Académique Documents
Professionnel Documents
Culture Documents
Exhaust emission data sheet: EPA Tier 1 exhaust emission compliance sheet: Sound performance data sheet: Cooling performance data sheet: Prototype test summary data sheet: Standard set-mounted radiator cooling outline: Optional set-mounted radiator cooling outline: Optional heat exchanger cooling outline: Optional remote radiator cooling outline:
Fuel consumption
Ratings Load US gph L/hr
Standby kW (kVA) 140 (175) 1/4 1/2 2.7 10 5.1 19 3/4 7.6 29 Full 10.2 39
Prime kW (kVA) 125 (156) 1/4 1/2 2.5 9 4.6 17 3/4 6.7 25 Full 9.1 34
Engine
Engine manufacturer Engine model Configuration Aspiration Gross engine power output, kWm (bhp) BMEP at rated load, kPa (psi) Bore, mm (in) Stroke, mm (in) Rated speed, rpm Piston speed, m/s (ft/min) Compression ratio Lube oil capacity, L (qt) Overspeed limit, rpm Regenerative power, kW
Standby Prime rating rating Cummins Inc. 6CTA8.3-G2 Cast iron in-line 6 cylinder Turbocharged and aftercooled 179.8 (241.0) 163.4 (219.0) 1551.3 (225.0) 1392.7 (202.0) 114.0 (4.49) 135.1 (5.32) 1500 6.8 (1330.0) 16.8:1 23.8 (25.2) 1850 50 17.00
Continuous rating
Fuel flow
Fuel flow at rated load, L/hr (US gph) Maximum inlet restriction, mm Hg (in Hg) Maximum return restriction, mm Hg (in Hg) 208.2 (55.0) 101.6 (4.0) 254.0 (10.0)
2008|Cummins Power Generation Inc.|All rights reserved|Specifications subject to change without notice|Cummins Power Generation and Cummins are registered trademarks of Cummins Inc. Our energy working for you. is a trademark of Cummins Power Generation. D-3433 (4/08)
Air
Combustion air, m /min (scfm) Maximum air cleaner restriction w/clean filter, kPa (in H2O) 3 Alternator cooling air, m /min (scfm)
3
Continuous rating
Exhaust
Exhaust flow at rated load, m /min (cfm) Exhaust temperature, C (F) Maximum back pressure, kPa (in H2O)
3
5.6 (5241)
5.6 (5241)
100 (212)
Weights2
Unit dry weight kgs (lbs) Unit wet weight kgs (lbs) 1513 (3336)
Notes:
1 2
For non-standard remote installations contact your local Cummins Power Generation representative. Weights represent a set with standard features. See outline drawing for weights of other configurations.
Derating factors
Standby Prime Continuous Engine power available up to 2231 m (7320 ft) at ambient temperatures up to 40 C (104 F). Above 2231 m (7320 ft), derate at 4% per 305 m (1000 ft), and 2% per 11 C (1% per 10 F) above 40 C (104F). Engine power available up to 2231 m (7320 ft) at ambient temperatures up to 40 C (104 F). Above 2231 m (7320 ft), derate at 4% per 305 m (1000 ft), and 2% per 11 C (1% per 10 F) above 40 C (104F).
Ratings definitions
Emergency standby power (ESP): Applicable for supplying power to varying electrical load for the duration of power interruption of a reliable utility source. Emergency Standby Power (ESP) is in accordance with ISO 8528. Fuel Stop power in accordance with ISO 3046, AS 2789, DIN 6271 and BS 5514. Limited-time running power (LTP): Applicable for supplying power to a constant electrical load for limited hours. Limited Time Running Power (LTP) is in accordance with ISO 8528. Prime power (PRP): Applicable for supplying power to varying electrical load for unlimited hours. Prime Power (PRP) is in accordance with ISO 8528. Ten percent overload capability is available in accordance with ISO 3046, AS 2789, DIN 6271 and BS 5514. Base load (continuous) power (COP): Applicable for supplying power continuously to a constant electrical load for unlimited hours. Continuous Power (COP) is in accordance with ISO 8528, ISO 3046, AS 2789, DIN 6271 and BS 5514.
Alternator data
Three phase table1 Feature code Alternator data sheet number 105 C B328 212 110/190 thru 127/220 220/380 thru 254/440 165 Shunt PMG Full load current amps at standby rating Single phase table Feature code Alternator data sheet number Voltage ranges Surge kW Motor starting kVA (at 90% sustained voltage) Shunt PMG Full load current amps at standby rating 110/2202 424 110/190 513 535 678 115/200 487 105 C B328 212 110/220 thru 120/2402 141 315 395 110/2203 636 125 C B327 211 110/190 thru 127/220 220/380 thru 254/440 164 467 583 125 C B339 212 110/190 thru 127/220 220/380 thru 254/440 165 535 678 120/208 468 125 C B339 212 110/220 thru 120/2403 141 315 395 127/220 443 150 C B420 210 110/190 thru 127/220 220/380 thru 254/440 162 400 500 220/380 256 230/400 244 240/415 235 254/440 221
Voltage ranges
Notes:
1. 2. 3.
Single phase power can be taken from a three phase generator set at up to 2/3 set rated 3-phase kW at 1.0 power factor. Also see Note 3 below. The broad range alternators can supply single phase output up to 2/3 set rated 3-phase kW at 1.0 power factor. The extended stack (full single phase output) and 4 lead alternators can supply single phase output up to full set rated 3-phase kW at 1.0 power factor.
Cummins Power Generation rd 1400 73 Avenue N.E. Minneapolis, MN 55432 USA Phone: 763 574 5000 Fax: 763 574 5298 Warning: Back feed to a utility system can cause electrocution and/or property damage. Do not connect to any buildings electrical system except through an approved device or after building main switch is open.