Air Conditioning
Air Flow Rates

When determining air flow rates for rooms that are air conditioned, the following
procedure should be adopted;

1. Calculate heat gains.

2. Complete psychometric chart.

3. Determine mass flow rate of supply air from the following;

m = H / (Cp x (tr ts))
where;
H = Sensible heat gain (kW)
m = mass flow rate of air (kg/s)
Cp = Specific heat capacity of air (1.005 kJ/kg K)
t
r
= room temperature (
o
C)
t
s
= supply air temperature (
o
C) from psychometric chart.

4. Convert mass flow rate to a volume flow rate:

Volume flow rate (m
3
/s) = mass flow rate (kg/s) / density of air
(kg/m
3
)

5. Convert this to an Air Change rate for comparison.

Volume flow rate (m
3
/h) = Volume flow rate (m
3
/s) x 3600

Supply Air Rate (AC/h) = Volume Flow Rate (m
3
/h) / Room
Volume (m
3
)

6. Check out the recommended air flow rate from CIBSE Guide B2 (Ventilation
and Air Conditioning) Section 3 - Requirements.

Use the higher value of air change rate for design purposes.

Example 1
2/10/14 Air Flow Rates
www.arca53.dsl.pipex.com/index_files/airflow.htm 2/6

Determine the supply, fresh air and recirculation air flow rates for the Sports Centre
(Fitness Suite No.1) shown below.
See Assignments section Drawings.
The room is to be fully air conditioned.





















2/10/14 Air Flow Rates
www.arca53.dsl.pipex.com/index_files/airflow.htm 3/6
DATA
Occupancy = 80 people
Room volume = 3740 m
3
.
Room temperature = 18
o
C from table 3.19 CIBSE guide.
Sensible heat gain = 70 kW from calculations (not shown)
See Heat Gains section of these notes for further details.
Supply air temp. = 13
o
C from psychrometric chart (not shown)
See Psychrometrics section of these notes for further details.
Supply air density = See Science section Properties of air density at 13
o
C and
50% = 1.225 kg/m
3
.

Supply Air Rate

m = H / (Cp x (tr ts))

m = 70 / (1.005 x (18 -13))

m = 70 / 5.025

m = 13.93 kg/s

Volume flow rate (m
3
/s) = mass flow rate (kg/s) / density of air (kg/m
3
)
= 13.93 / 1.225
= 11.37 m
3
/s
Volume flow rate (m
3
/h) = Volume flow rate (m
3
/s) x 3600
= 11.37 m
3
/s x 3600
= 40,932 m
3
/h
Supply Air Rate (AC/h) = Volume Flow Rate (m
3
/h) / Room Volume (m
3
)
= 40,932 m
3
/h / 3740
= 10.9 AC/h

Table 3.1 Summary of Recommendations (Guide B2) directs to Table 3.19.
From Table 3.19 for Fitness Centre the air flow rate is 10 to 12 AC/h.

Use higher value of 12 AC/h supply air rate as found from above Table.
This higher value is then used to size all plant and ductwork.

Fresh Air Rate
2/10/14 Air Flow Rates
www.arca53.dsl.pipex.com/index_files/airflow.htm 4/6

Section 3.2.1.3 Body odour (CIBSE guide B2) gives the following information;
Therefore in the absence of further information, it is recommended that 8 litre.s-1 per person
should be taken as the minimum ventilation rate to control body odour levels in rooms with
sedentary occupants.

Since the level of activity is higher than sedentary in the Fitness Room, we will adopt a
fresh air rate of 24 l/s per person.

Fresh air rate = 24 l/s x 80 people
= 1920 l/s
= 1.92 m
3
/s
= 1.92 x 3600 = 6912 m
3
/h
= 6912 m
3
/h / 3740 = 1.9 AC/h

Percentage fresh air; 1.9 / 12.0 (x 100%) = 15.8%

Recirculation Air Rate

Recirculation Air Rate = Supply air rate - Fresh air rate
= 12.0 - 1.9
= 10.1 AC/h

Percentage recirculation air; 10.1 / 12.0 (x 100%) = 84.2%

The air flow rates are shown on the diagram below.

2/10/14 Air Flow Rates
www.arca53.dsl.pipex.com/index_files/airflow.htm 5/6






















2/10/14 Air Flow Rates
www.arca53.dsl.pipex.com/index_files/airflow.htm 6/6

A slight negative pressure may be provided in the Fitness Room .
This is so that contaminated air does not enter the adjoining Reception / Foyer area.
The Return air amount may be increased to 110% of the previously calculated value; that
is, 13.2 AC/h or 13.72 m
3
/s.