ANTAMINA PROJECT

220 kV VIZCARRA SUBSTATION

220 kV CABLE BUS CONDUCTORS


ELECTRICAL PHASE SPACING CALCULATIONS

Revised
Report

Approved

21-30-21-E - Rev A

Date

220Kv CABLE BUS CONDUCTORS. ELECTRICAL PHASE SPACING CALCULATIONS


21-30-21-E-Rev A

REVISION
REV

DESCRIPTION

DATE

First Issue

May 19, 1999

/var/www/apps/conversion/tmp/scratch_1/225917164.doc
2

220Kv CABLE BUS CONDUCTORS. ELECTRICAL PHASE SPACING CALCULATIONS


21-30-21-E-Rev A

220 kV VIZCARRA SUBSTATION


220 kV CABLE BUS CONDUCTORS
ELECTRICAL PHASE SPACING CALCULATIONS
CONTENT

1.00

PURPOSE

2.00

STANDARDS & REFERENCES

3.00
3.01
3.02
3.03

PROJECT DATA
Service Conditions
Electrical System
Construction Data

4.00
4.01

CALCULATION HYPOTHESIS
Maximum Wind
Wind Load
Wind Angle
Electrical Distance
Shortcircuit
Shortcircuit Load
Shortcircuit Angle
Electrical Distance

4.02

/var/www/apps/conversion/tmp/scratch_1/225917164.doc
3

220Kv CABLE BUS CONDUCTORS. ELECTRICAL PHASE SPACING CALCULATIONS


21-30-21-E-Rev A

220kV Vizcarra Substation


220kV Cable Bus Conductors
Electrical Clearances Calculations
1.0

PURPOSE
The purpose of this document is to provide the calculations for 220kV Electrical
Cable Bus Phase Spacing applicable to Vizcarra Substation as a part of the electric
supply for Antamina Project.

2.0

STANDARD & REFERENCES


This report check the safety of the design for the distance between phases, each of
them with two conductor per phase with respect to the distances recommended by
the IEEE Technical Paper 54-80, 1954.
The calculations begins with the design spacing of 5 meters, phase-to-phase, and
applies, separately, the wind loading and short-circuit conditions. This determines
the maximum movement or minimum spacing that will result from these
conditions.

3.0

PROJECT DATA
3.1

Service Conditions
For Vizcarra Substation, we will consider the Maximum Wind Velocity as:
V = 130km/h

3.2

Electrical System
The design short circuit level is:
I = 6kA

3.3

Construction Data

Arrangment of Conductors
We will use phase to phase distances (center line value):

/var/www/apps/conversion/tmp/scratch_1/225917164.doc
4

220Kv CABLE BUS CONDUCTORS. ELECTRICAL PHASE SPACING CALCULATIONS


21-30-21-E-Rev A

d = 5m
There will be two conductors per phase and the separation between each
of them is:
e = 200mm

Insulators
Each insulator string has following characteristics:

Length:

l = 3.5 m

Diameter:

Weight:

Wa = 165 kgf

= 280mm

Conductors
The conductor has the following characteristics:

4.0

Diameter:

c =31.62

mm

Weight per length unit:

wc = 1.979 kgf/m

Span:

a = 48 m

CALCULATION HYPOTHESIS
4.1

Maximum Wind

Wind Load
In this part we will find the wind load on an insulator string (Ea) and a
conductor (Ec) :

Ea : (127.kg .m 3 ).0.00482.v 2 .(0.5.l.a )


Ea = 39.885.kgf

/var/www/apps/conversion/tmp/scratch_1/225917164.doc
5

220Kv CABLE BUS CONDUCTORS. ELECTRICAL PHASE SPACING CALCULATIONS


21-30-21-E-Rev A

Ec :=(127.kg .m 3 ).0.00482.v 2 .(0.8.a.c )

Ec

=98.834kgf

ec :=

Ec
a

/var/www/apps/conversion/tmp/scratch_1/225917164.doc
6