Vous êtes sur la page 1sur 49

POWER SYSTEM PROTECTION

COORDINATION
REPO
RT

Client:

M/s. GMR CHHATTISGARH ENERGY


PVT LTD
Project:

RAW WATER INTAKE


PACKAGE
2 X 685 MW THERMAL POWER
PLANT
Engineering Consultant:

MAHINDRA CONSULTING
ENGINEERS LTD
CHENNAI
Project
Consultant:

DEVELOPMENT CONSULTANT
PVT LTD MUMBAI

Report Compiled
by:

Interface Electronics Pvt Ltd,Chennai


Email:ife@vsnl.com
website:www.ifepwrana.com Mobile
no:9884370326

Contents
Sl.No

Descriptiion

Page No

Executive Summary

Reference Documents

Device Details

Single Line Diagram

Short Circuit Report

3500 kVA Transformer Setting Calculations

400 kVA Transformer Setting Calculations

11

Motor Setting Calculations

13

Stabilising Resistance Calculations

14

10

Setting Details for 33 kV Switch Board

16

11

Setting Details for 3.3 kV Switch Board

23

12

Setting Details for PMCC Panel

34

13

Time Current Characteristic Curves

41

Executive Summary
Introduction
Interface Electronics pvt ltd was requested to prepare a protection co-ordination report for
33/3.3/0.415 kV Distribution for theRaw Water Intake Package for 2 x 685 Thermal Power Plant in
Raipur,Chattisgarh.
This report includes calculation results of the study 33/3.3/0.415 kV Switchgear.
The system data for calculation are based on the data provided by M/sMahindra Consulting
Engineers,Chennai The most important tool for documentation of over current protection coordination is Paladin Design Base 5. Typical grading paths have been chosen in a single line and in a
current/time diagram the selectivity of the characteristic curves of the devices are shown.

2 Power System Data


It is stated the Power source is from a 132/33 kV substation 18 km away from this Plant and source
Fault MVA is calculated and this value is taken for further calculations of short circuit currents down
stream.

3 Infeed Data
In the absense of exact short circuit data of utility ,minimum Short-circuit power 3-phase @132/33 kV
SS is taken as 3000 MVA at 132 kV and that of maximum is taken to be 6000 MVA for evaluation and
study

4 Protection Coordination
The short circuit currents at various busbars are calculated .based on the above
assumptions.
Based on the short circuit calculations, protection coordination study was carried out for this
Project
Calculated Short circuit currents are tabulated in the report and also shown in
the SLD.
Selectivity of relays have been worked out for all the relays in the 33 kV Switch Board,3.3 kV Switch
board and
415 V PMCC Panel. The tripping time selection of 3.3 kV Incomer is arrived at based on two motors
starting simultaneously with acceleration time of 3 sec.Keeping this time as reference other timing are
worked out with time gradation of 150 mill sec.

5 Conclusion
Setting sketches for the over current devices have been performed for the 33/3.3/0.415 kV
network The selectivity of the protection settings for characteristic feeders was verified with the
protection grading diagrams prepared with software Paladin Design Base 5 Generally, attention was
given to provide the largest possible safety clearance between the individual protective devices.

Reference Documents / Drawings


Sl.No
1
2
3
4
5
6
7
8
9
10
11
12

Document
Title
Single Line Diagram -High Tension
GA and Foundation-33kV,630,25 kA 8 PNL VCB
Scheme of 33kV 25,kA Transformer Feeder (power circuit)
Scheme of 3.3kV 25,kA Incomer (power circuit)
Scheme of 3.3kV 25,kA Transformer Feeder (power circuit)
Scheme of 3.3kV 25,kA MotorFeeder (power circuit)
Scheme of 3.3kV 25,kA CapacitorFeeder (power circuit)
PMCC /MCC Schemes
Transformer Data sheet 3500 kVA
Transformer Data sheet 400 kVA
Motor Data Sheet 580 kW
CABLE SCHEDULE

File
reference
SLD HT SPEC-1038-mace-795-4002-r3.pdf
RK_BD-2_1.pdf
RK_BD-2_2.pdf
Incomer.pdf
Transformer.pdf
4motor.pdf
5APFC.pdf
LT SCHEME -R2.pdf
3500KVA.pdf
400KVAtrafo.pdf
580KW HT Motor.pdf
Cable Schedule_SEPC-1038-MACE-795-4013 Rev
A.doc

Document
No
SEPC-1038-mace-795-4002
rev 3
NVISL036GA46973 rev 0 sheets 1-7
NVISL039SC47075 rev 0 sheets 1-7
MVISL039SC47046 rev 0 sheets1-9
MVISL039SC47048 rev 0 sheets1-9
MVISL039SC47049 rev 0 sheets1-9
MVISL039SC47050 rev 0 sheets1-9
VISHAL/J2895/501 REV 2 SHEETS 1-9
Voltamp JN No:-JN41531
Voltamp JN No:-JN61107
CGL WO:- 2111231
SEPC-1038-MACE-795-4013 REV A Sheets
1-4

Device
Details
2-Winding Transformers
Details of Equipment

Transformers 1 & 2
Transformers 3 & 4

kVA rating High


Voltage
side
3500
33000 V
400
3300 V

Low voltage
side

Percentage
Impedance

Low
winding

High
winding

Grounding
Mode

3450 V
433 V

7.15
4.50

Star
Star

Delta
Delta

Through NGR Dyn11


Direct
Dyn1

Diesel Generating Set


Details of Equipment
DG1

kVA rating Output Sub transient


Voltage Reactance
25
415 V
9%

Starting
Electric Manual

Vector
Group

Type of
Cooling

Supply Variation on
Primary side

ONAN
AN

-7.5% to +7.5% tapping


-5% to +5% tapping

GRID
Source 3

OH Line1

GRID

Source 1
TR_S1

ARANG SS

Cab:Source1
OH Line
Sending End

33kV SWBD

IC1_33kV_SWBD
50
51

IC2_33kV_SWBD
BC_33kV_SWBD1

33kV_SWBD_RHS

50
51

33kV_SWBD_LHS

50
51

OG2_33kV_SWBD

OG3_33kV_SWBD

50
51

50
51

50
51

OG1_33kV_SWBD
Cab:Tr1_HV

Cab:Tr2_HV

TR1

TR2

Cab:Tr1_LV

Cab:Tr2_LV

3.3kV SWBD
IC1_3.3kV_SWBD3

50
51

50
51

IC2_3.3kV_SWBD

50
51

BC_3.3kV_SWBD
3.3kV_SWBD_LHS1

3.3kV_SWBD_RHS1

OG2_3.3kV_SWBD
OG3_3.3kV_SWBD

50
51

50
51

Cab:Tr3_HV

Cab:APFC1

OG1_3.3kV_SWBD

OG5_3.3kV_SWBD

50
51

50
51

Cab:Mot2
OG4_3.3kV_SWBD

Cap1

OG6_3.3kV_SWBD

50
51

OG7_3.3kV_SWBD

50
51

Cab:Mot4

50
51

Cab:Mot1

Cab:Mot3

OG8_3.3kV_SWBD
50
51

OG9_3.3kV_SWBD
50
51

OG10_3.3kV_SWBD
50
51

Cab:APFC2

Cab:TR4_HV

Cap 2
DG

TR3

Motor 2

Motor 4

Motor 1

Motor 3

TR4

GEN

Cab:DG
Cab:Tr3_LV
Cab:Tr4_LV
R_PMCC_IC1

PMCC

PMCC_IC2

PMCC_IC1
PMCC_BC

PMCC_LHS

OG2

Cab:Tr5_HV

Cab:Tr6_HV

MLDB_IC1

MLDB_IC2

TR5

TR6

MLDB_IC11
MLDB_LHS

PMCC_IC3
PMCC_RHS

OG1

MLDB

R_PMCC_IC3

R_PMCC_IC2

MLDB_IC21

MLDB_IC12
MLDB_RHS

REV. DATE ECO# DWN APP


TH IS

DESCRIPTION

DR A W ING IS PR OP RIE TA R Y INF OR M AT ION

You r C omp any Na me


Add ress
Add ress
Ph one a nd w eb sit e

Electrical One-Line Diagram for Coordination Study

DRA WN BY/DATE:
DW G No .:
EN G. APP./DATE:
MFG. APP./ DATE:
PAR T N o.:
SCALE:

DWG SIZE:

RE V.

Short Circuit Current Details

GRID
Source 3
Ik" : 13157.5A

OH Line1

GRID

Source 1

ARANG SS
Ik" : 2739.78A

TR_S1

Cab:Source1
OH Line
Sending End
Ik" : 6328.23A

33kV SWBD

IC1_33kV_SWBD
50
51

IC2_33kV_SWBD
BC_33kV_SWBD1

50
51

33kV_SWBD_RHS
Ik" : 1454.84A

50
51

33kV_SWBD_LHS
Ik" : 1454.9A

OG3_33kV_SWBD

OG2_33kV_SWBD
50
51

50
51

50
51

OG1_33kV_SWBD
Cab:Tr1_HV

Cab:Tr2_HV
TR2

TR1

Cab:Tr1_LV

Cab:Tr2_LV

3.3kV SWBD
50
51

IC1_3.3kV_SWBD3

50
51

IC2_3.3kV_SWBD

BC_3.3kV_SWBD

3.3kV_SWBD_RHS1
Ik" : 6578.25A

50
51

3.3kV_SWBD_LHS1
Ik" : 6521.77A
OG2_3.3kV_SWBD
OG3_3.3kV_SWBD

50
51

50
51

Cab:Tr3_HV

Cab:APFC1

OG1_3.3kV_SWBD

OG5_3.3kV_SWBD

50
51

50
51

Cab:Mot2
OG4_3.3kV_SWBD

Cap1
Ik" : 6440.68A

TR3

OG6_3.3kV_SWBD

50
51

Motor 2
Ik" : 6338.78A

OG7_3.3kV_SWBD

50
51

Cab:Mot4

50
51

Cab:Mot1

Cab:Mot3

OG8_3.3kV_SWBD
50
51

OG9_3.3kV_SWBD
50
51

OG10_3.3kV_SWBD
50
51

Cab:APFC2

Cab:TR4_HV

Cap 2
Ik" : 6479.84A

Motor 4
Ik" : 6311.67A

Motor 1
Ik" : 6378.28A

Motor 3
Ik" : 6378.28A

TR4

DG
Ik" : 4825.02A

GEN

Cab:DG
Cab:Tr3_LV
Cab:Tr4_LV
R_PMCC_IC1

PMCC

PMCC_IC1

PMCC_IC2

PMCC_LHS
Ik" : 9284.87A

PMCC_BC

OG1

PMCC_IC3

Cab:Tr6_HV

MLDB_IC1

MLDB_IC2

TR5

TR6

MLDB_IC11
MLDB_LHS
Ik" : 706.54A

PMCC_RHS
Ik" : 9609.4A

OG2

Cab:Tr5_HV

MLDB

R_PMCC_IC3

R_PMCC_IC2

MLDB_IC12

MLDB_IC21
MLDB_RHS
Ik" : 666.42A

REV. DATE ECO# DWN APP


TH IS

DESCRIPTION

DR A W ING IS PR OP RIE TA R Y INF OR M AT ION

You r C omp any Na me


Add ress
Add ress
Ph one a nd w eb sit e

Electrical One-Line Diagram for Coordination Study


Short Circuit Currents
DRA WN BY/DATE:

DW G No .:

EN G. APP./DATE:
MFG. APP./ DATE:
PAR T N o.:
SCALE:

DWG SIZE:

RE V.

Short Circuit Detailed Report for source Fault 3000MVA Sec

at 132 kV

3P Fault - IEC60909 Method at the Following Times


Bus Description
Pre fault Instantan 1/2 cycle 1 cycle
3 cycle
5 cycle
8 cycle
standard
voltage in eus current
sym
sym
sym
sym
sym
sym
in A
current in current in current in current in current in current in
Volts
Amps
Amps
Amps
Amps
Amps
Amps
Source 3
Sending End
33kV_SWBD_LHS
33kV_SWBD_RHS
3.3kV_SWBD_RHS
1
3.3kV_SWBD_LHS1

13200
34483
13158
033000
14415
6328
33000
2081
1455
33000
2081
1455
3300
11447
6578
3300
11334
6522
Cap 2
3300
11221
6480
Cap 1
3300
11149
6441
PMCC_RHS
415
19747
9609
PMCC_LHS
415
19048
9285
MLDB_LHS
415
1515
707
MLDB_RHS
415
1433
666
LL Fault - IEC60909 Method at the Following Times
Source 3
13200
34475
13153
033000
Sending End
12654
5566
33kV_SWBD_LHS
33000
1804
1262
33kV_SWBD_RHS
33000
1804
1262
3.3kV_SWBD_LHS1
3300
9821
5654
3.3kV_SWBD_RHS
3300
9919
5703
1
Cap
2
3300
9723
5617
Cap 1
3300
9660
5583
PMCC_RHS
415
17103
8324
PMCC_LHS
415
16499
8043
MLDB_LHS
415
1312
612
MLDB_RHS
415
1241
577
LG Fault - IEC60909 Method at the Following Times
Source 3
13200
34450
13140
033000
Sending End
17914
7897
33kV_SWBD_LHS
33000
1977
1352
33kV_SWBD_RHS
33000
1977
1352
3.3kV_SWBD_RHS
3300
14080
7785
1
3.3kV_SWBD_LHS1
3300
13920
7711
Cap 2
3300
13582
7569
Cap1
3300
13511
7533
PMCC_RHS
415
19634
9574
PMCC_LHS
415
19187
9344
MLDB_LHS
415
1550
712
MLDB_RHS
415
1492
684
LLG Fault - IEC60909 Method at the Following Times
Source 3
13200
35743
13637
033000
Sending End
17018
7490
33kV_SWBD_LHS
33000
2222
1543
33kV_SWBD_RHS
33000
2222
1543
3.3kV_SWBD_RHS
3300
14089
7854
1
3.3kV_SWBD_LHS1
3300
13919
7774
Cap 2
3300
13531
7606
Cap1
3300
13462
7570
PMCC_RHS
415
19723
9608
PMCC_LHS
415
19134
9323
MLDB_LHS
415
1550
718
MLDB_RHS
415
1480
683

13152
6306
1437
1437
6429
6374
6334
6296
9518
9249
706
666

13144
6270
1411
1411
6203
6154
6114
6081
9414
9193
706
666

13136
6239
1389
1389
6024
5979
5940
5910
9334
9147
706
665

13136
6239
1389
1389
6024
5979
5940
5910
9334
9147
706
665

13122
6180
1349
1349
5702
5688
5626
5625
9037
9067
705
664

13149
5546
1247
1247
5525
5573
5491
5458
8245
8011
612
577

13141
5515
1224
1224
5335
5378
5301
5272
8154
7963
611
576

13135
5488
1205
1205
5184
5223
5150
5124
8085
7923
611
576

13135
5488
1205
1205
5184
5223
5150
5124
8085
7923
611
576

13122
5439
1172
1172
4933
4963
4897
4878
7980
7854
611
576

13137
7874
1343
1343
7648
7576
7439
7404
9496
9320
712
684

13133
7838
1330
1330
7439
7373
7240
7209
9411
9282
712
684

13129
7807
1320
1320
7271
7210
7081
7053
9347
9251
712
684

13129
7807
1320
1320
7271
7210
7081
7053
9347
9251
712
684

13122
7749
1301
1301
6986
6934
6809
6788
9308
9197
711
683

13632
7470
1532
1532
7728
7649
7486
7450
9517
9299
717
683

13624
7437
1515
1515
7536
7464
7303
7272
9412
9264
717
682

13617
7409
1502
1502
7385
7317
7158
7130
9330
9235
717
682

13617
7409
1502
1502
7385
7317
7158
7130
9330
9235
717
682

13604
7354
1478
1478
7108
7069
6894
6891
9142
9187
717
681

Setting Calculation for Power Transformers 3.5 MVA

33kV,
-7.5% to

CTHV:100/1

3.5 MVA

CTLV:800/1

Transformer capacity
Primary Voltage
Secondary Voltage
Transformer HV side CT details CTHV
Turns Ratio
Transformer LV side CT details CTLV
Turns Ratio
Percentage Impedance of Transformer
3 Phase Min. Fault Current at 33 kV Bus as per report
3 Phase Min Fault current at 3.3 kV Bus as per report
Transformer HV side Phase Rated current
Transformer LV side Phase Rated current
Max Through Fault Current on HV side
Max Through Fault Current on LV side
The O/C Pickup setting is usually 110% of the rated Current
Over current setting at 33 kV side
Over current setting at 33 kV side (CT Secondary)
I > (Ip) Rounded off to
Time Multiplier Setting for Normal Inverse curve

3.3kV

3500
33
3.45
100/1
100
800/1
800
7.15%
2466
6806.00
61.23
585.72
711.54
6806.00
1.10 x 61.23
67.35
0.67

kVA
kV
kV

Amps
Amps
Amps
Amps
Amps
Amps

0.70

Amps
Amps
x In

tms=Required time to trip 't' /[0.14/(I


-1]
f /I
s )
In this incidence, time required to trip, t=1.07+0.15
Therefore ,tms

1.22

sec

Setting proposed on HV side Ip


Setting proposed on HV side tms
Curve selected
Earth fault current is set at 20 % of the rated Current
Required Earth Fault setting Ie>

0.7
0.41
Normal Inverse
0.2 x61.23
12.246

0.02

0.41

12.246/100
0.12246
0.15
Normal Inverse

Therefore,Setting
Therefore Recommended setting
Curve selected

Amps
Amps
x In

Time Multiplier Setting for Normal Inverse curve


0.02

tms=Required time to trip 't' /[0.14/(I


-1]
f /I
s )
In this incidence, time required to trip, t=0.45+0.15
Therefore ,tms

0.60

Setting proposed on HV side Ie>


Setting proposed on HV side tms for Ie
Curve selected

0.15
0.34
Normal Inverse

0.34
x In

Transformer LV side Phase Rated current


The O/C Pickup setting is usually 110% of the rated Current
Over current setting at 3.3 kV side
setting at 3.3 kV side (CT Secondary)
Rounded off to
Time Multiplier Setting for Normal Inverse curve
tms=Required time to trip 't' /[0.14/ 0.02-1]
(If/Is)
In this incidence, time required to trip t=1.07,
Therefore

this

585.73
Amps
1.10 x 585.73
644.31
Amps Over current
0.81
Amps I > (Ip)
0.85
x In

arrived at
1.07
sec
,tms

based

on

0.36
Curve

Normal Inverse

Setting proposed on LV side Ip

0.85

Amps Setting proposed


on LV side tms

0.36

Amps
current is set at 20 % of the rated Current
Required Earth Fault setting Ie>

Therefore,Setting
Therefore Recommended setting

Earth
0.2 x585.73
117.146

fault

Amps
117.15/800

Amps

0.1464325
0.15

In
Curve selected

Time Multiplier Setting for Normal Inverse


curve
tms=Required time to trip 't' /[0.14/ 0.02-1]
(If/Is)
In this incidence, time required to trip t
Therefore ,tms
Setting proposed on LV side Ie>
Setting proposed on LV side tms for Ie
Curve selected

Normal Inverse

0.45

0.27
0.15
0.27
Normal Inverse

x In

Setting Calculation for Power Transformers 400 kVA

3.3kV
CTHV:100/
,
1
-5% to +5%

0.433kV
400
kVA

CTLV:650/1

Transformer capacity

Secondary Voltage
Transformer HV side CT details CTHV
Turns Ratio
Transformer LV side CT details CTLV
Turns Ratio
Percentage Impedance of Transformer
3 Phase Min. Fault Current at 3.3 kV Bus as per report
3 Phase Min Fault current at 0.433 kV Bus as per report
side Phase Rated current
side Phase Rated current
Fault Current on HV side
Fault Current on LV side
setting is usually 110% of the rated Current
Over current setting at 3.3 kV side
setting at 3.3 kV side (CT Secondary)
Rounded off to
Time Multiplier Setting for Normal Inverse curve
tms=Required time to trip 't' /[0.14/ 0.02-1]
(If/Is)
In this incidence, time required to trip, t =0.15+0.15
Therefore ,tms
Setting proposed on HV side Ip
Setting proposed on HV side tms
Curve selected
Earth fault current is set at 20 % of the rated Current
Required Earth Fault setting Ie>

400
kVA Primary Voltage
3.3
kV
0.433
kV
100/1
100
650/1
650
4.50%
6806
Amps
9339
Amps Transformer HV
69.98
Amps Transformer LV
530.43
Amps Max Through
1225.39
Amps Max Through
9339.00
Amps The O/C Pickup
1.10 x 69.98
76.98
Amps Over current
0.77
Amps I > (Ip)
0.80
x In

0.30
0.80
0.12
Normal Inverse
0.2 x69.98
13.996

13.996/100
Therefore,Setting
Therefore Recommended setting
Curve selected

Time Multiplier Setting for Normal Inverse curve


tms=Required time to trip 't' /[0.14/ 0.02 (If/Is)

sec

0.12

0.13996
0.15
Normal Inverse

Amps
Amps
x In

-1]
In this incidence, time required to trip t
Therefore ,tms
Setting proposed on HV side Ie>
Setting proposed on HV side tms for Ie
Curve selected

0.30

0.20
0.15
0.20
Normal Inverse

x In

Transformer LV side Phase Rated current


The O/C Pickup setting is usually 110% of the rated Current
Over current setting at 0.433 kV side
setting at 0.433 kV side (CT Secondary)
Rounded off to
Time Multiplier Setting for Normal Inverse curve
tms=Required time to trip 't' /[0.14/ 0.02-1]
(If/Is)
In this incidence, time required to trip t
Therefore ,tms

530.43
Amps
1.10 x 533.36
583.48
Amps Over current
0.90
Amps I > (Ip)
0.90
x In

0.15

sec

0.06

Curve
Setting proposed on LV side Ip

Normal Inverse
0.90

Setting proposed on LV side tms


Earth fault current is set at 20 % of the rated Current

0.05
0.2 x533.36

Amps

106.672

Amps
Amps

Required Earth Fault setting Ie>

106.672/650
Therefore,Setting
Therefore Recommended setting
Curve selected

Time Multiplier Setting for Normal Inverse curve


tms=Required time to trip 't' /[0.14/ 0.02-1]
(If/Is)
In this incidence, time required to trip t
Therefore ,tms

0.164110769
0.18
Normal Inverse

Amps

x In

0.15

0.10

Setting proposed on LV side Ie>


Setting proposed onLV side tms for Ie

0.18
0.10

Curve selected

Normal Inverse

x In

Sample Calculations for Relay settings for Motor Feeder


1. Available motor data

Sl No

Size

Value

1.01 Power
1.02 Rated voltage
1.03 Motor rated current IA

units
580 kW
3.3 kV
120 A

1.04 Max. starting current (at 100 % Vn)

6 xIA

1.05 Rated Power factor


1.06 Full load efficiency
1.07 Starting time (at 100% Vn)
1.08 Starting time (at 80% Vn)
1.09 Max. blocked rotor time hot @100 %Voltage
1.10 Max. blocked rotor time Cold @100% Voltage
1.11 Locked rotor Current
2. General power system data

Parameter

0.89
95.30 %
2 sec
3 sec
20 sec
25 sec
720 A

Value

2.01 CurrentTransformer rated current,phase primary


2.02 Current Transformer rated current, phase secondary
2.03 Core Balance CurrentTransformer rated current,phase primary
2.04 Core balance Current Transformer rated current, phase secondary

Units
150 A
1A
50 A
1

Sample Calculations
Fulload current of Motor IA

120 A

CT secondary current corresponding to full load current


I base current for the relay(IB)
Max. starting current (at 100 % Vn)

IA x CT ratio
120x 1/150
0.8 x In
6X IA

Starting Current
CT secondary current corresponding to Starting Current
Starting current in terms of IB
Starting current in terms of IN
High set current I>> is normally set 1.3times the starting current
CT secondary current corresponding to High set Over current I>>
Rounded off to
High set Current I>> In terms of IB

13

=6 x
120 720
=720 x 1/150 A
4.8 A
6 xIB
4.8 xIN
=1.3 x 720
936 A
=936*1/150
6.24 A
6.25 xIN
7.8 xIB

Calculation for the Value of Stabilizing Resistor -TR1


Setting:
The setting volatge may be determined by:
VS = IF/n [Rct + 2RL + Ra ]
VS = Setting Voltage
IS = Setting Current
IF = Fault level in CT Primary
n = CT Ratio
Rct = Resistance of CT at operating temperature
RL = Lead resistance at operating temperature
Ra = Additional resistance due to relay,contact/connection resistance etc at operating temperature
The Full CT requirement is therefore : Class X, ratio N,CT resistance Rct and knee point voltage > 2 x Vs

Transformer 1 Details
TRF Capacity =
TRF Primary =
TRF Secondary =
CT Primary(n)
CT Secondary =
TRF Impedance =
n =

3500 kVA
33000 volts
3300 volts
800 Amps
1 amps
7.15 %
800

CT Secondary wiring Length =


CT Secondary wiring size =
Resistance of conductor =
CT resistance(RCT) =
CT magnitization current(Im) =
Fault level in CT Primary, Not taking source fault into account
IF Secondary =
Fault level in CT Primary, as per report taking Source
fault into consideration
IF Secondary =
Lead Resistance:
RL= CT Secondary wiring Length x Resistance of Conductor per
meter
Additional Resistance: Ra=0.01 ohms
Vs=If/n (Rct+2RL+Ra)
Knee point voltage must be in excess of 2 x Vs
V kn

52 met
4 Sq.mm
4.61 ohms per km
5 ohms
4 mA
8564.46Amps
10.71 Amps
6806.00Amps
8.51 Amps
52*4.61/1000 ohms
0.23972ohms
0.01
46.70 volts
93.40 volts
93.40 volts

10% Percent setting


Required Loop Resistance value
Rs=Vs/Is
Is=10 %
Is= 0.1 Amps
Vs=
Rs=
Relay VA burden= VA

10
0.1 Amps
46.70 volts
467.01ohms
1
1 ohms

Relay resistance= VA/Is


Rstab=Rs-Relay resistance

466.01Ohms

14

Calculation for the Value of Stabilizing Resistor- TR 2


Setting:
The setting volatge may be determined by:
VS = IF/n [Rct + 2RL + Ra ]
VS = Setting Voltage
IS = Setting Current
IF = Fault level in CT Primary
n = CT Ratio
Rct = Resistance of CT at operating temperature
RL = Lead resistance at operating temperature
Ra = Additional resistance due to relay,contact/connection resistance etc at operating temperature
The Full CT requirement is therefore : Class X, ratio N,CT resistance Rct and knee point voltage > 2 x Vs

Transformer 2 Details
TRF Capacity =
TRF Primary =
TRF Secondary =
CT Primary(n)
CT Secondary =
TRF Impedance =
n =
CT Secondary wiring Length =
CT Secondary wiring size =
Resistance of conductor =
CT resistance(RCT) =
CT magnitization current(Im) =
Fault level in CT Primary: Not taking source fault into account
IF Secondary =
Fault level in CT Primary: as per report
IF Secondary =
Lead Resistance:
RL= CT Secondary wiring Length x Resistance of Conductor per
meter
Additional Resistance: Ra=0.01 ohms
Vs=If/n (Rct+2RL+Ra)
Knee point voltage must be in excess of 2 x Vs
V kn

3500 kVA
33000 volts
3300 volts
800 Amps
1 amps
7.15 %
800
32 met
4 Sq.mm
4.61 ohms per km
5 ohms
4 mA
8564.46Amps
10.71 Amps
6806.00Amps
8.51 Amps
32*4.61/1000 ohms
0.14752ohms
0.01
45.13 volts
90.27 volts
90.27 volts

10% Percent setting


Required Loop Resistance value
Rs=Vs/Is
Is=10 %
Is= 0.1 Amps
Vs=
Rs=
Relay VA burden= VA

10
0.1 Amps
45.13 volts
451.33ohms
1
1 ohms

Relay resistance= VA/Is


Rstab=Rs-Relay resistance

450.33Ohms

15

Setting Details for


33 kV SwitchBoard

16

Setting Details 33 kV Switch Board


33kV Incomer 1 & 2
Relay type: Areva P127 Located in Panels 3 & 7
SCOPE OF FUNCTION
Address
Setting Title
Fault Records
Function 50/51
Function 50N/51N
Function 27
Function 59
Function 50BF
Other functions are disabled
Power System Data 1
Title Setting
CTs
CT Primary
CT Secondary
PT
PT Primary
PT Secondary
Phase over current Protection: 50/51
Setting name
Units
50-2 pickup
I> >
50-2 Delay
T I>>
51-1Pickup
I>
51-1Delay
tI>
Time dial
I> TMS
IEC Curve

Ground over current Protection: 50N/51 N


Setting name
Units
50N-2 Pickup
Ie>>
50N-2 Delay
Te>>
51N-1Pickup
Ie>
51N-1Delay
TIe>
Delay type
Time dial
Ie> TMS
IEC Curve

Setting Range
Setting
Enabled/Disabled Enabled

Range
10..50000 A
1A/5A
110..132000V
57-130,220-480

Setting
100
1
33000/3
110/3

Range
0.1~40.00 A
0.00..150.00 s
0.4~10.00 A
0.00..150.00 s
0.02~1.5
IEC Standard
Inverse(SI) ,IEC
Very Inverse(VI)
,IEC Extremely
Inverse(EI)

Setting
8
0.3
1.25
NA
0.2
IEC
Standar
d
Inverse

unit Prim Value


800
x In
s
125
x In

Range
0.01 to 8 Ien
0.02..99.00 s
0.002 to1 Ien
0.02..150.00 s

Setting
NA
NA
0.2
NA
DT
0.38
IEC
Standar
d
Inverse

unit Prim Value

0.02~1.5
IEC Standard
Inverse(SI) ,IEC
Very Inverse(VI)
,IEC Extremely
Inverse(EI)

x In

20

Over Voltage Protection 59


Setting name
Mode selection
Over voltage Stage 1
Time Delay Stage 1
Over voltage stage 2
Time Delay Stage 2
Under Voltage Protection 27
Setting name
Mode selection
Under voltage Stage 1
Time Delay Stage 1
Under voltage stage 2
Time Delay Stage 2
Circuit Breaker failure
Setting name
Mode selection
Set Current
CB Fail Time
Block I>
Block Ie>

Units
U> ?
U>
tU>
U>>
tU>>

Range
Setting unit Prim Value
No or AND or OR
OR
36300
2V-260V
121 V
0-260 s
3 sec
37950
2V-260V
126.5 V
0-260 s
1 sec

Units
U< ?
U<
tU<
U<<
tU<<

Range
Setting unit Prim Value
No or AND or OR
OR
29700
2V-130V
99 V
0-260 s
3 sec
28050
2V-130V
93.5 V
0-260 s
1 sec

Units
CB Fail ?
I< BF
tBF
U<<
tU<<

Range
Yes or No
0.02 -1.0 In
0-10s
Yes or No
Yes or No

Setting unit Prim Value


Ye
s0.2 xIn
20
0.15 sec
No
No

33kV Bus Coupler


Relay type: Areva P122
SCOPE OF FUNCTION
Address

Located in Panel 5
Setting Title
Fault Records
Function 50/51
Function 50N/51N
Function 50BF

Setting Range
Setting
Enabled/Disabled Enabled

Other functions are disabled


Power System Data 1
Title Setting
CTs
CT Primary
CT Secondary
Phase over current Protection: 50/51
Setting name
Units
50-2 pickup
I> >
50-2 Delay
T I>>
51-1Pickup
I>
51-1Delay
tI>
Time dial
I> TMS
IEC Curve

Ground over current Protection: 50N/51 N


Setting name
Units
50N-2 Pickup
Ie>>
50N-2 Delay
Te>>
51N-1Pickup
Ie>
51N-1Delay
TIe>
Delay type
Time dial
Ie> TMS
IEC Curve

Circuit Breaker failure


Setting name
Mode selection
Set Current
CB Fail Time
Block I>
Block Ie>

Units
CB Fail ?
I< BF
tBF
U<<
tU<<

Range
10..50000 A
1A/5A

Setting
100
1

Range
0.1~40.00 A
0.00..150.00 s
0.4~10.00 A
0.00..150.00 s
0.02~1.5
IEC Standard
Inverse(SI) ,IEC
Very Inverse(VI)
,IEC Extremely
Inverse(EI)

Setting
8
0.3
0.75
NA
0.25
IEC
Standar
d
Inverse

unit Prim Value


800
x In
s
75
x In

Range
0.01 to 8 Ien
0.02..99.00 s
0.002 to1 Ien
0.02..150.00 s

Setting
NA
NA
0.17
NA
DT
0.39
IEC
Standar
d
Inverse

unit Prim Value

0.02~1.5
IEC Standard
Inverse(SI) ,IEC
Very Inverse(VI)
,IEC Extremely
Inverse(EI)
Range
Yes or No
0.02 -1.0 In
0-10s
Yes or No
Yes or No

x In

17

Setting unit Prim Value


Ye
s0.2 xIn
20
0.15 sec
No
No

33kV Outgoing Feeders 1,2 & 3


Relay type: Areva P122
SCOPE OF FUNCTION
Address
Setting Title
Fault Records
Function 50/51
Function 50N/51N
Function 50BF
Other functions are disabled
Power System Data 1
Title Setting
CTs
CT Primary
CT Secondary
Phase over current Protection: 50/51
Setting name
Units
50-2 pickup
I> >
50-2 Delay
T I>>
51-1Pickup
I>
51-1Delay
tI>
Time dial
I> TMS
IEC Curve

Ground over current Protection: 50N/51 N


Setting name
Units
50N-2 Pickup
Ie>>
50N-2 Delay
Te>>
51N-1Pickup
Ie>
51N-1Delay
TIe>
Delay type
Time dial
Ie> TMS
IEC Curve

Circuit Breaker failure


Setting name
Mode selection
Set Current
CB Fail Time
Block I>
Block Ie>

Units
CB Fail ?
I< BF
tBF
U<<
tU<<

Located in Panels 2,4 &8


Setting Range
Setting
Enabled/Disabled Enabled

Range
10..50000 A
1A/5A

Setting
100
1

Range
0.1~40.00 A
0.00..150.00 s
0.4~10.00 A
0.00..150.00 s
0.02~1.5
IEC Standard
Inverse(SI) ,IEC
Very Inverse(VI)
,IEC Extremely
Inverse(EI)

Setting
8
0.05
0.7
NA
0.25
IEC
Standar
d
Inverse

unit Prim Value


800
x In
s
70
x In
s

Range
0.01 to 8 Ien
0.02..99.00 s
0.002 to1 Ien
0.02..150.00 s

Setting
NA
NA
0.15
NA
DT
0.34
IEC
Standar
d
Inverse

unit Prim Value

0.02~1.5
IEC Standard
Inverse(SI) ,IEC
Very Inverse(VI)
,IEC Extremely
Inverse(EI)
Range
Yes or No
0.02 -1.0 In
0-10s
Yes or No
Yes or No

x In

15

Setting unit Prim Value


Ye
s0.2 xIn
20
0.15 sec
No
No

33kV BUS PT LHS and RHS BUS


Relay type: Areva P922
SCOPE OF FUNCTION
Address
Setting Title
Fault Records
Function 27
Function 59
Function 81L
Function 81H
Other functions are disabled
Power System Data 1
Title Setting
PT
PT Primary
PT Secondary
Over Voltage Protection 59
Setting name
Units
Voltage range seletion
Over voltage Stage 1
V>
Time Delay Stage 1
tV>
Over voltage stage 2
V>>
Time Delay Stage 2
tV>>
Over voltage stage 3
V>>>
Time Delay Stage 3
tV>>>
Under Voltage Protection 27
Setting name
Units
Voltage range seletion
Under voltage Stage 1
V<
Time Delay Stage 1
tV<
Under voltage stage 2
V<<
Time Delay Stage 2
tV<<
Under voltage stage3
V<<<
Time Delay Stage 3
tV<<<

Located in Panels 1 & 6


Setting Range
Setting
Enabled/Disabled Enabled

Range
110..132000V
57-130,220-480

Setting
33000/3
57-130

Range
Setting unit Prim Value
57-130/ 220-480
57-130
36300
0.5-200 V
121 V
DT/IDMT 0-100 s
2 sec
37950
0.5V-260V
126.5 V
0-599 s
0.5 sec
39600
0.5V-260V
132 V
0-599 s
0.2 sec
Range
Setting unit Prim Value
57-130/ 220-480
57-130
29700
0.5V-130V
99 V
DT/IDMT 0-100 s
2 sec
28050
0.5V-130V
93.5 V
0-599 s
0.5 sec
26400
0.5V-130V
88 V
0-599 s
0.2 sec

Under /Over Frequency Protection 81 U/81 O


Setting name
Units
Stage 1 selection
F1
Time Delay Stage 1
tF1
Stage 2 selection
F2
Time Delay Stage 2
tF2
Stage 3 selection
F3
Time Delay Stage 3
tF3
Stage 4 selection
F4
Time Delay Stage 4
tF4
Stage 5 selection
F5
Time Delay Stage 5
tF5
Stage 6 selection
F6
Time Delay Stage 6
tF6
Check synchronisationProtection 25
Relay type: Areva SKE 11
Setting name
Units
<
Phase angle Setting
Differential Voltage setting
^V
Time set
t

Range
Setting unit Prim Value
40-60 Hz
48.5 Hz
0-599
3 sec
40-60 Hz
47.5 Hz
0-599
1 sec
40-60 Hz
45 Hz
0-599 s
0.5 sec
40-60 Hz
51.5 Hz
0-599
3 sec
40-60 Hz
52.5 Hz
0-599
1 sec
40-60 Hz
53.5 Hz
0-599 s
0.5 sec
Relay type SKE11
Located in Panel
5
Range
Setting unit Prim Value
o
o
deg
5-90
20
0-10%
5%
0-99sec
0.5 sec

Setting Details
for
3.3kV Switch
Boards

23

Setting Details 3.3 kV Switch Board


3.3kV Incomer 1 & 2
Relay type: Areva P127
SCOPE OF FUNCTION
Address

Setting Title
Setting Range
Setting
Fault Records
Enabled/Disabled Enabled
Function 50/51
Function 50N/51N
Function 27
Function 59
Function 50BF
Function 51NS

Other functions are disabled


Power System Data 1
Title Setting
CT Primary
CT Secondary
Neutral CT for 50NS
CT Primary
CT Secondary
PT
PT Primary
PT Secondary
Phase over current Protection: 50/51
Setting name
Units
50-2 pickup
I> >
50-2 Delay
T I>>
51-1Pickup
I>
51-1Delay
tI>
Time dial
I> TMS
IEC Curve
CTs

Ground over current Protection: 50N/51 N


Setting name
Units
50N-2 Pickup
Ie>>
50N-2 Delay
Te>>
51N-1Pickup
Ie>
51N-1Delay
TIe>
Delay type
Time dial
Ie> TMS
IEC Curve

Range
10..50000 A
1A/5A
10..50000 A
1A/5A
110..132000V
57-130,220-480

Setting
800
1
300
1
3300/3
110/3

Range
0.1~40.00 A
0.00..150.00 s
0.4~10.00 A
0.00..150.00 s
0.02~1.5
IEC Standard
Inverse(SI) ,IEC
Very Inverse(VI)
,IEC Extremely
Inverse(EI)

Setting
unit
5
x In
0.05
s
0.85
x In
NA
0.2
IEC Standard
Inverse

Prim Value
4000

Range
0.01 to 8 Ien
0.02..99.00 s
0.002 to1 Ien
0.02..150.00 s

Setting
unit
NA
NA
0.15
x In
NA
DT
0.27
IEC Standard
Inverse

Prim Value

0.02~1.5
IEC Standard
Inverse(SI) ,IEC
Very Inverse(VI)
,IEC Extremely
Inverse(EI)

680

120

Over Voltage Protection 59


Setting name
Units
Mode selection
U> ?
Over voltage Stage 1
U>
Time Delay Stage 1
tU>
Over voltage stage 2
U>>
Time Delay Stage 2
tU>>
Under Voltage Protection 27
Setting name
Units
Mode selection
U< ?
Under voltage Stage 1
U<
Time Delay Stage 1
tU<
Under voltage stage 2
U<<
Time Delay Stage 2
tU<<
Circuit Breaker failure
Setting name
Units
Mode selection
CB Fail ?
Set Current
I< BF
CB Fail Time
tBF
Block I>
U<<
Block Ie>
tU<<
Sensitive Ground Fault Protection: 51NS
Setting name
Units
Current Set
Ie>
Time Delay
REF Protectioin for Incomer
Relay type: Areva P120
SCOPE OF FUNCTION
Address

Range
Setting
unit
No or AND or OR
OR
2V-260V
121 V
0-260 s
3 sec
2V-260V
126.5 V
0-260 s
1 sec

Prim Value

Range
Setting
unit
No or AND or OR
OR
2V-130V
99 V
0-260 s
3 sec
2V-130V
93.5 V
0-260 s
1 sec

Prim Value

Range
Yes or No
0.02 -1.0 In
0-10s
Yes or No
Yes or No

Setting

Prim Value

Range
0.002 to 1 Ien

Setting
0.1

unit
x Ien

Te>

0.00..150 s

sec

Setting Title
Fault Records
Function 64R

Setting Range
Setting
Enabled/Disabled Enabled

unit

3630
3795

2970
2805

Yes
0.2 xIn
0.15 sec
No
No

160

Prim Value
30

Power System Data 1


Title Setting
Range
CTs
CT Primary
10..50000 A
CT Secondary
1A/5A
Restricted Earth Fault Protection 64R for Incomer 1 (TR1)
Setting name
Units
Range
Current Set
Ie>
0.1~1 In
Time Delay
T Ie>
0.00..150.00 s
Stabilising resistance value for the above setting
Restricted Earth Fault Protection 64R for Incomer 2 (TR2)
Setting name
Units
Range
Current Set
Ie>
0.1~1 In
Time Delay
T Ie>
0.00..150.00 s
Stabilising resistance value for the above setting

Setting
800
1
Setting
0.1
1
466

Prim Value
unit
80
x In
s
ohms

Setting
0.1
1
450

Prim Value
unit
80
x In
s
ohms

3.3kV Bus coupler


Relay type: Areva P122
SCOPE OF FUNCTION
Address

Setting Title
Setting Range
Setting
Fault Records
Enabled/Disabled Enabled
Function 50/51
Function 50N/51N
Function 50BF

Other functions are disabled


Power System Data 1
Title Setting
CT Primary
CT Secondary
Phase over current Protection: 50/51
Setting name
Units
50-2 pickup
I> >
50-2 Delay
T I>>
51-1Pickup
I>
51-1Delay
tI>
Time dial
I> TMS
IEC Curve
CTs

Ground over current Protection: 50N/51 N


Setting name
Units
50N-2 Pickup
Ie>>
50N-2 Delay
Te>>
51N-1Pickup
Ie>
51N-1Delay
TIe>
Delay type
Time dial
Ie> TMS
IEC Curve

Circuit Breaker failure


Setting name
Mode selection
Set Current
CB Fail Time
Block I>
Block Ie>

Units
CB Fail ?
I< BF
tBF
U<<
tU<<

Range
10..50000 A
1A/5A

Setting
800
1

Range
0.1~40.00 A
0.00..150.00 s
0.4~10.00 A
0.00..150.00 s
0.02~1.5
IEC Standard
Inverse(SI) ,IEC
Very Inverse(VI)
,IEC Extremely
Inverse(EI)

Setting
unit
4.5
x In
0.05
s
0.8
x In
NA
0.2
IEC Standard
Inverse

Prim Value
3600

Range
0.01 to 8 Ien
0.02..99.00 s
0.002 to1 Ien
0.02..150.00 s

Setting
unit
NA
NA
0.12
x In
NA
DT
0.25
IEC Standard
Inverse

Prim Value

Setting

Prim Value

0.02~1.5
IEC Standard
Inverse(SI) ,IEC
Very Inverse(VI)
,IEC Extremely
Inverse(EI)
Range
Yes or No
0.02 -1.0 In
0-10s
Yes or No
Yes or No

unit
Yes
0.2 xIn
0.15 sec
No
No

640

96

160

3.3kV Outgoing to 400 kVA Transformer Feeders (3 feeders )


Relay type: Areva P122
SCOPE OF FUNCTION
Address
Setting Title
Setting Range
Fault Records
Enabled/Disabled
Function 50/51
Function 50N/51N
Function 50BF
Other functions are disabled
Power System Data 1
Title Setting
Range
CTs
CT Primary
10..50000 A
CT Secondary
1A/5A
Core balance CT
CT Primary
10..50000 A
CT Secondary
1A/5A
Phase over current Protection: 50/51
Setting name
Units
Range
50-2 pickup
I> >
0.1~40.00 A
50-2 Delay
T I>>
0.00..150.00 s
51-1Pickup
I>
0.4~10.00 A
51-1Delay
tI>
0.00..150.00 s
Time dial
I> TMS
0.02~1.5
IEC Curve
IEC Standard
Inverse(SI) ,IEC
Very Inverse(VI)
,IEC Extremely
Inverse(EI)
Ground over current Protection: 50N/51 N
Setting name
Units
50N-2 Pickup
Ie>>
50N-2 Delay
Te>>
51N-1Pickup
Ie>
51N-1Delay
TIe>
Delay type
Time dial
Ie> TMS
IEC Curve

Range
0.01 to 8 Ien
0.02..99.00 s
0.002 to1 Ien
0.02..150.00 s
0.02~1.5
IEC Standard
Inverse(SI) ,IEC
Very Inverse(VI)
,IEC Extremely
Inverse(EI)

Setting
Enabled

Setting
100
1
50
1
Setting
unit
21
x In
0.3
s
0.8
x In
NA
0.16
IEC Standard
Inverse

Prim Value
2100

Setting
unit
NA
NA
0.15
x In
NA
DT
0.2
IEC Standard
Inverse

Prim Value

80

15

Sensitive Ground Fault Protection: 50G


Setting name
Units
Current Set
Ie>
Time Delay
Circuit Breaker failure
Setting name
Mode selection
Set Current
CB Fail Time
Block I>
Block Ie>

Range
0.002 to 1 Ien

Setting
0.1

unit
x Ien

Te>

0.00..150 s

sec

Units
CB Fail ?
I< BF
tBF
U<<
tU<<

Range
Yes or No
0.02 -1.0 In
0-10s
Yes or No
Yes or No

Setting

unit
Yes
0.2 xIn
0.15 sec
No
No

Prim Value
5

Prim Value
20

3.3kV Outgoing to 450 kVAr Capacitor Panel Feeder (2 feeders )


Relay type: Areva P122
SCOPE OF FUNCTION
Address
Setting Title
Setting Range
Fault Records
Enabled/Disabled
Function 50/51
Function 50N/51N
Function 50BF
Other functions are disabled
Power System Data 1
Title Setting
Range
CTs
CT Primary
10..50000 A
CT Secondary
1A/5A
Phase over current Protection: 50/51
Setting name
Units
Range
50-2 pickup
I> >
0.1~40.00 A
50-2 Delay
T I>>
0.00..150.00 s
51-1Pickup
I>
0.4~10.00 A
51-1Delay
tI>
0.00..150.00 s
Time dial
I> TMS
0.02~1.5
IEC Curve
IEC Standard
Inverse(SI) ,IEC
Very Inverse(VI)
,IEC Extremely
Inverse(EI)
Ground over current Protection: 50N/51 N
Setting name
Units
50N-2 Pickup
Ie>>
50N-2 Delay
Te>>
51N-1Pickup
Ie>
51N-1Delay
TIe>
Delay type
Time dial
Ie> TMS
IEC Curve

Range
0.01 to 8 Ien
0.02..99.00 s
0.002 to1 Ien
0.02..150.00 s
0.02~1.5
IEC Standard
Inverse(SI) ,IEC
Very Inverse(VI)
,IEC Extremely
Inverse(EI)

Setting
Enabled

Setting
150
1
Setting
unit
8
x In
0.2
s
0.6
x In
NA
0.18
IEC Standard
Inverse

Prim Value
1200

Setting
unit
NA
NA
0.1
x In
NA
DT
0.24
IEC Standard
Inverse

Prim Value

90

15

Negative sequence Over Current 46


Setting name
Units
Mode selection
I2> ?
Set Current
I2> ?
Delay type
tBF
Time delay
tI2>
Circuit Breaker failure
Setting name
Units
Mode selection
CB Fail ?
Set Current
I< BF
CB Fail Time
tBF
Block I>
U<<
Block Ie>
tU<<

Range
Yes or No
0.1 -25.0 In
DT or IDMT
0-150s

Setting

Range
Yes or No
0.02 -1.0 In
0-10s
Yes or No
Yes or No

Setting

unit

Prim Value

Yes
0.2 xIn

30

DT
5 sec
unit
Yes
0.2 xIn
0.15 sec
No
No

Prim Value
30

3.3kV BUS PT LHS and RHS BUS


Relay type: Areva P922
SCOPE OF FUNCTION
Address
Setting Title
Fault Records
Function 27
Function 59
Function 81L
Function 81H
Other functions are disabled
Power System Data 1
Title Setting
PT
PT Primary
PT Secondary
Over Voltage Protection 59
Setting name
Units
Voltage range seletion
Over voltage Stage 1
V>
Time Delay Stage 1
tV>
Over voltage stage 2
V>>
Time Delay Stage 2
tV>>
Over voltage stage 3
V>>>
Time Delay Stage 3
tV>>>
Under Voltage Protection 27
Setting name
Units
Voltage range seletion
Under voltage Stage 1
V<
Time Delay Stage 1
tV<
Under voltage stage 2
V<<
Time Delay Stage 2
tV<<
Under voltage stage3
V<<<
Time Delay Stage 3
tV<<<
Under /Over Frequency Protection 81 U/81 O
Setting name
Units
Stage 1 selection
F1
Time Delay Stage 1
tF1
Stage 2 selection
F2
Time Delay Stage 2
tF2
Stage 3 selection
F3
Time Delay Stage 3
tF3
Stage 4 selection
F4
Time Delay Stage 4
tF4
Stage 5 selection
F5
Time Delay Stage 5
tF5
Stage 6 selection
F6
Time Delay Stage 6
tF6

Setting Range
Setting
Enabled/Disabled Enabled

Range
110..132000V
57-130,220-480

Setting
3300/3
110/3

Range
Setting
unit
57-130/ 220-480
57-130
0.5-200 V
121 V
DT/IDMT 0-100 s
2 sec
0.5V-260V
126.5 V
0-599 s
0.5 sec
0.5V-260V
132 V
0-599 s
0.2 sec

Prim Value

Range
Setting
unit
57-130/ 220-480
57-130
0.5V-130V
99 V
DT/IDMT 0-100 s
2 sec
0.5V-130V
93.5 V
0-599 s
0.5 sec
0.5V-130V
88 V
0-599 s
0.2 sec

Prim Value

Range
40-60 Hz
0-599
40-60 Hz
0-599
40-60 Hz
0-599 s
40-60 Hz
0-599
40-60 Hz
0-599
40-60 Hz
0-599 s

Prim Value

Setting

unit
48.5 Hz
3 sec
47.5 Hz
1 sec
45 Hz
0.5 sec
51.5 Hz
3 sec
52.5 Hz
1 sec
53.5 Hz
0.5 sec

3630
3795
3960

2970
2805
2640

Relay Setting details for Motor Feeders in 3.3kV Switch board


(5 Feeders)
1. Available motor data
Relay type Areva P220
Sl No
Size
Value
Units
1.01 Power
1.02 Rated voltage
1.03 Motor rated current IA

580 kW
3.3 kV
120 A

1.04 Max. starting current (at 100 % Vn)

6 xIA

1.05 Rated Power factor


0.89
1.06 Full load efficiency
95.30 %
1.07 Starting time (at 100% Vn)
2 sec
1.08 Starting time (at 80% Vn)
3 sec
1.09 Max. blocked rotor time hot @100 %Voltage
20 sec
1.10 Max. blocked rotor time Cold @100% Voltage
25 sec
1.11 Locked rotor Current
720 A
Thermal replica
(ANSI 49)
Sl No Parameter
Value (Range) Step
Set Value Set unit
2.01 Thermal current threshold I>
0.2 to 1.5 x In
0.01
0.8 xIn
2.02 Trip thermal threshold Set to 100%
2.03 Thermal Alarm stage:
2.04 Reset ratio for Thermal trip
2.05 Tripping time
Io> (Earth Fault) (ANSI 50N/51N)

20 to 100%
30 to 99%
0.1 to 50 s

1.00
%
1.00
% 0.1

80%%
70%%
2s

Sl No Parameter
3.01 Current set
3.02 Time delay
Short Circuit Protection (ANSI 50/51)

Value (Range) Step


Set Value Set unit
0.002 to 1.0
0.01
0.08 xIn
0-100 sec
0.01
0.05 s

Sl No Parameter
4.01 Current set I>>
4.02 Time delay t>>
4.03 Current set I>
4.04 Time delay t> ( tms)
I<(Loss of load ) ANSI 37

Value (Range) Step


Set Value Set unit
0.5 to 40
1
6.25 xIn
0-150
0.1
0.1 s
0.1 to 25
1
0.9 xIn
0.1 -1.5
0.1
1.25

Sl No Parameter
5.01 Current set
5.02 Time delay
Unbalance Protection ( ANSI 46)
Sl No Parameter

Value (Range) Step


Set Value Set unit
20 to 90%
1
30 %
0.02 to 99.9
0.1
1s
Value (Range) Step

Set Value Set unit

6.01 Current Set I2>

0.04 to 0.8 In

0.01

0.1 xIn

6.02 Time delay


6.03 Current Set I2>>
6.04 Time Multiple setting ( TMS) I2>>
6.05 IDMT Time delay

0.02 to 99.9
0.04 to 0.8 In
0.2 to 2
t=TMS x 1.2 (I2/In)

0.1
0.01
0.1

1s
0.2 xIn
1

Prolonged start or stall


Sl No Parameter
7.01 Current set
7.02 Time Delay for prolonged start:
Number of permitted starts
Sl No Parameter
8.01 Number of Cold Starts
8.02 Number of Hot Starts
8.03 T reference
8.04 Restart Inhibition time
8.05 Time between 2 Start ups
Locked Rotor Protection ( ANSI 51LR/50s)
9.01 Current set
9.02 Time Delay for prolonged start:
9.03 Locked rotor Start up Detection

Value (Range) Step


Set Value Set unit
0.5 to 5 In
0.01
2 xIn
1 to 200 s
1
4s
Value (Range) Step
0-5
0-5
10-120 mins
1-120 mins
1-120 mins
0.5 to 5 In
1 to 60 s
No/Input/PF

Set Value Set unit


1
3
1
2
5
60 mins
1
20 mins
1
20 mins

0.01
1

4.8 xIn
4s
No

3.3kV BUS PT LHS and RHS BUS


Relay type: Areva P922
SCOPE OF FUNCTION
Address
Setting Title
Fault Records
Function 27
Function 59
Function 81L
Function 81H
Other functions are disabled
Power System Data 1
Title Setting
PT
PT Primary
PT Secondary
Over Voltage Protection 59
Setting name
Units
Voltage range seletion
Over voltage Stage 1
V>
Time Delay Stage 1
tV>
Over voltage stage 2
V>>
Time Delay Stage 2
tV>>
Over voltage stage 3
V>>>
Time Delay Stage 3
tV>>>
Under Voltage Protection 27
Setting name
Units
Voltage range seletion
Under voltage Stage 1
V<
Time Delay Stage 1
tV<
Under voltage stage 2
V<<
Time Delay Stage 2
tV<<
Under voltage stage3
V<<<
Time Delay Stage 3
tV<<<
Under /Over Frequency Protection 81 U/81 O
Setting name
Units
Stage 1 selection
F1
Time Delay Stage 1
tF1
Stage 2 selection
F2
Time Delay Stage 2
tF2
Stage 3 selection
F3
Time Delay Stage 3
tF3
Stage 4 selection
F4
Time Delay Stage 4
tF4
Stage 5 selection
F5
Time Delay Stage 5
tF5
Stage 6 selection
F6
Time Delay Stage 6
tF6

Setting Range
Setting
Enabled/Disabled Enabled

Range
110..132000V
57-130,220-480

Setting
3300/3
110/3

Range
Setting
unit
57-130/ 220-480
57-130
0.5-200 V
121 V
DT/IDMT 0-100 s
2 sec
0.5V-260V
126.5 V
0-599 s
0.5 sec
0.5V-260V
132 V
0-599 s
0.2 sec

Prim Value

Range
Setting
unit
57-130/ 220-480
57-130
0.5V-130V
99 V
DT/IDMT 0-100 s
2 sec
0.5V-130V
93.5 V
0-599 s
0.5 sec
0.5V-130V
88 V
0-599 s
0.2 sec

Prim Value

Range
40-60 Hz
0-599
40-60 Hz
0-599
40-60 Hz
0-599 s
40-60 Hz
0-599
40-60 Hz
0-599
40-60 Hz
0-599 s

Prim Value

33

Setting

unit
48.5 Hz
3 sec
47.5 Hz
1 sec
45 Hz
0.5 sec
51.5 Hz
3 sec
52.5 Hz
1 sec
53.5 Hz
0.5 sec

3630
3795
3960

2970
2805
2640

Setting Details for PMCC

34

Setting Details 415 V PMCC


415 V Incomer 1 & 2
Relay type: Areva P127
SCOPE OF FUNCTION
Address

Setting Title
Setting Range
Setting
Fault Records
Enabled/Disabled Enabled
Function 50/51
Function 50N/51N
Function 27
Function 59
Function 50BF

Other functions are disabled


Power System Data 1
Title Setting
CT Primary
CT Secondary
PT
PT Primary
PT Secondary
Phase over current Protection: 50/51
Setting name
Units
50-2 pickup
I> >
50-2 Delay
T I>>
51-1Pickup
I>
51-1Delay
tI>
Time dial
I> TMS
IEC Curve
CTs

Ground over current Protection: 50N/51 N


Setting name
Units
50N-2 Pickup
Ie>>
50N-2 Delay
Te>>
51N-1Pickup
Ie>
51N-1Delay
TIe>
Delay type
Time dial
Ie> TMS
IEC Curve

Range
10..50000 A
1A/5A
110..132000V
57-130,220-480

Setting
650
1
415/3
110/3

Range
0.1~40.00 A
0.00..150.00 s
0.4~10.00 A
0.00..150.00 s
0.02~1.5
IEC Standard
Inverse(SI) ,IEC
Very Inverse(VI)
,IEC Extremely
Inverse(EI)

Setting
10
0.05
0.9
NA
0.05
IEC
Standar
d
Inverse

unit Prim Value


6500
x In
s
585
x In

Range
0.01 to 8 Ien
0.02..99.00 s
0.002 to1 Ien
0.02..150.00 s

Setting
NA
NA
0.18
NA
DT
0.09
IEC
Standar
d
Inverse

unit Prim Value

0.02~1.5
IEC Standard
Inverse(SI) ,IEC
Very Inverse(VI)
,IEC Extremely
Inverse(EI)

35

x In

117

Over Voltage Protection 59


Setting name
Mode selection
Over voltage Stage 1
Time Delay Stage 1
Over voltage stage 2
Time Delay Stage 2
Under Voltage Protection 27
Setting name
Mode selection
Under voltage Stage 1
Time Delay Stage 1
Under voltage stage 2
Time Delay Stage 2
Circuit Breaker failure
Setting name
Mode selection
Set Current
CB Fail Time
Block I>
Block Ie>

Units
U> ?
U>
tU>
U>>
tU>>

Range
Setting unit Prim Value
No or AND or OR
OR
456.5
2V-260V
121 V
0-260 s
3 sec
477.25
2V-260V
126.5 V
0-260 s
1 sec

Units
U< ?
U<
tU<
U<<
tU<<

Range
Setting unit Prim Value
No or AND or OR
OR
373.5
2V-130V
99 V
0-260 s
3 sec
352.75
2V-130V
93.5 V
0-260 s
1 sec

Units
CB Fail ?
I< BF
tBF
U<<
tU<<

Range
Yes or No
0.02 -1.0 In
0-10s
Yes or No
Yes or No

36

Setting unit Prim Value


Ye
s0.2 xIn
130
0.15 sec
No
No

415 V Buscoupler
Relay type: Areva P143
SCOPE OF FUNCTION
Address

Setting Title
Setting Range
Setting
Fault Records
Enabled/Disabled Enabled
Function 50/51
Function 50N/51N
Function 27
Function 59
Function 50BF

Other functions are disabled


Power System Data 1
Title Setting
CTs
CT Primary
CT Secondary
Phase over current Protection: 50/51
Setting name
Units
50-2 pickup
I> >
50-2 Delay
T I>>
51-1Pickup
I>
51-1Delay
tI>
Time dial
I> TMS
IEC Curve

Ground over current Protection: 50N/51 N


Setting name
Units
50N-2 Pickup
Ie>>
50N-2 Delay
Te>>
51N-1Pickup
Ie>
51N-1Delay
TIe>
Delay type
Time dial
Ie> TMS
IEC Curve

Range
10..50000 A
1A/5A

Setting
650
1

Range
0.1~40.00 A
0.00..150.00 s
0.4~10.00 A
0.00..150.00 s
0.02~1.5
IEC Standard
Inverse(SI) ,IEC
Very Inverse(VI)
,IEC Extremely
Inverse(EI)

Setting
9
0.05
0.85
NA
0.05
IEC
Standar
d
Inverse

unit Prim Value


5850
x In
s
552.5
x In

Range
0.01 to 8 Ien
0.02..99.00 s
0.002 to1 Ien
0.02..150.00 s

Setting
NA
NA
0.15
NA
DT
0.05
IEC
Standar
d
Inverse

unit Prim Value

0.02~1.5
IEC Standard
Inverse(SI) ,IEC
Very Inverse(VI)
,IEC Extremely
Inverse(EI)

37

x In

97.5

415 V Incomer 3 from DG


Relay type: Areva P127
SCOPE OF FUNCTION
Address

Setting Title
Setting Range
Setting
Fault Records
Enabled/Disabled Enabled
Function 50/51
Function 50N/51N
Function 27
Function 59
Function 50BF

Other functions are disabled


Power System Data 1
Title Setting
CT Primary
CT Secondary
PT
PT Primary
PT Secondary
Phase over current Protection: 50/51
Setting name
Units
50-2 pickup
I> >
50-2 Delay
T I>>
51-1Pickup
I>
51-1Delay
tI>
Time dial
I> TMS
IEC Curve
CTs

Ground over current Protection: 50N/51 N


Setting name
Units
50N-2 Pickup
Ie>>
50N-2 Delay
Te>>
51N-1Pickup
Ie>
51N-1Delay
TIe>
Delay type
Time dial
Ie> TMS
IEC Curve

Range
10..50000 A
1A/5A
110..132000V
57-130,220-480

Setting
50
1
415/3
110/3

Range
0.1~40.00 A
0.00..150.00 s
0.4~10.00 A
0.00..150.00 s
0.02~1.5
IEC Standard
Inverse(SI) ,IEC
Very Inverse(VI)
,IEC Extremely
Inverse(EI)

Setting
6
0.05
0.77
NA
0.27
IEC
Standard
Inverse

unit Prim Value


300
x In
s
38.5
x In

Range
0.01 to 8 Ien
0.02..99.00 s
0.002 to1 Ien
0.02..150.00 s

Setting
NA
NA
0.07
NA
DT
0.57
IEC
Standar
d
Inverse

unit Prim Value

0.02~1.5
IEC Standard
Inverse(SI) ,IEC
Very Inverse(VI)
,IEC Extremely
Inverse(EI)

38

x In

3.5

Over Voltage Protection 59


Setting name
Mode selection
Over voltage Stage 1
Time Delay Stage 1
Over voltage stage 2
Time Delay Stage 2
Under Voltage Protection 27
Setting name
Mode selection
Under voltage Stage 1
Time Delay Stage 1
Under voltage stage 2
Time Delay Stage 2
Circuit Breaker failure
Setting name
Mode selection
Set Current
CB Fail Time
Block I>
Block Ie>

Units
U> ?
U>
tU>
U>>
tU>>

Range
Setting unit Prim Value
No or AND or OR
OR
456.5
2V-260V
121 V
0-260 s
3 sec
477.25
2V-260V
126.5 V
0-260 s
1 sec

Units
U< ?
U<
tU<
U<<
tU<<

Range
Setting unit Prim Value
No or AND or OR
OR
373.5
2V-130V
99 V
0-260 s
3 sec
352.75
2V-130V
93.5 V
0-260 s
1 sec

Units
CB Fail ?
I< BF
tBF
U<<
tU<<

Range
Yes or No
0.02 -1.0 In
0-10s
Yes or No
Yes or No

39

Setting unit Prim Value


Ye
s0.2 xIn
10
0.15 sec
No
No

415V PMCC BUS PT LHS and RHS BUS


Relay type: Areva P922
SCOPE OF FUNCTION
Address
Setting Title
Fault Records
Function 27
Function 59
Function 81L
Function 81H
Other functions are disabled
Power System Data 1
Title Setting
PT
PT Primary
PT Secondary
Over Voltage Protection 59
Setting name
Units
Voltage range seletion
Over voltage Stage 1
V>
Time Delay Stage 1
tV>
Over voltage stage 2
V>>
Time Delay Stage 2
tV>>
Over voltage stage 3
V>>>
Time Delay Stage 3
tV>>>
Under Voltage Protection 27
Setting name
Units
Voltage range seletion
Under voltage Stage 1
V<
Time Delay Stage 1
tV<
Under voltage stage 2
V<<
Time Delay Stage 2
tV<<
Under voltage stage3
V<<<
Time Delay Stage 3
tV<<<
Under /Over Frequency Protection 81 U/81 O
Setting name
Units
Stage 1 selection
F1
Time Delay Stage 1
tF1
Stage 2 selection
F2
Time Delay Stage 2
tF2
Stage 3 selection
F3
Time Delay Stage 3
tF3
Stage 4 selection
F4
Time Delay Stage 4
tF4
Stage 5 selection
F5
Time Delay Stage 5
tF5
Stage 6 selection
F6
Time Delay Stage 6
tF6

40

Setting Range
Setting
Enabled/Disabled Enabled

Range
110..132000V
57-130,220-480

Setting
415/3
110/3

Range
Setting unit Prim Value
57-130/ 220-480
57-130
456.5
0.5-200 V
121 V
DT/IDMT 0-100 s
2 sec
477.25
0.5V-260V
126.5 V
0-599 s
0.5 sec
498
0.5V-260V
132 V
0-599 s
0.3 sec
Range
Setting unit Prim Value
57-130/ 220-480
57-130
373.5
0.5V-130V
99 V
DT/IDMT 0-100 s
2 sec
352.75
0.5V-130V
93.5 V
0-599 s
0.5 sec
332
0.5V-130V
88 V
0-599 s
0.3 sec
Range
40-60 Hz
0-599
40-60 Hz
0-599
40-60 Hz
0-599 s
40-60 Hz
0-599
40-60 Hz
0-599
40-60 Hz
0-599 s

Setting unit Prim Value


48.5 Hz
3 sec
47.5 Hz
1 sec
45 Hz
0.5 sec
51.5 Hz
3 sec
52.5 Hz
1 sec
53.5 Hz
0.5 sec

Time Current Characterstic


Curves

41

10000
1000
100

Motor 2

OG4_3.3kV_SWBD
IC2_33kV_SWBD
BC_33kV_SWBD1
OG1_33kV_SWBD

Cold Stall Time


Hot Stall Time

IC1_3.3kV_SWBD3

10

Time in Seconds

OG1_3.3kV_SWBD

TR1

.01

.1

.5

3300 Volt Phase

10

100
Current in Amperes X 100
Time-Current Characteristic Curves

0 - Path Source2-33kV_SWBD_IC2-33kV_SWBD_BC33kV_SWBD_OG1-TR1-3.3kV_SWBD_IC1-3.3kV_SWBD_OG-Motor

1000

10000
01-08-2014
04:15:16

mahindra_thermal_rev_0701143

10000
1000
100

OG2_3.3kV_SWBD

10

IC2_33kV_SWBD

Time in Seconds

IC1_3.3kV_SWBD3
OG1_33kV_SWBD

BC_33kV_SWBD1

TR1

.01

.1

.5

3300 Volt Phase

10

100
Current in Amperes X 10
Time-Current Characteristic Curves

2 - Source3-33kV_SWBD-TR1-3.3kV_SWBD-CAP_feeder

1000

10000
01-08-2014
05:03:17

mahindra_thermal_rev_0701143

10000
1000
100

IC2_33kV_SWBD
BC_33kV_SWBD1
OG1_33kV_SWBD

.01

.1

Time in Seconds

10

IC1_3.3kV_SWBD3

.5

3300 Volt Ground

10

100
Current in Amperes X 100
Time-Current Characteristic Curves

0 - Path Source2-33kV_SWBD_IC2-33kV_SWBD_BC33kV_SWBD_OG1-TR1-3.3kV_SWBD_IC1-3.3kV_SWBD_OG-Motor

1000

10000
01-08-2014
04:27:13

mahindra_thermal_rev_0701143