The Design of the plant is to minimize hazardous chemicals emission and losses
thereby ensuring maximum safety of the plant and negligible environmental
impact.
The products of the plant are taken by campaign basis according to the market
demand. These are
This synthesis gas is reacted with propylene to give Aldehydes, N – Bal, and I–
Bal by low pressure Hydroformylation.
The products 2-EH, N-BUOH and I-BUOH are produced on campaign basis. N
– Butyraldehyde after Aldolisation and Hydrogenation produces 2-Ethyl Hexanol.
Hydrogenation of individual N – Butyraldehyde and I – Butyraldehyde, produce two
other Alcohols N – Butanol and I – Butanol on campaign basis, respectively.
Product Uses
1) 2-ETHYL HEXANOL
2) 2-ETHYL HEXANOL
Product Use
2) BUTANOL
Product Use
Fire Vehicles: are mobile vehicles meant for transporting equipment /fire fighting
agents / fire fighting crew to the site of fire / other emergency.
Foam :are an aggregate of air filled bubbles that will float on the surface of a
flammable liquid . They are made from aerated solutions of water and a proper
proportion of foam concentrate. Foam forms a cohesive floating blanket on the liquid
surface that extinguishes the fire by mothering an cooling the fuel. They also prevent
re-ignition of combustibles mixtures of vapour and air.
Foam Tender: is a mobile fire tender consisting of pump, foam proportioning system,
foam monitor, water and foam compound tank which can generate foam for
blanketing / fire fighting
DCP Tender: is a mobile fire vehicle consisting of Dry Chemical Powder Vessels,
Nitrogen gas cylinders. The Dry Chemical Powder can be used with pressure to
knockdown the flame / fire.
Foam Nurser : is a mobile fire vehicle consisting of pump, foam compound tank
which can be used to replenish the foam compound in the foam tenders /Trailer
mounted foam tank monitors at emergency site.
Emergency Rescue Tender (ERT) : for handling LPG emergencies is a mobile fire
vehicle consisting of pump, compressor for handling LPG emergencies (particularly
off-site area) including emergency equipment.
Water Tender : is a mobile fire vehicle consisting of pump, water tank which can be
used to deliver water with pressure or foam with auxiliary connection for fire fighting.
Sources of Heat
i. Heat from Mechanical Energy : Friction always produces heat, every
moving thing is a possible source of heat energy spinning shafts cause
considerable heat in the bearings that support them, to prevent the
destruction of the shaft and to reduce the temperatures when the equipment
is operating it is lubricated. Oils and greases not only make the shaft to turn
smoothly, but also conduct the heat away from the shaft and the bearing
rapidly. As such a plant engineer should look on every friction source as a
potential fire hazard.
ii. Heat by compression : Anything that is squeezed or compressed gets
warmer. When gas is compressed it heats up, this principle is used in diesel
engine by compressing the air to such an extent as to burn the fuel when
injected.
iii. Heat by Electricity : As electricity flows through a conductor, heat is
produced. If the cable is large enough to carry the current the heat produced
will be harmlessly dissipated, on the other hand if the cable is small and the
current is more, it will produce excessive heat and will create a serious fire
risk. To prevent such incidence correct size fuse or proper circuit breakers to
be installed in the circuit.
iv. Heat from Chemical Action : A strong acid will produce considerable heat
when water is added to it, even time for instance will generate enough heat
to ignite combustible materials when water is added to it. Now a days
various chemicals are used in industries as a result fire in industries have
increased manifold due to carelessness or accidental mixing of chemicals
which infact releases excessive heat. A striking example Is glycerine and
potassium permanganate when these two chemicals comes in contact first
fumes (slow combustion) and soon afterwards burst into flames (rapid
combustion)
The absorption of oxygen by certain vegetable or animal oils and facts and
the absorption of oxygen by certain substances like coal may lead to such an
increase in temperature as to bring out spontaneous ignition. However to
raise the temperature to a point sufficient to cause spontaneous combustion,
it is essential that the heat generated by the various chemical reaction should
be in excess of the heat dissipated. It is therefore, recommended that the
adequate ventilation should be provided to minimize the potential danger.
Ignition Temperature
The temperatures at which combustion can take place fall into three categories,
namely, Flash Point, Fire Point and Spontaneous Ignition Temperature.
a. Flash Point : At certain temperature, the vapor given off by a liquid will
“Flash” momentarily on the application of a small flame but will not continue to
burn. There are several types of apparatus for determining flash point (Abel,
Pensky-Martyn)
b. Fire Point : This may be defined as the lowest temperature at which the heat
from the combustion of a burning vapor is capable of producing sufficient vapor
to enable the combustion to continue. It will be seen that the difference between
flash point and fire point is that the flash point temperature is only the required
to produce vapor to enable a momentary flash to take place where as the fire
point temperature has to be high enough to produce sufficient vapor to sustain
the reaction, so that the substance continues to burn independently of the
ignition source.
c. Spontaneous Ignition Temperature : this is the lowest temperature at which
the substance will ignite spontaneously that is the substance will burn without
the introduction of flame or other ignition source. This implies that under
certain conditions some materials undergo spontaneous combustion. This is
sometimes referred to as Ignition Temperature.
It should be noted that specific gravity has no units, it is simply a number or ratio
and it is the same whatever system of units is being used for expressing densities.
b. Vapour Density : The density of a gas or vapour is often given in relation to the
density of an equal volume of Hydrogen or Air, under the same condition of
temperature and pressure. Hydrogen is often used as a basis of vap9our density
because it is the lightest gas, and the vapour density of Air as compared with
Hydrogen is 14.4. For carbon dioxide the corresponding figure is 22 and carbon
dioxide is, therefore, about 1 ½ times as heavy as air at the same temperature and
pressure. For fire service purposes it is much more convenient to compare the
density of gases and vapours with that of Air, but in that case the reference gas
should be qucted e.g. vapour density of methane is 0.856 (air-1) or the vapour
density of methane is a 8 (hydrogen-1).
The following are the examples of vapour density as compared with Hydrogen.
Three conditions have long been regarded as essential components of any fire :
1. Fuel (i.e. the combustible material).
2. Oxygen (from the atmosphere).
3. Heat (essential to start the fire initially, but maintained bye the fire itself once it has
started).
These are familiar to fire fighters as the ‘fire triangle’ or pyramid. If any one of
these conditions is removed, the fire goes out. Methods of fire fighting thus depend on
removing or shutting off the source of fuel, excluding oxygen or removing heat from
the fire faster than it is liberated. A fourth condition is now recognised. Flames proceed
chemically as branched chain reactions through the intermediary of free radicals which
are constantly being formed and consumed. If the free radicals can be removed and
prevented from continuing the chain reaction, the flame goes out.
D. Metal fires.
Class A Fires. Carbonaceous Solids
The general method of extinguishing class A fires is by water jets which quench
the fire and cool the material to below its ignition temperature.
Class A fires are often deep-rooted and well below the surface of the material,
so that sufficient water must be applied to penetrate and cool the whole of the burning
material to below its ignition temperature.
Flash point. The flash point of a flammable liquid is the lowest temperature at
which enough vapour is given off near the surface of the liquid to produce a flammable
mixture with air; that is a mixture which may be ignited by a spark or other source of
ignition, and which contains the proper ratio of vapour and air to support combustion.
These rations vary widely from liquid to liquid, but it should always be assumed that
any flammable solvent above its flash point is in equilibrium with a flammable vapour-
air mixture. Once a fire has started, its heat rapidly vapourises more liquid until the
whole mass is a flame. In general, the lower the flash point of a liquid the more
flammable is the material and the more violent the resulting fire.
The fact that a liquid is at a temperature below its flash point does not mean that
it is safe. If a material such as kerosene with a flash point of 400C is brought into
contact with a source of intense heat – a welding torch, furnace or open fire-a small part
of it could be heated above the flash point, give off vapour and burst into flame. The
heat thus produced would heat the rest of the kerosene and the fire would spread. A
mist of a high flash solvent is also almost as easily ignited as if it were a true mixture of
air and vapour.
Nearly all flammable vapurs are heavier than air, so that explosive mixtures of
air and vapour will spread over the ground or floor when the air is still and flow into
depressions in the ground, drains, trenches and cellars.
Building in which flammable liquids are used should have good ventilation and
the quantities of liquid in a building should be kept to a minimum. No smoking should
be the rule in a building where flammable liquids are used and a careful check should
be made regularly to eliminate all other possible sources of ignition. Empty containers
of flammable liquids should not be kept in the building but returned to stores for
refilling.
Many of the fire involving flammable liquids have occurred where the liquid
was present as a paint, lacquer or rubber solution or paste solvent. The vapour from the
drying article where the solvent was used or from the open paint or paste tin built up in
concentration and spread to a point of ignition until a flash back occurred.
Where flammable liquids are used in plants for washing and dipping operations
the tanks or containers should be provided with hinged covers which are automatically
closed by a fusible link and a spring operated mechanism if the tank or container
catches fire.
1. For liquids heavier than water (e.g. carbon disulphide) and at temperatures lower
than the boiling point of water.
2. For liquids readily soluble in water provided either that the quantity of diluted
material is small enough to be contained or provided that the material can be
washed away without causing an unacceptable pollution problem.
Alternatively the most suitable3 extinguishing agents are dry powder, foam,
carbon dioxide or a suitable vapourising liquid provided they are used in conditions
where they do not create a new hazard. If water has to be used to cool other equipment
or plant close to a vapourising liquid fire, care must be taken that the water does not
flow into the burning liquid and spread the fire.
When a fire involving a flammable liquid has been extinguished there is often a
danger that fresh vapour will form and mix with air creating an explosive vapour
mixture which will re-ignite, often on hot or glowing material left from the earlier fire.
While various measures may be taken to prevent this, there are some cases where it is
better to let a vapourising liquid fire burn itself out, at the same time concentrating
efforts on cooling objects exposed to the fire and preventing it from spreading.
Class C Fires, Gases and Electrical
There is always a serious danger whenever a fire from a leaking or fractured gas
main or container is extinguished, that the unignited gas continuing to escape will mix
with air to form an explosive mixture. This when reignited may result in a serious
explosion which causes more destruction and injury than the original fire would have
done if left to burn itself out. The only safe way of estinguishing a gas fire is to shut off
the supply of gas to the fire.
Great care should be taken where electrical appliances and switches are exposed to a
gas leak. It may seem logical to switch off any electric motors or other electrical
equipment in the neighborhood of such a leak. But unless the switch is flameproof the
mere act of switching off a motor may create a sparking in the switch which could
ignite an explosive gas-air mixture surrounding the switch. Electrical appliances
exposed to such conditions should therefore be switched off remotely from a switch in
a safe area and not from a switch exposed to the gas-mixture, unless the switch itself is
known to be flameproof.
If a gas cylinder starts to leak and the leak cannot be immediately stopped, it
should be moved at once to the open air where the gas can disperse safely. If a cylinder
has been involved in a fire, it should be emptied and tested in a proper cylinder testing
station or returned to its makers properly marked for testing.
The larger appliances used exclusively by fire brigades which include mobile
pumps, mobile turntables, platforms and extension ladders, rescue and demolition
equipment are not dealt with in this section since they come under the control of a
trained and experienced fire officer.
Equipment which is handled by the normal (and also in most cases by the works
fire brigade or department) works personnel is dealt with here. It falls broadly into two
categories.
1. Fixed appliances and hose reels.
2. Portable appliances.
Fixed installations using water and high expansion foam are most suitable for
general protection while those using other extinguishing agents are intended for special
risks such as oil or electrical fires. The choice and positioning of fixed installations
should be considered when a works or building is being designed, since it is more
expensive to install them once building has been completed.
Hose Reels
Hose reels are first-aid fire extinguishing equipment provided for the use of the
occupants of a building or works and they may be installed instead of, or in addition to,
portable water type extinguishers. When installed they will also be used on small fires
by the brigade on arrival. This causes less water damage than the brigade’s larger
hoses.
With one type of hose reel, all that is necessary to obtain a jet of water is to
grasp the nozzle, pull out the amount of hose needed to reach the fire and open the cock
at the nozzle. The action of unwinding the reel or removing the nozzle from a special
wall fitting turns on the water supply valve. With another type, a valve on the water
inlet to the reel must be opened manually before the hose is run out.
A hose reel may be fixed or pivoted. The fixed type has guides fitted so that the
hose can be pulled off the reel without kinking or jamming. The pivoted type swings to
the direction in which the hose is pulled.
Nozzles for hose reels are available with internal diameters of 4.5-6.5 mm. The
size chosen depends mainly on the pressure of water available. Nozzles should give a
minimum flow of 0.38 liters per second. For a 4.8 mm bore nozzle, this requires a
water pressures of 2.5 kg/ cm2 gauge at the nozzle. For a 6.4 mm bore nozzle this
requires a water pressure of 0.8 kg/cm2 gauge at the nozzle. The pressure loss caused by
friction through 10 m of hose at a flow rate of 0.38 liters/second is 0.15 kg/cm2 for a 19
mm bore hose and 0.035 kg/cm2 for a 25mm hose.
Hose reels may be supplied with fixed covers to protect them from dust. Dirt
and light which cause deterioration of the rubber tubing. They should be positioned so
that no part of a building is more than 6 m from a nozzle when the hoses are fully
extended, making due allowance for obstructions.
The flow of water through a hose reel with nozzle can be simply checked by
measuring the maximum horizontal throw of the jet by directing it over a flat roof or
open floor. A nozzle with a bore of 4.8 mm should give a maximum throw of at least
12 m and a nozzle with a bore of 6.5 mm should give a maximum throw of at least 18
m.
Hose reels require regular maintenance and checking at least once a year, in
accordance with manufacturers recommendations. Brief instructions for operating a
hose reel should be displayed on or close to it. All employees should be trained to use
hose reels, including how to pull the hose round obstacles.
Hydrants
Hydrants are arrangements of piping outlets to which large diameter hose (64
mm or more) may be connected for use by the fire brigade or fully trained works
firemen. Some hydrants inside buildings which are known as dry risers are kept empty
until they are needed. These are used in cold climates where water in a wet riser might
freeze, and also in very tall buildings where water will not reach the top of the riser
until the fire pump is started.
Other hydrants, known as wet risers, are kept permanently full of water. If the
water pressure in the fire main is not sufficient to deliver it to hydrant outlets at the top
of tall buildings must be supplied with water from a pump, usually a mobile one carried
by a fire brigade. Wet risers are generally preferred to dry once in situations where they
can be used.
Hydrants may be fitted with foam inlets to which firemen attach a supply of
foaming agent that mixes with water in the hydrant and hose.
Automatic Sprinklers
These consist of a system of pipes, spray nozzles and heat operated valves by
means of which a fire is automatically detected, the alarm given and water delivered to
the fire. Sprinklers are useful for stores and other buildings containing combustible
materials which are left unattended. The cost of the installation may be partly or wholly
offset by the reduction in the fire insurance premium paid.
Similar systems may also be used on the outside of buildings and tank to keep
them cool if a fire develops near them and so to prevent the fire from spreading to
them.
Multi-storey buildings are protected, with similar but larger ducts which run
from roof to ground level. One or more floors may be flooded with a foam of very low
density but sufficient stability not to collapse at once when exposed to a fire.
The foam may be filled with carbon dioxide instead of air. Its action is to
smother and blanket a fire.
This is a relatively new system which has been mainly used to protect
basements and tunnels to which access may be difficult if a fire develops there. It is
finding wider application in warehouses and large buildings. The local fire brigade
should be consulted for advice when the installation of such a system is considered.
This is mainly suitable for flammable liquid fires where the liquid is immiscible
with water. Liquids such as alcohols which mix with water tend to break down the
foam blanket. But for these conditions special compounds are available, which give
stable foams, although they are more expensive than protein foam.
Gas extinguishing systems consist of a supply of the inert gas under pressure
(usually in cylinders), a system of pipework and valves delivering the inert gas to the
points of application and an automatic detection and initiating system which opens inert
gas valves once the fire has been detected. It also, in many cases, closes doors and
ventilation ducts. These systems operate by reducing the oxygen content of the
atmosphere and/or by interrupting the chemical reaction in a flame.
Most of the gases used are suitable for electrical equipment and plants handling
flammable liquids. This system is particularly suitable for protecting valuable
equipment which is easily damaged by water and foam, such as computers. For these
systems to operate most effectively, the fire fighting equipment should be housed in a
gas-tight compartment which is closed to the atmosphere when a fire starts. Carbon
dioxide installations need special care to avoid introducing risks of ignition by static
electricity.
Dry Powder
Dry powder is a term used for various free-flowing powders which when
poured or otherwise discharged over a fire will extinguish it. The compositions of many
fire extinguishing powders are not publicised by their makers for obvious reasons. They
generally contain three principal ingredients each with a particular function.
Dry powder installations comprise dry powder container to which a gas cylinder
(usually carbon dioxide) is coupled, and a system of piping and outlets which are
located above the places where fires are likely to break out. They can be operated
automatically or manually by opening valve on the gas cylinder so that the gas drives
the powder to the outlets.
These installations are suitable for flammable liquids and electrical equipment
and for protecting some processes involving solids which are easily damaged by water
or foam.
Portable Appliances
Portable fire extinguishers may be used to deliver water, dry powder, foam,
carbon dioxide or a vapourising liquid to the seat of a fire. Their use should, as far as
possible, be standardised and the minimum number of types necessary should be
carried. Hose reels are generally preferable.
Supervisors should be abel to identify the different classes of fires and should
know which type of portable extinguisher to use. All personnel should know how to
recongnise and use the various types of extinguishers present. Practice sessions should
be set up to ensure that all personnel act promptly and effectively in dealing with small
fires.
When using a water-filled extinguisher, direct the jet at the base of the flame
and keep it moving across the area of fire. A fire moving vertically should be attacked
at its lowest point and followed up. Seek out any hot spots after the main fire is
extinguished.
When a liquid fire has been extinguished by foam, the foam blanket left over
the liquid remains in position thus preventing re-ignition and allowing the liquid to
cool. Foam extinguishers should therefore be used for liquid fires where the liquid has
been burning for some time and has become hot.
Foam is not effective on flowing liquids, whether the flow is horizontal or
vertical. Foam conducts electricity and should not be used on live electrical fires. Most
water miscible liquids break up ordinary foams.
When a liquid on fire is in a container, direct the jet at the far inside edge of the
container, or at an adjoining vertical surface above the level of the burning liquid. This
breaks up the jet and allows the foam to build up and flow across the surface of the
liquid. When this is not possible, stand well back and direct the jet slightly upward so
that the foam falls on to the surface of the liquid. Move the jet gently from side to side
to cover the surface of the liquid. Do not direct the jet into the liquid because this will
dive the foam beneath the surface and render it ineffective. It may also splash the
burning liquid on to surrounding objects.
These are the best type of extinguisher for dealing with fires of flammable
liquids. They extinguish the flames over the liquid and thus act faster than foam. They
can deal with larger areas of burning liquid than other extinguishers of the same size,
and they are effective on fires of flowing liquid. Dry powder can be safely used on
electric fires. The main limitation of dry powder is that it gives no protetion against re-
ignition after application ceases since it has poor quenching properties. It is less
effective than foam on liquid fires where the liquid has become overheated (i.e. through
prolonged burning).
Two kilograms of dry powder can normally extinguish a liquid fire converting
and area of one square meter when properly applied.
Portable Carbon Dioxide Extinguishers
Carbon dioxide extinguishers should only be used sparingly in buildings due to
the dangers of asphyxiating personnel. A second hazard of carbon dioxide
extinguishers is the formation of static electricity in the discharge which can ignite
flammable vapours, sometimes with fatal consequences.
Carbon dioxide acts more rapidly than foam and is more suitable for dealing
with fires which might spread to surrounding materials before a complete foam blanket
could be formed over the burning liquid. Carbon dioxide extinguishers are suitable for
dealing with small fires of liquids flowing over horizontal and vertical surfaces. They
should be used where the main concern is to avoid damage or contamination by dry
powder deposit or foam, for example to laboratory equipment or food preparation.
The cooling properties of carbon dioxide are limited and it gives no protraction
against re-ignition after application ceases. It is less effective that foam for very hot
liquids burning in containers.
Carbon dioxide extinguishers contain the carbon dioxide and high pressure as a
liquid in steel cylinders, with a valve leading via flexible hose to a horn shaped
discharge tube. These extinguishers are normally used with the valve uppermost so that
carbon dioxide is discharged as a gas. If they are inverted, a mixture resembling snow
of carbon dioxide gas and solid carbon dioxide is discharged, provided the extinguisher
is full and the ambient temperature is not excessive.
Portable carbon dioxide extinguishers have capacities ranging from 1 to 6 kg
and a range from 1 to 3 m.
On fires involving liquids, either in containers or on the ground, direct the jet or
discharge horn towards the near edge of the fire and with a rapid sweeping motion
drive the fire towards the far edge until all the flames are extinguished. On fires in
falling liquids, direct the jet or horn at the base of the lames and sweep upwards.
When dealing with electrical equipment fires, first turn off the current. Then
direct the jet or horn straight at the fire. When the equipment is enclosed, direct the jet
or horn straight at the fire. When the equipment is enclosed, direct the jet or horn into
any opening so that it penetrates the interior.
If the extinguisher has a control valve on the discharge, shut it when the fire
appears to be extinguished, wait until the atmosphere clears and, if any flame is then
visible, open the valve and discharge again.
Recharging Extinguishers
All extinguishers should be recharged immediately after use, irrespective of
whether they have been completely or only partly discharged. The safety or fire officer
should arrange for books to be kept by supervisor to record every use of an extinguisher
and when it was recharged.
Ordinary Combustibles
Water
OR Flammable Liquids
CO2
Electrical Equipment
Dry Chemical
Multi-Purpose
Metals
Water is one of the most commonly used extinguishing agents for type A fires. You can recognize an APW
by its large silver container. They are filled about two-thirds of the way with ordinary water, then
pressurized with air. In some cases, detergents are added to the water to produce a foam. They stand
about two to three feet tall and weigh approximately 25 pounds when full.
APWs extinguish fire by cooling the surface of the fuel to remove the "heat" element of the fire triangle.
APWs are designed for Class A (wood, paper, cloth, rubber, and certain plastics) fires only.
Important:
Never use water to extinguish flammable liquid fires. Water is extremely ineffective at extinguishing
this type of fire and may make matters worse by the spreading the fire.
Never use water to extinguish an electrical fire. Water is a good conductor and may lead to
electrocution if used to extinguish an electrical fire. Electrical equipment must be unplugged and/or de-
energized before using a water extinguisher on an electrical fire.
Carbon dioxide extinguishers
This type of extinguisher is filled with Carbon Dioxide (CO2), a non-flammable gas under extreme
pressure. These extinguishers put out fires by displacing oxygen, or taking away the oxygen element of
the fire triangle. Because of its high pressure, when you use this extinguisher pieces of dry ice shoot
from the horn, which also has a cooling effect on the fire.
You can recognize this type of extinguisher by its hard horn and absent pressure gauge.
CO2 cylinders are red and range in size from five to 100 pounds or larger.
CO2 extinguishers are designed for Class B and C (flammable liquid and electrical) fires only.
Important:
CO2 is not recommended for Class A fires because they may continue to smolder and re-ignite after the
CO2 dissipates.
Never use CO2 extinguishers in a confined space while people are present without proper respiratory
protection.
Locations:
Carbon dioxide extinguishers will frequently be found in industrial vehicles, mechanical rooms, offices,
computer labs, and flammable liquid storage areas.
Dry chemical extinguishers
Dry chemical extinguishers put out fires by coating the fuel with a thin layer of fire
retardant powder, separating the fuel from the oxygen. The powder also works to
interrupt the chemical reaction, which makes these extinguishers extremely effective.
Dry chemical extinguishers are usually rated for class B and C fires and may be marked
multiple purpose for use in A, B, and C fires. They contain an extinguishing agent and
use a compressed, non-flammable gas as a propellant.
ABC fire extinguishers are red in color, and range in size from five pounds to 20
pounds.
Dry Chemical extinguishers will have a label indicating they may be used on
class A, B, and/or C fires.
or
Locations:
These extinguishers will be found in a variety of locations including: public hallways,
laboratories, mechanical rooms, break rooms, chemical storage areas, offices,
commercial vehicles, and other areas with flammable liquids
FIRE PROTECTION IN PETROCHEMICAL INDUASTRY
From the above one car well imagine the potential fire risks in a petrochemical
industry. The fire protection can be divided into three phases :
i. By good plant, design and layout
ii. Fire control – keeping the fires localised
iii. Fire extinguishment
i. Plant Design & Layout : A good plant, design and layout, with strict
adherence to safe operating procedures, proper built-in fire prevention system,
fire-fighting training and adequate emergency plan to meet fire emergencies, is
the best way to minimise the possibility of fire damages. Factors to be
considered for the plant layout include adequate spacing and proper
arrangement of various utilities, process units, storage units and vessels, loading
and filling installations. For plant layout, safety rules laid down in the
petroleum act should be followed.
ii. Fire Control : This embodies protection of tanks, pressure vessels, structures,
pipelines and equipment that are effected by direct flame impingement or by
radiate heat exposure. Cooling prevents the spread of fire from its point of
origin to the surrounding areas.
iii. Fire Extinguishers : After adequate fire control measures fire is extinguished
by employing suitable extinguishing media, like water, foam, dry chemical
powder, Co2, Halogenated vapourising .
Storage Tanks
In a petrochemical complex, storage tanks of various types of storing the raw materials
like Naptha, and Zylene as also the other products are required. These materials being
highly inflammable adequate fire protection, fire prevention and fire-fighting
arrangements are very essential. In case of any fire emergency, there must be
arrangement to cool the tanks which is involved and the surroundingones.
Arrangements for fighting the fire is also necessary, while planning the fire protection
arrangement, it should worked out on the basis of meeting a major fire indicants.
Among the extinguishing media water is employed extensively for cooling and foam
generation. The maximum water flow rate is determines by taking into consideration
the possibility of following simultaneous operations.
i. Water for foam generation.
ii. Water for cooling.
i. Water for foam generation : As per N.F.P.A. Handbook and code and
American Institute Standard for petroleum refineries, water for foam generation
for fixed foam pourers should be provided not less than 4.03 L/min for each IM2
of the liquid surface area. For hose streams, at least 6.5 Lit/min of water should
be provided. In case of liquid hydrocarbon a delivery rate of 300 liters of
foam/m2 of burning area is specified for a minimum period of 10 min.
ii. Water for cooling : In a fire emergency the tanks which are on fire to be
cooled as also the adjoining tanks are to be protected from exposure. For these
purposes a flow rate of 10.2 L/min to 20.4 L/min per m2 and 8.16 L/min – 10.2
L/min respectively is considered satisfactory.
Water Storage
Adequate water storage is one of the most essential requirement of fire-fighting system.
The total capacity of water storage as usually based on 4-10 Hrs. duration of fire-
fighting. Provision storage tanks. The fire water storage tanks should be so placed that
water can be delivered under gravity in case of failure of all pumps.
The people who may be in danger act in a calm and orderly manner.
Where necessary, those designated carry out their allotted duties to ensure the safety of
all concerned.
The means of escape are used in accordance with a predetermined and practiced plan.
Formulating a Fire Routine
Before formulating a fire routine, it is essential to visit the premises concerned,
when our fundamental points will need to be considered. The points are :
The type of buildings.
The occupancy.
The existing means of escape.
Fire defense.
a. The type of Buildings :
Are the buildings attached or detached?
Are the buildings single-storey or multi-storey?
Are the buildings of fire-resisting or non-fire-resisting construction?
Will the degree of effective fire-resisting compartmentation preclude the necessity
of total evacuation?
b. The Occupancy :
This covers two points :
i. Population characteristics, i.e. the number of occupants, their distribution in
the building, their physical condition and the way they can be expected to
react in any emergency. The last two characteristics depend on such factors
as age, discipline and whether they are asleep or alert.
ii. The use to which the building is put, i.e. the processes carried on the nature
of the contents of the buildings including furnishings, and goods stored or
displayed.
c. The existing means of escape :
Is the existing means of escape adequate - distance to travel-place of safety -
lighting etc.?
d. Fire Defense :
Have satisfactory arrangements been made to cover the following points?
Type of fire alarm and arrangements for sounding it.
Fire extinguishers - hose reels - fire parties.
Arrangements for calling the fire service.
General and specific notices.
Availability of staff in certain premises, assembly points, roll call.
Training : Repeated practice evacuations will be necessary in many cases to ensure
that the “plan of action” is fully understood and can be carried out efficiently when
the occasion demands. Varying conditions should be assumed for these practices so
that the occupants are familiar with all alternative routes. Labour, turn-over and
newly engaged staff will need to be considered.
The time taken for persons to reach a place of safety will indicate the degree
of efficiency attained by the occupants in their fire drill.
Frequency of Drills
The amount of instruction and frequency of drills will vary according to the
degree of risk i.e. the liability to out break of fire and the size, construction and layout
of the premises and any legislative requirement.
Preamble Introduction
As a result of increased demands for synthetic fibers, detergents, plastics and
fertilizers etc., the petroleum and petrochemical industries are assuming greater
importance in our country. The processes involved in a petrochemical industry are
manifold and depends on the final products manufactured. These industries generally
deal with bulk quantities of highly inflammable materials, mostly liquid and gases and
employ high temperature and pressure ranges for processing which may ignite them
spontaneously. Thus industries are very much susceptible to fire and explosion.
Considering the potential risk in a petroleum industry a sound fire protection plan is of
paramountrimportance for the every existence and growth. Petroleum industries have
essentially table located away from cities and have therefore, to be self-sufficient in fire
fighting arrangement.
FIRE RISK OF ELECTRICITY
Preventive Measures
As a preventive measure against fire due to short circuit, some protective device
should be incorporated in the circuit, such as by “thermal Fuse” or “Magnetic Circuit
Breakers”. In domestic wirings or in the office premises normally, thermal Fuses of the
appropriate rating is inserted in a convenient position, near the main, main switch board
and in industrial installation, where high voltage motors etc. are in operation, magnetic
circuit breakers are to be provided.
In the case of thermal fuses, a metal alloy of low melting point (about 3000F) is
usually inserted in the distribution system. In the event of an excess current flowing
through the circuit, the thermal fuses will melt at a much lower temperature before any
fire could take place and it will disconnect the circuit. Whereas in the event of
industrial motors, when an excess current flows, magnetic circuit breakers will trip the
circuit by the magnetic relay switch render the circuit safe, such as in the single phasing
of multi-phase A.C. motor (commonly known as “Single Phasing”).
Wherever possible, electrical equipment and wiring are best located outside the
areas of most severe hazard.
Lights, for example, may be located outside a hazardous room or enclosure and
illuminate the inside through transparent panels. Motors can be located outside, with
drive shafts extending through the wall or partition, with openings for the shafts tightly
sealed. Controllers, switches, cutouts, remoter scan be located in adjoining, less
hazardous areas. Such arrangements frequently effect a considerable saving.