Automatic synchronization and load sharing of two generating sets

controlled by a single module


GENERAL POINTS
DUOGEN is a microprocessor based single module which gathers
the control of two generators. DUOGEN carries out manual and auto
synchronization, isochronous load sharing or droop load sharing.
DUOGEN integrates the following features:
- 1 digital input for auto synchronization.
- 1 sync check relay is checking phase, frequency and voltage
differences.
- 1 'Load shedding' output relay is calling for need of power, allowing
a better power plant global efficiency.
- 2 Isochronous kW sharing controls.
- 2 Iso-voltage kVAR sharing controls.
- 2 Reverse power protections.
INPUTS/OUTPUTS FOR EACH GENSET
3 phases genset voltages (3 or 4 wires, 100 to 440 VAC).
3 phases genset currents (1A or 5A CTs).
1 digital input: feedback of the genset breaker position.
1 digital input: unload request (adjustable ramp time).
1 analogue input for speed control
( 5 VDC or potentiometer).
2 output relays: trip request and reverse power protection.
1 analogue output: active power monitor
(0-5V or 0-1mA adjustable).
Proportional and integral gain pot for synchronization.
1 analogue output for speed control adjustable with Gain pot and
Offset pot, compatible with most electronic governors (Barber
Colman, Woodward, GAC, Heinzmann, Ambac, DDEC, MDEC).
1 analogue output for voltage control, adjustable with Gain pot and
Offset pot, compatible with most AVR (Leroy Somer, Stamford,
Basler).
COMMON INPUTS/OUTPUTS
'SYNC OK' output relay: always active. Stays open in
dead bus conditions.
The coupling authorization safety relay is authorizing the
coupling only when differences in frequency, voltage and
phase meet the requirements of the installation.
'LOAD SHEDDING' output relay: active when application
needs the power of the two gensets.
1 digital input: remote synchronization request.
1 digital input: droop mode.
Stability and load sharing pot. for ILS.

APPLICATIONS
Two gensets in change over application:
Manual mode: potentiometer speed for synchronization
and kW control.
Auto mode: automatic synchronization and load
sharing.
Two gensets in change over application + no
break return to mains with soft load transfer:
Add a C2S-III (CRE module, reference A25W0) to
synchronize the power plant to mains.
Gaz, fuel, and turbines:
Duogen can be installed regardless the type of prime
mover and fuel.








CHARACTERISTICS
Weight - Size: 1.5 kg - 200x275x26 mm
Measuring voltage and current input:
Reference Switch GE 1 & 2
pos. 1 110 VAC / 5AAC
pos. 2 240 VAC / 5AAC

A40R0
pos. 3 440 VAC / 5AAC

Frequency: 50 or 60 Hz.
Output relay contacts:
Volt free contacts, 5 A at voltage of 250 VAC, maximum cutting voltage 440
VAC. Switched power on resistive load, 1250 VA .






ENVIRONMENT
Power supply:
9 to 40VDC 10 Watts
Operating temperature:
-20 to +85 C.
Mounting:
can be mounted in all positions.
Humidity:
will operate normally in humid conditions (Tropic-proof
circuits).
CE Mark:
Duogen is in conformity with European CE Mark
requirements.
WIRING DIAGRAM
DUOGEN
AVR
Speed
governor
-Alim
17 Gen1 Speed out
23 Gen1 I1-
24
Gen1 I2+
25 Gen1 I2-
26 Gen1 I3+
27 Gen1 I3-
41
S
y
n
c
h

O
K
N
O
40
16 Gen1 Speed CCW -
15
Gen1 Speed CW + 14
1
P
o
w
e
r

s
u
p
p
ly

+
2
p
o
w
e
r

s
u
p
p
ly

-
18 Gen1 Speed Ref
20 Gen1 AVR out +
21 Gen1 AVR out -
28 Gen1 L1
29 Gen1 L2
30 Gen1 L3
31 Gen1 N (optional)
22 Gen1 I1+
Chassis
isolated from
power supply
From speed
governors
4 mm wire
19
P1
P2
S1
S2
L2
N
L3
L1
analog
100 - 480 V
5 A
48 Gen2 Speed out
57
Gen2 I3-
56 Gen2 I2+
55 Gen2 I2-
54 Gen2 I1+
53 Gen2 I1-
49 Gen2 Speed ref
51 Gen2 AVR out +
52 Gen2 AVR out -
50
59 Gen2 L1
60 Gen2 L2
61 Gen2 L3
62 (optional) Gen2 N
58 Gen2 I3+
G2
Surge
diverter
3
G
e
n
1

b
r
e
a
k
e
r

I
N
4
G
e
n
2

B
r
e
a
k
e
r

I
N
5
G
e
n
1

U
n
lo
a
d
37
G
e
n
2

U
n
lo
a
d
36
S
y
n
c

in
G
e
n
1

t
r
ip

o
u
t
N
O
G
e
n
2

t
r
ip

o
u
t
N
O
G
e
n
2

R
e
v
.

k
W
N
O
11
12
Gen1 kW out +5V
Gen1 kW out 0
Power monitor
0-5V or 0-1mA
L
o
a
d

s
h
e
d
d
in
g
N
O
AVR
Speed
governor
6
D
r
o
o
p
Gen1 Speed setpoint
+/- 5V or potentiometer
16 Gen2 Speed CCW -
15
Gen2 Speed CW + 14
Gen2 Speed setpoint
38 39
G
e
n
1

R
e
v
.

k
W
N
O
13 Gen1 kW out 1mA
42
43
Gen2 kW out +5V
Gen2 kW out 0
44 Gen2 kW out 1mA
-
Battery
+
5Amps
Power monitor
0-5V or 0-1mA
P1
P2
S1
S2
P1
P2
S1
S2
analog
F
F
F
Load
C2S III
Auto
Mains
Failure
L2
N
L3
L1
+/- 5V or potentiometer
analog
analog
F
100 - 480 V
Surge
diverter
F
F
F
P1
P2
S1
S2
P1
P2
S1
S2
P1
P2
S1
S2
5 A
-Alim
to pin 36
G2 breaker in
G2 breaker in
G1 breaker in
-Alim
to pin 5
G1 breaker in
Breaker control
35 34 32 33 10 9 7 8
G1

A40R090011C.doc

Vous aimerez peut-être aussi