Vous êtes sur la page 1sur 89

Ki ngf i sher PLUS+

Superseded Hardware Reference Manual


7.1


Kingfisher PLUS+Hardware Manual 6.0 www.cse-semaphore.com/mykingfisher Page 2

Document Information
Document Control
Copyright
Copyright CSE-Semaphore (Australia) Pty Ltd. ABN 35 006 805 910
www.cse-semaphore.com/mykingfisher, info.kingfisher@cse-semaphore.com
Intellectual Property
CSE-Semaphore asserts ownership of the intellectual property contained herein and
claims copyright and authorship. CSE-Semaphore has and retains all rights of
ownership and use of the material herein in its on-going business.
Licence
This document is provided to the intended recipient(s) under a non-exclusive licence.
This licence permits Fair Use of the document for operational requirements, without
payment of further royalty or licence fee. Fair Use includes making copies of the
document for operational, backup and archive purposes. Fair Use includes distributing
copies of the document to other entities for the purposes of their performing related
works for the intended recipient(s). Fair Use does not include creating, selling or
distributing copies of the document for other purposes. All copies must retain this
statement of Intellectual Property and Copyright.

Revision History
Rev. Date Remarks
6.11 2/8/2011 Changed order of some chapters. Added PSU-4 power supply (higher power version of the PSU-3).
PS-xx temperature sensor wires are now red with a black stripe.
Added PS-22, IO-5 and MC-31 modules.



Kingfisher PLUS+Hardware Manual 6.0 www.cse-semaphore.com/mykingfisher Page 3

Contents


1.1 PS-1/PSU-1: AC Supply Input ............................................................................................... 6
PS-1 Battery Charging States .............................................................................................................. 7
PS-1/PSU-1 Specifications .................................................................................................................. 8
Output Characteristics ......................................................................................................................... 9
PS-1/PSU-1 Block Diagram ................................................................................................................. 9
PS-1/PSU-1 Module LEDs ................................................................................................................. 10
PS-1 - Additional Features ................................................................................................................. 10
PSU-1 Wiring Diagram ...................................................................................................................... 11
PS-1 Wiring Diagram AC Supply .................................................................................................... 11
PS-1 Wiring Diagram DC Supply .................................................................................................... 12
1.2 PS-10: AC Supply Input 90 to 260 VAC & PS-20: DC Supply Input 20 to 60 VDC ............. 13
PS-10-CU, PS-20-CU ................................................................................................ 13
PS-10/PS-20 Standard Specifications ............................................................................................ 14
PS-10-2/PS-20-2 24 V Specifications ............................................................................................. 15
PS-10/PS-20 Block Diagram .......................................................................................................... 15
PS-10/PS-20 Module LEDs ............................................................................................................ 16
PS-10/PS-20 - Additional Features ................................................................................................... 16
PS-10 Wiring Diagram AC Supply .................................................................................................. 17
PS-10 Wiring Diagram DC Supply .................................................................................................. 17
PS-20 Wiring Diagram ....................................................................................................................... 18
1.3 PSU-2: DC Supply Input, 18 to 36 VDC .............................................................................. 19
PSU-2 Specifications ......................................................................................................................... 19
PSU-2 Block Diagram ........................................................................................................................ 20
PSU-2 Module LEDs .......................................................................................................................... 20
PSU-2 Wiring Diagram ...................................................................................................................... 21
PSU-2 Output Characteristics ............................................................................................................ 21
1.4 PSU-4: AC Supply Input, 60 W (Pre 2008) .......................................................................... 22
PSU-4 Specifications ......................................................................................................................... 22
PSU-4 Block Diagram ........................................................................................................................ 22
PSU-4 Mounting and Connection ...................................................................................................... 23
PSU-4 Output Characteristics ............................................................................................................ 23
1.5 CP-1: Standard Processor Module ...................................................................................... 24
Figure: CP-1 Rear View And Link Location ........................................................... 24
CP-1 Specifications ........................................................................................................................... 25
CP-1 Block Diagram .......................................................................................................................... 26
CP-1 Connections .............................................................................................................................. 26
Figure: CP-1 Front Module and Port Identification ............................................... 26
Note: Port 2 RTS and CTS do not function on Rev. C boards ............................. 27
1.6 SBX-2: Mini Processor Unit ................................................................................................. 28
Figure: SBX-2 Rear Module IO-3 and RAM Battery Link Location ...................... 28
SBX-2 Specifications ......................................................................................................................... 29
SBX-2 Block Diagram ........................................................................................................................ 30
SBX-2 Connections ........................................................................................................................... 30
1.7 LM-2: Line Modem Module, Dual Leased Line 2-Wire ........................................................ 31
LM-2 Specifications ........................................................................................................................... 32
LM-2 Block Diagram .......................................................................................................................... 32
LM-2 Connections .............................................................................................................................. 33
2. RTS, CTS & CD signals active low to 0 V .......................................................... 34
1.8 LNA-6: Line Amplifier Module, Leased Line ........................................................................ 35
LNA-6 Specifications ......................................................................................................................... 35
LNA-6 Block Diagram ........................................................................................................................ 36
Kingfisher PLUS+Hardware Manual 6.0 www.cse-semaphore.com/mykingfisher Page 4

LNA-6 Connections ............................................................................................................................ 36
1.9 MC-1: Multi Communications Module .................................................................................. 37
MC-1 Part Numbers ........................................................................................................................... 37
Ordering Information .............................................................................................. 37
MC-1 Module LEDs ........................................................................................................................... 37
MC-1 Specifications ........................................................................................................................... 38
MC-1 Block Diagram .......................................................................................................................... 38
MC-1 Connections ............................................................................................................................. 39
1.10 BA-3: 3 Slot Backplane ........................................................................................................ 40
Figure: BA-3 Mounting Details ............................................................................... 40
BA-3 External Connections ................................................................................................................ 41
1.11 BAX-6: 6 Slot Backplane for LNA-6 Module ........................................................................ 42
Figure: Backplane Mounting Details - BAX-6 ........................................................ 42
External Connections ......................................................................................................................... 43
NOTE: PTT, CTS and CD are active low referred to 0 V ....................................... 43
1.12 BA-4: 4 Slot Backplane ........................................................................................................ 44
BA-4 External Connections ................................................................................................................ 44
1.13 BA-40: 4 Slot Backplane ...................................................................................................... 46
BA-40 External Connections .............................................................................................................. 46
1.14 BA-6: 6 Slot Backplane ........................................................................................................ 47
Figure: BA-6 Dimensions (mm) .............................................................................. 47
BA-6 External Connections ................................................................................................................ 47
1.15 BA-12: 12 Slot Backplane .................................................................................................... 48
BA-12 External Connections .............................................................................................................. 48
1.16 DI-1: 12-24 Volt AC or DC Input, 16 Point ........................................................................... 49
DI-1 Specifications ............................................................................................................................. 49
DI-1 Wiring Diagram .......................................................................................................................... 50
1.17 DI-2: 48 Volt AC or DC Input, 16 Point ................................................................................ 51
DI-2 Specifications ............................................................................................................................. 51
DI-2 Wiring Diagram .......................................................................................................................... 52
1.18 DI-3: 120 Volt AC Input, 16 Point ......................................................................................... 53
DI-3 Specifications ............................................................................................................................. 53
DI-3 Wiring Diagram .......................................................................................................................... 54
DI-3 Output Characteristics ............................................................................................................... 54
1.19 DI-4: 240 Volt AC Input, 16 Point ......................................................................................... 55
DI-4 Specifications ............................................................................................................................. 55
DI-4 Wiring Diagram .......................................................................................................................... 56
DI-4 Output Characteristics ............................................................................................................... 56
1.20 TEL REL 001: DPDT Relay Board For DO-5 ....................................................................... 57
Relay Board - TEL REL 001 Specifications ....................................................................................... 57
Relay Board - TEL REL 001 Wiring Diagram .................................................................................... 58
Interface Cable DO-5 To TEL REL 00x Relay Board ..................................................................... 59
1.21 AI-4: Analog Current Input, 8 Channel (Flying Capacitor) ................................................... 60
Scaling of the input is shown below. ..................................................................... 60
Figure: AI-4 Scaling for Analog Current 4 to 20 mA ............................................. 60
Figure: AI-4 Rear Module and Link Location ........................................................ 61
AI-4 Specifications ............................................................................................................................. 62
AI-4 Block Diagram ............................................................................................................................ 63
AI-4 Wiring Diagram .......................................................................................................................... 63
1.22 AO-2: Analog Current Output, 4 Channel ............................................................................ 64
Figure: AO-2 Rear Module and Link Location ....................................................... 65
Kingfisher PLUS+Hardware Manual 6.0 www.cse-semaphore.com/mykingfisher Page 5

Module LEDs ..................................................................................................................................... 65
AO-2 Load Current Characteristics (24 V Out) .................................................................................. 65
AO-2 Specifications ........................................................................................................................... 66
AO-2 Wiring Diagram ......................................................................................................................... 67
1.23 RT-1: Analog RTD Input, 4 Channel .................................................................................... 68
Figure: RT-1 Scaling ............................................................................................... 68
RT-1 Specifications ............................................................................................................................ 69
RT-1 Block Diagram .......................................................................................................................... 70
RT-1 Wiring Diagram ......................................................................................................................... 70
1.24 COMMS OPTION S: Serial Option Board ........................................................................... 71
Serial Option Board Specifications .................................................................................................... 71
Serial Option Board Connections ...................................................................................................... 71
RS232 Wiring Diagram (Null Modem Cable) ..................................................................................... 71
1.25 COMMS OPTION Z: 2400 bps Dial Option Board ............................................................... 72
Dial Option Board Connections ......................................................................................................... 72
Dial Option Board Specifications ....................................................................................................... 72
1.26 MODEM BOARD M: 4-Wire Line Option Board ................................................................... 73
4-Wire Line Option Board Specifications ........................................................................................... 73
4-Wire Line Option Board Connections ............................................................................................. 73
4-Wire Line Option Board Wiring Diagrams ...................................................................................... 73
1.27 CP-21 GPS Option Board .................................................................................................... 74
GPS Option Board Specifications ...................................................................................................... 74
1.28 DO-5: Relay Driver Output, 16 Channel .............................................................................. 75
Module LEDs ..................................................................................................................................... 75
DO-5 Specifications ........................................................................................................................... 76
DO-5 Wiring Diagram ........................................................................................................................ 76
1.29 PS-11: AC Supply Input 100 to 240 VAC ............................................................................ 77
PS-11 Specifications .......................................................................................................................... 79
PS-11 Module LEDs .......................................................................................................................... 80
Battery Charging ................................................................................................................................ 81
Part Numbers ..................................................................................................................................... 81
PS-11-C AC input, Auxiliary 24 V converter fitted ......................................... 81
PS-11-0 AC input, Auxiliary 24 V converter not fitted ................................... 81
PS-11 Block Diagram ........................................................................................................................ 81
PS-11 Wiring Diagram AC Supply .................................................................................................. 82
PS-11 Wiring Diagram DC Supply .................................................................................................. 82
1.30 PS-21: DC Supply Input 20 to 60 VDC ................................................................................ 83
PS-21 Specifications .......................................................................................................................... 85
PS-21 Module LEDs .......................................................................................................................... 86
Battery Charging ................................................................................................................................ 87
Part Numbers ..................................................................................................................................... 87
PS-21-C DC input, Auxiliary 24 V converter fitted ......................................... 87
PS-PS-21 Block Diagram .................................................................................................................. 87
PS-21 Wiring Diagram ....................................................................................................................... 88



Kingfisher PLUS+Hardware Manual 6.0 www.cse-semaphore.com/mykingfisher Page 6

1.1 PS-1/PSU-1: AC Supply Input
The AC supply input module provides AC to DC conversion, DC voltages for the backplane, battery
and radio (or an external device), an optional isolated 24 VDC output and various monitoring
functions.

The PSU-1 was manufactured to power a 24 V backplane, 24 V battery and 24 V radio. The PS-1 was
manufactured in two models. PS-1-1: powers a 12 V backplane, 12 V battery and 12 V radio. PS-1-2
(similar to the PSU-1): powers a 24 V backplane, 24 V battery and 24 V radio.

The module has limited charging capacity for externally connected lead acid batteries. The charging
capacity is designed for float operation and short term boost of batteries already charged and in good
condition. Use of this supply on flat or fully discharged batteries may cause damage.

An optional isolated 24 VDC output rated at 10 W (400 mA) is available for powering a limited number
of analog loops or digit input circuits. It cannot be used with inductive loads such as coils, contactors
etc. Power for these is to be provided from a separate supply.

The PS-1/PSU-1 features supply, voltage, current and temperature monitoring circuits that enable the
processor unit to access these as analog and digital points in the system. When the AC supply fails
and the system is powered from external lead acid batteries if connected the voltage monitoring circuit
provides battery cut-off (for battery preservation) when battery cell voltage reaches +10.5 V (12 V
battery) or 21 VDC (24 V battery). The load capacities for each output of the power supply are shown
in the following table.

This module can be installed in any I/O slot of a 3, 6 or 12 slot backplane in a system. Up to 4 Power
Supply modules of any type can be installed in a backplane thus providing redundant and alternative
power source configurations.


Kingfisher PLUS+Hardware Manual 6.0 www.cse-semaphore.com/mykingfisher Page 7

PS-1 Battery Charging States
Charge State: The power supply starts up in the Charge State. In the Charge State the Power
supply will charge the battery with the highest possible current. This current is determined by the
maximum current the power supply can supply and the maximum battery charge current. The
maximum battery charge current is typically 0.25 * the battery capacity. E.g. if the battery capacity is
6.5 AH the maximum charge current will be 0.25 * 6.5 =1625 mA. To achieve the desired charge
current the supply voltage will be slowly increased. If the supply voltage reaches 14.25 V at 25 C the
charge mode will be terminated and the Boost mode will be entered.
Boost State: In the Boost State the supply voltage will be maintained at 14.25 V at 25 C

as long as
the battery charge current and the maximum supply current are not exceeded. The Boost State lasts
8% of the charging time. If the charging time was less than 12 minutes the Boost State will be skipped
and the Float State will be entered.
Float State: In the Float State the power supply wants to maintain 13.8 V at 25 C as long as the
maximum supply current is not exceeded. The voltage will be very slowly decreased from 14.25 V
(Boost/Charge voltage) to 13.8 V. The maximum adjustment rate is one adjustment every 2 minutes.
This is done to let the battery float down to this voltage. The float state is also entered when the
power supply is in Charge or Boost mode and AC power is lost. If the AC power returns, the power
supply will enter the Charge State.
No Battery State: If the power supply is in any of the above states and the battery current is less
than 10 mA and greater than -10 mA for longer than 5 minutes, then the No Battery state is entered.
In this state the power supply wants to maintain 12.5 V at any temperature. If the battery current
becomes greater than 15 mA or less than -15 mA the No battery state is terminated and the Charge
state is entered.
Manual State: If the Manual bit in the power supply is set, the Manual state is entered. In Manual
state there is no control except that the supply voltage will be reduced if the maximum supply current
is exceeded. Resetting the Manual bit will cause the power supply to enter the Charge State.

Float
Vs =13.8V*
Boost
Vs =14.25V*
Charge
Ibat =Imax
charge
No battery
Vs =12.5V
Manual
Vs =user
trim
manual
reset
(Ibat >
15mA or
Ibat <
-15mA)
manual
set
Vs =
14.25V*
(Ibat <10mA and
Ibat >-10mA
for 5 min.)
AC
returns
AC
fail
8% of
charge time
expired
startup

* These voltages are temperature compensated. The voltage shown is the voltage at 25 C. The
voltages are increased by 22 mV for each degree Celsius the temperature decreases. If the
temperature is 80 C or -20 C (minimum or maximum values) the temperature sensor is assumed to
be faulty. An error will be flagged and a temperature of 25 C will be assumed.

Kingfisher PLUS+Hardware Manual 6.0 www.cse-semaphore.com/mykingfisher Page 8

Notes:
A condition has to be valid for 3 seconds before the trim voltage is adjusted.
In float state the trim voltage will only be decreased at a maximum rate of once every 2 minutes.
In every state the maximum supply current is continuously monitored and the voltage is reduced if
exceeded.



PS-1/PSU-1 Specifications
Specifi cation PS-1-1 (12 V backplane) PS-1-2 / PSU-1 (24 V backplane)
Input Supply 90 to 220 VAC 50/60 Hz USA & Asia
150 to 250 VAC Aus. & Asia
90 to 220 VAC 50/60 Hz USA & Asia
150 to 250 VAC Aus. & Asia
Load Capacity 50 W 25 W up to S/N 11723
50 W for Serial Numbers >11910
Outputs +5 VDC @ <10 W to Backplane
+12 VDC @ <50 W to Backplane
+12 VDC @ <50 W to Battery
+13.8 VDC @ 2 A to Radio
+24 VDC Isolated @ <10 W to Field
(optional)
Total 50 W max.
+5 VDC @ <10 W to Backplane
+24 VDC @ <50 W to Backplane
+24 VDC @ <50 W to Battery
+27.6 VDC @ 1 A to Radio (PS-1-2)
+24 V Isolated @ <10 W to Field
(optional)
Total 50 W max.
Backup Battery 12 VDC, 26 AH max. Sealed Lead-
Acid
24 VDC, 15 AH max. Sealed Lead-Acid
Isolation 2.5 kV AC input/DC output
2.5 kV Isolated 24 VDC output
2.5 kV AC input/DC output
2.5 kV Isolated 24 VDC output
Deep Discharge
Protection
RTU Shutdown at 10.5 V RTU Shutdown at 21 V
Startup Voltage 11.8 V 23.6 V
Supply Fuse 1.6 A slow blow internal 1.6 A slow blow internal
Monitoring
Circuits
Battery Current and Voltage,
Temperature, AC Supply, DC Supply
Battery Current and Voltage,
Temperature, AC Supply, DC Supply
Status
Indicators
Voltage Supplies and Battery on
Front Bezel
Voltage Supplies and Battery on Front
Bezel
Connector Removable for AC/DC connectors Removable for AC/DC connectors

Kingfisher PLUS+Hardware Manual 6.0 www.cse-semaphore.com/mykingfisher Page 9

Output Characteristics
The output voltage is controlled to limit the output to below 50 W at 25C. High ambient temperatures
will cause automatic supply derating in accordance with the curve shown below.

-20
AMBIENT TEMPERATURE (DegC)

OUTPUT
POWER
(W)
0 20 40 60 80
10
20
30
40
50
25
PSU-1/PS-1
EARLY
PSU-1




PS-1/PSU-1 Block Diagram
N
FILTER
RECTIFIER A
E
B+
B-
OPTIONAL
BATTERY
+5V
REGULATOR
25 or50W
DC/DC
CONVERTER
+12 OR24V
5V
0V
EARTH
ON/OFF
(PS-1
ONLY)
BACKPLANE
80C51 MICRO
CONTROLLER
RS485
DRIVER
10W DC/DC
CONVERTER
(OPTIONAL)
VA+
VA-
R+
R-
LOW POWER
RADIO
(PS-1 ONLY)
+24V
ISOLATED
OUTPUT
ON/OFF
(PSU-1
ONLY)
BATTERY
CUTOFF
SERIALBUS
LED DISPLAY
MONITORING
MODULE
ADC 8 BIT
TEMP.
SENSOR
V
I

Kingfisher PLUS+Hardware Manual 6.0 www.cse-semaphore.com/mykingfisher Page 10

PS-1/PSU-1 Module LEDs
LED Description
OK ON when module is functioning OK
DC +5 V ON when the internal 5 V supply is OK. This LED should
always be on
+Vs PSU1: ON when the Auxiliary 24 V supply is OK (will only
display if the 24 V converter is installed).
PS-1: AC Power ON
+Va PS-1: ON when the Auxiliary 24 V supply is OK (will only
display if the 24 V converter is installed)
BATT CHG Battery is being charged
FL Battery is in float charge mode
BO Battery is in boost charge mode
LO Battery has reached its discharged condition (<22 V for
PSU-1/PS-1-2 or <11.3 V for PS-1-1)
+24 V PSU1: ON when the internal 24 V supply is OK. This LED
should always be ON.


PS-1 - Additional Features
The PS-1-1 has an additional 13.8 V for powering external low power radio units. The connections are
on the DC terminal block. This output is limited to 2 A maximum at 10% duty cycle and is switched off
on low battery voltage for battery protection.

NOTE: The PS-1 is supplied with a battery temperature sensor that must be fitted to the negative (-)
terminal of the battery to ensure correct charging operation.

Kingfisher PLUS+Hardware Manual 6.0 www.cse-semaphore.com/mykingfisher Page 11

PSU-1 Wiring Diagram
It is recommended that the battery charging Current Limiter is used when using back-up batteries with
the PSU-1 to prevent overloading. Note: External loads are to be wired directly off the PSU-1, not off
the Battery.

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
+

-
24VDC AUX. OUTPUT (OPTIONAL)
BATTERY


NEUTRAL
-
+
CONNECT POSITIVE TERMINAL
TO (4) IF EXTERNAL BATTERY
CHARGER IS USED
AC INPUT SUPPLY
ACTIVE
EARTH

1N5819
CURRENT LIMITER
CLOSE FOR OFF
18 ohms 2W




PS-1 Wiring Diagram AC Supply
+
-


PS-1
OFF

E
N
A
+
-

24 VDC AUX. OUTPUT (OPTIONAL)
LOW POWER DC OUTPUT
(FOR RADIO OR OTHER DEVICE)
BATTERY

TEMP.
SENSOR
NEUTRAL

+
-

TAPE TEMPERATURE SENSOR
TO NEGATIVE BATTERY
TERMINAL. CONNECT BLACK
STRIPED WIRE OF SENSOR TO
R- OR B-
90-250 VAC INPUT SUPPLY
VA+
VA-
R+
R-
TS
B+
B-

ACTIVE
EARTH


Kingfisher PLUS+Hardware Manual 6.0 www.cse-semaphore.com/mykingfisher Page 12

PS-1 Wiring Diagram DC Supply
The battery input of the PS-1 can also be used as a DC supply input. The following diagram shows
how the PS-1 is wired for a DC supply.

+
-


PS-1
OFF

E
N
A
+
-

24 VDC AUX. OUTPUT (OPTIONAL)
DC OUTPUT
(FOR RADIO OR OTHER DEVICE)
+
-

VA+
VA-
R+
R-
TS
B+
B-

NOT
CONNECTED
11.8 TO 14.0 VDC SUPPLY
(MUST BE ISOLATED FROM FIELD
SUPPLY)


Kingfisher PLUS+Hardware Manual 6.0 www.cse-semaphore.com/mykingfisher Page 13

1.2 PS-10: AC Supply Input 90 to 260 VAC
& PS-20: DC Supply Input 20 to 60 VDC
The PS-10 power supply provides AC to DC conversion, DC voltages for the backplane, battery and
radio (or an external device), an optional isolated 24 VDC output and an optional monitoring
processor. The PS-20 power supply offers the same functionality as the PS-10 except it has a DC
supply input instead of an AC supply input.

The PS-10 and PS-20 are manufactured to power a 12 V backplane, 12 V battery and 12 V radio. The
PS-10 and PS-20 are available as a 24 V module by special order (please see below for
specifications).

An isolated 24 VDC output rated at 10 W (400 mA) is an option available for powering a limited
number of analog loops or digit input circuits. It cannot be used with inductive loads such as coils,
contactors etc. Power for these is to be provided from a separate supply.

In addition the module has limited charging capacity for externally connected lead acid batteries. The
temperature compensated charging capacity is designed for float operation and short term boost of
batteries already charged and in good condition. Use of this supply on flat or fully discharged batteries
may cause damage.

When the AC supply fails and the system is powered from external lead acid batteries (if connected),
the voltage monitoring circuit provides battery cut-off (for battery preservation) when battery cell
voltage drops to 10.5 V 0.2 V.

The PS-10/20 has an optional monitoring processor that can be factory fitted. This allows battery
voltage, battery current, regulated supply current, and internal or external temperature to be
monitored.

If no monitoring circuit is loaded, the PS-10/PS-20 will not be able to communicate with the processor
module and therefore will not show up in the hardware overview. In addition, there will be no power
supply monitoring information (i.e. indication of battery current, battery voltage, temperature, battery
low, AC present, Aux 24 V present) in the system. On/off control of the radio power and auxiliary 24 V
output power will be under control of the processor module.

A power supply module can be installed in any I/O slot of a 3, 6 or 12 slot backplane in a system. Up
to 4 Power Supply modules of any type can be installed on a backplane thus providing redundant and
alternative power source configurations.

Part numbers:

PS-10-CU, PS-20-CU

C=Auxiliary 24 V DC to DC converter fitted. 0=Not fitted.
U=Power supply monitoring processor fitted. 0=Not fitted.
Kingfisher PLUS+Hardware Manual 6.0 www.cse-semaphore.com/mykingfisher Page 14

PS-10/PS-20 Standard Specifications
Input Supply 90 to 260 VAC 50/60 Hz (PS-10)
+20 to +60 VDC or 20 to 60 VDC (PS-20)
Note: the module can also be powered using 12 to 13.8 VDC when
powered from the backup battery terminals.
Backup Battery 12 VDC, 26 AH max. Sealed Lead-Acid
Outputs +5 VDC @ 2 A Max. to Bus
+12 VDC @ 4 A Max. to Bus
+12 VDC @ 4 A Max. to Battery
+24 VDC Isolated @ 400 mA Max. to Field (optional)
+13.8 VDC @ 3.6 A Max. to Radio
Maximum output power: 50 W
Isolation 3 kV AC input/DC output
3 kV Isolated 24 VDC output
Deep Discharge
Protection
RTU Shutdown at 10.5 V +0.2 V
RTU Startup at 11.8 V +0.2 V
Supply Fuse Slow blow internal
1.6 A (PS-10) or 6.3 A (PS-20)
Battery Fuse 4 A Polyfuse (self-resetting)
Connector Removable for AC/DC connections
LED indicators
(Standard)
Vsup DC voltage present
Vb Battery voltage present
5 V 5 V present
Vaux Auxiliary converter present
Monitoring Processor
(Optional)
Monitoring Circuits:
Battery Current
Battery Voltage *
Supply Current *
Temperature
Detection circuits:
AC present
Battery low
Aux. 24 V present
Control circuits:
Aux. 24 V on/off
Radio power on/off
LED indicators:
OK Microprocessor Watchdog
Batt CHG Battery Charging
FL Float Charge
BO Boost Charge
LO Battery Low

* The battery voltage is monitored when the input supply is disconnected. While the input supply is
connected, the module will measure the regulated voltage and current output of its AC (PS-10) or DC
(PS-20) input circuit.
Kingfisher PLUS+Hardware Manual 6.0 www.cse-semaphore.com/mykingfisher Page 15

PS-10-2/PS-20-2 24 V Specifications
The 24 V power supply has the same specifications as the 12 V power supply (PS-10-1, PS-20-1)
except it supplies 24 VDC to the backplane, battery and radio as detailed below.

Outputs +5 VDC @ 2 A to Bus
+24 VDC @ 2 A Max. to Bus
+24 VDC @ 2 A Max. to Battery
+24 VDC Isolated @ 400 mA to Field (optional)
+27.6 VDC @ 1.8 A to Radio
Maximum output power: 50 W



PS-10/PS-20 Block Diagram
N
FILTER
RECTIFIER
A
E
LED
VSUP
TEMPERATURE
COMPENSATION
INTERNAL
TEMP.
SENSOR
TS
R-
EXT.
TEMP.
SENSOR
B+
B-
OPTIONAL
BATTERY
+5V
REGULATOR 50 W
DC/DC
CONV.
Vb
5 V
0V
PCON
EARTH
LOW
VOLTAGE
CUTOFF
S1
LED
Vb
BACKPLANE
LOW
VOLTAGE
MONITOR
LED
LO
MICRO CONTROLLER
RS485
DRIVER
LED
OK
LED
CHG
LED
BO
LED
FL
BACKPLANE
ISOLATED
24V AUX.
DC/DC
CONVERTER
10 W
(OPTIONAL)
LED
VAUX
VA+
VA-
R+
R-
RADIO LK4
LK5
Vb
RADIO
POWER
AUX24 PWR
Isup CURRENT
MONITOR
Ibat CURRENT
MONITOR
PWR TEMP Ibat Isup
BAT LOW
OPTIONAL
MONITORING

Kingfisher PLUS+Hardware Manual 6.0 www.cse-semaphore.com/mykingfisher Page 16

PS-10/PS-20 Module LEDs

LED Description (when ON)
OK * Module is functioning OK
Vsup AC supply input is powered. For PS-20, ON when DC input circuitry is powered.
Vb Battery voltage supply is OK. This LED should always be on and means that the power
supply is able to charge a battery or is being powered by the battery input.
5 V Internal 5 V supply is OK. This LED should always be on as the 5 V supply is used to
power all the modules.
Vaux Auxiliary 24 V supply is OK (will only display if the 24 V converter is installed).
Controllable if a monitoring processor is fitted.
BATT CHG * Battery is being charged
FL * Battery is in float charge mode
BO * Battery is in boost charge mode
LO *
Battery has reached discharged condition (<11.5 V0.2 V).
LO LED is cleared when battery >12.4 V 0.2 V
* Only enabled when a monitoring processor is fitted (optional for the PS-10 and PS-20)



PS-10/PS-20 - Additional Features
The PS-10 and PS-20 have an additional DC output for powering low power radios. The connections
are on the DC terminal block. This output is switched off on low battery voltage for battery protection
and can be controlled when the monitoring processor is fitted.

The PS-10/PS-20 is supplied with an internal and external temperature sensor. When a battery is
connected, the external sensor should be mounted close to the negative terminal of the battery to
ensure correct charging operation. The lowest temperature is monitored by the monitoring processor
and used by the temperature compensated battery charging (in normal operation the internal
temperature sensor will indicate a higher temperature than the external sensor).

Kingfisher PLUS+Hardware Manual 6.0 www.cse-semaphore.com/mykingfisher Page 17

PS-10 Wiring Diagram AC Supply
+
-


PS-10
OFF

+
-

24 VDC AUX. (OPTIONAL)
13.8 VDC (FOR RADIO
OR OTHER DEVICE)
BATTERY

TEMP.
SENSOR
+
-

TAPE TEMPERATURE SENSOR
TO NEGATIVE BATTERY
TERMINAL. CONNECT BLACK
STRIPED WIRE OF SENSOR TO
R- OR B-
VA+
VA-
R+
R-
TS
B+
B-

E
N
A
90-260 VAC
NEUTRAL


ACTIVE

EARTH





PS-10 Wiring Diagram DC Supply
The battery input of the PS-10 can be used as a DC supply input.

VA+
VA-
R+
R-
TS
B+
B-
+
-


PS-10
OFF

+
-

24 VDC AUX. (OPTIONAL)
13.8 VDC (FOR RADIO
OR OTHER DEVICE)
NOT
CONNECTED
+
-

11.8 TO 14.0 VDC SUPPLY
(MUST BE ISOLATED FROM FIELD
SUPPLY)
E
N
A



Kingfisher PLUS+Hardware Manual 6.0 www.cse-semaphore.com/mykingfisher Page 18

PS-20 Wiring Diagram
+
-


PS-20
OFF

E
-
+
+
-

24 VDC AUX. OUTPUT (OPTIONAL)
13.8 VDC OUTPUT
(FOR RADIO OR OTHER DEVICE)
BATTERY

TEMP.
SENSOR
+
-

TAPE TEMPERATURE SENSOR
TO NEGATIVE BATTERY
TERMINAL. CONNECT BLACK
STRIPED WIRE OF SENSOR TO
R- OR B-
20-60 VDC INPUT SUPPLY *
VA+
VA-
R+
R-
TS
B+
B-

- SUPPLY

+SUPPLY
EARTH
*A NEGATIVE DC INPUT SUPPLY CAN BE USED.
CONNECT THE MORE POSITIVE WIRE
(eg 0 V) TO +SUPPLY AND CONNECT THE MORE
NEGATIVE WIRE (eg -48 V) TO -SUPPLY.


Kingfisher PLUS+Hardware Manual 6.0 www.cse-semaphore.com/mykingfisher Page 19

1.3 PSU-2: DC Supply Input, 18 to 36 VDC
The PSU-2 DC supply (18 to 36 VDC) module provides DC to DC conversion, galvanic isolation,
+12 VDC, +5 VDC and various monitoring functions to power the RTU modules.

An isolated 24 VDC output rated at 10 W (400 mA) is available for powering a limited number of
analog loops or digit input circuits. It cannot be used with inductive loads such as coils, contactors etc.
Power for these is to be provided from a separate supply.

The PSU-2 features optional supply, voltage, current and temperature monitoring circuits that enable
the processor unit to access these as analog and digital points in the system. When the DC supply
fails and the system is powered from external lead acid batteries if connected the voltage monitoring
circuit provides battery cut-off (for battery preservation) when battery cell voltage reaches 10.5 VDC.
The load capacities for each output of the power supply are shown in the following table. Note: the
specifications shown are for the 12 V model of the PSU-2. The PSU-2 was also available as a 24 V
model.


PSU-2 Specifications
Input Supply 18 to 36 VDC Nominally 24 VDC
Outputs +5 VDC @ <10 W to Bus
+12 VDC @ <50 W to Bus
+12 VDC @ <50 W to Battery
+24 VDC Isolated @ 10 W to Field
Total 50 W max.
Isolation 2.5 kV DC input/DC output
2.5 kV Isolated 24 VDC output
Deep Discharge Protection RTU Shutdown at 10.5 V
RTU Startup at 11.8 V
Supply Fuse 4 A slow blow internal
Monitoring Circuits Battery Current and Voltage, Temperature, DC
Supply
Status Indicators Supplies and Battery on Front Bezel
Connector Removable for DC connectors

Kingfisher PLUS+Hardware Manual 6.0 www.cse-semaphore.com/mykingfisher Page 20

PSU-2 Block Diagram
+
FILTER
-
E
B+
B-
OPTIONAL
BATTERY
+5V
REGULATOR
50W
DC/DC
CONVERTER
+12V
5V
0V
EARTH
ON/OFF
BACKPLANE
80C51 MICRO
CONTROLLER
RS485
DRIVER
10W DC/DC
CONVERTER
VA+
VA-
+24V
ISOLATED
OUTPUT
ON/OFF
BATTERY
CUTOFF
SERIALBUS
LED DISPLAY
MONITORING
MODULE
ADC 8 BIT
TEMP.
SENSOR
V
I
Vs




PSU-2 Module LEDs
Three red LEDs labelled +5 V, +12 V and Vs are on when the various power supply sections are
functioning correctly. The Vs LED indicates when the isolated 24 Volt/10 Watt output is activated. This
output is under the main processor control (CP-1 or SBX-2) but is normally in the on state. A green
LED at the top of the face plate is ON when the microcontroller of the monitoring circuit and the power
conversion circuits are operating correctly. An additional four red LEDs labelled CHG, FL, BO and LO
indicate the condition of a connected battery which are:

CHG Battery is being charged
FL Battery is in float charge mode
BO Battery is in boost charge mode
LO Battery has reached its discharged condition (<22 V)

This module can be installed in any I/O slot of a 3, 6 or 12 slot backplane in a system. Up to 4 Power
Supply modules of any type can be installed in a backplane thus providing redundant and alternative
power source configurations.

Kingfisher PLUS+Hardware Manual 6.0 www.cse-semaphore.com/mykingfisher Page 21

PSU-2 Wiring Diagram
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
+

-
24VDC AUX. OUTPUT
BATTERY


SUPPLY -
+
-
Vs, DC INPUT SUPPLY
SUPPLY +
EARTH
CLOSE FOR OFF




PSU-2 Output Characteristics
-20
AMBIENT TEMPERATURE (DegC)

OUTPUT
POWER
(W)
0 20 40 60 80
10
20
30
40
50
25


Kingfisher PLUS+Hardware Manual 6.0 www.cse-semaphore.com/mykingfisher Page 22

1.4 PSU-4: AC Supply Input, 60 W (Pre 2008)
The PSU-4 (Pre 2008 version) provides 5 VDC and 12 or 24 VDC outputs for powering a backplane
without the need for a PS-xx power supply module. The PSU-4 does not provide power monitoring
data and is not mounted on the backplane.


PSU-4 Specifications
Input Supply 90 to 260 VAC 50/60 Hz
Load Capacity 60 W
Outputs +5 VDC @ 3 A
+24 VDC @ 1.8 A or +12 VDC @ 3 A
Isolation 2.5 kV AC input / DC output
Supply Fuse 1.6 A slow blow internal
Monitoring Circuits Nil
Status Indicators Nil
Connector Screw Terminals
Weight 530 gm



PSU-4 Block Diagram
FILTER AND
RECTIFIER
E
3
N
A
2
1
DC/DC
60 WATT
0V
+5V
4
5
BACKPLANE
6 PIN
PLUG
+12 or +24V
7
6
5V REG

Kingfisher PLUS+Hardware Manual 6.0 www.cse-semaphore.com/mykingfisher Page 23

PSU-4 Mounting and Connection





PSU-4 Output Characteristics
-20
AMBIENT TEMPERATURE (DegC)

OUTPUT
POWER
(W)
0 20 40 60 80
20
30
40
50
60
25

Kingfisher PLUS+Hardware Manual 6.0 www.cse-semaphore.com/mykingfisher Page 24

1.5 CP-1: Standard Processor Module
The CP-1 standard processor module provides all processing, I/O scan, logic, control and
communications functions required in any of the RTU configurations that may be adopted. This
module has two independent serial ports; one of which, port 2 (P2) may be software configured for
RS232C or RS485 circuit interfaces. Port 1 is fixed at RS232C.

In addition this module is available in two memory configurations. The standard configuration is 256K
of FLASH MEMORY for the storage of all operating code and selected system parameters, and 256K
of battery backed static RAM for all configuration and event storage data. This memory configuration
is ordered as CP-1-0. An optional extended memory configuration adds 512K of static RAM and is
ordered as CP-1-2. The extended memory configuration is only required in very large systems
employing many field RTUs which report back to a master RTU - all data being held in the master
RTU.

The RAM battery in earlier production units is enabled at shipping time by the factory. Later production
units allow the user to enable the battery by a link at the rear of the module - see figure below.


Link for RAM
battery (LK1)


Link for +12 V supply
to ports 1 and 2
Factory default:
RAM link installed
+12 V link not
installed


Figure: CP-1 Rear View And Link Location

Two groups of four (4) LEDs show the status of ports 1 and 2. Each port has TXD, RXD, RTS and CD
LEDs in a vertical group. A green LED at the top of the face plate is ON when the module is operating
correctly. This module consumes power from the +5 VDC bus on the backplane. The module can be
installed in any I/O slot of a 6 or 12 slot backplane in a system. Up to two processor modules can be
installed in an RTU system. For example these two may reside anywhere in one, two, three or four
backplane systems.


Kingfisher PLUS+Hardware Manual 6.0 www.cse-semaphore.com/mykingfisher Page 25

CP-1 Specifications
Processor Intel 80C186
Word Size 16 Bit
Clock Speed 16 MHz
BIOS Y
FLASH MEMORY 256 kB (32 kB used for drivers)
Static CMOS RAM 256 kB or 768 kB
RTC Y
WDT Y
Status Indication Y
Battery Life - module
unpowered
15 Years (256 kB)
10 Years (768 kB)
Communication Ports
2
Serial Port 1 (RS232) 300 to 115200 Baud
Serial Port 2 (RS232/RS485) 300 to 115200 Baud
Communications Master or Outstation
Configuration Software Toolbox 32
RTU Address Range 1 249
Communications Protocol Kingfisher, Modbus, +many more
Analog Block Processing Y
PID Block Processing Y
Logic Processing Ladder
CPUs per RTU 1 or 2
Internal Power Consumption 120 mA from +5 VDC Bus on backplane
I/O Bus Data Rate 250 kbps
CM Bus Data Rate 83 kbps
Cyclic Redundancy Port 1 and 2
Operating Temperature -20 to 70 C
Storage Temperature -40 to 85 C
Operating Humidity 5 to 98% RH non-condensing
Kingfisher PLUS+Hardware Manual 6.0 www.cse-semaphore.com/mykingfisher Page 26

CP-1 Block Diagram
CM BUS
I/O BUS
FLASH
RAM
256 kB
DUART
PORT 1
BUS
RESE
T
RS485
DRIVER
uP
80C186
16 MHz RS485
DRIVER
PORT 2
RAM
256 kB OR
768 kB
RTC
POWER
MANAGEMENT
3 V
RS232 RS232 RS485


CP-1 Connections
The CP-1 module features two serial ports accessible by the RJ 45 connectors on the front of the
module and covered by the snap on cable cover. Port 1 is at the top for RS232 connections only and
Port 2 is below for either RS232 or RS485 connections. Earlier CP-1 modules have two serial ports
accessible by the DB9 connectors on the front of the module and covered by the snap on cable cover.
Port 1 is at the top for RS232 connections only and Port 2 is below for either RS232 or RS485
connections.



CP-1
P2

P1

RS232

P2

RS232

RS485

CP-1
P2

P1

RS232

RS232 /
RS485
EARLY MODELS

Figure: CP-1 Front Module and Port Identification


Kingfisher PLUS+Hardware Manual 6.0 www.cse-semaphore.com/mykingfisher Page 27

RS232C
Function
CP-1 Ports 1,2
RJ45
CP-1 Ports
1,2 DB9-M
DTR 1 OUT 4 OUT
+12 V Low
Power
2 OUT N/A N/A
RTS 3 OUT 7 OUT
DCD 4 IN 1 IN
GND (0 V) 5 COM 5 COM
CTS 6 IN 8 IN
RXD 7 IN 2 IN
TXD 8 OUT 3 OUT

Note: Port 2 RTS and CTS do not function on Rev. C boards


RS485
Function
CP-1 Port 2
RJ45
CP-1 Port 2
DB9-M
Line - 1 4
Line + 6 6


RJ45 Socket RJ45 Plug
87654321
12345678
GREEN / WHITE 1
GREEN 2
ORANGE / WHITE 3
BLUE 4
BLUE / WHITE 5
ORANGE 6
BROWN / WHITE 7
BROWN 8

Kingfisher PLUS+Hardware Manual 6.0 www.cse-semaphore.com/mykingfisher Page 28

1.6 SBX-2: Mini Processor Unit
The SBX-2 mini processor unit provides all processing, I/O scan, logic, control and communications
required in a small RTU. This unit has two independent serial ports; one of which, port 2 (P2) may be
software configured for RS232C or RS485 circuit interfaces. Port 1 is fixed at RS232C. This unit is
manufactured as an option board for the combination IO-3 module and must be fitted to this module
prior to installing on a BA-3 backplane. The SBX-2 is used with a 3-slot 24 VDC backplane (BA-3).
The two serial ports are accessed using cables that connect to the backplane.

In addition this unit is available in two memory configurations. The standard configuration is 128 kB of
flash memory for the storage of all operating code and selected system parameters, and 128 kB of
battery backed static RAM for all configuration and event storage data. This memory configuration is
ordered as SBX-2/IO-3-0. An optional extended memory configuration adds 128 kB of static RAM and
is ordered as SBX-2/IO-3-1. The extended memory configuration is only required in special
circumstances and intended users should consult the factory.

The RAM battery is enabled by a link at the rear of the module - see figure below.


Link for RAM
battery

Factory default:
RAM link installed

Figure: SBX-2 Rear Module IO-3 and RAM Battery Link Location

LEDs showing status of the serial ports are present on the IO-3 module and reference to this module
should be made. This module consumes power from the +5 VDC bus on the backplane. The module
can be installed only in slot 2 of a BA-3 backplane in a system.

Kingfisher PLUS+Hardware Manual 6.0 www.cse-semaphore.com/mykingfisher Page 29

SBX-2 Specifications
Processor Intel 80C188
Word Size 16 Bit internal data bus
8 Bit external data bus
Clock Speed 16 MHz
BIOS Y
Flash Memory 128 kB
Static CMOS RAM 128 kB or 256 kB
RTC Y
WDT Y
Status Indication N
Battery Life - module
unpowered
15 Years (128 kB)
10 Years (256 kB)
Communication Ports 2
Serial Port 1 (RS232) 300 to 19200 bps
Serial Port 2 (RS232/RS485) 300 to 19200 bps
Communications Outstation
Configuration Software Toolbox 32
RTU Address Range 1 - 249
Communications Protocol Kingfisher, Modbus, +many more
Analog Block Processing Y
PID Block Processing Y
Logic Programs Ladder Logic
Processors per RTU 1
Internal Power Consumption 120 mA from +5 VDC Bus on backplane
I/O Bus Data Rate 250 kbps
CM Bus Data Rate 83 kbps
Cyclic Redundancy Port 1 and 2
Operating Temperature -20 to 70 C
Storage Temperature -40 to 85 C
Operating Humidity 5 to 98% RH non-condensing

Kingfisher PLUS+Hardware Manual 6.0 www.cse-semaphore.com/mykingfisher Page 30

SBX-2 Block Diagram
CM BUS
I/O BUS
FLASH
RAM
128 kB
DUART
PORT 1
BUS
RESE
T
RS485
DRIVER
uP
80C188
16 MHz RS485
DRIVER
PORT 2
RAM
128 kB OR
256 kB
RTC
POWER
MANAGEMENT
3 V
RS232 RS232 RS485



SBX-2 Connections
SBX-2 Ports 1,2
Cable DB9 Male
Function
1 Carrier Detect CD
2 Receive Data RXD
3 Transmit Data TXD
4 Port 1: Data Terminal Ready DTR
Port 2: RS485-
5 Signal Ground GND
6 RS485+
7 Request to Send RTS
8 Clear to Send CTS
9 Do Not Connect

Kingfisher PLUS+Hardware Manual 6.0 www.cse-semaphore.com/mykingfisher Page 31

1.7 LM-2: Line Modem Module, Dual Leased Line 2-Wire
The LM-2 line modem module provides a telephone line interface and data exchange functions for
remotely connected units over leased circuits. This module is equipped with two ports that may be
used simultaneously. The integral modems are standard V22BIS devices allowing speeds up to
1200 bps. Using this module simplifies the user interface in that a great deal of the setup procedure
has been eliminated.

The LM-2 modules primary function is to provide a leased line interface to two separate telephone
lines into the RTU at speeds up to 1200 bps. All communications flow control is managed by the CP-1
or SBX-2 processor module. This module cannot be used by itself (i.e. it must be used with a
processor module).

The module also incorporates dual RJ 45 connectors to allow use with external radio transceivers up to
1200 bps in CCITT V23 mode. This is a non-isolated interface and therefore must be close coupled
with a compatible transceiver if used. The 0 V of the radio must be connected to the 0 V of the
backplane.

Red LEDs on the front bezel show the status of data transfer, for port 1 and port 2. A green LED at the
top of the faceplate labelled OK is ON when the module is operating correctly. This module consumes
power from +5 VDC bus on the backplane. The module can be installed in any I/O slot of a 6 or 12 slot
backplane and in slot no. 3 of a BA-3 backplane and any slot except slot 1 of a BA-4 backplane. Up to
four modem modules can be installed in an RTU system.

Kingfisher PLUS+Hardware Manual 6.0 www.cse-semaphore.com/mykingfisher Page 32

LM-2 Specifications
Data Rates and Modulation 1200 bps CCITT V23 FSK
Data Pump SSI324
Equaliser (Adaptive) Y
Transmit Level -10 dBm
Scrambler/Descrambler Y
Receive Level 0 dBm to -43 dBm
Data Formats Asynchronous
Remote RTS Signalling Y
Bit Error Rate (BER)
10
-6
@ S/N 22 dB
Connection 2 Wire
Line Isolation 4 kV
Processor Intel 80C51
Word Size 8 bit
Flash Memory 4 kB
Static CMOS RAM 32 kB
CM Bus Data Rate 83 kbps
Modem Modules per RTU 4
Internal Power Consumption 65 mA from +5 VDC Bus on backplane
Operating Temperature -20 to 70 C
Storage Temperature -40 to 85 C
Operating Humidity 5 to 98% RH non-condensing


LM-2 Block Diagram
CM BUS
DUART
PLINE
PORT 1
BUS
RS485
DRIVER
uP
80C51
16 MHz
PLINE
PORT 2
RAM
32 kB
DAA DAA
V22BIS
MODEM
V22BIS
MODEM
RADIO
PORT 1
RADIO
PORT 2

Kingfisher PLUS+Hardware Manual 6.0 www.cse-semaphore.com/mykingfisher Page 33

LM-2 Connections
The LM-2 module features a dual RJ 12 socket for connection to two leased lines (PL) and a dual RJ 45
connector for the external VF (voice frequency) interface to external radio. These connectors are
covered by a snap-on cable cover. Earlier models are fitted with a high density DB15 connector
instead of the dual RJ 45s.


LM-2
P1

P1

RADIO
PLINE

P2

P2


LM-2
P1

RADIO
PLINE

P2

EARLY MODELS



Radio Function LM-2 Ports 1&2
RJ45

RJ45 Socket RJ45 Plug
87654321
12345678
GREEN / WHITE 1
GREEN 2
ORANGE / WHITE 3
BLUE 4
BLUE / WHITE 5
ORANGE 6
BROWN / WHITE 7
BROWN 8

DTR 1 COM
+12 V low power 2 OUT
RTS 3 OUT
DCD 4 IN
GND (0 V) 5 COM
CTS 6 IN
RXA 7 IN
TXA 8 OUT



Kingfisher PLUS+Hardware Manual 6.0 www.cse-semaphore.com/mykingfisher Page 34

Radio Function LM-2 (Earlier
Models)
DB15HD
Connector
TXA1 @ -7 dBm 1 OUT
RTS1 2 OUT
CTS1 3 IN
DCD2 4 IN
DCD1 5 IN
RTS2 6 OUT
TXA2 @ -7 dBm 7 OUT
NC 8 -
RXA2 @ 0 to -30 dBm 9 IN
DTR1 10 COM
DTR2 11 COM
OV 12 COM
OV 13 COM
CTS2 14 IN
RXA1 @ 0 to -30 dBm 15 IN
Notes: 1. dBm is referenced to 600
2. RTS, CTS & CD signals active low to 0 V


Private Line Function LM-2 Ports 1, 2
RJ12 Connector

RJ12 Socket RJ12 Plug
654321
BLUE 1
YELLOW 2
GREEN 3
RED 4
BLACK 5
WHITE 6
123456

Line - 2
Line + 5

Kingfisher PLUS+Hardware Manual 6.0 www.cse-semaphore.com/mykingfisher Page 35

1.8 LNA-6: Line Amplifier Module, Leased Line
The LNA-6 line amplifier module provides a matched leased line interface for up to six (6) leased
circuits from a single modem. Modems with speeds up to 2400 bps may be connected via the VF
circuit interface that is bussed to the backplane connector.

There are six (6) RJ 12 sockets on the front panel for connection to leased circuits. The module
provides galvanic isolation and surge protection from the line to the equipment side and signal voltage
limiting, line matching from the equipment side to the line side.

This module must be located within a BAX-6 backplane and cannot be fitted or mixed with standard
Kingfisher PLUS+modules.


LNA-6 Specifications
Line Isolation 3000 VAC
5000 VDC
Transmit Level -10 dBm with -10 dBm input
Receive Level 0 dBm to -43 dBm
Signal Limiting +/- 4 V Peak
Surge Clamping 360 V
Max. Number of Modules 4
Internal Power Consumption 36 mA from +5 VDC bus on backplane
Operating Temperature -20 to 70 C
Storage Temperature -40 to 85 C
Operating Humidity 5 to 98% RH non-condensing

Kingfisher PLUS+Hardware Manual 6.0 www.cse-semaphore.com/mykingfisher Page 36

LNA-6 Block Diagram

BUFFER

BUFFER
TXA RXA
AMPLIFIER
& HYBRID
LINE
TRANSF.
LINE 1
AMPLIFIER
& HYBRID
LINE
TRANSF.
LINE 2
AMPLIFIER
& HYBRID
LINE
TRANSF.
LINE 3
AMPLIFIER
& HYBRID
LINE
TRANSF.
LINE 4
AMPLIFIER
& HYBRID
LINE
TRANSF.
LINE 5
AMPLIFIER
& HYBRID
LINE
TRANSF.
LINE 6



LNA-6 Connections

LNA-6
L1

PLINE

L2

L3

L4

L5

L6



Function LNA-6
RJ12 Connector

RJ12 Socket RJ12 Plug
654321
BLUE 1
YELLOW 2
GREEN 3
RED 4
BLACK 5
WHITE 6
123456

Line - 2
Line + 5

Kingfisher PLUS+Hardware Manual 6.0 www.cse-semaphore.com/mykingfisher Page 37

1.9 MC-1: Multi Communications Module
The MC-1 multi communications module provides additional ports in any RTU configuration. This
module has three independent serial ports. Ports 1 and 2 are fixed as RS232C while Port 3 can be
loaded with a plug-in option board.

This module consumes power from the +5 VDC bus on the backplane. Up to five MC-1 modules can
be installed in any I/O slot of a 4, 6 or 12 slot backplane. An RTU can have up to 16 communications
ports.


MC-1 Part Numbers
The MC-1 is available with one port option as detailed below.

Ordering Information
Part No. MC-1- P

P Options:
P
Option Port 3 Type
0=Not Fitted
R=Radio, V.23 FSK
P=2-Wire Line, V.23 FSK
S=Serial RS232/RS485
M=4-Wire Line, V.23 FSK

Example: MC-1-R MC-1 with radio option port


MC-1 Module LEDs
Three groups of four (4) LEDs show the status of ports 1 2 and 3. Each port has Tx, Rx, RTS and CD
LEDs in a vertical group.

MC-1 LED Description
OK ON when module is functioning OK
Tx ON when port is transmitting
Rx ON when port is receiving
RTS Request to send. Set ON to begin transmitting
CD Carrier detect. ON while a communications signal is detected.
WD Processor Watchdog Timer. Set ON when the processor is reset.
DR1, DR2,
T1, T2
Not used


Kingfisher PLUS+Hardware Manual 6.0 www.cse-semaphore.com/mykingfisher Page 38

MC-1 Specifications
Processor Intel 80C188
Word Size 16 Bit internal data bus
8 Bit external data bus
Clock Speed 16 MHz
BIOS Y
Flash Memory 128 kB
Static CMOS RAM 128 kB
Status Indication Y
Communication Ports 3
Ports 1&2 (RS232) Serial, 300 to 115200 bps
Port 3 (optional) Same options as PC-1 port 2
Communications Master or Outstation
MC-1s per RTU Maximum of 16 ports per RTU
Eg. Can use 5 MCs if each has 3 ports
Internal Power Consumption 120 mA from +5 VDC Bus on backplane
CM Bus Data Rate 83 kbps
Cyclic Redundancy Port 1, 2 and 3
Operating Temperature -20 to 70 C
Storage Temperature -40 to 85C
Operating Humidity 5 to 98% RH non-condensing


MC-1 Block Diagram
CM BUS
FLASH
RAM
256 kB
RS232 /
RS485
DUART
RS232
PORT 1
BUS
RESET
RS485
DRIVER
uP
80C188
16 MHz
PORT 2

RAM
256 kB
POWER
MANAGEMENT
3 V
PORT 3
Option port
PLUG-IN OPTION BOARD


Kingfisher PLUS+Hardware Manual 6.0 www.cse-semaphore.com/mykingfisher Page 39

MC-1 Connections
The MC-1 module features two serial ports accessible by the RJ 45 connectors on the front of the
module and covered by the snap on cable cover. Port 1 is at the top and Port 2 is immediately below
for RS232 connections only. Port 3 is optional and is detailed in the PC-1 Option Boards chapter.



MC-1
Port 1
Port 2
RS232

RS232/
RADIO
PLINE
Port 3
RS232
Link for +12 V
supply to RS232
ports. Note: +12V is
always enabled on
port 3 radio boards.

Factory default:
+12 V link not
installed.
Not used
FRONT REAR



RS232C
Function
MC-1 Ports 1,2
RJ45 Connector



RJ45 Socket RJ45 Plug
87654321
12345678
GREEN / WHITE 1
GREEN 2
ORANGE / WHITE 3
BLUE 4
BLUE / WHITE 5
ORANGE 6
BROWN / WHITE 7
BROWN 8

DTR 1 OUT
+12 V Low Power
(requires link)
2 OUT
RTS 3 OUT
DCD 4 IN
GND (0 V) 5 COM
CTS 6 IN
RXD 7 IN
TXD 8 OUT

Kingfisher PLUS+Hardware Manual 6.0 www.cse-semaphore.com/mykingfisher Page 40

1.10 BA-3: 3 Slot Backplane
The 3-slot backplane will accommodate a variety of module types in different configurations. I/O
modules and power supplies may be placed in any of the three (3) positions. In addition the centre
position will accommodate an SBX-2 and/or I/O-1, 2 or 3 module. It is not possible to fit a CP-1 or any
communication modules to this position.

There are five (5) connectors at the far right of the backplane. The two (2) small 8-way connectors are
for inter-backplane communication links. The longer six way connector is for external power (+5 V and
+24 V DC), if the standard supply is not fitted. The two lower 10 way pin headers are for the two serial
ports of an SBX-2 module, if used.

This backplane is designed for surface mounting. Mounting brackets (2 pieces) are supplied for user
fitting.



Figure: BA-3 Mounting Details
Kingfisher PLUS+Hardware Manual 6.0 www.cse-semaphore.com/mykingfisher Page 41

BA-3 External Connections
J14 Power Connector Pinout (viewed from the top)

24 V 12 V*
5 V

PCON
0 V 0 V

PCON =Processor controlled power enable.
The 24 V pin is not used by the PC-1. The 12 V and 5 V output pins can be used to power a second
BA-4 backplane. These pins are supplied by the PC-1 when the 12 V battery or 12 V input supply is
connected to the orange BL9 connector.

*CAUTION: The 24 V and 12 V pins are shorted on early revision backplanes (prior to revision 1.3).
Early revision backplanes were designed for 24 V only.



J13 (in), J15 (out) Inter-rack Backplane Comms Connectors

1
2
3
4
8
7
6
5
Pin 1: IO+Serieal I/O link
Pin 2: CM+Serial CM link
Pin 3: 0 V Signal ground
Pin 4: IO- Serial I/O link
Pin 5: CM- Serial CM link
Pin 6: 0 V Signal ground
Pin 7: CSR
Pin 8: PCON Processor controlled power enable



J17, J18 Serial Ports (P1, P2)
Pin 1 CD Carrier data detect
Pin 2 RXD Receive Data
Pin 3 TXD Transmit Data
Pin 4 N/C or I/O (RS485) Port 2 only
Pin 5 0 V (RS232 and RS485)
Pin 6 N/C or +IO (RS485) Port 2 only
Pin 7 RTS Request to send
Pin 8 CTS Clear to send
Pin 9 NC
Pin 10 NC


Kingfisher PLUS+Hardware Manual 6.0 www.cse-semaphore.com/mykingfisher Page 42

1.11 BAX-6: 6 Slot Backplane for LNA-6 Module
The 6-slot backplane is designed to accommodate four (4) LNA-6 modules and an optional power
supply module in the far left slot location.

There are two connectors in the far right position that provide access to the UF signals that are bussed
along the backplane to each of the module positions. A third connector (6 way) on the far right is for
the external power supply input (+5 V).

This backplane is designed for surface mounting. Mounting brackets (2 pieces) are supplied for user
fitting.




Figure: Backplane Mounting Details - BAX-6
Kingfisher PLUS+Hardware Manual 6.0 www.cse-semaphore.com/mykingfisher Page 43

External Connections
J5 Power
Pin 1 NC
Pin 2 +5 V Supply
Pin 3 0 V
Pin 4 0 V
Pin 5 NC
Pin 6 NC


J9 - VF Signal Interface (Mini DIN-8)
Pin 1 CTS - Clear to send
Pin 2 0 V - Signal ground
Pin 3 NC
Pin 4 TXA - Transmit analog (-10 dBm)
Pin 5 NC
Pin 6 PTT - Request to send (Press to talk)
Pin 7 CD - Carrier data detect
Pin 8 RXA - Receive analog (-10 dBm)


J9 - VF Signal Interface (Mini DIN-8)
Pin 1 TXA - Transmit Analog (-100 dBm)
Pin 2 PTT - Request to send (Press to talk)
Pin 3 CTS - Clear to send
Pin 4 0 V - Signal ground
Pin 5 0 V - Signal ground
Pin 6 +5 V
Pin 7 +5 V
Pin 8 GND Chassis ground
Pin 9 GND Chassis ground
Pin 10 +5 V
Pin 11 +5 V
Pin 12 0 V - Signal ground
Pin 13 0 V - Signal ground
Pin 14 CD - Carrier data detect
Pin 15 RXA - Receive analog (-10 dBm)

NOTE: PTT, CTS and CD are active low referred to 0 V
Kingfisher PLUS+Hardware Manual 6.0 www.cse-semaphore.com/mykingfisher Page 44

1.12 BA-4: 4 Slot Backplane
The superseded BA-4 backplane uses Harwin data connectors for linking backplanes. The newer
revision BA-4 PLUS backplane uses Phoenix data connectors.

A BA-4 backplane is designed to be used with a PC-1 power and processor module. The PC-1 is
installed in the left slot and any IO or communications modules can be installed in the other 3 slots.

The BA-4 has connections for an external DC power supply and a second socket (J 5) is provided for
the PC-1 to be installed in the left hand slot.

Please use a BA-40 backplane if requiring a 4 slot backplane for use with a CP-xx processor and PS-
xx power supply.

The 4-slot backplane is designed for surface mounting. Mounting brackets (2 pieces) are supplied for
user fitting.


102
36
DETAIL
174
176
7
10
156
194
176
J 5
SL9


Dimensions shown in
millimetres

BA-4 External Connections
J14 Power Socket

24 V
5 V
0 V
12 V
PCON Power Control
0 V
.
.
. .
.
.


J13 (in), J15 (out) Inter-rack Harwin Data Sockets

IO Link IO+
Comms link CM+
Signal Ground GND
IO link IO-
.

.

.

.

.

.

. .
CM- Comms Link
GND Signal ground
CSR Processor Interrupt
PCON Power Control


Orange SL9 Socket
Kingfisher PLUS+Hardware Manual 6.0 www.cse-semaphore.com/mykingfisher Page 45


+24 V Aux. Supply Output (optional)
0 V Aux. Supply Output (optional)
+12 V To/From Battery
0 V To/From Battery
+12 V To Radio
0 V To Radio
+12 V Input Supply
0 V Input Supply
Earth
.
.
.
.
.
.
.
.
.

Kingfisher PLUS+Hardware Manual 6.0 www.cse-semaphore.com/mykingfisher Page 46

1.13 BA-40: 4 Slot Backplane
The superseded BA-40 backplane uses Harwin data connectors for linking backplanes. The newer
revision BA-40 PLUS backplane uses Phoenix data connectors.

A BA-40 backplane is the same as a BA-4 backplane except the J 5 (PC-1 lower connector) and SL-9
(PC-1 power) connectors have been removed. A BA-40 is designed to be used with a PS-xx power
supply and a CP-xx processor module or linked to any other backplane to provide additional slots.

The 4-slot backplane is designed for surface mounting. Mounting brackets (2 pieces) are supplied for
user fitting.


102
36
DETAIL
174
176
7
10
156
194
176


Dimensions shown in
millimetres


BA-40 External Connections
J14 Power Socket

24 V
5 V
0 V
12 V
PCON Power Control
0 V
.
.
. .
.
.



J13 (in), J15 (out) Inter-rack Harwin Data Sockets

IO Link IO+
Comms link CM+
Signal Ground GND
IO link IO-
.

.

.

.

.

.

. .
CM- Comms Link
GND Signal ground
CSR Processor Interrupt
PCON Power Control


Kingfisher PLUS+Hardware Manual 6.0 www.cse-semaphore.com/mykingfisher Page 47

1.14 BA-6: 6 Slot Backplane
The superseded BA-6 backplane uses Harwin data connectors for linking backplanes. The newer
revision BA-6 PLUS backplane uses Phoenix data connectors.

The BA-6 six slot backplane is designed to support any power supply, IO or communications module
in any slot position. A BA-6 is designed to be used with a PS-xx power supply and a CP-xx processor
module or linked to any other backplane to provide additional slots.

There are three (3) connectors at the far right of the backplane. There are two black 8-way Harwin
data connectors for linking backplanes together and there is one 6-way connector is for external power
(+5 V and +12 V DC) if a power supply module is not installed on the backplane.

This backplane is designed for surface mounting. Mounting brackets (2 pieces) are supplied for user
fitting.


102
36
DETAIL
174
176
7
10
228
266
248

Figure: BA-6 Dimensions (mm)


BA-6 External Connections
J14 Power Socket

24 V
5 V
0 V
12 V
PCON Power Control
0 V
.
.
. .
.
.


CAUTION: The 24 V and 12 V pins are shorted on early revision backplanes (prior to revision 1.3).
Early revision backplanes were designed for 24 V only.

J13 (in), J15 (out) Inter-rack Harwin Data Sockets

IO Link IO+
Comms link CM+
Signal Ground GND
IO link IO-
.

.

.

.

.

.

. .
CM- Comms Link
GND Signal ground
CSR Processor Interrupt
PCON Power Control

Kingfisher PLUS+Hardware Manual 6.0 www.cse-semaphore.com/mykingfisher Page 48

1.15 BA-12: 12 Slot Backplane
The superseded BA-12 backplane uses Harwin data connectors for linking backplanes. The newer
revision BA-12 PLUS backplane uses Phoenix data connectors.

The BA-12 twelve slot backplane is designed to support any power supply, IO or communications
module in any slot position. A BA-12 is designed to be used with a PS-xx power supply and a CP-xx
processor module or linked to any other backplane to provide additional slots.

There are three (3) connectors at the far right of the backplane. There are two black 8-way Harwin
data connectors for linking backplanes together and there is one 6-way connector is for external power
(+5 V and +12 V DC) if a power supply module is not installed on the backplane.

This backplane is designed for surface mounting. Mounting brackets (2 pieces) are supplied for user
fitting. Mounting in a 19" rack may be achieved using the alternative MBR-3 rack mounting brackets.


102
DETAIL
174
176
7
10
444
482
464
36

Figure: BA-12 Dimensions (mm)


BA-12 External Connections
J14 Power Socket

24 V
5 V
0 V
12 V
PCON Power Control
0 V
.
.
. .
.
.

CAUTION: The 24 V and 12 V pins are shorted on early revision backplanes (prior to revision 1.3).
Early revision backplanes were designed for 24 V only.


J13 (in), J15 (out) Inter-rack Harwin Data Sockets

IO Link IO+
Comms link CM+
Signal Ground GND
IO link IO-
.

.

.

.

.

.

. .
CM- Comms Link
GND Signal ground
CSR Processor Interrupt
PCON Power Control

Kingfisher PLUS+Hardware Manual 6.0 www.cse-semaphore.com/mykingfisher Page 49

1.16 DI-1: 12-24 Volt AC or DC Input, 16 Point
The DI-1 provides 16 input points in one group with common power input terminals. This input module
is designed to have either positive or negative logic characteristics in the DC input mode. Input
characteristics are compatible with a wide range of user-supplied input devices, such as: push
buttons, limit switches, and electronic proximity switches. Current into an input point results in a logic 1
in the input status table (#DI). The digital inputs are powered using an external power supply (the
module does not provide field power).

LED indicators that provide the ON/OFF status of each point are located at the top of the module. This
LED block has four vertical columns with four red LEDs in each column, the left two columns labelled
A1 through 8 (points 1 through 8) and the right two columns labelled B1 through 8 (points 9 through
16). An insert goes between the inside and outside surface of the hinged door. The surface towards
the inside of the module (when the hinged door is closed) has circuit wiring information, and circuit
identification information can be recorded on the outside surface. The outside left edge of the insert is
color-coded blue to indicate a low-voltage module. This module can be installed in any I/O slot of a 3,
4, 6 or 12 slot backplane system.


DI-1 Specifications
Rated Voltage +12 to 24 V AC/DC nominal (supports reverse polarity)
Inputs per Module 16 (two groups, each with separate common)
Isolation 3000 VRMS between field and logic
500 VRMS between channel groups
(Channel groups 1-8 and 9-16 are isolated from each other
provided that the commons for each group are not linked)
Input Current 4 mA (typical) at rated voltage
Input Characteristics:
On-state Voltage 11.5 to 30 VAC/DC
Off-state Voltage 0 to +4 VAC/DC
On-state Current 4.3 mA minimum
Off-state Current 1 mA maximum
On response Time 10 ms typical
Off response Time 17 ms typical
Operating Temperature -20 to 70 C
Storage Temperature -40 to 85 C
Operating Humidity 5 to 98% RH non-condensing
Kingfisher PLUS+Hardware Manual 6.0 www.cse-semaphore.com/mykingfisher Page 50

DI-1 Wiring Diagram


1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
CH 6
CH 1
CH 4
CH 2
CH 3
CH 5
CH 8
CH 7
0 V / Common Chs 1-8

CH 14

CH 9
CH 12
CH 10
CH 11
CH 13
CH 16
CH 15
FIELD CONTACT
CH x
0 V
External positive
power supply

+
Wiring Examples
FIELD CONTACT
External negative
power supply
-
POWER
SUPPLY
POWER
SUPPLY
CH x
0 V
-
+
CH x
0 V
+
-
POWER
SUPPLY
POWER
SUPPLY
CH y
-
+
Combined positive
and negative power
supplies

0 V / Common Chs 1-8
0 V / Common Chs 9-16
0 V / Common Chs 9-16

Kingfisher PLUS+Hardware Manual 6.0 www.cse-semaphore.com/mykingfisher Page 51

1.17 DI-2: 48 Volt AC or DC Input, 16 Point
The DI-2 48 volt DC input module provides 16 input points in one group with a common power input
terminal. This input module is designed to have either positive or negative logic characteristics in the
DC input mode. This input module is designed to function with DC user inputs. Input characteristics
are compatible with a wide range of user-supplied input devices, such as: push buttons, limit switches,
and electronic proximity switches. Current into an input point results in a logic 1 in the input status
table (#DI). Power to operate the field devices must be supplied by the user.

LED indicators which provide the ON/OFF status of each point are located at the top of the module.
This LED block has four vertical columns with four red LEDs in each column, the left two columns
labelled A1 through 8 (points 1 through 8) and the right two columns labelled B1 through 8 (points 9
through 16). An insert goes between the inside and outside surface of the hinged door. The surface
towards the inside of the module (when the hinged door is closed) has circuit wiring information, and
circuit identification information can be recorded on the outside surface. The outside left edge of the
insert is color-coded blue to indicate a low-voltage module. This module can be installed in any I/O slot
of a 4, 6 or 12 slot backplane system.


DI-2 Specifications
Rated Voltage 48 VAC or DC
Input Voltage Range 0 to 60 VAC or DC
Inputs per Module 16 (two groups, each with separate common)
Isolation 3000 VRMS between field and logic
500 VRMS between channel groups
(Channel groups 1-8 and 9-16 are isolated from
each other provided that the commons for each
group are not linked)
Input Current 4 mA (typical) at rated voltage
Input Characteristics On-state Voltage 23 to 60 VDC
Off-state Voltage 0 to 20 VDC
On-state Current 4.8 mA minimum
Off-state Current 2.2 mA maximum
On response Time 10 ms maximum
Off response Time 17 ms maximum
Operating Temperature -20 to 70 C
Storage Temperature -40 to 85 C
Operating Humidity 5 to 98% RH non-condensing
Kingfisher PLUS+Hardware Manual 6.0 www.cse-semaphore.com/mykingfisher Page 52

DI-2 Wiring Diagram


1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
CH 6
CH 1
CH 4
CH 2
CH 3
CH 5
CH 8
CH 7
0 V / Common Chs 1-8

CH 14

CH 9
CH 12
CH 10
CH 11
CH 13
CH 16
CH 15
FIELD CONTACT
CH x
0 V
External positive
power supply

+
Wiring Examples
FIELD CONTACT
External negative
power supply
-
POWER
SUPPLY
POWER
SUPPLY
CH x
0 V
-
+
CH x
0 V
+
-
POWER
SUPPLY
POWER
SUPPLY
CH y
-
+
Combined positive
and negative power
supplies

0 V / Common Chs 1-8
0 V / Common Chs 9-16
0 V / Common Chs 9-16

Kingfisher PLUS+Hardware Manual 6.0 www.cse-semaphore.com/mykingfisher Page 53

1.18 DI-3: 120 Volt AC Input, 16 Point
The DI-3 120 volt AC input module provides 16 input points with two common power input terminals.
The input circuits are reactive (resistor/capacitor) inputs. Current into an input point results in a logic 1
in the input status table (#DI). Input characteristics are compatible with a wide range of user-supplied
input devices, such as: push buttons, limit switches and electronic proximity switches. Power to
operate the field devices must be supplied by the user. This module requires an AC power source; it
cannot be used with a DC power source for field inputs.

LED indicators that provide the ON/OFF status of each point are located at the top of the module. This
LED block has four vertical columns with four red LEDs in each column, the left two columns labelled
A1 through 8 (points 1 through 8) and the right two columns labelled B1 through 8 (points 9 through
16). An insert goes between the inside and outside surface of the hinged door. The surface towards
the inside of the module (when the hinged door is closed) has circuit wiring information, and circuit
identification information can be recorded on the outside surface. The outside left edge of the insert is
color-coded red to indicate a high-voltage module. This module can be installed in any I/O slot of a 3,
4, 6 or 12 slot backplane system.


DI-3 Specifications
Rated Voltage 120 VAC
Input Voltage Range 0 to 132 VAC, 50/60 Hz
Inputs per Module * 16 (two groups, each with separate common)
Isolation 3000 VRMS between field and logic
500 VRMS between channel groups
(Channel groups 1-8 and 9-16 are isolated from
each other provided that the commons for each
group are not linked)
Input Current 12 mA (typical) at rated voltage
Input Characteristics On-state Voltage 74 to 132 VAC
Off-state Voltage 0 to 20 VAC
On-state Current 6 mA minimum
Off-state Current 2.2 mA maximum
On response Time 15 ms maximum
Off response Time 34 ms maximum
Operating Temperature -20 to 70 C
Storage Temperature -40 to 85 C
Operating Humidity 5 to 98% RH non-condensing
* Number of inputs on is dependent upon ambient temperature as shown below
Kingfisher PLUS+Hardware Manual 6.0 www.cse-semaphore.com/mykingfisher Page 54

DI-3 Wiring Diagram
There are two isolated input groups. Each group of 8 channels can be powered by a separate AC
source.

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
CH 6
CH 1
CH 4
CH 2
CH 3
Wi ri ng Exampl e
CH 5
CH 8

CH 7
Common For Chs 1-8
CH 14

CH 9
CH 12
CH 10
CH 11
CH 13
CH 16

CH 15
FIELD CONTACT
CH x
Common
+
Common For Chs 1-8
Common For Chs 9-16
Common For Chs 9-16
74-132 V AC
External power supply
POWER
SUPPLY




DI-3 Output Characteristics
-20
AMBIENT TEMPERATURE (DegC)

NUMBER
OF INPUTS
ON
0 20 40 60 80
0
4
8
12
16

Kingfisher PLUS+Hardware Manual 6.0 www.cse-semaphore.com/mykingfisher Page 55

1.19 DI-4: 240 Volt AC Input, 16 Point
The DI-4 240 volt AC input module provides 16 input points with two common power input terminals.
The input circuits are reactive (resistor/capacitor) inputs. Current into an input point results in a logic 1
in the input status table (#DI). Input characteristics are compatible with a wide range of user-supplied
input devices, such as: push buttons, limit switches and electronic proximity switches. Power to
operate the field devices must be supplied by the user. This module requires an AC power source; it
cannot be used with a DC power source.

LED indicators that provide the ON/OFF status of each point are located at the top of the module. This
LED block has four vertical columns with four red LEDs in each column, the left two columns labelled
A1 through 8 (points 1 through 8) and the right two columns labelled B1 through 8 (points 9 through
16). An insert goes between the inside and outside surface of the hinged door. The surface towards
the inside of the module (when the hinged door is closed) has circuit wiring information, and circuit
identification information can be recorded on the outside surface. The outside left edge of the insert is
color-coded red to indicate a high-voltage module. This module can be installed in any I/O slot of a 4,
6 or 12 slot backplane system.


DI-4 Specifications
Rated Voltage 240 VAC
Input Voltage Range 0 to 264 VAC, 50/60 Hz
Inputs per Module * 16 (two groups, each with separate common)
Isolation 3000 VRMS between field and logic
500 VRMS between channel groups
(Channel groups 1-8 and 9-16 are isolated from
each other provided that the commons for each
group are not linked)
Input Current 12 mA (typical) at rated voltage
Input Characteristics On-state Voltage 148 to 264 VAC
Off-state Voltage 0 to 40 VAC
On-state Current 6 mA minimum
Off-state Current 2.2 mA maximum
On response Time 15 ms maximum
Off response Time 34 ms maximum
Operating Temperature -20 to 70 C
Storage Temperature -40 to 85 C
Operating Humidity 5 to 98% RH non-condensing
* Number of inputs on is dependent upon ambient temperature as shown below.
Kingfisher PLUS+Hardware Manual 6.0 www.cse-semaphore.com/mykingfisher Page 56

DI-4 Wiring Diagram

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
CH 6
CH 1
CH 4
CH 2
CH 3
Wi ri ng Exampl e
CH 5
CH 8

CH 7
Common For Chs 1-8
CH 14

CH 9
CH 12
CH 10
CH 11
CH 13
CH 16

CH 15
FIELD CONTACT
CH x
Common
+
Common For Chs 1-8
Common For Chs 9-16
Common For Chs 9-16
148-264 V AC
External power supply
POWER
SUPPLY




DI-4 Output Characteristics
-20
AMBIENT TEMPERATURE (DegC)

NUMBER
OF INPUTS
ON
0 20 40 60 80
0
4
8
12
16

Kingfisher PLUS+Hardware Manual 6.0 www.cse-semaphore.com/mykingfisher Page 57

1.20 TEL REL 001: DPDT Relay Board For DO-5
The TEL REL 001 16-point relay board provides 16 DPDT voltage free output contacts, each rated at
5 A AC/DC. The relay board is connected to a DO-5 digital output module using a standard cable.

Each relay consumes 30 mA @ +12 VDC or 15 mA @ +24 VDC backplane supply. An external supply
can be connected to a screw terminal on the PCB if required (not if used with the standard cable
supplied with the DO-5 module).

LED indicators are provided for each relay on the relay board: LED ON =relay active.


Relay Board - TEL REL 001 Specifications
Outputs per Terminal Board 16
Commons 32 (2 commons per channel)
Relay Type (per channel) DPDT (Double Pole, Double Throw)
Rated Load (per contact) 5 A at 250 VAC Resistive
5 A at 30 VDC Resistive
Maximum Current 5 A
Maximum Operating Voltage 380 VAC, 125 VDC (2 A max.)
Maximum Switching Power 750 VA, 90 W Resistive
Minimum Load 10 mA at 5 VDC
Contact Resistance 50 m maximum
Relay Operations >10,000,000
Operating Temperature -20 to 70 C (no icing)
Humidity 5 to 98% RH non-condensing
Isolation 5 kV coil to contacts
Coil Rated Voltage 12 VDC @ 40 mA/coil
24 VDC @ 15 mA/coil
Coil Resistance 400 @ 12 V or 1600 @ 24 V
Dimensions 253 mm(L) x 90 mm(W) x 70 mm(H)
(280 mm long with 2 end clamps)
Mounting 35 mm DIN rail
Interface cable length
(for connection to the DO-5 module)
0.8 m to 3.0 m (made to order)
CAUTION! Contacts should be protected with appropriate suppression devices when wired with inductive loads to
increase life of relays (please see DO-1 Switching Inductive Loads). Contacts should also be protected with
external fusing.
Kingfisher PLUS+Hardware Manual 6.0 www.cse-semaphore.com/mykingfisher Page 58

Relay Board - TEL REL 001 Wiring Diagram
CH 1
CH 2
CH 3
CH 4
CH 5
CH 6
CH 7
CH 8
CH 9
CH 10
CH 11
CH 12
CH 13
CH 14
CH 15
CH 16


NO (a) - Normally open contact
C (a) - Common
NC (a) - Normally closed contact
NO (b)
C (b)
NC (b)
External Power
Supply. Note:
polarity can be
reversed.
NO (a) LOAD
C (a) +
Wiring Example
POWER
SUPPLY
When the output
channel is set ON,
the load is
energised
Terminal Layout For Each DO-5 Channel
There are two sets of relay outputs
for each channel (i.e. DPDT )

Kingfisher PLUS+Hardware Manual 6.0 www.cse-semaphore.com/mykingfisher Page 59

Interface Cable DO-5 To TEL REL 00x Relay Board
To DO-5 Module
Fujicon
Connector
Panduit 20-way
socket (1x20)
2
4
6
8
10
12
14
16
18
20
1
3
5
7
9
11
13
15
17
19
20
1

To TEL-REL-00x
Relay Board
Panduit 20-way
header
Belden 9431
Cable Color
Fujicon
Pin DO-5
Multi-core cable
Belden 9431 cabl e
Relay Board
Panduit 20-way
Header
Black 1 CH1

1 CH1
White 2 CH2 2 CH2
Red 3 CH3 3 CH3
Green 4 CH4 4 CH4
Orange 5 CH5 5 CH5
Blue 6 CH6 6 CH6
White/Black 7 CH7 7 CH7
Red/Black 8 CH8 8 CH8
Green/Black 9 0 V 9 0 V
Orange/Black 10 0 V 10 0 V
Blue/Black 11 CH9 11 CH9
Black/White 12 CH10 12 CH10
Red/White 13 CH11 13 CH11
Green/White 14 CH12 14 CH12
Blue/White 15 CH13 15 CH13
Black/Red 16 CH14 16 CH14
White/Red 17 CH15 17 CH15
Orange/Red 18 CH16 18 CH16
Blue/Red 19 +12 V 19 +12 V
Green/Red 20 +12 V 20 +12 V

Kingfisher PLUS+Hardware Manual 6.0 www.cse-semaphore.com/mykingfisher Page 60

1.21 AI-4: Analog Current Input, 8 Channel (Flying
Capacitor)
The AI-4 module provides eight individually isolated input channels, each capable of converting an
analog input signal to a digital signal for use as required by your application. This module provides two
input ranges. The default range is 4 to 20 mA with user data scaled so that 4 mA corresponds to a
count of 0 and 20 mA corresponds to a count of 32760 with each 1000 counts representing 0.5 A. A
link on the rear of the module selects 4-20 mA or 0-20 mA for all channels.

Conversion speed for each of the eight channels is 250 ms. By default the update rate is 8 seconds
but can be configured in the range of 1-10 seconds. Resolution of the converted signal is 12 bits
binary (1 part in 4096) over the range. User data in the #AI registers is in 16-bit 2'x complement
format. The placement of the 12 bits from the A/D converter in the #AI data word is shown below.

MSB LSB
0 D11 D10 D9 D8 D7 D6 D5 D4 D3 D2 D1 D0 0 0 0

If the current source is reversed into the input, or is less than the low end of the current range, then
the module will output a data word corresponding to the low end of the current range (0000H in #AI). If
an input that is out of range is entered (i.e. greater than 20 mA), the A/D converter will output up to full
scale (corresponding to 7FF8H in #AI).

Scaling of the input is shown below.

32760
0
0 4 20
Current (mA)
(4 to 20 mA range)

Raw
Value
(decimal)
32760

0

0

20
Current (mA)
(0 to 20 mA range)


Raw
Value
(decimal)


Figure: AI-4 Scaling for Analog Current 4 to 20 mA


Input protection for the module is sufficient to guarantee operation with reduced performance with up
to 1500 V common-mode. The module provides electrical isolation of externally generated noise
between field wiring and the backplane through the use of flying capacitor relay scanning system.

To minimise the capacitive loading and noise, all field connections to the module should be wired
using a good grade of twisted, shielded instrumentation cable. The shields can be connected to GND.
The GND connection provides access to the backplane (frame ground).


Kingfisher PLUS+Hardware Manual 6.0 www.cse-semaphore.com/mykingfisher Page 61

Link for 4-20 mA
operation. Remove
for 0-20 mA
operation.

Factory default:
Link installed


Figure: AI-4 Rear Module and Link Location

Eight red LEDs labelled A1 to A8 on the faceplate are ON when current is 1% above the input range
(i.e. 4.16 mA for 4-20 mA and 0.2 mA for 0-20 mA range). A green LED at the top of the faceplate is
ON when the module is operating correctly. This module also consumes power from the +5 VDC and
+12 VDC bus.

An insert goes between the inside and outside surface of the hinged door. The surface towards the
inside of the module (when the hinged door is closed) has circuit wiring information and circuit
identification information can be recorded on the outside surface. The outside left edge of the insert is
color-coded blue to indicate a low-voltage module.

This module can be installed in any I/O slot of a 4, 6 or 12 slot backplane in a system. Up to 10 Analog
Current Input modules can be installed in a backplane.


Kingfisher PLUS+Hardware Manual 6.0 www.cse-semaphore.com/mykingfisher Page 62

AI-4 Specifications
Input Current Ranges 4 to 20 mA and 0 to 20 mA
Input Voltage Ranges * 1 to 5 V and 0 to 5 V *
Inputs per Module 8
Calibration Factory calibrated to 5 A
Update Rate 1 to 10 s(all eight channels)
Scanning Life Expectancy
(for G6A-234P-ST relay)
100 million scans or 31.7 years @ 10 s update rate
Resolution 5 A (1 LSB =5 A)
Absolute Accuracy 0.1% full scale +0.1% reading
Common Mode Voltage 1500 V
Linearity <1 Least Significant Bit
Isolation 1500 VRMS between field and logic and between channels
Common Mode Rejection >70 dB at DC; >70 dB at 60 Hz
Cross-Channel Rejection >80 dB from DC to 1 kHz
Input Impedance 250
Input Filter Response 2 kHz
Operating Temperature -20 to 70 C
Storage Temperature -40 to 85 C
Operating Humidity 5 to 98% RH non-condensing

* Analog inputs can be modified from current inputs to voltage inputs by lifting one leg of the 250
channel resistor. Each channel has its own resistor, so any combination of channels can be converted.
If necessary, the response time of the analog input can be improved by replacing the 250 resistor
with a 100 K resistor. It is recommended that modules be returned to Semaphore for factory
conversion if required. No responsibility will be taken by Semaphore for damage caused to boards
during modification performed by clients. The circuit board resistors to change are: channels 1 - 8 =
R1 R8.

Kingfisher PLUS+Hardware Manual 6.0 www.cse-semaphore.com/mykingfisher Page 63

AI-4 Block Diagram
ADC
+5V
80C51 MICRO
CONTROLLER
LED DISPLAY
RS485
DRIVER
PROTECTION
AND FILTER
CH1
+
-
PROTECTION
AND FILTER
CH8
+
-




AI-4 Wiring Diagram
CH 7-


CH 3-


CH 1-


1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
CH 1+


CH 2+

CH 3+


CH 4+


CH 5+

CH 6+

CH 7+


CH 8+


SHIELD

SHIELD

SHIELD

SHIELD

Wi ri ng Exampl e
CH 2-

CH 4-


CH 5-

CH 6-

CH 8-


4-wire transmitter
(powered externally)
+
-
CH x+

CH x-

Analog
Input
PWR

POWER
SUPPLY
+
-
3-wire transmitter
(powered externally)
+
-
CH x+
CH x-

Analog
Input
PWR
POWER
SUPPLY
+
-
CH x+
2-wire transmitter
(powered externally)

CH x-
+
-
Analog
Input
POWER
SUPPLY
+
-


Kingfisher PLUS+Hardware Manual 6.0 www.cse-semaphore.com/mykingfisher Page 64

1.22 AO-2: Analog Current Output, 4 Channel
FEATURES

12-Bit Resolution

0-20 or 4-20 mA Outputs

1.5 kV Field to Logic Isolation

1.5 kV Channel Group to Channel
Group Isolation

The AO-2 provides four current output channels that use 12-bit digital to analog converter (DAC). The
sign bit is not used in the conversion process. The placement of the 12 bits within the data word is
shown below.

MSB LSB
0 D11 D10 D9 D8 D7 D6 D5 D4 D3 D2 D1 D0 0 0 0

If the module is sent data that is out of range (less than 0 or greater than 32767), the software does
not accept the value.

This module provides two output ranges. The default range is 4 to 20 mA with user data scaled so that
a count of 0 corresponds to 4 mA and a count of 32760 corresponds to 20 mA. A range link (on the
rear of the module) selects either 4-20 mA or 0-20 mA for all four channels. The default condition is 4-
20 mA with the link on. The module provides 12 bits of resolution in either range. Scaling of the output
is as shown below.

32760
0
0 4 20
Current (mA)
(4 to 20 mA range)

Raw
Value
(decimal)
32760

0

0

20
Current (mA)
(0-20 mA range)


Raw
Value
(decimal)


Figure: AO-2 Scaling for Current Output

Analog outputs 1 & 2 and analog outputs 3 & 4 form two groups that are isolated from each other and
from the backplane logic. Each group is powered by a separate DC-DC converter module that
produces an isolated voltage of +24 V to drive the current loop outputs and analog front-end.

The current loop drivers on the module are source type drivers. To minimize the capacitive loading
and noise, all field connections to the module should be wired using a good grade of twisted, shielded
instrumentation cable. The shields should be connected to E (Shield) on the user terminal connector
block. The E connection provides path to the backplane (frame Earth / Ground) resulting in attenuation
of noise caused by the shield drain currents. To further improve noise immunity, direct connection of
the analog cable shields to the Earth / Ground rails with metal clamps or similar method is
recommended, especially in environments with high electromagnetic noise levels.

This module can be installed in any I/O slot of a 4, 6 or 12 slot backplane in a system.

Kingfisher PLUS+Hardware Manual 6.0 www.cse-semaphore.com/mykingfisher Page 65

Link for 4-20 mA
operation. Remove
for 0-20 mA
operation.

Factory default:
Link installed

Figure: AO-2 Rear Module and Link Location


Module LEDs
OK
A
1
AO-2
B
2
C
3
D
4
FU


LED State Description
OK OFF Module fault (no power)
ON Normal
FU OFF Not used. Always OFF
A1, B2,
C3, D4
OFF Channel output level <1%
ON Channel output level >1%


AO-2 Load Current Characteristics (24 V Out)

80 mA
0 50
Ambient Temperature (Deg C)
Load Current
-20


Kingfisher PLUS+Hardware Manual 6.0 www.cse-semaphore.com/mykingfisher Page 66

AO-2 Specifications
Output Current Range 4 to 20 mA and 0 to 20 mA
Outputs per Module 4
Output Power Isolated 24 VDC @ 40 mA for outputs 1 & 2
Isolated 24 VDC @ 40 mA for outputs 3 & 4
Calibration Factory calibrated to 5 A pe r count
Supply Voltage (nominal) +5 VDC and +12 VDC backplane
Update Rate 250 ms (all channels) Determined by I/O scan time and is application
dependent
Resolution 12 bit (no sign bit)
Accuracy +0.2% @ 25 C. +0.5% @ -20 to 70 C
User Load 0 to 850
Output Load Capacitance 2000 pF
Output Load Inductance 1 H
Isolation Analog outputs 1 & 2 and analog outputs 3 & 4 form two groups.
Each group is isolated from the other group and from the backplane
logic. There is no isolation between outputs 1 & 2 and no isolation
between outputs 3 & 4.
Transient voltage (Group to Group and Group to Logic): 1.5 kV
Operating Temperature -20 to 70 C
Storage Temperature -40 to 85 C
Operating Humidity 5 to 98% RH non-condensing
Hot Swap Yes. Module can be swapped while RTU is running. Hot swap will not
cause a Warm Start. Outputs will be restored within 2 seconds once
module is replaced.
Open Loop Detection Not supported. Please see AO-3.


Kingfisher PLUS+Hardware Manual 6.0 www.cse-semaphore.com/mykingfisher Page 67

AO-2 Wiring Diagram

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

Wiring


CH 2 +

CH 1+

CH 1 -

SHIELD

CH 2 -

SHIELD

CH 4+

CH 3+

CH 3 -

SHIELD

CH 4 -

SHIELD

CH x +

CH x -

SHIELD

0-20 / 4-20 mA
Current Loop
Receiver

+
-
Analog
Load


Kingfisher PLUS+Hardware Manual 6.0 www.cse-semaphore.com/mykingfisher Page 68

1.23 RT-1: Analog RTD Input, 4 Channel
The RT-1 RTD input module provides four input channels for Pt100 Resistance Temperature Devices,
each capable of converting the 100 (DIN standard) temperature sensor to a digital signal for use as
required by your application. Modules are available in the standard range of -150 to 400C or can be
manufactured to special order with minimum 100C span in the -150 to 400C range.

Conversion speed for each of the four channels is 20 S and this provides a maximum update rate of
two milliseconds for the module. Resolution of the converted signal is 12 bits binary (1 part in 4096)
over the range. The placement of the 12 bits from the A/D converter in the #AI data word is shown
below. The relationship between the temperature and the data from the A/D converter is shown in the
figure below.

MSB LSB
0 D11 D10 D9 D8 D7 D6 D5 D4 D3 D2 D1 D0 0 0 0

The input circuit features a constant current RTD excitation using the third lead of the RTD to sense
and compensate for the RTD lead resistance, resulting in an accurate RTD temperature
measurement. The RTD voltage is then amplified and fed to the 12-bit ADC. The module is factory
calibrated to provide 0.1% resolution of span.

To ensure accurate operation each input is factory calibrated using Toolbox 32 software. The
calibration is stored in EPROM on the RT-1 and is therefore non-volatile.


32760
0 400
DegC

Raw Value
-150
-
1
5
0


t
o

4
0
0

D
e
g
C



Figure: RT-1 Scaling


Input protection for the module is sufficient to guarantee operation with reduced performance with up
to 1500 V common-mode. The module provides electrical isolation of externally generated noise
between field wiring and the backplane through the use of optical isolation.

To minimise the capacitive loading and noise, all field connections to the module should be wired
using a good grade of twisted, shielded instrumentation cable. The shields can be connected to E. The
E connection provides access to the backplane (frame ground).

Four red LEDs labelled A1 to A4 on the faceplate are ON when an RTD is connected. A green LED at
the top of the faceplate is ON when the module is operating correctly. This module also consumes
power from the +5 VDC and 12 VDC bus. A 24 VDC isolated converter is used to provide power to the
RTD conditioning and ADC circuits. This module can be installed in any I/O slot of a 4, 6 or 12 slot
backplane in a system. Up to 10 RTD modules can be installed in a backplane.


Kingfisher PLUS+Hardware Manual 6.0 www.cse-semaphore.com/mykingfisher Page 69

RT-1 Specifications
RTD Type
Pt100, 100 , 0.00385 ohm/ohm/C (DIN
standard)
Range -150 to +400 C Standard
-50 to +150 C (Special order)
0 to +100 C (Special order)
Other ranges within the Standard range (-150 to
+400 C) can be supplied on request.
Inputs per Module 4
Leadwire Resistance 40 maximum
Leadwire Effect Less than 1% of span error
Accuracy 0.1% (+/- 0.5 C)
Resolution 12 bit (no sign bit)
Update Rate 2 msec (all four channels)
Response Time 100 msec typical
Common Mode Voltage 1500 V
Isolation 3000 VRMS between field and logic
Common Mode Rejection >70 db from DC to 60 Hz
Cross-Channel Rejection >80 db from DC to kHz
Operating Temperature -20 to 70 C
Operating Humidity 5 to 98% RH non-condensing
Storage Temperature -40 to +85 C



Kingfisher PLUS+Hardware Manual 6.0 www.cse-semaphore.com/mykingfisher Page 70

RT-1 Block Diagram
+24V
80C51 MICRO
CONTROLLER
LED DISPLAY
RS485
DRIVER
OPTO
ISOLATION
DC/DC
+5V
RANGE SWITCH
0-20 OR 4-20mA
REF
ADC
CH1
PT100
BRIDGE
CH2
PT100
BRIDGE
CH3
PT100
BRIDGE
CH4
PT100
BRIDGE


RT-1 Wiring Diagram
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
CH 1

CH 2

SHIELD

RTD
RTD
SHIELD

CH 3

CH 4

SHIELD

RTD
RTD
SHIELD



Kingfisher PLUS+Hardware Manual 6.0 www.cse-semaphore.com/mykingfisher Page 71

1.24 COMMS OPTION S: Serial Option Board
The non-isolated serial option board provides is best suited for RS232C communications. It is
recommended that the isolated serial option board be used for RS422 or RS485 communications.



Serial Option Board Specifications
Baudrate 300 115200 bps
Internal Power Consumption 15 mA from +5 VDC Bus on backplane
Output Power +4.3 V @ 100 mA max.
RS422 Line drive 10 Receivers
RS485 Line drive 32 Receivers
Communications 8 data bits, no parity, 1 stop (8, N, 1)
Isolation None
Operating Temperature -20 to 70 C
Storage Temperature -40 to 85 C
Operating Humidity 5 to 98% RH non-condensing
RTU Hardware Required Can be installed in any of the following ports:
CP-10/11/21/30 Port 2 or Port 3
MC-10/11/30/31 Port 2 or Port 3
LP-1/2 Port4
LP-3 Port 3 or Port 4


Serial Option Board Connections
RJ45 Pin Direction RS232C

RJ45 Socket RJ45 Plug
87654321
12345678
GREEN / WHITE 1
GREEN 2
ORANGE / WHITE 3
BLUE 4
BLUE / WHITE 5
ORANGE 6
BROWN / WHITE 7
BROWN 8
TIA/EIA-568-B
Telecommunications
Standard
T568A Wiring
Standard

1 OUT DTR
2 OUT 4.3 V
3 OUT RTS
4 IN DCD
5 COM GND (0 V)
6 IN CTS
7 IN RXD
8 OUT TXD


RS232 Wiring Diagram (Null Modem Cable)
Maximum RS232 Wire Length: 15 m.

TXD
GND
CTS
RXD
RTS
RTU SERIAL
PORT
TXD
GND
CTS
RXD
RTS
RTU SERIAL
PORT

Kingfisher PLUS+Hardware Manual 6.0 www.cse-semaphore.com/mykingfisher Page 72

1.25 COMMS OPTION Z: 2400 bps Dial Option Board
The Z dial option board provides a V22 PSTN interface. The port speed is software configurable. The
dial option board is designed to be compliant with British standards that are also used in Australia and
Hong Kong.

Telecommunication Line Cord

CAUTION
To reduce the risk of fire, use only No. 26 AWG or larger telecommunication line cord



Dial Option Board Connections
RJ45 Pin PSTN Function

RJ45 Socket RJ45 Plug
87654321
12345678
GREEN / WHITE 1
GREEN 2
ORANGE / WHITE 3
BLUE 4
BLUE / WHITE 5
ORANGE 6
BROWN / WHITE 7
BROWN 8
TIA/EIA-568-B
Telecommunications
Standard
T568A Wiring
Standard

1 -
2 -
3 Reserved
4 Line -
5 Line +
6 Reserved
7 -
8 -


Dial Option Board Specifications
PSTN Modem / Data Rate V.22, 600 to 2400 bps
RTU DTE Port Speed 300 115200 bps
Line Impedance 600
Approval International
Transmit level -10 dBm
Receive level -43 dBm to - 9 dBm
Dialling Pulse or Tone
Internal Power Consumption 175 mA from +5 VDC Bus on backplane
Isolation Maximum working voltage in respect to system
earth/ground must not exceed TNV-2 limits (80 V)
Transient voltage: 5 kV
Recommended Initialisation String Z Option: AT&FE0V0S0=2&C1&W
Operating Temperature -20

to 70 C
Storage Temperature -40

to 85 C
Operating Humidity 5 to 98% RH non-condensing
RTU Hardware Required Can be installed in any of the following ports:
CP-10/11/21/30 Port 2 or Port 3
MC-10/11/30/31 Port 2 or Port 3
LP-1/2 Port4
LP-3 Port 3 or Port 4
* Original dial circuit board is labelled S2-DOB REV 1.0 and did not have a second soldered-on circuit board.
Kingfisher PLUS+Hardware Manual 6.0 www.cse-semaphore.com/mykingfisher Page 73

1.26 MODEM BOARD M: 4-Wire Line Option Board
The line option board provides a supports communications over 2 and 4-wire leased line circuits. This
option board is designed for use with a PC-1 or MC-1.

The unit can be connected to perform the following functions:
2 wire point-to-point
2 wire multi-drop
4 wire point-to-point
4 wire multi-drop



4-Wire Line Option Board Specifications
Data Rates and Modulation 1200 Bps CCITT V.23FSK
Data Pump SSI312
Equaliser (adaptive) Y
Transmit Level -10 dBm in 2x 600
Scrambler/Descrambler Y
Receive Level 0 dBm to -43 dBm
Data Formats Asynchronous
Bit Error Rate (BER) 10
-6
@ S/N 22 dB
Connection 2 or 4 wire RJ 12
Termination 600 at each end of line per pair
Line Isolation 4 kV
Line drive in multidrop configuration 10 drops for 2 wire
20 drops for 4 wire


4-Wire Line Option Board Connections
4-Wire Line
Function
RJ12 Pin

RJ12 Socket RJ12 Plug
654321
BLUE 1
YELLOW 2
GREEN 3
RED 4
BLACK 5
WHITE 6
123456

Tx - 2
Rx - 3
Rx + 4
Tx + 5


4-Wire Line Option Board Wiring Diagrams
Please see CP-xx Line Option Board wiring diagrams.
Kingfisher PLUS+Hardware Manual 6.0 www.cse-semaphore.com/mykingfisher Page 74

1.27 CP-21 GPS Option Board
The GPS (Global Positioning System) option board is designed for use in a CP-21 and allows the RTU
to determine its location and synchronize its clock to universal time anywhere in the world. Location
and time information is obtained by connecting a GPS antenna to the option board SMB-F connector
which then allows the option board to communicate with nearby satellites.


GPS Option Board Specifications
Baudrate 19200 bps
Data Format 8 data bits, no parity, 1 stop
Max. Update Rate 1 Hz
Typical Acquisition Time 60 seconds (first time powered up)
2-6 seconds (powered down for <2hrs)
Operational Limits Altitude <60,000 ft
Position Accuracy Approx. 5 m
Antenna Type Passive
Option Board Antenna Socket SMB Female. Antenna cable requires an SMB Male
connector to connect.
Antenna Cable RG174 0-7 m cable runs
RG58 0-20 m cable runs
RG213 0-60 m cable runs
Available Data Position (degrees and minutes of latitude and longitude)
Time (hours, minutes and thousandths of seconds)
Altitude
Number of available satellites
Internal Power Consumption 140 mA from +5 VDC Bus on backplane
Operating Temperature -20 to 70 C
Storage Temperature -40

to 85 C
Operating Humidity 5 to 98% RH non-condensing

Kingfisher PLUS+Hardware Manual 6.0 www.cse-semaphore.com/mykingfisher Page 75

1.28 DO-5: Relay Driver Output, 16 Channel
FEATURES

16 Open Drain Outputs - designed to
operate the TEL REL 00x relay board

DC Output for Powering Output
Circuits

The DO-5 provides 16 output circuits for controlling the TEL REL 00x relay board. Power for the
external relay circuits is provided by the module from the +12 VDC bus on the backplane. A maximum
of three pairs of DO-5 modules and TEL REL 00x relay boards can be used per PS-xx power supply.
Additional pairs of DO-5 modules and TEL REL 00x relay boards can be used if the TEL REL 00x
relay boards are powered by an external source.

The insert in the hinged cover of the terminal strip has circuit wiring information. Circuit identification
information can be recorded on the outside surface of the insert. The outside left edge of the insert is
color-coded red to indicate a high-voltage module.


Module LEDs
OK
1 5
2 6
DO-5
9 13
10 14
3 7
4 8
11 15
12 16


LED State Description
OK OFF Module fault (no power)
ON Normal
A1-A16 OFF Digital output OFF (open)
ON Digital output ON (closed)


Kingfisher PLUS+Hardware Manual 6.0 www.cse-semaphore.com/mykingfisher Page 76

DO-5 Specifications
Outputs per Module 16
Commons 1
Rated Voltage 12 VDC
Operating Voltage 5 to 32 VDC
Output Type N-FET, Open Drain
Isolation None
Maximum Load 100 mA per channel
Output Power 12 VDC @ 1.6 A, non-isolated, supplied by module
On Response Time 15 ms maximum
Off Response Time 15 ms maximum
Operating Temperature -20 to 70 C
Storage Temperature -40 to +85 C
Operating Humidity 5 to 98% RH non-condensing
Hot Swap Yes. Module can be swapped while RTU is running. Hot swap
will not cause a Warm Start. Outputs will be restored within 2
seconds once module is replaced.



DO-5 Wiring Diagram
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
CH 1
CH 3
CH 6
CH 8
0 V
CH 2
CH 4
CH 5
CH 7
CH 9
CH 11
CH 14
CH 16
CH 10
CH 12
CH 13
CH 15
0 V
+12 V Output
+12 V Output
External DC
Power Supply
CH x
0 V
+

Wi ri ng Exampl es
LOAD
POWER
SUPPLY
+12 V Output
LOAD
CH x
+

Load powered by
DO-5 module
+

When output is energised, output channel is
shorted to the 0 V terminal.
INTERNAL
CIRCUITRY


Kingfisher PLUS+Hardware Manual 6.0 www.cse-semaphore.com/mykingfisher Page 77

1.29 PS-11: AC Supply Input 100 to 240 VAC
FEATURES

Monitoring - battery and input supply

AC Input Supply



Redundancy - two or more power
supplies per backplane

DC Input Supply

Isolated DC Output

Low Voltage Battery Protection

The PS-11 power supply provides AC to DC conversion for the backplane, battery and radio (or an
external device), a monitoring processor and an optional isolated 24 VDC output.

Fire Risk

CAUTION
A supply voltage outside the specified limits may cause fire.

Electrical Hazard

CAUTION
Only appropriately qualified and trained personnel can install and service this
equipment.
Mains Power must be connected in accordance with local national wiring rules and
regulations. Building installation shall provide appropriate short-circuit backup protection.
Always remove input mains voltage (by disconnecting power cord from the mains power
outlet or by switching off an external circuit breaker, depending on installation) before
performing any operation on this product. Failure to do so may cause fire and may result
in a serious personnel injury or even death.
Disconnect power cord from the Power Supply Module before wiring, removing or
servicing.

An isolated 24 VDC output rated at 10 W (400 mA) is an option available for powering a limited
number of analog loops or digital circuits. It cannot be used with inductive loads such as coils,
contactors etc. Power for these is to be provided from a separate supply.

In addition the module has limited charging capacity for externally connected lead acid batteries. The
temperature compensated charging capacity is designed for float operation and short term boost of
batteries already charged and in good condition. Use of this supply on flat or fully discharged batteries
may cause damage to the power supply module.

When the AC supply fails and the system is powered from the backup battery, the voltage monitoring
circuit provides battery cut-off (for battery preservation) when battery cell voltage drops to
10.5 V 0.2 V.

The PS-11 has battery voltage, battery current, supply current, and internal or external temperature
monitoring circuits that enable the processor module to access these as analog and digital points in
the system.

Kingfisher PLUS+Hardware Manual 6.0 www.cse-semaphore.com/mykingfisher Page 78

The PS-11 has an internal temperature sensor and also allows an external temperature sensor to be
connected. When using a backup battery, the external sensor should be mounted close to the
negative terminal of the battery to ensure correct charging operation. The internal temperature sensor
will typically indicate a higher temperature than the external sensor. The lower temperature is used for
temperature compensated battery charging.

There is a connection on the DC terminal block for powering low power radios. This output is switched
off on low battery voltage for battery protection and can also be controlled by the RTU configuration.

A power supply module can be installed in any I/O slot of a 4, 6 or 12 slot backplane.

Two or more power supply modules of any type can be installed on a backplane in any available slots.
This provides redundant and alternative power source configurations.
Kingfisher PLUS+Hardware Manual 6.0 www.cse-semaphore.com/mykingfisher Page 79

PS-11 Specifications
Input Supply 100 to 240 VAC 50/60 Hz
+96 to +340 VDC
Can also be powered using 12.0 to 15.0 VDC when powered from the backup
battery terminals.
Backup Battery Sealed Lead-Acid, 12 VDC, 26 AH max. Note: batteries exceeding 26 AH can
be connected. However, full charging cannot be guaranteed.
Outputs Item Range Max. Current Protection Switchable
from Logic?
12 V Backplane
#
10.2 - 14.4 V 4.5 A Electronic No
5 V Backplane 5 V +5% 3.0 A Electronic No
12 V Battery
#
10.8 - 15.0 V 4.5 A Polyfuse No
12 V Auxiliary (V
R
)
#
10.8 - 15.0 V 4.0 A Electronic Yes
24 V Auxiliary 24 V +5% 0.4 A Polyfuse Yes
Maximum total current: 4.5 A
Maximum load: 60 W (for ambient temperatures up to 50C)
#
These voltages are electrically linked and are varied by the module when charging a
battery. 12 V Battery and 12 V Auxiliary are nominally 13.8 V @ 25C. These voltages
will also vary when the module is powered from a backup battery.
Isolation 2.5 kV Transient AC input / DC output
Deep Discharge
Protection
RTU Shutdown at 10.8 V +0.2 V
RTU Startup at 11.6 V +0.2 V
When mains power is restored, a PS-11 will switch from battery power to mains power
within 30 seconds provided the battery voltage is less than 13.8 V. If the battery
voltage is higher, the PS-11 will continue to run on the battery until the battery voltage
drops below 13.8 V. If a battery powered PS-11 shuts down due to low battery
voltage, it will startup again within 60 seconds when the battery voltage is 11.6 V or
greater or mains power is restored.
Connector Plugs Low Voltage: 5 mm pitch TB plug (Phoenix MSTB2.5/7-ST or similar)
AC Mains: 7.62 mm pitch TB plug (Phoenix PC4/3-ST-7.62)
Monitoring Item Accuracy
Battery Current
Supply or Battery Voltage
Supply or Battery Current
Temperature
AC present
Battery low
24 V Auxiliary Present
+10%
+2%
+10%
+2C
N/A
N/A
N/A
Operating
Temperature
-20 to 70C
Storage
Temperature
-40 to 85C
Operating Humidity 5 to 98% RH non-condensing
Redundant Power
Supplies
Yes. Two or more power supplies can be installed on a backplane in any
available slots. Equal load sharing is not guaranteed.
Hot Swap Yes. When 2 power supplies are present on the backplane, one power supply
can be swapped with no interruption to the processor or I/O.
Bundled
Accessories
External temperature sensor. Attach to or near negative battery terminal to
ensure full life span of backup battery is achieved.
When connected the temperature sensor returns 10 mV per Kelvin.
(Note 0 Kelvin =-273 C). When functioning correctly, the sensor will provide
2.73 V @ 0 C and 2.93 V @ 20 C etc.

Kingfisher PLUS+Hardware Manual 6.0 www.cse-semaphore.com/mykingfisher Page 80

PS-11 Module LEDs


LED Description (when ON)
OK
#
Module is functioning OK. OK LED will flash when communications is lost with the
processor module
Vsup*
#

AC input supply is powered
Vb
#
Battery detected. ON while the current into or out of the battery is 100 mA or greater. If
a battery has not been detected (ie. the current into or out of the battery is less than
100 mA) OR if the battery is fully charged, Vb will flash once every 4 seconds.
5V
#
Internal 5 V supply is OK. This LED should always be ON as the 5 V supply is used to
power all the modules.
Vaux
#
Auxiliary 24 V supply is OK (will only display if the 24 V converter is installed).
BATT CHG
#
Battery is being charged. Current into battery is 100 mA or greater.
FL
#
Battery is in float charge mode
BO
#
Battery is in boost charge mode
LO
#

Battery has reached discharged condition (<11.5 V0.2 V).
LO LED is cleared when battery >12.4 V 0.2 V
All LEDs
except Vsup
Power supply is operating in redundant mode and the Input Supply is not powered.

#
Redundant Power Suppl y LEDs ON When Power Suppl y Is Switched OFF
When a redundant power supply is switched OFF, the LEDs will still be ON. The LEDs are powered by the
RS485 bus.
The PS-11 microprocessor does not run and the OK LED will flash to indicate that there is no communications
with the processor module.
If the input supply is disconnected to the redundant power supply, the Vsup LED will go OFF.

* PS-11 Continues to Run From The Backup Battery (After Input Suppl y is Restored)
If the PS-11 is running from its AC input supply and a Sealed Lead-Acid battery is connected to the PS-11,
when the Input Supply is disconnected (eg. mains fail) and then reconnected, the Vsup LED will not turn ON.
The PS-11 will assume there is no AC or DC input supply and will continue to run from the battery and will
eventually shut down when the battery is discharged.
This problem can be fixed by either:
1. Open the original RTU configuration file using Toolbox 32 1.45f or newer, save the file and then re-
download the configuration into the RTU (automatically configures the PS-11 to use a Seal Lead-Acid
battery).
2. If using Toolbox 32 1.45e or older, open the original RTU configuration file, add the PS-11 module to the
IO Modules List (from the menu Configuration, I/O Modules List). Configure the PS-11 module from the IO
Modules List to use a Battery Type of Sealed Lead-Acid. Save the configuration and then download into the
RTU.

OK
BATT
CHG Vsup
FL Vb
BO 5V
LO Vaux
PS-xx
Kingfisher PLUS+Hardware Manual 6.0 www.cse-semaphore.com/mykingfisher Page 81

Battery Charging
Whenever the battery begins to draw more than 100 mA out of the power supply (eg when the power
supply is first turned on or a battery is connected), the power supply measures the initial battery
current. The initial battery current is used to estimate how long the battery will need to be Boost
charged for. After Boost charging the battery for the estimated time (3-10 hours, Vb, BATT CHG and
BO LEDs ON), the power supply will switch to Float charging (Vb, BATT CHG and FL LEDs ON).
Note: if the battery charging current falls below 100 mA at any stage during Boost or Float charging,
the Power Supply will stop charging the battery (BATT CHG, BO and FL LEDs OFF, Vb now flashes
every 4 seconds).


Part Numbers
PS-11-C AC input, Auxiliary 24 V converter fitted
PS-11-0 AC input, Auxiliary 24 V converter not fitted


PS-11 Block Diagram

N
FILTER &
RECTIFIER
A
E
LED
VSUP
INTERNAL
TEMP.
SENSOR
TS
R-
EXT.
TEMP.
SENSOR
B+
B-
OPTIONAL
BATTERY
Vb
5V
0V
PCON
EARTH
LOW
VOLTAGE
CUTOFF
S1
LED
Vb
BACKPLANE
LED
LO
RS485
DRIVER
LED
OK
LED
CHG
LED
BO
LED
FL
BACKPLANE
LED
VAUX
VA+
VA-
R+
R-
RADIO LK4
LK5
Vb
RADIO
POWER
AUX24 PWR

Isup CURRENT
MONITOR
Ibat CURRENT
MONITOR
PWR TEMP Ibat Isup
BAT LOW
MONITORING
TEMPERATURE
COMPENSATION
+5V
REG. 70W
DC/DC
CONVERTER
LOW
VOLTAGE
MONITOR
MICRO CONTROLLER
ISOLATED 24V
AUXILIARY
DC/DC
CONVERTER
10W
(OPTIONAL)






Kingfisher PLUS+Hardware Manual 6.0 www.cse-semaphore.com/mykingfisher Page 82

PS-11 Wiring Diagram AC Supply
Safety Warnings

CAUTION
Ensure power cord is unpowered before disconnecting power cord from module
Disconnect power cord from module before wiring, removing or servicing the
module
Connect module to AC mains supply in accordance with national wiring
regulations

PS-11
OFF
TEMPERATURE SENSOR
#

+
#
TAPE OR CABLE TIE THE TEMPERATURE SENSOR TO THE NEGATIVE BATTERY
TERMINAL (OR AS CLOSE AS POSSIBLE). CONNECT THE BLACK STRIPED WIRE OF THE
SENSOR TO R- OR B-
VA+
VA-
R+
R-
TS
B+
B-
-
+
24 VDC AUXILIARY OUTPUT (OPTIONAL)
13.8 VDC OUTPUT (FOR RADIO OR OTHER DEVICE)
-
-
+
BACKUP
BATTERY
**Colour may vary
A
N
E
ACTIVE (+)
NEUTRAL (-)
EARTH
100-240 VAC
96-340 VDC
**Temperature sensor will be supplied in one of the
following wire colours based on availability:
-

Black (-) / Black striped white (+)
-

Black (-) / Grey (+)
-

Black (-) / Whilte (+)
-

Black (-) / Red (+)




PS-11 Wiring Diagram DC Supply
A battery or other low voltage DC supply can be connected to the battery input terminals to power the
PS-11 module.


+

PS-11
OFF

A
N
E
24 VDC AUXILIARY OUTPUT (OPTIONAL)
12 VDC OUTPUT (FOR RADIO OR OTHER DEVICE)
+
VA+
VA-
R+
R-
TS
B+
B-

-
-
-
+
12 VDC SUPPLY (NOMINAL)
(MUST BE ISOLATED FROM FIELD SUPPLY)
+
-
96 TO 340 VDC SUPPLY
(ALTERNATIVE TO USING BATTERY TERMINALS)



Kingfisher PLUS+Hardware Manual 6.0 www.cse-semaphore.com/mykingfisher Page 83

1.30 PS-21: DC Supply Input 20 to 60 VDC
FEATURES

Monitoring - battery and input supply

DC Input Supply



Redundancy - two or more power
supplies per backplane

Low Voltage Battery Protection

Isolated DC Output

The PS-21 power supply provides DC to DC conversion for the backplane, battery and radio (or an
external device), a monitoring processor and an optional isolated 24 VDC output.

Fire Risk

CAUTION
A supply voltage outside the specified limits may cause fire.

An isolated 24 VDC output rated at 10 W (400 mA) is an option available for powering a limited
number of analog loops or digital circuits. It cannot be used with inductive loads such as coils,
contactors etc. Power for these is to be provided from a separate supply.

In addition the module has limited charging capacity for externally connected lead acid batteries. The
temperature compensated charging capacity is designed for float operation and short term boost of
batteries already charged and in good condition. Use of this supply on flat or fully discharged batteries
may cause damage to the power supply module.

When the DC input supply fails and the system is powered from the backup battery, the voltage
monitoring circuit provides battery cut-off (for battery preservation) when battery cell voltage drops to
10.5 V 0.2 V.

The PS-21 has battery voltage, battery current, supply current, and internal or external temperature
monitoring circuits that enable the processor module to access these as analog and digital points in
the system.

Kingfisher PLUS+Hardware Manual 6.0 www.cse-semaphore.com/mykingfisher Page 84

The PS-21 has an internal temperature sensor and also allows an external temperature sensor to be
connected. When using a backup battery, the external sensor should be mounted close to the
negative terminal of the battery to ensure correct charging operation. The internal temperature sensor
will typically indicate a higher temperature than the external sensor. The lower temperature is used for
temperature compensated battery charging.

There is a connection on the DC terminal block for powering low power radios. This output is switched
off on low battery voltage for battery protection and can also be controlled by the RTU configuration.

A power supply module can be installed in any I/O slot of a 4, 6 or 12 slot backplane. Up to 4 Power
Supply modules of any type can be installed on a backplane thus providing redundant and alternative
power source configurations.
Kingfisher PLUS+Hardware Manual 6.0 www.cse-semaphore.com/mykingfisher Page 85

PS-21 Specifications
Input Supply +20 to +60 VDC or 20 to 60 VDC
The modules can also be powered using 12.0 to 15.0 VDC when powered
from the backup battery terminals.
Backup Battery Sealed Lead-Acid, 12 VDC, 26 AH max. Note: batteries exceeding 26 AH can
be connected. However, full charging cannot be guaranteed.
Outputs Item Range Max. Current Protection Switchable
from Logic?
12 V Backplane
#
10.2 - 14.4 V 4.5 A No No
5 V Backplane 5 V +5% 3.0 A Electronic No
12 V Battery
#
10.8 - 15.0 V 4.5 A Polyfuse * No
12 V Auxiliary (V
R
)
#
10.8 - 15.0 V 4.0 A No Yes
24 V Auxiliary 24 V +5% 0.4 A Polyfuse Yes
Maximum total current: 4.5 A
Maximum load: 60 W (for ambient temperatures up to 50C)
#
These voltages are electrically linked and are varied by the module when charging a
battery. 12 V Battery and 12 V Auxiliary are nominally 13.8 V @ 25C. These voltages
will also vary when the module is powered from a backup battery.
* The battery input of the PS-21 does not have auto-resetting protection against
reverse polarity! Please ensure the battery is connected correctly.
Isolation 3 kV DC input / DC output
Deep Discharge
Protection
RTU Shutdown at 10.8 V +0.2 V
RTU Startup at 11.6 V +0.2 V
Connector Plugs Low Voltage: 5 mm pitch TB plug (Phoenix MSTB2.5/7-ST or similar)
DC Mains: 0.156 housing with 3 crimp contacts (J ST VHR-3M housing /
SVH-41T-p1.1 contact or similar)
Monitoring Item Accuracy
Battery Current
Supply or Battery Voltage
Supply or Battery Current
Temperature
AC present
Battery low
24 V Auxiliary Present
+10%
+2%
+10%
+2C
N/A
N/A
N/A
Operating
Temperature
-20 to 70C
Storage
Temperature
-40 to 85C
Operating Humidity 5 to 98% RH non-condensing
Redundant Power
Supplies
Yes. Two or more power supplies can be installed on a backplane in any
available slots. Equal load sharing is not guaranteed.
Hot Swap Yes. When 2 power supplies are present on the backplane, one power supply
can be swapped with no interruption to the processor or I/O.
Bundled
Accessories
External temperature sensor. Attach to or near negative battery terminal to
ensure full life span of backup battery is achieved.
When connected the temperature sensor returns 10 mV per Kelvin.
(Note 0 Kelvin =-273 C). When functioning correctly, the sensor will provide
2.73 V @ 0 C and 2.93 V @ 20 C etc.

Kingfisher PLUS+Hardware Manual 6.0 www.cse-semaphore.com/mykingfisher Page 86

PS-21 Module LEDs

OK
BATT
CHG Vsup
FL Vb
BO 5V
LO Vaux
PS-xx


LED Description (when ON)
OK
#
Module is functioning OK. OK LED will flash when communications is lost with the
processor module
Vsup*
#

DC input supply is powered
Vb
#
Battery detected. ON while the current into or out of the battery is 100 mA or greater. If
a battery has not been detected (ie. the current into or out of the battery is less than
100 mA) OR if the battery is fully charged, Vb will flash once every 4 seconds.
5V
#
Internal 5 V supply is OK. This LED should always be ON as the 5 V supply is used to
power all the modules.
Vaux
#
Auxiliary 24 V supply is OK (will only display if the 24 V converter is installed).
BATT CHG
#
Battery is being charged. Current into battery is 100 mA or greater.
FL
#
Battery is in float charge mode
BO
#
Battery is in boost charge mode
LO
#

Battery has reached discharged condition (<11.5 V0.2 V).
LO LED is cleared when battery >12.4 V 0.2 V
All LEDs
except Vsup
Power supply is operating in redundant mode and the Input Supply is not powered.

#
Redundant Power Suppl y LEDs ON When Power Suppl y Is Switched OFF
When a redundant power supply is switched OFF, the LEDs will still be ON. The LEDs are powered by the
RS485 bus.
The PS-21 microprocessor does not run and the OK LED will flash to indicate that there is no communications
with the processor module.
If the input supply is disconnected to the redundant power supply, the Vsup LED will go OFF.

* PS-21 Continues to Run From The Backup Battery (After Input Suppl y is Restored)
If the PS-21 is running from its DC input supply and a Sealed Lead-Acid battery is connected to the PS-21,
when the Input Supply is disconnected (eg. mains fail) and then reconnected, the Vsup LED will not turn ON.
The PS-21 will assume there is no DC input supply and will continue to run from the battery and will
eventually shut down when the battery is discharged.
This problem can be fixed by either:
1. Open the original RTU configuration file using Toolbox 32 1.45f or newer, save the file and then re-
download the configuration into the RTU (automatically configures the PS-21 to use a Seal Lead-Acid
battery).
2. If using Toolbox 32 1.45e or older, open the original RTU configuration file, add the PS-21 module to the
IO Modules List (from the menu Configuration, I/O Modules List). Configure the PS-21 module from the IO
Modules List to use a Battery Type of Sealed Lead-Acid. Save the configuration and then download into the
RTU.
If a backup battery is being used, the power supply may also need to be returned to the factory for a firmware
upgrade.

Kingfisher PLUS+Hardware Manual 6.0 www.cse-semaphore.com/mykingfisher Page 87

Battery Charging
Whenever the battery begins to draw more than 100 mA out of the power supply (eg when the power
supply is first turned on or a battery is connected), the power supply measures the initial battery
current. The initial battery current is used to estimate how long the battery will need to be Boost
charged for. After Boost charging the battery for the estimated time (3-10 hours, Vb, BATT CHG and
BO LEDs ON), the power supply will switch to Float charging (Vb, BATT CHG and FL LEDs ON).
Note: if the battery charging current falls below 100 mA at any stage during Boost or Float charging,
the Power Supply will stop charging the battery (BATT CHG, BO and FL LEDs OFF, Vb now flashes
every 4 seconds).


Part Numbers
PS-21-C DC input, Auxiliary 24 V converter fitted
PS-21-0 DC input, Auxiliary 24 V converter not fitted


PS-PS-21 Block Diagram

+SUPPLY
-SUPPLY
E
LED
VSUP
INTERNAL
TEMP.
SENSOR
TS
R-
EXT.
TEMP.
SENSOR
B+
B-
OPTIONAL
BATTERY
Vb
5V
0V
PCON
EARTH
LOW
VOLTAGE
CUTOFF
S1
LED
Vb
BACKPLANE
LED
LO
RS485
DRIVER
LED
OK
LED
CHG
LED
BO
LED
FL
BACKPLANE
LED
VAUX
VA+
VA-
R+
R-
RADIO LK4
LK5
Vb
RADIO
POWER
AUX24 PWR

Isup CURRENT
MONITOR
Ibat CURRENT
MONITOR
PWR TEMP Ibat Isup
BAT LOW
MONITORING
TEMPERATURE
COMPENSATION
+5V
REG. 70W
DC/DC
CONVERTER
LOW
VOLTAGE
MONITOR
MICRO CONTROLLER
ISOLATED 24V
AUXILIARY
DC/DC
CONVERTER
10W
(OPTIONAL)




Kingfisher PLUS+Hardware Manual 6.0 www.cse-semaphore.com/mykingfisher Page 88

PS-21 Wiring Diagram
PS-21
OFF
E
-
+
TEMPERATURE SENSOR
#

- SUPPLY
#
TAPE OR CABLE TIE TEMPERATURE SENSOR TO NEGATIVE BATTERY TERMINAL (OR AS
CLOSE AS POSSIBLE). CONNECT BLACK STRIPED WIRE OF SENSOR TO R- OR B-
20 TO 60 VDC INPUT SUPPLY *
VA+
VA-
R+
R-
TS
B+
B-
+SUPPLY
EARTH
* A NEGATIVE DC INPUT SUPPLY CAN BE USED. CONNECT THE MORE POSITIVE WIRE
(eg. 0 V) TO +SUPPLY AND CONNECT THE MORE NEGATIVE WIRE (eg. -48 V) TO - SUPPLY.
CAUTION! Connecting the
battery in reverse may cause
damage to the power supply.
-
+
24 VDC AUXILIARY OUTPUT (OPTIONAL)
13.8 VDC OUTPUT (FOR RADIO OR OTHER DEVICE)
-
-
+
BACKUP
BATTERY
GREY OR WHITE OR RED WITH BLACK STRIPE
+
FUSE
SLOW BLOW, EXTERNAL FUSE. USE FOLLOWING FUSE ACCORDING TO SUPPLY
VOLTAGE: 20 TO 28 V = 4.0 A, 29 TO 39 V =3.0 A, 40 TO 56 V =2.0 A, 57-60 V =1.5 A


Kingfisher PLUS+Hardware Manual 6.0 www.cse-semaphore.com/mykingfisher Page 89

Chapter 2 Glossary
AI, AO, DI, DO Analog Input, Analog Output, Digital Input and Digital Output respectively
Byte A group of 8 bits. Each bit can be a 0 (off) or a 1 (on) allowing up to 256
combinations.
Comms Communications
Current Sinking Current is supplied into the RTUs IO terminal.
IO Input, Output
IP Internet Protocol. Used for Ethernet communications.
Port A physical connection or socket on an RTU used for communications
Processor Module Processor module containing a CPU (central processing unit)
Protocol Refers to the format of messages that may be passed to, from and through an
RTU in communication with local and remote devices. Communications may
use one or more RTU ports. Examples of protocols used within telemetry
include Kingfisher, Modbus and DNP3.
RTU Acronym for Remote Terminal Unit. Describes a group of processor,
communication and IO modules that comprise a device for monitoring and
control of equipment in remote locations.
TCP/IP Transfer Control Protocol / Internet Protocol. Commonly used for Ethernet
communications.
UDP Universal Datagram Protocol.