Académique Documents
Professionnel Documents
Culture Documents
Session Two:
Fundamentals of Earth Electrode Design
Author: Rohit Narayan
Presenter: Chris Holst
ERICO
The electrode resistance is that resistance offered to the flow of current into the
ground down to the expanse where the resistance of the ground becomes so low that
it becomes negligible.
Consider the cut away section of the sheaths surrounding the earth electrode in
Figure 1. In simple terms this resistance can be explained by the following
relationship.
R 1/A
where R is the resistance and A the area of each of the sheaths.
As the distance from the ground rod increases, the surface area of the sheaths, get
larger. This means that at some distance, the additional soil area has negligible effect
on the ground resistance.
It is for this reason, when measuring earth resistance to a remote earth, the test only
needs to be confined to few tens, perhaps a few hundred of metres. For example:
When testing a single 2-metre electrode, the test is referenced to remote earth at
Earthing, Lightning & Surge Protection Forum IDC Technologies
distance of about 40 metres. Any greater reference distance than this would add
insignificantly to the resistance. Testing of earth resistance is discussed in more
detail later in this paper.
It is easier to see which dimensions of the earth electrode will have a greater impact
on the electrode resistance, if we consider what happens to the area of the
hemispherical sheaths. In Figure 2, we see that when the electrode is made longer,
the area increases significantly. Hence 1/A reduces giving us a reduction in the earth
resistance. However, if the diameter of the ground rod is increased, this offers very
little change in the area of the hemispherical shells and hence little changes in the
resistance.
! " ##
&"
'
Another factor that will have an impact on the earth resistance is the conductivity or
resistivity of the soil. It is this factor that makes it impossible to have a one size fits
all earthing design for different sites.
3) Soil Resistivity
Soil resistivity is another name for the specific resistance of the soil. It is measured in
ohm-metres or ohm centimetres. An ohm-metre is that resistivity of the soil when it
has a resistance of 1 ohm between opposite faces of a cube with 1 m sides.
Resistance is directly proportional to soil resistivity. This relationship is not as easy to
compute in real life as it may sound, because soil resistivity will inevitably vary with
depth. The second difficulty in dealing with different locations is that the resistivity
can vary greatly across a large site and from one site to another.
The tables below give an idea of the resistivity of several mediums that are of interest
for the design of grounding system.
MATERIAL
TYPICAL RESITIVITY
Copper
GEM, Material
0.12 ohm.m
Bentonite
2.5 ohm.m
Concrete
30 to 90 ohm.m
Factors that will affect the resistivity of the soil are the soil type, compactness,
chemical composition, temperature and water content. Figure 4 shows the effect of
moisture content and temperature on soil resistivity.
!"
##
#$
% &
'
&
%% ( )
For example, if the resistivity is very high at the top 3 metres but drastically drops
after that depth, the designer would specify electrodes that are driven or drilled to
deeper than 3 metres. Conversely if the resistance does not improve beyond a
certain depth, say 2 metres, then horizontal electrodes may be considered in the
earth electrode design because installing deeper electrodes would yield diminishing
returns.
&
*"+
) ,!
Figure 6 shows a typical record sheet for resistivity measurements. Experience has
shown that many people performing soil resistivity tests do not have a full
appreciation of the extent to which the test needs to be carried out. It is often noted
that only a single or a handful of values are measured. It is recommended that for the
design of an earthing electrode system a comprehensive set of results in the range
from 2-40metres should be requested.
SPACING a
Measured
Value of Re
2
4
6
8
10
12
14
16
18
20
25
30
35
40
&
" )'
Resistivity R =
2 a Re
# +
) $
6
Traditionally software programs have been able to carry out earthing electrode
system designs using two-layer models of soil resistivity. That means that resistivity
measured had to be averaged out to two values with corresponding depths. Modern
software can take multiple layer resistivity values as inputs.
In fact, the real value of software is not so much in computing resistance values for
single or a few electrodes as this can be done easily with formulae. Software can be
powerful tools for calculating resistance of multiple electrodes, step and touch
voltages and also simulating fault current injection.
Another method of calculating the resistance of a single earth rod, when the
dimensions and the resistivity are known is using nomograms. In the example in
Figure 7, a 7m earth rod, of diameter 10mm will produce a resistance of 7.6 ohms if
the reading from the Wenner 4 point test is 1 ohm.
&
&
%%
# %
Rules of thumb and utilisation factors are used in everyday calculations to quickly
compute parallel resistances without excessive analysis.
For example when two electrodes are placed 1 electrode length apart, 85% utilisation
of their parallel resistance is achieved. When these electrodes are 2 electrodes apart,
92 % utilisation is achieved. We sometimes see a rule of thumb used in practice that
states that the electrode spacing needs to be at least twice the electrode depth,
based on this utilisation.
Prior to the existence of software to carry out calculations, nomograms were the
incumbent method of calculating resistance of multiple electrode systems. There is
no reason that these cannot be used today for quick calculations.
Figure 9 shows a nomogram that can be used to design a multiple electrode system
if the resistance of one electrode was known through calculation or measurement.
This has been extracted from the Handbook of the Electricity Authority of NSW,
1973.
&
&
%%
# & '
&
The calculation of the electrode resistance for multiple ground rod systems is quite
easy when using modern software. It is essentially a matter of inputting the soil
resistivity, electrode dimensions and the grid size layout and it will churn out a
number without too much fuss.
7) Measurement of Electrode Resistance
When an electrode system has been designed and installed, it is usually necessary
to measure and confirm the earth resistance between the electrode and true Earth.
The most commonly used method of measuring the earth resistance of an earth
electrode is the 3-point measuring technique shown in Figure 10. This method is
derived from the 4-point method, which is used for soil resistivity measurements.
&*
The 3-point method, called the fall of potential method, comprises the earth
electrode to be measured labelled E (electrode) and two other electrically
independent test electrodes, usually labelled P (potential) and C (current). These
test electrodes can be of lesser quality (higher earth resistance) but must be
electrically independent of the electrode to be measured. An alternating current (I) is
passed between electrodes E and C through the soil while a voltage measurement is
taken between E and P. The resistance from E to true earth, remote earth or
general mass of earth is simply calculated using Ohms Law; Rg = V/I, internally by
the test equipment.
When performing a measurement, the aim is to position the auxiliary test electrode C
far enough away from the earth electrode under test so that the auxiliary test
electrode P will lay outside the effective resistance areas of both the earth system
and the other test electrode (see Figure 11). If the current test electrode, C, is too
close, the resistance areas will overlap and there will be a steep variation in the
measured resistance as the voltage test electrode is moved. If the current test
electrode is correctly positioned, there will be a flat (or very nearly so) resistance
area somewhere in between it and the earth system, and variations in the position of
the voltage test electrode should only produce very minor changes in the resistance
figure.
10
Measurement accuracy can be affected by the proximity of other buried metal objects
to the auxiliary test electrodes. Fences, buildings, buried metal pipes or even other
earthing systems can interfere with the measurement and introduce errors. Often it
is difficult to judge, merely from visual inspection of the site, a suitable location for the
tests stakes and so it is always advisable to perform more than one measurement to
ensure the accuracy of the test.
Fall of Potential Method
This is one of the most common methods employed for the measurement of earth
resistance and is best suited to small systems that dont cover a wide area. It is
simple to carry out and requires a minimal amount of calculation to obtain a result.
The outer test electrode, or current test stake, is driven into the ground a good
distance away from the earth system, This distance will depend on the size of the
system being tested and the inner electrode, or voltage test stake, is then driven into
the ground mid-way between the earth electrode and the current test stake, and in a
direct line between them.
Maximum dimension
across earth system, m
15
30
20
40
30
60
10
43
85
20
60
120
50
100
200
100
140
280
! -
11
The Fall of Potential method incorporates a check to ensure that the test electrodes
are indeed positioned far enough away for a correct reading to be obtained. It is
advisable that this check be carried out, as it is really the only way of confirming the
accuracy of the test results.
To perform a check on the resistance figure, two additional measurements should be
made; the first with the voltage test electrode (P) moved 10% of the original voltage
electrode-to-earth system separation away from its initial position, and the second
with it moved a distance of 10% closer than its original position, as shown in Figure
13.
&
! 0 )'
' 1
' $
%
12
the resistance corresponding to this is the true resistance of the electrode being
measured. In this case it is 20 ohms.
For full details of this method, refer to paper 62975, written by Dr G.F. Tagg, taken
from the proceedings of IEE volume 117, No 11, Nov. 1970.
8) Soil Improvement Techniques
In areas of very high soil resistivity, low resistance cannot be achieved through the
use of buried and driven earth electrodes alone. There are four techniques commonly
used for the improvement of soil. These include:
a) Soluble salts will often give good short-term results and are sometimes necessary.
These are soluble in nature and it is envisaged that these will leach away into the soil
over time. No long-term studies have been done to show their performance over
extended periods.
b) Bentonite and Bentonite-Gypsum mixes are relatively cheap in Australia and
available in abundance. Some caution needs to apply when these are used in very
dry soil conditions as exhibited in large parts of Australia. The IEEE Std 80 2000
Section 14.5 States that
Use of bentonite, a natural clay containing the mineral montmorillionite, which was
formed by volcanic action years ago. It is non-corrosive, stable, and has a resistivity
of 2.5 m at 300% moisture. The low resistivity results mainly from an electrolytic
process between water, Na2O (soda), K2O (potash), CaO (lime), MgO (magnesia),
and other mineral salts that ionize forming a strong electrolyte with pH ranging from
8 to 10. This electrolyte will not gradually leach out, as it is part of the clay itself.
Provided with a sufficient amount of water, it swells up to 13 times its dry volume
and will adhere to nearly any surface it touches. Due to its hygroscopic nature, it
acts as a drying agent drawing any available moisture from the surrounding
environment. Bentonite needs water to obtain and maintain its beneficial
characteristics. Its initial moisture content is obtained at installation when the slurry
is prepared. Once installed, bentonite relies on the presence of ground moisture to
maintain its characteristics. Most soils have sufficient ground moisture so that
drying out is not a concern. The hygroscopic nature of bentonite will take advantage
of the available water to maintain its as installed condition. It may not function well
in a very dry environment, because it may shrink away from the electrode,
increasing the electrode resistance.
c) GEM, or Ground Enhancement Materials usually are poured into drilled holes as a
slurry backfill for the electrodes and set hard over time. This material contains a small
percentage of bentonite and cement, but mostly constitutes a conductive form of
carbon. Formulae used for calculating the resistance for concrete encased electrodes
but using the resistivity value of GEM, can be used to calculate or predict
resistances. It is often not possible to predict the resistance when using other types
of soil improvement techniques. Studies have shown that GEM can produce
Earthing, Lightning & Surge Protection Forum IDC Technologies
13
excellent long-term results in a variety of soil conditions. The IEEE Std 80 2000
Section 14.5 States that
Ground enhancement materials, some with a resistivity of less than 0.12 m
(about 5% of the resistivity of bentonite), are typically placed around the rod in an
augured hole or around grounding conductors in a trench, in either a dry form or
premixed in a slurry. Some of these enhancement materials are permanent and
will not leach any chemicals into the ground. Other available ground enhancement
materials are mixed with local soil in varying amounts and will slowly leach into the
surrounding soil, lowering the earth resistivity.
d) Chemical rods are sometimes used in extreme cases of very high resistivity.
Chemical-type electrodes consist of a copper tube filled with a salt. Holes in the tube
allow moisture to enter, dissolve the salts, and allow the salt solution to leach into the
ground. These electrodes are installed in an augured hole and typically back-filled
with soil treatment. Periodic refilling is required otherwise the electrode will become
ineffective.
9) Step and Touch Voltages
Step and touch voltages are a concern that needs to be incorporated into the
electrode design and testing regime at substations, transmission towers, areas
frequented by people and major sites like wind farms. Figure 15 shows how touch
and step voltages can develop in the near vicinity of a structure, which encounters a
fault current. It also depicts how this voltage can be mitigated, by designing a ground
grid in the area of concern.
&
*"
'
&
IEEE Std 80-2000 in Annex B, C and D provides the methodology and the
calculations for computing the maximum step and touch voltages using formulae.
It has become a common practice these days to compute maximum and step
voltages, using software programs, most of which use the formulae from IEEE Std
80. Modern programs can use two layer soil models or multi layer soil models
referring to the variation in soil resistivity used as a possible input into the software.
14
The example below has been generated by commercially available software and
provided by PhysElec Solutions, courtesy of Dr Franco DAllesandro.
TYPE REFLECTION
RESISTIVITY
THICKNESS
COEFFICIENT
(ohm-meter)
(METERS)
------ ------------- ------------- ------------Air
0.00000
0.1E+11
Infinite
Soil -0.999990
100.000
3.00000
Soil
0.666667
500.000
20.0000
Soil
0.818182
5000.00
Infinite
15
SOIL SURFACE
Z AXIS (METERS)
12
24
36
48
30
Y
IS
AX
18
(M
S)
ER
ET
-6
-18
-30
-30
-18
-6
18
30
X AXIS (M TE
E RS)
3-D View of Conductors
Results:
Resistance of Electrode System: 6.68 ohms
Main Electrode Potential Rise (GPR max.): 13360 volts
13348
13308
13267
13226
13185
13145
13104
13063
13022
12982
12941
12900
12859
12819
12778
12737
12696
12656
12615
12574
16
Safety report:
MAXIMUM
MAXIMUM
ALLOWABLE
COMPUTED
OUTCOME
VALUE (V)
VALUE (V)
---------------------------------------------------------------------TOUCH VOLTAGE (on grid):
542
490
ACCEPTABLE
STEP VOLTAGE (on grid):
1700
364
ACCEPTABLE
All computed voltages in the observation zone are below the maximum
allowable values.
17
345 .. 364
326 .. 345
307 .. 326
287 .. 307
268 .. 287
249 .. 268
230 .. 249
211 .. 230
192 .. 211
173 .. 192
154 .. 173
135 .. 154
116 .. 135
97 .. 116
78 .. 97
59 .. 78
40 .. 59
21 .. 40
2 .. 21
18
be used where high concentrations of current may occur, such as at a neutral-toground connection of generators, capacitor banks, or transformers.
e) The ratio of the sides of the grid meshes usually is from 1:1 to 1:3. Frequent crossconnections have a relatively small effect on lowering the resistance of a grid. Their
primary role is to assure adequate control of the surface potentials. The crossconnections are also useful in securing multiple paths for the fault current, minimizing
the voltage drop.
Figure 16 shows the typical layout of an earth electrode for an electrical substation.
11) Post Installation Measurement of Step and Touch Voltage Measurements.
Most good quality ground testers can be used as an aid to measure step and touch
voltages at an installed site. The measurements are made directly by the use of test
probes supplied with the equipment. A reference probe is connected to the main
earth bar of the facility when these tests are being done. For example the touch
voltage test can be done between a piece of switchgear and a distance of 1 m from
the equipment. Or the tests for step voltages can be done at several locations with
the spacing of 1 m in the ground, for example, outside the fence line. These readings
are measured in ohms and need to be multiplied by the maximum permissible fault
current to obtain the step and touch voltages.
These values should then be compared to maximum permissible values for a
specified body mass.
&
"
#
& 3
)%
19
20
&
# 4
&
)'
&
%
21
Conclusion
The process for the design of the earthing electrode system starts with careful
planning. A scaled site drawing showing where equipment, structures and building
will be installed is a good start. The soil resistivity tests should be completed and
results recorded. If it is not possible to access the site for soil resistivity testing, then
it may be possible to have a series of design scenarios or a scaleable design based
on an assumed range of resistivity values.
The key target criteria in the design are the system resistance to remote earth and
the step and touch voltages. The understanding of the sheath theory of conductivity
helps us decide upon the geometry of the earthing electrodes. Empirical formulae,
nomograms and software programs can be used to carry out the calculations. IEEE
Std 80 used in conjunction with country specific guides like the ENA Earthing Guide
in Australia form an excellent reference set for the design of earthing electrode
systems for electrical substations. AS3015-2004 is an excellent reference for the
design of telecommunications earthing electrode systems.
The earthing grid resistance can be measured using several methods. Fall of
potential methods may be used for small earth grids. Larger grids will require testing
using the slope method or more sophisticated methods. The advantage of the slope
method is that it minimises the chances of error and provides a more accurate result
for larger earthing electrode systems.
Post installation step and touch voltages should be measured where step and touch
voltages are part of the design criteria. The resistances and the step and touch
voltages should be measured after installation and compared with the design values.
Ground improvement materials can be used in soils with high resistivity to reduce the
earth resistance. IEEE Std 80 2000 notes the advantages of cement-based ground
improvement materials like GEM. Care should be taken if using bentonite materials in
dry environments.
22
The most comprehensive test standard for the pre-qualification of connectors used in
earthing electrode systems is IEEE Std 837-2000. Exothermic (CADWELD)
connections pass the test regime stipulated in this standard c-crimps and bolted
connections do not.
Discussing the choice of conductor size is outside the scope of this paper. Various
standards can be referred to for guidance on this. Copper is the most widely used
conductor material for earthing systems. The high incidence of copper theft has led to
the development and introduction of other materials suitable for use as grounding
conductors if consideration is given to their electrical properties relative to copper.
23
Bibliography
1) NSW State Electricity Earthing Handbook, 1973.
2) Standard IEEE 80, - 2000: IEEE Guide for Safety in AC Substation Grounding
3) Standard IEEE 837 IEEE Standard for Qualifying Permanent Connections
Used in Substation Grounding
4) Telecom Training Centre Fiji; Course Notes, Earthing Principles PS001
5) Earthing Training Manual ERICO 2001
6) GROUND MEASURING TECHNIQUES: ELECTRODE RESISTANCE TO
REMOTE EARTH & SOIL RESISTIVITY Elvis R. Sverko ERICO, Inc. Facility
Electrical Protection, U.S.A. Revision Date: February 11, 1999
7) Photos and Images are Courtesy of ERICO Inc.
8) 3 D Graphics of Earth Simulation. Images Courtesy of Dr Franco DAllesandro
9) Paper 62975, written by Dr G.F. Tagg, taken from the proceedings of IEEE
volume 117, No 11, Nov. 1970
10) Grounding Design Example: Generated by PhysElec Solutions, Dr Franco
DAllesandro
11) Standard AS3015 Electrical installationsExtra-low voltage d.c. power
24
&
/ 0
&
&
5& '
4+
25
&
4+
4 4
.4 $
7 .
26
&
9"
:
&
%
&'
%
%
&
&
!" ''
&
!"
&
% $
5& '
27