Vous êtes sur la page 1sur 2

TD.37B.07A.T.E.

Clipper VL80 (CVL080)


The Clipper VL is a commercial grade and light industrial surge protection device (SPD) that combines surge
suppression components and EMI/RFI filtering to provide effective protection for sensitive electronic loads.
This Clipper VL has 80 kA per phase of surge current capacity. Features include:
10 year warranty
Independently Tested
UL 1449 2
nd
Edition, UL 1283 Listed, CSA Approved, CE
Marked
Highly reliable hybrid MOV/filter system Individually fused surge suppression components
Provides Sinewave tracking Status LED indicator, Audible alarm and Form C
I. Surge Current Capacity
Configuration Surge Current Capability per phase and per mode (8x20 s)
Per phase (kA) L-G (kA) L-N (kA) N-G (kA) L-L (kA)
3 Wye (4W + G) 80 40 40 40 -----
3 Delta (3W + G) 80 40 ----- ----- 40
Single Split Phase
(3W + G)
80 40 40 40 -----
II. Model Features: (please check appropriate features for your application)
CVL080CH
III. Performance Specifications
A. Filtering Capabilities
1. UL 1283 Complimentary Listed
2. EMI / RFI Attenuation : 40 dB @ 100 kHz
3. Filter Bandwidth : 10 kHz to 100 MHz
B. UL 1449 2
nd
Edition Surge Voltage Ratings
Nominal
Voltage
Modes of Protection
Wye: L-N L-G N-G L-L
208Y/120 500 500 500 500
480Y/277 800 800 800 1500
600Y/347 1000 1000 1000 2000
Delta:
240D ------ 800 ------ 800
480D ------ 1500 ------ 1500
600D ------ 2000 ------ 2000
C. Other Specifications
1) Warranty : Ten (10) years
2) Agency Listings: UL 1449 2
nd
Edition, UL1283,
CSA 22.2
3) Response Time : <0.5 ns
4) Line Frequency : 47 to 65 Hz
5) Line Voltage : +/ - 15% normal
6) Temperature : -40 to +60 C
7) Relative Humidity : 0 to 95% non-condensing
8) Altitude : >0 to 28,000 feet
9) Audible Noise : none
10) Maximum Continuous Operating Voltage (MCOV)
150 V (L-N,G,N-G) for 208Y/120 V systems
275/150 V (L-L/L-N, G, N-G) for 240/120 V
systems
320 V (L-N, G, N-G) for 400Y/230 V systems
320 V (L-N, G, N-G) for 480Y/277 V systems
420 V (L-N, G, N-G) for 600Y/347 V systems
11)Enclosure Dimensions
NEMA 1: 11.55 x 5.00 x 2.60
NEMA 3R: 11.55 x 5.00 x 2.92
Voltage
Code
BD
Status indicator on
each phase
Enclosure
Application
Voltage Code 120/208
240 V
230/400
400 V
277/480
480 V
347/600
600 V
120/240 Single Split Phase
(3W+G)
! 240S
Three Phase Wye (4W+G) ! 208Y ! 400Y ! 480Y ! 600Y
Three Phase Delta (3W+G) ! 240D ! 400D ! 480D ! 600D
Retrofit Enclosure
! RSX - Standard Retrofit (NEMA 1)
! R3X - weatherproof
Technical Doc. CPS-B 3/6/98 2 CPS-B Specifications Cutler-Hammer,1998