Calculation sheet
STRUCTURALREPORT
SOLARLIGHTINGPOOLFOOTING
DESIGN BRIEF
Design a footing of 6.00 m high free-standing solar lighting pole located in a Jebel Ali Village, on a
gentle slope and shielded. The footing is pier will be set in insitu sandy- material, with cautious
estimates of the means of density 20 kN/m3, internal angle of friction 30 and cohesion 5.0 kPa.
Ultimate design gust wind speed
Vhu = 45.0 m/s = 160 km/h
Ultimatefreestreamgustdynamicwindpressure
qzu = 0.0006Vzu
2
= 0.0006 x 45.0
2
= 1.215 kPa
Ultimatenetwindpressureonfreestandingpole
pnu = Cfig qzu
= 1.20 x 1.215
=1.46kPa
PIER DETAILS
Total depth of pier
D = 1. 00 m embedded, 1.20 m total depth
Pier diameter
dpier = 0.50 m
Note
Thefollowingcalculationsconvertacircularpiertoanequivalentsquarepierofthesameoverallcross
sectionalarea.Byusingthiseffectivesquaresection,wecanhaveconfidenceinthecalculatedweightof
pier,andtheeffectivehorizontalleverarmsfromanassumedpointofrotation.
Reinforcement
Modulus of elasticity
E = 1,000 fm
= 1,000 x 8.06
=8,060MPa
Area of main reinforcment
Ast = Nt(3.1416 Ddia.t2/4) (approx)
= 1 x 3.1416 x 12
2
/4
= 160 mm2
Design area of main tensile reinforcement
Asd = min [0.29(1.3fm) bd/fsy, Ast]
= min [(0.29 x 1.3 x 8.06 x 760 x 95 / 500), 200]
= min [438, 160]
= 160 mm2