Vous êtes sur la page 1sur 5

Reliance Industries Ltd.

Fire, Safety & Environment


Procedure Manual
Page No. 1 of
!."#" N$ISE LE%EL M$NI&$RIN'
Introduction(
The purpose is to identify the high noise areas and recommend necessary
corrective actions to overcome the unhealthy conditions.
Noise level survey within plant after commissioning of new plant or
equipments is done once in six months for three times. After this noise mapping
of the area is done and regular survey is stopped. Noise level survey on the
periphery of factory is done once in six month to ensure the compliance with
the statutory norms.
Procedure (
Noise level survey is carried with the help of sound level meter Optel
or any other reputed make. And report is issued in the form described
in 2.!"A#.
$ound level meter is calibrated at %&'(%) *ombay once in a year.
$ound level meter has measurement range ! to +! d* and frequency
range +., to -!!! ./. %t has four indication ranges i.e. ! to -!) ,!
to +!! 0 -! to +! d*. Noise levels are measured in d*A scale.
(onitoring is done at (ax. hold position with wind screen on the
microphone. All readings are taken at +1(eter distance from the
source.

2or existing plant) noise mapping is done and noise contour diagrams
are prepared. These are displayed in the plant for reference and
identification of high noise level area.
2or new area3equipments noise level monitoring reports are prepared
and engineering and administrative recommendations are worked out
wherever feasible. 4opy of report is sent to plant .O& of respective
plant for necessary action like) intallation of caution board)
demarkation of area or control of noise at source through engineering
measures at their end.
%n case if noise in peripheral area is found higher than the norms) the
source will be investigated by 'nv. 4ell and concerned plant .O&
will be informed to take corrective measure.
Section No. ( !."#" Rev. ( #1 )ate ( #".#.!##!
Reliance Industries Ltd. Fire, Safety & Environment
Procedure Manual
Page No. ! of
References (
Operation (anual of Optel sound level meter.
*$4 audit guideline.
Res*onsi+ilities (
A. 'nvironmental cell will conduct Noise 5evel survey 3 prepare noise
mapping diagram with the support of plant personnel.
*. Noise level survey on peripheral roads within factory premises will be done
by 'nvironmental 4ell.
Records(
Noise 5evel (onitoring 6eport is prepared as per format 2.!"A#. And a
table 2.!"*# indicating duration for permissible esposure limit at 7 -,
d*A is attached with the report. The same is preserved for two years.
4alibration record of sound level meter is preserved for two years.
Reason for Revision ( 2irst %ssue
Pre*ared ,y ( -tul .a/i 01ec2ed +y ( N. .. %alec1a -**roved +y ( San/eev Pat1a2
Section No. ( !."#" Rev. ( #1 )ate ( #".#.!##!
Reliance Industries Ltd. Fire, Safety & Environment
Procedure Manual
Page No. " of
2.!"A#
Noise Level Monitoring Re*ort
Name of the plant 8
&ocument No. 8
6eport No. 8
$r. No. 5ocation Noise 5evel in d*A
9revious On 4urrent On
6emarks 3 Observation8
6ecommendations8
Section No. ( !."#" Rev. ( #1 )ate ( #".#.!##!
Reliance Industries Ltd. Fire, Safety & Environment
Procedure Manual
Page No. 3 of
2.!"*#
9ermissible 'xposure 5imits for 7 -,1d*A noise level:.
Noise
level
Exposure
NOISE(dBA) HOUR MIN NOISE(dBA) HOUR MIN NOISE(dBA) HOUR MIN
85 8 0
85.1 7 50 86.1 6 13 87.1 4 56
85.2 7 40 86.2 6 5 87.2 4 50
85.3 7 30 86.3 5 57 87.3 4 44
85.4 7 20 86.4 5 50 87.4 4 37
85.5 7 10 86.5 5 42 87.5 4 31
85.6 7 1 86.6 5 34 87.6 4 25
85.7 6 51 86.7 5 26 87.7 4 19
85.8 6 41 86.8 5 18 87.8 4 12
85.9 6 31 86.9 5 10 87.9 4 6
86 6 21 87 5 2 88 4 0
88.1 3 55 89.1 3 7 90.1 2 28
88.2 3 50 89.2 3 3 90.2 2 25
88.3 3 45 89.3 2 59 90.3 2 22
88.4 3 40 89.4 2 55 90.4 2 19
88.5 3 35 89.5 2 51 90.5 2 16
88.6 3 30 89.6 2 47 90.6 2 12
88.7 3 25 89.7 2 43 90.7 2 9
88.8 3 20 89.8 2 39 90.8 2 6
88.9 3 15 89.9 2 35 90.9 2 3
89 3 10 90 2 31 91 2 0
91.1 1 58 92.1 1 33 93.1 1 14
91.2 1 55 92.2 1 31 93.2 1 12
91.3 1 53 92.3 1 29 93.3 1 11
91.4 1 50 92.4 1 27 93.4 1 9
91.5 1 48 92.5 1 25 93.5 1 8
91.6 1 45 92.6 1 23 93.6 1 6
91.7 1 43 92.7 1 21 93.7 1 5
91.8 1 40 92.8 1 20 93.8 1 3
91.9 1 38 92.9 1 18 93.9 1 2
92 1 35 93 1 15 94 1 0
94.1 0 59 95.1 0 47 96.1 0 37
94.2 0 58 95.2 0 46 96.2 0 36
94.3 0 56 95.3 0 45 96.3 0 35
94.4 0 55 95.4 0 44 96.4 0 35
94.5 0 54 95.5 0 43 96.5 0 34
94.6 0 53 95.6 0 42 96.6 0 33
94.7 0 51 95.7 0 41 96.7 0 32
94.8 0 50 95.8 0 40 96.8 0 32
94.9 0 49 95.9 0 39 96.9 0 31
95 0 47 96 0 37 97 0 30
Section No. ( !."#" Rev. ( #1 )ate ( #".#.!##!
Reliance Industries Ltd. Fire, Safety & Environment
Procedure Manual
Page No. of
97.1 0 29 98.1 0 23 99.1 0 19
97.2 0 29 98.2 0 23 99.2 0 18
97.3 0 28 98.3 0 22 99.3 0 18
97.4 0 28 98.4 0 22 99.4 0 17
97.5 0 27 98.5 0 21 99.5 0 17
97.6 0 26 98.6 0 21 99.6 0 17
97.7 0 26 98.7 0 20 99.7 0 16
97.8 0 25 98.8 0 20 99.8 0 16
97.9 0 24 98.9 0 19 99.9 0 15
98 0 23 99 0 18 100 0 15
100.1 0 15 101.1 0 12 102.1 0 9
100.2 0 14 101.2 0 11 102.2 0 9
100.3 0 14 101.3 0 11 102.3 0 9
100.4 0 14 101.4 0 11 102.4 0 9
100.5 0 13 101.5 0 11 102.5 0 8
100.6 0 13 101.6 0 10 102.6 0 8
100.7 0 13 101.7 0 10 102.7 0 8
100.8 0 13 101.8 0 10 102.8 0 8
100.9 0 12 101.9 0 10 102.9 0 8
101 0 11 102 0 9 103 0 7
103.1 0 7 104.1 0 6 105.1 0 5
103.2 0 7 104.2 0 6 105.2 0 5
103.3 0 7 104.3 0 6 105.3 0 4
103.4 0 7 104.4 0 5 105.4 0 4
103.5 0 7 104.5 0 5 105.5 0 4
103.6 0 7 104.6 0 5 105.6 0 4
103.7 0 6 104.7 0 5 105.7 0 4
103.8 0 6 104.8 0 5 105.8 0 4
103.9 0 6 104.9 0 5 105.9 0 4
104 0 5 105 0 4 106 0 3
: *$4 audit guideline suggests T5; for noise exposure level should be< -, d*A.
Section No. ( !."#" Rev. ( #1 )ate ( #".#.!##!