Precision Cooling For Business-Critical Continuity

Liebert DSE
System Design Manual80-150kW, 23-43 Tons, Downflow 60Hz

TABLE OF CONTENTS
1.0
1.1

LIEBERT DSE COMPONENTS AND NOMENCLATURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1


Model Number Nomenclature - 25 Digit Configuration Number . . . . . . . . . . . . . . . . . . . . . . 2

2.0 3.0 4.0


4.1 4.2 4.3 4.4 4.5 4.6 4.7

AIR-COOLED PERFORMANCE DATA. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 DIMENSIONS AND EQUIPMENT LAYOUT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8 ELECTRICAL CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31


Standard Electrical Field Connections, DA080, DA085 Downflow Models . . . . . . . . . . . . . 36 CANbus Electrical Connections, DA080, DA085 Downflow Models . . . . . . . . . . . . . . . . . . . 36 Optional Electrical Field Connections, DA080, DA085, Downflow Models . . . . . . . . . . . . . 37 Optional Low Voltage Terminal Package Field Connections, DA080, DA085, Downflow Models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37 Liebert DSE Electrical Field Connection Descriptions, DA125 and DA150 Downflow Models Standard Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40 Optional Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40 Optional Low Voltage Terminal Package Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41

GUIDE SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .42

FIGURES
Figure 1 Figure 2 Figure 3 Figure 4 Figure 5 Figure 6 Figure 7 Figure 8 Figure 9 Figure 10 Figure 11 Figure 12 Figure 13 Figure 14 Figure 15 Figure 16 Figure 17 Figure 18 Figure 19 Downflow model component locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Cabinet and floor planning dimensionsdownflow, air-cooled, DA080, DA085, scroll and digital scroll compressor models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Floor stand and floor planning dimensions, DA080, DA085 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Cabinet and floor planning dimensionsdownflow, air-cooled, DA125 and DA150, tandem scroll compressor models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Floor stand dimensionsdownflow, DA125 and DA150 models . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Primary connection locationsdownflow, air-cooled DA080 and DA085, scroll compressor models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Primary connection locationsdownflow, air-cooled, DA125 and DA150, scroll compressor models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Piping schematicair-cooled, tandem compressor models, DA0805, DA085 . . . . . . . . . . . . . . . . 14 Piping schematicair-cooled, tandem compressor models, DA125 and DA150 . . . . . . . . . . . . . . 15 Liebert MC cabinet and anchor dimensions, MCL110, MCL165 and MCL220 . . . . . . . . . . . . . 16 Liebert MC cabinet and anchor dimensions, three-fan, 120 models with 18" legs. . . . . . . . . . . 17 Liebert MC cabinet and anchor dimensions, three-fan, 120 models with 60" legs. . . . . . . . . . . 18 Liebert MC cabinet and anchor dimensions, MCM120 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Typical receiver mounting MCL110, MCL165, MCL220 units, left-side mounting outlet receiver . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Typical receiver mounting MCL110, MCL165, MCL220 units, right-side mounting outlet receiver . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Typical receiver mounting MCM120 units, left-side mounting outlet receiver. . . . . . . . . . . . . . . 22 Typical receiver mounting MCM120 units, right side mounting outlet receiver . . . . . . . . . . . . . 23 Required receiver mounting MCM120 and MCM160 units, left-side mounting outlet receiver . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 Required receiver mounting MCM120, MCM160 units, right-side mounting outlet receiver . . . 25

Figure 20 Figure 21 Figure 22 Figure 23 Figure 24 Figure 25 Figure 26 Figure 27 Figure 28 Figure 29 Figure 30 Figure 31

Leg installation Liebert MC, three-fan cabinet, 120 model. . . . . . . . . . . . . . . . . . . . . . . . . . . . . Plenum dimensionsdownflow, DA080 and DA085 models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Liebert EconoPhase pump box dimensions, typical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Condenser and Liebert EconoPhase unit locations, typical unit arrangement diagram layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Liebert DSE disassembly dimensions, downflow air-cooled DA125 and DA150 models . . . . . . . Electrical field connections Premium Efficiency Control, three-fan models . . . . . . . . . . . . . . . . . Liebert EconoPhase pump box field electrical connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CANbus cable connections between indoor unit, Liebert MC and optional Liebert EconoPhase unit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Electrical field connections, DA080, DA085, single molded case switch disconnect with main fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Electrical field connections, DA080 and DA085 models, dual-fused disconnect switches . . . . . . Electrical field connections for downflow models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Electrical field connections for DA125 and DA150 downflow models . . . . . . . . . . . . . . . . . . . . . .

26 27 28 29 30 31 32 33 34 35 38 39

TABLES
Table 1 Table 2 Table 3 Table 4 Table 5 Table 6 Table 7 Table 8 Table 9 Table 10 Table 11 Capacity data with and EC fans . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Electrical Data - DA080 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Physical dataAir-cooled units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Electrical dataDA125 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Electrical Data - DA085 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Electrical dataLiebert EconoPhase units (PR085 and PR125) . . . . . . . . . . . . . . . . . . . . . . . . . 6 Electrical dataLiebert MC three-fan, three-phase condensers . . . . . . . . . . . . . . . . . . . . . . . . . 6 Electrical Data - DA150 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Liebert MC shipping dimensions and weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Cabinet and anchor dimensions, MCL110, MCL165 and MCL220 . . . . . . . . . . . . . . . . . . . . . . . . 16 Approximate dry weight, includes panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

ii

Liebert DSE Components and Nomenclature

1.0

LIEBERT DSE COMPONENTS AND NOMENCLATURE


Downflow model component locations
3 2 1

Figure 1

11

10

7 5

1. Liebert iCom Control Display 2. Electric Box 3. Filters Plenum (not shipped with unit) 4. Evaporator Coil 5. Fan Modules (internal position) 6. Compressor Section

7. Infrared Humidifier (optional) 8. Disconnect (optional) 9. Condensate Pump (optional) 10. Smoke Sensor (optional) 11. THD Assembly (575V units only)

DPN002402 Rev. 0

Liebert DSE

Liebert DSE Components and Nomenclature

1.1
1 D 2 A

Model Number Nomenclature - 25 Digit Configuration Number


Model #** Part 1/2 3 1 4 2 5 5 6 D 7 A 8 1 9 A 10 T 11 H 12 A 13 0 14 8 Model Details 15 1 16 1 17 D 18 0 19 0 20 S 21 P Model # Part 2 * 22 1 23 2 24 3 25 S

Digits 1-2 - Product Family DA = Liebert DSE Digits 3-5 - Cooling Capacity, kW Nominal Sensible Capacity, kW Digit 6 - Air Discharge Downflow Digit 7 - System Type A = Air-Cooled P = Air-Cooled, Econ-O-Phase Ready Digit 8 - Airflow (Fan Type) 1 = EC Plug Fans Digit 9 - Power Supply A = 460V / 3ph / 60Hz B = 575V / 3ph / 60Hz C = 208V / 3ph / 60Hz D = 230 / 3ph / 60Hz 2 = 380-415 / 3ph / 60Hz Digit 10 - Cooling System D = Digital Scroll, R-410A T = Tandem with Digital, R-410A Digit 11 - Humidification 0 = None H = Infrared Humidifier Digit 12 - Display D = Liebert iCOM Control with Large Display E = Liebert iCOM Control with Large Display with Supply Air Sensor Digit 13 - Reheat 0 = None 1 = Electric Reheat, 30kW Digit 14 - Air Filter 8 = MERV 8, 4" 9 = MERV 11, 4" A = MERV 13, 4" 6 = MERV 11, 2" plus MERV 8 prefilter, 2" C = MERV 13, 2" plus MERV 8 prefilter, 2" Digit 15 - Coil Options 1 = Non-Coated Coil, Indoor Unit 2 = Coated Coil, Indoor Unit Digit 16 - Enclosure Options 1 = Color standard 2 = Color Optional 6 = Color Standard W/Double-Skin Panels 9 = Color Optional W/Double-Skin Panels 3 = Color Standard & IBC/OSHPD Bracing 4 = Color Optional & IBC/OSHPD Bracing 8 = Color Standard, IBC/OSHPD, W/Double-Skin Panels A = Color Optional, IBC/OSHPD, W/Double-Skin Panels *

Digit 17 - High-Voltage Options 0 = No disconnect D = Non-Locking Disconnect L = Locking Disconnect 3 = No Disconnect, With Condensate Pump 4 = Non-Locking Disconnect, With Condensate Pump 5 = Locking Disconnect, With Condensate Pump Digit 18 - Option Packages 0 = None L = Option Package #1 - Low Voltage Terminal Package H = Reheat and Humidifier Lockout R = Remote Humidity Contact C = Option Package #1, Plus Reheat/Humidifier Lockout D = Option Package #1, Plus Remote Humidifier Contact E = Option Package #1, Plus Reheat/Humidifier Lockout, plus remote contact F = Remote Humidity Contact Plus Reheat/Humidifier Lockout Digit 19 - Monitoring Cards 0 = No Cards 1 = IS-WEBL Card 3 = IS-485L Card F = IS-IPBML Card C = IS-485EXI Card 5 = IS-WEBL & IS-485L Cards H = IS-WEBL & IS-IPBML Cards D = IS-WEBL & IS-485EXI Cards J = IS-485L & IS-IPBML Cards E = IS-485L & IS-485EXI Cards K = IS-IPBML & IS-485EXI Cards Digit 20 - Sensors 0 = None S = Smoke Sensor H = High-Temperature Sensor F = Smoke and High-Temperature Sensors C = Compressor Overload Sensors A = Compressor, High-Temperature Sensor D = Compressor, Smoke Sensor K = Compressor, High-Temperature, Smoke Sensors Digit 21 - Packaging P = Domestic Digit 22 - 24 Configuration Code Digit 25 - Configuration Code A=1 S = SFA

The 14-digit model number consists of the first 10 digits and last four digits of the Configuration Number.

Liebert DSE

Air-Cooled Performance Data

2.0

AIR-COOLED PERFORMANCE DATA


Table 1 Capacity data with and EC fans
Model Size Net Capacity Data kW (kBTUH) 95F DB, 67.7F WB, 52.3F DP (35C DB, 19.8.C WB) 24% RH Total, kW (BTUH) Sensible, kW (BTUH) Net Full-Load SCOP (kW/kW) @ 95 Oudoor Ambient (Compressor Mode) Net Full-Load SCOP (kW/kW) @ 35 Oudoor Ambient (Pump Mode) 90F DB, 66.1F WB, 52.3F DP (32.2C DB, 18.9C WB) 28% RH Total, kW (BTUH) Sensible, kW (BTUH) Net Full-Load SCOP (kW/kW) @ 95 Oudoor Ambient (Compressor Mode) Net Full-Load SCOP (kW/kW) @ 35 Oudoor Ambient (Pump Mode) 85F DB, 64.5F WB, 52.3FDP (29.4C DB, 18.1C WB) 32% RH Total, kW (BTUH) Sensible, kW (BTUH) Net Full-Load SCOP (kW/kW) @ 95 Oudoor Ambient (Compressor Mode) Net Full-Load SCOP (kW/kW) @ 35 Oudoor Ambient (Pump Mode) 80F DB, 62.8F WB, 52.3F DP (26.7C DB, 17.1C WB) 38% RH Total, kW (BTUH) Sensible, kW (BTUH) Net Full-Load SCOP (kW/kW) @ 95 Oudoor Ambient (Compressor Mode) Net Full-Load SCOP (kW/kW) @ 35 Oudoor Ambient (Pump Mode) 75F DB, 61.1F WB, 52.3F DP (23.9C DB, 16.2C WB) 45% RH Total, kW (BTUH) Sensible, kW (BTUH) Net Full-Load SCOP (kW/kW) @ 95 Oudoor Ambient (Compressor Mode) Net Full-Load SCOP (kW/kW) @ 35 Oudoor Ambient (Pump Mode) FAN SECTION - Downflow models - Fixed Pitch, Two Belts Standard Air Volume - CFM (CMH) 0.2" external static Operating Fan kW, Total for All Fans Quantity of Fans 9,600 (16,310) 4.6 2 10,400 (17,670) 5.7 2 18,000 (30,582) 5.9 3 18,000 (30,582) 5.9 3 75 (256) 67 (229) 2.6 7.5 86 (294) 73 (249) 2.4 7.2 116 (396) 112 (382) 3.0 10.7 134 (457) 134 (457) 2.4 10.2 83 (283) 72 (246) 2.8 8.2 89 (304) 78 (266) 2.6 7.9 123 (420) 123 (420) 3.3 11.5 145 (494) 145 (494) 2.7 11.1 85 (290) 77 (263) 3.0 9.1 92 (314) 83 (283) 2.7 8.7 130 (444) 130 (444) 3.4 12.2 153 (522) 153 (522) 2.9 12.0 86 (294) 80 (273) 3.1 9.8 98 (334) 88 (300) 3.0 9.4 138 (471) 138 (471) 3.6 14.1 162 (552) 162 (552) 3.1 12.5 88 (300) 84 (287) 3.2 10.5 100 (341) 94 (321) 3.1 10.1 146 (499) 146 (499) 3.8 17.5 170 (581) 170 (581) 3.2 13.0 80 85 125 150

1. Capacity data is rated and factory certified per ASHRAE 127-2007 with a 5% tolerance 2. Some options or combinations of options may result in reduced air flowconsult factory for recommendations.

Liebert DSE

Air-Cooled Performance Data

Table 2

Physical dataAir-cooled units


Model Size Face Area, sq. ft. (sq. m) Rows of Coil Face Velocity, FPM (m/s), STD Air Vol. 80 24.65 (2.3) 6 389.5 (2.0) 85 24.65 (2.3) 6 421.9 (2.2) 125 56.2 (5.2) 6 320.3 (1.6) 150 56.2 (5.2) 6 320.3 (1.6)

EVAPORATOR COIL- A-Frame - Copper Tube/Aluminum Fin

REHEAT SECTION Electric - Three (3) Stage, Stainless Steel Fin Tubular, capacity does not include fan motor heat Capacity,- kW (KBTUH) - Std Selection Capacity, kW (KBTUH) - Opt Selection HUMIDIFIER SECTION Infrared Humidifier Capacity, lb./hr. (kg/h) Nominal Size, inches Quantity Line Sizes Liquid Line, O.D. Copper (2/unit), up to 300 eq ft Hot Gas Line, O.D. Copper (2/unit), up to 300 eq ft. Infrared Humidifier,O.D. Copper Condensate Drain, FPT Condensate Drain w/opt Condensate Pump, OD 7/8" 1-1/8" 1/4" 3/4" 1/2" 7/8" 1-1/8" 1/4" 3/4" 1/2" 7/8" 1-3/8" 1/4" 1-1/8" 1/2 7/8" 1-3/8" 1/4" 1-1/8" 1/2 22 (10) 25 x 20 4 22 (10) 25 x 20 4 22 (10) 21.5 x 24 10 22 (10) 21.5 x 24 10 FILTER SECTION - Disposable Type - Nominal Sizes and Quantities 15 (51.20) 10 (34.13) 15 (51.20) 10 (34.13) 30 (102.4) 10.0 (34.1) 30.0 (102.4) 10.0 (34.1)

Table 3
Unit Voltage Rating 208V

Electrical Data - DA080


Reheat Options Humidifier Options FLA WSA OPD FLA Electric, Std kW Infrared 119.2 128.5 150 114.8 124.1 150 74.8 81.4 100 59.6 64.6 80 46.6 50.2 60 None Infrared 119.2 128.5 150 114.8 124.1 150 74.8 81.4 100 59.6 64.6 80 46.6 50.2 60 Electric, Std kW None 97.1 116.8 125 94.6 113.7 125 62.6 69.2 90 48.0 57.6 70 35.8 43.2 50 None None 92.6 101.9 125 92.6 101.9 125 62.6 69.2 90 48.0 53.0 70 35.0 38.6 50

230V

WSA OPD FLA

380V

WSA OPD FLA

460V

WSA OPD FLA

575V

WSA OPD

Liebert DSE

Air-Cooled Performance Data

Table 4
Unit Voltage Rating 208V

Electrical Data - DA085


Reheat Options Humidifier Options FLA WSA OPD FLA Electric, Std kW Infrared 152.2 165.6 200 147.8 161.2 200 74.8 81.4 100 61.0 66.2 80 50.8 54.9 70 None Infrared 152.2 165.6 200 147.8 161.2 200 74.8 81.4 100 61 66.175 80 50.8 54.9 70 Electric, Std kW None 125.6 139.0 175 125.6 139.0 175 62.6 69.2 90 49.4 58.5 70 39.2 45.775 50 None None 125.6 139.0 175 125.6 139 175 62.6 69.2 90 49.4 54.575 70 39.2 43.3 50

230V

WSA OPD FLA

380V

WSA OPD FLA

460V

WSA OPD FLA

575V

WSA OPD

Table 5
Unit Voltage Rating 208V

Electrical dataDA125
Reheat Options Humidifier Options FLA WSA OPD FLA Electric Std kW Infrared 174.6 193.2 200 170.2 192.5 200 93.6 102.7 110 79.9 92.2 100 63.4 70.7 80 None Infrared 174.6 193.2 200 170.2 192.5 200 93.6 102.7 110 79.9 83.5 90 63.4 66.1 70 Electric Std kW None 165.7 193.2 200 165.2 192.5 200 88.1 102.7 100 78.8 92.2 100 60.5 70.7 80 None None 148 155.7 175 148 155.7 175 81.4 85.7 100 68.3 71.9 80 51.8 54.5 60

230V

WSA OPD FLA

380V *

WSA OPD FLA

460V

WSA OPD FLA

575V

WSA OPD

* 380V version of DA125 is not CSA- listed Full-load amperage values do not reflect operating amperage values.

Liebert DSE

Air-Cooled Performance Data

Table 6
Unit Voltage Rating 208V

Electrical Data - DA150


Reheat Options Humidifier Options FLA WSA OPD FLA Electric Std kW Infrared 200.2 209.5 225 195.8 206.9 225 130.4 137.0 150 102.7 107.7 125 77.8 81.4 90 None Infrared 200.2 209.5 225 195.8 205.1 225 130.4 137 150 102.7 107.7 125 77.8 81.4 90 Electric Std kW None 182.2 207.6 225 181.9 206.9 225 118.2 128.1 150 93.7 104.3 110 69.3 77.2 80 None None 173.6 182.9 200 173.6 182.9 200 118.2 124.8 150 91.1 96.1 110 66.2 69.8 80

230V

WSA OPD FLA

380V *

WSA OPD FLA

460V

WSA OPD FLA

575V

WSA OPD

Table 7
Unit Voltage Rating 208/230V

Electrical dataLiebert EconoPhase units (PR085 and PR125)


Electrical Characteristic FLA WSA OPD FLA

Amperes 13.8 15.5 20 8.4 9.4 15 7.0 7.9 15 5.6 6.3 15

380V *

WSA OPD FLA

460V

WSA OPD FLA

575V

WSA OPD

* 380V version of pump box is not CSA-listed

Table 8
Model Input Voltage 208/230 460

Electrical dataLiebert MC three- and four-fan, three-phase condensers


MCL110 MCM120 MCM160 MCL165 MCL220

FLA WSA OPD FLA WSA OPD FLA WSA OPD FLA WSA OPD FLA WSA OPD 11.4 5.6 12.8 6.3 15 15 6.9 4.2 7.5 4.6 15 15 9.2 5.6 9.8 6.0 15 15 17.1 8.4 18.5 9.1 20 15 22.8 11.2 24.2 11.9 25 15

1. FLA = Full Load Amps; WSA = Wire Size Amps; OPD = Maximum Overcurrent Protection Device. 2. Must be connected to Wye 3-phase systems with solidly grounded neutral. 3. Source: 306258, Rev. 1

Liebert DSE

Air-Cooled Performance Data

Table 9

Liebert MC shipping dimensions and weights


# of Fans 2 3 3 4 Dimensions, L x W x H in. (mm) 124-1/8 x 55-5/8 x 43-5/8 (3152 x 1413 x 1108) 153 x 54 x 82 (3886 x 1372 x 2083) 180-1/4 x 55-5/8 x 43-5/8 (4578 x 1413 x 1108) 236-3/8 x 55-5/8 x 43-5/8 (6003 x 1413 x 1108) Weights, Approximate lb. (kg) 605 (273) 3785 (1717) 890 (404) 1185 (538)

Model # MCL110 MCM120 MCL165 MCL220

Liebert DSE

Dimensions and Equipment Layout

3.0

DIMENSIONS AND EQUIPMENT LAYOUT


Cabinet and floor planning dimensionsdownflow, air-cooled, DA080, DA085, scroll and digital scroll compressor models
Secondary Refrigerant Piping Entrance 80" (2032mm) Opening Notes: Filters are accessible through top of unit only. Downflow electrical connections can be made from top or bottom of unit. 3/4" (19mm) Bezels

Figure 2

33" (838mm) 35" (889mm)

AIR INLET OPENING

24-5/8" (625mm) Opening

Secondary Entrance High Volt Connection(s)

TOP VIEW
Secondary Entrance Low Volt Connections Minimum required for filter replacement

"A "
5" (127mm)

76" (1930mm)

2" (51mm)

"B "

Shaded area indicates a recommended minimum clearance for component access

34" (864mm)

FRONT VIEW
Model No. Weights, lb. (kg) Air-Cooled Dual-Cool Dimensions, in. (mm) Air-Cooled "A" Air Cooled "B"
Source: DPN000925, Rev. 2

DPN000925 Rev. 2
DA085 2250 (1021) N/A 100 (2540) 99 (2515)

DA080 2200 (998) N/A 100 (2540) 99 (2515)

Liebert DSE

Dimensions and Equipment Layout

Figure 3

Floor stand and floor planning dimensions, DA080, DA085


A B

3/4" (19mm)

Piping Access Area

31-1/2" (800mm)

32" (813mm) Center Feet

3/4" (19mm) 3/4" (19mm)

C Support Feet Centers

32-3/4" (832mm)

7/8" (23mm) See Note 4 3" (76mm) 1" (25mm) 33" (838mm)

1. This floor stand should be used when EC fans are intended to be lowered under a raised floor. The standard Liebert DS floor stand can be used if the fans are to remain in their original raised position. 2. Right side of paneled unit is flush with right side of floorstand. All other paneled sides overhang floor stand 1" (25mm). 3) The floor stand used with EC units is not symmetrical and its orientation to the Liebert DSE is critical for lowering the EC fans. Unless the floor stand is installed in the correct position, the blowers will not lower into the floor stand. 4. Jack and jack support are shipped loose and are intended to be placed into position under each fan and utilized to lower or raise that fan as needed. * Leveling feet are provided with 1-1/2" (38mm) adjustment from nominal height C.

F*

35" (889mm) Overall Depth

DPN002151 Rev. 1
Height, F In. (mm) 24 (610) 30 (762) 36 (914) 42 (1067) 48 (1219)

Dimensions, In. (mm) Model # DA080, DA085 Air-Cooled Digital Scroll Models A 99 (2515) B 17 (432) C 97.5 (2477) D 99 (2515) E 100.5 (2553)

Liebert DSE

Dimensions and Equipment Layout

Figure 4

Cabinet and floor planning dimensionsdownflow, air-cooled, DA125 and DA150, tandem scroll compressor models
Filter Plenum (shipped separately)

Secondary Refrigerant Piping Entrance 117-11/16" Opening (2989mm) 47" (1194mm) 45" (1143mm) 3/4" (19mm) Bezels 144" (3658mm) 18" (457mm)

Filters are removed though the front of the plenum 48" (1219mm)

42" (1067mm) Opening

Striated area indicates the recommended minmum clearance for component access.

24" (610mm)

Shaded area indicates the required minimum clearance below the unit to lower the fans into the floor. Fans may remain in their shipped position. 45" (1143mm) Plenum

76" (1930mm) Base Unit

94" (2388mm) Total Height

142" (3607mm)

FRONT VIEW
Dry Weights DA125: 3465lb (1572kg) DA150: 3565 (1617kg)
1" TYP (25mm) 45" (1143mm) 47" (1194mm)

DPN002311 Rev. 0

Liebert DSE

10

Dimensions and Equipment Layout

Figure 5

Floor stand dimensionsdownflow, DA125 and DA150 models


C + 1-1/2" (38mm) (with feet) C D

46-1/2" (1181mm) With Feet 43-1/2" Typ (1105mm) Center Feet Typ

43" (1092mm)

118-1/2" Center Feet (3010mm) 120-3/4" Center Feet (3067mm) 3/4" (19mm) Typical 7/8" (23mm) Typical

59-1/4" Center Feet (1505mm) 1" (25mm) Typical 45" (1143mm) Typical
A*

3" (76mm) Typical

47" (1194mm) Typical

1. This floor stand should be used when EC fans are intended to be lowered into the floor stand. The standard Liebert floor stand can be used if the fans are to remain in their original raised position. 2. All paneled sides of unit overhang floorstand 1" (25mm). 3. The floor stand used with EC units is not symmetrical and proper orientation required for lowering the blowers. Unless the floor stand is installed in the correct position, the blowers will not lower into the floor stand. 4) Jack and jack support are shipped loose and are intended to be placed into position under each fan and utilized to lower or raise that fan as needed individually. 5) Jack to lower blowers not provided with 18" floor stand. * Leveling feet are provided with 1-1/2 (38mm) adjustment from nominal height A.

DPN002315 Rev. 1

Height, in. (mm) A* 24 (610) 30 (762) 36 (914) 42 (1067) 48 (1219) B* 5 (127) 11 (279) 17 (432)

Dimensions, in. (mm) C 142 (3607) D 21 (533)

Source: DPN002315, Rev. 1

11

Liebert DSE

Dimensions and Equipment Layout

Figure 6

Primary connection locationsdownflow, air-cooled DA080 and DA085, scroll compressor models
All dimensions from rear corner of unit including panels

NOTE: Drawing not to scale. Tolerance on all piping dimensions is 1/2" (13mm).

A
FRONT VIEW SECTION A-A

A
X O

R
4" (102mm)
L1 L2 G1 G2

Y
BLOWER OUTLET 35" (889mm)

12-3/16" (310mm) ECS ECR CD


LV1 LV2 LV3

B1

E1

E2 HUM

FRONT OF UNIT
DA = 100" (2540mm)

DPN002182 Rev. 1
Point R Description Refrigerant Access X, in. (mm) 81-3/4 (2076) Y, in. (mm) 14-3/4 (374) Connection Size / Opening 12-3/16 x4" (310mm x 102mm) 53kW (15tons) / 70 & 77kW (20 & 22tons) L1 L2 G1 G2 CD Hum HS HR E1 E2 LV1 LV2 LV3 B1
*

Liquid Line System 1 Liquid Line System 2 Hot Gas Discharge 1 Hot Gas Discharge 2 Condensate Drain (Infrared Humidifier or No Humidifier) * W/ Optional Pump Humidifier Supply Line Hot Water Reheat Supply Hot Water Reheat Return Electrical Connection (High Volt) Electrical Connection (High Volt) Electrical Connection (Low Volt) Electrical Connection (Low Volt) Electrical Connection (Low Volt) Blower Outlet

94-11/16 (2405) 91-7/8 (2334) 88-3/4 (2254) 85-9/16 (2173) 68-3/8 (1737) 68-3/8 (1737) 76-1/2 (1943)

16-3/4 (425) 16-3/4 (425) 16-3/8 (416) 16-3/8 (416) 31-3/8 (797) 31-3/8 (797) 29 (736) Consult Factory Consult Factory

1/2" / 5/8" Cu Sweat 1/2" / 5/8" Cu Sweat 7/8" / 1-1/8" Cu Sweat 7/8" / 1-1/8" Cu Sweat 3/4 FPT 1/2" Cu Sweat 1/4" Cu Sweat

78-1/2 (1994) 75-3/8 (1915) 2 (51) 2 (51) 2 (51) 4-1/2 (114)

31-1/8 (790) 31-1/8 (790) 29 (737) 30-7/8 (784) 32 (813) 33 (838)

2-1/2" 2-1/2" 7/8" 7/8" 7/8" 58-3/8" x 30" (1483mm x 762mm)

Field pitch Condensate Drain line a minimum of 1/8" (3.2mm) per foot (305mm). All units contain a factory installed condensate trap. Do not trap external to the unit. Drain line may contain boiling water; select appropriate drain system materials. The drain line must comply with all local codes. Source: DPN002182, Rev. 1

Liebert DSE

12

Dimensions and Equipment Layout

Figure 7

Primary connection locationsdownflow, air-cooled, DA125 and DA150, scroll compressor models

NOTE: Drawing not to scale. Tolerance on all piping dimensions is 1/2" (13mm).

A
FRONT VIEW SECTION A-A
3-3/8" (86mm)

All dimensions from rear corner of unit including panels

X O

G1 G2

L1 L2

R
Y

19" (483mm)

CD E1 E2 HUM

41" (1041mm) Typical AIR DISCHARGE AREA

29-5/16" (744mm) Typical AIR DISCHARGE AREA


LV1 LV2 LV3

47" (1193mm)

FRONT EDGE OF UNIT


144" (3657mm) Opening for conduit chase, E1 and E2 are openings for conduit for connections to 2-1/2", 1-3/4" and 1-3/8" knockouts at electric panel

DPN002312 Rev. 1

DX Only Point R L1 L2 G1 G2 Description Refrigerant Access Liquid Line System 1 Liquid Line System 2 Hot Gas Discharge 1 Hot Gas Discharge 2 Condensate Drain * (infrared humidifier or no humidifier) CD Condensate Drain (steam generating humidifier) * W/ Optional Pump HUM Humidifier Supply Line HS HR E1 E2 Hot Water Reheat Supply Hot Water Reheat Return Electrical Connection (High Volt) Electrical Connection (High Volt) 113 (2870) 110 (2794) 2-1/2 (64) 2-1/2 (64) 2-1/2 (64) 110 (2794) 101-1/4 (1359) 43 (1091) X inches (mm) 122-5/16 (3106) 127-7/8 (3248) 124-3/16 (3170) 140 (3554) 136-11/16 (3471) 110 (2794) Y inches (mm) 13-3/4 (348) 13-3/4 (348) 14 (355) 14 (355) 35-1/16 (891)

DX with Liebert EconoPhase Unit

Connection Size/ Opening inches (mm) 19 x 3-3/8 (483 x 86) 7/8 Cu Sweat 7/8 Cu Sweat 1-3/8 Cu Sweat 1-3/8 Cu Sweat 1-1/8 FPT 7/8 Cu Sweat 7/8 Cu Sweat 1-1/8 Cu Sweat 1-1/8 Cu Sweat 1-1/8 FPT

12-1/8 (333) 19 x 3-3/8 (483 x 86)

Consult Factory 35-1/16 (891) 1/2 Cu Sweat 1/4 Cu Sweat Consult Factory Consult Factory 42-1/2 (1080) 42-1/2 (1080) 36 (914) 37-1/2 (952) 39 (991) 2-1/2 2-1/2 7/8 7/8 7/8 2-1/2 2-1/2 7/8 7/8 7/8 1/2 Cu Sweat 1/4 Cu Sweat

LV1 Electrical Connection (Low Volt) LV2 Electrical Connection (Low Volt) LV3 Electrical Connection (Low Volt)
*

Field pitch Condensate Drain line a minimum of 1/8" (3.2 mm) per foot (305mm). All units contain a factory-installed condensate trap. Do not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply with all local codes. Source: DPN002312, Rev. 1

13

Liebert DSE

Dimensions and Equipment Layout

Figure 8

Piping schematicair-cooled, tandem compressor models, DA0805, DA085


Optional Liebert EconoPhase Unit
Check Valve 7/8" Liquid to Indoor Unit See Note 2 Ball Valve

Differential Check Valve 1-3/8" Liquid from Condenser See Note 2 AIR-COOLED CONDENSER

Differential Check Valve

RECEIVER
Ball Valve Solenoid Valve

Includes Factory traps. No external trap required

HOT GAS DISCHARGE

1-1/8" Hot Gas Discharge from Indoor Unit See Note 2

DA
Service Valve

LIQUID EVAPORATOR COIL


SUCTION

For rises over 25ft. (7.6m), trap every 20ft. (6m) or evenly divided*

Check Valve

Trap at base of risers over 5ft. (1.5m)* *Full Ported Ball Valve See Note 4

Service Valve Check Valve Electronic Expansion Valve HOT GAS DISCHARGE See Note 2 LIQUID RETURN See Note 2

*Full Ported Ball Valve See Note 4

Differential Check Valve (Recommended)

REFRIGERANT PIPING FIELD PIPING SERVICE/SCHRADER (ACCESS) CONNECTION, WITH VALVE CORE SERVICE/SCHRADER (ACCESS) CONNECTION, NO VALVE CORE

* Components are not supplied by Liebert but are recommended for proper circuit operation and maintenance

1. Two refrigeration circuits provided. Single refrigeration circuit shown for clarity. 2. Circuit 1 must be maintained between indoor unit, condenser and Liebert EconoPhase unit. Circuit 2 must be maintained between indoor unit, condenser and Liebert EconoPhase unit. 3. Schematic representation shown. Do not use for specific connection locations. 4. Port in ball must be the same diameter as the piping I.D. 5. Length of piping between condenser and indoor unit shall be no greater than 300 ft (91.4 m) (Maximum equivalent length of 450 ft [137.2 m]). 6. Vertical height of condenser above indoor unit shall be no greater than 60ft (18.3m). 7. All indoor and outdoor field refrigerant piping must be insulated, 1/2" minimum thickness. All outdoor insulation must be UV- and ozone-resistant.

DPN002615 Rev. 0

Liebert DSE

14

Dimensions and Equipment Layout

Figure 9

Piping schematicair-cooled, tandem compressor models, DA125 and DA150

Differential Check Valve 1-3/8" Liquid Line from Condenser See Note 2.

Optional EconoPhase Unit


Check Valve Check Valve
Solenoid Ball Valve Valve

Differential Check Valve

Air-Cooled Condenser
Receiver
Ball Valve

7/8" Liquid to Indoor Unit See Note 2

Hot Gas Discharge Includes Factory Traps. No External Trap Required.

1-3/8" Hot Gas Discharge from Indoor Unit See Note 2.

DA125

Liquid Service Valve Suction

Evaporator Coil

For rises over 25ft. (7.6m), trap every 20ft. (6m) or evenly divided

Check Valve

* Trap at Base of Risers Over 5ft. (1.5m) *Full Ported Ball Valve See Note 4.

Service Valve Check Valve Electronic Expansion Valve


Refrigerant Piping

Hot Gas Discharge See Note 2. Liquid Return *Full Ported See Note 2. Ball Valve See Note 4. Differential Check Valve (Recommended)

* Components are not supplied by Liebert but are recommended for Service/Schrader (Access) Connection, With Valve Core proper circuit operation and 1. Two refrigeration circuits provided. Single refrigeration circuit shown for clarity. maintenance. 2. Circuit 1 must be maintained between indoor unit, condenser and Econophase unit.
Circuit 2 must be maintained between indoor unit, condenser and Econophase unit. 3. Schematic representation shown. Do not use for specific connection locations. 4. Port in ball must be the same diameter as the piping I.D. 5. Length of piping between condenser and indoor unit must be no greater than 300ft. (91.4 m) (Maximum equivalent length of 450ft. s[137.2m]). 6. Vertical height of condenser above indoor unit must be no greater than 60ft. (18.3m). 7. All indoor and outdoor field refrigerant piping must be insulated, 1/2" minimum thickness. All outdoor insulation must be UV and ozone resistant.

Field Piping Service/Schrader (Access) Connection, No Valve Core

DPN002340 Rev. 2

15

Liebert DSE

Dimensions and Equipment Layout

Figure 10 Liebert MC cabinet and anchor dimensions, MCL110, MCL165 and MCL220
55-5/8" (1413mm)

43-5/8" (1108mm) Eyebolts for Lifting Condenser Provided on 3&4 Fan Models

A B

35-7/8" (911mm)

Height to Top of Fan Guard

18" (457mm)

Emerson recommends a clearance of 36" (915mm) on each side for proper operation and component access

55-1/2" (1409mm) 13/16" (21mm)

2-1/2" (64mm)

3-5/8" (93mm) 1-7/8" (48mm)

Electric Box End

2-1/2" (64mm) PROVIDED ON 3&4 FAN MODELS 3-5/8" (93mm) 1/2"x1"(12.7mm x 25.4mm) Obround 1-7/8" (48mm) TYPICAL FOOTPRINT

48-3/4" (1239mm)

ANCHOR PLAN

DPN002416 Rev. 1

Table 10
Liebert Model # MCL110 MCL165 MCL220

Cabinet and anchor dimensions, MCL110, MCL165 and MCL220


# of Fans 2 3 4 Dimensions, In. (mm) A 124-1/8 (3152) 180-1/4 (4578) 236-5/16 (6003) B 73-7/16 (1866) 129-9/16 (3291) C 112-1/8 (2848) 168-1/4 (4274) 224-3/8 (5699) D 110-1/2 (2806) 110-1/2 (2806) 110 1/2 (2806) E 56-1/8 (1425) 112-1/4 (2851)

Source: DPN002416, Rev. 1

Liebert DSE

16

Dimensions and Equipment Layout

Figure 11 Liebert MC cabinet and anchor dimensions, three-fan, 120 models with 18" legs
Overall height to the top of fan guard 39-5/8"(1006mm) 46-1/4" (1175mm)

152-3/4" (3880mm)

31-5/8" (803mm) Emerson recommends a clearance of 36"(915mm) on each end and each side for proper operation and component access. Typical Condenser Footprint Dimensions 144-5/16" (3666mm) 46" (1168mm) 5/8" (16mm) 5/8" (16mm) 2-11/16" (69mm) 1-7/8" 48mm 2-11/16" (69mm) 3-5/8" (93mm)

NOTE: 3-5/8" Install (2) two condenser leg spacers, (93mm) part number 304679P1, in two places where shown, between each pair of legs that adjoin each other. Use four of part number: 301375G1 (fastener assembly), 301369P1 (washer fender) and 301392P1 (nut hex), to secure each pair of legs and spacers together. See leg installation drawing #306256 detail A. 1-1/2" (38mm) 94-3/4" (2407mm)

1/2" (12.7mm) x 1" (25.4mm) Obround

1-7/8" 48mm

46-11/16" (1186mm)

Install two each 1/8" (3.18mm) leg spacers in each of these locations (see note above)

44-3/4" (1137mm) 39-5/16" (999mm)

ANCHOR PLAN
Domestic Packaging Model # 120 Number of Fans 3 Net Weight lb (kg) 522 (237) Weight lb (kg) 632 (287) Dimensions (LxWxH) in. (mm) 162x28x61 (4115x711x1549) Volume ft3 (m3) 160 (4.5)

306252 Rev. 1

Source: 306252, Rev. 1

17

Liebert DSE

Dimensions and Equipment Layout

Figure 12 Liebert MC cabinet and anchor dimensions, three-fan, 120 models with 60" legs

46-1/4" (1175mm) 152-3/4" (3880mm)

NOTE: Overall height to the top of fan guard is 81-5/8"(2073mm) 73-5/8" (1870mm)

60" (1524mm)

Typical Condenser Footprint Dimensions


5/8" (16mm) 5/8" (16mm) 1-7/8" (48mm) 2-11/16" (69mm) 3-5/8" (93mm)

144-5/16" (3666mm) 46-11/16" (1186mm)

2-11/16" (69mm)

1/2"x1" (12.7mm x 25.4mm) Obround 3-5/8" (93mm)

Emerson recommends a clearance of 36" (915mm) on each end and each side for proper operation and component access. 1-1/2" (38mm) 94-3/4" (2407mm)

46" (1168mm)

1-7/8" (48mm)

Install two each 1/8"(3.18mm) leg spacers in each of these locations (see note below)

44-3/4" (1137mm) 39-5/16" (999mm)

NOTE: Install two condenser leg spacers, Part Number 304679P1, Use four of part number: 301375G1 (fastener assembly), in two places where shown, between each pair of legs that 301369P1 (washer fender) and 301392P1 (nut hex), to secure each pair of legs and spacers together. See adjoin each other. leg installation drawing #306256 Detail A.

ANCHOR PLAN

307564 Rev. 1
Domestic Packaging Model # 120 Number of Fans 3 Net Weight lb (kg) 9352 (424) Weight lb (kg) 1045 (474) Dimensions (LxWxH) in. (mm) 162 x 28 x 61 (4115 x 711 x 1549) Volume ft3 (m3) 160 (4.5)

Source: 307564, Rev. 1

Liebert DSE

18

Dimensions and Equipment Layout

Figure 13 Liebert MC cabinet and anchor dimensions, MCM120


Emerson recommends a clearance of 36" (915mm) on each end and each side for proper operation and component access. C B A Shown with typical 60" legs.

46-1/4" 1175mm 152-3/4" (3880mm)

13/16" 21mm 2-1/2" (64mm) 3-5/8" (93mm) 1-7/8" (48mm) 2-1/2" (64mm)

144-5/16" (3666mm) 46" (1169mm) Econophase receiver adds 8 1/2"(216mm) to the unit width and may be mounted on the right or left side.

Fastener assembly, fender washer and hex nuts. 3-5/8" 4 Each required, (93mm) 2 places 1-7/8" (48mm)

1/2"x1" (12.7mmx25.4mm) Obround

TYPICAL FOOTPRINT
Spacer 2 Each required, 2 places

DETAIL A
1-7/8" (48mm) 46-5/16" (1177mm)

94-7/16" (2398mm)

44-3/8" (1127mm) Install two (2) each 1/8"(3.18mm) leg spacers in each of these locations (see note below) 39-5/16" (999mm)

NOTE: Install (2) two condenser leg spacers, part number 304679P1, in two places where shown, between each pair of legs that adjoin each other. Use (4) four of part number: 301375G1 (fastener assembly), 301369P1 (washer fender) and 301392P1 (nut hex), to secure each pair of legs and spacers together.

ANCHOR PLAN

DPN002555 Rev. 1
Dimensions

Model # 120
*

Number of Fans 3

Net Weight lb (kg) 935 (424)

Domestic Packaging Weight lb (kg) 1045 (474) Dimensions, (LxWxH) in. (mm) 162x28x61 (4115x711x1549) Volume ft3 (m3) 160 (4.5)

Leg Height A 18 (457) 36 (914)


48 (1219) 60 (1524)

B
31-5/8 (803) 49-5/8 (1260) 61-5/8 (1565) 73-5/8 (1870)

C
39-5/8 (1006) 57-5/8 (1464) 69-5/8 (1768) 81-5/8 (2073)

Cross-bracing required for legs longer than 18" (457). Quantity varies per model and options selected.

19

Liebert DSE

Dimensions and Equipment Layout

Figure 14 Typical receiver mounting MCL110, MCL165, MCL220 units, left-side mounting outlet receiver

Receiver Mounting Holes Single Circuit

Typ. 4 Places 4, 3, 2 Trim piping as needed 14 8 13,12 2

DETAIL A

1 16 15

A
7

11.23" (285.3mm)

Notes
1. 2.

Use Items 15 and 16 as needed for mounting Item 1. Item 12 to be used on MCL165 units. Item 13 to be used on MCL220 units. size may vary.

36" (914.4mm) Clearance required for viewing sight glass

64.3" (1383.1mm)

Cross-Bracing Not Shown

3. Small receiver shown. Actual receiver

DPN002554 Pg. 1, Rev. 3


Receiver and Bracket Assembly Cap Screw HXDIN933M8-1.25x25A2 Fender Washer DIN9021 M8x24 A2 Lock Nut, Hex Nylon Insert, M8 90-degree Elbow FTGXC 7/8" Copper Copper Formed Tube 1-1/8" Coupling, Copper 1-1/8" Coupling, Copper 1-1/8" / Reducer, Copper CXC 1-3/8"x1-1/8" Reducer, Copper CXC 1-1/8"x7/8" Support Leg Fastener assembly: Cap Screw, Lock Washer, Fender Washer 1 4 8 4 1 1 1 1 1 1 4

1 2 3 4 7 8 12 13 14 15 16

Source: DPN002554, Page 1, Rev. 3

Liebert DSE

20

Dimensions and Equipment Layout

Figure 15 Typical receiver mounting MCL110, MCL165, MCL220 units, right-side mounting outlet receiver
Receiver Mounting Holes Single Circuit

Trim piping as needed 2 12, 13 8

DETAIL B
Typ. 4 Places 4, 3, 2

B
9 5,6 1 3

7 14

15 16 1

11.13" (282.6mm) 3 64.3" (1383.1mm) 36" (914.4mm) Clearance required for viewing sight glass

Notes
1. 2. 3.

Use Items 15 and 16 as needed for mounting Item 1. Item 12 to be used on MCL165 units. Item 13 to be used on MCL220 units. Small receiver shown. Actual receiver size may vary.

Cross-Bracing Not Shown

DPN002554 Pg. 2, Rev. 3


Item # 1 2 3 4 5 6 7 8 9 12 13 14 15 16 Description

Quantity 1 4 8 4 1 2 1 1 1 1 1 1 1 4

Receiver and Bracket Assembly Cap Screw HXDIN933M8-1.25x25A2 Fender Washer DIN9021 M8x24 A2 Lock Nut, Hex, Nylon Insert, M8 Clamp Omega 1-1/8" Screw Self-Drilling HWH YZ 10-16 x 5/8 90-degree Elbow FTGXFTG 7/8" Copper Copper Formed Tube 1-1/8" Copper Formed Tube 1-1/8" Coupling, Copper 1-1/8" Coupling, Copper 1-1/8" / Reducer, Copper CXC 1-3/8"x1-1/8" Reducer, Copper CXC 1-1/8"x7/8" Support Leg Fastener assembly: Cap Screw, Lock Washer, Fender Washer

Source: DPN002554, Page 2, Rev. 2

21

Liebert DSE

Dimensions and Equipment Layout

Figure 16 Typical receiver mounting MCM120 units, left-side mounting outlet receiver

4 3 2 Typically 4 Places

15, 16

1 7 8 Trim piping as needed

11.11" (282.1mm) 36.00" (914.4mm) Clearance required for viewing sight glass 54.45" (1383.1mm)

Cross-Bracing Not Shown

DPN002453 Page 1, Rev. 2


Item # 1 2 3 4 7 8 15 16 Description Receiver and Bracket Assembly Condenser Screw Cap HXDIN933M8-1.25x25A2 Washer Fender DIN9021 M8x24 A2 Lock Nut Hex Nylon Insert M8 90-Degree Elbow FTGXC 7/8" Cu Copper Form Tube 7/8" Condenser, Rec. 1 Support Leg Condenser GCP Fastener Assembly, screw, fender washer, lock washer, SCRMACHM8-1.25x25SS Qty 1 4 8 4 1 1 1 4

Source: DPN002453, Page 12, Rev. 2

Liebert DSE

22

Dimensions and Equipment Layout

Figure 17 Typical receiver mounting MCM120 units, right side mounting outlet receiver

Trim piping as needed 8


2, 3,4 Typically 4 Places

7 5, 6 9 1

15, 16

11.11" (282.1mm) 36.00" (914.4mm) Clearance required for viewing sight glass

54.49" (1384.1mm)

Cross-Bracing Not Shown

DPN002453 Page 2, Rev.2


Item # 1 2 3 4 5 6 7 8 9 15 16 Description Receiver and Bracket Assembly Condenser Screw Cap HXDIN933M8-1.25x25A2 Washer Fender DIN9021 M8X24 A2 Lock Nut Hex Nylon Insert M8 Clamp Omega 7/8" Screw, Self-Drilling, SD HWH YZ 10-16 x 5/8 90-Degree Elbow, FTGXC 7/8" Cu Copper Form Tube 7/8 Condenser Rec L Copper Form Tube 7/8 Condenser Rec L Support Leg Condenser GCP Fastener Assembly, screw, lock washer, 1.25x25SS Qty 1 4 8 4 1 2 1 1 1 1 4

Source: DPN002453, Page 2, Rev. 2

23

Liebert DSE

Dimensions and Equipment Layout

Figure 18 Required receiver mounting MCM120 and MCM160 units, left-side mounting outlet receiver
Receiver Mounting Holes Single Circuit

DETAIL A

Typ. 4 Places 4, 3, 2

16, 15 1 1

A
7 8 Trim piping as needed

11.23" (285.3mm)

36" (914.4mm)

54.45" (1383.1mm)

NOTE 1 Small receiver shown. Actual receiver size may vary. Cross-Bracing Not Shown

DPN002383 Pg. 1, Rev. 4


Item # 1 2 3 4 7 8 15 16 Description Receiver and Bracket Assembly Cap Screw HXDIN933M8-1.25x25A2 Fender Washer DIN9021 M8x24 A2 Lock Nut, Hex Nylon Insert, M8 90-degree Elbow FTGXC 7/8" Copper Copper Formed Tube 7/8" Support Leg Fastener assembly: Cap Screw, Lock Washer, Fender Washer Quantity 1 4 8 4 1 1 1 4

Source: DPN002383, Page 1, Rev. 4

Liebert DSE

24

Dimensions and Equipment Layout

Figure 19 Required receiver mounting MCM120, MCM160 units, right-side mounting outlet receiver
Receiver Mounting Holes Single Circuit

DETAIL B
Trim Piping As Needed 8 2, 3, 4 Typ. (4) Places

B
5, 6 9 1 1

15, 16

11.23" (285.3mm) 1 54.49" (1384.1mm) 1 36" (914.4mm) Small receiver shown. Actual receiver size may vary

Cross-bracing Not Shown

DPN002383 Pg. 2, Rev. 4


Item # 1 2 3 4 5 6 7 8 9 15 16 Description Receiver and Bracket Assembly Cap Screw HXDIN933M8-1.25x25A22 Fender Washer DIN9021 M8x24 A2 Lock Nut, Hex Nylon Insert, M8 Clamp Omega 7/8" Screw, Self-Drilling, HWH YZ 10-16 x 5/8 90-degree Elbow FTGXC 7/8" Copper Copper Formed Tube 7/8" Copper Formed Tube 7/8" Support Leg Fastener assembly: Cap Screw, Lock Washer, Fender Washer Quantity 1 4 8 4 1 2 1 1 1 1 4

Source: DPN002383, Page 2, Rev. 4

25

Liebert DSE

Dimensions and Equipment Layout

Figure 20 Leg installation Liebert MC, three-fan cabinet, 120 model


Liebert P/N 301375G1 Liebert P/N 301369P1 Liebert P/N 301392P1 4 each required, 2 places

Liebert P/N 304679P1 2 each required, 2 places

DETAIL A

Liebert P/N 301375G1 4 each required, 8 places Liebert P/N 305923P1 8 places

Liebert P/N 305924P2 2 each required, 2 places as shown Liebert P/N S12-0750 Liebert P/N S05-0150 Liebert P/N S05-0400 5 each required, 6 places as shown

Liebert P/N 305924P1 2 each required, 2 places as shown

Liebert P/N 305924P3 2 each required, 2 places as shown

Notes: 1. When assembling legs and leg angles to condenser unit, leave hardware finger tight to allow for adjustment. Tighten all hardware when assembly is complete. 2. Install two condenser leg spacers, P/N 304679P1 in two places where shown, between each pair of legs that adjoin each other. Use four each of P/N 301375G1 (Fastener Assembly), 301369P1 (Washer Fender) and 301392P1 (Hex Nut), to secure each pair of legs and spacers together

306256 Rev. 1

Liebert DSE

26

Dimensions and Equipment Layout

Figure 21 Plenum dimensionsdownflow, DA080 and DA085 models


80-1/2" (2045mm) Return air inlet opening

Height, in. (mm)


7/8" (22mm) Typical 32-1/8" (816mm) Opening

H 20 (508) 24 (610) 36 (914)

34" (864mm)

Plenum Hinged door for filter access 1" (25mm)

82-1/4" (2089mm)

12" (305mm)

76" (1930mm)

Liebert DSE Unit

DPN001107 Pg. 2, Rev. 2

27

Liebert DSE

Dimensions and Equipment Layout

Figure 22 Liebert EconoPhase pump box dimensions, typical


Electric Box End of Unit 42" (1067mm) Minimum Clearance

Pump Access Typical Both Sides

36" (914mm) Minimum Clearance 4-15/16" (125mm)

21-7/16" (544mm)

36" (914mm) Minimum Clearance 1-3/8" Liquid Line from Condenser 42 1/16" (1069mm)

ISOMETRIC VIEW

System Circuit 2 Liquid In 36-15/16" (939mm)

System Circuit 1 Liquid In 40-1/8" (1019mm) 7/16" (11mm) typical 8 places for unit mounting

9-3/8" (238mm)

System Circuit 2 Liquid Out

System Circuit 1 Liquid Out

DETAIL B
7/16" (11mm) Typical 8 Places for unit mounting 40-11/16" (1033mm)

4-13/16" (123mm)

7/8" Liquid to Indoor Unit 21-5/16" (542mm)

LEFT SIDE VIEW

40" (1016mm) 39-3/8" (1000mm)

REAR VIEW (PIPING END)


36-3/16" (919mm)

Approximate Weight 208/230, 380 & 560V: 340lb.(154kg) 575V: 390lb. (177kg)

5/8" (16mm)

2-3/16" (56mm) 12-3/16" (310mm) 22-3/16" (564mm) 32-3/16" (818mm) 35-7/8" (911mm)

SECTION A-A
35-7/8" (911mm)

FRONT VIEW

DPN002326 Rev. 2

Liebert DSE

28

Dimensions and Equipment Layout

Figure 23 Condenser and Liebert EconoPhase unit locations, typical unit arrangement diagram layout

Top View

Circuit 1 Circuit 2
Liquid Line to Liebert EconoPhase from Bottom of Receiver

Air-Cooled Condenser
Entering Hot Gas Line

Top View

CIRCUIT 1
*Liquid line from Condenser 1-3/8". Do Not Trap Line Slope toward Liebert EconoPhase unit.

42" (1067mm) Minimum Clearance

Air-Cooled Condenser
Entering Hot Gas Line

CIRCUIT 2

Liebert EconoPhase Unit

Liquid Line from Condenser 1-3/8" Do Not Trap Line Slope down 2 per 10 toward Liebert EconoPhase unit * Liquid from Condenser 1-3/8" Do Not Trap Line Slope down 2 per 10 toward Liebert EconoPhase unit

CIRCUIT 1 CIRCUIT 2
60" (1524mm)

60" leg height Typical; see Note 1.

Factory-supplied, Field-installed Field Piping


1. For proper pump function, a minimum elevation difference of 60 (1524 mm) must be maintained between the bottom of condenser box to the bottom of Liebert EconoPhase unit. 2. All indoor and outdoor field refrigerant piping must be insulated, 1/2" minimum. All outdoor insulation must be UV- and ozone-resistant.

*Components are not supplied by Liebert but are recommended for proper circuit operation and maintenance. **Components supplied by Liebert and must be field-installed.

DPN002324 Rev. 2

29

Liebert DSE

Dimensions and Equipment Layout

Figure 24 Liebert DSE disassembly dimensions, downflow air-cooled DA125 and DA150 models

Filter Assembly 18" (457mm)

Electric Box Assembly

40-11/16" (1034mm) 94" (2388mm) Assembled Height

Compressor Assembly

Blower & Coil Assembly

76" (1930mm)

74-3/16" (1884mm)

35" (889mm)

45" (1143mm)

22" (558mm)

120" (3048mm) 142" (3607mm) Assembled Length

DPN002420 Rev. 0

Drawing views are simplified with panels removed to show overall dimensions. See disassembly and handling instructions.

Table 11

Approximate dry weight, includes panels


EC Fans Air-Cooled Weight, lb (kg) 630 (286) 417 (189) 2218 (1006) 200 (91)

Component Compressor Assembly Electric Box Assembly Blower and Coil Assembly Filter Assembly
Source: DPN002420, Rev . 0

Liebert DSE

30

Electrical Connections

4.0

ELECTRICAL CONNECTIONS

Figure 25 Electrical field connections Premium Efficiency Control, three-fan models


Condenser #1
12 13 70 71 23 0
71 230

Connect this wire only to Condenser #1

Fan #3

Fan #2

70

C1 C2

Condenser #2
12 13 70 71 230

Liebert Indoor Unit

Connect this wire only to Condenser #2

Fan #1

DETAIL A
ON

123 45678 CAN

DETAIL B
(DIPswitch 1 Setting Position) Factory-Installed Contactors Factory-Installed Fuse Blocks Electrical Service Connection Terminals with factory-supplied disconnect Factory-Installed Disconnect Earth Ground Connection Connection terminal for fieldsupplied earth grounding wire Earth Ground Bar Connection terminals with factory ground from each high voltage component for field-supplied earth grounding wire. Factory-wired to GND to the fans. . Electrical Service Entrance Factory-Installed Transformer 7/8 in. (22.2mm) diameter holes in 1-1/8 in. (28.6mm) knockouts provided in bottom of electric box

See Note 4

B A

Remote shutdown Remote Shutdown (See Note 3) Alarm Connections

Field-wired SPD Field-installed CANbus Electrical Service (Optional) communication with indoor Not by Emerson unit. (See Note 2) NOTE: 1. Refer to specification sheet for full load amp and wire size amp ratings. 2. For the Premium models, the CANbus wiring must be shielded cable that has at least one triad of 24-20AWG conductors plus a drain wire, similar to Belden Part #1348A or Alpha Wire Part # 6351. The cable must either be water resistant and sunlight resistant, or be run in conduit once it is outside the building. 3. 24V field-supplied control voltage wiring from Liebert indoor unit must be a minimum of 18 gauge (1.6mm) or not to exceed 1 volt drop in control line. Wire per local code. 4. If two condensers are used for one dual-circuit Liebert indoor unit, the condenser used for Circuit 2 must have CAN DIPswitch 1 set to the Off position. See Detail B.

306266 Rev. 3

31

Liebert DSE

Electrical Connections

Figure 26 Liebert EconoPhase pump box field electrical connections

Field Connection From Condenser CANbus. Wire Per Local Codes

Field High Voltage Connection. Wire Per Local Codes.

Field Ground Connection. Wire Per Local Codes

Optional Low Voltage Field Wiring Connection 7/8" Knockout

FRONT VIEW

Optional High Voltage Field Wiring Connection 2" Knockout Optional High Voltage Optional Low Field Wiring Connection Voltage Field 1-3/4" Knockout Wiring Connections 1-3/4" Knockout

Optional High Voltage Field Wiring Connections 1-3/4" Knockouts

DPN002327 Rev. 2
Input Voltage 208/230 380 * 460 575 Full Load Amps, FLA 13.8 8.4 7.0 5.6 Wire Size Amps, WSA 15.5 9.4 7.9 6.3 Overload Protection Device, OPD 20.0 15.0 15.0 15.0

* 380V unit is not CSA-listed. Source: DPN002327, Rev. 2

Liebert DSE

32

Electrical Connections

Figure 27 CANbus cable connections between indoor unit, Liebert MC and optional Liebert EconoPhase unit
Factory wiring between control boards and terminal strip
EconoPhase EconoPhase Control Board Control Board Single Circuit Dual Circuit (Factory Set) (Factory Set)
CIRCUIT ONE CIRCUIT ONE

49-1 CANbus 49-3 Connections

4
CIRCUIT TWO

No Shield Connection DETAIL 4 CAN Cable Connection

Liebert EconoPhase
Last Device on CANbus (If Present)
Two Two Condensers Condensers With EconoPhase
CONDENSER 2 CONDENSER 2

C
CONDENSER 2

J6

J6

CONDENSER 1

CONDENSER 1

J6

J6

DETAIL 3 CAN Cable Connection Low-voltage field entrance located on bottom left of Condenser 2 enclosure

CONDENSER 2
Factory wiring between Liebert MC control board and terminal strip

CONDENSER 1

Remove jumper

B G

H CONDENSER 1
Remove jumper Factory wiring between Liebert MC control board and terminal strip Remove jumper

Low-voltage field entrance located on bottom left of Condenser 1 enclosure Heat Rejection Interlock

F A 2 1

Component Notes: DETAIL 2 1. Component appearance, orientation and position may vary between product lines. Terminal names and callouts remain constant. Heat Rejection Interlock Cable Notes (A, B, C): 1. Field-supplied cable. shielded 24-18AWG stranded tinned copper twisted pair (minimum 8 twists per foot) low capacitance (17pf/ft or less) must be rated to meet local codes and conditions. Shield examples Belden 89207 (plenum rated), or Alpha Connection wire 6454 Category 5, 5e or higher. 2. Do not run in same conduit, raceway or chase as high voltage wiring. 3. For CANbus network lengths greater than 350ft (107m), SH contact factory. Wire Notes (F, G,H): 49-1 1. Field-supplied wire 49-3 18AWG or greater rated 600V 2. For single circuit systems, run two wires from indoor unit to condenser(s). 3. For dual circuit systems, run three wires from the indoor DETAIL 1 CAN Cable Connection unit to first condenser and one wire from first condenser to second condenser (if present). Factory Wiring Between Liebert iCOM and

Terminal Strip

INDOOR UNIT

DPN002361 Rev. 2

33

Liebert DSE

Electrical Connections

Figure 28 Electrical field connections, DA080, DA085, single molded case switch disconnect with main fuses
Refer to Section 4.1 through 4.2 for keys to numbered items.
2 4 Liebert IntelliSlot Housing

OVERCURRENT PROTECTION DEVICES


15

A CD

Alternate Location

6 60Hz

P64

CONTACTORS

P67

13

CONTACTORS, RELAYS, & OVERLOAD PROTECTORS

6 50Hz

Downflow 3

Downflow Low-Voltage Section


11

Note: Typical orientation of components shown. Component location varies by option and unit size. 17 18 9 22 16 19

82 83 88 89

75 76 94 95 96 97 91 92 93 80 81 11 12

A
24 23 21 7 58 59 84 85

B
8 10 20 12 37C 37B 38C 38B 37 38 24 50 51 55 56 70 71 23072 73

D
DPN000807 Pg. 2, Rev. 7

Item 12 Installation Conditions 1. Follow all local installation codes. 2. Do not run CAN cables in same conduit, raceway or chase as high-voltage wires (120-600V). 3. Separate high-voltage wires from CAN wires by 12 in. (305mm). 4. Contact factory for runs greater than 350ft. (107m).

Liebert DSE

34

Electrical Connections

Figure 29 Electrical field connections, DA080 and DA085 models, dual-fused disconnect switches
Refer to Section 4.1 through 4.2 for keys to numbered items.
2 14 4 Liebert Intellislot Housing

A
15 6 60Hz 15

OVERCURRENT PROTECTION DEVICES CD


Alternate Alternate Location Location P64

CONTACTORS
PR IM AR Y SEC ON DA RY

P67

13

CONTACTORS, RELAYS, & OVERLOAD PROTECTORS

50 Hz

Downflow 3

Downflow Low-Voltage Section


11 22 16 19

Note: Typical orientation of components shown. Component location varies by option and unit size 17 18 9

82 83 88 89

75 76 94 95 96 97 91 92 93 80 81 11 12

A
24 23 21 7

B
8 10 20 12

58 59 84 85

37C 38C 37B 38B 37 38 24 50 51 55 56 70 71 23072 73

Item 12 Installation Conditions 1. Follow all local installation codes. 2. Do not run CAN cables in same conduit, raceway or chase as high voltage wires (120-600V). 3. Separate high volt wires from CAN wires by 12 in. (305mm). 4. Contact factory for runs greater than 350ft. (107m).

DPN000807 Pg. 3, Rev. 7

35

Liebert DSE

Electrical Connections

4.1

Standard Electrical Field Connections, DA080, DA085 Downflow Models


Source: DPN000807, Revision 7; refer to Figures 28 and 29 1. Primary high voltage entrance2.5" (64mm); 1.75" (44mm); 1.375" (35mm) diameter concentric knockouts in bottom of box. 2. Secondary high voltage entrance2.5" (64mm); 1.75" (44mm); 1.375" (35mm) diameter concentric knockouts in top of box. 3. Primary low voltage entranceThree knockouts, each 1.125" (28mm) diameter, in bottom of unit. 4. Secondary low voltage entranceThree knockouts, each 1.125" (28mm) diameter, in top of box. 5. Three-phase electrical serviceTerminals are on main fuse block (disregard if unit has optional disconnect switch). Three-phase service not by Emerson. 6. Earth groundTerminal for field-supplied earth grounding wire. Earth grounding required for Liebert units. 7. Remote unit shutdownReplace existing jumper between Terminals 37 and 38 with field-supplied, normally closed switch having a minimum 75VA, 24VAC rating. Use field-supplied Class 1 wiring. 8. Customer alarm inputsTerminals for field-supplied, normally open contacts, having a minimum 75VA, 24VAC rating, between Terminals 24 and 50, 51, 55, 56. Use field-supplied Class 1 wiring. Terminal availability varies by unit options. 9. Common alarmOn any alarm, normally open dry contact is closed across Terminals 75 and 76 for remote indication. 1 AMP, 24VAC maximum load. Use field-supplied Class 1 wiring. 10. Heat rejection interlockOn any call for compressor operation, normally open dry contact is closed across Terminals 70 and 71 (Circuit 1), 230 (Circuit 2) to heat rejection equipment. 1 AMP, 24VAC maximum load. Use field-supplied Class 1 wiring. Liebert DA units must be connected to Liebert MC Series Condenser with Premium Control. It is required that the jumper between Terminal 71 and Terminal 230 be removed. Three wires must connect Terminals 70, 71 and 230 of the indoor unit to Terminals 70, 71 and 230 of the Liebert MC series condenser.

4.2

CANbus Electrical Connections, DA080, DA085 Downflow Models


Source: DPN000807, Revision 7; refer to Figures 28 and 29 11. CANBus Connector Terminal block with terminals 49-1 (CAN-H) and 49-3 (CAN-L) + SH (shield connection). The terminals are used to connect the CANBus communication cable (provided by others) from the indoor unit to the Liebert Microchannel Condenser Premium Model and Optional PRE Unit. 12. 12) CANBus Cable CANBus cable provided by others to connect to the outdoor condenser. Cable must have the following specifications: a. Conductors22-18AWG stranded tinned copper b. Twisted pair c. Braided shield or foil shield with drain wire d. Low Capacitance15pf/ft or less e. UL approved temperature rated to 75C f. UL approved voltage rated to 300V g. UV-resistant and moisture-resistant if not provided in conduit. h. Plenum ratedNEC type CMP (if required by national or local codes.)

Liebert DSE

36

Electrical Connections

4.3

Optional Electrical Field Connections, DA080, DA085, Downflow Models


Source: DPN000807, Revision 6; refer to Figures 28 and 29 13. Unit factory installed disconnect switch, fuse block and main fusesTwo types of disconnect switches are available: Non-Locking and Locking. The non-locking type consists of a non-automatic molded case switch operational from the outside of the unit. Access to the high-voltage electric panel compartment can be obtained with the switch in either the On or Off position. The locking type is identical except access to the high-voltage electric panel compartment can be obtained only with the switch in the Off position. The molded case switch disconnect models contain separate main fuses. Units with fused disconnect have main fuses within the disconnect. 14. Secondary disconnect switch and earth ground 15. Three -phase electrical serviceTerminals are on top of the disconnect switch. Three-phase service not by Emerson. 16. Smoke sensor alarmFactory-wired dry contacts from smoke sensor are 91-common, 92-NO, and 93-NC. Supervised contacts, 80 and 81, open on sensor trouble indication. This smoke sensor is not intended to function as, or replace, any room smoke detection system that may be required by national or local codes. 1 AMP, 24VAC maximum load. Use field-supplied Class 1 wiring. 17. Reheat and humidifier lockoutRemote 24VAC required at Terminals 82 and 83 for lockout of reheat and humidifier. 18. Condensate alarm (with condensate pump option)On pump high water indication, normally open dry contact is closed across Terminals 88 and 89 for remote indication. 1 AMP, 24VAC maximum load. Use field-supplied Class 1 wiring. 19. Remote humidifierOn any call for humidification, normally open dry contact is closed across Terminals 11 and 12 to signal field-supplied remote humidifier. 1 AMP, 24VAC maximum load. Use field-supplied Class 1 wiring. 20. Auxiliary cool contactOn any call for Liebert Econ-O-Coil operation, normally open dry contact is closed across Terminals 72 and 73 on dual-cool units only. 1 AMP, 24VAC maximum load. Use field-supplied Class 1 wiring.

4.4

Optional Low Voltage Terminal Package Field Connections, DA080, DA085, Downflow Models
Source: DPN000807, Revision 6; refer to Figures 28 and 29 21. Remote unit shutdownTwo additional contact pairs available for unit shutdown (labeled as 37B and 38B, 37C and 38C). Replace jumpers with field-supplied normally closed switch having a minimum 75VA, 24VAC rating. Use field-supplied Class 1 wiring. 22. Common alarmOn any alarm, two additional normally open dry contacts are closed across Terminals 94 and 95 and 96 and 97 for remote indication. 1 AMP, 24VAC maximum load. Use field-supplied Class 1 wiring. 23. Main fan auxiliary switchOn closure of main fan contactor, normally open dry contact is closed across Terminals 84 and 85 for remote indication. 1 AMP, 24VAC maximum load. Use field-supplied Class 1 wiring. 24. Liebert Liqui-tect shutdown and dry contactOn Liebert Liqui-tect activation, normally open dry contact is closed across Terminals 58 and 59 for remote indication (Liebert Liqui-tect sensor ordered separately). 1 AMP, 24VAC maximum load. Use field-supplied Class 1 wiring. NOTE Refer to specification sheet for total unit full load amps, wire size amps and maximum overcurrent protective device size.

37

Liebert DSE

Electrical Connections

Figure 30 Electrical field connections for downflow models

High-Voltage Field Wiring Pathways

Low-Voltage Field Wiring Pathways

DPN002317 Pg. 1, Rev. 2

Liebert DSE

38

Electrical Connections

Figure 31 Electrical field connections for DA125 and DA150 downflow models
Refer to Section 4.5 through 4.7 for keys to numbered items.

Liebert IntelliSlot Housing

OVERCURRENT PROTECTION DEVICES

P67 P64

A B C D

4 11

OVERLOADS
1
24 50 51 55 56 75 76 94 95 96 97

Contactors and Relays

Low-Voltage Section

16 5

7 17

37C 38C 37B 38B 37 38

Notes: Typical orientation of components shown. Component location varies by option and unit size. Refer to DPN002318 for descriptions of numbered callouts

13 14

82 83 88 89 80 81 91 92 93

10

12

19 8 18 15

58 59 70 71 230 84 85 11 12

Item 10 Installation Conditions 1. Follow all local installation codes. 2. Do not run CAN cables in same conduit, raceway, or chase as high voltage wires (120-600V). 3.Separate high volt wires from CAN wires by 12 in. (305mm). 4. Contact factory for runs greater than 350ft (107m).

DPN002317 Pg. 2, Rev. 2

39

Liebert DSE

Electrical Connections

4.5

Liebert DSE Electrical Field Connection Descriptions, DA125 and DA150 Downflow Models Standard Electrical Connections
Source: DPN002318, Revision 1 1. Primary high voltage entrance2.50" (64mm); 1.75" (44mm); 1.375" (35mm) diameter concentric knockouts located in bottom of box. 2. Primary low voltage entranceQuantity of three 1.375" (35mm) diameter knockouts in bottom of unit. 3. Three-phase electrical serviceTerminals are on top of disconnect switch. Three-phase service not by Emerson. 4. Earth groundTerminal for field-supplied earth grounding wire. Earth grounding required for Liebert units. 5. Remote unit shutdownReplace existing jumper between Terminals 37 and 38 with field-supplied normally closed switch having a minimum 75VA, 24VAC rating. Use field-supplied Class 1 wiring. 6. Customer alarm inputsTerminals for field-supplied, normally open contacts, having a minimum 75VA, 24VAC rating, between Terminals 24 and 50, 51, 55, 56. Use field-supplied Class 1 wiring. Terminal availability varies by unit options. 7. Common alarmOn any alarm, normally open dry contact is closed across Terminals 75 and 76 for remote indication. 1 AMP, 24VAC maximum load. Use field-supplied Class 1 wiring. 8. Heat rejection interlockOn any call for compressor operation, normally open dry contact is closed across Terminals 70 and 71 (Circuit 1), 230 (Circuit 2) to heat rejection equipment. 1 AMP, 24VAC maximum load. Use field-supplied Class 1 wiring. 9. CANbus Surge ProtectorSurge protector with Terminals 49-1 (CAN-H) and 49-3 (CAN-L). The terminals are used to connect the CANbus communication cable (provided by others) from the indoor unit to the Liebert Microchannel Condenser-Premium Model. 10. CANbus Cable Shield ConnectionConnection terminal of the braided shield or drain wire of the CANbus cable (provided by others) to the outdoor condenser. 11. CANbus CableCANbus cable provided by others to connect to the outdoor condenser. Cable must meet the following specifications: a. Conductors22-18AWG stranded, tinned copper b. Twisted pair c. Braided shield or foil shield with drain wire d. Low capacitance15pf/ft or less e. UL approved temperature rated to 75C f. UL approved voltage rated to 300V g. UV- and moisture-resistant if not run in conduit. h. Plenum ratedNEC type CMP, if required by national or local codes 12. Factory-installed disconnect switch

4.6

Optional Electrical Connections


Source: DPN002318, Revision 1 13. Smoke sensor alarmFactory-wired dry contacts from smoke sensor are 91-common, 92-NO, and 93-NC. Supervised contacts, 80 and 81, open on sensor trouble indication. This smoke sensor is not intended to function as or replace any room smoke detection system that may be required by local or national codes. 1A, 24VAC maximum load. Use field-supplied Class 1 wiring. 14. Reheat and humidifier lockoutRemote 24VAC required at Terminals 82 and 83 for lockout of reheat and humidifier. 15. Condensate alarm (with condensate pump option)On pump high water indication, normally open dry contact is closed across Terminals 88 and 89 for remote indication. 1A, 24VAC maximum load. Use field-supplied Class 1 wiring. 16. Remote humidifierOn any call for humidification, normally open dry contact is closed across Terminals 11 and 12 to signal field-supplied remote humidifier. 1A, 24VAC maximum load. Use field-supplied Class 1 wiring.

Liebert DSE

40

Electrical Connections

4.7

Optional Low Voltage Terminal Package Connections


Source: DPN002318, Revision 1 17. Remote unit shutdownTwo additional contact pairs available for unit shutdown (labeled as 37B and 38B, 37C and 38C). Replace jumpers with field-supplied normally closed switch having a minimum 75VA, 24VAC rating. Use field-supplied Class 1 wiring. 18. Common alarmOn any alarm, two additional normally open dry contacts are closed across Terminals 94 and 95 and 96 and 97 for remote indication. 1A, 24VAC maximum load. Use Class 1 field-supplied wiring. 19. Main fan auxiliary switchOn closure of main fan contactor, normally open dry contact is closed across Terminals 84 and 85 for remote indication. 1A, 24VAC maximum load. Use field-supplied Class 1 wiring. 20. Liebert Liqui-tect shutdown and dry contactOn Liebert Liqui-tect activation, normally open dry contact is closed across Terminals 58 and 59 for remote indication (Liebert Liqui-tect sensor ordered separately). 1A, 24VAC maximum load. Use field-supplied Class 1 wiring NOTE Refer to specification sheet for total unit full load amps, wire size amps and maximum overcurrent protective device size.

41

Liebert DSE

GUIDE SPECIFICATIONS

GUIDE SPECIFICATIONS 1.0


1.1

GENERAL
SUMMARY
These specifications describe requirements for a Precision Cooling system. The system shall be designed to control temperature and humidity conditions in rooms containing electronic equipment, with good insulation and vapor barrier. The manufacturer shall design and furnish all equipment to be fully compatible with heat dissipation requirements of the room.

1.2

DESIGN REQUIREMENTS
The Precision Cooling system shall be a Liebert self-contained, factory-assembled unit with downflow air delivery. The system shall have a net total cooling capacity of ____ kW (BTUH) with a net sensible cooling capacity of ____ kW (BTUH) based on an entering air temperature of ____ F (____C) dry bulb and ____ F (____C) wet bulb. The unit is to be supplied with ____ volt ____ ph ____ Hz electrical service. Net capacities shall include losses due to fan motor heat. The system cooling capacity shall be factory certified per ASHRAE127-2007, and the system sensible coefficient of performance (SCOP) shall exceed ASHRAE 90.1-2010.

1.3

SUBMITTALS
Submittals shall be provided after the agreement of the proposal and shall include: Single-Line Diagrams; Dimensional, Electrical and Capacity Data; Piping and Electrical Connection Drawings.

2.0
2.1

PRODUCT
FRAME
The frame shall be welded, formed sheet metal. It shall be protected against corrosion using the autophoretic coating process. The frame shall be capable of being separated into three parts in the field to accommodate rigging through small spaces.

2.1.1 2.1.1 2.1.2 2.1.3

Downflow Air Supply


The supply air shall exit from the bottom of the unit.

Downflow Front Supply


The supply air shall exit from the front of the unit.

Downflow Air Return


The return air shall enter the unit from the top.

Exterior Panels
The exterior panels shall be insulated with a minimum 1 in. (25mm), 1.5 lb. (0.68 kg) density fiber insulation. The main front panel shall have captive quarter-turn fasteners. The main unit color shall be _____________________.

2.2
2.2.1 2.2.1 2.2.1

FILTERSDA080, DA085
2.2.1Filters, 4" MERV 8
Filters shall be deep pleated 4" filters with an ASHRAE 52.2 MERV8.

Filters, 4" MERV11


Filters shall be deep pleated 4" filters with an ASHRAE 52.2 MERV11.

Filters, 2" MERV8 and 2" MERV11


Filters shall be deep pleated 2" filters with an ASHRAE 52.2 MERV8, plus 2" MERV11 filters.

Liebert DSE

42

GUIDE SPECIFICATIONS

2.2.2

Extra Filter Set


____ extra set(s) of filters shall be provided per system.

2.2

FILTERSDA125, DA150
The filter plenum shall be exterior to the main cooling unit, and shall be field assembled and installed. The filters shall be removable from the front or top of the filter plenum. The filter plenum shall be painted to match the panel colors of the indoor cooling unit.

2.2.1 2.2.1 2.2.1 2.2.1 2.2.1 2.2.2

Filters, 4" MERV 8


Filters shall be deep pleated 4" filters with an ASHRAE 52.2 MERV8.

Filters, 4" MERV11


Filters shall be deep pleated 4" filters with an ASHRAE 52.2 MERV11.

Filters, 4" MERV13


Filters shall be deep pleated 4" filters with an ASHRAE 52.2 MERV13.

Filters, 2" MERV8 and 2" MERV11


Filters shall be deep pleated 2" filters with an ASHRAE 52.2 MERV8, plus 2" MERV11 filters.

Filters, 2" MERV8 and 2" MERV13


Filters shall be deep pleated 2" filters with an ASHRAE 52.2 MERV8, plus 2" MERV13 filters.

Extra Filter Set


____ extra set(s) of filters shall be provided per system.

2.3
2.3.1

FAN SECTION
Electronically Commutated (EC) Fan
The fans shall be plug/plenum type, motorized impellers, single inlet and dynamically balanced. The drive package shall be direct drive, electronically commutated and variable speed. The fans shall be located to draw air over the A-frame coil to ensure even air distribution and maximum coil performance. EC fans shall be capable of being lowered into a raised floor (during field installation) with minimum height of 24" (609.6mm). EC fans shall also be capable of operating within the cooling cabinet, instead of under the floor.

2.4

HUMIDIFIER
A humidifier shall be factory-installed inside the unit. Bypass air slots shall be included to enable moisture to be absorbed into the air stream. The humidifier capacity shall be 22.1 lb./hr (10 kg/hr). The humidifier shall be removable from the front of the cabinet.

2.4.1

Infrared Humidifier
The humidifier shall be of the infrared type, consisting of high-intensity quartz lamps mounted above and out of the water supply. The humidifier pan shall be stainless steel and arranged to be removable without disconnecting high-voltage electrical connections. The complete humidifier section shall be pre-piped, ready for field connection to the water supply. The humidifier shall be equipped with an automatic water supply system and shall have an adjustable water-overfeed to prevent mineral precipitation. A high-water detector shall shut down the humidifier to prevent overflowing. A factory provided air gap shall prevent backflow of the humidifier supply water.

2.5

REHEAT
The Precision Cooling unit shall include a factory-installed reheat to control temperature during dehumidification.

43

Liebert DSE

GUIDE SPECIFICATIONS

2.5.1

Three-Stage Electric Reheat


The electric reheat coils shall be low watt density, 304/304 stainless steel fin tubular construction, protected by thermal safety switches, shall be ____ kW (____ BTUH) controlled in three stages. The reheat elements shall be removable from the front of the cabinet. A ground-current detection device shall disable reheat in the case where a ground-fault is detected in the reheat element.

2.6

DUAL REFRIGERATION SYSTEM


Each unit shall include two (2) independent refrigeration circuits and shall include liquid line filter driers, refrigerant sight glass with moisture indicator and electronic expansion valves. Compressors shall be located outside the airstream and shall be removable and serviceable from the front of the unit. Each compressor circuit shall be connected to the full-face area of the evaporator coil.

2.6.1

Digital Scroll Compressors-DA080, DA085


The compressors shall be scroll-type with a variable capacity operation capability. Compressor solenoid valve shall unload the compressor and allow for variable capacity operation. The compressor shall have vibration isolators, thermal overloads, automatic reset high-pressure switch with lockout after three failures, rotalock service valves, suction line strainer and a maximum operating speed of 3500 RPM. The compressor motor shall be suction gas cooled.

2.6.1

Tandem Digital Scroll CompressorsDA125, DA150


The compressors shall be tandem, scroll-type with a variable capacity operation capability of one compressor of the pair. Compressor solenoid valve shall unload the compressor and allow for variable capacity operation. The compressor shall be equipped with a suction gas cooled motor, vibration isolators, thermal overloads, automatic reset high pressure switch with lockout after three failures, rotalock service valves, suction line strainer and shall have a maximum operating speed of 3500 RPM.

2.6.1.1 2.6.2

Crankcase Heaters
The compressors shall include crankcase heaters, powered from the indoor unit electric panel.

Evaporator Coil
The evaporator coil shall be A-frame design and have ______ sq. ft. (______ sq m) face area, six rows deep, with each circuit feeding three rows. It shall be constructed of rifled copper tubes and aluminum fins with a maximum face velocity of _____ ft. per minute (_____ m/s) at _____ CFM (_____ CMH). A stainless steel condensate drain pan shall be provided.

2.6.3

R-410A Refrigerant
The system shall be designed for use with R-410A refrigerant, which meets the U.S. Clean Air Act for phase-out of HCFC refrigerants. Refrigerant shall be field-supplied and field-charged by the installing contractor.

2.7

ECONOPHASE CYCLEOPTIONAL (SELECT ONLY IF PR085 OR PR125 IS SELECTED)


During cold ambient temperatures refrigerant pumps shall circulate refrigerant through the cooling system in lieu of operating the compressors. The compressors shall ramp down during EconoPhase operation, and if able to completely offset the load, the control system shall shut Off the compressors. Dual refrigerant pumps shall be housed in an enclosure with each pump dedicated to a single refrigerant circuit. The EconoPhase system shall include a variable speed drive on each refrigerant pump to enable to pumps speed to adjust in response to load.

2.8
2.8.1

MISCELLANEOUS OPTIONS
Non-Locking Disconnect SwitchOptional
The manual disconnect switch shall be mounted in the high voltage section of the electrical panel. The switch shall be accessible with the door closed. The electrical system shall be rated for 65 kA, shortcircuit current rating (28kA at 575V).

Liebert DSE

44

GUIDE SPECIFICATIONS

2.8.1

Locking Disconnect SwitchOptional


The manual disconnect switch shall be mounted in the high-voltage section of the electrical panel. The switch shall be accessible from the outside of the unit with the door closed and prevent access to the high voltage electrical components until switched to the Off position. The electrical system shall be rated for 65 kA, short-circuit current rating (25kA at 575V).

2.8.2

High-Temperature SensorOptional
The high-temperature sensor shall be factory-installed in the unit and shall be factory-set to 125F (52C). It shall immediately shut down the Precision Cooling system when activated. The sensor shall be mounted with the sensing element in the return air.

2.8.3

Smoke SensorOptional
The smoke sensor shall immediately shut down the Precision Cooling system and activate the alarm system when activated. The smoke sensor shall be mounted in the electrical panel with the sensing element in the return air compartment. The smoke sensor is not intended to function as or replace any room smoke detection system that may be required by local or national codes. The smoke sensor shall include a supervision contact closure.

2.8.4

Condensate Pump, Dual FloatOptional


The condensate pump shall have a minimum capacity of 145 GPH (548 l/h) at 20 ft. (58 kPa) head. It shall be complete with integral dual-float switches, pump-and-motor assembly and reservoir. The secondary float shall send a signal to the local alarm and shut down the unit upon high water condition.

2.8.5

Low-Voltage Terminal PackageOptional


Factory-installed and wired terminals shall be provided for customer connection to lock out the reheat and humidifier upon contact closure. Two (2) extra N/O common alarm contacts shall be provided. Two (2) extra remote shutdown terminals shall be provided.

2.8.6 2.8.7 2.8.8

Remote Humidifier ContactOptional


A pair of N/O contacts shall be provided for connection to a remote humidifier.

Main Fan OverloadOptional


A pair of N/O contacts shall be factory-installed and factory-wired to indicate Main Fan Overload.

Compressor OverloadOptional
A pair of N/O contacts shall be factory-installed and factory-wired to each compressor to indicate Compressor Overload.

2.9

AIR-COOLED SYSTEMS
The indoor evaporator unit shall include refrigerant piping and shall have a factory holding charge of nitrogen. The hot-gas and liquid lines shall be spun shut and each shall include a factory-installed Schrader valve. Field-relief of the Schrader valve shall indicate a leak-free system from the factory. Installing contractor shall cut the evaporator piping and shall evacuate and charge the system. Refrigerant shall be supplied by the installing contractor.

2.9.1

Air-Cooled Condenser
The Liebert-manufactured outdoor air-cooled condenser shall be the low profile, multiple direct drive, propeller fan type. The condenser shall balance the heat rejection of the compressor at ____ F (____ C) ambient. The condenser shall be constructed of a microchannel coil. LIEBERT LIQUI-TECT SENSORS ____ (quantity) solid state water sensors shall be provided for installation under the raised floor.

2.10

45

Liebert DSE

GUIDE SPECIFICATIONS

2.11

FLOOR STAND
The floor stand shall be constructed of a welded steel frame. The floor stand shall have adjustable legs with vibration isolation pads. The floor stand shall be _______ inches (mm) high.

2.11.1 Seismic Rated Floor StandOptional


The floor stand shall be seismic rated per IBC2009 and shall be attached to the unit frame (field-installed). The floor stand shall also be capable of being anchored to the subfloor.

2.12

RETURN AIR PLENUM FOR DOWNFLOW UNITS


The air plenum shall be constructed of 20 gauge steel, powder coated to match unit color. The plenum shall be _____" (_____ mm) high. A door shall be included in the front of the plenum to enable front filter access. Air shall enter the plenum from the top.

3.0
3.1 3.2

EXECUTION
INSTALLATION OF PRECISION COOLING UNITS
The customer or the customer's representative shall be responsible for the following:

GENERAL
Install precision cooling units in accordance with manufacturer's installation instructions. Install units plumb and level, firmly anchored in locations indicated and maintain manufacturer's recommended clearances.

3.3

ELECTRICAL WIRING
Install and connect electrical devices furnished by manufacturer but not specified to be factorymounted. Furnish copy of manufacturer's electrical connection diagram submittal to electrical contractor.

3.4

PIPING CONNECTIONS
Install and connect devices furnished by manufacturer but not specified to be factory-mounted. Furnish copy of manufacturer's piping connection diagram submittal to piping contractor.

3.5

FIELD QUALITY CONTROL


Start cooling units in accordance with manufacturer's startup instructions. Test controls and demonstrate compliance with requirements. These specifications describe requirements for a computer room environmental control system. The system shall be designed to maintain temperature and humidity conditions in the rooms containing electronic equipment. The manufacturer shall design and furnish all equipment to be fully compatible with heat dissipation requirements.

Liebert DSE

46

Ensuring The High Availability Of Mission-Critical Data And Applications.

Emerson Network Power, a business of Emerson (NYSE:EMR), is the global leader in enabling Business-Critical Continuity from grid to chip for telecommunication networks, data centers, health care and industrial facilities. Emerson Network Power provides innovative solutions and expertise in areas including AC and DC power and precision cooling systems, embedded computing and power, integrated racks and enclosures, power switching and controls, infrastructure management, and connectivity. All solutions are supported globally by local Emerson Network Power service technicians. Liebert AC power, precision cooling and monitoring products and services from Emerson Network Power deliver Efficiency Without Compromise by helping customers optimize their data center infrastructure to reduce costs and deliver high availability.

Technical Support / Service


Web Site www.liebert.com Monitoring liebert.monitoring@emerson.com 800-222-5877 Outside North America: +00800 1155 4499 Single-Phase UPS & Server Cabinets liebert.upstech@emerson.com 800-222-5877 Outside North America: +00800 1155 4499 Three-Phase UPS & Power Systems 800-543-2378 Outside North America: 614-841-6598 Environmental Systems 800-543-2778 Outside the United States: 614-888-0246

Locations
United States 1050 Dearborn Drive P.O. Box 29186 Columbus, OH 43229 Europe Via Leonardo Da Vinci 8 Zona Industriale Tognana 35028 Piove Di Sacco (PD) Italy +39 049 9719 111 Fax: +39 049 5841 257 Asia 29/F, The Orient Square Building F. Ortigas Jr. Road, Ortigas Center Pasig City 1605 Philippines +63 2 687 6615 Fax: +63 2 730 9572

While every precaution has been taken to ensure the accuracy and completeness of this literature, Liebert Corporation assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions. 2010 Liebert Corporation All rights reserved throughout the world. Specifications subject to change without notice. Liebert is a registered trademark of Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners.