Vous êtes sur la page 1sur 1

Voltage ratio

GBE S.p.A. TEST REPORT


Order Customer
Type Serial Number Phase KVA
Voltage ratio (V)
Connection
Currents
Insulation Class Temperature Class
TRAFOTECH
TS3R07.1600 9877.1/2 -- (OCT29) 1.600
5.700
F F 100 C 100 C
162,06 2.309,40 -
Dyn5
400 2 2,50 - % / - 50 Hz
Pos. Theoretical U Measured V Measured W Measured
Insulation test
Voltage test applied to the primary against secondary and ground:
20000 V 60Sec
Voltage test applied to the secondary against primary and ground:
3000 V t = 60Sec
Test voltage t = Result: POSITIVE
Result: POSITIVE Test voltage
Measurement of no-load loss and current
Winding supply : Frequency
Induced voltage test
Supplied voltage 800 V t = 60 Sec Result: POSITIVE f = 100 Hz
50 Hz
Voltage K = 1
VMuv
Note
VMuw VMvw VMm Iu Iv Iw Averag W tot
Current K 1 1 K W =
X
404,11
360,22
439,66
395,04
359,87
441,25
403,17
361,56
440,58
400,77 6,08 7,36 6,98
4,37 5,70 4,22 360,55
440,50 20,98 22,36 21,45
6,80
4,76
21,60 3.806,74
1.987,56
2.641,32
Winding resistance measurement, Voltamperometric method
1V1W 1,6540 14,0450 0,1178 14,9883 0,6252 9,3713 2U2W
Primary winding Secondary winding 400 V 5.700 V
0,6272 14,9882 9,4005 2U2V 0,1183 14,1000 1,6680 1U1W
Terminals Volt Amp. Ohm mVolt Amp. mOhm Terminals
1U1V 1,6510 14,0020 0,1179 2V2W 9,4211 14,9882 0,6286
0,1180 Ohm 0,6270 mOhm
t. amb. : 20 C
Measurement of short circuit impedence and load loss
Voltage K = 1 Current K 1 K W = 1
Note
427,21 426,54 421,36 425,04 163,22 162,45 159,48 161,72 11.345,89
50 Hz Frequency Winding supply :
W tot Averag Iw Iv Iu Vm Vvw Vuw Vuv
Determination of short circuit impedance and load loss
Ambient temperature
Ratio Primary winding Secondary winding
20,3 C Reference temperature 120 C K Temp 1,39 1,39 /
Vcc at rated current
A Current 162,06 A
425,95 V
ZIp% = (VCC/VNcc)*100 = 7,47 %
Pcc at rated current 11394,6 W
RIp % (WCup/PN)*100 0,71 %
XIp % = ((ZIp%)-(RIp%)) 7,44 %
RIn % = RIp % * KTemp 0,98 %
ZIn % = ((XIn%) + (RIn%)) = 7,51 %
XIn% = XIp% 7,44 %
Load losses
Ohmic losses primary windings
Ohmic losses secondary
Additional losses
6.413,4 W
6.887,7 W
1220,8 W
Voltage drop (%)
load Cos
5,349 %
3,984 %
2,623 %
99,086 %
98,922 %
98,855 %
99,012 %
98,656 % 100 %
75 %
50 % 99,204 %
Efficiency
=0,8 Cos =1 Cos =0,8 Cos =1
1,097 %
0,772 %
0,480 %
14680,0 W
Partial discharge
U V W Phase
Pre-stressing voltage V
Test voltage V
Partial discharge pC
3
720,0 720,0 720,0
520,0 520,0 520,0
< 10 < 10 < 10
5.700 V
/
400 V
Note
(20,3 C) (20,3 C)
Note
Measured at 400,0 V

Customer
10/03/2014 Date
/
-
/
The transformer is delievered with the following ratio 5.700 / 400 V
I0 = 0,29 % P0 = 2641,32 W
Average resistance
Average resistance
Average resistance
Average resistance
Copper Copper
Secondary
Primary
Tests carried out according to IEC 60726 and IEC 60076 Standards
Instrument used Norma D5255 and Norma 4000

/
Manufacturer