Report No. : ETL / Relay/ 2013-14/ 52 Report on: Over Current & E/F Relay.
Location: MRSS-2, 33 kV control panel Date: 11.09.2013
System : Bay-3, outgoing to Oxygen plant
1.0 Relay Specification:
Make : Alstom Type: P127
Sl No : 130598330432001 Relay Rating (In): 1.0
Aux. Volts : 130-250 V dc CTR: 600/1
2.0 Existing Setting:
2.1 Over Current Protection (Phase Fault):

I >>> - I/In
TI >>> - sec
I >> 12.0 I/In
TI >> 0.2 sec
I > - I/In
TI > - sec
Char ph S inverse
Tp 0.175 sec
Ip 1.5 I/In

2.2 Earth Fault Protection :

IE >>> - I/In
TI E>>> - sec
IE >> 4.0 I/In
TIE >> 0.15 sec
IE > - I/In
TIE > - sec
Char S inverse
TIEP 0.125 sec
IEP 0.8 I/In

Electro Technical Laboratory
(An ISO Certified Electrical Testing Lab)
Jindal Steel & Power Limited,
Post Box No.16, Kharsia Road, Raigarh-496001
Phone: 07762-227001-05(extn-2955/5280)
E-mail:- etl@jspl.com
F-02(6.3.0-08)/Issue 01, Dt. 08.10.2010
- 2 -


3.0 Secondary Injection Test:

3.1: Phase over Current Protection:

3.1.1: I >>> Protection Check







3.1.2. I >> Protection Check:







3.1.3. I > Protection Check:







3.1.4. IDMT Over current Protection Check:












Phase
Relay set at
Amp
Relay p.u. at
Amp
Timer set at
sec
Operating time measured at
1.5xIset of current injected in
msec
R,Y,B - - - -
Phase
Relay set at
Amp
Relay p.u. at
Amp
Timer set at
sec
Operating time measured at
1.5xIset of current injected in
sec
R,Y,B 2.5 0.2 2.51 0.249
Phase
Relay set at
Amp
Relay p.u. at
Amp
Timer set at
sec
Operating time measured at
1.5xIset of current injected in
sec
R,Y,B - - - -
Operating time measured at multiple of current
injected in sec
Relay set at
Char= Normal inv

TMS
set at sec
2 5 10
TP = 0.175 sec
IP = 1.0 Amp

0.175 1.804 0.779 0.557
Electro Technical Laboratory
(An ISO Certified Electrical Testing Lab)
Jindal Steel & Power Limited,
Post Box No.16, Kharsia Road, Raigarh-496001
Phone: 07762-227001-05(extn-2955/5280)
E-mail:- etl@jspl.com
F-02(6.3.0-08)/Issue 01, Dt. 08.10.2010
- 3 -


3.2. Earth Fault Protection:

3.2.1. IE>>> Protection Check:







3.2.2. IE>> Protection Check:







3.2.2. IE> Protection Check:







3.2.3. IDMT Earth Fault Protection Check:







Phase
Relay set at
Amp
Relay p.u. at
Amp
Timer set at
sec
Operating time measured at
1.5xIset of current injected in
sec
N - - - -
Phase
Relay set at
Amp
Relay p.u. at
Amp
Timer set at
sec
Operating time measured at
1.5xIset of current injected in
sec
N .0 4.12 0.15 0.199
Phase
Relay set at
Amp
Relay p.u. at
Amp
Timer set at
sec
Operating time measured at
1.5xIset of current injected in
sec
N - - - -
Operating time measured at multiple of current
injected in sec
Relay set at
Char= Normal
inv



Phase

TMS set at
sec
2 5 10
TIEP=0.125 sec
IEP = 0.8 Amp


N

0.125 1.285 0.574 0.409
Electro Technical Laboratory
(An ISO Certified Electrical Testing Lab)
Jindal Steel & Power Limited,
Post Box No.16, Kharsia Road, Raigarh-496001
Phone: 07762-227001-05(extn-2955/5280)
E-mail:- etl@jspl.com
F-02(6.3.0-08)/Issue 01, Dt. 08.10.2010
- 4 -




5.0 General Function Checks:

5.1 Led Indication: OK

5.2 Display: OK

5.3 Key Pad: OK


6.0 Remarks:
6.1. Master relay and circuit breaker operation checked and found satisfactory. Relay test
results are found satisfactory.






Smita Shukla M. Chawhan M. Chawhan
Tested By Checked By Approved By