ELECTRICAL INSTALLATION

The quoted price for the item 11 of the Bill of Quantities shall include all necessary materials such as
cables, PVC conduits, PVC sunk boxes, cable trunking etc and labour required to complete the
electrical installation according to dra!ing "oTCP#$%&#'(T)#%*#++, in good !orking order
-ll types of fittings, materials particularly cable trunking system and distribution boards shall be
appro.ed by the /ngineer0s representati.e prior to installation
The !iring installation shall comply !ith the requirements of 1/T 2iring 3egulations, latest edition
The installation shall be properly grounded by means of a suitable earthing system comply !ith the
requirements of 1/T 2iring 3egulations, latest edition
1.0 The Distribution Board
4upply and installation of single phase and neutral !all mounted $istribution Board complete !ith
plastic enclosure !ith lockable door
1t shall include incoming &CB, 3C$, outgoing &CBs, busbars, terminals, mounting rails and all
required accessories
1.1 Miniature Circuit BreakersMCB!
The miniature circuit breakers 5&CB6 shall comply !ith B4 7891 Part 1 and shall ha.e a Type ,
Classification or equi.alent 1/C classification
The frame si:e of all &CBs shall be the same so that they can be easily interchanged
Circuit breaker dollies shall be of the trip;free pattern to pre.ent closing the breaker on a faulty circuit
and they shall be engra.ed to indicate the ("#(<< position
1." Residua# Current De$icesRCD!
3C$ shall conform to B4 =,>7 and shall be sensiti.e to pulsating $C fault current The 3C$ shall
consist of a current transformer, a tripping coil !ith contact assembly, main supply contacts, ("#(<<
s!itch, a test button and a trip;free mechanism, all mounted on robust body of all insulated material
3C$ shall be suitable for operation on a ,7+V, 1;ph, ?+ *: supply and shall gi.e trouble;free ser.ice
in the locally pre.ailing climatic conditions
The tripping current shall be 7+ m-
".0 Li%ht &ittin%s
@ight fittings shall be of the high quality C<@ and each light fitting shall be subAect to the appro.al of
the /ngineer0s representati.e 2iring of a light point includes supply of required cables, PVC casing,
flush s!itch and all other required materials
2iring of ceiling fixed recessed, pendant or suspended type lamp light point from the distribution
board, using 1+sqmm Cu PVC#PVC cable dra!n through securely fixed surface PVC casing,
controlled by a 1+- flush s!itch
1
'.0 Socket Out#ets
-ll socket outlets shall be ?- s!itched, shuttered, single socket outlet complying !ith B4 ?=B
2iring of ?- po!er socket outlet shall be !ith 1+sqmm Cu PVC#PVC cable in radial circuits and
,?sqmm Cu PVC earth !ire, dra!n through the concealed PVC conduits, from the distribution
board