EN 15650

ROUND FIRE DAMPER


EUROPEAN STANDARD
Test EN 1366-2
Classification EN 13501-3
WH23 SERIES - 300Pa
CE Certification
fax 049 9317070 tel 049 9303516
www.mp3-italia.it
Via G. La Pira 9 A/B
Cert. N 1812-CPD-1024 2012
35012 Camposampiero PD Italia

ROUND FIRE DAMPER
EUROPEAN STANDARDS EN 1366-2 EN 13501-3
CE MARKING ACCORDING TO EN 15650
WH23
SERIES
ORGANIZATION
TECHNOLOGY
TESTING
WH23 13.01_eng.xlsx WH23-2

FIRE RESISTANCE CLASS
WH23
SERIES
ROUND FIRE DAMPER
EUROPEAN STANDARDS EN 1366-2 EN 13501-3
CE MARKING ACCORDING TO EN 15650
Overview
EI 120 S EI 90S EI 60 S
(300Pa) (300Pa)
from 100
(300Pa)
from 100
to 315
from 100
to 315
from 100
to 315
Minimum distances
between dampers
200mm
from the ceiling / side wall
75mm
between dampers
ve (i o )
200mm
Rigid wall
Minimum thickness 100mm
Minimum density 550Kg/m
Support
Standard plasterboard wall
Minimum thickness 100mm
New safety tools
The circular WH23 series fire dampers have been designed
for air distribution within buildings combining maximum
safety in the prevention of propagation of fires and with
aeraulic and acoustic performances even in the smallest
foreseen dimensions.
They guarantee perfect isolation from heat and a complete air
tight seal for both hot and cold smoke, as shown from the
numerous tests carried out in accordance with EN 1366-2 and
then classifications obtained in accordance with EN 13501-3.
The WH23 series circular fire dampers are a fundamental
safety tool against the propagation of fires, heat transfer and
spread of smoke and harmful gasses.
Prevention of indirect damages
The patented WH23 circular fire dampers guarantee a perfect
seal both when cold and hot during all the fire test with a
depression of 300 Pa as foreseen by EN 1366-2 (article 10.3)
standard.
By connecting the fire dampers to the fire and smoke alarm
system, it is possible to anticipate the closure of the damper
compared to the direct reaction resulting from the propagation
of fumes and gassed generated by combustion with buildings.
ve = E=
ho= I=
S=
Pa= Pascal of depression
ho (i o ) 75mm
from 100
to 315
from
100
to 315
from 100
to 315
ho (i o )
Ceiling between dampers
from 100
to 315
200mm
from 100
to 315
from 100
to 315
Horizontal installation thermal insulation
(i o ) = Origin of fire not relevant Smoke seal
Vertical installation
Carreaux de Pltre/gypsum blocks
Minimum thickness 100mm
Minimum density 650Kg/m
Minimum thickness 70mm
ve (i o )
Ceiling
Minimum thickness 150mm
Minimum density 650Kg/m
Cert. N 1812-CPD-1024 2012
200mm
from the ceiling / side wall
75mm
integrity
from the side walls
75mm
between dampers
200mm
from the side walls
75mm
between dampers
200mm
from the ceiling / side wall
from 100
to 315
from 100
to 315
Light wall made with plaster blocks
Minimum thickness 100mm
Rock wool minimum density 40Kg/m
ve (i o )
WH23 13.01_eng.xlsx WH23-3

ROUND FIRE DAMPER
EUROPEAN STANDARDS EN 1366-2 EN 13501-3
CE MARKING ACCORDING TO EN 15650
WH23
SERIES
Possible installations
When installing the dampers, a minimum distance of 200mm between dampers must be kept as established by EN
1366-2 (article 13.5)
In all wall installations, a minimum distance of 75mm must be kept from the ceiling, pavement and side walls.
In all ceiling installations, a minimum distance of 75mm will also have to be kept from the side walls, as established
in EN 1366-2 (article 13.5).
WH23 13.01_eng.xlsx WH23-4

ROUND FIRE DAMPER
EUROPEAN STANDARDS EN 1366-2 EN 13501-3
CE MARKING ACCORDING TO EN 15650
WH23
SERIES
Overview
Tests carried out
Repeated stress tests for damper open-close cycles have
been carried out according to standards EN 1366-2 (article
10.2) and EN 15650 (attachment C)
50 cycles with versions with mechanical release;
300 cycles with versions with magnetic release;
10.000 cycles with versions with servomotor;
Air tight seal tests for cold fumes with 300 Pa depression
have been carried out on the smallest and biggest dampers,
in accordance with the EN 1366-2 standard (article 6.1);
Various fire tests have been carried out on the largest damper
to reproduce all the possible installations foreseen by then
1366-2 standard (articles 6.2 and 6.3).
Air tight seal test for hot fumes maintaining a depression of
300 Pa through the duration of the fire test;
Temperature controlled during the fire test on the sides of
the frame, on the extraction duct, on the supporting wall
close to all the perimeter of the damper with certification
that none of the points measures more that 180 C, as
indicated by the EN 1363-1 standard (article 11.3).
Test on the thermal fuse which should guarantee the
closure of the damper within two minutes from the start of
the fire test as established by EN 1366-2 (article 10.4.6).
The execution of the fire test on the largest size and the air
seal test against cold fumes on the smallest and largest
Materials
Duct made in galvanized carbon steel or stainless steel;
blade made from refractory material;
gasket for cold fumes made from silicone;
thermal expanding graphite gasket.
Excellent aeraulic and acoustic performances .
The patented WH23 circular fire dampers show minimum
pressure loss and noise power levels . They allow an air speed
up to 12 m/s.
Quick and easy installation
The prime objective during the planning of the WH23
dampers, was to maximum the ease and simplicity of
installation and sealing.
Opening and Closing Mechanisms
The release of the damper blade occurs by means of a thermal
fuse with certified melting point of 70 C or 72 C ( for
versions with servomotor).
The pre-loaded spring mechanism conforms to standard UNI
103565.
Electrical accessories and remote control
The air seal for cold fumes with 300Pa depression makes it
particularly interesting with the possibility of anticipating the
dampers allows to extend the test result to all the
intermediate sizes, as established by EN 1366-2 (article 6.1).
Again, on the basis of the above standard (article 13.6), the
test results on one type of support (wall or ceiling) are
extended to supports with greater thickness and /or greater
density.
Minimum distances
In cases where two or more dampers are to be installed in
the same wall, a minimum distance of at least 200mm
must be kept between dampers, as established in EN
1366-3 (article 13.5)
For the installation of each damper, a minimum distance
of 75mm will need to be kept from the ceiling, pavement
and side walls, as established by EN1366-2 (article 13.5).
Obligations of the installer
The certification of the fire dampers is strictly linked to the
installation made on the dampers themselves as established
by EN 1366-2 (article 7.1).
The installer is held to observe scrupulously the installation
procedures provided by the manufacturer (both for the
method and the materials to be used) described in the
present technical data sheet and which reflect the
installations made during the fire test.
closure of the damper in relation to the action of heat on the
thermal fuse (which must always be present in any case) by
using an electrical remote control generated from the fire alarm
system or from the smoke detection system.
In fact, in the event of fire, danger to personnel present in the
building derives more frequently from smoke intoxication
rather than heat generated from the fire.
This remote control may be done in different ways:
by adding an electromagnet on the release mechanism, when
the damper closes accidentally (black out, failure, fault in
alarm system), control occurs manually;
by using a servomotor, when reopening the damper as a result
of an accidental closure (black out, failure, fault in alarm
system), control occurs automatically when power is restored.
In any case, the closing of the damper always occurs using a
pretension spring in accordance with UNI 10365 (article 4.1)
therefore guaranteeing the closure in the event of fire even in
the absence of power supply.
Within the limits of 300Pa pressure, the rectangular WK23
fire dampers fitted with servomotor, can therefore also be used
as intercepting dampers.
WH23 13.01_eng.xlsx WH23-5

Version with electromagnetic release mechanism and motorized rearming.
In addition to the thermal fuse, it allows to anticipate the closure
of the damper using an electrical signal, generated from the alarm system.
Rearming is made using an electrical motor.
Two microswitches, closed/open damper supplied as standard.
ROUND FIRE DAMPER
EUROPEAN STANDARDS EN 1366-2 EN 13501-3
CE MARKING ACCORDING TO EN 15650
WH23
SERIES
Versions - Accessories
Version with integrated mechanical release mechanism
with electromagnet.
In addition to the thermal fuse, it allows to anticipate the closure
of the damper using an electrical signal, generated from the alarm system.
Rearming is made manually.
Magnet for remote control
Interruption version - closing signal at power cut off
Version with mechanical release mechanism and manual rearming.
Two microswitches, closed/open damper on request
Two additional microswitches closed/open damper on request.
Two microswitches, closed/open damper supplied as standard.
* not compatible with UNI 10365 (article 4.3)
Interruption version closing signal at power cut off
24 V DC power supply
Input version - closing signal by supplying power *
24V DC power supply
In the event of accidental closure of the damper, reopening is made manually.
Electrical board for magnet management, Interruption or Input versions
complete with two microswitches open/closed damper
Electrical board to manage to microswitches open/close damper
Versions without electromagnet: main microswitches
Versions with electromagnet: additions microswitches
Siemens type servomotor unit
Remote close signal by interrupting power supply.
GNA 126.1E/T12* 24V AC/DC power supply - 2 microswitches - 72C thermal fuse
GNA 326.1E/T12* 230V AC power supply - 2 microswitches - 72C thermal fuse
In the event of accidental closure of the damper, reopening occurs automatically
when power is restored.
Wiring instructions
Connection of the electrical accessories must always be made by qualified electricians and expert.
The detailed technical data sheets of the servomotors are available from our Technical Office.
WH23 13.01_eng.xlsx WH23-6

ROUND FIRE DAMPER
EUROPEAN STANDARDS EN 1366-2 EN 13501-3
CE MARKING ACCORDING TO EN 15650
WH23
SERIES
Overview
1
2
3
4
5
6
7
8
9
10
11
12
13
S
250
315
==
==
==
==
17
49,5
125
160
200
100
Case made from galvanized carbon sheet steel
Thermal labyrinth
External thermal expanding graphite gasket on outside of casing
Damper blade made from refractory material
Blade pivot
External thermal expanding graphite gasket
Protecting case
Graphite thermal expanding gasket on the inside on the case to seal the blade once closed
Thermal release mechanism (thermal fuse)
Blade actioning mechanism
Manual control actioning system (test button)
Manual rearming lever
Closed damper mechanical block
WH23 13.01_eng.xlsx WH23-7

ROUND FIRE DAMPER
EUROPEAN STANDARDS EN 1366-2 EN 13501-3
CE MARKING ACCORDING TO EN 15650
WH23
SERIES
Rigid vertical walls
EI 120 S
Installation within vertical rigid walls
The WH23 rectangular fire dampers, classified EI 120S within rigid
vertical walls, guarantee insulation to fire and heat up to 120 minutes
only if the installed within walls with a fire resistance classification at
least REI 120 and a minimum thickness of 100mm.
This said, the degree of fire resistance will be that of the wall, being the
weaker of the two.
Lab tests have been carried out with a 100mm thick aerated concrete
blocks with density 550Kg/m. On the basis of EN 1366-2 (article 13.6)
the outcomes of the tests are valid also for wider and/or more dense walls.
The WH23 fire dampers can therefore also be used within brick walls
with a minimum thickness of 100mm.
1. Wall opening
A round opening must be provided in the wall with a diameter 25mm
greater than the nominal diameter of the damper. For concrete
breezeblock or brick walls, it is recommended to use a reinforcing beam
above the opening.
2. Damper positioning
Position the damper so that the side with the closing mechanism
protrudes from the wall by 200mm.
Furthermore, the double test (with mechanism inside and outside the fire
area) has demonstrated that there is no preferential direction of
installation of the damper , nor in relation to the direction of the air flow
in the duct or the side with higher probability of exposure to fire, as
indicated too in EN 1366-2 (article 6.2).
3. Filling
Fill the space around the damper using mortar suitable for wall with fire
resistance class M10 or higher.
WH23 13.01_eng.xlsx WH23-8

ROUND FIRE DAMPER
EUROPEAN STANDARDS EN 1366-2 EN 13501-3
CE MARKING ACCORDING TO EN 15650
WH23
SERIES
light plasterboard vertical wall
EI 60 S
Installation within light walls (plasterboard)
The WH23 series EI 60 S classified fire damper within light
vertical walls (plasterboard) guarantee fire and heat isolation for 60
minutes only if installed within walls with a fire resistance
classification at least EI 60 and at least 100mm thick.
This said, the degree of fire resistance will be that of the wall, being
the weaker of the two.
Lab tests have been carried out with a wall 100mm thick with two
plasterboard layers each 12.5mm thick and insulated with rock wool
of density 40 Kg/m. On the basis of EN 136-2 (article 13.6) the test
results are extended to walls with greater thickness and/or greater
density.
1. Wall opening
A rectangular opening must be provided in the wall with a perimeter
composed by metal profiles suitable for plasterboard (minimum
thickness 0.6mm) with one side 50mm greater than the nominal
diameter of the damper.
2. Damper positioning
Position the damper so that the side with the closing mechanism
protrudes from the wall by 200mm.
Furthermore, the double test (with mechanism inside and outside the
fire area) has demonstrated that there is no preferential direction of
installation of the damper , nor in relation to the direction of the air p
flow in the duct or the side with higher probability of exposure to
fire, as indicated too in EN 1366-2 (article 6.2).
3. Filling
Fill the space around the damper using rock wool with density
100Kg/m.
Cover the rock wool by applying a layer of plasterboard on each face
of the wall, for a total minimum thickness of 12.5mm on each side.
The result must be a frame with a side 215mm greater than the
nominal diameter of the damper.
WH23 13.01_eng.xlsx WH23-9

ROUND FIRE DAMPER
EUROPEAN STANDARDS EN 1366-2 EN 13501-3
CE MARKING ACCORDING TO EN 15650
WH23
SERIES
Light vertical modular walls made of plaster,
type "carreaux de pltre"
EI 90 S
Installation within light modular walls (plaster boards) "carreaux de
pltre"
The WH23 EI 90S classified fire dampers installed within aerated
light vertical walls "carreaux de pltre" guarantee fire and heat
isolation for 90 minutes only if installed within walls with a fire
resistance at least EI 90 and a minimum thickness of 70mm.
This said, the degree of fire resistance will be that of the wall, being the
weaker of the two.
1. Wall opening
A round opening must be provided in the wall with a diameter 25mm
greater than the nominal diameter of the damper.
2. Damper positioning
Position the damper so that the side with the closing mechanism
protrudes from the wall by 200mm.
Furthermore, the double test (with mechanism inside and outside the
fire area) has demonstrated that there is no preferential direction of
installation of the damper , nor in relation to the direction of the air flow
in the duct or the side with higher probability of exposure to fire, as
indicated too in EN 1366-2 (article 6.2).
3. Filling
Fill the space around the damper by using plaster butty.
WH23 13.01_eng.xlsx WH23-10

ROUND FIRE DAMPER
EUROPEAN STANDARDS EN 1366-2 EN 13501-3
CE MARKING ACCORDING TO EN 15650
WH23
SERIES
Ceiling with 150mm thickness
EI 120 S
Installation within ceiling
The WH23 series fire dampers certified EI 120S installed within a
concrete ceilings guarantee isolation to fire and heat up to 120 minutes
only if within concrete floors with a fire resistance classification of at
least REI 120 and at least 150mm thick.
This said, the degree of fire resistance will be that of the wall, being the
weaker of the two.
Lab tests have been carried out in a concrete floor 150mm thick and with
650Kg/m density. On the basis of EN 1366-2 standard (section 13.6) the
outcomes of the tests are valid also for thicker and/or more dense
ceilings.
1. Ceiling opening
A round opening must be provided in the wall with a diameter 25mm
greater than the nominal diameter of the damper.
2. Damper positioning
Position the damper so that the side with the closing mechanism
protrudes from the wall by 190mm.
Furthermore, the double test (with mechanism inside and outside the
fire area) has demonstrated that there is no preferential direction of
installation of the damper , nor in relation to the direction of the air flow
in the duct or the side with higher probability of exposure to fire, as
indicated too in EN 1366-2 (article 6.2).
ll 3. Filling
Fill the space around the damper using mortar suitable for wall with fire
resistance class M10 or higher.
WH23 13.01_eng.xlsx WH23-11

ROUND FIRE DAMPER
EUROPEAN STANDARDS EN 1366-2 EN 13501-3
CE MARKING ACCORDING TO EN 15650
WH23
SERIES
Ceiling with 100mm thickness
EI 90 S
Installation within ceiling
The WH23 series fire dampers certified EI 90S installed within a
concrete ceilings guarantee isolation to fire and heat up to 90 minutes
only if within concrete floors with a fire resistance classification of at
least REI 90 and at least 100mm thick.
This said, the degree of fire resistance will be that of the wall, being the
weaker of the two.
Lab tests have been carried out in a concrete floor 150mm thick and with
650Kg/m density. On the basis of EN 1366-2 standard (section 13.6) the
outcomes of the tests are valid also for thicker and/or more dense ceilings.
1. Ceiling opening
A round opening must be provided in the wall with a diameter 25mm
greater than the nominal diameter of the damper.
2. Damper positioning
Position the damper so that the side with the closing mechanism protrudes
from the wall by 190mm.
Furthermore, the double test (with mechanism inside and outside the fire
area) has demonstrated that there is no preferential direction of
installation of the damper , nor in relation to the direction of the air flow in
the duct or the side with higher probability of exposure to fire, as indicated
too in EN 1366-2 (article 6.2).
3. Filling
ll h d h d bl f ll h f Fill the space around the damper using mortar suitable for wall with fire
resistance class M10 or higher.
WH23 13.01_eng.xlsx WH23-12

ROUND FIRE DAMPER
EUROPEAN STANDARDS EN 1366-2 EN 13501-3
CE MARKING ACCORDING TO EN 15650
WH23
SERIES
Technical Data
Available Front Net Maximum
diameters section section air flow
mm m m m/h
100
125 0,0123 0,0094 550
0,0079 0,0056 350
200 0,0314 0,0267 1350
160 0,0201 0,0163 850
250 0,0491 0,0431 2100
315 0,0779 0,0703 3350
WH23 - 100
WH23 - 125
WH23 - 160
0 500 1000 1500 2000 2500 3000 3500 4000
WH23 - 200
WH23 - 250
WH23 - 315
Air flow (m/h)
WH23 13.01_eng.xlsx WH23-13

ROUND FIRE DAMPER
EUROPEAN STANDARDS EN 1366-2 EN 13501-3
CE MARKING ACCORDING TO EN 15650
WH23
SERIES
Technical data
40
50
60
70
80
90

P

(
P
a
)
Pressuredropandsoundpower
4000
-22 -15
63
Corrections to estimate the sound spectrum in octave band
Values to add to the noise pressure in dBa
8000
frontal speed
1000 250
Frequency Hz
4 -4 -9
5
-4 -16
-19 17
-12
-20 -4
9 20
9
12
2000 125
7
-15
-9 -10
-9 5
m/s
6 15
500
-10
8
0
10
20
30
0 1 2 3 4 5 6 7 8 9 10 11 12 13
V (m/s)
WH23 13.01_eng.xlsx WH23-14

WH
Size
WH 23 VPS 200
VPB for Belimo motor BLF 24V
DPB for Belimo motor BLF 230V
23
VPS for Siemens motor GNA 24V
DPS for Siemens motor GNA 230V
25mm damper blade - 300 Pa air seal
ROUND FIRE DAMPER
EUROPEAN STANDARDS EN 1366-2 EN 13501-3
CE MARKING ACCORDING TO EN 15650
WH23
SERIES
Ordering codes
FIRE DAMPERS WITH MOTORIZED REARMING
Circular fire damper
B
M
S0
S2
M0
MI
(*) Only version "B"
Size
WH
WH 23 M S2 MR 200
Mechanical control with magnet
MR
Mechanical control
Without end run microswitch (*)
With two end run microswitches
Without Magnet (*)
24 V DC Interruption magnet
24V DC Input magnet
FIRE DAMPERS WITH MANUAL REARMING
23
Circular fire damper
25mm damper blade - 300 Pa air seal
WH23 13.01_eng.xlsx WH23-15