FAN DUTY : 1.

269 m/s
Item Description Size / Quantity
Unit App. Pressure Drop
(Pascal)
Total App. Pressure
Drop (Pascal)
1 Fume Hood Total Pressure Drop 1 No. 500 500
2 Phoenix Flow Control Valve 1 No: 250 250
3 Manual/ Motorised Volume Control Dampers 1 No. 30 30
4 Back draft damper 1 No. 35 35
5 Sound Attenuator 1 No. 80 80
6 Approximate Ducting Length,0.37 Pascal per Metre 3.5 m. 0.37 Pascal per Metre 1.3
7
Approximate Ducting Length, 1.93 Pascal per
Metre
14.2 m 1.93 Pascal per Metre 27.5
8
Approximate Ducting Length, 2.51 Pascal per
Metre ( horizontal 87+35+31.5 )
153.5 m 2.51 Pascal per Metre 385.3
9
Approximate Ducting Length, 2.51 Pascal per
Metre ( vertical riser )
48 m 2.51 Pascal per Metre 120
10 Approximate Duct Fittings 20 % of Duct pressure drop 106.8
11 Duct & Fittings safety factor 10 % safety factor 153.60
1689.50
Static Pressure Calculations
H-M2-45-24-HDE-20
Exhaust of Contaminated Lab fume air to outside.
Total ESP For the fan
FAN DUTY : 0.741 m/s
Item Description Size / Quantity
Unit App. Pressure Drop
(Pascal)
Total App. Pressure Drop
(Pascal)
1 Fume Hood Total Pressure Drop 1 No. 500 500
3 Phoenix Flow Control Valve 1 No: 250 250
3
Manual/ Motorised Volume Control
Dampers
1 No. 30 30
4 Back draft damper 1 No. 35 35
5 Sound Attenuator 1 No. 80 80
6
Approximate Ducting Length,0.54
Pascal per Metre (horizontal)
25.2 m. 0.54 Pascal per Metre 13.6
7
Approximate Ducting Length, 0.19
Pascal per Metre (horizontal )
8.5 m 0.19 Pascal per Metre 1.6
8
Approximate Ducting Length, 0.49
Pascal per Metre ( horizontal )
4.5 m 0.49 Pascal per Metre 2.2
9
Approximate Ducting Length, 0.91
Pascal per Metre ( horizontal )
60 m 0.91 Pascal per Metre 54.6
10
Approximate Ducting Length, 0.91
Pascal per Metre ( vertical )
25 m 0.91 Pascal per Metre 22.8
11
Approximate Ducting Length, 0.91
Pascal per Metre ( horizontal )
67 m 0.91 Pascal per Metre 61
Approximate Ducting Length, 0.91
Pascal per Metre ( horizontal )
13 m 0.91 Pascal per Metre 11.8
12 Approximate Duct Fittings 20 % of Duct pressure drop 36.2
13 Duct & Fittings safety factor 10 % safety factor 109.80
1208.6
H-M2-45-24-HDE-15
Static Pressure Calculations
Exhaust of Contaminated Lab fume air to outside.
Total ESP For the fan
FAN DUTY : 0.382 m/s
Item Description Size / Quantity
Unit App.
Pressure Drop
(Pascal)
Total App. Pressure
Drop (Pascal)
1
Fume Hood Total Pressure
Drop
1 No. 500 500
3
Phoenix Flow Control
Valve
1 No: 250 250
3
Manual/ Motorised Volume
Control Dampers
1 No. 30 30
4 Back draft damper 1 No. 35 35
5 Sound Attenuator 1 No. 80 80
6
Approximate Ducting
Length, 2.69 Pascal per
Metre (horizontal)
58 m.
2.69 Pascal per
Metre
156
7
Approximate Ducting
Length, 2.69 Pascal per
Metre (vertical )
25 m
2.69 Pascal per
Metre
67.3
8
Approximate Ducting
Length, 2.69 Pascal per
Metre ( horizontal )
20 m
2.69 Pascal per
Metre
53.8
9 Approximate Duct Fittings
20 % of Duct
pressure drop
55.4
11
Duct & Fittings safety
factor
10 % safety factor 122.70
1350.2
H-M2-45-24-HDE-01
Static Pressure Calculations
Exhaust of Contaminated Lab fume air to outside.
Total ESP For the fan
FAN DUTY : 0.382 m/s
Item Description Size / Quantity
Unit App.
Pressure Drop
(Pascal)
Total App. Pressure
Drop (Pascal)
1
Fume Hood Total Pressure
Drop
1 No. 500 500
3
Phoenix Flow Control
Valve
1 No: 250 250
3
Manual/ Motorised
Volume Control Dampers
1 No. 30 30
4 Back draft damper 1 No. 35 35
5 Sound Attenuator 1 No. 80 80
6
Approximate Ducting
Length, 2.69 Pascal per
Metre (horizontal)
62 m.
2.69 Pascal per
Metre
166.8
7
Approximate Ducting
Length, 2.69 Pascal per
Metre (vertical )
25 m
2.69 Pascal per
Metre
67.3
8
Approximate Ducting
Length, 2.69 Pascal per
Metre ( horizontal )
22 m
2.69 Pascal per
Metre
59.2
9 Approximate Duct Fittings
20 % of Duct
pressure drop
58.7
10
Duct & Fittings safety
factor
10 % safety factor 124.70
1371.7
H-M2-45-24-HDE-02
Static Pressure Calculations
Exhaust of Contaminated Lab fume air to outside.
Total ESP For the fan
FAN DUTY : 0.382 m/s
Item Description Size / Quantity
Unit App.
Pressure Drop
(Pascal)
Total App. Pressure
Drop (Pascal)
1
Fume Hood Total Pressure
Drop
1 No. 500 500
3
Phoenix Flow Control
Valve
1 No: 250 250
3
Manual/ Motorised Volume
Control Dampers
1 No. 30 30
4 Back draft damper 1 No. 35 35
5 Sound Attenuator 1 No. 80 80
6
Approximate Ducting
Length, 2.69 Pascal per
Metre (horizontal)
20 m.
2.69 Pascal per
Metre
53.8
7
Approximate Ducting
Length, 2.69 Pascal per
Metre (vertical )
25 m
2.69 Pascal per
Metre
67.3
8
Approximate Ducting
Length, 2.69 Pascal per
Metre ( horizontal )
38 m
2.69 Pascal per
Metre
102.2
9 Approximate Duct Fittings
20 % of Duct
pressure drop
44.7
10
Duct & Fittings safety
factor
10 % safety factor 116.30
1279.3
H-M2-45-24-HDE-04
Static Pressure Calculations
Exhaust of Contaminated Lab fume air to outside.
Total ESP For the fan
FAN DUTY : 0.382 m/s
Item Description Size / Quantity
Unit App.
Pressure Drop
(Pascal)
Total App. Pressure
Drop (Pascal)
1
Fume Hood Total Pressure
Drop
1 No. 500 500
3
Phoenix Flow Control
Valve
1 No: 250 250
3
Manual/ Motorised
Volume Control Dampers
1 No. 30 30
4 Back draft damper 1 No. 35 35
5 Sound Attenuator 1 No. 80 80
6
Approximate Ducting
Length, 2.69 Pascal per
Metre (horizontal)
30 m.
2.69 Pascal per
Metre
80.7
7
Approximate Ducting
Length, 2.69 Pascal per
Metre (vertical )
25 m
2.69 Pascal per
Metre
67.3
8
Approximate Ducting
Length, 2.69 Pascal per
Metre ( horizontal )
49 m
2.69 Pascal per
Metre
131.8
9 Approximate Duct Fittings
20 % of Duct
pressure drop
55.9
10
Duct & Fittings safety
factor
10 % safety factor 122.40
1353.1
H-M2-45-24-HDE-05
Static Pressure Calculations
Exhaust of Contaminated Lab fume air to outside.
Total ESP For the fan
FAN DUTY : 0.382 m/s
Item Description Size / Quantity
Unit App.
Pressure Drop
(Pascal)
Total App. Pressure
Drop (Pascal)
1
Fume Hood Total Pressure
Drop
1 No. 500 500
3
Phoenix Flow Control
Valve
1 No: 250 250
3
Manual/ Motorised
Volume Control Dampers
1 No. 30 30
4 Back draft damper 1 No. 35 35
5 Sound Attenuator 1 No. 80 80
6
Approximate Ducting
Length, 2.69 Pascal per
Metre (horizontal)
30 m.
2.69 Pascal per
Metre
80.7
7
Approximate Ducting
Length, 2.69 Pascal per
Metre (vertical )
25 m
2.69 Pascal per
Metre
67.3
8
Approximate Ducting
Length, 2.69 Pascal per
Metre ( horizontal )
49 m
2.69 Pascal per
Metre
131.8
9 Approximate Duct Fittings
20 % of Duct
pressure drop
55.9
10
Duct & Fittings safety
factor
10 % safety factor 123.10
1353.8
H-M2-45-24-HDE-06
Static Pressure Calculations
Exhaust of Contaminated Lab fume air to outside.
Total ESP For the fan
FAN DUTY : 0.382 m/s
Item Description Size / Quantity
Unit App.
Pressure Drop
(Pascal)
Total App. Pressure
Drop (Pascal)
1
Fume Hood Total Pressure
Drop
1 No. 500 500
3
Phoenix Flow Control
Valve
1 No: 250 250
3
Manual/ Motorised
Volume Control Dampers
1 No. 30 30
4 Back draft damper 1 No. 35 35
5 Sound Attenuator 1 No. 80 80
6
Approximate Ducting
Length, 2.69 Pascal per
Metre (horizontal)
30 m.
2.69 Pascal per
Metre
80.7
7
Approximate Ducting
Length, 2.69 Pascal per
Metre (vertical )
25 m
2.69 Pascal per
Metre
67.3
8
Approximate Ducting
Length, 2.69 Pascal per
Metre ( horizontal )
49 m
2.69 Pascal per
Metre
131.8
9 Approximate Duct Fittings
20 % of Duct
pressure drop
55.9
10
Duct & Fittings safety
factor
10 % safety factor 123.10
1353.8
H-M2-45-24-HDE-07
Static Pressure Calculations
Exhaust of Contaminated Lab fume air to outside.
Total ESP For the fan
FAN DUTY : 0.382 m/s
Item Description Size / Quantity
Unit App.
Pressure Drop
(Pascal)
Total App. Pressure
Drop (Pascal)
1
Fume Hood Total Pressure
Drop
1 No. 500 500
3
Phoenix Flow Control
Valve
1 No: 250 250
3
Manual/ Motorised
Volume Control Dampers
1 No. 30 30
4 Back draft damper 1 No. 35 35
5 Sound Attenuator 1 No. 80 80
6
Approximate Ducting
Length, 2.69 Pascal per
Metre (horizontal)
30 m.
2.69 Pascal per
Metre
80.7
7
Approximate Ducting
Length, 2.69 Pascal per
Metre (vertical )
25 m
2.69 Pascal per
Metre
62.3
8
Approximate Ducting
Length, 2.69 Pascal per
Metre ( horizontal )
49 m
2.69 Pascal per
Metre
131.8
9 Approximate Duct Fittings
20 % of Duct
pressure drop
54.9
10
Duct & Fittings safety
factor
10 % safety factor 122.40
1347.1
H-M2-45-24-HDE-08
Static Pressure Calculations
Exhaust of Contaminated Lab fume air to outside.
Total ESP For the fan
FAN DUTY : 0.382 m/s
Item Description Size / Quantity
Unit App.
Pressure Drop
(Pascal)
Total App. Pressure
Drop (Pascal)
1
Fume Hood Total Pressure
Drop
1 No. 500 500
3
Phoenix Flow Control
Valve
1 No: 250 250
3
Manual/ Motorised
Volume Control Dampers
1 No. 30 30
4 Back draft damper 1 No. 35 35
5 Sound Attenuator 1 No. 80 80
6
Approximate Ducting
Length, 2.69 Pascal per
Metre (horizontal)
30 m.
2.69 Pascal per
Metre
80.7
7
Approximate Ducting
Length, 2.69 Pascal per
Metre (vertical )
25 m
2.69 Pascal per
Metre
62.3
8
Approximate Ducting
Length, 2.69 Pascal per
Metre ( horizontal )
49 m
2.69 Pascal per
Metre
131.8
9 Approximate Duct Fittings
20 % of Duct
pressure drop
54.9
10
Duct & Fittings safety
factor
10 % safety factor 122.40
1347.1
H-M2-45-24-HDE-09
Static Pressure Calculations
Exhaust of Contaminated Lab fume air to outside.
Total ESP For the fan
FAN DUTY : 0.382 m/s
Item Description Size / Quantity
Unit App.
Pressure Drop
(Pascal)
Total App. Pressure
Drop (Pascal)
1
Fume Hood Total Pressure
Drop
1 No. 500 500
3
Phoenix Flow Control
Valve
1 No: 250 250
3
Manual/ Motorised
Volume Control Dampers
1 No. 30 30
4 Back draft damper 1 No. 35 35
5 Sound Attenuator 1 No. 80 80
6
Approximate Ducting
Length, 2.69 Pascal per
Metre (horizontal)
34 m.
2.69 Pascal per
Metre
91.5
7
Approximate Ducting
Length, 2.69 Pascal per
Metre (vertical )
25 m
2.69 Pascal per
Metre
62.3
8
Approximate Ducting
Length, 2.69 Pascal per
Metre ( horizontal )
36 m
2.69 Pascal per
Metre
96.8
9 Approximate Duct Fittings
20 % of Duct
pressure drop
50.1
10
Duct & Fittings safety
factor
10 % safety factor 119.60
1315.3
H-M2-45-24-HDE-10
Static Pressure Calculations
Exhaust of Contaminated Lab fume air to outside.
Total ESP For the fan
FAN DUTY : 0.382 m/s
Item Description Size / Quantity
Unit App.
Pressure Drop
(Pascal)
Total App. Pressure
Drop (Pascal)
1
Fume Hood Total Pressure
Drop
1 No. 500 500
3
Phoenix Flow Control
Valve
1 No: 250 250
3
Manual/ Motorised
Volume Control Dampers
1 No. 30 30
4 Back draft damper 1 No. 35 35
5 Sound Attenuator 1 No. 80 80
6
Approximate Ducting
Length, 2.69 Pascal per
Metre (horizontal)
30 m.
2.69 Pascal per
Metre
80.7
7
Approximate Ducting
Length, 2.69 Pascal per
Metre (vertical )
25 m
2.69 Pascal per
Metre
62.3
8
Approximate Ducting
Length, 2.69 Pascal per
Metre ( horizontal )
36 m
2.69 Pascal per
Metre
96.8
9 Approximate Duct Fittings
20 % of Duct
pressure drop
48
10
Duct & Fittings safety
factor
10 % safety factor 118.30
1301.1
H-M2-45-24-HDE-11
Static Pressure Calculations
Exhaust of Contaminated Lab fume air to outside.
Total ESP For the fan
FAN DUTY : 0.382 m/s
Item Description Size / Quantity
Unit App. Pressure
Drop (Pascal)
Total App. Pressure
Drop (Pascal)
1
Fume Hood Total Pressure
Drop
1 No. 500 500
3
Phoenix Flow Control
Valve
1 No: 250 250
3
Manual/ Motorised Volume
Control Dampers
1 No. 30 30
4 Back draft damper 1 No. 35 35
5 Sound Attenuator 1 No. 80 80
6
Approximate Ducting
Length, 2.69 Pascal per
Metre (horizontal)
18 m.
2.69 Pascal per
Metre
48.4
7
Approximate Ducting
Length, 2.69 Pascal per
Metre (vertical )
53 m
2.69 Pascal per
Metre
142.6
8
Approximate Ducting
Length, 2.69 Pascal per
Metre ( horizontal )
32 m
2.69 Pascal per
Metre
86.1
9
Approximate Ducting
Length, 2.69 Pascal per
Metre ( horizontal )
75 m
2.69 Pascal per
Metre
201.8
10 Approximate Duct Fittings
20 % of Duct
pressure drop
95.7
11
Duct & Fittings safety
factor
10 % safety factor 146.90
1616.5
H-M2-45-24-HDE-14
Static Pressure Calculations
Exhaust of Contaminated Lab fume air to outside.
Total ESP For the fan
FAN DUTY : 0.382 m/s
Item Description Size / Quantity
Unit App.
Pressure Drop
(Pascal)
Total App. Pressure
Drop (Pascal)
1
Fume Hood Total Pressure
Drop
1 No. 500 500
3
Phoenix Flow Control
Valve
1 No: 250 250
3
Manual/ Motorised
Volume Control Dampers
1 No. 30 30
4 Back draft damper 1 No. 35 35
5 Sound Attenuator 1 No. 80 80
6
Approximate Ducting
Length, 2.69 Pascal per
Metre (horizontal)
50 m.
2.69 Pascal per
Metre
134.5
7
Approximate Ducting
Length, 2.69 Pascal per
Metre (vertical )
6.5 m
2.69 Pascal per
Metre
17.5
8
Approximate Ducting
Length, 2.69 Pascal per
Metre ( horizontal )
75 m
2.69 Pascal per
Metre
201.8
9 Approximate Duct Fittings
20 % of Duct
pressure drop
70.8
10
Duct & Fittings safety
factor
10 % safety factor 132.00
1451.6
H-M2-45-24-HDE-13
Static Pressure Calculations
Exhaust of Contaminated Lab fume air to outside.
Total ESP For the fan
FAN DUTY : 0.382 m/s
Item Description Size / Quantity
Unit App.
Pressure Drop
(Pascal)
Total App. Pressure
Drop (Pascal)
1
Fume Hood Total Pressure
Drop
1 No. 500 500
3
Phoenix Flow Control
Valve
1 No: 250 250
3
Manual/ Motorised
Volume Control Dampers
1 No. 30 30
4 Back draft damper 1 No. 35 35
5 Sound Attenuator 1 No. 80 80
6
Approximate Ducting
Length, 2.69 Pascal per
Metre (horizontal)
20 m.
2.69 Pascal per
Metre
53.8
7
Approximate Ducting
Length, 2.69 Pascal per
Metre (vertical )
4.5 m
2.69 Pascal per
Metre
12.1
8
Approximate Ducting
Length, 2.69 Pascal per
Metre ( horizontal )
12 m
2.69 Pascal per
Metre
32.3
9 Approximate Duct Fittings
20 % of Duct
pressure drop
19.6
10
Duct & Fittings safety
factor
10 % safety factor 101.30
1114.1
H-M2-45-24-HDE-03
Static Pressure Calculations
Exhaust of Contaminated Lab fume air to outside.
Total ESP For the fan
FAN DUTY : 0.575 m/s
Item Description Size / Quantity
Unit App. Pressure
Drop (Pascal)
Total App. Pressure
Drop (Pascal)
1
Fume Hood Total Pressure
Drop
1 No. 500 500
3
Phoenix Flow Control
Valve
1 No: 250 250
3
Manual/ Motorised Volume
Control Dampers
1 No. 30 30
4 Back draft damper 1 No. 35 35
5 Sound Attenuator 1 No. 80 80
6
Approximate Ducting
Length, 2.37 Pascal per
Metre (horizontal)
90 m.
2.37 Pascal per
Metre
213.3
7
Approximate Ducting
Length, 2.37 Pascal per
Metre (vertical )
50 m
2.37 Pascal per
Metre
118.5
8
Approximate Ducting
Length, 2.37 Pascal per
Metre ( horizontal )
42 m
2.37 Pascal per
Metre
99.5
9
Approximate Ducting
Length, 2.37 Pascal per
Metre ( horizontal )
35 m
2.37 Pascal per
Metre
82.9
10 Approximate Duct Fittings
20 % of Duct
pressure drop
102.8
11
Duct & Fittings safety
factor
10 % safety factor 151.20
1663.2
H-M2-45-24-HDE-12
Static Pressure Calculations
Exhaust of Contaminated Lab fume air to outside.
Total ESP For the fan
FAN DUTY : 0.844 m/s
Item Description Size / Quantity
Unit App. Pressure
Drop (Pascal)
Total App. Pressure
Drop (Pascal)
1
Fume Hood Total Pressure
Drop
1 No. 500 500
3
Phoenix Flow Control
Valve
1 No: 250 250
3
Manual/ Motorised Volume
Control Dampers
1 No. 30 30
4 Back draft damper 1 No. 35 35
5 Sound Attenuator 1 No. 80 80
6
Approximate Ducting
Length, 0.91 Pascal per
Metre (horizontal)
28 m.
0.91 Pascal per
Metre
25.5
7
Approximate Ducting
Length, 0.91 Pascal per
Metre (horizontal)
23 m
0.91 Pascal per
Metre
20.9
8
Approximate Ducting
Length, 0.91 Pascal per
Metre ( vertical )
25 m
0.91 Pascal per
Metre
22.8
9
Approximate Ducting
Length, 1.17 Pascal per
Metre ( horizontal )
15 m
1.17 Pascal per
Metre
17.6
10 Approximate Duct Fittings
20 % of Duct
pressure drop
17.4
11
Duct & Fittings safety
factor
10 % safety factor 99.90
1099.1
H-M2-45-24-HDE-21
Static Pressure Calculations
Exhaust of Contaminated Lab fume air to outside.
Total ESP For the fan
FAN DUTY : 0.634 m/s
Item Description Size / Quantity
Unit App. Pressure
Drop (Pascal)
Total App. Pressure
Drop (Pascal)
1
Fume Hood Total Pressure
Drop
1 No. 500 500
3
Phoenix Flow Control
Valve
1 No: 250 250
3
Manual/ Motorised Volume
Control Dampers
1 No. 30 30
4 Back draft damper 1 No. 35 35
5 Sound Attenuator 1 No. 80 80
6
Approximate Ducting
Length, 0.91 Pascal per
Metre (horizontal)
25 m.
0.91 Pascal per
Metre
22.8
7
Approximate Ducting
Length, 0.91 Pascal per
Metre (horizontal)
64 m
0.91 Pascal per
Metre
58.2
8
Approximate Ducting
Length, 0.91 Pascal per
Metre ( vertical )
14 m
0.91 Pascal per
Metre
12.7
9
Approximate Ducting
Length, 1.31 Pascal per
Metre ( horizontal )
13 m
1.31 Pascal per
Metre
17
10 Approximate Duct Fittings
20 % of Duct
pressure drop
22.14
11
Duct & Fittings safety
factor
10 % safety factor 102.78
1130.6
H-M2-45-24-HDE-23
Static Pressure Calculations
Exhaust of Contaminated Lab fume air to outside.
Total ESP For the fan
FAN DUTY : 0.634 m/s
Item Description Size / Quantity
Unit App. Pressure
Drop (Pascal)
Total App. Pressure
Drop (Pascal)
1
Fume Hood Total Pressure
Drop
1 No. 500 500
3
Phoenix Flow Control
Valve
1 No: 250 250
3
Manual/ Motorised Volume
Control Dampers
1 No. 30 30
4 Back draft damper 1 No. 35 35
5 Sound Attenuator 1 No. 80 80
6
Approximate Ducting
Length, 0.91 Pascal per
Metre (horizontal)
17.5 m.
0.91 Pascal per
Metre
15.9
7
Approximate Ducting
Length, 0.91 Pascal per
Metre (horizontal)
65 m
0.91 Pascal per
Metre
59.2
8
Approximate Ducting
Length, 0.91 Pascal per
Metre ( vertical )
14 m
0.91 Pascal per
Metre
12.7
9
Approximate Ducting
Length, 1.31 Pascal per
Metre ( horizontal )
13 m
1.31 Pascal per
Metre
17
10 Approximate Duct Fittings
20 % of Duct
pressure drop
20.96
11
Duct & Fittings safety
factor
10 % safety factor 102.08
1122.8
H-M2-45-24-HDE-22
Static Pressure Calculations
Exhaust of Contaminated Lab fume air to outside.
Total ESP For the fan
FAN DUTY : 0.844 m/s
Item Description Size / Quantity
Unit App.
Pressure Drop
(Pascal)
Total App. Pressure
Drop (Pascal)
1
Fume Hood Total Pressure
Drop
1 No. 500 500
3
Phoenix Flow Control
Valve
1 No: 250 250
3
Manual/ Motorised Volume
Control Dampers
1 No. 30 30
4 Back draft damper 1 No. 35 35
5 Sound Attenuator 1 No. 80 80
6
Approximate Ducting
Length, 0.91 Pascal per
Metre (horizontal)
19 m.
0.91 Pascal per
Metre
17.3
7
Approximate Ducting
Length, 0.18 Pascal per
Metre (horizontal)
3 m
0.18 Pascal per
Metre
0.5
8
Approximate Ducting
Length, 0.65 Pascal per
Metre ( horizonta )
81 m
0.65 Pascal per
Metre
52.7
9
Approximate Ducting
Length, 0.65 Pascal per
Metre ( horizontal )
66 m
0.65 Pascal per
Metre
42.9
10
Approximate Ducting
Length, 0.65 Pascal per
Metre ( horizontal )
13 m
0.65 Pascal per
Metre
8.5
11
Approximate Ducting
Length, 0.65 Pascal per
Metre (vertical )
33 m
0.65 Pascal per
Metre
21.5
12 Approximate Duct Fittings
20 % of Duct
pressure drop
28.7
13
Duct & Fittings safety
factor
10 % safety factor 106.71
1173.8
H-M2-45-24-HDE-16
Static Pressure Calculations
Exhaust of Contaminated Lab fume air to outside.
Total ESP For the fan
FAN DUTY : 0.951 m/s
Item Description Size / Quantity
Unit App.
Pressure Drop
(Pascal)
Total App. Pressure
Drop (Pascal)
1
Fume Hood Total Pressure
Drop
1 No. 500 500
3
Phoenix Flow Control
Valve
1 No: 250 250
3
Manual/ Motorised Volume
Control Dampers
1 No. 30 30
4 Back draft damper 1 No. 35 35
5 Sound Attenuator 1 No. 80 80
6
Approximate Ducting
Length, 0.91 Pascal per
Metre (horizontal)
27 m.
0.91 Pascal per
Metre
24.6
7
Approximate Ducting
Length, 0.95 Pascal per
Metre (horizontal)
52 m
0.95 Pascal per
Metre
49.4
8
Approximate Ducting
Length, 0.95 Pascal per
Metre ( horizonta )
25 m
0.95 Pascal per
Metre
23.8
9
Approximate Ducting
Length, 0.95 Pascal per
Metre ( horizontal )
37 m
0.95 Pascal per
Metre
35.2
10
Approximate Ducting
Length, 0.95 Pascal per
Metre ( vertical )
50 m
0.95 Pascal per
Metre
47.5
11
Approximate Ducting
Length, 0.81 Pascal per
Metre (horizontal )
13 m
0.81 Pascal per
Metre
10.5
12 Approximate Duct Fittings
20 % of Duct
pressure drop
38.2
13
Duct & Fittings safety
factor
10 % safety factor 112.42
1236.6
H-M2-45-24-HDE-19
Static Pressure Calculations
Exhaust of Contaminated Lab fume air to outside.
Total ESP For the fan
FAN DUTY : 0.899 m/s
Item Description Size / Quantity
Unit App.
Pressure Drop
(Pascal)
Total App. Pressure
Drop (Pascal)
1
Fume Hood Total Pressure
Drop
1 No. 500 500
3
Phoenix Flow Control
Valve
1 No: 250 250
3
Manual/ Motorised Volume
Control Dampers
1 No. 30 30
4 Back draft damper 1 No. 35 35
5 Sound Attenuator 1 No. 80 80
6
Approximate Ducting
Length, 1.93 Pascal per
Metre (horizontal)
10.5 m.
1.93 Pascal per
Metre
20.3
7
Approximate Ducting
Length, 1.93 Pascal per
Metre (vertical)
23 m
1.93 Pascal per
Metre
44.4
8
Approximate Ducting
Length, 1.93 Pascal per
Metre ( horizontal )
35 m
1.93 Pascal per
Metre
67.6
9
Approximate Ducting
Length, 1.93 Pascal per
Metre ( horizontal )
30 m
1.93 Pascal per
Metre
57.9
10
Approximate Ducting
Length, 1.93 Pascal per
Metre ( vertical )
27 m
1.93 Pascal per
Metre
52.1
11
Approximate Ducting
Length, 1.31 Pascal per
Metre (horizontal )
13 m
1.31 Pascal per
Metre
17
12 Approximate Duct Fittings
20 % of Duct
pressure drop
51.8
13
Duct & Fittings safety
factor
10 % safety factor 120.61
1326.7
H-M2-45-24-HDE-18
Static Pressure Calculations
Exhaust of Contaminated Lab fume air to outside.
Total ESP For the fan
FAN DUTY : 1.864 m/s
Item Description Size / Quantity
Unit App.
Pressure Drop
(Pascal)
1 Grille (450x600) 1 No. 50
2
350x200 Ducting, 0.32
Pa/m
6 m
0.32 Pascal per
Metre
3
Phoenix Flow Control
Valve
1 No: 250 Pascal
4 Sound Attenuator 1 No. 80
5
200x150 Ducting, 0.95
Pa/m
4.5 m
0.95 Pascal per
Metre
5
300x250 Ducting, 0.47
Pa/m
1.6 m
0.47 Pascal per
Metre
6 300x250 Ducting, 0.8 Pa/m 95 m
0.8 Pascal per
Metre
7
Motorised Fire Dampers/
Fire damper
4 No. 30 Pascal
8
300x250 Ducting, 0.93
Pa/m
4 m
0.93 Pascal per
Metre
8 300x250 Ducting, 1.5 Pa/m 5 m
1.5 Pascal per
Metre
7 Motorised Fire Dampers 1 No. 30 Pascal
8 300x250 Ducting, 2.2 Pa/m 2.5 m
2.2 Pascal per
Metre
8 300x250 Ducting, 2.9 Pa/m 11 m
2.9 Pascal per
Metre
8
400x300 Ducting, 1.87
Pa/m
4 m
1.87 Pascal per
Metre
8 400x300 Ducting, 2.3 Pa/m 2 m
2.3 Pascal per
Metre
8 400x300 Ducting, 3.2 Pa/m 20 m
3.2 Pascal per
Metre
8
500x300 Ducting, 2.88
Pa/m (vertical)
14 m
2.88 Pascal per
Metre
H-PL-45-21-HDE-03A / 03B
Static Pressure Calculations
Exhaust of Contaminated Lab fume air to outside.
8
500x300 Ducting, 2.88
Pa/m (horizontal diversion)
25 m
2.88 Pascal per
Metre
8
500x300 Ducting, 2.88
Pa/m (vertical)
32.5 m
2.88 Pascal per
Metre
8
500x300 Ducting, 2.88
Pa/m (horizontal)
13 m
2.88 Pascal per
Metre
8
400x400 Ducting, 2.88
Pa/m (horizontal)
7 m
2.88 Pascal per
Metre
NRD 1 No: 35 Pascal
12 Approximate Duct Fittings
20 % of Duct
pressure drop
13
Duct & Fittings safety
factor
10 % safety factor
Total ESP For the fan
Total App. Pressure
Drop (Pascal)
50
1.9
250
80
4.3
0.8
76
30
3.7
7.5
30
5.8
31.9
7.4
4.6
64
40.32
H-PL-45-21-HDE-03A / 03B
Static Pressure Calculations
Exhaust of Contaminated Lab fume air to outside.
72
93.6
37.5
20.2
35
94.3
104.08
1144.9
Sn Fan Ref. Location Flow Rate (m/s)
1
H-M2-45-24-HDE-01 Roof 0.382
2
H-M2-45-24-HDE-02 Roof 0.382
3
H-M2-45-24-HDE-03 Roof 0.382
4
H-M2-45-24-HDE-04 Roof 0.382
5
H-M2-45-24-HDE-05 Roof 0.382
6
H-M2-45-24-HDE-06 Roof 0.382
7
H-M2-45-24-HDE-07 Roof 0.382
8
H-M2-45-24-HDE-08 Roof 0.382
9
H-M2-45-24-HDE-09 Roof 0.382
10
H-M2-45-24-HDE-10 Roof 0.382
11
H-M2-45-24-HDE-11 Roof 0.382
12
H-M2-45-24-HDE-12 Roof 0.575
13
H-M2-45-24-HDE-13 Roof 0.382
14
H-M2-45-24-HDE-14 Roof 0.382
15
H-M2-45-24-HDE-15 Roof
0.741
16
H-M2-45-24-HDE-16 Roof
0.846
17
H-M2-45-24-HDE-17 Roof
0.951
18
H-M2-45-24-HDE-18 Roof
0.899
19
H-M2-45-24-HDE-19 Roof
0.951
20
H-M2-45-24-HDE-20 Roof
1.269
21
H-M2-45-24-HDE-21 Roof
0.846
22
H-M2-45-24-HDE-22 Roof
0.634
23
H-M2-45-24-HDE-23 Roof
0.634