This document provides information on portable earthing lances used in high voltage substations. It discusses the characteristics and components of the earthing lances. The key points are:
- Portable earthing lances allow for earthing of phase conductors in de-energized substations without permanent installation. They consist of an insulated tube, earth contact, phase contact and can include extension rods.
- The document outlines the different types of earthing lances and their components like fixed points and describes how projects are planned and lances installed.
- Visual inspections of the characteristics of the lances and their components are recommended before each use to ensure safety. This includes checking for damage, proper
This document provides information on portable earthing lances used in high voltage substations. It discusses the characteristics and components of the earthing lances. The key points are:
- Portable earthing lances allow for earthing of phase conductors in de-energized substations without permanent installation. They consist of an insulated tube, earth contact, phase contact and can include extension rods.
- The document outlines the different types of earthing lances and their components like fixed points and describes how projects are planned and lances installed.
- Visual inspections of the characteristics of the lances and their components are recommended before each use to ensure safety. This includes checking for damage, proper
This document provides information on portable earthing lances used in high voltage substations. It discusses the characteristics and components of the earthing lances. The key points are:
- Portable earthing lances allow for earthing of phase conductors in de-energized substations without permanent installation. They consist of an insulated tube, earth contact, phase contact and can include extension rods.
- The document outlines the different types of earthing lances and their components like fixed points and describes how projects are planned and lances installed.
- Visual inspections of the characteristics of the lances and their components are recommended before each use to ensure safety. This includes checking for damage, proper
Portable Earthing Lances by Dipl.-Ing. (FH) Christian Niklis I. General Characteristics, usage, type test, short-circuit current capacity, current traces 17.10.2013 2 17.10.2013 3 Characteristics Only fixed points for phase and earth connection are permanently installed in the substation When needed, the earthing lance will be transported to the earthing place, and connected to the fixed points The earthing rod is a firm part of the earthing lance The earthing lance, together with its fixed points, is a tested system for which we guarantee 17.10.2013 4 17.10.2013 5 17.10.2013 6 Usage Working procedure following the 5 safety rules, in de-energised condition Short circuit-proof connection between phase conductor and earth installation in high voltage substations of up to 380/420kV Conductor heights of up to approximately 8 metres Installation in nearly any position on phase supports, or on a number of different switchgear
17.10.2013 7 Type tests Type tests according to IEC 1219/ DIN EN 61219: January 1995, 6.4 (Test of short circuit current capacity) 1999: 80kA/0.5s (peak 200kA) (IPH-No. 1722.135.9.150) 2009: 63kA/1.0s (peak 158kA) (IPH-No. 1926.2090727.0637)
17.10.2013 8 Videos of IPH 1999 and 2009 17.10.2013 9 17.10.2013 10 Short circuit current capacity Test values (= rated values): 36 kA for 3.0s 44 kA for 2.0s 63 kA for 1.0s 80 kA for 0.5s and shorter duration
(values are not valid for type 618136) 17.10.2013 11 Nach dem Kurzschluss ...
17.10.2013 12 Current traces 17.10.2013 13 17.10.2013 14 17.10.2013 15 II. System components Types of earthing lances, phase fixed points, earth fixed point, extension rods 17.10.2013 16 Types of earthing lances 618136: Lg=2900, Li=500, Lh=454mm *) (short circuit current capacity 63kA/0.5s) 618137: Lg=4100, Li=550, Lh=507mm *) 618138: Lg=6100, Li=550, Lh=807mm 618141: customised 697033: customised *)
*) Handle extendable
(weight for 618138: approx. 17kg) 17.10.2013 17 Phase fixed points Diameter of contact cross bar 30mm Length of cross bar min. 120mm Distance between cross bar and conductor clamping or flange plate (clear opening) min. 120mm Current-proof design particularly with higher voltages above 110kV (if needed, additional measures for field control need to be taken on site) Sufficient short circuit current capacity 17.10.2013 18 17.10.2013 19 17.10.2013 20 17.10.2013 21 Earth fixed point Type 618135 Mechanical bearing for insertion and removal of the earthing lance (support and guidance) Low resistance electric connection to earth during insertion procedure (relief of residual voltages) Short circuit-proof connection to earth after complete contacting of the earthing lance 17.10.2013 22 17.10.2013 23 17.10.2013 24 17.10.2013 25 Extension rods 698780: L=500mm 618124: L=1000mm 698795: L=1200mm 698781: L=1500mm 698772: L=1700mm 618125: L=2000mm 618111: customised 17.10.2013 26 III. Project planning and installation Details of phase conductor, details of subconstruction, project planning, installation, adaptor for earth fixed point , additional earth connection 17.10.2013 27 17.10.2013 28 Essential: Fill-in questionnaire completely! 17.10.2013 29 Details of phase conductor Height and run (horizontal, vertical, ...) Material (Al or Cu) Type (tube, line, single, double or multiple conductor) Dimensions (diameter, cross-section, spacing and alignment of double or multiple conductors) If applicable, information about corona rings, connectors, isolators, etc. Details of subconstruction Height Construction (with photos and drawing of steel construction, if possible)
17.10.2013 30 17.10.2013 31 Project planning Based on the available information, and after clarification of technical queries, a project drawing is generated The project drawing shows all important components and dimensions, and permits assessment of feasibility Commercial offer and installation on site are based on the project drawing 17.10.2013 32 Projektierungszeichnung
Video of installation in Hungary 17.10.2013 33 17.10.2013 34 Adaptor for the earth fixed point In many cases use of an adaptor is required Adaptors need to make safe electric and mechanic connection between the earth fixed point and the subconstruction For production and installation of such adaptors, ARCUS is ready to offer advice. 17.10.2013 35 17.10.2013 36 Additional earth connection 17.10.2013 37 Installed to some extent, but not required (Type tests were passed without additional electric connection) IV. Visual inspection on site Characteristics for examination (see also DIN EN 61219: January 1995, C.3) of earthing lances immediately before each use 17.10.2013 38 General characteristics for examination Is the earthing lance classified for the respective earthing point? Is the instruction for use attached or is it available on site? Are type lable and other markings clearly legible? Is the earthing lance complete as far as recognisable? Is the earthing lance straight?
17.10.2013 39 17.10.2013 40 Test characteristics for insulated tube Is the varnish of the insulated tubes still in good order? Is the insulated tube free of fissures, cracks, or other distortions? Is the hand protection disc mounted and safely fixed to the insulated tube? Is the end cap at the end of the insulated tube mounted? Is the insulated tube completely turned back counter-clockwise? Is the insulated tube easy to turn (function check)?
17.10.2013 41 17.10.2013 42 Test characteristics for earth contact Are the slots in the aluminium tube completely stress-relieved (parallel edges)? Are the slots in the aluminium tube free of soiling? Is the surface of the aluminium tube, especially in the area between the red dots (contact area), metallic bright, and free of fissures, cracks, roughness, burnings? Are the slots widening up when the in- sulated tube is turned (function check)? 17.10.2013 43 17.10.2013 44 Test characteristics for transition between contacts Is the surface of the aluminium tube free of fissures, cracks, deformations, or deep scratches? 17.10.2013 45 17.10.2013 46 Test characteristics for phase contact Is the surface of the contact area metallic bright, free of fissures, cracks, breakings, roughness, burnings? Is the centre of the clamp part movable (function check)? Is the head of the earthing lance clean and free of heavy soiling (sand, soil, etc.)? 17.10.2013 47 17.10.2013 48 17.10.2013 49 Test characteristics for earth fixed point Is the surface inside the earth fixed point free of fissures, cracks, roughness, burnings, as far as visible? Is the earth fixed point complete (especially the stainless steel rings on both ends of the earth fixed point), as far as recognisable? Is the earth fixed point rotatable as far as the adjustment of the rotation range limitation allows (function check)? 17.10.2013 50 17.10.2013 51 Thank you very much for your attention! 17.10.2013 52