1 Seismic Design Criteria

1.1 Based on Saudi Building Code


In accordance with Saudi Building Code 301 chapter 9, figure 9.4.1(a), Jeddah is in Region 6.

Figure 2.1a: Regions for Determination of the Maximum Considered Earthquake Ground
Motion in the Kingdom of Saudi Arabia ( Figure 9.4.1(a) of SBC-301)

S
s
, 0.2 sec Spectral Response Acceleration (% of g) for 5% critical damping and site class B =
25% g = 0.25g - refer figure 9.4.1(h).
S
1
, 0.1 sec Spectral Response Acceleration (% of g) for 5% critical damping and site class B =
10% g = 0.10g - refer figure 9.4.1 (p).
Site Class D assuming stiff soil (refer Table 14.1.1).


Page 2




Site Coefficients values are as follows based on Table 9.4.3 a & b of Saudi Building Code 301:
F
a
1.6 S
s
0.25 and Site
Class D
F
v
2.4 S
1
0.10 and Site
Class D

The maximum considered earthquake spectral response acceleration for short period
S
MS
= F
a
S
s
= 1.6 x 0.25g = 0.40g
The maximum considered earthquake spectral response acceleration for 1 sec period
S
M1
= F
v
S
1
= 2.4 x 0.10g = 0.24g

Figure 2.1b: Maximum Considered Earthquake Ground Motion for the Kingdom of 0.2 SEC
Spectral Response Acceleration (Ss in %g) 5 percent Critical Damping, Site Class B.
(Region 6)-( Figure 9.4.1(h) of SBC-301)





Page 3






Figure 2.1c: Maximum Considered Earthquake Ground Motion for the Kingdom of 1 SEC
Spectral Response Acceleration (S1 in %g) 5 percent Critical Damping, Site Class B.
(Region 6)-( Figure 9.4.1(p) of SBC-301)

1.1.1 Design Spectral Response Acceleration Parameter
Design Spectral Response Acceleration Parameters are as follows based on section 9.4.4 of
Saudi Building Code 301:
S
DS
= 2/3 x S
MS
0.27g
S
D1
= 2/3 x S
M1
0.16g



Page 4




1.1.2 Design Response Spectrum
Based on Saudi Building Code 301 section 9.4.5, the design response spectrum is as follows.

Figure 2.1.2: Saudi Building Code Region 4 design response spectrum site class A
where,
S
a
= The design Spectral Response Acceleration
T = The fundamental period of structure
T
o
= 0.2 S
D1
/S
DS
= 0.119 sec
T
s
= S
D1
/S
DS
= 0.593 sec
For T T
o
, S
a
= S
DS
(0.4+0.6 T/T
o
)
For T
o
TT
s
, S
a
= S
DS

For T>T
s
, S
a
= S
D1
/T
1.1.3 Occupancy Importance Factor
Based on Saudi Building Code 301 table 1.6-1, the Sky Villa is under Category II which
suggests I = 1.0 in accordance with table 9.5.
Sa = SD1/T
T0 Ts
SD1
SDS

Page 5



1.1.4 Seismic Design Category
Based on section 9.6.1, as S
DS
is equal to 0.27g which is greater than 0.167g but less than
0.33g and the building is under the occupancy category II, the seismic design category of the
structure is B. S
D1
is equal to 0.16g which is greater than 0.20g but less than 0.133g and the
building is under the occupancy category II, the seismic design category of the structure is C.
For seismic design category C the following analytical procedures are permitted based on Table
10.6.1 for regular or irregular structure:
(a) Equivalent Lateral Force Analysis Section 10.9
(b) Modal Response Spectrum Analysis Section 10.10
For Building Frame System with ordinary reinforced concrete shear walls which is not limited for
seismic design category C, the following design parameters have used for the sky villa lateral
analysis under seismic load.
Response Modification
Coefficient, R
4
SBC -Table 10.2
System Overstrength
Factor, o
2.5
Deflection Amplification
Factor, Cd
4.5
Reliability Factor 1.0
SBC- Section
10.3.3.1



Page 6




1.1.5 Seismic Base Shear for the Building
The fundamental time period of the building has been determined based on section 10.9.3.
The maximum limit of T = Cu Ta where Cu = 1.58 from Table 10.9.3.1 based on SD1 = 0.16g
and Ta = Ct hn^x from equation 10.9.3.2-1.
Ct = 0.055 from Table 10.9.3.2 for all other structural system and x = 0.75 where as hn, the
height above the base to the highest level of the structure i.e, from B1 to level 3 = 19.3 m.
Ta = 0.055 x (180)^0.75 = 2.7 sec. & Ta,max = 1.58 x 2.7 = 4.27 sec.
Based on Saudi Building Code 301 section 10.9 using equivalent lateral force procedure V = C
s

W where Cs is the seismic response coefficient.
C
s

S
DS

R/I
0.27
4.0/1.0
= 0.0675
C
s, max


S
D1
T (R/I)
0.16
4.27 x (4.0/1.0)
= 0.0094
C
s, min


0.044 S
DS
I 0.044 x 0.27 x 1.0 = 0.012
V
design
= 0.012 x W



Page 7




2 Load Combinations
In accordance with Saudi Building Code 301 section 2.3 load combinations for strength design
have been used as follows.
(a) 1.2D+1.0E+f1 L (Eq. 2.3.2-5)
(b) 0.9D+1.0E+1.6H (Eq. 2.3.2-7)
where f1=1.0 for areas as places of public assembly, for live load in excess of 5.0 kPa, and for
parking garrage live load
f1 = 0.5 for other live load
D = dead load
E = Earthquake load = Q
E
+ 0.2 S
DS
D = 1.0 Q
E
+ 0.2 x 0.27 x D = Q
E
+ 0.054 D to be used
for Eq. 2.3.2-5
E = Earthquake load = Q
E
- 0.2 S
DS
D = 1.0 Q
E
- 0.2 x 0.27 x D = Q
E
- 0.054 D to be used for
Eq. 2.3.2-7
H = load due to lateral earth pressure, ground water pressure or pressure of bulk materials
L = live load
Lr = roof live load

Specific strength design load combinations are to be used :
(i) 1.254D+1.0EQx+0.3EQy+0.5L
(ii) 1.254D-1.0EQx-0.3EQy+0.5L
(iii) 1.254D+1.0EQy+0.3EQx+0.5L
(iv) 1.254D-1.0EQy-0.3EQx+0.5L
(v) 0.846D+1.0EQx+0.3EQy
(vi) 0.846D-1.0EQx-0.3EQy
(vii) 0.846D+1.0EQy+0.3EQx+0.5L
(viii) 0.846D-1.0EQy-0.3EQx+0.5L