All Aluminum Conductor, Bare


Construction
Aluminum alloy 1350-H19 wires, concentrically stranded.
Specications
Meets or exceeds the following ASTM specications:
B-230 Aluminum Wire, 1350-H19 for Electrical Purposes
B-231 Aluminum Conductors, Concentric-Lay-Stranded
Applications
Classes* AA and A are used primarily for overhead transmission and
primary and secondary distribution where ampacity must be maintained
and a lighter conductor (compared to ACSR) is desired, when conductor
strength is not a critical factor. Classes B and C are used primarily as bus,

apparatus connectors and jumpers where additional exibility is required.


*Classes refer to stranding and are an indication of relative conductor exibility, AA being the least exible,
C the most exible.
See referenced page in the
Hardware & Supplies section:
Suggested Prep Tool
Cable End Strippers
2x2, 4x4 - I-9

Code Word
Size (AWG
or kcmils) No. of Wires Class
Individual
Wire Dia. (in)
Complete
Cable Dia. (in) DC @ 20C AC @ 20C
Allowable Ampacity
(amps)
Iris 2 7 AA, A .0974 .292 .26000 .31800 185
Poppy 1/0 7 AA, A .1228 .368 .16400 .20000 247
Aster 2/0 7 AA, A .1379 .414 .13000 .15900 286
Phlox 3/0 7 AA, A .1548 .464 .10300 .12600 331
Oxlip 4/0 7 AA, A .1739 .522 .08170 .09990 383
Laurel 266.8 19 A .1185 .592 .06480 .07930 444
Tulip 336.4 19 A .1331 .665 .05140 .06300 513
Daffodil 350 19 A .1357 .679 .04940 .06050 526
Canna 397.5 19 AA, A .1446 .723 .04350 .05340 570
Cosmos 477 19 AA .1584 .792 .03620 .04450 639
Dahlia 556.5 19 AA .1711 .856 .03110 .03820 703
Mistletoe 556.5 37 AA .1226 .858 .03110 .03820 704
Meadowsweet 600 37 AA .1273 .891 .02280 .03550 738
Orchid 636 37 AA, A .1311 .918 .02720 .03550 765
Petunia 750 37 AA .1424 .997 .02300 .02860 847
Arbutus 795 37 AA .1466 1.026 .02170 .02700 878
Magnolia 954 37 AA .1606 1.124 .01810 .02260 982
Bluebell 1033.5 37 AA .1671 1.170 .01670 .02100 1031
Narcissus 1272 61 AA, A .1444 1.300 .01360 .01730 1169
Coreopsis 1590 61 AA .1614 1.453 .01090 .01410 1333
Lupine 2500 91 A .1657 1.823 .00698 .00969 1706
Stranding
Resistance
(Ohms/M-ft)
Other cables not listed here may be available upon request.
Information based on Southwire specs.
AAC
www.ptsupply.com
marketing@ptsupply.com
800-238-7514
2
Aluminum Conductor,
Steel Reinforced
Construction
Aluminum alloy 1350-H19 wires, concentrically stranded about a steel
core. Core wire for ACSR is available with class A, B or C galvanizing;
"aluminized" aluminum coated (AZ); or aluminum-clad (AW). Additional
corrosion protection is available through the application of grease to the
core or infusion of the complete cable with grease.
Specications
Meets or exceeds the following ASTM specications:
B-230 Aluminum Wire, 1350-H19 for Electrical Purposes
B-231 Aluminum Conductors, Concentric-Lay-Stranded
B-232 Aluminum Conductors, Concentric-Lay-Stranded, Coated Steel Reinforced for ACSR
B-341 Aluminum-Coated Steel Core Wire for ACSR/AZ
B-498 Zinc-Coated Steel Core Wire for ACSR
B-802 Zinc-5% Aluminum-Mischmetal Alloy-Coated Steel Core Wire for ACSR
Applications
Used as bare overhead transmission cable and as primary and secondary distribution cable. ACSR offers optimal
strength for line design. Variable steel core stranding enables desired strength to be achieved without sacricing
ampacity.

See referenced page in the


Hardware & Supplies section:
Suggested Prep Tool
Cable End Strippers
2x2, 4x4 - I-9

Code Word AWG


Stranding
(Alum./Stl.) AIum. Steel
Steel
Core
Complete
Cable
Weight
(lbs/M-ft) DC @ 20C AC @ 20C
Allowable
Ampacity (amps)
Swanate 4 7/1 .0772 .1030 .1030 .257 67 .3990 .5190 140
Sparrow 2 6/1 .1052 .1052 .1052 .316 91 .2540 .3320 184
Sparate 2 7/1 .0974 .1298 .1298 .325 107 .2510 .3380 184
Raven 1/0 6/1 .1327 .1327 .1327 .398 145 .1590 .2170 242
Quail 2/0 6/1 .1489 .1489 .1489 .447 183 .1260 .1760 276
Pigeon 3/0 6/1 .1672 .1672 .1672 .502 230 .1000 .1440 315
Penguin 4/0 6/1 .1878 .1878 .1878 .563 291 .0795 .1190 357
Merlin 336.4 18/1 .1367 .1367 .1367 .684 365 .0510 .0625 519
Linnet 336.4 26/7 .1137 .0885 .2654 .720 462 .0505 .0618 529
Pelican 477 18/1 .1628 .1628 .1628 .814 517 .0360 .0442 646
Drake 795 26/7 .1749 .1360 .4080 1.107 1093 .0214 .0263 907
Resistance
(Ohms/M-ft)
Individual Wire
Dia. (in)
Diameter (in)
Other cables not listed here may be available upon request.
Information based on Southwire specs.
ACSR
www.ptsupply.com
marketing@ptsupply.com
800-238-7514
3
Covered Line Wire
Aluminum Conductor
Construction
Aluminum alloy 1350-H19, 6201 or ACSR conductors, concentrically
stranded. Covered with PE or XLP.
Specications
Meets or exceeds the following ASTM specications:
B-230 Aluminum Wire, 1350-H19 for Electrical Purposes
B-231 Aluminum Conductors, Concentric-Lay-Stranded
B-232 Aluminum Conductors, Concentric-Lay-Stranded, Coated Steel
Reinforced (ACSR)

B-399 Concentric-Lay-Stranded 6201-T81 Aluminum Alloy Conductors


Applications
Used primarily for, but not limited to, overhead secondary distribution lines. Installed on insulators, otherwise
treated as a bare conductor.

See referenced page in the


Hardware & Supplies section:
Suggested Prep Tool
Cable End Strippers
2x2, 4x4 - I-9

Code Word
Size
(AWG or kcmils) Stranding
Cover
Thickness (mils)
Total Diameter
(mils) XLP Conv. Poly. Allowable Ampacity
6201 Aluminum Alloy
*Oilnut 1/0 7 60 518 159 159 250
*Waterash 2/0 7 60 567 195 195 290
*Planetree 4/0 7 60 683 297 297 385
All-Aluminum
Pear 4 1 30 264 47 47 135
Peach 2 7 45 373 84 84 180
Quince 1/0 7 60 477 136 136 240
Orange 2/0 7 60 522 167 167 280
Olive 4/0 7 60 626 253 253 370
Pomegranate 4/0 19 60 632 247 247 370
Mulberry 266.8 19 60 694 305 305 430
Annona 336.4 19 60 765 377 377 495
Huckleberry 477 37 80 931 538 538 610
Paw Paw 556.5 37 80 992 619 619 670
Breadfruit 636 61 95 1,081 715 715 720
Persimmon 795 61 95 1,186 877 877 825
Grapefruit 1,033.5 61 95 1,326 - 1,118 970
ACSR
Butternut 4 6/1 30 310 72 72 135
Hickory 4 7/1 30 317 83 83 135
Pignut 2 6/1 45 406 118 118 180
Almond 1/0 6/1 60 518 190 190 235
Pecan 2/0 6/1 60 567 233 233 270
Filbert 3/0 6/1 60 622 288 288 305
Buckeye 4/0 6/1 60 683 357 357 345
Weight (lbs/M-ft)
*AWG equivalent to ACSR construction or 1350 aluminum equivalent.
Information based on Southwire specs.
Other cables not listed here may be available upon request.
Covered Line Wire, Aluminum
www.ptsupply.com
marketing@ptsupply.com
800-238-7514
4
Duplex Service Drop
Construction
Conductors are concentrically stranded, compressed 1350-H19 aluminum.
Insulated with either PE or XLP. Neutral messengers are concentrically
stranded 6201, AAC or ACSR.
Specications
Meets or exceeds the following ASTM specications:
B-230 Aluminum Wire, 1350-H19 for Electrical Purposes
B-231 Aluminum Conductors, Concentric-Lay-Stranded
B-232 Aluminum Conductors, Concentric-Lay-Stranded, Coated Steel Reinforced
(ACSR)
B-399 Concentric-Lay-Stranded 6201-T81 Aluminum Alloy Conductors

B-901 Compressed Round Stranded Aluminum Conductors Using Single Input Wire
Applications
Primarily used for 120V overhead service applications such as street lighting, outdoor lighting and temporary
service for construction. To be used at voltages of 600V phase-to-phase or less and at conductor temperatures not
to exceed 75C for PE insulated conductors or 90C for XLP insulated conductors.

Code Word* AWG Stranding AWG Stranding XLP PE XLP PE


6201 Alloy Neutral-Messenger
Chihuahua 6 1 6 7 65 65 85 70
Vizsla 6 7 6 7 68 68 85 70
Harrier 4 1 4 7 99 99 115 90
Whippet 4 7 4 7 103 103 115 90
Schnauzer 2 7 2 7 157 157 150 120
Heeler 1/0 9 1/0 7 250 250 205 160
AAC Neutral-Messenger
Pekingese 6 1 6 7 61 61 85 70
Collie 6 7 6 7 64 64 85 70
Dachshund 4 1 4 7 92 92 115 90
Spaniel 4 7 4 7 96 96 115 90
Doberman 2 7 2 7 147 147 150 120
Malemute 1/0 9 1/0 7 234 234 205 160
ACSR Neutral-Messenger
Setter 6 1 6 6/1 72 72 85 70
Shepherd 6 7 6 6/1 75 75 85 70
Eskimo 4 1 4 6/1 110 110 115 90
Terrier 4 7 4 6/1 115 115 115 90
Chow 2 7 2 6/1 176 176 150 120
Bull 1/0 9 1/0 6/1 280 280 205 160
Phase
Conductor
Bare Neutral
Messenger
Weight
(lbs/M-ft)
Allowed
Ampacities
*Code word for XLP insulated products are formed by adding
/XLP to the conventional code word (e.g. Chihuahua/XLP).
Information based on Southwire specs.
See referenced page in the
Hardware & Supplies section:
Suggested Prep Tool
Cable End Strippers
2x2, 4x4 - I-9

Duplex Service Drop


www.ptsupply.com
marketing@ptsupply.com
800-238-7514
5
Triplex Service Drop
Construction
Conductors are concentrically stranded, compressed 1350-H19 aluminum.
Insulated with either PE or XLP. Neutral messengers are concentrically
stranded 6201, AAC or ACSR.
Specications
Meets or exceeds the following ASTM specications:
B-230 Aluminum Wire, 1350-H19 for Electrical Purposes
B-231 Aluminum Conductors, Concentric-Lay-Stranded
B-232 Aluminum Conductors, Concentric-Lay-Stranded, Coated Steel Reinforced (ACSR)
B-399 Stranded 6201-T81 Aluminum Alloy Conductors
B-901 Compressed Round Stranded Aluminum Conductors Using Single Input Wire
Meets or exceeds all applicable requirements of ANSI/ICEA S-76-474.
Applications
Used to supply power, usually from a pole-mounted transformer, to the user's service
head where connection to the service entrance cable is made. To be used at voltages of
600V phase-to-phase or less and at conductor temperatures not to exceed 75C for PE
insulated conductors or 90C for XLP insulated conductors.

See referenced page in the


Hardware & Supplies section:
Suggested Prep Tool
Cable End Strippers
2x2, 4x4 - I-9

Code Word* AWG Stranding AWG Stranding XLP PE XLP PE


6201 Alloy Neutral-Messenger
Hippa 6 7 6 7 107 107 85 70
Barnacle 4 7 4 7 160 160 115 90
Shrimp 2 7 2 7 243 243 150 120
6201 Alloy Reduced Neutral-Messenger
Crab 4 7 6 7 143 143 115 90
AAC Neutral-Messenger
Patella 6 7 6 7 103 103 85 70
Oyster 4 7 4 7 154 154 115 90
ACSR Neutral-Messenger
Paludina 6 1 6 6/1 109 109 85 70
Whelk 4 1 4 6/1 - 164 115 90
Periwinkle 4 7 4 6/1 172 172 115 90
Neritina 1/0 7 1/0 6/1 420 420 205 160
Runcina 2/0 7 2/0 6/1 520 520 235 185
Zuzara 4/0 18 4/0 6/1 789 789 315 245
ACSR Reduced Neutral-Messenger
Strombus 4 7 6 6/1 151 151 115 90
Cockle 2 7 4 6/1 228 228 150 120
Janthina 1/0 7 2 6/1 366 366 205 160
Cerapus 4/0 18 2/0 6/1 681 681 315 245
Phase
Conductor
Bare Neutral
Messenger
Weight
(lbs/M-ft)
Allowed
Ampacity
*Code word for XLP insulated products are formed by adding
/XLP to the conventional code word (e.g. Hippa/XLP).
Other cables not listed here may be available upon request.
Information based on Southwire specs.
Triplex Service Drop
www.ptsupply.com
marketing@ptsupply.com
800-238-7514
6
Information based on Southwire specs.
*Code word for XLP insulated products
are formed by adding /XLP to the con-
ventional code word (e.g. Arabian/XLP).
Bare Neutral
Messenger
Code Word*
AWG or
kcmils Stranding
AWG or
kcmils Stranding XLP PE XLP PE
6201 Alloy Neutral-Messenger
Arabian 4 7 48.69 7 217 217 100 80
Belgian 2 7 77.47 7 328 328 135 105
Shetland 1/0 9 123.3 7 519 519 180 140
Thoroughbred 2/0 11 155.4 7 639 639 205 160
Walking 4/0 18 246.9 7 977 977 275 210
AAC Neutral-Messenger
Pinto 4 7 4 7 211 211 100 80
Mustang 2 7 2 7 318 318 135 105
Criollo 1/0 9 1/0 7 506 503 180 140
Percheron 2/0 11 2/0 7 619 619 205 160
Oldenburg 4/0 18 4/0 19 945 945 275 210
Lippizaner 336.4 19 336.4 19 1,519 1,519 370 280
ACSR Neutral-Messenger
Chola 6 7 6 6/1 153 153 75 60
Hackney 4 7 4 6/1 229 229 100 80
Palomino 2 7 2 6/1 347 347 135 105
Costena 1/0 9 1/0 6/1 549 549 180 140
Grullo 2/0 11 2/0 6/1 - 677 205 160
Suffolk 3/0 17 3/0 6/1 837 837 235 185
Appaloosa 4/0 18 4/0 6/1 1,038 1,038 275 210
Bronco 336.4 19 336.4 18.1 1,568 1,568 370 280
Weight
(lbs/M-ft)
Allowed
Ampacity
Phase
Conductor
Quadruplex Service Drop
Construction
Conductors are concentrically stranded, compressed 1350-H19 aluminum.
Insulated with either PE or XLP. Neutral messengers are concentrically
stranded 6201, AAC or ACSR. Conductors are manufactured with
ridges for phase identication (one conductor one ridge, one conductor two
ridges, one conductor plain).
Specications
Meets or exceeds the following ASTM specications:
B-230 Aluminum Wire, 1350-H19 for Electrical Purposes
B-231 Aluminum Conductors, Concentric-Lay-Stranded
B-232 Aluminum Conductors, Concentric-Lay-Stranded, Coated Steel Reinforced (ACSR)
B-399 Concentric-Lay-Stranded, 6201-T81 Aluminum Alloy Conductors

B-901 Compressed Round Stranded Aluminum Conductors Using Single Input Wire
Meets or exceeds all applicable requirements of ANSI/ICEA S-76-474.
Applications
Used to supply three-phase power, usually from a pole-mounted transformer, to the user's service head where
connection to the service entrance cable is made. To be used at voltages of 600V phase-to-phase or less and at
conductor temperatures not to exceed 75C for PE insulated conductors or 90C for XLP insulated conductors.

See referenced page in


the Hardware & Supplies
section:
Suggested Prep Tool
Cable End Strippers
2x2, 4x4 - I-9

Other cables not listed here may be available upon request.


Quadruplex Service Drop
www.ptsupply.com
marketing@ptsupply.com
800-238-7514
7
Triplex 600V
Secondary UD HI-SCORE
Construction
Conductors are stranded, compressed 1350-H16/H26 aluminum, insulated
with an XLP meeting the requirements of ANSI/ICEA S-81-570. Neutrals
are triple yellow extruded stripe. Cables with "YES" neutrals have
sequential footage markers. Conductors are durably surface printed for
identication. Two-phase conductors and one neutral conductor are cabled
to produce the triplex cable conguration. Conductors are also available
paralleled.
Specications
Meets or exceeds the following applicable ASTM specications:
B-231 Aluminum 1350 Conductors, Concentric-Lay-Stranded
B-609 Aluminum 1350 Round Wire, Annealed and Intermidiate Tempers, for Electrical Purposes
B-786 19 Wire Combination Unilay-Stranded Aluminum Conductors for Subsequent Insulation
B-901 Compressed Round Stranded Aluminum Conductors Using Single Input Wire
HI-SCORE triplex or paralleled 600V secondary UD cable insulation meets or exceeds all grade and type require-
ments of ANSI/ICEA S-81-570 and UL Standard 854 for Type USE-2.
Applications
Used for secondary distribution and underground service at 600V or less, either direct burial or in ducts.
Especially suited for applications requiring superior resistance to mechanical damage. Rated 90C continuous
operation, 130C emergency overload and short circuit 250C.

Information based on Southwire specs.


Code Word
AWG or
kcmils Stranding
AWG or
kcmils Stranding
Single Phase
Conductor
Neutral
Cond.
Complete
Cable
Weight
(lbs/M-ft)
Direct
Burial
In
Ducts
Vassar/HI-SCORE 4 7 4 7 345 345 745 192 125 90
Stephens/HI-SCORE 2 7 4 7 403 345 870 250 165 120
Ramapo/HI-SCORE 2 7 2 7 403 403 870 279 165 120
Brenau/HI-SCORE 1/0 9 2 7 512 403 1,106 387 215 160
Bergen/HI-SCORE 1/0 9 1/0 9 512 512 1,106 442 215 160
Converse/HI-SCORE 2/0 11 1 9 555 473 1,199 479 245 180
Hunter/HI-SCORE 2/0 11 2/0 11 555 555 1,199 535 245 180
Hollins/HI-SCORE 3/0 17 1/0 9 603 512 1,302 572 280 205
Sweetbriar/HI-SCORE 4/0 18 2/0 11 658 555 1,421 709 315 240
Monmouth/HI-SCORE 4/0 18 4/0 18 658 658 1,421 797 315 240
Pratt/HI-SCORE 250 26 3/0 17 732 603 1,581 856 345 265
Wesleyan/HI-SCORE 350 37 4/0 18 831 658 1,795 1,121 415 320
Newark/HI-SCORE 350 37 350 37 831 831 1,795 1,282 415 320
Rider/HI-SCORE 500 37 350 37 980 831 2,117 1,602 495 395
Faireld/HI-SCORE 750 61 500 37 1,188 980 2,566 2,317 620 495
Phase
Conductor Neutral Diameter (mils)
Allowed
Ampacity
See referenced page in the Hardware & Supplies section:
Suggested Prep Tool
Cable End Strippers 2x2, 4x4 - I-9
Triplex 600V
www.ptsupply.com
marketing@ptsupply.com
800-238-7514
8
Information based on Southwire specs.
15kV Primary UD Cable
Construction
The phase conductor is concentrically stranded, compressed soft copper or
1350-H16/26 aluminum alloy. The cable is composed of the conductor, cov-
ered by a semi-conducting XLP strand shield, a tree-retardant XLP primary
insulation and a semi-conducting XLP insulation shield. Conductors are
available with either 100% or 133% insulation levels. A concentric neutral of bare copper wires is applied over the
insulation shield.
Size
(AWG or
kcmils) Stranding
No. of
Wires AWG
Bare Phase
Cond.
Over
Insul.
Over Insul.
Shield
Comp.
Cable
Comp.
Cable Weight
(lbs/M-ft)
Direct
Burial
In
Ducts
Aluminum Conductor, .175" insulation, 100% insulation level Call for specs on cable with copper conductor
2 7 10 14* 283 678 758 886 356 168* 119*
1/0 19 16 14* 362 758 838 966 496 218* 155*
2/0 19 20 14* 406 800 880 1,008 589 248* 177*
3/0 19 25 14* 456 850 930 1,058 703 284* 201*
4/0 19 20 12* 512 908 988 1,149 852 324* 230*
250 37 16 10* 558 963 1,043 1,246 1,020 360* 257*
350 37 18 14** 660 1,063 1,163 1,291 866 389** 319**
500 37 25 14** 789 1,193 1,293 1,421 1,142 468** 384**
750 61 24 12** 968 1,383 1,483 1,644 1,613 569** 468**
1,000 61 20 10 1,117 1,530 1,630 1,834 2,055 642 542
Aluminum Conductor, .22" insulation, 133% insulation level Call for specs on cable with copper conductor
2 7 10 14* 283 770 850 978 403 168 119*
1/0 19 16 14* 362 850 930 1,058 547 218 155*
2/0 19 20 14* 406 893 973 1,101 642 248 177*
3/0 19 25 14* 456 943 1,023 1,151 760 284 201*
4/0 19 20 12* 512 1,000 1,080 1,242 912 324 230*
250 37 16 10* 558 1,055 1,155 1,359 1,101 360 257*
350 37 18 14** 660 1,155 1,255 1,383 936 389 319**
500 37 25 14** 789 1,285 1,385 1,513 1,219 468 384**
750 61 24 12** 968 1,475 1,575 1,737 1,702 569 468**
1,000 61 20 10 1,117 1,623 1,753 1,956 2,193 642 542
Allowed
Ampacity Diameter (mils)
*Full neutral construction (ampacities assume - single phase circuit, one cable).
**1/3 neutral cable (ampacities assume - three-phase circuit, three cables triplexed, multi-point grounding per ICEA methods).
Specications
Meets or exceeds the following applicable ASTM
specications:
B-3 Soft Annealed Copper Wire
B-8 Concentric-Lay-Stranded Copper Conductors,
Hard, Medium-Hard or Soft
B-230 Aluminum, 1350-H19 Wire for Electrical
Purposes

B-231 Aluminum 1350 Conductors,


Concentric-Lay-Stranded
B-609 Aluminum 1350 Round Wire, Annealed and
Intermediate Tempers, for Electrical Purposes
Manufactured to the latest edition of the following
specications and, in case of specication conicts,
in the order listed: ANSI/ICEA S-94-649, AEIC CS-8,
RUS U-1.

Applications
Predominantly used for primary underground distribution; suitable for use in wet or dry locations, direct burial,
underground duct and where exposed to sunlight. To be used at 15kV or less and at conductor temperatures not
to exceed 90C for normal operation.
Phase
Conductor
Neutral
15kV HI-DRI UD
www.ptsupply.com
marketing@ptsupply.com
800-238-7514
9
25kV Primary UD Cable
Construction
The phase conductor is concentrically stranded, compressed soft copper
or 1350-H16/26 aluminum alloy. The cable is composed of the conductor,
covered by a semi-conducting XLP strand shield, a tree-retardant XLP pri-
mary insulation and a semi-conducting XLP insulation shield. Conductors
are available with either 100% or 133% insulation levels. A concentric
neutral of bare copper wires is applied over the insulation shield.
Specications
Meets or exceeds the following applicable ASTM specications:
B-3 Soft Annealed Copper Wire
B-8 Concentric-Lay-Stranded Copper Conductors, Hard, Medium-Hard or Soft
B-230 Aluminum, 1350-H19 Wire for Electrical Purposes
B-231 Aluminum 1350 Conductors, Concentric-Lay-Stranded
B-609 Aluminum 1350 Round Wire, Annealed and Intermediate Tempers, for Electrical Purposes
Manufactured to the latest edition of the following specications and, in case of specication conicts, in the
order listed: ANSI/ICEA S-94-649, AEIC CS-8, RUS U-1
Applications
Predominantly used for primary underground distribution; suitable for use in wet or dry locations, direct burial,
underground duct and where exposed to sunlight. To be used at 25kV or less and at conductor temperatures not
to exceed 90C for normal operation.

Information based on Southwire specs.


Size
(AWG or kcmils) Stranding
No. of
Wires AWG
Bare Phase
Cond.
Over
Insul.
Over Insul.
Shield
Comp.
Cable
Comp. Cable Weight
(lbs/M-ft)
Direct
Burial
In
Ducts
Aluminum Conductor, .26" insulation, 100% insulation level
1 19 13 14* 322 880 960 1,088 513 189* 134*
1/0 19 16 14* 362 920 1,000 1,128 590 214* 152*
2/0 19 20 14* 406 965 1,045 1,173 688 243* 173*
3/0 19 25 14* 456 1,015 1,095 1,223 808 278* 197*
4/0 19 20 12* 512 1,070 1,170 1,332 979 318* 225*
250 37 16 10* 558 1,125 1,225 1,429 1,153 353* 252*
350 37 18 14** 660 1,228 1,328 1,456 994 387** 320**
500 37 25 14** 789 1,358 1,458 1,586 1,284 466** 386**
750 61 24 12** 968 1,545 1,645 1,807 1,773 567** 475**
Copper Conduct, .26" insulation, 100% insulation level
1 19 20 14* 322 880 960 1,686 801 235* 168*
1/0 19 25 14* 362 920 1,000 1,128 937 268* 190*
2/0 19 20 12* 405 965 1,045 1,207 1,130 307* 220*
3/0 19 25 12* 456 1,015 1,095 1,257 1,363 351* 250*
4/0 19 20 10* 512 1,070 1,170 1,374 1,682 402* 287*
250 37 24 10* 558 1,125 1,225 1,429 1,959 445* 317*
350 37 18 12** 661 1,230 1,330 1,492 1,890 487** 403**
500 37 26 12** 790 1,358 1,458 1,619 2,575 575** 475**
Phase
Conductor Neutral
Allowed
Ampacity Diameter (mils)
*Full neutral construction (ampacities assume - single phase circuit, one cable).
**1/3 neutral cable (ampacities assume - three-phase circuit, three cables triplexed, multi-point grounding per ICEA methods).
25kV HI-DRI UD
www.ptsupply.com
marketing@ptsupply.com
800-238-7514
10
Bare Copper Conductors
Construction
Bare copper, solid or stranded. Available in tempers hard, medium-hard,
or soft. Stranded conductors are concentrically stranded in hard and
medium-hard tempers and are Combination Unilay stranded in the
soft-drawn temper.
Specications
Meets or exceeds the following applicable ASTM specications:
B-1 Hard-Drawn Copper Wire
B-2 Medium-Hard Copper Wire
B-3 Soft or Annealed Copper Wire
B-787 19 Wire Combination Unilay-Stranded Soft Copper Wire
B-8 Concentric-Lay-Stranded Hard, Medium-Hard or Soft Copper Conductor
Applications
Solid and stranded (classes AA and A) bare copper are suitable for overhead transmission and distribution
applications. Stranded conductor of greater exibility (classes B and C) are suitable for uninsulated hook up,
jumpers and grounds in electrical construction. Soft drawn copper is unilay construction.

AWG
Weight
(lbs/M-ft)
Diameter
(mils) Hard Drawn
Medium
Hard Drawn
Soft Drawn
(Annealed)
Allowable
Ampacity
Solid
14 12.4 64.1 2.626 2.613 2.525 -
12 19.8 80.8 1.652 1.643 1.588 -
10 31.4 101.9 1.039 1.033 .999 -
8 50 128.5 .653 .650 .628 95
6 79.4 162 .411 .409 .395 125
4 126.3 204.3 .258 .257 .249 170
2 200.9 257.6 .163 .162 .156 225
DC Resistance
(Ohms/M-ft @ 20C)
Size
(AWG or
kcmils) Stranding
Stranding
Class
Weight
(lbs/M-ft)
Indv.
Wires
Complete
Cables Hard Drawn
Medium
Hard Drawn
Soft Drawn
(Annealed)
Allowable
Ampacity
Stranded
8 7 B 51 49 146 .66630 .66290 .64080 95
6 7 B 81 61 184 .41910 .41690 .40300 130
4 7 A, B 128.9 77 232 .26360 .26220 .25340 170
2 7 A, B 204.9 97 292 .16600 .16500 .15780 230
1/0 7 A, AA 326.1 123 368 .10420 .10370 .10020 310
2/0 7 A, AA 410.9 138 414 .08627 .08224 .07949 355
3/0 7 A, AA 518.1 155 464 .06556 .06522 .06304 410
4/0 7 A, AA 653.3 174 522 .05199 .05172 .04999 480
4/0 19 B 653.3 106 528 .05199 .05172 .04999 480
250 19 A 771.9 115 574 .04400 .04378 .04231 530
350 19 A 1080.6 136 679 .03143 .03127 .03022 650
500 37 A, B 1543.8 116 814 .02200 .02189 .02116 810
DC Resistance
(Ohms/M-ft @ 20C) Diameter (in)
Information based on Southwire specs.
Other cables not listed here
may be available upon request.
Other cables not listed here may be available upon request.
Bare Copper
www.ptsupply.com
marketing@ptsupply.com
800-238-7514
11
Covered Line Wire
Copper Conductor
Construction
Conductors are hard or medium-hard concentrically stranded copper.
Covered with black PE or XLP.
Specications
Meets or exceeds the following ASTM specications:
B-1 Hard-Drawn Copper Wire
B-3 Medium Hard-Drawn Copper Wire
B-8 Concentric-Lay-Stranded Copper Conductors, Hard, Medium-Hard or Soft
Meets all applicable requirements of ANSI/ICEA S-70-547.
Applications
Used primarily for, but not limited to, overhead secondary distribution lines.
Installed on insulators, otherwise treated as a bare conductor.

Information based on Southwire specs.


Size (AWG
or kcmils) Stranding
O.D.
Covered (mils)
Weight
(lbs/M-ft)
DC Resistance
(ohms/M-ft @ 20C)
Allowable
Ampacity
Solid
6 1 222 86.7 .411 130
4 1 264 135.3 .258 170
3 1 319 174.9 .205 195
2 1 348 218.1 .163 225
Stranded
6 7 238 90.3 .503 130
4 7 285 140.8 .316 175
2 7 373 227.1 .199 230
1/0 7 477 363.3 .125 305
2/0 7 522 453.3 .0992 350
3/0 7 570 565.6 .0788 405
4/0 7 626 707.6 .0625 465
250 19 677 825.4 .0530 520
300 19 729 984.6 .0442 580
350 19 779 1,144.5 .0380 640
500 37 950 1,637.2 .0278 785
750 61 1,128 2,422.8 .0182 995
1,000 61 1,307 3,234 .0140 1,180
See referenced page in the
Hardware & Supplies section:
Suggested Prep Tool
Cable End Strippers
2x2, 4x4 - I-9

Covered Line Wire, Copper


www.ptsupply.com
marketing@ptsupply.com
800-238-7514
12
See referenced page in the
Hardware & Supplies section:
Suggested Prep Tool
Cable End Strippers
2x2, 4x4 - I-9

Information based on Southwire specs.


Transformer Riser Wire
Construction
Conductors are solid or stranded soft copper. Stranded conductors are
concentrically stranded, compressed. The covering is high molecular weight
PE, black.
Specications
Meets or exceeds the following ASTM specications:
B-3 Soft or Annealed Copper Wire
B-8 Concentric-Lay-Stranded Copper Conductors, Hard, Medium-Hard or Soft

AWG Stranding Bare Covered


Weight
(lbs/M-ft)
8 Solid 128.5 348.5 83
6 Solid 162 382 117
4 Solid 204.3 424.3 170
Diameter (mils)
Applications
Used as uninsulated transformer risers at voltages up to and includ-
ing 13.2kV. Although not treated as an insulation, the covering on
transformer riser wire does reduce faults due to atmospheric conditions,
shorts caused by excessive vibrations and faulting caused by objects
crossing the leads.
Transformer Riser Wire
www.ptsupply.com
marketing@ptsupply.com
800-238-7514
13
Copper
Conductors
Conductor
Shield
XLP Insulation
Insulation
Shield
Copper Tape
Shield
PVC Jacket
5kV, 5kVU Type MV-90
XLP, TS, PVC
Construction
Single conductor XLP insulated, shielded, thermoplastic jacket power cable.
Proven XLP insulation, 90C continuous conductor operating temperature, 100%
copper tape shield coverage, fast stripping thermosetting insulation shield and
it is triple extruded. Cable is sunlight resistant, suitable for direct burial. Also
available listed for cable tray use in sizes 250 kcmils and larger upon request.
Specications
Manufactured and tested in accordance with the latest revisions of the following
standards and specication:
UL 1072 - Medium Voltage Power Cables
ICEA S-93-639 (NEMA WC 74) - 5-46 kV Shielded Power Cable for Use in
the Transmission & Distribution of Electric Energy
Certied qualication tests were performed in accordance with the requirements of AEIC CS-8. Cable has fully
met the qualication testing requirements of AEIC CS-8.
Applications
For use in aerial, direct burial, conduit, and underground duct installations as permitted by the NEC

. These
cables are capable of operating continuously at a conductor temperature not in excess of 90C for normal opera-
tion, 130C for emergency overload conditions and 250C for short circuit conditions and are rated at 5kV, 100%
(grounded system) and 133% insulation level (ungrounded system).

See referenced page in the


Hardware & Supplies section:
Suggested Prep Tool
WS 5 End Stripper - I-9
Information based on Southwire specs.
Size (AWG
or kcmils)
Conductor
Diameter (in)
Mininum
Point Jacket
Thickness (in)
Approx. Overall
Diameter (in)
Approx.
Net Weight
(lbs/M-ft) Duct
Conduit
in Air
4 .225 .055 .654 309 110 97
2 .283 .055 .709 406 145 130
1 .322 .055 .749 474 170 155
1/0 .362 .055 .789 557 195 180
2/0 .405 .070 .860 681 220 205
3/0 .456 .070 .910 809 250 240
4/0 .512 .070 .965 968 290 280
250 .558 .070 1.020 1,108 320 315
350 .661 .070 1.125 1,462 385 385
500 .790 .070 1.250 1,977 470 475
750 .968 .070 1.437 2,826 585 600
1,000 1.117 .070 1.582 3,654 670 690
Allowable
Ampacity
Type MV-90
www.ptsupply.com
marketing@ptsupply.com
800-238-7514
14
Copper
Conductors
Conductor
Shield
XLP Insulation
Insulation
Shield
Copper Tape
Shield
PVC Jacket
15kV Type MV-90
XLP, TS, PVC
Construction
Single conductor XLP insulated, shielded, thermoplastic jacket power cable.
Proven XLP insulation, 90C continuous conductor operating temperature, 100%
copper tape shield coverage, fast stripping thermosetting insulation shield and
it is triple extruded. Cable is sunlight resistant, suitable for direct burial. Also
available listed for cable tray use in sizes 250 kcmils and larger upon request.
Specications
Manufactured and tested in accordance with the latest revisions of the following
standards and specication:
UL 1072 - Medium Voltage Power Cables
ICEA S-93-639 (NEMA WC 74) - 5-46 kV Shielded Power Cable for Use in
the Transmission & Distribution of Electric Energy
Certied qualication tests were performed in accordance with the requirements of AEIC CS-8. Cable has fully
met the qualication testing requirements of AEIC CS-8.
Applications
For use in aerial, direct burial, conduit and underground duct installations as permitted by the NEC

. These
cables are capable of operating continuously at a conductor temperature not in excess of 90C for normal opera-
tion, 130C for emergency overload conditions and 250C for short circuit conditions and are rated at 15kV, 100%
insulation level (grounded system).

See referenced page in the


Hardware & Supplies section:
Suggested Prep Tool
WS 5 End Stripper - I-9
Information based on Southwire specs.
Size (AWG
or kcmils)
Conductor
Diameter (in)
Mininum
Point Jacket
Thickness (in)
Approx. Overall
Diameter (in)
Approx.
Net Weight
(lbs/M-ft) Duct
Conduit
in Air
2 .283 .07 .905 531 155 150
1 .322 .07 .945 603 175 170
1/0 .362 .07 .985 692 200 195
2/0 .405 .07 1.025 797 230 225
3/0 .456 .07 1.075 930 260 260
4/0 .512 .07 1.130 1,095 295 295
250 .558 .07 1.185 1,241 325 330
350 .661 .07 1.290 1,605 390 395
500 .790 .07 1.415 2,132 65 480
750 .968 .07 1.602 3,002 565 585
1,000 1.117 .10 1.810 3,948 640 675
Allowable
Ampacity (amps)
Type MV-90
www.ptsupply.com
marketing@ptsupply.com
800-238-7514
15
Copper
Conductors
Conductor
Shield
XLP Insulation
Insulation
Shield
Copper Wire
Shield
PVC Jacket
Binder Tape
5kV, 5kVU Type MV-90
XLP, WS, PVC
Construction
Single conductor XLP insulated, shielded, thermoplastic jacket power cable. Proven
XLP insulation, 90C continuous conductor operating temperature, fast stripping
thermosetting insulation shield and it is triple extruded. Cable is sunlight resistant,
suitable for direct burial.
Specications
Manufactured and tested in accordance with the latest revisions of the following
standards and specication:
UL 1072 - Medium Voltage Power Cables
ICEA S-93-639 (NEMA WC 74) - 5-46kV Shielded Power Cable for Use in the
Transmission & Distribution of Electric Energy
Certied qualication tests were performed in accordance with the requirements
of AEIC CS-8. Cable has fully met the qualication testing requirements of AEIC CS-8.
Applications
For use in aerial, direct burial, conduit and underground duct installations as permitted by the NEC

. These
cables are capable of operating continuously at a conductor temperature not in excess of 90C for normal opera-
tion, 130C for emergency overload conditions and 250C for short circuit conditions and are rated at 5kV, 100%
(grounded system) and 133% insulation level (ungrounded system).

See referenced page in the


Hardware & Supplies section:
Suggested Prep Tool
WS 5 End Stripper - I-9
Information based on Southwire specs.
Size (AWG
or kcmils)
Conductor
Diameter (in)
Mininum
Point Jacket
Thickness (in)
Approx. Overall
Diameter (in)
Approx.
Net Weight
(lbs/M-ft) Duct
Conduit
in Air
1 .322 .055 .777 442 170 155
1/0 .362 .07 .848 546 195 180
2/0 .405 .07 .888 646 220 205
3/0 .456 .07 .938 772 250 240
4/0 .512 .07 .993 926 290 280
250 .558 .07 1.048 1,065 320 315
350 .661 .07 1.153 1,412 385 385
500 .790 .07 1.278 1,920 470 475
750 .968 .07 1.465 2,759 585 600
1,000 1.117 .07 1.610 3,579 670 690
Allowable
Ampacity (amps)
Type MV-90
www.ptsupply.com
marketing@ptsupply.com
800-238-7514
16
Copper
Conductors
Conductor
Shield
XLP Insulation
Insulation
Shield
Copper Wire
Shield
PVC Jacket
Binder Tape
15kV Type MV-90
XLP, WS, PVC
Construction
Single conductor XLP insulated, shielded, thermoplastic jacket power cable. Proven
XLP insulation, 90C continuous conductor operating temperature, fast-stripping
thermosetting insulation shield and it is triple extruded. Cable is sunlight resistant,
suitable for direct burial.
Specications
Manufactured and tested in accordance with the latest revisions of the following
standards and specication:
UL 1072 - Medium Voltage Power Cables
ICEA S-93-639 (NEMA WC 74) - 5-46 kV Shielded Power Cable for Use in
Transmission & Distribution of Electric Energy
Certied qualication tests were performed in accordance with the requirements
of AEIC CS-8. Cable has fully met the qualication testing requirements of AEIC CS-8.
Applications
For use in aerial, direct burial, conduit and underground duct installations as permitted by the NEC

. These
cables are capable of operating continuously at a conductor temperature not in excess of 90C for normal opera-
tion, 130C for emergency overload conditions and 250C for short circuit conditions and are rated at 15kV, 100%
insulation level (grounded system).

See referenced page in the


Hardware & Supplies section:
Suggested Prep Tool
WS 5 End Stripper - I-9
Information based on Southwire specs.
Size (AWG
or kcmils)
Conductor
Diameter (in)
Minimum
Point Jacket
Thickness (in)
Approx. Overall
Diameter (in)
Approx.
Net Weight
(lbs/M-ft) Duct
Conduit
in Air
2 .283 .07 .933 494 155 150
1 .322 .07 .973 563 175 170
1/0 .362 .07 1.013 651 200 195
2/0 .405 .07 1.053 753 230 225
3/0 .456 .07 1.103 884 260 260
4/0 .512 .07 1.170 1,119 295 295
250 .558 .07 1.225 1,266 325 330
350 .661 .07 1.330 1,633 390 395
500 .790 .07 1.455 2,162 465 480
750 .968 .07 1.642 3,034 565 585
1,000 1.117 .10 1.850 3,985 640 675
Allowable
Ampacity
Type MV-90
www.ptsupply.com
marketing@ptsupply.com
800-238-7514
17
2.4kV Type MV-90
EPR Heavy Wall, N/S
Construction
Single conductor EPR insulated, PVC jacket power cable. Flexible, easy bending
insulation, easy cable preparation, 90C continuous operating temperature,
resistance to moisture. Flame-retardant. Also available listed for cable tray use in
sizes 1/0 and larger.
Specications
Manufactured and tested in accordance with the latest revisions of the following
standards and specication:
UL 1072 - Medium Voltage Power Cables
ICEA S-96-659 (NEMA WC 71) - Unshielded Cables Rated 2001-5000 Volts for
Use in the Distribution of Electric Energy
Applications
For use primarily in raceways in industrial applications as specied by the NEC

.
These cables are capable of operating continuously at a conductor temperature
not in excess of 90C for normal operation, 130C for emergency overload condi-
tions and 250C for short circuit conditions and are rated at 2.4kV in wet or dry
locations.

See referenced page in the


Hardware & Supplies section:
Suggested Prep Tool
WS 5 End Stripper - I-9
Copper
Conductors
Conductor
Shield
EPR Insulation
PVC Jacket
Information based on Southwire specs.
Size (AWG
or kcmils)
Conductor
Diameter (in)
Jacket
Thickness (in)
Approx. Overall
Diameter (in)
Approx.
Net Weight
(lbs/M-ft) Duct
Conduit
in Air
6 .178 .080 .645 253 85 75
4 .225 .080 .692 321 110 97
2 .283 .080 .750 422 145 130
1 .322 .080 .789 489 170 155
1/0 .362 .080 .829 574 195 180
2/0 .405 .080 .871 676 220 205
3/0 .456 .095 .954 834 250 240
4/0 .512 .095 1.010 995 290 280
250 .558 .110 1.127 1,199 320 315
350 .661 .110 1.229 1,560 385 385
500 .790 .110 1.357 2,088 470 475
750 .968 .125 1.608 3,044 585 600
1,000 1.117 .125 1.756 3,897 670 690
Allowable
Ampacity
Type MV-90
www.ptsupply.com
marketing@ptsupply.com
800-238-7514
18
5kVU, 8kV Type MV-105
TS, PVC, CT Rated
Construction
Single conductor EPR insulated, shielded, thermoplastic jacketed power
cable. Flexible, easy bending insulation, easy cable preparation, fast strip-
ping thermosetting insulation shield, 105C continuous operating tem-
perature, 100% shield coverage and it is triple extruded. Cable is sunlight
resistant, suitable for direct burial and listed for cable tray use in sizes 1/0
and larger.
Specications
Manufactured and tested in accordance with the latest revisions of the
following standards and specications:
UL 1072 - Medium Voltage Power Cables
ICEA S-93-639 (NEMA WC 74) - 5-46 kV Shielded Power Cable for
Use in the Transmission & Distribution of Electric Energy

ICEA S-97-682 (when requested) 5-46 kV Standard for Utility Shielded Power Cable
UL 1685 - (AWG 1/0 and larger) -UL Flame Exposure Test
IEEE 1202 - Flame Test (70,000 Btu/hr Vertical Tray Test)
Certied qualication tests were performed in accordance with the requirements of ICEA CS-6. Cable has fully
met the qualication testing requirements of ICEA CS-6.
Applications
For use in aerial, direct burial, cable trays, conduit and underground duct installations as permitted by the
NEC

. These cables are capable of operating continuously at a conductor temperature not in excess of 105C for
normal operation, 140C for emergency overload conditions and 250C for short circuit conditions and are rated
at 5kV, 133% (ungrounded system) and 8kV 100% insulation level (grounded system).

See referenced page in the


Hardware & Supplies section:
Suggested Prep Tool
WS 5 End Stripper - I-9
Conductor
Shield
EPR
Insulation
Insulation
Shield
Copper Tape
Shield
PVC Jacket
Copper
Conductors
Information based on Southwire specs.
Size (AWG
or kcmils)
Conductor
Diameter (in)
Min. Point Jacket
Thickness (in)
Approx. Overall
Diameter (in)
Approx.
Net Weight
(lbs/M-ft) Duct
Conduit
in Air
6 .178 .055 .656 282 92 84
4 .225 .055 .701 351 120 110
1 .322 .055 .799 525 180 175
1/0 .362 .070 .870 641 210 200
2/0 .405 .070 .910 745 235 225
3/0 .456 .070 .960 877 270 270
4/0 .512 .070 1.015 1,036 310 305
250 .558 .070 1.070 1,181 345 355
350 .661 .070 1.175 1,543 415 430
500 .790 .070 1.300 2,067 505 530
750 .968 .070 1.487 2,932 630 665
1,000 1.117 .070 1.632 3,771 720 770
Allowable
Ampacity
Type MV-105
www.ptsupply.com
marketing@ptsupply.com
800-238-7514
19
5kV, 5kVU Type MV-105
TS, GW, PVC, CT Rated
Construction
Three conductor EPR insulated, shielded, thermoplastic jacketed power
cables with grounding conductor. Alternate constructions available.
Specications
Manufactured and tested in accordance with the latest revisions of the
following standards and specications:
UL 1072 - Medium Voltage Power Cables
ICEA S-93-639 (NEMA WC 74) - 5-46 kV Shielded Power Cable for use
in the Transmission & Distribution of Electric Energy
ICEA S-97-682 (when requested) 5-46 kV Standard for Utility Shielded
Power Cable
UL 1685 - UL Flame Exposure Test
IEEE 1202 (Sizes 4 AWG and larger) - Flame Test (70,000 Btu/hr
Vertical Tray Test)
Certied qualication tests were performed in accordance with the
requirements of AEIC CS-8. Cable has fully met the qualication testing
requirements of AEIC CS-8.
Applications
For use in aerial installations, direct buried, cable trays, troughs
or raceway. These cables are capable of operating continuously at a
maximum conductor temperature of 105C for normal operation, 140C
for emergency overload conditions and 250C for short circuit conditions
and are rated at 5kV, 100% (grounded system) and 133% insulation levels
(ungrounded system).

See referenced page in the


Hardware & Supplies section:
Suggested Prep Tool
WS 5 End Stripper - I-9
PVC Jacket
Copper
Conductors
Conductor
Shield
EPR Insulation
Insulation Shield
Copper Tape Shield
Core Binder Tape
Fillers
Ground Conductor
Information based on Southwire specs.
Size (AWG
or kcmils)
Conductor
Diameter (in)
Ground
Conductor
(AWG)
Min. Point Jacket
Thickness (in)
Approx. Overall
Diameter (in)
Approx.
Net Weight
(lbs/M-ft) Duct
Conduit
in Air
2 .283 6 .070 1.443 1,447 145 135
1 .322 4 .070 1.529 1,730 165 155
1/0 .362 4 .070 1.616 1,987 190 185
2/0 .405 4 .100 1.765 2,421 220 210
3/0 .456 3 .100 1.873 2,869 250 245
4/0 .512 3 .100 1.992 3,384 285 285
250 .558 3 .100 2.123 3,868 315 315
350 .661 2 .100 2.349 5,056 380 390
500 .790 1 .100 2.619 6,770 460 475
750 .968 1/0 .125 3.077 9,722 570 585
Allowable
Ampacity (amps)
Type MV-105
www.ptsupply.com
marketing@ptsupply.com
800-238-7514
20
Type TC Power Cable
600V THHN/PVC, GW
Construction
Available in sizes 8 AWG through 750 kcmils and is manufactured using Type
THHN or THWN conductors. Individual conductors are bare annealed copper
covered with a PVC insulation over which a nylon (polyamide) or UL listed equal
jacket is applied. The overall jacket consists of a ame- retardant, moisture- and
sunlight-resistant PVC jacket. Non-halogen jacket available upon request.
Specications
Meets or exceeds the applicable requirements of the following standards and
specications:
See referenced page in the
Hardware & Supplies section:
Suggested Prep Tool
Cable End Strippers
2x2, 4x4 - I-9

ASTM - (All applicable standards)


UL 1277 - Electrical Power and Control Tray Cables
UL 1581 - Electrical Wires, Cables and Flexible Cords
ICEA S-58-679 - Control Cable Conductor Identication. (Method 4 - single color compounds with surface
printing of numbers)
UL 1685 - UL Flame Exposure Test (70,000 Btu/hr)
ICEA T-29-520 - Vertical Cable Tray Flame Test (210,000 Btu/hr)
IEEE 1202 - Flame Testing of Cables for Use in Cable Tray in Industrial and Commercial Occupancies
(70,000 Bth/hr)
Applications
Used to supply power to motors or for connection to other power devices in industrial settings. Primary installa-
tions include cable trays, raceways and outdoor locations where supported by a messenger wire. Type TC Power
Cable is listed for direct burial and for use in Class 1, Division 2 hazardous locations and Class 1 control circuits.
This cable may be used at temperatures not to exceed 75C in wet locations and 90C in dry locations. 6 and 8
AWG constructions with insulated grounds (standard) and 4 AWG and larger with bare or insulated ground are
UL Listed for exposed runs (ER) per NEC

336.10.

Copper
Conductors
PVC Insulation
with Nylon
Jacket
Ground
Conductor
Ground
Conductor
PVC Jacket
Information based on Southwire specs.
Size (AWG
or kcmils) Stranding
Ground
Conductor
(AWG)
Average Overall
Diameter (in)
Approx. Weight
(lbs/M-ft) 75C 90C
8 7 10 .625 295 50 55
6 7 8 .710 433 65 75
4 7 8 .795 605 85 95
2 7 6 .958 940 115 130
1 19 6 1.100 1,193 130 150
1/0 19 6 1.184 1,442 150 170
2/0 19 6 1.281 1,730 175 195
3/0 19 4 1.391 2,159 200 225
4/0 19 4 1.508 2,613 230 260
250 37 4 1.659 3,065 255 290
350 37 3 1.942 4,270 310 350
500 37 2 2.220 5,899 380 430
750 61 1 2.652 8,600 475 535
Ampacity
Type TC
www.ptsupply.com
marketing@ptsupply.com
800-238-7514
21
See referenced page in the
Hardware & Supplies section:
Suggested Prep Tool
Cable End Strippers
2x2, 4x4 - I-9

Type TC Composite Cable


600V, TFFN or VW-1 THHN/THWN
Construction
Multiconductor cables have TFFN or VW-1 THHN/THWN (PVC/Nylon)
conductors with an overall gas/vapor-tight PVC jacket. Three power conductors
and four or six control conductors.
Specications
Conforms to the following standards and specications:
NEC

Article 392 Cable Trays and 336 Power and Control Cable Type TC
Standard 1277 of Underwriters Laboratories, Inc.
ICEA T-30-520 - Flame Test
ICEA T-29-520 - Vertical Cable Tray Flame Test (210,000 Btu/hr)
IEEE-383 - 70,000 BTU Cable Tray Propagation Test
IEEE 1202 - 70,000 BTU Flame Tests
CSA FT4
UL E60749
Applications
For supplying power and control signals to motors or providing connection to
other power devices utilizing remote control circuits. Specically approved
for direct burial, wet or dry locations and outdoors in cable trays where
a sunlight-resistant rating is required. UL Listed and OSHA acceptable.
Recognized for use in Class 1 or 2, Division 2 hazardous locations and for
installation in trays, wireways, troughs, channels, ducts and conduit.

Stranded Bare
Copper
High Dielectric
Strength PVC
Insulation
Conductor Jacket
Tape Binder
(optional)
PVC Jacket
Note: Stranding is
Class B, 2-14 AWG
Information based on AIW specs.
No. of
Conductors AWG
No. of
Conductors AWG
Overall Jacket
Thickness (mils)
Approx.
O.D. (in)
Approx. Weight
(lbs/M-ft)
3 12 4 14 45 .470 192
3 10 4 14 45 .515 265
3 8 4 14 60 .650 356
3 6 4 14 60 .715 458
3 4 4 14 80 .880 702
3 2 4 14 80 1.005 982
Power Conductors Control Conductors
Type TC
www.ptsupply.com
marketing@ptsupply.com
800-238-7514
22
Copper
Conductors
PVC Insulation
with Nylon
Jacket
Ground
Conductor
Filler
PVC Jacket
Binder String
Type TC Power Cable
600V, XHHW/PVC, GW
Construction
Available in sizes 8 AWG through 750 kcmils and is manufactured using Type
XHHW-2 conductors. Individual conductors are bare annealed copper covered with
XLP insulation. The overall jacket consists of a ame-retardant, moisture- and
sunlight-resistant PVC jacket. Non-halogen jacket available upon request.
Specications
Meets or exceeds the applicable requirements of the following standards and
specications:
ASTM - (All applicable standards)
UL 44
UL 1277 - Electrical Power and Control Tray Cables. UL 1581 - Electrical

Wires, Cables and Flexible Cords


ICEA S-58-679 - Control Cable Conductor Identication. (Method 4 - single color (black) compounds with
surface printing of numbers)
UL 1685 - Flame Exposure Test (70,000 Btu/hr)
ICEA T-29-520 - Vertical Cable Tray Flame Test (210,000 Btu/hr)
IEEE 1202 - Flame Testing of Cables for Use in Cable Tray in Industrial and Commercial Occupancies
(70,000 Bth/hr)
Meets and exceeds all construction requirements of ICEA S-95-658 (NEMA WC 70) - Unshielded 0 - 2 kV Cables,
with testing frequencies based on UL requirements.

Applications
For supplying power to motors or for connection to other power devices in industrial settings. Primary installa-
tions include cable trays, raceways and outdoor locations where supported by a messenger wire. Type TC Power
Cable is listed for direct burial or in underground ducts and for use in Class 1, Division 2 hazardous locations
and Class 1 control circuits. This cable may be used in wet and dry locations at temperatures not to exceed 90C.
6 and 8 AWG constructions with insulated grounds (standard) and 4 AWG and larger with bare or insulated
ground are UL Listed for exposed runs (ER) per NEC

336.10C.

Size (AWG
or kcmils) Stranding
Ground
Conductor
(AWG)
Average Overall
Diameter (in)
Approx. Weight
(lbs/M-ft)
Ampacity
90C
8 7 10 .681 330 55
6 7 8 .766 468 75
4 7 8 .797 606 95
2 7 6 .960 954 130
1 19 6 1.100 1,173 150
1/0 19 6 1.186 1,421 170
2/0 19 6 1.279 1,704 195
3/0 19 4 1.385 2,135 225
4/0 19 4 1.506 2,580 260
250 37 4 1.653 3,021 290
300 37 3 1.827 3,684 320
350 37 3 1.935 4,219 350
400 37 3 2.032 4,747 380
500 37 2 2.214 5,838 430
750 61 1 2.663 8,543 535
See referenced page in the
Hardware & Supplies section:
Suggested Prep Tool
Cable End Strippers
2x2, 4x4 - I-9

Information based on Southwire specs.


Type TC
www.ptsupply.com
marketing@ptsupply.com
800-238-7514
23
RHH/RHW Power Cable
600V CT Rated
Construction
RHH or RHW-2 or USE-2 copper conductors are annealed (soft) copper.
Insulation is an abrasion-, moisture-, heat-resistant and ame-retardant
XLP. This product is sunlight resistant and rated for cable tray use.
Specications
Meets or exceeds the applicable requirements of the following standards
and specications:
UL 44 - Thermoset-Insulated Wires and Cables
UL 1581 - UL Flame Exposure Test (VW-1)
UL 854 - Service Entrance Cables
UL 1685 - UL Flame Exposure Test
ICEA S-95-658 (NEMA WC70) Unshielded Power Cables 2000 Volts or
Less for the Distribution of Electrical Energy
IEEE 1202 Flame Test (4/0 and Larger)
Type RHH or RHW-2 or USE-2 meets and exceeds all construction
requirements of ICEA S-95-658 (NEMA WC 70) - Unshielded 0 - 2kV
cables, with testing frequencies based on UL requirements.

Applications
For use in conduit or cable tray as specied in the NEC

. When used as
Type USE-2 conductor is suitable for use as underground service entrance
cable for direct burial at conductor temperatures not to exceed 90C. When
used as RHH or RHW-2, conductor temperatures shall not exceed 90C in
wet or dry locations. Voltage rating for RHH or RHW-2 or USE-2 conduc-
tors is 600V.

See referenced page in the


Hardware & Supplies section:
Suggested Prep Tool
Cable End Strippers
2x2, 4x4 - I-9

Size (AWG
or kcmils)
No. of
Strands
Approx. Overall
Diameter (in)
Approx. Weight
(lbs/M-ft) Conduit Free Air
1/0 19 .525 390 170 260
2/0 19 .568 481 195 300
3/0 19 .619 597 225 350
4/0 19 .675 741 260 405
250 37 .751 880 290 455
350 37 .854 1,207 350 570
500 37 .983 1,693 430 700
750 61 1.191 2,516 535 885
1,000 61 1.340 3,315 615 1,055
Allowable
Ampacities (amps)
Information based on Southwire specs.
RHH/RHW
www.ptsupply.com
marketing@ptsupply.com
800-238-7514
24
Welding Cable
105C, Black
Construction
Bare, annealed copper per ASTM B-3. 30 AWG rope lay stranded per
ASTM B-172. Jacket is black thermoset EPDM. 105C to -55C. RoHS
compliant.
Applications
Designed for welding cable use where resistance to cuts, tears and
abrasion is required.
90C, Orange
Construction
Bare, annealed copper per ASTM B-3. 34 AWG rope lay stranded per
ASTM B-172 (Class M #34 stranding). Jacket is oil-resistant, thermoset
CPE per ASTM D-4313. Rated 90C to -55C.
Applications
Designed for welding cable use where resistance to cuts, tears and abra-
sion is required.
Size (AWG
or kcmils) Stranding Nominal O.D. (in) Amps*
Shipping Weight
(lbs/M-ft)
6 665 x 34 .395 105 134
4 1,045 x 34 .450 140 191
2 1,650 x 34 .515 190 286
1 2,090 x 34 .545 220 350
1/0 2,640 x 34 .600 260 454
2/0 3,300 x 34 .685 300 530
3/0 4,180 x 34 .755 350 658
4/0 5,225 x 34 .825 405 839
*Ampacity ratings are based on cable in free air at 30C. Ampacities will be
greater when used for intermittent welding applications.
Size (AWG
or kcmils) Stranding Nominal O.D. (in) Amps*
Shipping Weight
(lbs/M-ft)
6 259 x 30 .320 115 125
4 413 x 30 .375 150 182
2 651 x 30 .440 205 271
1 826 x 30 .505 240 360
1/0 1,044 x 30 .570 285 444
2/0 1,308 x 30 .605 325 535
3/0 1,653 x 30 .670 380 667
4/0 2,071 x 30 .720 440 809
*Ampacity ratings are based on cable in free air at 30C. Ampacities will be
greater when used for intermittent welding applications.
Information based on AIW specs.
Information based on AIW specs.
Separator
Thermoset
Insulation
Class K (#30)
Rope Lay
Stranding
Welding Cable
www.ptsupply.com
marketing@ptsupply.com
800-238-7514
25
Type SOOW Cable
90C, 600V
Construction
Stranded bare copper, EPR insulation, suitable llers,
separator, oil- and weather-resistant, black CPE jacket.
Specications
Meets or exceeds all applicable requirements of:
UL 62 (Flexible Cord and Fixture Wire)
CSA Standard 22.2 No. 49 (Flexible Cords and Cables)
Mine Safety and Health Administration (MSHA) ame resistance for
Mining Applications
This product complies with the requirements of Federal and Military
Specication JC-580B, NEC

Article 400 and is OSHA acceptable.


Applications
Permitted for use as specied by Article 400 and related articles of the NEC

. Some typical applications for Type


SOOW Cords include wiring for industrial machinery, motors and associated equipment, portable tools and
equipment, and temporary electrical power and lighting installations for construction sites. Type SOOW Cords
are suitable for use in (i) dry locations not to exceed minimum -40C or maximum 90C or (ii) wet locations or
other applicable locations. When exposed to oil or coolant at temperatures not to exceed 60C. Type SOOW cords
are ideal for ex applications in harsh environments where the highest degree of oil resistance and extended
service life are essential.
AWG Stranding
Nominal Insul.
Thickness (mils)
Nom.
Overall
Dia. (mils)
Weight
(lbs/M-ft) Ampacity
18/2 16 x 30 30 345 70 10
18/3 16 x 30 30 365 80 7
18/4 16 x 30 30 390 95 5.6
16/2 26 x 30 30 370 80 13
16/3 26 x 30 30 390 95 10
16/4 26 x 30 30 420 115 8
14/2 41 x 30 45 510 135 18
14/3 41 x 30 45 535 170 15
14/4 41 x 30 45 575 205 12
12/2 65 x 30 45 570 195 25
12/3 65 x 30 45 595 225 20
12/4 65 x 30 45 650 270 16
10/2 104 x 30 45 620 250 30
10/3 104 x 30 45 660 290 25
10/4 104 x 30 45 715 355 20
AWG Stranding
Nominal Insul.
Thickness (mils)
Nom.
Overall
Dia. (mils)
Weight
(lbs/M-ft) Ampacity
8/2* 65 x 26 50 660 290 40
8/3* 65 x 26 50 720 365 35
8/4* 65 x 26 50 780 500 28
8/5* 65 x 26 50 860 545 28
6/3* 101 x 26 50 800 515 45
6/4* 101 x 26 50 845 620 36
6/5* 101 x 26 50 945 750 36
4/2* 119 x 25 50 890 500 70
4/3* 119 x 25 50 940 670 60
4/4* 119 x 25 50 1,010 835 48
4/5* 119 x 25 50 1,135 1,065 48
2/3* 133 x .0211 55 1,090 1,030 80
2/4* 133 x .0211 55 1,170 1,285 64
2/5* 133 x .0211 55 1,435 1,620 64
*Not UL or CSA, but manufactured to acceptable commercial standards.
2-8 AWG are non-UL and non-CSA, but the option is available.
See referenced pages in the Hardware & Supplies section
Suggested Prep Tools
Cable End Strippers 2x2, 4x4 - I-9
MKO1A Jacket Stripper - I-11
721 Multi-Wire Stripper/Cutter - I-9

For SDN

Flexible Control
Cable see page 16 in the
Instrumentation & Tray section
Flexible Bunch Stranded
Bare Copper Conductors
Synthetic Rubber
Insulation (EPDM)
Separator
Thermoset
CPE Jacket
Information based on AIW specs.
Type SOOW
www.ptsupply.com
marketing@ptsupply.com
800-238-7514
26
Type SOW
Industrial Motor Lead Cable
See referenced page in the
Hardware & Supplies section:
Suggested Prep Tool
Cable End Strippers
2x2, 4x4 - I-9

AWG Stranding Conductor O.D. (in)


Insulation
Thickness (in)
Jacket
Thickness (in) Nominal O.D. (in) Amps
Shipping Weight
(lbs/M-ft)
16 26 x .01 .060 .030 .03 .186 13 25
14 41 x .01 .075 .045 .03 .233 18 48
12 65 x .01 .095 .045 .03 .253 25 51
10 104 x .01 .120 .045 .03 .278 30 66
90C, 600V
Construction
Stranded, annealed bare copper conductor, EPDM insulation, heavy-duty,
oil-resistant thermoset jacket.

Applications
Designed for use as motor and power leads where exibility and
portability are required.
For SDN

Flexible Control
Cable see page 16 in the
Instrumentation & Tray section
Information based on AIW specs.
Stranded
Copper
Conductor
EPDM
Insulation
Thermoset
Jacket
Type SOW
www.ptsupply.com
marketing@ptsupply.com
800-238-7514
27
See referenced pages in the
Hardware & Supplies section:
Suggested Prep Tools
MK01A Jacket Stripper - I-11
MK04 Jacket Stripper - I-11

Type G & G-GC Round


90C, 2kV & 600V/2kV
Construction
Manufactured with rope-lay stranded, bunched members, annealed copper
conductors which are insulated with a premium-grade EPDM. The three
or four insulated conductors are assembled round with non-wicking rubber
llers as needed and are covered with a black jacket rated -40C - 90C
(90C dry locations, 75C wet locations).
Specications
UL Listed
CSA and MSHA approved



RoHS compliant
Meets FT-5 Flame Test

Size (AWG
or kcmils)
Cond.
Strand
Ground
Check AWG
Ground
Cond. AWG
Nom. Insulation
Thick. (in)
Nominal
O.D. (in)
Current
Amps
Approx. Net
Weight (lbs/M-ft)
3 Conductor Type G-GC 2kV
8 133 10 2#10 .060 .965 65 665
6 259 10 2#10 .060 1.050 87 830
4 259 10 2#8 .060 1.105 114 1,145
2 259 10 2#7 .080 1.300 152 1,485
1 259 8 2#6 .080 1.465 177 2,100
1/0 259 8 2#5 .080 1.605 205 2,550
2/0 259 8 2#4 .080 1.750 237 3,020
3/0 259 8 2#3 .080 1.860 274 3,660
4/0 259 8 2#2 .080 1.940 316 4,410
250 627 8 2#2 .095 2.390 352 6,060
350 855 8 2#1/0 .095 2.680 433 7,400
500 1,235 8 2#2/0 .095 3.030 536 10,100
4 Conductor Type G 600V/2kV
8 133 4#12 - .060 1.045 52 635
6 259 4#12 - .060 1.125 70 900
4 259 4#10 - .060 1.210 91 1, 280
2 259 4#9 - .080 1.435 122 2,000
1 259 4#8 - .080 1.650 142 2,660
1/0 259 4#7 - .080 1.720 164 3,140
2/0 259 4#6 - .080 1.860 190 3,780
3/0 259 4#5 - .080 2.075 219 4,500
4/0 259 4#4 - .080 2.155 253 5,520

Applications
For use in industrial and light- to medium-duty mining applications, heavy-duty service as power supply cable,
power cable for mobile and portable electrical equipment at continuous conductor temperature of 90C. Type
G cables are suitable for use on three-phase AC systems where 3 or 4 conductors are needed and grounding is
required. Excellent exibility, resistance to oils, solvents, ozone, aging and abrasion.
Color Coding:
3-conductor White/Black/Red
4-conductor White/Black/Red/Orange
Information based on Southwire specs.
Industrial Grade Cable
www.ptsupply.com
marketing@ptsupply.com
800-238-7514
28
Mine Power Feeder Cable
90C, 5kV/8kV/15kV
Construction
Bare stranded copper, extruded semi-conductor shield, XLP insulation,
extruded insulation shield, ground and ground check conductors, jute
llers, cable reinforcement and black PVC jacket.
Specications
UL Listed
OSHA and MSHA acceptable


Passes MSHA Flame Test
Meets ICEA requirements


Applications
For use in high-voltage distribution circuits for permanent or semi-portable
installations in bore holes, shafts, open pits, strip mines and tunnels.
AWG or
kcmils
No. of
Strands
Insulation
Thickness (in) AWG Strands AWG
Insulation
Thickness (in)
Nominal
O.D.(in) Amps
Approx. Ship.
Weight (lbs/M-ft)
5kV - 100% & 133% Insulation Level - ES-13139
6 7 .09 10 7 x .0385 10 .030 1.235 93 991
4 7 .09 8 7 x .0486 8 .045 1.320 122 1,197
2 7 .09 6 7 x .0612 8 .045 1.460 159 1,653
2/0 19 .09 3 7 x .0867 8 .045 1.690 243 2,591
4/0 19 .09 1 19 x .0664 8 .045 1.950 321 3,806
250 37 .09 1/0 19 x .0745 8 .045 2.075 355 4,660
350 37 .09 2/0 19 x .0837 8 .045 2.285 435 6,130
500 37 .09 4/0 19 x .1055 8 .045 2.550 536 8,240
8kV - 100% Insulation Level - ES-13140
6 7 .115 10 7 x .0385 10 .030 1.350 93 1,077
4 7 .115 8 7 x .0486 8 .045 1.445 122 1,290
2 7 .115 6 7 x .0612 8 .045 1.565 159 1,710
1 19 .115 5 7 x .0688 8 .045 1.630 184 1,996
2/0 19 .115 3 7 x .0867 8 .045 1.850 243 2,857
4/0 19 .115 1 19 x .0664 8 .045 2.070 321 3,946
250 37 .115 1/0 19 x .0745 8 .045 2.190 355 4,980
350 37 .115 2/0 19 x .0837 8 .045 2.400 435 6,280
500 37 .115 4/0 19 x .1055 8 .045 2.700 536 8,470
15kV - 100% Insulation Level - ES-13141
2 7 .175 6 7 x .0612 8 .045 1.875 164 2,117
1 19 .175 5 7 x .0688 8 .045 1.940 187 2,477
1/0 19 .175 4 7 x .0772 8 .045 2.025 215 2,742
2/0 19 .175 3 7 x .0867 8 .045 2.110 246 3,130
4/0 19 .175 1 19 x .0664 8 .045 2.330 325 4,385
250 37 .175 1/0 19 x .0745 8 .045 2.450 359 5,400
350 37 .175 2/0 19 x .0837 8 .045 2.700 438 6,730
500 37 .175 4/0 19 x .0940 8 .045 3.050 502 8,515
Ground
Check Grounding
Conductors
Power Conductor
Information based on AIW specs.
Uninsulated
Ground Wire
Insulation Shield
XLP Insulation
Conductor Shield
Bare Copper
Conductors
Insulated
Ground Check
PVC Jacket
Open Reinforcement
Industrial Grade Cable
www.ptsupply.com
marketing@ptsupply.com
800-238-7514
29
Type W Portable Power Cable
90C, 2kV
Construction
Manufactured with rope-lay stranded, bunched members, annealed copper conductors.
A polyester or paper tape separates the copper conductors from the EP rubber insula-
tion. The insulated conductors are assembled round with llers as needed. The cable
is covered with a black CPE rubber jacket. The jacket may be applied in two layers.
Two-layer jackets are reinforced by a braid of synthetic material. The reinforcing is
between the layers.
Specications
Conductors are manufactured in accordance with ASTM B-33 and B-172
Made in accordance with ICEA S-75-381 - Portable and Power Feeder Cables
for Use in Mines and Similar Locations
MSHA accepted, P-7K-123049 LR27151
UL Listed as Type RHH-RHW-2 per UL 44
CSA Approved
Meets FT-5 Flame Test

Applications
For use in mining machines, locomotives, power supply leads on A.C. welders, motor leads, entertainment,
generator leads and grounding cable at continuous conductor temperature of 90C. Type W cables also are
suitable for continuous immersion in shallow water. Excellent exibility, resistance to oils, solvents, ozone, aging,
and abrasion.

See referenced pages in the


Hardware & Supplies section:
Suggested Prep Tools
MK01A Jacket Stripper - I-11
MK04 Jacket Stripper - I-11

Bare Copper
Conductor
Fillers
Open
Reinforcement
Separator
EPDM
Insulation
CPE
Jacket
No. of
Conductors
Size (AWG
or kcmils)
Cond.
Strand
Nom. Insulation
Thick. (in)
Nominal
O.D. (in)
Current
Amps
Approx. Net
Weight (lbs/M-ft)
1 8 133 .060 .485 74 160
1 6 259 .060 .565 99 220
1 4 259 .060 .605 130 290
1 2 259 .080 .680 174 395
1 1 259 .080 .765 202 490
1 1/0 259 .080 .810 234 575
1 2/0 259 .080 .885 271 700
1 3/0 259 .080 .930 313 820
1 4/0 259 .080 .980 361 1,000
1 250 627 .095 1.045 402 1,170
1 350 855 .095 1.145 495 1,520
1 500 1,235 .095 1.310 613 2,090
Also available in 2, 3, 4, 5 conductor. Call for specications.
Information based on Southwire specs.
Industrial Grade Cable
www.ptsupply.com
marketing@ptsupply.com
800-238-7514
30
FAA L-824 Type C
5kV
Construction
Shielded or unshielded, single conductor cable with stranded, bare copper
conductor, XLP insulation and PVC jacket on shielded cable.
Specications
Meets ICEA S-96-659 for unshielded and ICEA S-93-639 for shielded.

Applications
For installation in ducts, conduit or direct burial for use in airport lighting
and control circuits.
AWG
Conductor
Strands
Insulation
Thick. (in)
Approx.
O.D. (in)
Approx. Weight
(lbs/M-ft)
Unshielded
8 7 .11 .375 94
6 7 .11 .415 130
4 7 .11 .460 189
Shielded
8 7 .09 .610 175
6 7 .09 .645 240
4 7 .09 .695 305
See referenced page in the
Hardware & Supplies section:
Suggested Prep Tool
WS 49 Airport Lighting Cable
End Stripper/Penciller - I-9

Information based on AIW specs.


Stranded Bare
Copper
Opaque Separator
(or Conductor Shield
for Shielded Cable)
XLP Insulation
Bare Copper
Tape Shield*
PVC Jacket*
Semi-conducting
Insulation Shield*
*Shielded cable only.
Airport Lighting Cable
www.ptsupply.com
marketing@ptsupply.com
800-238-7514