Medium Voltage Switchgear
NORMACEL

CASSETTE
With draw-out vacuum circuit breakers
Up to 17,5 kV
2500 A
40 kA
EFACEC Energia , Mquinas e Equipamentos Elctricos, S.A.
Medium Voltage Switchgear Division
www.efacec.pt
E-mail: en @efacec.pt
TECHNICAL DATA
Electrical
Ratedvoltage 7,2- 12- 17,5kV
Insulationlevel Impulse95kV
Power frequency38kV - 1min.
Frequency 50Hz
Ratedcurrent 630A, 1250A, 1600A, 2000A and2500A
Ratedpeak withstandcurrent 40- 63- 100kA
Ratedshort-timecurrent, 3s 16- 25- 40kA
Mechanical
Protectiondegree(CEI 529) IP3X (I P4X under request)
Enclosures Multifoldedhighquality2mmAluminium
galvanisedsheet steel sectionsbolted
together. Thedoor iselectrostatic coatedwith
anepoxy-polyester primer andthenstove
enamelled.
Standardcolour RAL 7032
Normal service conditions
Minimumambient temperature -5C
Maximumambient temperature 40C
Maximum24-hour average 35

C
Maximumrelativehumidity 95%
Sitealtitude 1000m
Applicable Standards
IEC 298, 694, 529, 56, 129 (BS standardsalsoapplicable)
Optional Equipment
Earthingswitch
Voltageindicators
Interlockingsandsecuritylocks
Micro switches
Heater / thermostat
Overpressurerelief device
Li sbon
RuadaGaragem, 1 Apartado527 Carnaxide
2796-853Linda-a-VelhaCodex Portugal
Tel: (351-21)4163600 Fax: (351-21) 4163620
Export
Arroteia LeadoBailio Apartado1018
4466-952S.MamededeInfestaCodex Portugal
Tel:(351-22) 9562300 Fax: (351-22)9562889
Oporto
Arroteia LeadoBailio Apartado1018
4466-952S.MamededeInfestaCodex Portugal
Tel: (351-22)9562300 Fax: (351-22) 9562889
NORMACEL

CASSETTE
NORMACEL

CASSETTE
DESIGN CONCEPT
Includedinthe EFACECsmediumvoltageswitchgear
manufacturinglongtradition, NORMACEL

CASSETTE opens
newdoorsinto theswitchgear future.
NORMACEL

CASSETTEmakestheworkwithmediumvoltage
Switchgear simpler, flexibleandeconomical.
NORMACEL

CASSETTE compact designisideal for the


replacement of obsoletecircuit-breakersinexistingswitchboards.
NORMACEL

CASSETTE givestheopportunityto all panel


makersto buildapersonalisedswitchboard.
NORMACEL

CASSETTEistotallysheet steel encloseddesign,


usingstandardcubicleunitsandwithdrawablecircuit breakers.
NORMACEL

CASSETTE, beingawareof theincreasingneeds


concerningpeopleandequipment protection, took into
considerationthefollowingfeatureson NORMACEL

CASSETTE development:
Safety andhighreliability
Activeandpassiveprotectionsystems
Simpleandsecureoperations
Compact design
Totallyfront operated
Functional flexibility
Reduceddimensions

Longmechanical andelectrical life


Widerangeof applications
Excellent performances CONSTRUCTION
Withdrawablevacuumcircuit breaker suitableto
beinstalledinametalcladcubicle.
NORMACEL

CASSETTE structure, inclu-ding


front door, isreinforcedinorder to beinternal
arcresistant.
Operationof all equipment frontally:
- Circuit-breaker ismovedinto theserviceor
test-positionwiththedoor closed.
- Final positionsarereachedthroughaclutch
system, independent fromtheoperator.
- Quick-makeearthingswitches(withmaking
capacity).
Earthingswitch, statusiseasilyvisiblethrough
thefront control panel.
Suitablefor all typesof cableterminations
INSTALLATION
NORMACEL

CASSETTE switchgear is simple


andquick toinstall.
TheInstructionManual distributedwitheach
panel describestherequiredprocedures. Technical
servicesareavailablefor additional support.
W
H
F F
A
B
179
E
C
163
346 803
3
1
8
5
7
4
6
5
6
2
4
D
10 11
9
CUBICLE COMPOSITION
1- WithdrawableDivac circuit-breaker 7- Voltagecapacitor divider
2- Earthingswitch 8- Lowvoltageplug
3- Earthingswitchcontrol 9- Exhaust vent (2000A/2500A)
4- Shutters 10- Overpressurerelief device(Optional 2500A)
5- Bushings 11- Overpressurerelief device(Optional upto 2000A)
6- Tee-off
Isc

25 kA 25kA< Isc

40 kA
DIMENSIONS In 1250A 1250A< In 2500A In 1250A
High(H) 1123 1314 1314
Depth(D) 803+346(withES) 803+346(withES) 803+346(withES)
Width(W) 700 850 750
Door (A) 750 834 834
LowVoltageCompartment(B) 194 296 296
Distancetothefloor (C) 542 574 574
DistancebetweenBushings(E) 255 320 320
WithdrawableDivacCircuit-breaker 1250A WithdrawableDivacCircuit-breaker 2500A