

1-1/2" IPS

991

878

796

681

604

547

503

468

439

415

394

376

360

346

333

2" IPS

1954

1719

1548

1312

1154

1060

970

898

839

790

748

711

679

651

626

1000BTUh=1CFH

Maximum Capacity of PE Pipe in Cubic Feet per Hour


with a Gas Pressure of 12.0 to 14 in. WC (1/2 psig or less) and a Pressure Drop of 6.0 in. WC
(based on a 0.60 specific gravity gas)
Tubing
Size

Tubing Length (ft)


5

10

15

20

25

30

40

50

60

70

80

90

100

125

150

1/2" CTS

462

310

246

208

183

165

140

123

111

101

94

88

83

73

65

3/4" IPS

2657

1784

1413

1197

1053

948

804

707

637

583

540

504

475

417

376

1" CTS

3445

2313

1832

1553

1366

1230

1042

917

825

755

700

654

615

541

487

1" IPS

4909

3295

2610

2212

1946

1752

1485

1306

1176

1076

997

932

877

771

694

1-1/4" IPS

8821

5922

4690

3975

3496

3148

2668

2347

2114

1934

1791

1674

1576

1386

1248

1-1/2" IPS

10606

7290

5854

5010

4440

4023

3443

3052

2765

2544

2367

2221

2097

1859

1684

2" IPS

24918

16727

13249

11229

9877

8894

7538

6630

5970

5464

5060

4729

4451

3915

3525

Tubing
Size

200

250

300

400

500

600

700

800

900

1000

1100

1200

1300

1400

1500

1/2" CTS

55

49

44

37

33

29

27

25

23

22

21

20

19

18

17

3/4" IPS

319

280

252

214

188

169

155

144

134

126

120

114

109

104

100

1" CTS

413

363

327

277

244

220

201

186

174

164

155

147

141

135

130

1" IPS

589

518

466

395

348

313

286

265

248

233

221

210

201

192

185

1-1/4" IPS

1058

930

838

710

625

562

515

477

445

419

397

377

361

345

332

1-1/2" IPS

1442

1278

1158

991

878

796

732

681

639

604

573

547

524

503

485

2" IPS

2988

2628

2366

2006

1764

1589

1454

1346

1258

1184

1121

1066

1018

976

938

Tubing Length (ft)

1000BTUh=1CFH

Ph: 1.800.662.0208 Fax: 615.325.9407 Web: www.gastite.com

12535-Gastite_Underground-Install_Guide

2/3/11

3:08 PM

Page 6

NATURAL GAS SIZING TABLES FOR PE PIPE - ELEVATED PRESSURE


Maximum Capacity of PE Pipe in Cubic Feet per Hour with a Gas Pressure of 2.0 psi and a Pressure Drop of 1.0 psi
(based on a 0.60 specific gravity gas)

Tubing
Size
1/2" CTS
3/4" IPS
1" CTS
1" IPS
1-1/4" IPS
1-1/2" IPS
2" IPS

Tubing
Size
1/2" CTS
3/4" IPS
1" CTS
1" IPS
1-1/4" IPS
1-1/2" IPS
2" IPS

Tubing Length (ft)


5
1167
6710
8687
12396
22276
25532
62923

10
783
4504
5832
8321
14953
17548
42239

15
621
3568
4619
6591
11844
14092
33455

20
526
3024
3915
5586
10038
12061
28355

25
463
2660
3443
4913
8829
10689
24940

30
417
2395
3101
4424
7950
9685
22458

40
353
2030
2628
3750
6738
8289
19034

200
140
805
1042
1486
2671
3470
7544

250
123
708
916
1307
2349
3076
6636

300
111
637
825
1177
2115
2787
5975

400
94
540
699
998
1793
2385
5064

500
83
475
615
878
1577
2114
4455

600
74
428
554
790
1420
1915
4011

700
68
391
507
723
1300
1762
3671

50
311
1785
2311
3298
5927
7347
16742

60
280
1608
2081
2970
5337
6657
15076

70
256
1471
1905
2718
4884
6124
13797

80
237
1363
1764
2517
4523
5697
12777

90
221
1273
1649
2352
4227
5345
11941

100
208
1198
1552
2214
3979
5049
11239

125
183
1054
1365
1947
3500
4475
9885

150
165
949
1229
1754
3151
4055
8902

1000
55
319
413
589
1059
1453
2990

1100
53
302
391
558
1002
1380
2831

1200
50
287
372
530
953
1316
2693

1300
48
274
355
507
910
1261
2572

1400
46
263
340
485
872
1211
2464

1500
44
253
327
467
838
1167
2368

Tubing Length (ft)


800
63
363
469
670
1204
1639
3400

900
59
339
439
626
1125
1538
3177

1000BTUh=1CFH

Maximum Capacity of PE Pipe in Cubic Feet per Hour with a Gas Pressure of 5.0 psi and a Pressure Drop of 3.5 psi
(based on a 0.60 specific gravity gas)

Tubing Length (ft)

Tubing
Size

5
1/2" CTS
2544
3/4" IPS
14628
1" CTS
18966
1" IPS
27024
1-1/4" IPS 48561
1-1/2" IPS 53153
2" IPS
137172

Tubing
Size
1/2" CTS
3/4" IPS
1" CTS
1" IPS
1-1/4" IPS
1-1/2" IPS
2" IPS

10
1708
9819
12731
18141
32598
36532
92082

15
1353
7777
10084
14368
25819
29336
72933

20
1147
6592
8546
12178
21883
25108
61813

25
1008
5798
7517
10711
19248
22253
54370

30
908
5221
6769
9645
17332
20163
48959

40
770
4425
5737
8175
14689
17257
41494

250
268
1543
2000
2850
5121
6403
14466

300
242
1389
1801
2566
4612
5802
13027

400
205
1177
1526
2175
3908
4965
11041

500
180
1036
1343
1913
3438
4401
9711

600
162
932
1209
1723
3096
3987
8745

700
148
853
1106
1577
2833
3668
8003

50
677
3892
5046
7190
12921
15294
36498

60
610
3505
4544
6475
11635
13858
32865

70
558
3207
4159
5925
10648
12749
30078

80
517
2970
3851
5488
9861
11860
27855

90
483
2776
3599
5128
9215
11128
26031

100
454
2613
3387
4827
8673
10512
24500

125
400
2298
2980
4246
7629
9316
21550

150
360
2069
2683
3823
6870
8441
19405

1000
121
695
901
1284
2308
3025
6519

1100
114
658
853
1216
2185
2873
6171

1200
109
626
812
1156
2078
2741
5870

1300
104
598
775
1104
1985
2624
5606

1400
100
573
743
1058
1902
2521
5372

1500
96
551
714
1017
1828
2429
5163

Tubing Length (ft)


200
305
1754
2274
3240
5822
7225
16447

800
137
790
1025
1460
2624
3413
7411

900
128
739
958
1364
2452
3202
6926

1000BTUh=1CFH

Maximum Capacity of PE Pipe in Cubic Feet per Hour with a Gas Pressure of 10.0 psi and a Pressure Drop of 5.0 psi
(based on a 0.60 specific gravity gas)

Tubing Length (ft)

Tubing
Size

5
1/2" CTS
3529
3/4" IPS
20291
1" CTS
26309
1" IPS
37487
1-1/4" IPS 67362
1-1/2" IPS 72320
2" IPS
190283

Tubing
Size
1/2" CTS
3/4" IPS
1" CTS
1" IPS
1-1/4" IPS
1-1/2" IPS
2" IPS

10
2369
13621
17661
25164
45220
49705
127734

15
1877
10789
13988
19931
35816
39915
101171

20
1590
9144
11856
16893
30355
34162
85746

25
1399
8043
10428
14858
26700
30277
75421

30
1260
7242
9390
13380
24043
27433
67915

40
1068
6138
7958
11340
20377
23479
57560

250
372
2140
2775
3953
7104
8712
20067

300
335
1927
2498
3560
6397
7894
18070

400
284
1633
2118
3017
5422
6756
15315

500
250
1437
1863
2654
4769
5988
13471

600
225
1294
1677
2390
4294
5425
12130

700
206
1184
1535
2187
3930
4991
11101

50
939
5399
7000
9974
17923
20809
50629

60
846
4862
6303
8982
16139
18855
45590

70
774
4449
5769
8220
14770
17346
41723

80
717
4120
5342
7612
13679
16137
38639

90
670
3851
4993
7114
12783
15141
36109

100
630
3624
4699
6696
12032
14302
33987

125
554
3188
4133
5889
10583
12676
29894

150
499
2871
3722
5303
9530
11485
26919

1000
168
964
1250
1782
3201
4115
9043

1100
159
913
1184
1686
3031
3908
8561

1200
151
868
1126
1604
2883
3729
8143

1300
144
829
1075
1532
2753
3571
7777

1400
138
795
1030
1468
2638
3430
7452

1500
133
764
990
1411
2536
3305
7162

Tubing Length (ft)


200
423
2433
3154
4495
8077
9830
22815

800
191
1096
1421
2025
3640
4643
10281

900
178
1025
1328
1893
3401
4357
9608

1000BTUh=1CFH

Gastite Division 1116 Vaughn Parkway Portland, TN 37148

12535-Gastite_Underground-Install_Guide

2/3/11

3:08 PM

Page 7

LP GAS SIZING TABLES FOR PE PIPE


Maximum Capacity of PE Pipe in Thousands of BTU per Hour of Liquefied Petroleum Gas
with a Gas Pressure of 11.0 in. WC and a Pressure Drop of 0.5 in. WC
(based on a 1.52 specific gravity gas)

Tubing
Size
1/2" CTS
3/4" IPS
1" CTS
1" IPS
1-1/4" IPS
1-1/2" IPS
2" IPS

Tubing
Size
1/2" CTS
3/4" IPS
1" CTS
1" IPS
1-1/4" IPS
1-1/2" IPS
2" IPS

Tubing Length (ft)


5
187
1073
1391
1983
3563
4724
10063

10
125
720
934
1331
2391
3247
6755

15
99
571
740
1054
1894
2608
5351

20
84
484
627
893
1605
2232
4535

25
74
425
551
786
1412
1978
3989

30
67
383
497
708
1272
1792
3592

40
56
325
421
600
1078
1534
3044

200
22
129
167
238
427
642
1207

250
20
113
147
209
376
569
1061

300
18
102
132
188
338
516
956

400
15
86
112
160
287
441
810

500
13
76
99
140
252
391
712

600
12
68
89
126
227
354
642

700
11
63
81
116
208
326
587

50
50
286
370
528
948
1359
2678

60
45
257
333
475
854
1232
2411

70
41
235
305
435
781
1133
2207

80
38
218
283
403
723
1054
2044

90
35
204
264
376
676
989
1910

100
33
192
249
354
636
934
1797

125
29
169
219
311
560
828
1581

150
26
152
197
280
504
750
1424

1000
9
51
66
94
169
269
478

1100
8
48
63
89
160
255
453

1200
8
46
60
85
152
244
431

1300
8
44
57
81
146
233
411

1400
7
42
54
78
140
224
394

1500
7
40
52
75
134
216
379

Tubing Length (ft)


800
10
58
75
107
192
303
544

900
9
54
70
100
180
285
508

2516BTUh=1CFH

Maximum Capacity of PE Pipe in Thousands of BTU per Hour of Liquefied Petroleum Gas
with a Gas Pressure of 2.0 psi and a Pressure Drop of 1.0 psi
(based on a 1.52 specific gravity gas)

Tubing Length (ft)

Tubing
Size

5
1/2" CTS
1966
3/4" IPS
11300
1" CTS
14652
1" IPS
20877
1-1/4" IPS 37514
1-1/2" IPS 43429
2" IPS
105963

Tubing
Size
1/2" CTS
3/4" IPS
1" CTS
1" IPS
1-1/4" IPS
1-1/2" IPS
2" IPS

10
1319
7586
9835
14014
25183
29848
71131

15
1045
6008
7790
11100
19946
23969
56339

20
886
5092
6602
9408
16905
20515
47750

25
779
4479
5807
8275
14869
18182
42000

30
702
4033
5229
7451
13389
16474
37820

40
595
3418
4432
6315
11348
14100
32054

250
207
1192
1545
2202
3956
5232
11175

300
187
1073
1391
1983
3563
4740
10063

400
158
910
1179
1680
3019
4057
8529

500
139
800
1037
1478
2656
3596
7502

600
125
720
934
1331
2391
3258
6755

700
115
659
855
1218
2189
2997
6182

50
523
3007
3898
5555
9982
12496
28194

60
471
2707
3510
5002
8988
11322
25388

70
431
2478
3213
4578
8226
10417
23234

80
399
2295
2975
4239
7618
9691
21517

90
373
2144
2780
3962
7119
9092
20108

100
351
2018
2617
3729
6700
8589
18926

1000
93
537
696
992
1783
2471
5036

1100
88
508
659
939
1688
2347
4767

1200
84
484
627
893
1605
2239
4535

1300
80
462
599
853
1533
2144
4331

125
309
1775
2302
3280
5894
7612
16647

150
278
1599
2073
2953
5307
6897
14990

Tubing Length (ft)


200
236
1355
1757
2503
4498
5903
12705

800
106
611
792
1128
2027
2788
5725

900
99
571
740
1054
1894
2616
5350

1400
1500
77
74
443
425
574
551
818
786
1469
1412
2060
1985
4150
3988
2516BTUh=1CFH

Maximum Capacity of PE Pipe in Thousands of BTU per Hour of Liquefied Petroleum Gas
with a Gas Pressure of 10.0 psi and a Pressure Drop of 1.0 psi
(based on a 1.52 specific gravity gas)

Tubing Length (ft)

Tubing
Size

5
1/2" CTS
2476
3/4" IPS
14234
1" CTS
18455
1" IPS
26296
1-1/4" IPS 47252
1-1/2" IPS 53960
2" IPS
133476

Tubing
Size
1/2" CTS
3/4" IPS
1" CTS
1" IPS
1-1/4" IPS
1-1/2" IPS
2" IPS

10
1662
9555
12388
17652
31720
37087
89601

15
1316
7568
9812
13981
25123
29782
70967

20
1116
6414
8316
11849
21293
25489
60148

25
981
5642
7315
10423
18729
22591
52905

30
884
5080
6587
9385
16865
20469
47640

40
749
4306
5583
7954
14294
17519
40376

250
261
1501
1946
2773
4983
6500
14077

300
235
1352
1753
2497
4487
5890
12676

400
199
1146
1485
2116
3803
5041
10743

500
175
1008
1306
1862
3345
4468
9449

600
158
907
1176
1676
3012
4048
8509

700
144
830
1077
1534
2757
3724
7787

50
659
3787
4910
6997
12572
15527
35514

60
593
3410
4422
6300
11321
14068
31980

70
543
3121
4047
5766
10361
12943
29267

80
503
2890
3747
5340
9595
12041
27104

90
470
2701
3502
4990
8967
11297
25329

100
442
2542
3296
4697
8440
10671
23840

125
389
2236
2899
4131
7423
9458
20970

150
350
2014
2611
3720
6685
8569
18882

1000
118
676
877
1250
2246
3071
6343

1100
111
640
830
1183
2126
2916
6005

1200
106
609
790
1125
2022
2782
5712

1300
101
582
754
1075
1931
2664
5455

1400
97
557
723
1030
1851
2560
5227

1500
93
536
695
990
1779
2466
5024

Tubing Length (ft)


200
297
1707
2213
3153
5665
7334
16004

800
134
769
997
1421
2553
3465
7212

900
125
719
932
1328
2386
3251
6739

2516BTUh=1CFH

Ph: 1.800.662.0208 Fax: 615.325.9407 Web: www.gastite.com

12535-Gastite_Underground-Install_Guide

2/3/11

3:08 PM

Page 8

TECHNICAL DATA
Part Number

Tubing Size

Average OD

SDR

Min. Wall

PE-8

1/2" CTS

.625

7.0

0.090

PE-12

3/4" IPS

1.050

11.0

0.095

PE-16

1" CTS

1.125

11.5

0.099

PE-16-IPS

1" IPS

1.315

11.0

0.120

PE-20

1-1/4" IPS

1.660

10.0

0.166

PE-24

1-1/2" IPS

1.900

11.0

0.173

PE-32

2" IPS

2.375

11.0

0.216

Normal Pipe Size and SDR must be used to match fittings and IPS PE pipe.
Nominal Pipe Size and Min. Wall must be used to match fittings and CTS PE pipe.

Gastite Division
1116 Vaughn Parkway
Portland, TN 37148
Toll Free: 1.800.662.0208
Fax: 615.325.9407
Web: www.gastite.com
E-mail: gastite@gastite.com

Rev. 2/2011

Underground Installation Guide