Académique Documents
Professionnel Documents
Culture Documents
Chapter 11
Balanced sequences
Synthesis equations
Synthesis equations
Analysis equations
1 0 = ( + + ) 3 1 2 1 = ( + + ) 3 1 2 2 = ( + + ) 3
Solution
Solution
0 = 0 A 1 = 0 A 2 = 1000 A This example shows that a balanced negative sequence network has only negative sequence components
Balanced circuits
Only line voltages are applicable Line currents and phase currents are applicable
Balanced circuits
= = = For positive phase sequence 1 = 3(300 ) 1 The magnitude of the line current is 3 the phase current and lags by 300
Balanced circuits
For negative phase sequence
2 = 3(+300 ) 2
The magnitude of the line current is 3 the phase current and leads by 300
Balanced Y circuits
Only line currents are applicable Line voltages and phase voltages are applicable
Balanced Y circuits
= = = For positive phase sequence 1 = 3(+300 ) 1 The magnitude of the line voltage is 3 the phase voltage and leads by 300
Balanced Y circuits
For negative phase sequence
2 = 3(300 ) 2
The magnitude of the line voltage is 3 the phase voltage and lags by 300
Example 11.3
Using symmetrical components calculate the power absorbed in the load of example 11.2 and check the answer.
= 1.02300
Actual = 1.02300(500)
= 513.320KW
= 125.5 A
1 = + 30 1 1 Which reduces to
1 = + 30 0 0
Example
Three equal impedances of j30 are connected in . Determine the sequence impedances and draw the sequence networks. Repeat the problem for the case where a mutual impedance of j5 exists between each branch of the load.
Solution
j10
j10
j30
j40
J8.3
J8.3
- self impedance of each phase conductor - self impedance of the neutral conductor - mutual impedance between phase conductors - mutual impedance between neutral and phase conductors
Example
A three phase transmission line has the following voltages at the sending and receiving ends =182+j70 kV =154+j28 kV =72.24-j32.62 kV =44.24-j74.62 kV =-170.24+j88.62 kV =-198.24+j46.62 kV The line impedances are =j60 =j20 =j80 =0 Determine the line currents , and
Solution
= + - 2 = j60 + j80 j60 = j80 = + - 2 = j20 + j80 j60 = j40 Then using = =
Solution
= =
28 + 42 80 40 40 28 + 42 x103 = 40 80 40 28 + 42 40 40 80
Solution
80 40 40 = 40 80 40 40 40 80
262.5 175 = 262.5 175 A 262.5 175
-1
28 + 42 28 + 42 x103 28 + 42
Solution
Using Symmetrical component The sequence components of the line volt drops are 0 1 1 =1 1 3 1 2 1 2 1 2
Solution
0 1 1 =1 1 3 1 2 1 2 1 2 28 + 42 28 + 42 x103 28 + 42
28 + 42 = x103 V 0 0
Solution
0 = + 2 + 3 - 6 = j60 + j40 + j240 j180 = j160 1 = 2 = - = j60 j20 = j40 So 0 = 0 0 1 = 1 1 2 = 2 2
Solution
(28 + 42) 103 = (j160) 0 0 = 262.5 j175 A 0 = j40 1 1 = 0 0 = j40 2 2 = 0 Therefore = = c = 262.5 j175 A
Example
A generator rated at 20 MVA, 13.8 kV has a direct axis subtransient reactance of 0.25 per unit. The negative and zero sequence reactances are 0.35 and 0.10 per unit respectively. The neutral of the generator is solidly grounded. If the generator is unloaded at rated voltage = 1.000 per unit and a single line to ground fault occurs at the machine terminals, which results in the following terminal voltages to ground
Example
= 0 = 1.0.13102.250 0 = 1.0.13 102.25 Determine the subtransient current in the generator and the line-to-line voltages for subtransient conditions due to the fault.
Zero sequence
0 = 3 + 3
0 = Z + 3 + 3
0 = Z + 3 + 3
1 = Z
2 = Z
0 cannot flow due to the absence of a path for current flow between the windings
VAB 0 = Vab0 = 0
VAB =
1
1 Vab1 2
VAB =
1 1 Vab 2
Negative sequence
1 0 - 3 IA = V ab 2
0
Zero sequence
VA =
2
1 Vab1 2
Positive sequence
VA =
1 Vab2 2
Negative sequence
0 = Z + 3
Zero sequence
VAB =
2
1 Vab1 2
Positive sequence
VAB =
1 Vab2 2
Negative sequence
Y transformers
VAB = VAB 2 =
1 1 3 Vab1 300 2 1 3 Vab2 300 2
In per unit VAB1 = Vab1 300 VAB 2 = Vab2 300 The same applies for currents in the per unit case IA1 = Ia1 300 IA2 = Ia2 300
Example
Three identical Y connected resistors form a load with a three phase rating of 2300 V and 500 kVA. If the load has applied voltages = 1840 V = 2760 V = 2300 V Find the line and currents in per unit into the load. Assume that the neutral of the load is not connected to the neutral of the system and select a base of 2300 V, 500 KVA.
Example
If the resistive Y connected load bank is supplied from the low voltage Y side of a Y- transformer, find the line voltages and currents in per unit on the high voltage side of the transformer.
Solution
Voltages and currents on the load side has been calculated previously = 0.882.80 = 1.241.40 0 = 1.0 180 Vab1 = 0.985773.60 Vab2 = 0.2346220.30 Van1 = 0.985743.60 Van2 = 0.2346250.30 Ia1 = 0.985743.60 Ia2 = 0.2346250.30
Solution
The calculated load voltages will be the voltages on the low voltage side of the transformer Vab1 = 0.985773.60 Vab2 = 0.2346220.30 Therefore high voltage side voltages in per unit will be VAB1 = Vab1 300 VAB 2 = Vab2 300 So VAB1 = 0.9857 103.60 VAB 2 = 0.2346 190.30 Next calculate the sequence components of the other lines VBC1 = 0.9857 (103.6120)0 = 0.9857 16.40 VCA1 = 0.9857 (103.6+120)0 = 0.9857 223.60 VBC 2 = 0.2346 (190.3+120)0 = 0.2346 310.30 VCA2 = 0.2346 (190.3120)0 = 0.234670.30
Solution
The line-line voltages on the high voltage side are VAB = VAB 0 + VAB1 + VAB 2 = 0 + 0.9857 103.60 + 0.2346 190.30 = 1.026 116.80 VBC = VBC0 + VBC1 + VBC2 = 0 + 0.9857 16.40 + 0.2346 310.30 = 1.19 22.60 VCA = VCA0 + VCA1 + VCA2 = 0 + 0.9857 223.60 + 0.2346 70.30 = 0.783 144.10
Solution
The calculated load currents will be the line currents on the low voltage side of the transformer Ia1 = 0.985743.60 Ia2 = 0.2346250.30 Therefore high voltage side voltages in per unit will be IA1 =Ia1 300 IA2 =Ia2 300 So IA1 = 0.9857 73.60 IA2 = 0.2346 220.30 Next calculate the sequence components of the other lines IB1 = 0.9857 (73.6120)0 = 0.9857 46.40 IC1 = 0.9857 (73.6+120)0 = 0.9857 193.60 IB 2 = 0.2346 (220.3+120)0 = 0.2346 340.30 IC 2 = 0.2346 (220.3120)0 = 0.2346100.30
Solution
The line currents on the high voltage side are IA = IA0 + IA1 + IA2 = 0 + 0.9857 73.60 + 0.2346 220.30 = 0.8 82.90 IB = IB 0 + IB 1 + IB 2 = 0 + 0.9857 46.40 + 0.2346 340.30 = 1.2 41.40 IC = IC 0 + IC 1 + IC 2 = 0 + 0.9857 193.60 + 0.2346 100.30 = 1.0 179.90
Sequence Networks
Sequence circuits have been developed for the following components: Loads (Y and ) Synchronous machines Transmission lines Transformers The components when combined make up a network Thus combining sequence circuits together make up a sequence network
Sequence Networks
Recapping sequence circuits: 1. Separate volt drop equations for each sequence can be set up 2. Z1 and Z2 are equal for static components (loads, lines and transformers) Z1 and Z2 are approximately equal for synchronous machines under subtransient conditions
Sequence Networks
Recapping sequence circuits: 3. Z0 is generally different different from and Z1 and Z2 4. Only the positive sequence of synchronous machines contains a voltage source (E) 5. The neutral is reference for positive and negative sequence circuits. Voltage to neutral and voltage to ground are the same
Sequence Networks
Recapping sequence circuits: 6. No positive or negative sequence currents flow between neutral and ground 7. The impedance Zn is not included in positive and negative sequence circuits but is represented as 3 Zn in the zero sequence.
Sequence Networks
Balanced 3 phase systems generally make up a positive sequence set. In such cases, the per phase equivalent circuit is the positive sequence network. Changing a positive sequence network to a negative sequence only involves changing the impedances of rotating machines
Sequence Networks
Consider the one line diagram shown below:
Sequence Networks
Positive sequence network:
XT1-1 Xline-1 XT2-1
Xg-1
Xm1-1
Xm2-1
Sequence Networks
Negative sequence network:
XT1-2 Xline-2 XT2-2
Xg-2
Xm1-1 X
m1-2
Xm2-2
Sequence Networks
Zero sequence network:
XT1-0 Xline-0 XT2-0
3Xgn-0 Xg-0
3Xn1-0
Xm2-0
Xm1-0