Académique Documents
Professionnel Documents
Culture Documents
SIPROTEC
Multifunction Generator
Protection Relay
7UM611/7UM612
V4.0
Instruction Manual
3UHIDFH_
7DEOH_RI_&RQWHQWV_
,QWURGXFWLRQ 1
+DUGZDUH_DQG_&RQQHFWLRQV 2
,QLWLDO_,QVSHFWLRQV 3
6,3527(& __'HYLFHV 4
&RQILJXUDWLRQ 5
)XQFWLRQV 6
&RQWURO_'XULQJ_2SHUDWLRQ 7
,QVWDOODWLRQ_DQG_&RPPLVVLRQLQJ 8
5RXWLQH_&KHFNV_DQG_0DLQWHQDQFH 9
7HFKQLFDO_'DWD 10
$SSHQGL[ A
,QGH[_
Siemens Manual No. C53000-G1176-C127-1
7UM61 Manual i
C53000-G1176-C127-1
Preface
Purpose of This
Manual
This manual describes the functions, operation, installation, and placing into service
of the device. In particular, one will find:
• General information regarding operation of SIPROTEC® 4 devices → Chapter 4;
• Information regarding customizing of the device → Chapter 5;
• Descriptions of device functions and settings → Chapter 6;
• Instructions for operation while in service → Chapter 7;
• Instructions for mounting and commissioning → Chapter 8;
• Compilation of technical specifications → Chapter 10;
• As well as a compilation of the most significant data for experienced users in the
Appendix.
Target Audience Protection engineers, commissioning engineers, personnel concerned with
adjustment,
checking, and service of selective protective equipment, automatic and control
facilities, and personnel of electrical facilities and power plants.
Applicability of
This Manual
This manual is valid for: SIPROTEC® 4 7UM61 Multifunction Machine Protections;
firmware version 4.0.
Additional Support For questions regarding SIPROTEC® 4 devices, please contact your
Siemens representative.
Training Courses Individual course offerings may be found in our Training Catalog, or questions
can be
directed to our training center. Please contact your Siemens representative.
Indication of Conformity
This product complies with the directive of the Council of the European Communities
on the approximation of the laws of the member states relating to electromagnetic
compatibility (EMC Council Directive 89/336/EEC) and concerning electrical equipment
for use within certain voltage limits (Low-voltage Directive 73/23/EEC).
This conformity is proved by tests conducted by Siemens AG in accordance with Article
10 of the Council Directive in agreement with the generic standards EN 50081
and EN 50082 for EMC directive, and with the standard EN 60255–6 for the low-voltage
directive.
The product conforms with the international standard of the series IEC 60255 and the
German standard DIN 57435 /Part 303 (corresponds to VDE 0435/Part 303).
Preface
ii 7UM61 Manual
C53000-G1176-C127-1
Instructions and
Warnings
The following indicators and standard definitions are used:
DANGER
means that death, severe personal injury, or considerable equipment damage will occur
if safety precautions are disregarded.
WARNING
means that death, severe personal injury, or considerable equipment damage could
occur if safety precautions are disregarded.
Caution
means that light personal injury or equipment damage may occur if safety precautions
are disregarded. This particularly applies to damage to the device and to resulting damage
of the protected equipment.
Instruction
is an important piece of information regarding the product or the part of the manual
that deserves special attention.
QUALIFIED PERSONNEL
Within the meaning of safety precautions of this manual and the instructions, qualified
personnel are those persons who are qualified to set up, install, place into service, and
operate this device, and who possess the following qualifications:
q Training and instruction (or other qualification) for switching, grounding, and designating
devices and systems.
q Training or instruction in accordance with safety standards for care and use of certain
safety equipment.
q First aid training.
Typographic and
Graphical Conventions
The following text formats are used to identify concepts giving device information described
by the text flow:
3DUDPHWHU_QDPHV, or identifiers for configuration or function parameters that appear
in the device display or on the screen of a PC (with DIGSI® 4) are shown in monoscript
(same point size) bold text. This also applies to header bars for selection menus.
Warning!
During operation of electrical equipment, certain parts of these devices are under high
voltage. Severe personal injury or significant equipment damage could result from improper
behavior.
Only qualified personnel should work on this equipment or in the vicinity of this equipment.
These personnel must be familiar with all warnings and service procedures described
in this manual, as well as with safety regulations.
Prerequisites to proper and safe operation of this product are proper transport, proper
storage, setup, installation, operation, and maintenance of the product, as well as
careful operation and servicing of the device within the scope of the warnings and instructions
of this manual.
In particular, the general facility and safety regulations for work with high-voltage
equipment (e.g. ANSI, IEC, EN, or other national or international regulations) must be
observed. Noncompliance may result in death, injury, or significant equipment damage.
Preface
7UM61 Manual iii
C53000-G1176-C127-1
3DUDPHWHU_FRQGLWLRQV, or possible settings of parameters that appear in the device
display or on the screen of a PC (with DIGSI® 4), are additionally shown in italic
style. This also applies to selection items for selection menus.
“$QQXQFLDWLRQV”, or identifiers for information produced by the device or required
by other devices or from the switch-gear is shown in mono-script (same point size) and
placed into quotation marks.
For diagrams in which the identifier type results from the representation itself, text conventions
may differ from the above-mentioned.
The following symbols are used in diagrams:
possible conditions 2Q and 2II
IL1
GND Fault device-internal (logical) input signal
GND Fault device-internal (logical) output signal
internal input signal of an analog quantity
>Release
Dev. Trip
external binary output signal with function number F# (annunciation
2Q
2II
____ )81&7,21
Parameter address
3DUDPHWHU_QDPH
Parameter Conditions
example of a parameter switch )81&7,21 with address ____ and
F#
F#
external binary input signal with function number F# (binary input,
from device)
respective annunciation to the device)
Input signal of an analog quantity
≥1
&
OR gate
AND gate
Signal inversion
OR
Preface
iv 7UM61 Manual
C53000-G1176-C127-1
I2>
____ ,_!!
0T
S
R
Q
≥ 1 Inputsignals of dynamic quantity
Formation of one output signal from a number
of analog inputs
Timer (dropout delayed)
Limit stage with parameter address and
T
Dynamic triggered pulse timer (monoflop)
Static memory (RS–flipflop) with setting input (S),
=1 Exclusive–OR gate: output is active, if only one
of the inputs is active
= Coincidence gate: output is active, if both inputs
are active simultaneously
T0
____ 7_,_!!
Timer (pick up delayed) with parameter address
and designator
resetting input (R), output (Q) and inverted Q
designator
output (Q)
Liability Statement
We have checked the text of this manual against the
hardware and software described. Exclusions and deviations
cannot be ruled out; we accept no liability for lack
of total agreement.
The information in this manual is checked periodically,
and necessary corrections will be included in future editions.
We appreciate any suggested improvements.
We reserve the right to make technical improvements
without notice.
Copyright
Copyright © Siemens AG 1999. All rights reserved.
Dissemination or reproduction of this document, or evaluation and communication
of its contents, is not authorized except where expressly permitted.
Violations are liable for damages. All rights reserved, particularly
for the purposes of patent application or trademark registration.
Registered trademarks
SIPROTEC®, SIMATIC®, SIMATIC NET ®, SINAUT ®, SICAM®, and
DIGSI® are registered trademarks of Siemens AG. Other designations
in this manual may be trademarks that if used by third parties for their
own purposes may violate the rights of the owner. n
7UM61 Manual v
C53000-G1176-C127-1
Table of Contents
1
Introduction......................................................................................................................................
1-1
1.1 Overall Operation ................................................................................................................ 1-2
1.2 Applications ......................................................................................................................... 1-5
1.3 Features .............................................................................................................................. 1-7
1.4 Scope of Functions.............................................................................................................. 1-8
2 Hardware and
Connections ............................................................................................................. 2-1
2.1 Version of 7UM61 for Panel Flush-Mounting / Cubicle Mounting........................................ 2-2
2.1.1 Construction ........................................................................................................................ 2-
2
2.1.2 Connections to Threaded Terminals ................................................................................... 2-
6
2.1.3 Connections to Plug-In Terminals ..................................................................................... 2-
10
2.1.4 Connections to Optical Communication Interfaces............................................................ 2-
13
2.1.5 Connections to Electrical Communication Interfaces ........................................................ 2-
14
2.2 Version of 7UM61 for Panel Surface-Mounting................................................................. 2-15
2.2.1 Construction ...................................................................................................................... 2-
15
2.2.2 Connections to Threaded Terminals ................................................................................. 2-
17
2.2.3 Connections to Optical Communication Interfaces............................................................ 2-
18
3 Initial
Inspections ............................................................................................................................. 3-1
3.1 Unpacking and Packing....................................................................................................... 3-2
3.2 Inspections Upon Receipt.................................................................................................... 3-3
3.2.1 Inspection of Features and Ratings..................................................................................... 3-
3
3.2.2 Electrical Check................................................................................................................... 3-
3
3.3 User Interface...................................................................................................................... 3-4
3.3.1 Navigating through the Operating Menus Using the Operator Control Panel...................... 3-
4
3.3.2 Operation Using DIGSI® 4................................................................................................... 3-
7
3.4 Storage............................................................................................................................. 3-12
4 SIPROTEC 4
Devices........................................................................................................................ 4-1
4.1 General............................................................................................................................... 4-2
4.1.1 Protection and Control......................................................................................................... 4-
2
4.1.2 Communication................................................................................................................... 4-3
4.1.3 Settings ............................................................................................................................... 4-
4
4.1.4 Operations.......................................................................................................................... 4-4
4.1.5 Waveform Capture .............................................................................................................. 4-
4
vi 7UM61 Manual
C53000-G1176-C127-1
4.2 Operator Control Facilities................................................................................................... 4-5
4.2.1 Operating Panel On Device................................................................................................. 4-
5
4.2.2 DIGSI® 4 Tool...................................................................................................................... 4-
7
4.3 Information Retrieval............................................................................................................ 4-8
4.3.1 Annunciations ...................................................................................................................... 4-
9
4.3.2 Measurements ................................................................................................................... 4-
11
4.3.3 Waveform Capture............................................................................................................. 4-
13
4.4 Control ............................................................................................................................... 4-14
4.5 Manual Overwrite / Tagging............................................................................................... 4-16
4.6 General Setting Procedure ................................................................................................ 4-17
4.7 Device Configuration ......................................................................................................... 4-20
4.8 Configuration of Inputs and Outputs (Configuration Matrix) .............................................. 4-21
4.9 Programmable Logic CFC ................................................................................................. 4-24
4.10 Power System Data........................................................................................................... 4-26
4.11 Setting Groups................................................................................................................... 4-27
4.12 General Device Settings.................................................................................................... 4-29
4.13 Time Synchronization ........................................................................................................ 4-
30
4.14 Serial Interfaces................................................................................................................. 4-31
4.15 Passwords ......................................................................................................................... 4-
33
5
Configuration ...................................................................................................................................
5-1
5.1 Configuration of Functions................................................................................................... 5-2
5.2 Configuration of Information, Meaured Values, and Commands......................................... 5-6
5.2.1 Preparation .......................................................................................................................... 5-
6
5.2.2 Structure and Operation of the Configuration Matrix ......................................................... 5-
10
5.2.3 Establishing Information Properties................................................................................... 5-
14
5.2.4 Performing Configuration................................................................................................... 5-
20
5.2.5 Transferring Metering Values ............................................................................................ 5-
27
5.2.6 Setting of Contact Chatter Blocking................................................................................... 5-
28
5.3 Creating User Defined Functions with CFC....................................................................... 5-30
5.4 Establishing a Default Display ........................................................................................... 5-38
5.5 Serial Interfaces................................................................................................................. 5-39
5.5.1 Settings in the property dialog ........................................................................................... 5-
39
5.5.1.1 Setting of IEC- and Profibus-FMS protocol........................................................................ 5-
39
5.5.1.2 Selecting additional protocols ............................................................................................
5-40
7UM61 Manual vii
C53000-G1176-C127-1
5.5.2 Setting the ports ................................................................................................................ 5-
42
5.5.2.1 Serial port on PC............................................................................................................... 5-
42
5.5.2.2 PC and Service Port ..........................................................................................................
5-43
5.5.2.3 Profibus FMS connection .................................................................................................. 5-
44
5.5.2.4 Setting VD addresses........................................................................................................ 5-
44
5.5.2.5 Device IEC ........................................................................................................................ 5-
45
5.6 Date and Time Stamping................................................................................................... 5-47
6
Functions..........................................................................................................................................
6-1
6.1 General............................................................................................................................... 6-3
6.1.1 Introduction, reference power system ................................................................................. 6-
3
6.1.2 Brief overview of the device operation................................................................................. 6-
4
6.1.3 Power System Data 1........................................................................................................ 6-
10
6.1.4 Settings ............................................................................................................................. 6-
13
6.1.4.1 Information ........................................................................................................................ 6-
14
6.1.5 Setting groups ................................................................................................................... 6-
14
6.1.5.1 Information ........................................................................................................................ 6-
16
6.1.6 Power System Data 2........................................................................................................ 6-
16
6.1.6.1 Settings ............................................................................................................................. 6-
17
6.1.6.2 Information ........................................................................................................................ 6-
17
6.2 Overcurrent Protection (ANSI 50, 51, 67).......................................................................... 6-18
6.2.1 Overcurrent Protection (Stage I>) with undervoltage seal–in............................................ 6-
18
6.2.1.1 Functional description........................................................................................................ 6-
18
6.2.1.2 Programming settings for ttime-overcurrent protection ..................................................... 6-
19
6.2.1.3 Settings for phase overcurrent protection.......................................................................... 6-
20
6.2.1.4 Information list for phase overcurrent protection ...............................................................
6-21
6.2.2 Overcurrent protection (stage I>>) with direction .............................................................. 6-
21
6.2.2.1 Functional description........................................................................................................ 6-
21
6.2.2.2 Programming settings........................................................................................................ 6-
24
6.2.2.3 Settings for I>> time-overcurrent stage of the definite time-overcurrent protection........... 6-
25
6.2.2.4 Information List ................................................................................................................. 6-
26
6.3 Inverse O/C time protection (ANSI 51) .............................................................................. 6-27
6.3.1 Functional description........................................................................................................ 6-
27
6.3.2 Functional settings ............................................................................................................ 6-
31
6.3.2.1 Parameter list of the inverse O/C time protection.............................................................. 6-
32
6.3.2.2 Information List ..................................................................................................................
6-33
6.4 Thermal overload protection (ANSI 49) ............................................................................. 6-34
6.4.1 Description of thermal overload protection........................................................................ 6-
34
6.4.2 Programming settings........................................................................................................ 6-
37
6.4.2.1 Settings for thermal overload protection............................................................................ 6-
41
6.4.2.2 Information list for thermal overload protection ................................................................. 6-
42
6.5 Unbalanced load protection (ANSI 46) .............................................................................. 6-43
6.5.1 Description of unbalanced load protection ........................................................................ 6-
43
6.5.2 Programming settings........................................................................................................ 6-
45
6.5.2.1 Settings for unbalanced load protection ............................................................................
6-48
6.5.2.2 Information list for unbalanced load protection.................................................................. 6-
49
viii 7UM61 Manual
C53000-G1176-C127-1
6.6 Underexcitation protection (ANSI 40) ................................................................................ 6-50
6.6.1 Functional description........................................................................................................ 6-
50
6.6.2 Functional settings............................................................................................................. 6-
52
6.6.2.1 Parameter lists of the underexcitation protection............................................................... 6-
56
6.6.2.2 Information list of the underexcitation protection ...............................................................
6-56
6.7 Reverse power protection (ANSI 32R) .............................................................................. 6-58
6.7.1 Functional description........................................................................................................ 6-
58
6.7.2 Functional settings............................................................................................................. 6-
59
6.7.2.1 Parameter list of the reverse power protection.................................................................. 6-
60
6.7.2.2 Information list of the reverse power protection................................................................. 6-
61
6.8 Forward power supervision (ANSI 32F)............................................................................. 6-62
6.8.1 Functional description........................................................................................................ 6-
62
6.8.2 Functional settings............................................................................................................. 6-
63
6.8.2.1 Parameter list of the forward power monitoring .................................................................
6-64
6.8.2.2 Information list of the forward power monitoring................................................................ 6-
64
6.9 Impedance protection (ANSI 21) ....................................................................................... 6-65
6.9.1 Functional description........................................................................................................ 6-
65
6.9.1.1 Fault detection ...................................................................................................................
6-65
6.9.1.2 Determination of the short–circuit impedance ...................................................................
6-65
6.9.1.3 Tripping characteristic........................................................................................................ 6-
67
6.9.1.4 Tripping logic ..................................................................................................................... 6-
68
6.9.2 Functional settings............................................................................................................. 6-
70
6.9.2.1 Parameter list of the impedance protection .......................................................................
6-73
6.9.2.2 Information list of the impedance protection...................................................................... 6-
74
6.10 Undervoltage protection (ANSI 27).................................................................................... 6-75
6.10.1 Function............................................................................................................................ 6-
75
6.10.2 Functional settings............................................................................................................. 6-
76
6.10.2.1 Parameter list of the undervoltage protection....................................................................
6-77
6.10.2.2 Information list of the undervoltage protection...................................................................
6-77
6.11 Overvoltage protection (ANSI 59)...................................................................................... 6-78
6.11.1 Description........................................................................................................................ 6-
78
6.11.2 Functional settings............................................................................................................. 6-
78
6.11.2.1 Parameter list of the overvoltage protection ......................................................................
6-79
6.11.2.2 Information list of the overvoltage protection.....................................................................
6-80
6.12 Frequency protection (ANSI 81) ........................................................................................ 6-
81
6.12.1 Description of frequency protection ................................................................................... 6-
81
6.12.2 Programming settings........................................................................................................ 6-
82
6.12.2.1 Settings for frequency protection.......................................................................................
6-83
6.12.2.2 Information list for frequency protectiion............................................................................
6-85
6.13 Overexcitation (Overflux) protection U/f (ANSI 24)............................................................ 6-86
6.13.1 Functional description........................................................................................................ 6-
86
6.13.2 Functional settings............................................................................................................. 6-
88
6.13.2.1 Parameter list of the overexcitation protection...................................................................
6-90
6.13.2.2 Information list of the overexcitation protection ................................................................
6-90
7UM61 Manual ix
C53000-G1176-C127-1
6.14 90–%–stator earth fault protection (ANSI 59N, 64G, 67G)................................................ 6-91
6.14.1 Functional description........................................................................................................ 6-
91
6.14.2 Functional settings ............................................................................................................ 6-
95
6.14.2.1 Parameter list of the 90% stator earth fault protection ......................................................
6-98
6.14.2.2 Information list of the 90% stator earth fault protection .....................................................
6-98
6.15 Sensitive earth current protection (ANSI 50/51GN, 64R).................................................. 6-99
6.15.1 Functional description........................................................................................................ 6-
99
6.15.2 Functional settings .......................................................................................................... 6-
101
6.15.2.1 Parameter list of the sensitive earth current detection ................................................... 6-
102
6.15.2.2 Information list of the sensitive earth current detection ...................................................
6-102
6.16 100–%–stator earth fault protection with 3rd harm. (ANSI 59TN/ 27TN (3.H.)) .............. 6-103
6.16.1 Functional description...................................................................................................... 6-
103
6.16.2 Functional settings .......................................................................................................... 6-
105
6.16.2.1 Parameter list of the 100–%–stator earth fault protection with 3rd harmonic ..................
6-106
6.16.2.2 Information list of the 100–%–stator earth fault protection with 3rd harmonic................. 6-
106
6.17 Breaker failure protection (ANSI 50BF)........................................................................... 6-107
6.17.1 Description of breaker failure protection.......................................................................... 6-
107
6.17.2 Programming settings...................................................................................................... 6-
109
6.17.2.1 Settings for breaker failure protection.............................................................................. 6-
110
6.17.2.2 Information list for breaker failure protection .................................................................. 6-
111
6.18 Inadvertent energization (ANSI 50, 27) ........................................................................... 6-
112
6.18.1 Functional description...................................................................................................... 6-
112
6.18.2 Functional settings .......................................................................................................... 6-
113
6.18.2.1 Parameter list of the inadvertent energizing protection ...................................................
6-114
6.18.2.2 Information list of the inadvertent energizing function .....................................................
6-115
6.19 Monitoring functions ........................................................................................................ 6-116
6.19.1 Description of Fuse-Failure-Monitor ................................................................................ 6-
116
6.19.2 Programming settings for Fuse-Failure-Monitor .............................................................. 6-
118
6.19.2.1 Settings for Fuse-Failure-Monitor ....................................................................................
6-118
6.19.2.2 Information ...................................................................................................................... 6-
118
6.19.3 Description of measured-value monitoring...................................................................... 6-
118
6.19.3.1 Hardware monitoring ....................................................................................................... 6-
118
6.19.3.2 Software monitoring......................................................................................................... 6-
120
6.19.3.3 Monitoring of external current transformer circuits ..........................................................
6-121
6.19.4 Programming settings for measured-value monitoring.................................................... 6-
122
6.19.4.1 Settings for measured-value monitoring.......................................................................... 6-
123
6.19.4.2 Information lists of the monitoring functions ....................................................................
6-124
6.19.5 Description of Trip Circuit Monitor (ANSI 74TC).............................................................. 6-
125
6.19.6 Programming settings for Trip Circuit Monitor ................................................................. 6-
129
6.19.6.1 Setting for Trip Circuit Monitor......................................................................................... 6-
131
6.19.6.2 Information ...................................................................................................................... 6-
131
6.19.7 Malfunction responses of the monitoring functions ......................................................... 6-
131
6.20 External trip commands via binary inputs........................................................................ 6-133
6.20.1 Description ...................................................................................................................... 6-
133
x 7UM61 Manual
C53000-G1176-C127-1
6.20.2 Programming settings...................................................................................................... 6-
133
6.20.2.1 Parameter list................................................................................................................... 6-
134
6.20.2.2 Information list ................................................................................................................. 6-
134
6.21 Phase rotation reversal.................................................................................................... 6-136
6.21.1 Description of phase rotation reversal ............................................................................. 6-
136
6.21.2 Programming settings...................................................................................................... 6-
137
6.22 Protection function logic................................................................................................... 6-138
6.22.1 Description...................................................................................................................... 6-
138
6.22.1.1 Pickup logic for the device............................................................................................... 6-
138
6.22.2 Tripping logic of the device.............................................................................................. 6-
139
6.22.2.1 Description...................................................................................................................... 6-
139
6.22.2.2 Programming settings for tripping logic ...........................................................................
6-140
6.22.3 Fault display on the LEDs/LCD........................................................................................ 6-
140
6.22.3.1 Description of “No Trip – No Flag” Option .......................................................................
6-140
6.22.3.2 Programming Settings .....................................................................................................
6-140
6.22.4 Statistical counters........................................................................................................... 6-
141
6.22.4.1 Description...................................................................................................................... 6-
141
6.22.4.2 Setting/Resetting ............................................................................................................. 6-
141
6.22.4.3 Information list for the device........................................................................................... 6-
142
6.23 Auxiliary functions............................................................................................................ 6-143
6.23.1 Message processing........................................................................................................ 6-
143
6.23.2 Measurements ................................................................................................................. 6-
144
6.23.3 Waveform Capture........................................................................................................... 6-
147
6.23.4 Programming Settings ..................................................................................................... 6-
147
6.23.4.1 Settings for oscillographic fault recording........................................................................ 6-
149
6.23.4.2 Fault recording information list......................................................................................... 6-
149
6.24 Breaker control ................................................................................................................ 6-150
6.24.1 Types of commands ........................................................................................................ 6-
150
6.24.2 Steps in the command sequence .................................................................................... 6-
151
6.24.3 Interlocking ...................................................................................................................... 6-
152
6.24.3.1 Interlocked/non-interlocked switching.............................................................................. 6-
153
7 Control During
Operation................................................................................................................. 7-1
7.1 Read-out of Information ....................................................................................................... 7-2
7.1.1 Messages ............................................................................................................................ 7-
2
7.1.1.1 Output of Messages.............................................................................................................
7-2
7.1.1.2 Operating Messages (Event Log) ........................................................................................
7-5
7.1.1.3 Fault Messages (Trip Log)...................................................................................................
7-6
7.1.1.4 Saving and Erasing the Messages ......................................................................................
7-8
7.1.1.5 General Interrogation......................................................................................................... 7-
10
7.1.1.6 Spontaneous Messages ....................................................................................................
7-10
7.1.2 Switching Statistics............................................................................................................ 7-
10
7.1.2.1 Viewing the Switching Statistics ........................................................................................
7-11
7.1.2.2 Resetting and Setting the Switching Statistics................................................................... 7-
12
7.1.2.3 Setting Limit Values for the Statistics Counters................................................................. 7-
12
7UM61 Manual xi
C53000-G1176-C127-1
7.1.3 Measured and Metered Values ......................................................................................... 7-
13
7.1.3.1 Measured Values .............................................................................................................. 7-
14
7.1.3.2 Energy, Metered Values.................................................................................................... 7-
17
7.1.3.3 Setting and Retrieval of User Defined Set-points ..............................................................
7-18
7.1.3.4 Resetting Metered Values and Min/Max Values................................................................ 7-
20
7.1.4 Fault Records .................................................................................................................... 7-
21
7.1.4.1 Viewing Fault Records....................................................................................................... 7-
21
7.1.4.2 Saving the Fault Records .................................................................................................. 7-
23
7.2 Control of Device Functions .............................................................................................. 7-24
7.2.1 Read and Set Date and Time............................................................................................ 7-
24
7.2.2 Switching Setting Groups .................................................................................................. 7-
29
7.2.3 Controlling Information to the System Interface during Test Operation............................. 7-
31
7.3 Control of Switchgear ........................................................................................................ 7-34
7.3.1 Display Equipment Position and Control ........................................................................... 7-
35
7.3.2 Manual Overwriting............................................................................................................ 7-
38
7.3.3 Set Status......................................................................................................................... 7-39
7.3.4 Interlocking ........................................................................................................................ 7-
41
7.3.5 Tagging ............................................................................................................................. 7-
42
7.3.6 Switching Authority ............................................................................................................ 7-
43
7.3.7 Switching Mode ................................................................................................................. 7-
43
7.3.8 Control Messages.............................................................................................................. 7-
45
7.3.9 Other Commands ............................................................................................................. 7-46
8 Installation and
Commissioning ..................................................................................................... 8-1
8.1 Installation and Connections ............................................................................................... 8-2
8.1.1 Installation ........................................................................................................................... 8-
2
8.1.2 Connections ........................................................................................................................ 8-
5
8.1.3 Hardware Modifications....................................................................................................... 8-
7
8.2 Checking Connections....................................................................................................... 8-19
8.2.1 Data Connections.............................................................................................................. 8-
19
8.2.1.1 Serial Interfaces ................................................................................................................ 8-
19
8.2.1.2 Test Mode and Blocking Data Transmission..................................................................... 8-
20
8.2.1.3 Generate indications ......................................................................................................... 8-
21
8.2.2 Checking the Device Connections..................................................................................... 8-
23
8.2.3 Checking the Integration in the Plant................................................................................. 8-
24
8.2.3.1 General Hints .................................................................................................................... 8-
24
8.2.3.2 Checking the Binary Inputs and Outputs........................................................................... 8-
26
8.2.3.3 Testing the Breaker Failure Scheme................................................................................. 8-
29
8.2.3.4 Testing User-Defined Functions (CFC) .............................................................................
8-29
8.2.3.5 Trip/Close Tests for Primary Equipment............................................................................ 8-
29
8.3 Commissioning Tests Performed with the Machine .......................................................... 8-31
8.3.1 General advices ................................................................................................................ 8-
31
8.3.2 Triggering Oscillographic Recordings................................................................................ 8-
33
8.3.3 Checking the current circuits ............................................................................................. 8-
34
8.3.4 Checking the voltage circuits............................................................................................. 8-
36
xii 7UM61 Manual
C53000-G1176-C127-1
8.3.5 Checking the earth fault protection.................................................................................... 8-
38
8.3.5.1 Block connection................................................................................................................ 8-
38
8.3.5.2 Bus–bar connection ...........................................................................................................
8-41
8.3.6 Checking the Sensitive Earth Fault Detection when Used for
Rotor Earth Fault Protection .............................................................................................. 8-45
8.3.7 Tests with the machine connected to the network............................................................. 8-
46
8.3.7.1 Checking the correct connection polarity........................................................................... 8-
46
8.3.7.2 Measurement of motoring power and angle error correction............................................. 8-
46
8.3.7.3 Calibrating the Reverse Power Protection......................................................................... 8-
48
8.3.7.4 Checking the underecxitation protection............................................................................ 8-
48
8.3.7.5 Checking the Directional Function of the Overcurrent Time Protection............................. 8-
49
8.4 Final Preparation of the Device ......................................................................................... 8-50
9 Routine Checks and
Maintenance................................................................................................... 9-1
9.1 General ............................................................................................................................... 9-2
9.2 Routine Checks ................................................................................................................... 9-3
9.3 Maintenance ........................................................................................................................ 9-4
9.3.1 Replacing the Buffer Battery................................................................................................ 9-
4
9.4 Troubleshooting.................................................................................................................. 9-7
9.5 Repairs ............................................................................................................................... 9-9
9.5.1 Software Procedures ........................................................................................................... 9-
9
9.5.2 Hardware Procedures.......................................................................................................... 9-
9
9.6 Return............................................................................................................................... 9-13
10 Technical
Data................................................................................................................................ 10-1
10.1 General Device Data ......................................................................................................... 10-2
10.1.1 Analog Inputs.....................................................................................................................
10-2
10.1.2 Power Supply.....................................................................................................................
10-2
10.1.3 Binary Inputs and Outputs .................................................................................................
10-3
10.1.4 Communications Interfaces ...............................................................................................
10-4
10.1.5 Electrical Tests ..................................................................................................................
10-8
10.1.6 Mechanical Stress Tests....................................................................................................
10-9
10.1.7 Climatic Stress Tests....................................................................................................... 10-
10
10.1.8 Service Conditions........................................................................................................... 10-
11
10.1.9 Construction.................................................................................................................... 10-
11
10.2 Definite-Time Overcurrent Protection (ANSI 50, 67) ....................................................... 10-
12
10.3 Inverse-Time Overcurrent Protection (ANSI 51).............................................................. 10-13
10.4 Thermal Overload Protection (ANSI 49) .......................................................................... 10-
18
10.5 Unbalanced load protection (ANSI 46) ............................................................................ 10-
20
10.6 Underexcitation protection (ANSI 40) .............................................................................. 10-
22
7UM61 Manual xiii
C53000-G1176-C127-1
10.7 Reverse power protection (ANSI 32R) ............................................................................ 10-
23
10.8 Forward active power supervision (ANSI 32F) ................................................................ 10-
24
10.9 Impedance protection (ANSI 21) ..................................................................................... 10-
25
10.10 Undervoltage protection (ANSI 27).................................................................................. 10-
26
10.11 Overvoltage protection (ANSI 59).................................................................................... 10-
27
10.12 Frequency Protection (ANSI 81)...................................................................................... 10-
28
10.13 Overexcitation protection U/f> (ANSI 24) ........................................................................ 10-
29
10.14 90–%–Stator earth fault protection (ANSI 59N, 64G, 67G) ............................................. 10-
31
10.15 Sensitive earth current detection (ANSI 51GN, 64F)....................................................... 10-
32
10.16 100–%–Stator earth fault protection with 3rd harm. (ANSI 27/59TN).............................. 10-
33
10.17 Breaker Failure Protection (ANSI 50BF) ......................................................................... 10-
34
10.18 Inadvertent energization (ANSI 50/27) ............................................................................ 10-
35
10.19 Additional Functions ........................................................................................................ 10-
36
10.20 Operating ranges of the protection functions................................................................... 10-
40
10.21 Dimensions..................................................................................................................... 10-
41
A
Appendix ..........................................................................................................................................
A-1
A.1 Ordering Information and Accessories ...............................................................................A-2
A.1.1 Accessories .........................................................................................................................A-
4
A.2 General Diagrams ...............................................................................................................A-6
A.3 Connection Examples........................................................................................................A-10
A.4 Definition of the Active Power Measurement.....................................................................A-17
A.5 Overview of the masking features of the user defined informations..................................A-19
A.6 Default Settings .................................................................................................................A-23
A.6.1 Binary Inputs .....................................................................................................................A-
23
A.6.2 Binary Outputs (output relays)...........................................................................................A-
23
A.6.3 LED Indicators...................................................................................................................A-25
A.6.4 Pre–defined CFC–charts ...................................................................................................A-
26
A.7 Interoperability List ............................................................................................................A-27
A.8 Settings .............................................................................................................................A-29
A.9 List of Information..............................................................................................................A-41
A.10 Protocol-Dependent Functions..........................................................................................A-76
Index
..........................................................................................................................................Index-1
xiv 7UM61 Manual
C53000-G1176-C127-1
7UM61 Manual 1-1
C53000-G1176-C127-1
Introduction 1
The SIPROTEC® 4 7UM61 devices are introduced in this section. An overview of the
devices is presented in their application, characteristics, and scope of functions.
1.1 Overall Operation 1-2
1.2 Applications 1-5
1.3 Features 1-7
1.4 Scope of Functions 1-8
Introduction
1-2 7UM61 Manual
C53000-G1176-C127-1
1.1 Overall Operation
The SIPROTEC® 4 7UM61 is a numerical, multi-functional, protective and control device
equipped with a powerful microprocessor. All tasks, such as the acquisition of the
measured quantities, issuing of commands to circuit breakers and other primary power
system equipment, are processed in a completely digital way. Figure 1-1 illustrates
the basic structure of the 7UM61.
Analog Inputs The measuring inputs (MI) section consists of current and voltage transformers.
They
convert the signals from the measuring transducers to levels appropriate for the internal
processing of the 7UM61.
Four current inputs are available in the MI section. Three inputs are used for measuring
of the phase currents. The fourth input can be used for measuring the ground current
from a separate current transformer (INs). The latter is used in a highly sensitive
ground fault protective scheme (INs).
A voltage measuring input is provided for each phase–earth voltage. A further voltage
input (UN) may optionally be used to measure either the displacement voltage (e–n–
μC
A
D
ERROR
RUN
Output
Relays, User-
Programmable
LEDs
on the Front
Panel, User-
Programmable
Display on
the Front Panel
Front
PC Port
To
PC
System
Serial Interface
To
SCADA
IL1
IL2
IL3
INs
UL1
UL2
UL3
789
456
123
(6& (17(5 . 0 +/-
Operator
Control Panel
Uaux.
Binary Inputs,
Power Supply
Rear
Service Port
MI IA AD μC AV
Figure 1-1 Hardware Structure of the Numerical Device 7UM61 (Maximum Configuration)
Status
PC/
Modem
Programmable
UN
Introduction
7UM61 Manual 1-3
C53000-G1176-C127-1
voltage) or any other voltage UX (for overvoltage protection). The analogue signals are
then routed to the input amplifier group IA.
The analog-to-digital (AD) stage consists of memory components, a multiplexer, and
an analog-to-digital (A/D) converter. The A/D converter processes the analog signals
from the IA stage. The digital signals from the converter are input to the microcomputer
system where they are processed as numerical values in the residing algorithms.
Microcomputer
System
The actual protection and control functions of the 7UM61 are processed in the microcomputer
system (μC). In addition, the μC controls the measured quantities. Specifically,
the μC performs:
− Filtering and preparation of the measured quantities
− Continuous monitoring of the measured quantities
− Monitoring of the pickup conditions for the individual elements and functions
− Evaluation of limit values and sequences in time
− Control of signals for the logic functions
− Decision for trip commands
− Recording of messages and data for events, alarms, faults, and control actions, and
provision of their data for analysis
− Management of the operating system and the associated functions such as data recording,
real-time clock, communications, interfaces, etc.
Frequency Follow-
Up Circuit
The frequency of the measured quantities is continuously measured and used in an
integrated follow-up circuit; this ensures that the protection functions are always processed
with algorithms matched to the actual frequency. Thus, a wide frequency range
from 40 Hz to 69 Hz is specified with small frequency influence. In general, processing
is even possible from approx 11 Hz on but with respectively slower speed.
The frequency follow-up circuit can, however, operate only when at least one a.c.
measured quantity is present at one of the the analog inputs, with an amplitude of at
least 10 % of rated value (operational condition 1).
If no suitable a.c. measured values are present, or if the frequency is below 11 Hz or
above 70 Hz, the relay cannot operate (operational condition 0, refer to Section
10.20).
Binary Inputs and
Outputs
The μC obtains external information through the binary inputs such as blocking commands
for protective elements or position indications of circuit breakers. The μC issues
commands to external equipment via the output contacts. These output commands
are generally used to operate circuit breakers or other switching devices. They
can also be connected to other protective devices, annunciators, or external carrier
equipment for use in Pilot-Relaying schemes.
Front Elements Light-emitting diodes (LEDs) and a display screen (LCD) on the front panel
provide
information such as messages related to events and functional status of the 7UM61.
Integrated control and numeric keys in conjunction with the LCD facilitate local interaction
with the 7UM61. All information of the device can be accessed using the integrated
control and numeric keys. The information includes protective and control settings,
operating and fault messages, and metering values (see also Chapter 7). The
settings can be modified; the procedures are discussed in Chapter 6. In addition, control
of circuit breakers and other equipment is possible from the 7UM61 front panel.
Introduction
1-4 7UM61 Manual
C53000-G1176-C127-1
Serial Interfaces A serial operating interface on the front panel is provided for local
communications
with the 7UM61 through a personal computer. Convenient operation of all functions of
the device is possible using the SIPROTEC® 4 operating program DIGSI® 4.
A separate serial service interface is provided for remote communications via a modem,
or local communications via a substation master computer that is permanently
connected to the 7UM61. DIGSI® 4 is required.
All 7UM61 data can be transferred to a central master or main control system through
the serial system interface. Various protocols and physical arrangements are available
for this interface to suit the particular application.
Further communications protocols can be realized via additional interface modules.
Power Supply The 7UM61 can be supplied with any of the common power supply voltages from
24
VDC to 250 VDC. The device can also be supplied with 115 VAC. Momentary dips of
the supply voltage up to 50 ms are bridged by a capacitor (see Technical Data, Subsection
10.1). Voltage dips can occur, for example, if the voltage supply system (substation
battery) becomes short-circuited or experiences a severe variation in load.
Introduction
7UM61 Manual 1-5
C53000-G1176-C127-1
1.2 Applications
SIPROTEC® 7UM61 is a numerical machine protection unit from the “Numerical Protection
series 7UM6” and provides a practical combination of the most important generator
protection functions. It provides the scope of protection functions for the two typical
basic applications:
• Bus-bar connection
• Block connection
Figure 1-2 Typical basic connections
SIPROTEC® 7UM61 provides comprehensive and safe protection for smaller generators
such as emergency diesel generator sets, run of the river hydro plants, or private
power stations.
Additionally, the device forms the basis for the protection of larger generators and can
be used as back–up protection for larger power units. By adding 7UM62 (further device
of protection series 7UM6), all protection requirements encountered for the smallest
to the largest machines can be met.
Further applications are
• Back–up protection for transformer differential protection,
• The scope of functions of the relay allows to use it as network splitting device.
7UM61
G
7UM61
G
Bus–bar connection
Block connection
Introduction
1-6 7UM61 Manual
C53000-G1176-C127-1
Messages and
Measured Values;
Storage of Data for
Fault Recordings
A series of operating messages provides information about conditions in the power
system and the 7UM61 itself. Measurement quantities and values that are calculated
can be displayed locally and communicated via the serial interfaces.
Messages of the 7UM61 can be indicated by a number of programmable LEDs on the
front panel, externally processed through programmable output contacts, and communicated
via the serial interfaces (see “Communication” below).
During a network fault (fault in the power system), important events and state changes
are stored in a fault annunciation buffer. The instantaneous measured values during
the fault are also stored in the device and are subsequently available for fault analysis.
Communication Serial interfaces are available for communications with external operating,
control,
and storage systems.
A 9-pin D-subminiature female connector on the front panel is used for local communications
with a personal computer. All of the operating and evaluation processes can
be done via this operating interface using the DIGSI® 4 software. These processes
include selecting and modifying the settings, allocation of the binary inputs and outputs,
configuration of the user-definable logic functions, reading the event and fault
data, retrieving the measured values, obtaining the oscillographic fault records, reading
the states of the 7UM61 and the measurement quantities, and issuing control commands.
Further interfaces are located on the back of the 7UM61 — dependent on the version
of the device. Comprehensive communications are possible between these interfaces
and other digital equipment used for operating, control, and data storage.
The service interface can be operated through data lines or optical fibres. Also, a modem
can be connected to this port. Servicing of the substation or plant is possible from
a remote computer with DIGSI® 4.
The system interface is for central communications between the 7UM61 and a main
or master computer station. The interface can be operated through data lines or optical
fibres. Several standard protocols are available:
− IEC 60870–5–103
Integration of the devices into the automation systems SINAUT® LSA and SICAM®
also take place with this profile.
− Profibus FMS
The PROFIBUS FMS is performed in accordance with IEC 61850, is an open communications
standard that particularly has wide acceptance in process control and
automation engineering, with especially high performance. A profile has been defined
for the PROFIBUS communication that covers all of the information types required
for protective and process control engineering. The integration of the devices
into the energy automation system SICAM® can also take place with this profile.
− Profibus DP
This protocol of automation technology allows to transmit annunciations and measured
values.This protocol do not support all possibilities which are offered by
PROFIBUS FMS.
− Modbus ASCII/RTU
This protocol of automation technology allows to transmit annunciations and measured
values. This protocol do not support all possibilities which are offered by
PROFIBUS FMS.
Introduction
7UM61 Manual 1-7
C53000-G1176-C127-1
1.3 Features
• Powerful 32-bit microprocessor system.
• Complete digital processing of measured values and control, from the sampling of
the analog input quantities to the initiation of outputs for, as an example, tripping
circuit breakers or other switch-gear devices.
• Complete galvanic and reliable separation between the internal processing circuits
of the 7UM61 and the external measurement, control, and DC supply circuits because
of the design of the analog input transducers, binary inputs and outputs, and
the DC converters.
• Complete scope of functions which are normally required for the protection of smaller
and medium-sized high-voltage machines.
• Abundance of additional protective functions available, some as options.
• Continuous calculation and display of measured quantities on the front of the device.
• Simple device operation using the integrated operator panel or by means of a connected
personal computer running DIGSI® 4.
• Storage of operational data, fault data, and oscillographic fault records with SER information
to be used for analysis and troubleshooting.
• Communication with central control and data storage equipment via serial interfaces
through the choice of data cable, modem, or optical fibers, as an option.
• Constant monitoring of the measurement quantities, as well as continuous self-diagnostics
covering the hardware and software.
Introduction
1-8 7UM61 Manual
C53000-G1176-C127-1
1.4 Scope of Functions
The protection features of a SIPROTEC® 7UM61 equipped with all options are listed
below pointing out highlights of each feature. The actual features of a 7UM61 depend
on the order number.
Definite-Time-Overcurrent
Protection
• Two instantaneous (Definite-Time) overcurrent elements for phase protection;
• undervoltage seal-in for synchronous machines, the excitation voltage of which is
derived from the machine terminals;
• Optionally additional directional determination with the I>>–stage;
• Blocking capability for reverse-interlocking busbar protection.
Inverse-Time-Overcurrent
Protection
• Common ANSI and IEC time overcurrent curves are available;
• Optionally voltage controlled or voltage restraint alteration of pick–up value during
undervoltage;
• Undervoltage influence can be blocked by fuse failure monitor or via binary input,
e.g. by a voltage transformer m.c.b..
Thermal Overload
Protection
• Temperature rise of the protected equipment is calculated using a thermal homogeneous-
body model that takes into account energy entering the equipment and
energy losses. Thermal overload protection has full memory capability;
• Adjustable warning levels based on temperature rise and current magnitude;
• input of cooling medium or ambient temperature possible (with Profibus DP–interface).
Unbalanced Load
Protection
• Evalution of negative sequence component of the three phase currents;
• Alarm stage when a set unbalanced load is exceeded;
• Thermal replica for rotor temperature rise with adjustable negative sequence factor
K and adjustable time for cool down;
• high-speed trip stage for large unbalanced loads (als Kurzschlussschutz nutzbar).
Underexcitation
Protection
• Conductance measurement from positive sequence components;
• Multi-step characteristic for steady-state and dynamic stability limits;
• Detection of the excitation voltage by input of the undervoltage criterion via BI.
Reverse Power Protection
• Calculation of power from positive sequence components;
• highly sensitive active power measurement (detection of small motoring powers
even with small power factor cos ϕ , angle error correction);
• insensitive to power swings;
• Independent long–time stage and short–time stage with stop valve tripped.
Forward active
power supervision
• Calculation of forward power from positive sequence components;
Introduction
7UM61 Manual 1-9
C53000-G1176-C127-1
• Supervision of over–power (P>) and/or under–power (P<) with individually adjustable
power limits;
• Optionally high–speed or high–accuracy power measurement.
Impedance Protection
• phase selective overcurrent fault detection with undervoltage seal-in (for synchronous
machines which take their excitation voltage from the terminal voltage);
• 2 impedance zones, 1 overreach zone for zone extension (controlled via binary input),
4 time stages;
• polygonal tripping characteristics.
Undervoltage Protection
• Two undervoltage elements, measuring positive sequence voltage.
Overvoltage Protection
• Two–stage overvoltage measurement, evaluation of the highest of the three voltages;
• Optionally with phase-to-phase voltages or with phase-to-earth voltages.
Frequency
Protection
• Four elements that are independently adjustable for function - underfrequency or
overfrequency, pickup, and time delay;
• Insensitive to harmonics and abrupt phase angle changes;
• Adjustable undervoltage blocking.
Overexcitation Protection
• Calculation of the ratio U/f;
• Adjustable warning and tripping stage;
• Standard characteristic or either optional characteristic selectable for calculation of
the thermal stress.
90–%–StatorEarth
Fault Protection
• For machines in block conection and for machines directly connected to bus-bars;
• Measurement of displacement voltage at the machine neutral earthing transformers
or the measurement winding of a line connected earthing transformer or by calculation
from phase–to–earth voltages;
• Highly sensitive earth current detection, optional with or without directional determination
with zero components (I0, U0);
• With adjustable slope of directional characteristic;
• Discrimination of the earth–faulted phase.
Sensitive earth current
protection
• Two sensitive ground fault instantaneous overcurrent elements: IEE>> and IEE>;
• Pickup currents are adjustable and can be set very sensitive (as low as 1.5 mA);
• Can be used for stator earth fault or rotor earth fault detection;
• Measured circuit monitoring when used for rotor earth fault protection.
100–%–Stator Earth
Fault Protection
• Detection of the 3rd harmonic of the voltage at the starpoint or open delta winding
of an earthing transformer;
Introduction
1-10 7UM61 Manual
C53000-G1176-C127-1
• In addition to the 90%–stator earth fault protection there is a protection of the entire
stator winding (protective range 100 %).
Breaker Failure
Protection
• Breaker failure condition determined by current flow after a trip signal has been issued.
As an option, the breaker position indication (binary input) can be evaluated;
• Breaker failure protection initiated by the tripping of any integrated protective element
that trips the circuit breaker (internal start);
• Initiation possible through a binary input from an external protective device (external
start);
Inadvertent energization
• The inadvertent accidental energizing protection serves to limit damages by accidental
connection of the standing generator by a fast actuation of the mains breaker.
• Detection of the instantaneous values of the phase currents;
• Released by operational condition check, undervoltage supervision, and fuse failure
monitor.
Phase Rotation • Selectable L1, L2, L3 or L1, L3, L2 with a setting (static) or binary input
(dynamic).
User-defined
Functions
• Internal and external signals can be logically combined to establish user-defined
logic functions;
• All common logic functions are available for programming (AND, OR,NOT, Exclusive
OR, etc.);
• Time delays and limit value inquiries are available;
• Processing of measured values, including zero suppression, adding a knee characteristic
for a transducer input, and live-zero monitoring.
Monitoring
Functions
• Availability of the 7UM61 is greatly increased because of self-monitoring of the internal
measurement circuits, power supply, hardware, and software;
• Current transformer and voltage transformer secondary circuits are monitored using
summation and symmetry check techniques;
• Trip circuit monitoring;
• Phase rotation.
Further Functions • Battery-buffered real time clock that can be synchronized with an IRIG-B
(or
DCF77) signal, binary input signal, or system interface command;
• Recording and saving of fault data in chronological order for the last eight faults;
• Recording, saving and transfer of waveform capture;
• Recording of circuit breaker statistics including the number of trip signals sent and
the accumulated, interrupted currents of each pole of the circuit breaker;
• Tracking of operating hours (time when load is supplied) of the equipment being
protected;
• Commissioning aids such as connection check, direction determination, and the
display of test recordings.
n
7UM61 Manual 2-1
C53000-G1176-C127-1
Hardware and Connections 2
An overview of the hardware of the 7UM61 and detailed information regarding connections
to the device are provided in this section.
The options for panel mounting and cubicle mounting are described. Device construction
is presented. The options for terminal connections and communication interfaces
are covered.
Data are given for wire connections and communication connections. Information on
accessories and tools is given.
2.1 Version of 7UM61 for Panel Flush-Mounting / Cubicle Mounting 2-2
2.2 Version of 7UM61 for Panel Surface-Mounting 2-15
Hardware and Connections
2-2 7UM61 Manual
C53000-G1176-C127-1
2.1 Version of 7UM61 for Panel Flush-Mounting / Cubicle
Mounting
The numerical, multi-functional SIPROTEC® 4 7UM61 for panel flush-mounting or cubicle
mounting is a sealed device in a 7XP20. 2 housing sizes are available, namely
1/3 (7UM611) and 1/2 (7UM612) (of 19 inch). Two different general types of terminals
are available, threaded terminals and plug-in terminals. The terminals provided depend
on the order number of the device.
2.1.1 Construction
The major components of a 7UM61 are the front panel, the case, and the rear panel.
The terminals for connections to external equipment are located on the rear panel,
which is bolted to the case. Inside the device are two printed circuit boards that have
the rear serial interface modules attached. The boards are connected together via a
ribbon-cable that has plug connectors. The boards are connected to the terminals and
supported in guide rails.
The front panel is removable. The screws for removing the component are located behind
the four covers at the corners. The front panel has a covered keypad with operating
and display elements necessary for equipment operation. All connections for
these elements are combined into an adapter module on the front panel that is linked
via a ribbon-cable with plug connectors to the internal processor board (CPU).
The nameplate sticker, showing important information such as power supply rating,
nominal current rating, and ordering number, is located on the top of the case and the
interior of the front panel.
View of Front Panel
(Housing Size 1/3)
Figure 2-1 Front View of a 7UM611, housing size 1/3, for Panel Flush-mounting / Cubicle
Mounting
SIEMENS SIPROTEC
12
6
3
0 +/-
45
789
RUN ERROR 7UM611
MENU
LED ESC ENTER
F4
F1
F2
F3
Event Log
Operation.
MAIN MENU 01 / 04
Annunciation 1
Measurement 2
1)
2)
4)
5)
7) 6)
10)
9)
8)
3)
11) 11)
11) 11)
Trip Log
Min/Max
Device faulty
Pickup GND
Pickup L3
Pickup L2
Pickup L1
Trip
Pri
Pickup
Reset
1)
3)
4)
5)
8)
9)
10)
2)
11)
11)
11)
11)
7)
6)
Pri
R
Q
1
2
3
4
5
6
7
8
9
10
11
12
P-Slave
P-Master
RS232
RS485
11)
11)
11)
11)
1)
2)
4)
5)
3)
6)
7)
8)
9)
10)
Trip Log
Operation.
Pri
Pickup GND
Device faulty
Pickup L1
L2
Pickup
Initial Inspections 3
This section describes the first steps that should be taken upon receiving the
SIPROTEC® 4 7UM61.
Unpacking and packing is explained.
Please note the SIPROTEC® 4 family of devices is described in general in this section,
and the examples shown may differ in detail from a specific device. Also, depending
on the version of the specific device, some of the functions discussed may not be
available.
Visual and electrical checks that are appropriate for initial inspection are discussed.
The electrical tests include navigating through the operating menus of the device using
the operator control panel on the front of the device, and the operator control windows
in DIGSI® 4. For personnel inexperienced with the 7UM61, these checks also
provide a quick and simple method for understanding the operation of the control panel
and DIGSI® 4. The electrical tests can be done without measuring quantities being
applied.
Observations relevant to long-term storage of the device are noted.
3.1 Unpacking and Packing 3-2
3.2 Inspections Upon Receipt 3-3
3.3 User Interface 3-4
3.4 Storage 3-12
Initial Inspections
3-2 7UM61 Manual
C53000-G1176-C127-1
3.1 Unpacking and Packing
The 7UM61 is packaged at the factory to meet the requirements of IEC 60255–21.
Unpacking and packing must be done with normal care, without using force, and with
appropriate tools. Visually check the device immediately upon arrival for correct mechanical
condition.
Please observe also the brief reference booklet and all notes and hints that are enclosed
in the packaging.
The shipping packaging can be reused in the same manner for further shipment. Storage
packaging alone, for individual devices, is not sufficient for shipping. If other packaging
is used, shock requirements under IEC 60255–21–1 Class 2 and IEC 60255–
21–2 Class 1 must be met.
The device should be in the final operating area for a minimum of two hours before the
power source is first applied. This time allows the device to attain temperature equilibrium,
and dampness and condensation to be avoided.
Initial Inspections
7UM61 Manual 3-3
C53000-G1176-C127-1
3.2 Inspections Upon Receipt
3.2.1 Inspection of Features and Ratings
Ordering Number Verify that the 7UM61 has the expected features by checking the complete
ordering
number with the ordering number codes given in Sub-section A.1 of the Appendix.
Also check that the required and expected accessories are included with the device.
The ordering number of the device is on the nameplate sticker attached to the top of
the case or housing. The nameplate also indicates the current, voltage, and power
supply ratings of the device. A verification that these ratings are the expected values
is especially important. The jumpers for the control voltage of the binary inputs are set
at the factory for a DC control voltage equal to the DC voltage rating of the power supply.
The jumpers can be changed if a different control voltage is to be used.
3.2.2 Electrical Check
Operating conditions that meet VDE 0100 and VDE 0105 Part 1, or national and international
standards, are to be observed.
Before applying power supply voltage or measuring quantities for the first time, be
sure the device has been in the operating area for at least two hours. This time period
allows the device to attain temperature equilibrium, and prevents dampness and condensation
from occurring.
Power-Up Ensuring safe grounding and applying power supply voltage are sufficient for a first
electrical inspection of the device.
o Connect the ground of the device to the ground of the location. The ground of a 7UM61
designed for flush-mounting is on the back panel. The ground of a device designed for
surface-mounting is on the terminal with the grounding symbol.
o With the protective switches (e.g. test switches, fuses, or miniature circuit breakers)
for the power supply open, prepare the connections to the power supply. Verify that
the power supply voltage has the correct magnitude. Check polarity connections to the
device inputs. Follow the appropriate connection diagram in the Appendix A.2.
o Close the protective switches to apply the power supply.
o The green “RUN” LED on the front panel must light after no more than 0.5 second, and
the red “ERROR” LED must go out after no more than 10 seconds.
o After no more than 15 seconds, the start-up messages must vanish from the display
(in which the complete ordering number, the version of firmware implemented, and the
factory number are shown) and the default display must appear. Depending on the
masking of the LEDs, some indicators may light up during and after power-up.
Warning!
The following inspection steps are done in the presence of dangerous voltages. Only
appropriately qualified personnel familiar with and adhering to safety requirements
and precautionary measures shall perform these steps.
Initial Inspections
3-4 7UM61 Manual
C53000-G1176-C127-1
3.3 User Interface
3.3.1 Navigating through the Operating Menus Using the Operator Control
Panel
Operator Control
Panel
The device has a hierarchically structured operating tree, within which movements
and actions are made using the , , , keys and the , , and keys
on the front panel.
The brief discussions below illustrate the navigation techniques using the integrated
operations in the operator control panel. Some typical operations are covered. For
easier understanding, the accompanying figures show the entire contents of the
menus, while only a limited number of lines can be seen in the display at any time.
Ordering Number /
Version Reading
To view the complete ordering number of the device, the version of firmware implemented,
and the serial number:
q When the device is ready for operation, first press the key. The 0$,1_0(18 appears.
q Using the key, select the menu item 6HWWLQJV, and move to the device settings
using the key. The 6(77,1*6 menu appears, as shown in Figure 3-1.
q Using the key, select the menu item 6HWXS_([WUDV and switch to the selection
6(783_(;75$6 using the key. See Figure 3-2.
Figure 3-1 Sub-menu 6(77,1*6
q Using the key, select the menu 0/)%_9HUVLRQ and view the selection 0/)%_
9(56,21 using the key.
The device-specific data appear in two or three locations. Press the key as necessary
to view all of the data:
MENU ENTER ESC
MENU
_0_$_,_1___0_(_1_8________________________
_$QQXQFLDWLRQ__²!____
_0HDVXUHPHQW___²!____
_&RQWURO_______²!____
!6HWWLQJV______²!____
_7HVW_'LDJQRVH_²!____
_6_(_7_7_,_1_*_6__________________________
_'HYLFH_&RQILJ__²!___
_0DVNLQJ__,_2___²!___
_3_6\VWHP_'DWD__²!___
_*URXS_$________²!___
_*URXS_%________²!___
_*URXS_&________²!___
_*URXS_'________²!___
_&KDQJH_*URXS___²!___
_2VF_)DXOW_5HF__²!___
!6HWXS_([WUDV___²!___
_'HYLFH_________²!___
Initial Inspections
7UM61 Manual 3-5
C53000-G1176-C127-1
Figure 3-2 Display of Device-specific Data - Examples
Measurement
Viewing
To view the measured values:
q If the main menu is not shown, press the key. The 0$,1_0(18 appears.
q Using the key, select the menu item 0HDVXUHPHQW, and move to the measurement
values using the key. The 0($685(0(17 menu appears.
q Using the key, select the menu item 2SHUDWLRQ__VHF (operating measured
values, secondary), and switch to the 23(5$7,21__6(& menu using the key.
q Using the and keys, all operating measured values can be viewed.
Since no AC voltages or currents are present at this time, all operating measured values
show near zero. Deviations of the last digit are insignificant.
Event Messages
Reading
Reading the event messages is described to serve as an additional example.
q If the main menu is not shown, press the key. The 0$,1_0(18 appears.
q Using the key, select the menu item $QQXQFLDWLRQ, and switch to the annunciation
using the key. The $1181&,$7,21 menu appears.
q Using the key, select the menu item (YHQW_/RJ, and move to the (9(17_/2*
menu using the key.
The last quantity in the upper right corner of the display indicates the number of event
messages stored in memory. The number before the slash indicates the message
presently being displayed. Upon entering the menu, the latest (newest) message is
shown. The date and time of the event are shown in the display line above the message.
q Use the key to read other event messages.
q Press the key; all LEDs should illuminate. Press the key. The newest message
in the event log should be “5HVHW_/('”, and the number of messages in
memory should increase by one (maximum of 200).
To return to the main menu, press the key once, or repeatedly press the key
or the key.
Display Contrast
Setting
If the image in the integrated LCD does not have satisfactory contrast, adjustments
can be made. A stronger contrast serves, among other purposes, to improve the readability
of the image from an angle. With increasing numbers, the contrast is increased
and the picture gets darker. If the contrast is too weak or too strong, there is a risk that
0/)%_9(56,21_________
0/)%___80____²_($__
_&$_
%)²1U_____________
_6_(_7_8_3___(_;_7_5_$_6__________________
_'DWH_7LPH______²!___
_&ORFN_6HWXS____²!___
_6HULDO_3RUWV___²!___
_'HYLFH_,'______²!___
!0/)%_9HUVLRQ___²!___
_&RQWUDVW_______²!___
0/)%_9(56,21_________
)LUPZDUH_____________
%RRWV\VWHP___________
MENU
MENU
LED
MENU ESC
Initial Inspections
3-6 7UM61 Manual
C53000-G1176-C127-1
the display will be unreadable and that no operation will be possible using the integrated
operator control panel. Therefore, the preset contrast value should only be
changed in small steps (1 or 2 levels).
q When the device is ready for operation, first press the key. The 0$,1_0(18 appears.
q Using the key, select the menu item 6HWWLQJV, and switch to the settings using
the key. The 6(77,1*6 menu appears.
q Using the key, select the menu item 6HWXS_([WUDV and switch to the selection
6(783_(;75$6 using the key. See Figure 3-3.
q Using the key, select the menu item &RQWUDVW.
q If a change of the contrast of the integrated LCD is desired, press the key. The
existing setting appears in a frame with a blinking cursor.
q Overwrite the present setting with the desired setting using the numerical keys. The
setting range is [11 to 22].
q Confirm the change with the key, or cancel the change with the key.
Exit the menu using the key, or return to the main menu using the key.
Figure 3-3 Operating Sub-menu for Adjusting the Display Contrast
MENU
ENTER
ENTER ESC
ESC MENU
ENTER 6(783_(;____________
____________________
_0/)%_9H____Q__²!___
_&RQWUDVW______²!___
__
_6_(_7_8_3___(_;_7_5_$_6_______________
_'DWH_7LPH_____²!___
_&ORFN_6HWXS___²!___
_6HULDO_3RUWV__²!___
_'HYLFH_,'_____²!___
_0/)%_9HUVLRQ__²!___
!&RQWUDVW______²!___
Initial Inspections
7UM61 Manual 3-7
C53000-G1176-C127-1
3.3.2 Operation Using DIGSI® 4
DIGSI® 4 Operator
Control Panel
DIGSI® 4 has the typical PC application Windows operating environment to guide the
user. The software has a modern, intuitive, user-interface. Further details are found in
Section 4, as well as in the DIGSI® 4 handbook “Device Operation”.
Some applications of DIGSI® 4 are described below. They include viewing the measurement
values, reading messages in the Event Log, and setting the clock. The handling
of the operator control windows of DIGSI® 4 can be learned quickly by following
the simple examples as descibed below. To perform the steps in the examples, first
connect the SIPROTEC® 4 device to the PC and match the DIGSI® 4 interface data
with the equipment. To accomplish this task:
q Establish a physical connection between a serial interface of the PC and the operating
serial interface of the device on the front panel.
q Open the DIGSI® 4 application in the PC.
q Generate a new project by clicking on )LOH → 1HZ in the DIGSI® 4–Manager menu
bar.
Figure 3-4 Dialog box to Open a New Project
q Enter a name for the new project in the 1DPH entry field (e.g. test 1) and close the
box with 2..
q Select )ROGHU by clicking on the item in the newly opened window. Then click on
',*6,_!_'HYLFH__3OXJ_ _3OD\_. The Plug & Play dialog box opens, as shown
in Figure 3-6.
Initial Inspections
3-8 7UM61 Manual
C53000-G1176-C127-1
Figure 3-5 Menu Device with option 'HYLFH_!_',*6,_3OXJ_ _3OD\)
q Enter the designation of the PC serial interface (COM 1,2, 3, or 4) and select in the
popup list under )UDPH the transfer format, to be used in making the connection.
q Click on 2.. DIGSI® 4 automatically determines the type of device present and
reads the settings needed for communication (transfer format, transfer speed)
through the interface.
Figure 3-6 Plug & Play Dialog Box for Communication between Device and PC
A direct connection is then established (on-line), the data are exchanged between the
PC and the device, and the initial window for DIGSI® 4 opens, as shown on Figure 3-7.
q By double clicking 2QOLQH in the navigation window (left window), the structure
opens (directory tree).
q By clicking on one of the menu items offered there, the associated contents become
visible in the right window.
Initial Inspections
7UM61 Manual 3-9
C53000-G1176-C127-1
Figure 3-7 DIGSI® 4 — Online Initial Window - Example
Measurement
Viewing
As an example the procedure for viewing the measured values is described.
q Double click on 0HDVXUHPHQW in the navigation window (left).
q Double click on the subdirectory 6HFRQGDU\_9DOXHV in the navigation window.
q Click on 2SHUDWLRQDO_YDOXHV__VHFRQGDU\.
q Date and time are shown in the data window (right), as illustrated in Figure 3-8.
q Double click on this entry in the data window.
Figure 3-8 DIGSI® 4 — Viewing the Secondary Operating Measured Values - Example
A table of the secondary operating measured values appears, as shown in Figure 3-9.
Since no AC currents or voltages are present, all measured values are close to zero.
Deviations of the last digit are insignificant. The measured values are automatically
updated.
In the same manner, other measured and counter values can be viewed.
Initial Inspections
3-10 7UM61 Manual
C53000-G1176-C127-1
Figure 3-9 DIGSI® 4 — Table of Secondary Operating Measured Values – Example
Event Messages
Reading
The readout of operating messages is described and serves as an additional example.
q Double click on $QQXQFLDWLRQV in the navigation window.
q Click on (YHQW_/RJ in the data window (right side).
The present date and time are shown in the data window.
q Double click on this entry in the data window.
A table of the accumulated event messages is displayed. See Figure 3-10. The number
designation for an event is provided with a description of the event. The corresponding
cause, value (ON or OFF), and date and time of the event are given. The
events are listed chronologically; the newest message is shown first.
Figure 3-10 DIGSI® 4 — Event Log Messages Window – Example
q Press the key on the device; all LEDs should light while the key is pressed.
q The message “Reset LED” appears as the newest message as soon as the window
is updated. The window is updated by clicking on 9LHZ in the menu bar, and then
on 5HIUHVK. Pressing the F5 function key on the keyboard also updates the window.
The operating messages can be saved in DIGSI® 4, and also deleted from the device’s
memory. For detailed information refer to Section 7.1.1).
LED
Initial Inspections
7UM61 Manual 3-11
C53000-G1176-C127-1
Date and Time
Setting
To enter the date and time:
q Click on 'HYLFH in the menu bar. See Figure 3-11.
q Select 6HW_FORFN.
Figure 3-11 DIGSI® 4 — Selection of the Option 6HW_&ORFN_
The dialog field 6HW_FORFN_ _GDWH_LQ_GHYLFH opens. The field shows the
present
date and the approximate present time according to the device. The day of the week
is automatically derived from the date and cannot be edited.
• Edit the input fields 'DWH and 7LPH. The format depends on your regional settings
of the PC. See Figure 3-12.
Date: mm/dd/yyyy or dd.mm.yyyyy
Time: hh.mm.ss
Click 2. to download the entered values to the device. The former values are
changed and the dialog field is closed.
Figure 3-12 DIGSI® 4 — Dialog Field: 6HW_FORFN_ _GDWH_LQ_GHYLFH
Initial Inspections
3-12 7UM61 Manual
C53000-G1176-C127-1
3.4 Storage
If the device is to be stored, note:
SIPROTEC® 4 devices and associated assemblies should be stored in a dry and clean
place, with a maximum temperature range of [–12 °F to 131 °F], or [–25 °C to +55 °C].
See also Section 10.1 under Technical Data.
To avoid premature aging of the electrolyte capacitors in the power supply, a temperature
range of [50 °F to 95 °F], or [+10 °C to +35 °C], is recommended for storage.
The relative humidity must not lead to condensation or ice buildup.
After extended storage, the power supply of the device should be energized, approximately
every two years, for one or two days to regenerate the electrolytic capacitors
in the power supply. This procedure should also be done prior to the device being put
in-service. Under extreme climatic conditions (tropics), preheating is achieved at the
same time, and condensation is prevented.
After long storage, power should not be applied until the device has been in the operating
area for a minimum of two hours. This time period allows the device to attain temperature
equilibrium, and prevents dampness and condensation from occurring.
n
7UM61 Manual 4-1
C53000-G1176-C127-1
SIPROTEC 4 Devices 4
This section provides an overview of the family of SIPROTEC® 4 devices and the integration
of the devices into process control systems. Principle procedures are provided
for setting the devices, controlling primary equipment with the devices, and performing
general operations with the devices.
Please note the SIPROTEC® 4 family of devices is described in general in this section,
and the examples shown may differ in detail from a specific device. Also, depending
on the version of the specific device, some of the functions discussed may not be
available.
Details about the extent of the functions of the devices, the individual settings, and the
representation structure of the system data are found in the following sections and the
DIGSI® 4 instruction book.
4.1 General 4-2
4.2 Operator Control Facilities 4-5
4.3 Information Retrieval 4-8
4.4 Control 4-14
4.5 Manual Overwrite / Tagging 4-16
4.6 General Setting Procedure 4-17
4.7 Device Configuration 4-20
4.8 Configuration of Inputs and Outputs (Configuration Matrix) 4-21
4.9 Programmable Logic CFC 4-24
4.10 Power System Data 4-26
4.11 Setting Groups 4-27
4.12 General Device Settings 4-29
4.13 Time Synchronization 4-30
4.14 Serial Interfaces 4-31
4.15 Passwords 4-33
SIPROTEC 4 Devices
4-2 7UM61 Manual
C53000-G1176-C127-1
4.1 General
The SIPROTEC® 4 family is an innovative product series of numerical protective and
control devices with open communication interfaces for remote control and remote
setting, ergonomically designed control panels, and highly flexible functionality.
4.1.1 Protection and Control
The devices utilize numerical measuring techniques. Complete numerical signal processing
offers high measurement accuracy and long-term consistency, as well as reliable
handling of harmonics and transients. Digital filtering techniques and dynamic
stabilization of measured values ensure the highest security in establishing the devices’
correct responses. Device errors are recognized and quickly annunciated by integrated
self-monitoring routines. Failure of protection during a fault is therefore almost
entirely prevented.
The user can choose devices with separate protective and process control functions,
or select a solution that implements both requirements.
The following solutions are available:
q Protection and control in separate devices,
q Protective devices that provide the capability of control of a circuit breaker or primary
switching equipment through a communication interface,
q Devices with combined features that, in addition to protective functions, offer on-site
operation for several circuit breakers and primary switching equipment and extensive
process control functions.
SIPROTEC 4 Devices
7UM61 Manual 4-3
C53000-G1176-C127-1
4.1.2 Communication
SIPROTEC® 4 devices are completely suited for the requirements of modern communication
technology. They have interfaces that allow for integration into higher-level
control centers, and user friendly operation through an on-site PC or via a modem connection.
Simple, comfortable device setup and operation are provided.
SIPROTEC® 4 devices support the widespread, internationally accepted communication
standards
q PROFIBUS FMS,
q PROFIBUS DP,
q IEC 60870-5-103
q DNP3.0 Level 2 and
q MODBUS ASCII/RTU
Figure 4-1 Integration of Field Devices in the SICAM Station Control System, examples
Operation and Observation
SICAM WinCC
DIGSI 4
SICAM SC
To SCADA
IEC60870-5-101
IEC60870-5-103
Profibus FMS
Time Synchronization
DCF, GPS
Field Devices
Profibus DP, DNP3.0
SIPROTEC 4 Devices
4-4 7UM61 Manual
C53000-G1176-C127-1
Refer to the sample configurations in Figure 4-1. In the case when data is transmitted
from the field devices it can be processed in the sub-station control device SICAM SC,
displayed at the operating and observation station SICAM WinCC, and transferred by
the remote terminal unit interfaces (via the network channels) to SCADA.
In the case when commands are sent to the devices, equally flexible processing is
possible; that is, substation control operations can be initiated from the network control
centers (SCADA), as well as from the operation and observation unit of the substation
control system.
The protocol PROFIBUS DP enables the uncomplicated integration of SIPROTEC®
devices into PLC-based process control systems (e.g. SIMATIC S5/S7). The protocols
DNP3.0 and MODBUS ASCII/RTU allow the integration into a large number of process
control systems and control systems of different manufacturers.
4.1.3 Settings
The devices in the SIPROTEC® 4 family are delivered with factory default settings. After
settings are made for specific applications, the devices are suitable for direct use
in power systems.
The windows-based DIGSI® 4 software program offers an application-oriented interface
with thorough guidance for quick and simple setting of the devices.
DIGSI® 4 is installed on a normal PC. For local use, the PC is connected to the operating
serial interface on the front panel of the device.
4.1.4 Operations
All on-site operations of a SIPROTEC® 4 device can be done with DIGSI® 4. Examples
of operations are breaker control, retrieval of information, or changing of setting
groups. All of the operations can also be performed using the HMI on the front of the
SIPROTEC® 4 device.
4.1.5 Waveform Capture
DIGSI® 4 can also be used to retrieve waveform data and SER information captured
by the SIPROTEC® 4 device. The DIGRA® 4 software program can then be used to
provide several different graphical representations of the captured signals. DIGRA® 4
also calculates additional values on the basis of the captured signals. The program
presents the data in analogue curves with time base, vector diagrams, circle diagrams,
and harmonic charts.
Note:
All SIPROTEC® 4 devices also operate with the proven star coupler (e.g. 7XV5). Thus,
for simple applications, the user can retrieve all information from the office or while on
the road.
SIPROTEC 4 Devices
7UM61 Manual 4-5
C53000-G1176-C127-1
4.2 Operator Control Facilities
4.2.1 Operating Panel On Device
The operating panels of SIPROTEC® 4 devices are ergonomically designed and easy
to read. The operating panels allow on-site control operations to be done, individual
settings to be entered, and all information required for operations to be displayed.
The operating panel contains either a full graphical display or a 4-line display, depending
on the specific device of the SIPROTEC® 4 family.
HMI with Four-Line
Display
Figure 4-2 SIPROTEC® 4 Device, HMI with Four-line Display, example
The functions of the operating and display elements are described below.
Note:
Refer to Section 2 to determine the type of HMI for the specific SIPROTEC®4 device.
SIEMENS SIPROTEC
12
6
3
0 +/-
45
789
RUN ERROR 7SA522
MENU
LED ESC ENTER
F4
F1
F2
F3
Event Log
Operation.
MAIN MENU 01/05
Annunciation 1
Measurement 2
SIEMENS SIPROTEC
12
6
3
0 +/-
45
789
RUN ERROR 7SA522
MENU
LED ESC ENTER
F4
F1
F2
F3
Meldungen
Meßwerte
MAIN MENU 01/04
Annunciation 1
Measurement 2
SIEMENS SIPROTEC
12
6
3
0 +/-
45
789
Trip
Pickup A
Pickup B
Pickup C
Pickup GND
Device faulty
RUN ERROR 7SJ61/62
MENU
LED ESC ENTER
F4
F1
F2
F3
Event Log
Operation.
MAIN MENU 01/05
Annunciation 1
Measuremen 2
Trip Log
Pri
Pri
SIPROTEC 4 Devices
4-6 7UM61 Manual
C53000-G1176-C127-1
Display Process and device information are displayed in the LCD. Commonly displayed
information
includes measured values, counter values, binary information regarding the
condition of the device, protection information, general messages, and alarms.
The light for the display is normally off. The light automatically turns on whenever a
key is pressed on the HMI. If no input from the HMI occurs for ten minutes, then the
light turns off again. The light can be controlled via a binary input that is configured
(programmed) for this purpose.
Keys The keys have various functions.
q Navigation through the operating menus of the device are accomplished with the
, , , keys.
q The main menu is opened with the key.
q Changes are cancelled or confirmed with the and keys, respectively.
q Numerical values are entered with the to keys, the key for a decimal
point, and the key for a negative sign. If a value of infinity (∞) is desired, press
the decimal point key twice; ∞ appears in the display.
q The to keys are programmable. The keys are typically used to execute commonly
performed actions. Labeling strips are provided.
q Latched LEDs and binary outputs are reset and the group of LEDs are tested with
the key (dual purpose).
LEDs q “RUN” and “ERROR” LEDs indicate the condition of the device.
q All other LEDs are freely configured to indicate process information, status, etc. Labeling
strips are provided.
Operating Serial
Interface
Local communication with the device is established through the front operating serial
interface with a PC running DIGSI® 4. The interface on the device is a 9-pin, female,
D-subminiature port.
MENU
ESC ENTER
09.
+/–
F1 F4
LED
SIPROTEC 4 Devices
7UM61 Manual 4-7
C53000-G1176-C127-1
4.2.2 DIGSI® 4 Tool
DIGSI® 4 uses the familiar Windows operating environment.
User Guide In DIGSI® 4 only the settings that are available within a specific device are shown in
the specific windows. If a protective feature is changed from disabled to enabled in the
Device Configuration, then the settings relevant to that feature become available.
Entering settings for SIPROTEC® 4 devices is simplified due to many types of assistance
offered, such as context menus, pop-up lists for the selection of available options,
and specific limits for the entry of numerical values.
Masking Inputs
and Outputs
(Configuration
Matrix)
A configuration matrix is used to mask the binary inputs, binary outputs, and LEDs.
Information to be saved in the various buffers and transmitted via the system interface
is also selected in this matrix. The setting options are presented in an easy-to-read
tabular format. Parts of the matrix can be minimized or expanded as desired to simplify
the displayed sections, and therefore the setting process. Filter functions can reduce
the size of the matrix to display only relevant information.
Passwords Password entry is required for tasks such as changing settings, executing control
commands, or exercising the test and diagnostics features. The passwords protect
against unauthorized access to these critical tasks.
Commissioning
Aids
DIGSI® 4 simplifies commissioning with test functions for the binary inputs, outputs
and LEDs. Control of primary equipment can be done. The measured values of the
device can be viewed with the program. Waveform capture can be triggered with
DIGSI® 4.
Help System The help system clarifies the individual functions and settings, and provides
additional
support.
Note:
Detailed information about DIGSI® 4 can be found in the DIGSI® 4 instruction book,
order number E50417-H1176-C097.
SIPROTEC 4 Devices
4-8 7UM61 Manual
C53000-G1176-C127-1
4.3 Information Retrieval
A SIPROTEC® 4 device has an abundance of information that can be used to obtain
an overview of the present and past operating conditions of the device and the portion
of the power system being protected or controlled by the device. The information is
represented in separate groups:
q Annunciation,
q Measurements,
q Waveform capture.
Remote If the device is integrated into a process control system, then information transfer can
take place, via a connection to the system interface of the SIPROTEC® 4 device, to:
q SCADA, or
q substation controller device, e.g. SICAM SC
Local On site, the HMI of the SIPROTEC® 4 device can be used to retrieve information.
DIGSI® 4 Information retrieval is simple and fast when DIGSI® 4 is used. For local use, connect
a PC to the operating serial interface at the front of the SIPROTEC® 4 device. For remote
retrieval of information, communication occurs via a modem connected to the
service serial interface. DIGSI® 4 must operate in the Online mode to obtain information
from the device.
SIPROTEC 4 Devices
7UM61 Manual 4-9
C53000-G1176-C127-1
4.3.1 Annunciations
The scope of the indication (messages) that are given under Annunciation is automatically
determined when settings for the basis configuration of functions are applied to
the SIPROTEC® 4 device.
The messages are divided into the following categories, and displayed using DIGSI® 4
or the HMI of the device:
q Event Log: Operational messages independent of network faults, e.g. messages
about control operations or monitoring functions;
q Trip Log: Fault messages;
q Sensitive Ground Fault Log: Ground fault messages for devices with sensitive
ground fault detection;
q General Interrogation: Display of present condition messages;
q Spontaneous Annunciation: Continuous display of important messages from the
device; e.g., after faults, control operations, etc. This feature is very helpful during
commissioning.
k451.gif
Figure 4-8 DIGRA® 4 Graphical Representations of the Waveform Data, View Examples
Details can be found in the DIGSI® 4 instruction book, order number E50417-H1176-
C097, and the DIGRA® 4 instruction book, order number E50417-H1176-C070.
SIPROTEC 4 Devices
4-14 7UM61 Manual
C53000-G1176-C127-1
4.4 Control
The multiple application possibilities for SIPROTEC® 4 devices require an equally
flexible concept for command editing and control.
Remote If the device is integrated into a control system, then command outputs can be remotely
controlled via the system interface using telegrams from
q SCADA or
q substation controller devices such as SICAM SC.
Local On-site, the SIPROTEC® 4 device offers the possibility to control a circuit breaker or
primary switching equipment using the HMI.
For devices with a four-line display, control operations are carried out using:
• 0DLQ_PHQX → &RQWURO → %UHDNHU_6ZLWFK → &RQWURO → Equipment
and intended
direction 21 or 2)) (Figure 4-9), or
• The Function Keys F1 to F4.
The functionality of these keys is programmable using CFC. Their factory default function
does not do any breaker control.
Figure 4-9 On-site Control Using the HMI
_0_$_,_1___0_(_1_8________________________
_0HDVXUHPHQW____²!___
!&RQWURO________²!___ _&_2_1_7_5_2_/__________________________
!%UHDNHU_6ZLWFK²!___
!7DJJLQJ_______²!___
_&_2_1_7_5_2_/__________________________
!%UHDNHU_6ZLWFK²!___
!7DJJLQJ_______²!___
%5($.(5_6:,7&+______
____________________
!'LVSOD\_______²!___
!&RQWURO_______²!___
SIPROTEC 4 Devices
7UM61 Manual 4-15
C53000-G1176-C127-1
The status of a primary switch can be read out on the display using %5($.(5_6:,7&+
→ 'LVSOD\ (Figure 4-10).
Figure 4-10 Determining Primary Switch Status using the HMI
DIGSI® 4 Control operations can be carried out using the DIGSI® 4 Tool. Connect a PC to the
PC-interface at front of the device on site, or communicate with the SIPROTEC® device
using a modem and the service interface.
DIGSI® 4 must operate in the On-line mode for this function.
• Select &RQWURO in the Navigation window and double click on %UHDNHU___
6ZLWFKHV in the data window.
In the dialog window that follows, all relevant primary control equipment is displayed
in a table with the present status.
• Enter the intended device position in the Scheduled column. Answer the question
with <HV.
The password is requested, the interlocking conditions are checked, and the command
is issued.
CFC Using the graphically supported design tool CFC for logic functions in DIGSI® 4, information
can be logically combined. Command outputs can be derived from the output
of logic functions. The link of the output of the CFC functions to the respective device
outputs is determined in the configuration matrix.
Password Only authorized personnel shall perform control operations. Control operations are
protected by passwords.
Interlocking Command outputs are subject to interlocking checks, which can be configured
individually
and graphically using the CFC logic too. Standard interlockings, such as ground
switch closed status indication are already contained in the basic settings of the device
when delivered from the factory.
Command Processing
Times
Details about the command output time, checkback indication monitoring time, etc.,
are entered within the framework of the settings.
Event Recording All control operations are recorded in the message list with date and time.
_'_,_6_3_/_$_<__________________________
!__%UHDNHU______23(1
___'LVF_6ZLW____&/26
_%_5_(_$_._(_5___6_:_,_7_&_+______________
!'LVSOD\________²!___
!&RQWURO________²!___
Note:
The control option of DIGSI® 4 is typically used during commissioning, and for test and
diagnostic purposes.
SIPROTEC 4 Devices
4-16 7UM61 Manual
C53000-G1176-C127-1
4.5 Manual Overwrite / Tagging
Manual Overwrite If the breaker/switch position is not available, the status of the switchgear can
be manually
set to the actual present position using the HMI: 0DLQ_0HQX → &RQWURO →
%UHDNHU_6ZLWFK → 0DQ__2YHUZULWH. The simulated breaker/switch position is
used for interlocking checks, and for automatically initiated control operations.
Set Status For convenience during commissioning or at other times, decoupling of the
switchgear
and the protective device may be desired for a short period, without disconnecting the
wires. This function is activated using the HMI: 0DLQ_0HQX → &RQWURO →
%UHDNHU_
6ZLWFK → 6HW_6WDWXV.
Tagging To identify unusual operating conditions in the power system, tagging can be done.
The tagging can, for example, be entered as additional operating conditions in interlocking
checks, which are set up with CFC. Tagging is configured in the same way as
for operating devices.
• The status of the tagging is displayed on the HMI, 0DLQ_0HQX → &RQWURO → 7DJ_
JLQJ → 'LVSOD\ (Figure 4-11),
or changed using
• 0DLQ_0HQX → &RQWURO → 7DJJLQJ → 6HW.
Figure 4-11 Tagging Equipment from the HMI
_7_$_*_*_,_1_*____________________________
'LVSOD\_________²!___
6HW_____________²!___
_&_2_1_7_5_2_/______________________________
%UHDNHU_6ZLWFK__²!____
7DJJLQJ_________²!___
,QWHUORFN_______²!___
_0_$_,_1___0_(_1_8______________________
$QQXQFLDWLRQ___²!___
0HDVXUHPHQW____²!___
&RQWURO________²!___
Note:
The Manual Overwrite function is always done using the HMI on the SIPROTEC® 4
devices.
SIPROTEC 4 Devices
7UM61 Manual 4-17
C53000-G1176-C127-1
4.6 General Setting Procedure
The SIPROTEC® 4 devices are delivered with standard default settings. Changes to
the settings are done with DIGSI® 4.
The setting procedure for a SIPROTEC® 4 device consists of:
q Overall Protection and Control Design:
q Determining the functions that are to be used (device configuration),
q Masking the binary inputs, outputs, LEDs, buffers, system port, etc.
q Defining special logic functions (CFC).
q Specific Settings:
q Settings for all elements to be used,
q Settings of the protective functions,
q Settings of the process control functions.
Settings are first done Off-line. The settings are then loaded into the SIPROTEC® 4
device on-site using the operating serial interface, or remotely by modem and the service
interface.
K450.gif
Figure 4-17 DIGSI® 4, Input/Output Masking with the Configuration Matrix, Example
Filter Function With the use of filters, either all information can be displayed or a selection can
be
done according to indications, commands, or measured values.
Additionally, there is a filter setting that differentiates between information configured
and not configured.
The filters allows for a quick overview and simple checking of the configuration settings.
Also, columns and rows can be temporarily hidden from view, so that the user can
combine only the sections of the total matrix that are relevant.
New Information A further function of the configuration matrix is the capability to define new
information.
This is accomplished by inserting a new line, assigning the appropriate information
type, and configuring the source with an output (binary outputs, LED, etc.). The new
information can also be displayed in the LCD of the SIPROTEC® 4 device.
Function Keys The function keys on the HMI of the SIPROTEC® 4 device can be assigned to
commonly
performed operating functions, e.g. initiation of a control operation. Select the
appropriate function key to in the Source F column for the related information
(e.g. control command).
F1 F4
SIPROTEC 4 Devices
7UM61 Manual 4-23
C53000-G1176-C127-1
CFC SIPROTEC® 4 device information can be connected in a user-specified manner using
the programmable logic components of the DIGSI® 4 CFC. For example, the user can
implement interlocking checks, create grouped messages, or derive limit value violation
messages.
Information can be both a source and a destination in combined CFC editing. The specific
logic’s inputs, e.g. the individual messages that are to be combined to form a
grouped message, must be marked in the 'HVWLQDWLRQ_& column. The logic’s output,
the grouped message in this example, is derived from the 6RXUFH_& column.
Displaying Masking
in the HMI
The masking can be seen in the HMI of the SIPROTEC® 4 device.
• In the main menu, select 6HWWLQJV → 0DVNLQJ__,_2_.
.
Figure 4-18 Reading the Masking using the HMI, example Binary Input 2
_0_$_6_._,_1_*_____,___2__________________
!%LQDU\_,QSXWV__²!___
!/('____________²!___
_%_,_1_$_5_<___,_1_3_8_7_6________________
!%LQDU\_,QSXW___²!__²
!%LQDU\_,QSXW___²!__²
SIPROTEC 4 Devices
4-24 7UM61 Manual
C53000-G1176-C127-1
4.9 Programmable Logic CFC
The CFC program in DIGSI® 4 can be used to create additional logic in SIPROTEC®
4 devices. For example, special interlocking conditions for controlled equipment can
be designed. Limit checks for measured values can be created, and corresponding
control can be designed.
SIPROTEC® 4 devices have some CFC functions set at the factory, according to the
version of the device.
User-defined CFC functions are done in graphical form. Generic logic modules (AND,
OR, NAND, etc.) and analog modules that are specially created for the requirements
of process control engineering (e.g., MAX, MIN, etc.) are available.
The CFC-modules are combined to form complete CFC-Logic Functions in order to
q perform system-specific checks (interlocking),
q generate messages if measured values approach a critical value, or
q build group messages for transfer to higher-level control systems.
k4122.gif
Figure 4-19 DIGSI® 4, CFC Basic Options, Example
CFC Designing Figure 4-20 shows the graphical nature of the CFC logic tool, and some of the
components
that can be used to build the logic.
Details about designing with the CFC program can be found in the instruction book,
order number E50417-H1176-C098.
Note:
Online changes are protected in DIGSI® 4 by Password No. 7 (Password for parameter
set).
SIPROTEC 4 Devices
7UM61 Manual 4-25
C53000-G1176-C127-1
Figure 4-20 CFC Logic, example
SIPROTEC 4 Devices
4-26 7UM61 Manual
C53000-G1176-C127-1
4.10 Power System Data
Power System
Data 1
In the window for Power System Data 1, important settings are entered that relate to
the power system and primary equipment connected to the device. The settings include:
q Power system data such as frequency, voltage, etc.
q Data for the main current transformers and voltage transformers,
q Circuit breaker or primary switchgear information, including a current threshold setting
that is used to indicate the open/close position of the primary equipment in several
protection functions.
k4124.gif
Figure 4-21 DIGSI® 4 Window for Setting the Power System Data 1, example
Power System
Data 2
Power System Data 2 are part of the setting groups, which can be switched over during
operation (see chapter 4.11). These include for example:
q Primary Operating Voltage
q Primary Operating Current
q Characteristic Data of the protected object etc.
SIPROTEC 4 Devices
7UM61 Manual 4-27
C53000-G1176-C127-1
4.11 Setting Groups
A SIPROTEC® 4 device has four setting groups A through D. The setting options for
each group are the same; however, the applied settings can be, and are typically intended
to be, different in each group. The active setting group can easily be changed
while the device is in-service. A major advantage of multiple setting groups is the capability
of optimizing the protection and control for the existing configuration of the network
being protected. In other words, the protection and control can be changed as
the network changes.
The setting groups are saved in the device. The setting groups can be changed during
operation using DIGSI® 4, from the HMI on the device, by triggering binary inputs, or
via the system interface.
k4114.gif
Figure 4-22 DIGSI® 4, Entering Settings in Setting Group A; Other Groups are Similar
Note:
Settings that are common to all protective functions, such as Power System Data 2,
can be dynamically activated like the settings in Groups A through D.
SIPROTEC 4 Devices
4-28 7UM61 Manual
C53000-G1176-C127-1
Settings Double click on a protective function shown in the smaller window of Figure 4-22or on
the button Settings (when the desired function has been selected) to obtain a window
for entering the general settings associated with the function and the settings of the
protective elements belonging to the function (Fig. 4-23).
f
Configuration 5
Configuration is the process of customizing the relay for the intended application.
To accomplish this, the following questions must be answered:
• Which functions are needed?
• Which data and measured quantities need to be retrieved via which inputs?
• Which control actions need to be issued via which outputs?
• Which user-definable functions need to be performed in CFC (Continuous Function
Chart)?
• Which information is to be presented on the display of the device?
• Which interfaces are to be used?
• Which time source is to be used to synchronize the internal clock?
This chapter describes in details how to configure the 7UM61.
5.1 Configuration of Functions 5-2
5.2 Configuration of Information, Meaured Values, and Commands 5-6
5.3 Creating User Defined Functions with CFC 5-30
5.4 Establishing a Default Display 5-38
5.5 Serial Interfaces 5-39
5.6 Date and Time Stamping 5-47
Configuration
5-2 7UM61 Manual
C53000-G1176-C127-1
5.1 Configuration of Functions
General The 7UM61 relay contains a series of protective and additional functions. The scope
of hardware and firmware is matched to these functions. Furthermore, commands
(control actions) can be suited to individual needs of the protected object. In addition,
individual functions may be enabled or disabled during configuration, or interaction between
functions may be adjusted.
The available functions must be configured as HQDEOHG RU GLVDEOHG. For individual
functions, the choice between several alternatives may be presented, as described
below.
Functions configured as GLVDEOHG are not processed by the 7UM61. There are no
messages, and corresponding settings (functions, limit values) are not displayed during
detailed settings.
Determination of
Functional Scope
Configuration settings may be entered using a PC and the software program DIGSI® 4
and transferred via the operating interface on the device front, or via the rear serial
service interface. Operation via DIGSI® 4 is described in Chapter 4 as well as in the
DIGSI® 4 manual, order number E50417–H1176–C097.
Entry of password No. 7 (for setting modification) is required to modify configuration
settings (see Section 4.16). Without the password, the settings may be read, but cannot
be modified and transmitted to the device.
The functional scope with the available options is set in the 'HYLFH_&RQILJXUDWLRQ
dialogue box (see Figure 5-1) to match equipment requirements. To change a function,
click on the corresponding line under 6FRSH, and select the desired option in the
list which appears. The drop-down list closes automatically upon selection of an item.
Note:
Available functions and default settings are depending on the ordering code of the relay
(see table 6-1 and ordering code in the appendix for details).
Configuration
7UM61 Manual 5-3
C53000-G1176-C127-1
Figure 5-1 Device Configuration dialogue box in DIGSI® 4 — example
Before closing the dialogue box, transfer the modified functional setting to the relay by
clicking on the item ',*6, → 'HYLFH. The data is stored in the relay in a non-volatile
memory buffer.
The configured functional scope can be viewed at the front of the relay itself, but cannot
be modified there. The settings associated with the functional scope can be found
in the 0$,1_0(18 under → 6HWWLQJV → 'HYLFH_&RQILJ.
Special Cases Most settings are self-explanatory. The special cases are described below.
If the setting group change-over function is to be used, the setting in address ____
*US_&KJH 237,21 must be set to (QDEOHG. In this case, it is possible to apply two
groups of settings for the function parameters (refer also to Sub-section 6). During normal
operation, a convenient and fast switch-over between these setting groups is possible.
The setting 'LVDEOHG implies that only one function parameter setting group
can be applied and used.
Parameter 01___)$8/7_9$/8( is used to specify whether the oscillographic fault recording
should record 0HDQ_YDOXHV or 506_YDOXHV. If 506_YDOXHV are recorded,
the available recording time increases by the factor 16.
For the I>> stage of the overcurrent protection, address ____ 2_&_3527__,!! allows
to seth that stage to 1RQ²'LUHFWLRQDO or 'LUHFWLRQDO. By setting 'LVDEOHG,
this overcurrent stage can be excluded altogether. For the inverse time overcurrent
protection set in address _____2_&_3527__,S, different sets of inverse characteristics
are available, depending on the version ordered; these are either according to
IEC (ZLWK_,(&_FKDUDFW_) or according to ANSI (ZLWK_$16,_FKDUDFW_). Inverse
time overcurrent protection can be excluded altogether by setting 'LVDEOHG.
For earth fault protection, address ____ 6_(_)_3527_ presents the options QRQ²
GLU__RQO\_8_, QRQ²GLU__8_ ,_ and 'LUHFWLRQDO, unless the whole function
is 'LVDEOHG. The first option evaluates only the displacement voltage (to be used with
block connection). The second option evaluates in addition to the displacement voltage
the magnitude of the earth fault current (or the difference between the starpoint
current and the total current of a cable CT, as is the case in busbar systems with lowohmic
switchable starpoint resistors). The third option considers as a third criterion the
Configuration
5-4 7UM61 Manual
C53000-G1176-C127-1
direction of the earth fault current in the case of machines in busbar connection where
the magnitudes of displacement voltage and earth fault current alone are not sufficient
to distinguish between system earth faults and machine earth faults.
For trip circuit monitoring, address ____ ___7ULS_&LU__6XS_ is used to specify
whether two binary inputs should be utilized, one binary input should be utilized, or the
function should be disabled.
Adr. Setting Setting Options Default Setting Explanation
103 Grp Chge OPTION Disabled
Enabled
Disabled Setting group switching
(A, B)
104 FAULT VALUE Disabled
Mean values
RMS values
Mean values Waveform capture
112 O/C PROT. I> Disabled
Enabled
Enabled Overcurrent time protection
(definite time element I>)
113 O/C PROT. I>> Disabled
Non–Directional
Directional
Non–Directional Overcurrent time protection
(definite time element I>>)
114 O/C PROT. Ip Disabled
with IEC–characteristic
with ANSI–characteristic
Disabled Overcurrent time protection
(inverse–time element)
116 Therm.Overload Disabled
Enabled
Enabled Thermal overload protection
117 UNBALANCE LOAD Disabled
Enabled
Enabled Unbalance load protection
130 UNDEREXCIT. Disabled
Enabled
Enabled Underexcitation protection
131 REVERSE POWER Disabled
Enabled
Enabled Reverse power protection
132 FORWARD POWER Disabled
Enabled
Enabled Forward power supervision
133 IMPEDANCE PROT. Disabled
Enabled
Enabled Impedance protection
140 UNDERVOLTAGE Disabled
Enabled
Enabled Undervoltage protection
141 OVERVOLTAGE Disabled
Enabled
Enabled Overvoltage protection
142 FREQUENCY Prot. Disabled
Enabled
Enabled Frequency protection (over and
under-frequency)
143 OVEREXC. PROT. Disabled
Enabled
Enabled Overexcitation protection
150 S/E/F PROT. non–dir only U0
non–dir. U0&I0
Directional
Disabled
non–dir. U0&I0 Stator earth fault protection
151 O/C PROT. Iee> Disabled
Enabled
Enabled Sensitive earth current protection
Configuration
7UM61 Manual 5-5
C53000-G1176-C127-1
152 SEF 3rd HARM. Disabled
Enabled
Enabled 100–%–Stator earth fault protection
with 3rd harmonic
170 BREAKER FAILURE Disabled
Enabled
Enabled Breaker failure protection
171 INADVERT. EN. Disabled
Enabled
Enabled Inadvertent energisation protection
180 FUSE FAIL MON. Disabled
Enabled
Enabled Fuse Failure Monitor
181 M.V. SUPERV Disabled
Enabled
Enabled Measured values monitoring
182 Trip Cir. Sup. Disabled
with 2 Binary Inputs
with 1 Binary Input
Disabled Trip circuit (e.g. breaker) monitoring
and method - using one
binary input or two.
186 EXT. TRIP 1 Disabled
Enabled
Enabled External trip command 1 via
binary input
187 EXT. TRIP 2 Disabled
Enabled
Enabled External trip command 2 via
binary inpu
188 EXT. TRIP 3 Disabled
Enabled
Enabled External trip command 3 via
binary inpu
189 EXT. TRIP 4 Disabled
Enabled
Enabled External trip command 4 via
binary inpu
Adr. Setting Setting Options Default Setting Explanation
Configuration
5-6 7UM61 Manual
C53000-G1176-C127-1
5.2 Configuration of Information, Meaured Values, and
Commands
General Upon delivery, the display on the front panel of the relay, some of the function keys,
the binary inputs and outputs (output contacts) are assigned to certain information.
These assignments may be modified, for most information, allowing adaptation to the
local requirements.
During configuration, certain information within the relay is assigned to certain physical
interfaces (e.g., binary inputs and output contacts) or logical interfaces (e.g., userdefined
logic, CFC).
It must be determined which information should be linked with which device interface.
It may also be determined which properties the information and the interfaces should
have.
Messages and statistical values from earlier events can be lost during configuration;
therefore, operational and fault data and statistic counters which are memorized in the
relay should be read and saved if desired, prior to changing the configuration.
5.2.1 Preparation
Before configuration is started, the overall interfacing requirements must be assessed.
The required inputs and outputs must be compared with the number of physical inputs
and outputs present on the relay. The types of indications and commands, and their
requirements, should be taken into account.
Indications Indications may be information of the device regarding events and conditions that
can
be transmitted via output contacts (e.g. start-up of the processor system or a trip signal
initiated by a protective function). These are defined as output indications. Indications
also include information from the plant to the relay regarding plant events and
conditions (e.g. position or condition of a circuit breaker). These are defined as input
indications.
Depending on the type, indications may be further classified. Figures 5-2 and 5-3
show typical indication types schematically. Two binary inputs whose normal conditions
are opposite, and which are monitored by the relay, are required for a double
point indication.
Figure 5-2 Output indication (OUT)
Restart
L+
(Internal logic
information)
Output indication via relay contact
(Plant)
(7UM61)
Configuration
7UM61 Manual 5-7
C53000-G1176-C127-1
Figure 5-3 Input indications (SP & DP)
Commands Commands (control actions) are output indications which are specially configured for
the transmission of control signals to switching devices (circuit breakers, isolators,
etc.).
q For each device to be controlled, determine if switching is to be done with 1 contact,
11/2 contacts (single contact and common), or 2 contacts; with a single or double
command; and with or without feedback signals. See Table 5-1 and Figures 5-4 to
5-12. The information to be processed and the command type are determined with
these decisions.
q Assign the necessary binary inputs and outputs in the SIPROTEC® device to the
specific function. Important to note are:
− Messages and commands associated with a switching device must always occupy
sequential binary inputs and outputs in the SIPROTEC® device;
− The TRIP (OFF)–command is always configured prior to the associated CLOSE
(ON)–command;
− Limitations may arise because of the commoning of some binary inputs and outputs
in the SIPROTEC® device.
When the types of commands have been established, DIGSI® 4 reserves a corresponding
number of relay outputs contacts. For this, the corresponding output contacts
are numbered consecutively. This must be observed when wiring the relays to
the corresponding equipment to be controlled.
Table 5-1 shows the most important command types. They are made available as options
in the Configuration Matrix for the SIPROTEC® device (see also “Binary Outputs
for Switching Devices” in Sub-section 5.2.4). All double commands, with and without
feedback indications, are also available as transformer step commands. The following
Figures 5-4 through 5-9 show time diagrams, control settings, and the sequence of relay
positioning in the configuration matrix for frequently used command types.
L+
L–
e.g. mcb
L+
L–
e.g. Isoloation
switch
M
Single point indication (SP) Double point indication (DP)
Binary input
(e.g. BI1) Binary input
(e.g. BI 2)
Binary input
(.e.g. BI 3)
(Plant)
(7UM61) (7UM61)
(Plant)
Table 5-1 Most Important Command Types
Single Command with Single
Output
With 1 contact without feedback
with feedback
&B6_
&)B6
Double Command with Single
Outputs
With 2 contacts without feedback
with feedback
&B'_
&)B'_
Double Command with Single
Outputs plus Common Output
With 3 contacts without feedback
with feedback
&B'_
&)B'_
Configuration
5-8 7UM61 Manual
C53000-G1176-C127-1
For double commands, the first output relay is selected using DIGSI® 4. The other output
relays will automatically be selected by DIGSI® 4. In the sequence of output relays,
each TRIP command is placed before the associated CLOSE command. For
commands with processing of feedback indications, DIGSI® 4 reserves a line in the
configuration matrix for the switching device feedback indications. Here, the OPEN
position feedback is placed before the CLOSED position feedback as well.
For Figures 5-4 through 5-9, the following abbreviations apply:
− C+ Relay Contact for Closing
− C– Relay Contact Tripping
− CC Relay Contact is Common
− CCC Relay Contact is Common to a Bus
− L+, L– Control Voltage
Figure 5-4 Single command with single contact
Figure 5-5 Double command with single contacts
Double Command with Single
Outputs and Common Bus Output
Minimum 3
contacts
without feedback
with feedback
C_D2
CF_D2
Double Command with Double
Outputs
With 4 contacts without feedback
with feedback
&B'_
&)B'_
Double Command with Double
(Close) and Single (Trip) Outputs
With 3 contacts without feedback
with feedback
&B'__
&)B'__
Table 5-1 Most Important Command Types
C+
X
C+
t
CLOSESwitching
device
C+
L+
L–
Matrix configuration:
1
CLOSE
command
CLOSE
command
C+
C–
TRIP
command
t
CLOSE Switching TRIP
device
C+ C–
L+
L–
Matrix configuration:
C+
X
1 C–
X
2
Configuration
7UM61 Manual 5-9
C53000-G1176-C127-1
Figure 5-6 Double command with single contacts plus common contact
Figure 5-7 Double Command on Common Bus with Single Contacts and Common Contact
Figure 5-7 shows the common output relay with several switching devices, in contrast
to all other output relays. Simultaneous control of multiple switching devices is
blocked, for safety reasons.
The common output relay automatically acquires the characteristics of the controlling
relay upon issuing of a command to a switching device and, therefore, is not individually
configured. The final command output is via a single contact.
CLOSE
command
C+
C–
TRIP
command
CC
t
CLOSE Switching TRIP
device
C+ C–
L+
L–
CC
Matrix configuration:
C+
X
1
C–
X
23
X
CC
CLOSING
Command
C+
C–
TRIPPING
Command
CCC
t
Switching
Device 2...n
CCC
Matrix Configuration:
C+
X
BO 1
C–
X
2
X
CCC
n
CLOSE TRIP
COIL COIL
CLOSESwitching TRIP
device
C+ C–
L+
L–
Configuration
5-10 7UM61 Manual
C53000-G1176-C127-1
Figure 5-8 Double command with double contacts (with 4 relays)
Figure 5-9 Double command with double and single contacts (with 3 relays)
5.2.2 Structure and Operation of the Configuration Matrix
General This section deals with the structure and operation of the configuration matrix. The
configuration matrix can be viewed without making any configuration changes. Information
characteristics and configuration steps are described in Section 5.2.3, and
configuration is demonstrated in Section 5.2.4.
Configuration of information is performed, using a PC and the DIGSI® 4 software program,
via the operator or service interface. The configuration is represented in
DIGSI® 4 as a matrix (Figure 5-10). Each row is assigned to an information of the device.
It is identified by a function number No, brief text (display text D), an explanation
CLOSE
command
C+1
C+2
TRIP
command
C–1
t
CLOSE Switching TRIP
device
C+1 C–1
L+
L–
C+2
C–2
C–2
Matrix configuration:
C+1
X
1
C–1
X
234
C+2
X
C–2
X
CLOSE
command
C+1
C+2
TRIP
command
C–
t
CLOSE Switching TRIP
device
C+1 C–
L+
L–
C+2
Matrix configuration:
C+1
X
1
C–
X
23
X
C+2
Configuration
7UM61 Manual 5-11
C53000-G1176-C127-1
(long text L, minimized in Figure 5-10), and an information type T. The columns give
the interfaces which should be the sources and/or destinations of the information. In
addition to physical device inputs and outputs, there may be internal interfaces for
user definable logic (CFC), message buffers, or the device display.
Figure 5-10 Extract from the Configuration Matrix in the DIGSI® 4 Software — Example
Information in the rows is assigned to appropriate interfaces in the columns via an entry
in the intersecting cell. This establishes which information controls which destination,
or from which source information is received.
In the configuration matrix, not only the configuration is shown, but also the type of
configuration. For example, information regarding an event which is configured for
display on a LED may be latched or unlatched.
The possible combinations of information and interfaces is dependent on the information
type. Impossible combinations are mostly filtered out by DIGSI® 4 plausibility
checks.
The matrix columns are divided into three types: Information, Source, and Destination.
To the left of the matrix, information is divided into information groups.
Filter Information Catalog Standard View Short view
Configuration
5-12 7UM61 Manual
C53000-G1176-C127-1
Reducing the Matrix
The matrix may become very extensive because of the amount of information contained
within. Therefore, it is useful to limit the display (via filtering) to certain information,
thus reducing the number of rows.
The toolbar below the menu line contains two pull-down menus by which information
may be filtered. Using the first menu, the rows can be limited to indications, commands,
indications and commands, or measured and metered values. The second
menu allows display of configured information, information configured to physical inputs
and outputs, or non-configured information.
A further reduction in the number of rows is possible, by compressing an information
group to one row. This is done by double-clicking on the group label area (located to
the far left). If this is done, the number of rows is reduced, allowing the user to focus
on the information group of interest. A second double-click restores all rows in the information
group.
To limit the width of the matrix, two possibilities exist: The tool bar allows to switch between
standard view and short view, or individual columns can be hidden.
In the latter case you double-click on the field with the column heading thus hiding the
contents of the associated column. In the example of Figure 5-10, the long text (/) under
IQIRUPDWLRQ is not shown. By double-clicking on long text field (/), the long text
becomes visible again, and vice versa.
With two options on the tool bar you may switch between standard view and short
view, thus modifying the all columns under the 6RXUFH and 'HVWLQDWLRQ title
blocks. The columns associated with the ,QIRUPDWLRQ block remain unchanged.
In standard view, all binary inputs, binary outputs, and LEDs are accessible, as shown
in Figure 5-10 for the binary outputs and LEDs.
In short view (not illustrated in the figure), a common column is displayed for each of
the sources and destinations. Within the individual cells of a common column, information
regarding the configuration type is available in an abbreviated form. For example,
the abbreviation H1 in a cell of the common binary input (BI) column means that
the corresponding information is configured with active voltage (High) to binary input
1. If an information is assigned to several sources or destinations, the abbreviations
of all destinations are shown, separated by commas. If there is not enough space in
the cell for the simultaneous display of all abbreviations, a double-click on the cell and
movement of the text cursor within the cell allows to scroll through the entire contents
of the cell.
To switch between standard view and short view, the menu item 9LHZ can also be
used.
Information Groups All information is organized into information groups. In addition to general
relay information,
information regarding individual device functions is also included.
By clicking on an information group title area with the right mouse button, a context
menu can be viewed, which contains information regarding the properties of that information
group. This is particularly useful if the information group is associated with a
function that contains parameter settings.
If the information group belongs to a protective function for the relay, a dialogue window
can be accessed in which the settings of the protective function may be read out
and modified. The procedure for entering settings of a protective function is described
in general in Chapter 4. Details regarding the settings for various functions are found
in Chapter 6.
The settings group to be processed may be selected via the menu item 9LHZ → 6HW_
WLQJ_*URXS.
Configuration
7UM61 Manual 5-13
C53000-G1176-C127-1
Information The column header ,QIRUPDWLRQ comprises the function number, the brief text
(display
text), an explanation (long text), and the information type. The following abbreviations
are used for the information types:
• Messages:
− SP Single Point Indication
− DP Double Point Indication
− OUT Output Indication
− IntSP Internal Single Point Indication
− IntDP Internal Double Point Indication
− TxTap Transformer Tap Changer
• Commands:
− C_S Single Command with Single Output without feedback
− CF_S Single Command with Single Output with feedback
− C_SN Single Command with Single Output Negated without
feedback
− CF_SN Single Command with Single Output Negated with feedback
− C_D2 Double Command (2 relays) with Single Outputs without
feedback
− CF_D2 Double Command (2 relays) with Single Outputs with
feedback
− C_D12 Double Command with Single Trip Outputs and Double Close
Outputs without feedback
− CF_D12 Double Command with Single Trip Outputs and Double Close
Outputs with feedback
− C_D3 Double Command (3 relays) with Single Outputs and
Common Output without feedback
− CF_D3 Double Command (3 relays) with Single Outputs and
Common Output with feedback
− C_D4 Double Command (4 relays) with Double Outputs without
feedback
− CF_D4 Double Command (4 relays) with Double Outputs with
feedback
− C_D2N Double Command (2 relays) with Single Outputs Negated
without feedback
− CF_D2N Double Command (2 relays) with Single Outputs Negated
with feedback
• Measured Values:
− MV Measured Value
− MVU Measured Value, User Defined
− MVT Measured Value with time
− LV Limit Value
− LVU Limit Value, User Defined
• Metered Values:
− MVMV Metered Value of Measured Values
− PMV Pulse Metered Value
Configuration
5-14 7UM61 Manual
C53000-G1176-C127-1
The information contains various properties depending on the information type, which
are partially fixed and may be partially influenced.
Source The source indicates the origin of the information which the device receives for further
processing. Possible sources are:
Destination The destination indicates to which interface the information is forwarded. Possible
destinations are:
For additional information please refer to appendix A.7.
5.2.3 Establishing Information Properties
General Different types of information contain different types of properties. To view the properties
associated with a specific information unit (indication, command, etc.), position the
mouse on the specific row under ,QIRUPDWLRQ, and then use the right mouse button
to access a context menu where 3URSHUWLHV can be selected.
For example, if the cursor is positioned on a specific output indication, the right mouse
button is pressed, and the menu item 3URSHUWLHV is selected, then a choice of
whether the indication should appear in the oscillographic fault records (Figures 5-11,
5-12, and 5-13) is presented. For internal single point indications, the default status of
the indication (on, off, or undefined) after device reset can be selected as well (Figure
5-12).
− BI Binary input
− F Function key, which may serve to introduce a control action
− C CFC, i.e., message comes from user-definable logic
− BO Binary output
− LED LED display on the device front panel
− Buffer O Operational indication buffer in the device
− Buffer T Trip Log buffer in the device
− S System interface
− C CFC, information is processed by CFC program of the user-definable
logic
− CM Control of switching devices, if a switching object should be controlled
from control display/menue of the device
Configuration
7UM61 Manual 5-15
C53000-G1176-C127-1
Output Indication
(OUT)
Figure 5-11 Information properties — example for the information type “Output Indication”
(OUT)
Internal Single
Point Indication
(IntSP)
Figure 5-12 Information properties — example for the information type “Internal Single Point
Indication” (IntSP)
Singe Point Indication
(SP)
Figure 5-13 Information properties — example for information type “Single Point Indication”
(SP)
Double Point Indication
(DP)
In addition to the properties entered for single point indications, a “Suppress intermediate
position” check box is available, which may be checked to suppress the intermediate
indication during operations. If this field is marked, then the filter time, which can
Configuration
5-16 7UM61 Manual
C53000-G1176-C127-1
also be set (see margin heading “Filtering/Contact Chatter Suppression” below), is
only effective for the intermediate (= undefined position) indication. Hence, briefly undefined
conditions or contact chattering will not lead to an alarm; however, defined
changes in the condition (final positions) are immediately reported.
Figure 5-14 Information properties — example for information type “Double Point Indication”
(DP)
Filtering / Contact
Chatter Suppression
For input indications (single point indications 63, double point indications '3), filter
times may be entered (pick-up and drop-out delays) to suppress momentary changes
in potential at the binary input (e.g. contact chatter), refer also to Figure 5-13 and 5-
14. Filtering occurs during an input change of state, with the same setting values
whether coming or going. Information is only distributed when the new state continues
to exist after a preset time interval (in milliseconds). The setting range is from 0 to
86,400,000 ms, or 24 hours. Whether or not the filter interval is restarted for each
change of state during the filtering (filter re-triggering) is selectable.
It is also possible to set chatter suppression for each indication (Figure 5-13 and 5-14).
The contact chatter settings, themselves, are set the same for all input indications (see
Sub-section 5.2.6).
Transformer Tap
Changer (TxTap)
The transformer tap changer position is communicated, via binary inputs, in a specified
encoding format (maximum of 62 positions). Only binary inputs that are in direct
order with regard to numbering can be used.
For the encoding formats available (binary code, BCD code, “1 of n” code), four settings
(number of positions, number of bits, display offset, and position change) may be
programmed. Their bit pattern corresponds to an individual transformer tap changer
position which is represented in the device display and in the indication buffers (Figure
5-15).
Configuration
7UM61 Manual 5-17
C53000-G1176-C127-1
Figure 5-15 Information Properties Example for Information Type “Transformer Tap Changer”
(TxTap)
If none of the available encoding formats are selected, each individual tap changer position
may be set in a table. The table is accessed after the pull-down menu 7DEOH for
encoding is opened, by selecting the button to the side.
The encoded transformer tap changer position bit pattern is transformed into digital
values between 1 and 62. An unrecognized pattern is interpreted as position 63.
The number of bits coincides with the number of the binary inputs to be configured,
and limits the number of positions to be represented.
Using the display offset, the beginning of the evaluated bits may have an offset of a
programmed number. The stepping of the transfomer taps may be modified, using the
tap interval feature (see example).
Example:Four transformer position settings are to be represented by three binary inputs,
using the designators 3 through 6. The encoding is binary.
Using three binary inputs (= 3 bits), a maximum of 23 = 8 position settings may be represented
in binary code. In order to begin the representation of transformer tap changer
positions with the value 3, the display offset is chosen accordingly. The following
must be set on the information property window:
Encoding %LQDU\_
Number of positions _
Number of bits _
Display offset _
Position change _
Orientation Desired representation
BI1 BI2 BI3
- - - 63.00
X - - 3.00
- X - 4.00
X X - 5.00
- - X 6.00
X - X 63.00
Configuration
5-18 7UM61 Manual
C53000-G1176-C127-1
The three binary inputs used for this must have sequential numbers, such as BI 1, BI
2, and BI 3.
User Defined Measured
Values (MVU)
and Limit Values
(LVU)
For the information type “Measured Values User Defined” (098), the units, the conversion
factor, and the number of significant digits following the decimal point may be
specified. For the information type “Limit Values User Defined” (/98), a limit value may
be programmed (Figure 5-16).
Figure 5-16 Information properties example for information type “Limit Value User Defined”
(LVU)
If, for example, a low current reporter should be established using the CFC logic, and
the percentage of the measured current should be matched to a certain amp value,
the following values are entered in window according to Figure 5-16:
The 'LPHQVLRQ is A (amps). The &RQYHUVLRQ_)DFWRU is 150: 150 A corresponds
to 100 % input current. The limit value upon start-up is set for 120 A.
Entering Your Own
Information
The available information in the configuration matrix is determined by the device type
and the configured functional scope. If necessary, you may extend the configuration
matrix to information groups or individual information defined and entered by yourself.
Such user defined groups and information may be deleted at any time, in contrast to
predefined groups and information.
In order to insert a new information group, click on a cell within a group that is next to
the location where the new group should be located. After pressing the right mouse
button, a context menu appears (Figure 5-17).
Figure 5-17 Dialogue box to insert a new information group
If one of the first two alternatives is selected, a second dialogue box opens, in which
the name of the new information group is entered, in short text (display text) and in
long text (Figure 5-18). After clicking 2., the new group is positioned.
Configuration
7UM61 Manual 5-19
C53000-G1176-C127-1
Figure 5-18 Entry of the name of a user defined information group
Information may be entered into the new information group using the information catalog
(Figure 5-19). The information catalog is found in the menu bar under the 9LHZ
option, or via an icon in the toolbar. User information may be entered into both the user
defined groups and any other available information group.
Figure 5-19 Information catalog window
The information catalog is basically structured the same way as the DIGSI® 4 Manager
with folders and sub-folders. To proceed to information of sub-folders in the catalog,
click on a plus symbol or double-click on an folder icon. The designation of the initial
levels of the catalog correspond to the information groups $QQXQFLDWLRQV, &RP_
PDQGV, 0HDVXUHG_9DOXHV and &RXQWHU_9DOXHV.
To insert a specific information unit into an information group, first select it in the catalog,
and using the left mouse button, it should then be dragged from the information
catalog window to a group area on the left of the matrix. After the mouse button is released,
the new information unit is inserted into the proper group.
In order to change the user defined information, double-click on the field containing
the new information and edit the text.
Deleting Groups
and Information
Only user defined groups and information can be deleted. To delete an entire group,
click on the field containing the group designator, then press the right mouse button to
Note:
When inserting information of the type &RQWURO_ZLWK_)HHG%DFN, two new rows will
be created within the group: one line for the actual command, and one for the associated
feedback message.
Configuration
5-20 7UM61 Manual
C53000-G1176-C127-1
open the context menu, and select 'HOHWH_*URXS. A confirmation window will appear
(Figure 5-20).
Figure 5-20 Confirmation window before deleting a user defined group
Click <HV if you actually want to delete the group.
To delete individual entries, click under ,QIRUPDWLRQ in the line with the entry to be
deleted. Then press the right mouse button to open the context menu, and select 'H_
OHWH_,QIRUPDWLRQ. The remaining steps are the same as those for deleting a
group.
5.2.4 Performing Configuration
The actual assignment between the information (rows) and the sources and destinations
(columns) of the information is made in the cell of intersection. You click into the
cell and press the right mouse button. A pull down menu appears where you may determine
the properties of the assignment.
In certain cases, the pull down menu will offer ; (allocated) or B (not allocated) as the
configuration choices. In other cases, three options will be offered (e.g. / = latched, 8
= unlatched, and B = not allocated). Entries resulting in an implausible configuration
are blocked and inaccessible to the user.
Configuring Binary
Inputs as Sources
Single point indications, double point indications, and pulse metered values can all be
configured as binary inputs. In addition, whether or not binary inputs are activated by
the presence of control voltage can be established. That is,
• “H” (High with voltage active): Control voltage at the binary input terminals activates
the indication;
• “/” (Low with voltage active): Control voltage at the binary input terminals deactivates
the indication.
Note:
When deleting a group, all information definitions within this group will be deleted.
Note:
A single logical indication should not be configured to two binary inputs, since an ORcombination
of both signals is not ensured. The operating program allows only one
combination, and deletes the first combination when a second is established.
Configuration
7UM61 Manual 5-21
C53000-G1176-C127-1
In addition, a single point indication cannot be configured to a binary input and to CFC
as a source at the same time. In this case, an error message would be displayed. Click
on 2., and select another configuration.
Figure 5-21 Error message resulting from double configuration
If a double point indication (DP) is configured to one binary input (e.g. feedback indications
from switching devices), the next binary input is also set in the matrix. If this
configuration is undone, the second binary input is automatically de-configured.
If a transformer tap changer indication is configured to a binary input, the next binary
inputs in order are also configured. Their total number is the same as the number of
bits configured for the transformer tap changer. If one of these inputs is deconfigured,
all related binary inputs are automatically deconfigured.
Configuring a
Function Key as a
Source
The four function keys on the front of the relay may also be configured as sources in
order to establish a link using CFC. In this situation, each function key may be linked
with one single internal indication. A function key may be occupied because it has already
been set as an operating function for the relay. As delivered from the factory, all
the device’s function keys are pre-configured:
In order to configure a new indication, select one of the options (OPEN/CLOSE, ON/
OFF, etc.) from the indication group in the information catalog and drag it to the left
side of the matrix. Upon release, a new row appears in the matrix. If the mouse is positioned
at the intersection of this row with column F, and the right mouse button is
pressed, a context menu opens (Figure 5-22) in which the function key may be set as
a source by clicking the proper choice.
F1 operating messages
F2 primary measured values
F3 overview of the last eight fault messages
F4 Reset of minimum/maximum measured values
Note:
When an indication is configured to a function key, its factory-assigned function is deleted.
Re-establishment of the factory default function of the F-keys is only possible
by initializing the relay with a new factory parameter set created within DIGSI® 4. All
device settings have to be re-entered.
Configuration
5-22 7UM61 Manual
C53000-G1176-C127-1
Figure 5-22 Selecting a function key as an information source
Configuring CFC as
a Source
If certain information should be created as a result of the implementation of a user defined
logic function (CFC), this information must appear in the matrix as a source from
CFC. Otherwise, this information will not be available to the user when editing the CFC
logic.
You must not configure information to CFC as a source if it is already configured to a
binary input.
Configuring Binary
Outputs as a
Destination
Up to 30 information units (commands and indications) may be configured to one binary
output (output relay). One indication may be configured to up to ten (10) binary
outputs (LEDs and output relays).
During configuration of binary outputs, you may select, for each output relay (besides
of the logic function itself), whether it should be latched (/) or unlatched (8). If you select
latched, the output relay remains energized, even after the indication is no longer
present. It must be manually reset by pressing the LED Reset button on the front panel
of the device, or via a binary input with the indication function “!/('_5HVHW”, or via
the serial system interface. If unlatched is selected, the output relay disengages as
soon as the indication disappears.
Binary Outputs for
Switching Devices
The user must be cautious when configuring binary outputs for switching devices. For
switching devices, the type of command (e.g., single or double commands, with or
without feedback) is defined and configured to the output relay. If the preset command
types are not desired, then appropriate command types can be selected from the Information
catalog (see also “Entering Your Own Information” in the previous sub-section)
and inserted into the Configuration Matrix.
Warning!
CFC connection have to be reestablished after renaming of a display text of an user
defined information. Within the CFC the old name is shown at the right column. Delete
this connection. Make connection to the desired blocks using the renamed information.
Configuration
7UM61 Manual 5-23
C53000-G1176-C127-1
Figure 5-23 Window Information Catalog (Example: Different Command Types)
If a command with multiple outputs is configured, all binary outputs required in the matrix
for the configuration are automatically defined. If one of these outputs is deconfigured,
all other binary outputs associated with the command will be automatically deconfigured.
Please pay attention to the comments and switching examples in Section 5.2.1, particularly
the fixed defined sequence of relay assignments (TRIP before CLOSE).
When configuring commands, the context menu is dependent on the type of command.
In some cases, the selection latched/unlatched is not available. Instead, the alternatives
are ; (configured), B (not configured), and ) (busy flag). The latter means,
independent of the switching direction, an indication is always issued during activation
of the switching device.
For double commands with a common output, a fourth alternative & (Common contact)
appears. Using this, the binary output may be defined as the common relay (common
contact). When this is the case, several double commands with common contacts may
be assigned to the same common relay (common contact), thus saving binary outputs.
This assumes the signals at the common outputs have the same potential.
Using the 2EMHFW_3URSHUWLHV dialog window, additional properties for commands
issued to the switching device may be defined. Thus, the operating mode (pulse or
latched) output of a switching command, the seal-in time for pulse commands, the output
delay of the command, and feedback monitoring may be set (see Figure 5-24). The
output delay is only relevant for equipment which removes an indication before the
switching is completed.
Example:
Double Command with
2 Contacts (acc. Table 5-1)
Configuration
5-24 7UM61 Manual
C53000-G1176-C127-1
Figure 5-24 Dialog Box - Object Properties for a Command with Feedback (Example: Double
Command with Single Trip Outputs and Double Close Outputs, CF_D12)
The conditional checks that should be conducted before execution of a switching command
can also be defined:
• System Interlocking (Substation controller): Checks the system interlocking status
(configured from the substation controller).
• Zone controlled (Bay Specific Interlocking): Logic functions created with CFC in the
relay are processed for interlocked switching.
• Device status (Open/Closed; scheduled/actual): The switching command is ignored
and a corresponding indication is issued if the switching device is already in the desired
position. If this check is activated, switching direction control occurs not only
for interlocked, but also for non interlocked switching.
• Blocked by protection: CLOSE–switching command for switchgear is blocked as
soon as one of the protective functions or elements in the relay has picked up.
OPEN commands, in contrast, can always be executed. Please be aware, activation
of thermal overload protection can create and maintain a fault condition indication,
and can therefore lead to the blocking of CLOSE commands.
• Double operation: Parallel switching operations are blocked with respect to each
other; while one switching operation is being conducted, a second one may not be
performed.
• Switching Authority – Local commands: A local control switching command is only
allowed if local control is enabled on the relay (via a setting).
• Switching Authority - Remote commands: A remote control switching command is
only allowed if remote control is enabled on the relay (via a setting).
Configuring a LED
Display as a Destination
Single point indications (SP), output indications (OUT), and internal single point indications
(IntSP) may be assigned to LEDs. When this is done, you may select whether
the indications are to be latched (/) or unlatched (8).
Up to 30 indications may be assigned to a LED display. One indication may be assigned
to a maximum of ten (10) outputs (LEDs and output relays).
Configuration
7UM61 Manual 5-25
C53000-G1176-C127-1
Configuring an
Indication Buffer
as a Destination
Two indication buffers are available for selection: Operation (Event Log) Buffer (() and
Trip Log (7). The indications from protective functions are firmly assigned to these indication
buffers. For the others, Table 5-2 provides an overview of which indication
type may be configured to which buffer.
One of the following options should be selected for all configured indication types:
• 2 (on) – the indication is stored in the buffer with the time of its arrival
• RR (on/off) – the indication is stored in the buffer with the time of its arrival and departure
• B (not configured) – the indication is not stored in a buffer.
Configuring the
SCADA Interface
as a Destination
Depending on the SCADA interfaces connected to the relay, the types of information
displayed in Table 5-3 may be configured. By placing an ; in the matrix cell, the information
is transferred to connected systems via the SCADA interface.
.
Table 5-2 Overview of Indication Buffers
Information type ↓ \Message buffer → E T
Single Point Indications (SP) X X
Double Point Indications (DP) X
Output Indications (OUT) X X
Internal Single Point Indications (IntSP) X X
Internal Double Point Indications (DP) X
Transformer Tap Change Indications (TxTap) X
Table 5-3 Overview of SCADA Interfaces
SCADA Interface →
Information Type ↓
IEC Profibus
FMS
Profibus
DP
DNP3.0 Modbus
Single Point Indication (SP) X X X X X
Double Point Indication (DP) X X X X X
Output Indication (OUT) X X X X X
Internal Single Point Indicator (IntSP) X X X X X
Internal Double Point Indicator (IntDP) X X
Transformer Tap Change Indicator (TxTap) X
Command with/without Feedback (C_**) X X X X X
Protective Measurement Value X X X X
Protective Measurement Value with Time
(MVT)
XX
Configuration
5-26 7UM61 Manual
C53000-G1176-C127-1
User-defined information (switching devices, indications, metered values, etc.) can be
entered in the matrix. However, a transmission to the substation control is only possible
with IEC 60870-5-103 and Profibus FMS. For other protocols, you will have to use
predefined CFC indications (see also Table “Protocol-dependent functions” in the Appendix).
Configuring CFC
as a Destination
Single point, double point, and output indications, as well as limit and measured values,
may be configured to CFC as the destination.
Configuring the
Default Display and
Control Diagram
as a Destination
All information, including limit values, may be configured, both in the default and control
display. By placing an ; in the matrix cell, the information may be used within the
default and control control display. This feature is not available on the 7SJ61_62 series
of relays.
Configuring Control
Display as a
Destination for
Command Initiation
Single point and double point indications, transformer tap change indications, and all
types of commands may be configured to the control display as the destination. These
indications and commands then become available in the relay’s control display for operational
control.
Configuring the
Measured Value
Window as a
Destination
In addition to the measured values available in the relay, user defined measured and
limit values may be configured into the measured value window. These values then
become available in the device display in the assigned measurement window.
Configuring the
Metered Value
Window as a
Destination
In addition to the metered values available in the device, user defined pulse and metered
values derived from the measured values may be configured into the metered
value window so that they may be shown at the front display.
Protective Measurement Value, User
Defined (MVU)
X
Pulsed Metered Value (PMV) X X X X
Metered Value from Measurement Value
(MVMV)
XXXX
Table 5-3 Overview of SCADA Interfaces
SCADA Interface →
Information Type ↓
IEC Profibus
FMS
Profibus
DP
DNP3.0 Modbus
Warning!
CFC connection have to be reestablished after renaming of a display text of an user
defined information. Within the CFC the old name is shown at the left column. Delete
this connection. Make connection to the desired blocks using the renamed information.
Configuration
7UM61 Manual 5-27
C53000-G1176-C127-1
Retrieving Device
Configurations
from the Device
Front
Retrieving the configurations is also possible from the device front. You may access
configuration information under 0DLQ_0HQX: → 6HWWLQJV → 0DVNLQJ__,_2_.
The menu title 0$6.,1*__,_2_ appears in the title bar. Configuration information regarding
each (physical) input and output is indicated in the display.
Any new user defined information is also shown in the display once loaded into the
relay from DIGSI® 4.
When selecting the 0$6.,1*__,_2_ menu, either binary inputs, LEDs, or binary outputs
may be selected. Selection of binary inputs is illustrated in Figure 5-25.
Figure 5-25 Reading the configuration in the front display of the device — example
Information regarding a binary input may be displayed by using the navigation keys to
select the binary input. See Figure 5-26.
Figure 5-26 Selection of binary input 2 — example
In the example of Figure 5-26, information is displayed regarding binary input 2. The
display for binary input 2 indicates that it is configured as reset of the latched LEDs
using a single point indication with voltage active (High). The present conditions of binary
input 2 is also given as 0 (not active). If a binary input is active, a 1 is displayed.
Assignment of LEDs may be indicated at the relay, itself, using a replaceable labelling
strip with plain text on the front panel located, directly next to the LEDs.
Preset Configurations
The pre-set configurations of the binary inputs and outputs and for the LED displays
upon relay delivery are listed in tables in Appendix A.5.
5.2.5 Transferring Metering Values
The transferring of metered values from the buffer of the device to SCADA or substation
controller may be performed both cyclically and/or by external polling.
_0_$_6_._,_1_*_____,___2__________________
!%LQDU\_,QSXWV__²!___
!/('____________²!___
_%LQDU\_2XWSXWV_²!___
_%_,_1_$_5_<___,_1_3_8_7_6________________
!%LQDU\_,QSXW__²!___²
!%LQDU\_,QSXW__²!___²
%_,_1_$_5_<___,_1_3_8_7_______________
!!5HVHW_/('_63______+
_____________________
6WDWXV_DW_7HUPLQDO___
Configuration
5-28 7UM61 Manual
C53000-G1176-C127-1
In the configuration matrix, click on 2SWLRQV and then on 5HVWRUH_0HWHUHG_9DO_
XHV. A dialog box, which contains a register for editing the individual values for cyclical
transferring will open.
Cyclic Restoring Here the origin of the initiation for the cyclic transfer is defined. Furthermore,
the transfer
interval is set here, as well as the selection whether the counter buffer in the device
must be reset following the transfer.
Figure 5-27 Dialogue box to restore values, cyclic restoring
The initiation is defined as an absolute time corresponding to the set time interval.
5.2.6 Setting of Contact Chatter Blocking
Contact Chatter
Blocking
The contact chatter filter checks whether the number of condition changes at a binary
input exceeds a preset value during a predetermined time interval. If this occurs, the
binary input will be blocked for a certain time, so the event list does not contain a large
number of unnecessary entries. The setting values necessary for this feature may be
entered in a dialogue box, as shown in Figure 5-28. This dialogue box can be found
from the open configuration matrix by clicking 2SWLRQV in the menu bar and then selecting
&KDWWHU_%ORFNLQJ.
Figure 5-28 DIGSI® 4: Setting the chatter blocking feature
Defining the Monitoring
Criteria
The operating mode of the chatter blocking feature is determined by five settings:
Configuration
7UM61 Manual 5-29
C53000-G1176-C127-1
• 1XPEHU_RI_SHUPLVVLEOH_VWDWH_FKDQJHV
This setting establishes how often the state of a binary input within the ,QLWLDO_
7HVW_7LPH may change. If this number is exceeded, the binary input is or remains
blocked. If the setting is 0 the chatter blocking is disabled.
• ,QLWLDO_WHVW_WLPH
Within this time interval (in seconds), the number of state changes of a binary input
is checked. The time interval begins with the first activation of a signal to the binary
input.
• 1XPEHU_RI_FKDWWHU_WHVWV
This number represents how many check cycles should be conducted before the
binary input is finally blocked. Please consider that even a high set value can be
reached over the normal life span of the device and could lead to blocking of the
binary input. Therefore this value can also be set to infinity. For this, enter the character
sequence of oo.
• &KDWWHU_,GOH_7LPH
If the 1XPEHU_RI_SHUPLVVLEOH_VWDWH_FKDQJHV at a binary input is exceeded
during the ,QLWLDO_WHVW_WLPH or the 6XEVHTXHQW_WHVW_WLPH, the
&KDWWHU_
LGOH_WLPH interval is initiated. The affected binary input is blocked for this time
interval. The &KDWWHU_LGOH_WLPH setting is entered in minutes. This settings can
only be programmed if the 1XPEHU_RI_FKDWWHU_WHVWV is not set to zero.
• 6XEVHTXHQW_WHVW_WLPH – Within this time interval, the number of state changes
at a binary input is checked again. This interval begins after the &KDWWHU_LGOH_
WLPH interval has expired. If the number of state changes is within allowable limits,
the binary input is released. Otherwise, the idle interval is restarted, until the maximum
1XPEHU_FKDWWHU_WHVWV is reached again. The 6XEVHTXHQW_WHVW_WLPH
setting is entered in seconds. This settings can only be programmed if the 1XPEHU_
RI_FKDWWHU tests is not set to zero.
The settings for the monitoring criteria of the chatter blocking feature are set only once
for all binary inputs; however, the status of the chatter suppression can be set individually
for each binary input. See “Filtering / Contact Chatter Suppression” in Sub-section
5.2.3.
The following should be noted:
• If there is contact chatter at a binary input and the input is blocked, the corresponding
indication will be displayed with “CCF” (example: “!'RRU_RSHQ_&&)_21”). Also,
the indication “&RQWDFW_FKDWWHU_ILOWHU” reports this condition. Both messages
are shown in the operating buffer.
• Chattering of a single point indication is set as ON (coming) if the binary input has
been in an active state.
• Chattering of a single point indication is set as OFF (going) if the binary input has
been in an inactive state.
• If this behaviour causes undesired results in individual situations, a blocking may
be configured in CFC.
• Chattering of a double point indication will be considered an “intermediate” condition.
Note:
Chatter blocking cannot be activated for any of the standard protective indications.
Configuration
5-30 7UM61 Manual
C53000-G1176-C127-1
5.3 Creating User Defined Functions with CFC
General The 7UM61 relay is capable of implementing user defined logic functions which may
be processed by the relay. This CFC feature (Continuous Function Chart) is needed
to process user defined supervision functions and logic conditions (e.g. interlocking
conditions for switching devices) or to process measured values. Interlocking conditions
and command sequences, for example, may be programmed, using pre-defined
function modules, by persons without any specialized software programming abilities.
A total of 22 types of functional modules (FM), with which the desired functions may
be composed, are saved in a library. Detailed explanations are in the CFC manual,
order number E50417–H1176–C098, or in the DIGSI® 4 manual, order number
E50417–H1176–C097.
The creation of a logical PLC function is performed by means of a personal computer
using application DIGSI® 4 and transferred via the operator or service interface. In order
to create user defined logic functions, the indications and measured values required
by these functions must first be configured in the matrix with CFC as the source
or destination (see Section 5.2).
CFC can be started by double-clicking on &)&. The names of all available CFC charts
will appear. The desired CFC chart for processing can be selected via a double-click
of the mouse. The CFC program will start, and the chart will be displayed. If no chart
is available yet, you can create a new chart via the menu &UHDWH → &)&²&KDUW.
Run-Time Properties
The functions to be implemented in CFC may be divided into four task levels:
• Measured values: This task is processed cyclically every 600 milliseconds
(09B%($5% = measurement value processing) and might become slower if the device
is in pick-up state.
• System logic: Operation is triggered by events (i.e. these functions are processed
for each change of state at one of its inputs). System logic has lower priority than a
protection function and will be suppressed as soon as the relay picks up
(3/&_B%($5% = slow PLC processing).
• Protective functions: These functions have the highest priority, and, like the system
logic functions, are event-controlled and processed immediately after a change of
state (3/&B%($5% = fast PLC processing).
• Switchgear Interlocking: This task is triggered by commands. In addition it is processed
cyclically approximately every second. It might becomes slower if device is
in pick-up state (6)6B%($5% = interlocking).
The function to be implemented must be associated to one of these four task levels.
To implement a function from the 6HWWLQJV → &)& menu, activate the menu by selecting
(GLW, and then 5XQ_6HTXHQFH, and then the desired task level (See Figure
5-29).
Configuration
7UM61 Manual 5-31
C53000-G1176-C127-1
Figure 5-29 Establishing the task level
Within the Run Sequence menu, select (GLW, and then 3UHGHFHVVRU_IRU_,Q_
VWDOODWLRQ, to ensure that the function modules selected from the library will be
implemented
into the desired task level (Figure 5-30).
Figure 5-30 Assignment of function modules to the selected task level
The proper assignment is important for several reasons. For example, if interlocking
logic were to be set up in the measured values task level, indications would constantly
be created by the cyclical processing, filling the buffer unnecessarily. On the other
hand, the interlocking condition at the moment of a switching operation may not be
processed at the right time, since measured value processing is done only every
600 ms.
Table 5-4 Selection guide for function modules and task levels
Function Modules Description
Run-Time Level
MW_BEARB
Meter
processing
PLC1_BEARB
Slow PLC
PLC_BEARB
Fast PLC
SFS_BEARB
Interlocking
ABSVALUE Magnitude calculation X – – –
AND AND–Gate – X X X
BOOL_TO_CO Boolean to Control
(conversion)
–XX–
Configuration
5-32 7UM61 Manual
C53000-G1176-C127-1
BOOL_TO_DI Boolean to Double Point
(conversion)
–XXX
BUILD_DI Create Double Point
annuciation
–XXX
CMD_INF Command information – – – X
CONNECT Connection – X X X
D_FF D–Flipflop – X X X
DI_TO_BOOL Double Point to Boolean
(conversion)
–XXX
LIVE_ZERO Live–zero, non linear Curve X – – –
LOWER_SETPOINT Lower limit X – – –
NAND NAND–Gate – X X X
NEG Negator – X X X
NOR NOR–Gate – X X X
OR OR–Gate – X X X
RS_FF RS–Flipflop – X X X
SR_FF SR–Flipflop – X X X
TIMER Timer – X X –
LONG_TIMER Timer (max. 1193 h) – X X –
UPPER_SETPOINT Upper limit X – – –
X_OR XOR–Gate – X X X
ZERO_POINT Zero suppression X – – –
Table 5-4 Selection guide for function modules and task levels
Function Modules Description
Run-Time Level
MW_BEARB
Meter
processing
PLC1_BEARB
Slow PLC
PLC_BEARB
Fast PLC
SFS_BEARB
Interlocking
Configuration
7UM61 Manual 5-33
C53000-G1176-C127-1
Configuration
Sheet
The configuration is performed within the configuration sheets (see Figure 5-31).
Figure 5-31 Principal representation of function modules in a CFC working page
The left border column of the configuration sheet shows the inputs; the right border
column shows the outputs of a function. In the above diagram the inputs are connected
with input signals IS1 to IS3. These may be indications from the breaker (via binary
inputs), from device function keys, or from a protective function. The output signal
(OS4 in the diagram) may control an output relay, for example, and can create entries
in the message buffers, depending on the preset configuration.
Configuring and
Connecting Function
Modules
The default run-time sequence is determined by the sequence of the insertion of the
logic modules. You may redefine the run-time sequence by pressing <CTRL> – <F11>
on the PC keyboard. Please refer to the CFC manual. The necessary function modules
(FM) are contained in a library located to the right of the configuration chart. The
module also indicates to which of the four run-time levels (MW_BEARB,
PLC1_BEARB, PLC_BEARB, SFS_BEARB) it is assigned. The modules possess at
least one input and one output. In addition to these inputs and outputs, which are displayed
on the configuration sheet, a module may have additional inputs. The additional
inputs can be made visible by selecting the module title block, pressing the right
mouse button, selecting the menu option 1XPEHU_2I_,_2V___ (see Figure 5-32),
and then increasing the number.
Figure 5-32 Example of an OR gate: module menu
Under the 2EMHFW_3URSHUWLHV menu, you may edit the name of the module, insert
a comment, or edit run-time properties and connection parameters.
Connecting modules with each other, and linking them with system input and output
signals, is performed by selection of the desired modules input or output and subse-
IS1
IS2
IS3
OS4
1 FM2
2
3
1 FM1
2
3 FM3
12
Configuration sheet 1
Input
signals
Output
signals
Function modules
Configuration
5-34 7UM61 Manual
C53000-G1176-C127-1
quently pressing the right mouse button, and selecting the menu option ,QVHUW_&RQ_
QHFWLRQ_WR_2SHUDQG (see Figure 5-33).
Figure 5-33 Example of module input menu
A window with a list of input signals will appear. By selecting one of these signals and
activating with 2., the selected signal is entered into the left border panel and, from
there, a connection is created to the module input. Selection of an output is done in
the same manner. A connection between two modules is established by a simple sequential
clicking on the two connections.
If the link line display becomes unwieldy or impossible because of space limitations,
the CFC editor creates a pair of connectors (target icons) instead. The link is recognizable
via correlated numbering (see Figure 5-34).
Figure 5-34 Connector
For additional information please refer to Appendix A.7.
Consistency check In addition to the sample configuration chart 1, shown in Figure 5-36, other
configuration
sheets may exist. The contents of any particular configuration sheet is compiled
by DIGSI® 4 into a program and processed by the protective device. For CFC charts
developed by the user, syntactic correctness can be verified by clicking the menu
command &KDUW, and then &KHFN_&RQVLVWHQF\. The consistency check will
determine
if the modules violate conventions of various run-time levels, or any of the principles
below.
Check of functional correctness must be performed manually.
The completed CFC chart can be saved via menu item &KDUW, and &ORVH. Likewise,
the CFC chart may be reopened and edited by clicking on &KDUW, selecting the appropriate
chart, and clicking on 2SHQ.
Please be aware, certain limitations exist, because of memory space and processing
power. The limits listed in Table 5-5 are generally applicable. The limits given in Table
Connector
Configuration
7UM61 Manual 5-35
C53000-G1176-C127-1
5-6 are relay-specific. These limits must not be exceeded because adverse effects to
the protective functionality (e.g. slower trip times) would result.
Table 5-6 Maximum Number of Modules per Process Area for SIPROTEC® 7UM61
The limits are monitored by the DIGSI® 4 operating program. When 100 % of the allowed
memory is used, DIGSI® 4 issues a warning message. See Figure 5-35.
Figure 5-35 Warning message from DIGSI® 4 when 100 % of allowed memory is used
After acknowledgement of the warning, the register sheet Compile under Option →
5HSRUWV can be accessed. By scrolling, an area can be reached in which statements
Table 5-5 Maximum Number of Charts and Inputs
Limit Description Limit Comment
Total number of all CFC charts for all
processing areas
32
Allowable number of CFC charts in a
single processing area
16
Total number of inputs on the left
panel for all CFC charts in eventdriven
process areas
100*)
*) If a message is used in two charts, it counts as two.
Valid for process areas:
PLC1_BEARB (system logic)
PLC_BEARB (protective
functions)
Maximum number of different inputs
on the left panel for all CFC charts in
event-driven process areas
50 Valid for process areas:
PLC1_BEARB (system logic)
PLC_BEARB (protective
functions)
Process Area (running level) Number of
Blocks
Comment
MW_BEARB (Meter processing) < 100
PLC1_BEARB (Slow PLC Logic) approx 30 Depends on the type of functional
blocks used and the number of
PLC_BEARB (Fast PLC Logic) approx 12 connections
SFS_BEARB (Interlocking) < 100
Configuration
5-36 7UM61 Manual
C53000-G1176-C127-1
are given regarding the memory usage, as a percentage of the portion reserved for
CFC. In Figure 5-36 for example, an overload of 56 % is presented for the run-time
level PLC_BEARB (specially noted), while the other running levels are within the allowed
range.
Figure 5-36 Reading the loading level for CFC–diagrams
The following contains a few examples. A summary of the CFC configurations provided
at the factory is shown in Appendix A.5.4.
Example 1 (MW):
Low Current
Monitor
A configuration for low-current monitoring alarm (see Figure 5-37) which can be produced
using CFC, should be a first example. This element may be used to detect operation
without load, or to recognize open circuited conditions. By connecting measured
current values with a limit function via an OR function, an indication may be generated
which can be used to cause switching operations.
• The configuration sheet is assigned to task level MW_BEARB.
• Four function modules (3 lower-value limit modules and an OR gate), are taken
from the function module library and copied into the configuration sheet.
• In the left panel, the measurement values to be monitored (IL1, IL2, IL3 in % of the
nominal current) are each selected and connected with the measured value inputs
of each limit module function.
• A lower limit setpoint value (IL<) is linked with the limit inputs of each of three limit
sensor functions.
• The limit value function outputs are passed on to the OR gate.
• The output of the OR gate is connected to the right border column at annunciation
“,__DODUP”.
The limit value message is triggered when the preset limit value is below the setpoint
(low current) in at least one of the three phases. The hysteresis of the limit values is
fixed and need not be entered (5 % of set point plus 0.5 % of nominal value).
Configuration
7UM61 Manual 5-37
C53000-G1176-C127-1
Figure 5-37 Under-current monitoring as an example of user defined measurement value
processing
Example 2 (PLC1):
Additional Logic
By using slow PLC processing, an additional, event-driven logic condition may be constructed
which delivers indications regarding facility operating status. These indications
may be passed externally via LEDs or relays, or used as input signals for further
logical links. In the example (see Diagram 5-38), the single-point indication
“!'DWD6WRS“ that can be injected by binary inputs is converted by means of a NEGATOR
block into an indication “8QORFN'7“ that can be processed internally (internal
single point indication, IntSP), and assigned to an output. This would not be possible
directly, i.e. without the additional block.
Figure 5-38 Logical link between input and output
FM:
Lower
Setpoint
Limit Vol
I<
alarm OUT
Measurement
IL1
FM:
Vol
Annunciation BO
Limit
FM:
Vol
Annunciation BO
Limit
Lower
Setpoint
Lower
Setpoint
FM:
Set points
IL<
Measurement
IL2
Set points
IL<
Set points
IL<
Measurement
IL3
Annunciation BO
>1
_*HQHUDO_!'DWD6WRS_63 287_'HYLFH__8QORFN'7_,QW63
,1__'HYLFH_
Configuration
5-38 7UM61 Manual
C53000-G1176-C127-1
5.4 Establishing a Default Display
Under normal conditions, a preset image is shown as the default display. It shows operating
information and/or measured values of the protected equipment. Depending
on the relay type, a number of predefined basic displays are available. Using the
and keys, one of the displayed images may be selected (see example in the following
figure), causing it to appear as the default display under normal conditions.
Figure 5-39 Example of a Basic Display
_______N$__________N9_
_______N$__________N9
_______N$__________N9
(______$___(_______9
Configuration
7UM61 Manual 5-39
C53000-G1176-C127-1
5.5 Serial Interfaces
The device contains one or more serial ports — a PC port is integrated into the front
panel. Depending on the model ordered, a rear service port and a SCADA port for connection
of a substation control system are integrated. Certain standards are necessary
for communication via these ports, which contain protection device identification,
transfer protocol, and transfer speed.
Configuration of these interfaces is performed in a first step in the property dialog. Details
are set when setting the port.
5.5.1 Settings in the property dialog
Select a project in the DIGSI® 4 Manager via )LOH → 2SHQ. For this, the button
3URMHFWV is to be activated.
Select a device with the right mouse key in the open menu 3URSHUWLHV: The system
interface is defined with the tab &RPPXQLFDWLRQV_PRGXOH. The protocol is selected
in the respective drop-down menu.
5.5.1.1 Setting of IEC- and Profibus-FMS protocol
These protocols are selected directly in the drop-down list (see Figure 5-40).
Figure 5-40 DIGSI® 4, Selecting IEC- and Profibus-FMS protocols
After the selection, another configuration has to take place on the tab )06_,(&_6HW_
WLQJV (see Figure 5-41).
Configuration
5-40 7UM61 Manual
C53000-G1176-C127-1
Figure 5-41 DIGSI® 4, Configuration of FMS and IEC settings
The left layer address is to be entered for IEC, according to the selected protocol; for
Profibus FMS you have to state also the communications reference and the VFD
name.
5.5.1.2 Selecting additional protocols
Additional protocols can be delivered for SIPROTEC® devices. At the moment these
are the protocols Profibus–DP, DNP3.0 and MODBUS. Select the option )XUWKHU_
3URWRFROV and /_____ is activated. Select and press /_(see Figure 5-42).
The window $GGLWLRQDO_LQIRUPDWLRQ opens. Select 3URWRFROV for the 1st
system
interface; with the 2nd interface you select the actual protocol. Confirm your selection
with 2..
The selected protocol is marked with an altered /_ button.
Note:
Refer to the SICAM center for the following configuration!
Configuration
7UM61 Manual 5-41
C53000-G1176-C127-1
Figure 5-42 DIGSI® 4, Selecting Other protocols
The settings for these protocols have to be carried out on the tab 2WKHU_SURWRFROV
afterwards (see Figure 5-43).
Figure 5-43 DIGSI® 4, Settings for Further protocols
A matching mapping file has to be selected. A mapping file contains references of deice
objects for the communications objects which are located on the bus. Without the
selection of such a mapping the faultfree operation of the interface cannot be guaranteed.
Select a mapping to view the changeable parameters in the window below. They
can be set directly (careful!) (see Figure 5-44).
Configuration
5-42 7UM61 Manual
C53000-G1176-C127-1
Figure 5-44 Mapping file with changeable parameters
Note, these parameters have to react to certain syntactic rules; this is why only the relevant
numerical values can be changed in the described way, if necessary!
The relevant protocol only works when the mapping has been selected and, if necessary,
set. Further information on the mapping files and additional protocols can be
found in the internet: see http//:www.siemens.com (English) or http//:www.siemens.de
(German; the protocol documentation is normally only available in English - also on
the German internet sites)
5.5.2 Setting the ports
It is necessary to set further parameters of the port. For this, double click on the device
to open it. DIGSI® 4 is now busy with extremely complex functions. Afterwards, the
settings can be carried out via 3DUDPHWHUV → 3RUWV. The ports are selected and set
via tabs. Values which cannot be changed anymore are grayed out.
5.5.2.1 Serial port on PC
In the first tab, the user should enter the communication port of the PC (&20___&20__
etc.) which is connected to the 7UM61 relay. Manual entry of settings for data format
and baud rate can not be entered, since these values were taken from the “3&_SRUW_
RQ_GHYLFH” tab or the “6HUYLFH_SRUW” tab (if present). In fact, many settings are
read from DIGSI® 4 directly via the port, and the corresponding setting fields are made
inaccessible (see Figure 5-40). On the other hand, for those settings that must be entered
by the user, the option ,QGHSHQGHQW_RI_GHYLFH should be selected.
The settings RQ 1 and RQ 2 are intended for Siemens use only. Please do not modify
these settings.
Configuration
7UM61 Manual 5-43
C53000-G1176-C127-1
Figure 5-45 DIGSI® 4, Parameters of the PC port
5.5.2.2 PC and Service Port
Both ports have the same settings and as described here.
Configuration
5-44 7UM61 Manual
C53000-G1176-C127-1
Figure 5-46 Parameters of the Service port - Example
Besides the usual parameters you can also set a permissible telegram gap. A gap is
the maximum allowable time duration of interrupted transmission within one telegram
transmission. With it, an adaptation to special features of the line or the modem can
be carried out. For good data transmission between modems, a setting of ___ sec is
recommended. For poor connections, this value should be increased. In this case, the
transmission speed is decreased. When using a direct PC connection, 0D[__PHV_
VDJH_JDSV may be set to ___ sec.
5.5.2.3 Profibus FMS connection
The PC can be equipped with a module CP5412A2. In this case, it is possible to connect
the PC with the device via the Profibus FMS. For this, the settings on the tab
352),%86_)06_DW_3& are necessary. Normally, presettings exist which have to be
checked for their correctness concerning the Profibus configuration.
5.5.2.4 Setting VD addresses
These settings agree with the parameters and are to be checked accordingly.
Note:
Do not use front port for modem communication!
Configuration
7UM61 Manual 5-45
C53000-G1176-C127-1
5.5.2.5 Device IEC
These settings are necessary, if the protocol IEC was selected for the system port (see
Figure 5-47).
.
Functions 6
This chapter describes the numerous functions available on the SIPROTEC® 7UM61
relay. The setting options for each function are defined, including instructions for reporting
setting values and formulae where required.
6.1 General 6-3
6.2 Overcurrent Protection (ANSI 50, 51, 67) 6-18
6.3 Inverse O/C time protection (ANSI 51) 6-27
6.4 Thermal overload protection (ANSI 49) 6-34
6.5 Unbalanced load protection (ANSI 46) 6-43
6.6 Underexcitation protection (ANSI 40) 6-50
6.7 Reverse power protection (ANSI 32R) 6-58
6.8 Forward power supervision (ANSI 32F) 6-62
6.9 Impedance protection (ANSI 21) 6-65
6.10 Undervoltage protection (ANSI 27) 6-75
6.11 Overvoltage protection (ANSI 59) 6-78
6.12 Frequency protection (ANSI 81) 6-81
6.13 Overexcitation (Overflux) protection U/f (ANSI 24) 6-86
6.14 90–%–stator earth fault protection (ANSI 59N, 64G, 67G) 6-91
6.15 Sensitive earth current protection (ANSI 50/51GN, 64R) 6-99
6.16 100–%–stator earth fault protection with 3rd harm. (ANSI 59TN/ 27TN
(3.H.)) 6-103
6.17 Breaker failure protection (ANSI 50BF) 6-107
6.18 Inadvertent energization (ANSI 50, 27) 6-112
6.19 Monitoring functions 6-116
6.20 External trip commands via binary inputs 6-133
6.21 Phase rotation reversal 6-136
6.22 Protection function logic 6-138
6.23 Auxiliary functions 6-143
6.24 Breaker control 6-150
Functions
6-2 7UM61 Manual
C53000-G1176-C127-1
Regionalization The SIPROTEC® 7UM61 protective relays are offered in regional versions. The
prepared
functions are adapted to the technical requirements of the regions. The user
should purchase only the functional scope that is needed.
Legend
(X) – Selectable option
(–) – Function not available for this region
Table 6-1 Regionalization
Function Region DE
Germany
Region worldwide
Worldwide
Region US
USA
Language German English American
English
Frequency 50 Hz 50 Hz / 60 Hz
Default 50 Hz
60 Hz
Characteristic curves for
inverse time-overcurrent
elements
IEC curves
ANSI curves
X
–
X
Default IEC
Characteristic
Curves
X
–
X
Functions
7UM61 Manual 6-3
C53000-G1176-C127-1
6.1 General
6.1.1 Introduction, reference power system
The following chapters explain the individual protective and additional functions and
provide information about on the setting values. The calculation examples are based
on two reference power systems with the two typical basic connections, i.e. the busbar
connection and the block connection (see figure 6-1). All default settings of the relay
are adapted accordingly.
Figure 6-1 Reference systems
Technical data of
the reference
power systems
Generator: SN, G = 5.27 MVA
UN, G = 6.3 kV
IN, G = 483 A
cos ϕ = 0.8
7UM61
7UM61
G
a) Busbar connection
b) Block connection
UE IL IEE UL
6.3 kV
√3
/ 500 V 500 A/1 A
5.27 MVA
6.3 kV
6.3 kV
√3
100 V
√3
5.3 MVA
20 kV/6.3 kV 20 kV
IL UL UE IEE
500 A/1 A
5.27 MVA
6.3 kV 6.3 kV
√3
100 V
√3
3∼
100 V
3 60/1 A
RL
Earthing
transformer
G
3∼
Functions
6-4 7UM61 Manual
C53000-G1176-C127-1
Current transformer: IN,prim = 500 A; IN, sek = 1 A
Toroidal current transformerIN,prim = 60 A; IN, sek = 1 A
Voltage transformer: UN, prim = (6.3/√3) kV UN, sek = (100/√3) V
Uen/3 = (100/3) V
Transformer: SN, T = 5.3 MVA
UOS = 20 kV
UUS = 6.3 kV
uK = 7 %
Neutral earthing
transformer: ü =
Resistor divider: 5 : 1
Further technical data is provided within the framework of the functional setting specifications
of the individual protective functions.
The calculated setting values are secondary setting values related to the device and
can be modified immediately by way of local operation.
The use of the DIGSI® 4 operating program is recommended for a complete reparameterization.
In this way, the user has the possibility to specify primary values in addition
to secondary settings. Within the framework of the 7UM61, the specification of primary
values is performed as a setting related to the nominal quantities of the object to be
protected (IN, G; UN, G; SN, G). This procedure has the advantage that system-independent,
typical settings of the protective functions can be pre-specified. The data of the
individual power system are updated in the power system data (see sections 6.1.3 and
6.1.6) and the conversion to secondary values is executed via a mouse click (conversion
to secondary values, see 6.1.2). All necessary conversion formula of the individual
functions are stored in the operating program.
6.1.2 Brief overview of the device operation
A few seconds after the device is powered up, the default display will appear showing
measured values by the 7UM61 protective relay.
The settings associated with the various device functions may be modified using the
controls on the front panel of the device or by using the DIGSI® 4 operator and service
interface on a personal computer. Password No. 5 is required to modify individual settings.
From the
Device Front
Select the 0$,1_0(18 by pressing the key. Using the key, select 6HWWLQJV,
and then press the key to navigate to the 6(77,1*6 display (see Figure 6-2).
In the 6(77,1*6 display, use the key to select the desired function, and then use
the key to navigate to that function (e.g., use the key to select the 3_6\VWHP_
'DWD_ function, and then use the key to navigate to the 3_6<67(0_'$7$_display,
as shown in Figure 6-3.
6.3 kV
√3
500 V
MENU
Functions
7UM61 Manual 6-5
C53000-G1176-C127-1
In general, an item number appears in the menu list to the right of each selection. Navigation
can be accomplished using the item number in place of the and keys.
This feature is particularly helpful in large menus (e.g., setting lists). Based on the example
above, from the 0$,1_0(18, the 6(77,1*6 display can be reached by pressing
on the keypad, and then the 3_6<67(0_'$7$_ display can be reached by
pressing on the keypad.
Figure 6-2 Example of navigation from the front control panel
Each setting contains a four-digit address number followed by the setting title as
shown in Figure 6-3. The value of the current setting is displayed in the line just below
the setting address number and title. The value may be text (Figure 6-3, setting ____)
or numerical (Figure 6-3, setting ____).
Figure 6-3 Example of power system data display
Settings are selected using the and keys. When the key is pressed, the
user is prompted for a password. The user should enter Password No. 5 and then
press the key. The current value of the setting appears in a text box, with a blinking
text insertion cursor.
Text Values A text setting may be modified using the and keys to select one of two or more
options.
Numerical Values
(including ∞)
A numerical setting may be modified by overwriting the current value using the numerical
keypad. See Figure 6-4. A value of “infinity” may be entered by pressing the decimal
key twice . The “∞”−symbol will appear in the display.
If the number entered is not within allowable limits, the maximum or minimum allowable
value will appear in the lower portion of the display. To enter a new, allowable value,
the key should be pressed again.
Note that measured values and limit values must be entered in secondary quantities
when using the front control panel of the device.
4
03
_0_$_,_1___0_(_1_8________________________
$QQXQFLDWLRQ__²!_____
0HDVXUHPHQW___²!_____
&RQWURO_______²!_____
6HWWLQJV______²!_____
7HVW_'LDJQRVH_²!_____
_6_(_7_7_,_1_*_6__________________________
'HYLFH_&RQILJ_²!_____
0DVNLQJ__,_2__²!_____
3_6\VWHP_'DWD_²!_____
$FWLYH_*URXS_LV_____$_
_3___6_<_6_7_(_0___'_$_7_$________________
_____&7_6WDUSRLQW
_____WRZDUGV_/LQH
_____8QRP_35,0$5<
__________N9
ENTER
ENTER
..
ENTER
Functions
6-6 7UM61 Manual
C53000-G1176-C127-1
Confirmation Any modification to a setting value must be confirmed by pressing the key. A
blinking asterisk is an indication that setting modification mode is still open. Other
modifications can be made to settings, even in sub-menus (if present), as long as setting
modification mode is still open. The actual modification of settings occurs once
setting modification mode is closed (see below, “Exiting the Setting Mode”).
Figure 6-4 Example of setting modification using the front control panel
If a setting modification is not confirmed with the key, the original value reappears
after one minute, and a message window appears after three minutes notifying the
user that the setting modification period has expired. When the key is pressed, a
further message window appears, notifying the user that the setting modifications
were discarded. Further modification of settings is possible by pressing the key
and re-entering the password.
Exiting the Setting
Mode
If an attempt is made to exit setting modification mode using the key or the key,
the message $UH_\RX_VXUH" will be displayed followed by the responses <HV__1R_
and (VFDSH (see Figure 6-5). If the response <HV is selected, modification of settings
can be confirmed by pressing the key. To cancel pending modifications to settings
and exit setting modification mode, the response 1R must be selected. Press the
key until the response 1R_is highlighted. Press the key to confirm and exit. Incorrect
entries may be retracted in this manner. To remain in the setting modification
mode, press the key until the response (VFDSH_is highlighted. Press the key
to confirm, and the user can remain in setting modification mode without down-loading
modifications.
Figure 6-5 Ending the setting mode using the front control panel
ENTER
ENTER
3:_6HWWLQJV"
_____ _______
Enter password No. 5 and confirm with
ENTER
____
8QRP_35,0$5<____________
3_6<67(0_'$7$__[_____
_____________________
_____8QRP_35,0$5<
> > > _____N9
The modified setting value appears in the
list; a blinking asterisk in the title bar indicates
setting modification mode is still
open.
Example for numerical setting:
Enter the new value and confirm with ENTER
3_6<67(0_'$7$________
_____________________
____!8QRP_35,0$5<
!___!_____N9
ENTER
ENTER
ENTER
MENU
ENTER
ENTER
ENTER
ENTER
$UH_\RX_VXUH"
!<HV_1R_(VFDSH
ENTER
6HWWLQJV_DUH_RN
______!&RQWLQXH
Functions
7UM61 Manual 6-7
C53000-G1176-C127-1
From PC with
DIGSI® 4
Using DIGSI® 4 to modify settings.
To select a function, double-click on 6HWWLQJV, and then double-click on the desired
setting function (e.g., 3RZHU_6\VWHP_'DWD__ is selected by double-clicking 6HW_
WLQJV, and then double-clicking 3RZHU_6\VWHP_'DWD__ as illustrated in Figure 6-6).
K450.gif
:
Functions
6-8 7UM61 Manual
C53000-G1176-C127-1
Figure 6-7 Power system data dialogue box in DIGSI® 4 — example
The left column of the dialogue box (identified as the 1R_ column) contains the fourdigit
address number of the setting. The middle column of the dialogue box (identified
as the 6HWWLQJV column) contains the title of the setting, and the right column of the
dialogue box (identified as the 9DOXH column) contains the current value of the setting
in text or numerical format. When the mouse cursor is positioned over a numerical field
in the 9DOXH column, the allowable range is shown.
To modify a setting, click on the setting value which is displayed in the 9DOXH column.
Text Values When a text setting value is selected, a pull-down menu of possible setting options
is
displayed. To modify the setting, simply click on the desired option. The pull-down
menu closes, and the new setting value appears in the 9DOXH column.
Numerical Values
(including ∞)
When a numerical setting value is selected, the setting is modified using the number
keys, if applicable, with a decimal comma (not a decimal point). A value of “infinity”
may be entered by pressing the small o key twice. Confirm the setting modification by
clicking on $SSO\, or select another setting to modify.
If the value entered is outside the allowable range, a message block appears on the
screen describing the error and displaying the acceptable range of values. To acknowledge
the message, click 2., and the original value reappears. A new entry can
be made or another setting value can be modified.
Functions
7UM61 Manual 6-9
C53000-G1176-C127-1
Primary or
Secondary Values
Setting values can be entered and displayed in primary terms or secondary terms, as
desired. DIGSI® 4 automatically performs the conversions based on the settings entered
for the transformer data and conversion ratios.
To switch between primary values and secondary values:
q Click on 2SWLRQV in the menu bar, as shown in Figure 6-8.
q Click on the desired alternative.
Figure 6-8 Selection of primary or secondary value entry — example
Additional Settings Those settings that are modified only in special cases are typically hidden.
They may
be made visible by checking on 'LVSOD\_$GGLWLRQDO_6HWWLQJV.
Confirmation Each entry may be confirmed by clicking $SSO\. Valid values are accepted
automatically
when another field is selected.
The final acceptance of a modified setting takes place once the setting mode is exited
(see below “Exiting the Setting Mode”).
The dialogue box may be closed by clicking 2.. Once closed, another function may
be selected for setting modification, or you can exit the setting mode.
Exiting the Setting
Mode
In order to transfer the modified setting values to the relay, the user should click on
',*6, → 'HYLFH. The user will be prompted for Password No. 5. After entering the
password and confirming with 2., data is transferred to the relay where modifications
become effective.
Functions
6-10 7UM61 Manual
C53000-G1176-C127-1
6.1.3 Power System Data 1
The device requires certain basic data regarding the protected equipment, so that the
device will be compatible with its desired application. Phase sequence data, nominal
system frequency data, CT&PT ratios and their physical connections, as well as,
breaker operating times and minimum current thresholds are selected in the 3RZHU_
6\VWHP_'DWD__ display.
To modify these settings from the front of the device, the user should press the key
and wait for the 0$,1_0(18 to appear. From the 0$,1_0(18, the user should use the
key to select 6HWWLQJV, and then use the key to navigate to the 6(77,1*6
display. To obtain the 3_6\VWHP_'DWD_ display, the user should use the key to
select 3_6\VWHP_'DWD_ in the 6(77,1*6 display, and then press the key.
To modify settings associated with 3RZHU_6\VWHP_'DWD__ using DIGSI® 4, the user
should double-click 6HWWLQJV, and then 3RZHU_6\VWHP_'DWD__, and the of theired
selection options will be displayed.
Polarity of current
transformers
At address _____&7_6WDUSRLQW, the polarity of the wye-connected current transformers
is specified (see Figure 6-9 for options). Modifying this setting also results in
a polarity reversal of the ground current inputs IN or INS.
Figure 6-9 Current Transformer Polarity
Nominal values of
voltage transformers
and current
transformers
At addresses ____ 8QRP_35,0$5< and ____ 8QRP_6(&21'$5<, information is entered
regarding the primary nominal voltage and secondary nominal voltages (L-L) of
the connected voltage transformers. At addresses ____ &7_35,0$5< and ____ &7_
6(&21'$5<, information is entered regarding the primary and secondary ampere ratings
of the current transformers. It is important to ensure that the rated secondary current
of the current transformer matches the rated current of the device, otherwise the
device will incorrectly calculate primary amperes.
W0 correction
angle
A correction of the angle faults of the current transformers and voltage transformers is
particularly important with regard to the reverse power protection (address _____&7_
$1*/(_:_), as in this case, a very low active power is calculated from a very high apparent
power (for small cos ϕ ).
The ∆ ϕ angle fault difference between the current transformers and voltage transformers
is particularly important in this context. As a correction, the sum of the medium angle
faults of the current transformers and voltage transformers is set. The corrective
value can be determined within the framework of machine commissioning (see section
8.3.7.2).
MENU
ENTER
$GGUHVV______ $GGUHVV_____
WRZDUGV__PDFKLQH_ WRZDUGV_VWDUSW_
GG
Functions
7UM61 Manual 6-11
C53000-G1176-C127-1
Uph/Udelta
adaptation factor
The address _____8SK_8GHOWD serves to communicate the adaptation factor between
the phase voltage and the displacement voltage to the device. This information
is relevant for measured-quantity monitoring.
If the voltage transformer set has e–n–windings and if these windings are connected
to the device (UE–input), this must be specified accordingly in address ____ (see below
at „displacement voltage“ paragraph title). As the transformation ratio of the voltage
transformers is usually:
the factor Uph/Uen (secondary voltage, address ____ 8SK_8GHOWD) in relation to 3/
√3 = √3 = 1.73 must be used if the Uen voltage is connected. For other transformation
rations, i.e. the formation of the displacement voltage via an interconnected transformer
set, the factor must be corrected accordingly.
Iee transformation
ratio
For the conversion of the sensitive ground current (INs) in primary quantities, the device
requires the primary/secondary transformation ratio of the transformer. The address
____ )$&725_,(( serves to communicate this transformation ratio to the device.
UE transformation
ratio
For the conversion of the UE displacement voltage in primary quantities, the device
requires the primary/secondary transformation ratio of the transformer delivering the
UE voltage. The following specification generally applies for this ratio _____)$&725_
8(:
In this context, UWdl, prim is the primary voltage and UE, sec is the secondary displayement
voltage applied to the device. If a voltage divider is used, its division ratio also
influences this factor. The following equation results for the example in figure 6-1b with
the power system data selected there and an 1:5 voltage divider ratio
Displacement
voltage
The address ____ 8(_&211(&7,21 serves for specifying whether the displacement
voltage is connected or QRW_FRQQHFWHG at the QHXWUDO_WUDQVIRUPHU or at
the
open GHOWD_ZLQGLQJ, e.g. of an earthing transformer. In the latter case, the device
calculates the displacement voltage from the phase-to-ground voltages. This information
is of primary importance for the 100–%–stator earth fault protection, whose measuring
procedure depends on the displacement voltage detection method.
If this voltage stage shall be used for monitoring any other voltage instead of the displacement
voltage, the user may select as fourth option 8(_FRQQHFWHG_WR_DQ\_97
under address 0211.
phase rotation reversal
Address ____ 3+$6(_6(4_ is used to establish phase rotation reversal. The default
phase sequence is “/_ /_ /_”. For systems that use a phase sequence of
“/_ /_ /_”, address ____ should be set accordingly. A temporary reversal of rotation
is also possible using binary inputs (see Section 6.21).
UNprim
3
-----------------
UNsek
3
---------------
UNsek
3
⁄ ⁄ ---------------
UWdl, prim
UE, sek
_____)$&725_8( = ------------------------
6.3 kV ⁄( 3)
500 V ⁄ 5
_____)$&725_8( = --------------------------------- = 36.4
Functions
6-12 7UM61 Manual
C53000-G1176-C127-1
Figure 6-10 Phase sequences
Trip command
duration
Address ____ 7PLQ_75,3_&0' is used to set the minimum time the tripping contacts
will remain closed. This setting applies to all protective functions that initiate tripping.
Current flow monitoring
Address ____ %NU&ORVHG_,_0,1 corresponds to the threshold value of the integrated
current flow monitoring feature. This setting is used for the elapsed-time meter and
the overload protection. If the threshold value set at address ____ is exceeded, the
circuit breaker is considered closed and the power system is considered to be in operation.
In the case of overload protection, this criterion serves for distinguishing between
the standstill and the motion of the machine to be protected.
Operating mode The _____6&+(0( setting is used for specifying if the generator to be protected
is operated
in the 8QLW_7UDQVI_ or the %XVEDU mode. This specification is important for
the inverse O/C time protection with undervoltage consideration, as different voltages
are used here, depending on the corresponding operating mode (see „Undervoltage
consideration“ in section 6.3.1).
Rated Frequency Address ____ 5DWHG_)UHTXHQF\ corresponds to the frequency at which
the power
system operates. The setting is dependent on the model number of the relay purchased,
and must be in accordance with the nominal frequency of the power system.
Starpoint earthing The _____67$5_32,17 setting serves to specify if the generator starpoint is
operated
in the ORZ_UHVLVWDQFH or the KLJK_UHVLVWDQFH mode. This specification is
important
for the measured-value monitoring. The total current monitoring of the three
phase currents is only useful for an isolated or high-resistance starpoint and earth
fault-free operation. For all other applications, it is not executed.
Settings In the list below, the setting ranges and default setting values of the pickup currents
are for a device with a nominal current rating IN = 1 A. For a nominal current rating IN
= 5 A, multiply the setting options values and default setting values by 5. Consider the
current transformer ratios when setting the device with primary values.
L1
L3 L2
L1
L2 L3
Clockw. rot. phase sequ. L1, L2, L3 Anti-clockw. rot. ph. sequ. L1, L3, L2
Functions
7UM61 Manual 6-13
C53000-G1176-C127-1
6.1.4 Settings
1) depending of the ordering code, please refer to Table 6-1
Addr. Setting Title Setting Options Default Setting Comments
209 PHASE SEQ. L1 L2 L3
L1 L3 L2
L1 L2 L3 Phase Sequence
213 SCHEME Direct connected to busbar
Unit transformer connected
Direct connected
to busbar
Scheme Configuration
214 Rated Frequency 50 Hz
60 Hz
50 Hz1) Rated Frequency
217 STAR-POINT Starpoint earthing: high resistance
Starpoint earthing: low resistance
Starpoint earthing:
high resistance
Earthing of Machine Starpoint
201 CT Starpoint CT starpoint towards
machine
CT starpoint towards starpoint
CT starpoint
towards machine
CT Starpoint
204 CT PRIMARY 10..50000 A 500 A CT Rated Primary Current
205 CT SECONDARY 1A
5A
1A1) CT Rated Secondary Current
207 CT ANGLE W0 -5.00..5.00 ° 0.00 ° Correction Angle CT W0
208 FACTOR IEE 1.0..300.0 60.0 CT Ratio Prim./Sec. Iee
202 Unom PRIMARY 0.10..400.00 kV 6.30 kV Rated Primary Voltage
203 Unom SECONDARY
100..125 V 100 V Rated Secondary Voltage (Ph-Ph)
206 Uph / Udelta 1.00..3.00 1.73 Matching Ratio Ph.-VT to Broken-
Delta-VT
211 UE CONNECTION UE connected to neutral
transformer
UE connected to broken
delta winding
not connected
UE connected to any VT
UE connected to
neutral transformer
UE Connection
218 FACTOR UE 1.0..2500.0 36.4 VT Ratio Prim./Sec. Ue
210 TMin TRIP CMD 0.01..32.00 sec 0.15 sec Minimum TRIP Command Duration
212 BkrClosed I MIN 0.04..1.00 A 0.04 A1) Closed Breaker Min. Current
Threshold
Functions
6-14 7UM61 Manual
C53000-G1176-C127-1
6.1.4.1 Information
6.1.5 Setting groups
Purpose of setting
groups
A setting group is nothing more than a collection of setting values to be used for a particular
application. In the 7UM61 relay, two independent setting groups (A and B) are
possible. The user can switch back and forward between setting groups locally, via binary
inputs (if so configured), via the operator or service interface using a personal
computer, or via the system interface.
A setting group includes the setting values for all functions that have been selected as
(QDEOHG during configuration (see Chapter 5). While setting values may vary among
the two setting groups, the selected functions of each setting group remain the same.
Multiple setting groups allows a specific relay to be used for more than one application.
While all setting groups are stored in the relay, only one setting group may be active
at a given time.
If multiple setting groups are not required, Group A is the default selection, and the
following paragraph is not applicable.
If multiple setting groups are desired, address ____ *US_&KJH_237,21 must be set
to (QDEOHG in the relay configuration. Refer to chapter 5.
Copying setting
groups
In most cases, only a few settings will vary from setting group to setting group. For this
reason, an option exists to copy stored setting values from one setting group to another
setting group using DIGSI® 4:
To copy the setting values from one setting group to another setting group, the user
should highlight the setting group in the list whose setting values are to be copied.
Next, the user should go to the menu bar, click on_(GLW and select &RS\ (see Figure
6-11).
F.No. Alarm Comments
5145 >Reverse Rot. >Reverse Phase Rotation
5147 Rotation L1L2L3 Phase Rotation L1L2L3
5148 Rotation L1L3L2 Phase Rotation L1L3L2
361 >FAIL:Feeder VT >Failure: Feeder VT (MCB tripped)
5002 Operat. Cond. Suitable measured quantities present
Functions
7UM61 Manual 6-15
C53000-G1176-C127-1
Figure 6-11 Copying a setting group in DIGSI® 4
The next step is to highlight the name of setting group in the list into which the setting
values should be copied. The user should go to the menu bar, click on (GLW and select
3DVWH. A confirmation box will appear (see Figure 6-12). Select <HV to copy the setting
values.
Figure 6-12 DIGSI® 4: Confirmation before copying a setting group
Setting groups may be copied more easily using the “Drag & Drop” feature. To use the
“Drag & Drop” feature, the name of the setting group in the list whose setting values
are to be copied should be highlighted. Holding down the left mouse button, the cursor
can then be dragged to the name of the setting group into which the setting values are
to be copied.
After copying setting groups, it is only necessary to modify those setting values that
are to be set differently.
Note:
All existing setting values in the setting group that has been copied to will be overwritten.
An inadvertent copy operation can be undone by closing and reopening the
DIGSI® 4 session without saving changes.
Functions
6-16 7UM61 Manual
C53000-G1176-C127-1
Restoring factory
settings
The factory settings may be restored for a modified setting group. To restore factory
settings to a setting group, the name of the setting group whose settings are to be restored
should be highlighted. Next, the user should select the menu option (GLW and
then click on 5HVHW. A confirmation box appears, and the user should click on <HV to
confirm restoration of factory settings.
Switching between
setting groups
The procedure to switch from one setting group to another during operations is of thecribed
in Subsection 7.2.2. The option of switching between several setting groups
externally via binary inputs is of thecribed in Subsection 8.1.2.
6.1.5.1 Information
6.1.6 Power System Data 2
General protective data (3_6<67(0_'$7$_) includes settings associated with all
functions rather than a specific protective or monitoring function. In contrast to the
3_6<67(0_'$7$_ as discussed in Sub-section 6.1.1, these settings can be changed
over with the setting groups. To modify these settings, the user should select the 6(7_
7,1*6 menu option *URXS_$ (setting group A), and then 3_6\VWHP_'DWD_.
The other setting group is *URXS_%_ as described in Subsection 6.1.2.
Definition of nominal
system values
At addresses ____ 8_35,0$5<_23_ and _____,_35,0$5<_23_, the nominal voltage
(phase-to-phase) and current (phase) of the protected equipment is entered (e.g.,
motors). These values do not effect pickup settings. They are generally used to show
values in reference to full scale. For example, if a CT ratio of 500/1 is selected and the
full load current of a motor is 483 amps, a value of 500 amps should be entered for
____&7 35,0$5< and a value of 483 amps should be entered for _____,_35,0$5<_
23_. 483 amps are now displayed as 100 % in the percentage metering display (Subsection
6.1.3).
Note:
All setting values in the setting group being restored to factory settings will be overwritten.
An inadvertent reset operation can be reversed by closing and reopening the
DIGSI® 4 session without saving changes.
Addr. Setting Title Setting options Default Setting Comments
302 CHANGE to Group A
Group B
Binary input
Protocol
Group A Change to Another Setting Group
F.No. Alarm Comments
7 >Set Group Bit0 >Setting Group Select Bit 0
Group A Group A
Group B Group B
Functions
7UM61 Manual 6-17
C53000-G1176-C127-1
Active power
direction
Address _____$&7,9(_32:(5 is used to specify the active power direction in the
normal mode (*HQHUDWRU = output or 0RWRU = input) or to adapt it to the power system
conditions without any recabling on the device.
6.1.6.1 Settings
6.1.6.2 Information
Addr. Setting Title Setting Options Default Setting Comments
1101 U PRIMARY OP. 0.10..400.00 kV 6.30 kV Primary Operating Voltage
1102 I PRIMARY OP. 10..50000 A 483 A Primary Operating Current
1108 ACTIVE POWER Generator
Motor
Generator Measurement of Active Power for
FNo AlarmComments Comments
533 IL1 = Primary fault current IL1
534 IL2 = Primary fault current IL2
535 IL3 = Primary fault current IL3
5012 UL1E= Voltage UL1E at trip
5013 UL2E= Voltage UL2E at trip
5014 UL3E= Voltage UL3E at trip
5015 P= Active power at trip
5016 Q= Reactive power at trip
5017 f= Frequency at trip
Functions
6-18 7UM61 Manual
C53000-G1176-C127-1
6.2 Overcurrent Protection (ANSI 50, 51, 67)
General The overcurrent time protection represents the short-circuit protection for extra-low or
low-voltage machines. For larger machines it is used as back-up protection for the machine
short-circuit protection (differential protection and/or impedance protection). It
provides back-up protection for network faults which are not promptly disconnected
and thus may endanger the machine.
In order to ensure that pick-up always occurs even with internal faults, the protection
- for generators - is always connected to the current transformer set in the neutral
leads of the machine. If this is not the case for an individual power system, the I>>
stage can be combined with a short-circuit direction determination and switch off a
generator short circuit by way of an undelayed tripping.
Initially, the currents are numerically filtered so that only the fundamental waves of the
currents are used for the measurement. This makes the measurement insensitive to
transient conditions at the inception of a short-circuit and to asymmetrical short-circuit
currents (d.c. component).
For each stage, the time stage can be blocked via binary input, thus avoiding a trip
command. The time stage is restarted if the blocking is canceled during a pickup.
In generators where the excitation voltage is derived from the machine terminals, the
short-circuit current subsides very quickly in the event of close-up faults (i.e. in the
generator or unit transformer range) due to the absence of excitation current and decreases
within a few seconds to a value below the pick-up value of the overcurrent
time protection. For this reason, the overcurrent time protection includes an undervoltage
stage which maintains the pick-up signal I> for a set seal-in time if the positive sequence
component of the voltages drops below a set level following pick-up of the
overcurrent time protection, even if the overcurrent drops below the set value. In this
way, the running of the trip delay time and tripping of the associated circuit-breakers
is ensured even for those cases. The undervoltage influencing can be switched off and
made ineffective by means of a binary input.
6.2.1 Overcurrent Protection (Stage I>) with undervoltage seal–in
6.2.1.1 Functional description
I> stage Each phase-to-phase current is compared individually with the ,!_common setting
value and each overrange of the common setting value is signalled separately. As
soon as the corresponding 7_,!_time delay has elapsed, a trip signal is transmitted
to the matrix. In the delivery status of the device, the drop-out value is set about 95 %
below the pick-up value. For special applications, it is also possible to specify a higher
value.
The I> stage has a (disconnectable) undervoltage stage. This stage maintains the
pick-up signal for a selectable seal-in time if the value falls below a selectable threshold
of the positive-sequence component of the voltages after an overcurrent pickup -
even if the value falls again below the overcurrent value. In this way, the elapsure of
the trip time delay and the tripping of the related breakers is also ensured in these cases.
If the voltage recovers before the seal-in time has elapsed or if the undervoltage
seal-in is blocked via a binary input, e.g. in case of a tripping of the voltage transformer
protective breaker or in case of a machine stopping, the protective relay drops out immediately.
Functions
7UM61 Manual 6-19
C53000-G1176-C127-1
Fig 6-13 shows the logic diagram of the overcurrent time protection.
Figure 6-13 Logic diagram of the overcurrent stage I> with undervoltage seal-in
6.2.1.2 Programming settings for ttime-overcurrent protection
General The time-overcurrent protection feature is only effective and accessible if ____ 2_&_
3527__,! = (QDEOHG was specified at address 0112. 'LVDEOHG is specified if this
function is not needed.
Stage I> At address ____ 2_&_,!, the definite time-overcurrent stage I> may be switched 21
or 2)). As an alternative, it is also possible to block only the trip command (%ORFN_
UHOD\). The pickup value of the I> stage (set at address _____,!) should be set
above the maximum anticipated load current. Pickup due to overload should never occur
since the I> stage is designed only for fault protection. For this reason, a setting
equal to 120 % of the expected peak load is recommended for generators, and a setting
equal to 140 % of the expected peak load is recommended for transformers and
motors.
The trip time delay (parameter ____ 7_,!) must be coordinated with the time grading
of the network in order to ensure that the protective equipment next to the corresponding
fault location switches off first (selectivity).
The selected time is only an additional time delay and does not include the operating
time (measuring time, drop-out time). The delay can also be set to ∞. In this case, the
stage does not trigger after pickup. However, the pickup is signalled. If the I> stage is
FNo. 1966
>BLOCK I> I > BLOCKED
FNo. 1722
Pickup IL1>
Tripping
matrix
70LQ
75,3_&0'
Pickup IL3>
Pickup IL2>
OR
&
OR
OR
FNo. 1970
U< seal in
&
& OR
FNo. 1811
I > Fault L1
FNo. 1812
I > FaultL2
FNo. 1813
I > Fault L3
____ 7_,!
FNo. 1815
I > TRIP
>Useal-in BLK
FNo. 1950
Pickup U1<
Fuse Failure &
OR
&
____ 7_6($/_,1
SQ
R
____ 8__6($/_,1
OR
Functions
6-20 7UM61 Manual
C53000-G1176-C127-1
not required at all, 2_&_,! = 2)) is specified under address ____. In this case, there
is neither a pickup signalization nor a trip.
The _____8__undervoltage stage (positive-sequence voltage) is set to a value below
the lowest phase-to-phase voltage permissible during operation, e.g. 80 V.
The seal-in time _____7²6($/²,1 limits the pickup seal-in introduced by the overcurrent/
undervoltage. It must be set to a value higher than the 7,!_time delay.
The drop-out ratio r = Iab/Ian of the I> overcurrent pickup is specified at the address
_____,!_'287_5$7,2. The recommended value is r = 0.95. For special applications,
e.g. overload warning, it can be set to a higher value (0.98).
Example:
Pick-up value 1.4 ⋅ IN Mach.
Tripping time delay 3 s
Undervoltage seal-in 0.8 ⋅ UN Mach.
Seal-in time of U< 4 s
Drop-out ratio 0.95
Nominal current IN, Mach 483 A Nominal voltage UN, Mach 6.3 kV
Nominal current IN, transf., prim500 A Nominal voltage UN, transf., prim 6.3 kV
Nominal current IN, sec 1 A Nominal voltage UN, sec 100 V
The following secondary setting values result from this specification:
6.2.1.3 Settings for phase overcurrent protection
In the list below, the setting ranges and default setting values for the pickup currents
are for a device with a nominal current rating IN = 1 A. For a nominal current rating IN
= 5 A, multiply the setting options values and default setting values by 5. Consider the
current transformer ratios when setting the device with primary values.
1.4 ⋅ IN, Mach
IN, transf., prim
= --------------------------------- ⋅ IN, sec 1.4 ⋅ 483 A
500 A
=---------------------------- ⋅ 1 A=1.35 A
0.8 ⋅ UN, Mach
UN, transf., prim
= ----------------------------------- ⋅ UN, sec 0.8 ⋅ 6.3 kV
6.3 kV
=----------------------------- ⋅ 100 V=80 V
,!
8_
Addr. Setting Title Setting Options Default Setting Comments
1201 O/C I> ON
OFF
Block relay for trip commands
OFF Overcurrent Time Protection I>
1202 I> 0.10..8.00 A 1.35 A I> Pickup
1203 T I> 0.00..60.00 sec 3.00 sec T I> Time Delay
1204 U< SEAL-IN ON
OFF
OFF State of Undervoltage Seal-in
1205 U< 10.0..125.0 V 80.0 V Undervoltage Seal-in Pickup
Functions
7UM61 Manual 6-21
C53000-G1176-C127-1
6.2.1.4 Information list for phase overcurrent protection
6.2.2 Overcurrent protection (stage I>>) with direction
6.2.2.1 Functional description
I>> stage Each phase current is compared individually with the ,!!_common pick-up value and
signalled in case of an overrange. A trip signal is transmitted to the matrix as soon as
the corresponding 7_,!! time delays have elapsed. The drop-out value is about 95 %
below the pick-up value.
Direction detection The I>> stage is equipped with a (disconnectable) direction element
permitting a tripping
only for faults in backward (i.e. machine) direction.
For this reason, this stage can be used especially in cases where no current transformers
exist in the generator starpoint and if a disconnection via an undelayed tripping
is nevertheless to take place in case of generator faults (see figure 6-14).
Figure 6-14 Selectivity via short-circuit direction detection
1206 T-SEAL-IN 0.10..60.00 sec 4.00 sec Duration of Undervoltage Seal-in
1207 I> DOUT RATIO 0.90..0.99 0.95 I> Drop Out Ratio
FNo Alarm Comments
1722 >BLOCK I> >BLOCK I>
1950 >Useal-in BLK >O/C prot. : BLOCK undervoltage seal-in
1965 I> OFF O/C prot. stage I> is switched OFF
1966 I> BLOCKED O/C prot. stage I> is BLOCKED
1967 I> ACTIVE O/C prot. stage I> is ACTIVE
1811 I> Fault L1 O/C fault detection stage I> phase L1
1812 I> Fault L2 O/C fault detection stage I> phase L2
1813 I> Fault L3 O/C fault detection stage I> phase L3
1970 U< seal in O/C prot. undervoltage seal-in
1815 I> TRIP O/C I> TRIP
Addr. Setting Title Setting Options Default Setting Comments
G
backward
Functions
6-22 7UM61 Manual
C53000-G1176-C127-1
The direction is detected phase-selectively by means of a cross-polarized voltage.
The phase-to-phase voltage located perpendicular to the pointer of the fault current is
typically used as cross-polarized voltage (Figure 6-15). This is considered during the
calculation of the direction vector in the clockwise rotating phase sequence by way of
a rotation by +90° and in the anti-clockwise rotating phase by way of a rotation by –
90°. In case of phase-to-phase faults, the position of the direction straight line may
change in relation to the collapse of the short-circuit voltage.
Figure 6-15 Cross-polarized voltages for direction determination
The phase carrying the highest voltage is selected for the direction decision. In case
of equal current levels, the phase with the smaller number is chosen (IL1 before IL2 before
IL3). Table 6-2 shows the assignment of voltage and current values for the determination
of the fault direction for various types of short-circuit faults..
Table 6-2 Voltage and Current Values for the Determination of Fault Direction
Pick up Current Voltage
L1 IL1 UL2 – UL3
L2 IL2 UL3 – UL1
L3 IL3 UL1 – UL2
L1, L2 mit IL1>IL2 IL1 UL2 – UL3
L1, L2 mit IL1=IL2 IL1 UL2 – UL3
L1, L2 mit IL1<IL2 IL2 UL3 – UL1
L2, L3 mit IL2>IL3 IL2 UL3 – UL1
L2, L3 mit IL2=IL3 IL2 UL3 – UL1
L2, L3 mit IL2<IL3 IL3 UL1 – UL2
L3, L1 mit IL3>IL1 IL3 UL1 – UL2
L3, L1 mit IL3=IL1 IL1 UL2 – UL3
L3, L1 mit IL3<IL1 IL1 UL2 – UL3
L1, L2, L3 mit IL1>(IL2, IL3) IL1 UL2 – UL3
L1, L2, L3 mit IL2>(IL1, IL3) IL1 UL2 – UL3
UL3-L1
UL1-L2
UL1
UL3 UL2
UL2-L3 UL2-L3
UL3 UL2
UL1
Local phase sequences
Short circuit in phase L2–L3; cross-polarized voltage UL3 - L1
Remote phase sequences
Functions
7UM61 Manual 6-23
C53000-G1176-C127-1
If the phase-to-phase voltage used for the direction decision is below the minimum value
of 7 V, the voltage is taken from a voltage memory. This voltage also allows an unambiguous
direction determination if the short-circuit voltage has seriously collapsed
(short circuit close to generator terminals). After the expiration of the storage period (2
cycles), the detected direction is saved, provided that and as long as no sufficient
measuring voltage is available. If a short circuit already exists by the moment of the
generator startup (or, in case of motors or transformers, during connection), so that no
voltage is present in the memory and no direction can be determined, a tripping is executed.
The direction detection can be blocked via a binary input and thus made ineffective.
Figure 6-16 indicates the I>> stage logic diagram with the direction element.
Figure 6-16 Logic diagram of I>> stage with direction element
Pickup IL1>>
>BLOCK I>>
FNo. 1721
&
&
&
OR &
FNo. 1808
I>> picked up
70LQ
75,3_&0'
Tripping
matrix
____ 7_,!!
FNo. 1809
I>> TRIP
FNo. 1803
I >> Fault L3
FNo. 1802
I >> Fault L2
FNo. 1801
I >> Fault L1
FNo. 1956
I>> BLOCKED
OR
OR
OR
FNo. 1806
I >> forward
FNo. 1807
I >> backward
Direction
detection no
“1”
Forward
Reverse
undeterminable
____ 3KDVH_'LUHFWLRQ
Pickup IL3>>
Pickup IL2>>
&
&
&
>BLOCK dir.
FNo. 1720
Ux
Ix
Functions
6-24 7UM61 Manual
C53000-G1176-C127-1
6.2.2.2 Programming settings
General The I>> time-overcurrent stage of the time overcurrent protection can only be effective
and accessible if it was specified at address ____ 2_&_3527__,!! = 1RQ²'LUHF_
WLRQDO or 'LUHFWLRQDO within the framework of project configuration. 'LVDEOHG is
selected if the function is not needed.
I>>time-overcurrent
stage
At address _____2_&_,!!, the I>> definite time-overcurrent stage may be switched
21 or 2))___In addition to this, it is also possible to block only the trip command
(%ORFN_UHOD\). As a rule, the ,!!_time-overcurrent stage (parameter ____ and
corresponding
delay 7_,!!, ____) is used for current grading with large impedances existing
for example with transformers, motors or generators. The definite time-overcurrent
stage must be specified in a way ensuring that it picks up for short circuits up to
this impedance.
Current transformer
in the starpoint
(without direction detection)
Example: Block connection
a) Short-circuit current calculation:
Three-pole short circuit
b) Setting value:
The setting value is achieved by means of a conversion on the sedondary side. In or
to exclude an unwanted operation caused by overvoltages or transient phenomena,
an additional safety factor of about 1.2 to 1.3 is recommended
A value of 7,!! = 0,1 s is recommended as tripping time delay, in order to enable a
preferred tripping of the differential protection.
Rated apparent power - generator SN, G = 5.27 MVA
Rated voltage - generator UN, G = 6.3 kV
Direct-axis transient reactance x’d = 29 %
Transient synchronous generated voltage
(Salient-pole generator)
U’P =1.2 ⋅ UN, G
Rated apparent power - transformer SN, T = 5.3 MVA
Rated voltage, on the generator side UN, T = 6.3 kV
Short-circuit voltage uk = 7 %
Current transformer IN, prim =500 A
IN, sek =1 A
IK 3pol
U’P ⁄( 3)
x’d
100 %
----------------
UN, G
2
SN, G
⋅ -------------- 0.5
uK
100 %
----------------
UN, T
2
SN, G
+ ⋅ ⋅ -------------
------------------------------------------------------------------------------------------- 1.2 ⋅ 6.3 kV ⁄( 3)
2.18Ω + 0.26Ω
≈ ≈ --------------------------------------------- ≈ 1789 A
1.2
IK 3pol
IN prim
⋅ ---------------⋅ IN sec 1.2
1789 A
500 A
,!! = = ⋅ ------------------⋅ 1 A=4.3 A
Functions
7UM61 Manual 6-25
C53000-G1176-C127-1
Current transformer
on the output
side
(with direction
detection)
The addresses _____3KDVH_'LUHFWLRQ and _____/,1(_$1*/( are only accessible
if_2_&_3527__,!! was configured as 'LUHFWLRQDO_at the address ____ (see
section 5.1). The inclination of the direction straight line (see figure 6-17) representing
the separating line between the tripping and the blocking zone can be adapted to the
network conditions by way of the /,1(_$1*/( parameter. To do this, the line angle
of the network is set. The direction straight line is perpendicular to the set direction angle.
Together with the parameter _____3KDVH_'LUHFWLRQ = )RUZDUG or 5HYHUVH,
this parameter covers the entire impedance level. This is the UHYHUVH direction, provided
that the protective relay has been connected correctly according to one of the
diagrams in annex A.3. A small zone is located between the forward and the reverse
zone. Due to phase displacement angles of the transformers, a safe direction decision
is not possible in this small zone. Consequently, there is no tripping in the parameterized
preferred direction in this zone.
.
L1
IL1
IL2
IL3
$ODUP_RQO\
Θ =0
_____7,0(_&2167$17_
_____._)$&725
3URILEXV_'3 127_(;,67,1*
(Θ K = 40 °C) 70LQ
75,3_&0'
Tripping
matrix
____ Θ _$/$50
100 % (fix)
OR &
OR OR
&
>BLK ThOverload
FNo. 1503
FNo. 1515
O/L I Alarm
FNo. 1516
O/L Θ Alarm
FNo. 1521
ThOverload TRIP
FNo. 1512
Th.Overload BLK
FNo. 1513
Overload ACT
FNo. 1511
Th.Overload OFF
>RM th.repl.Θ
FNo. 1506
OR
%ORFN_UHOD\
FNo. 1517
1I2
In
---
2
∑ ⋅ ∆t
I2
Icool
Reset
I2=0
Functions
6-46 7UM61 Manual
C53000-G1176-C127-1
Pickup threshold /
warning stage
The pickup and delay settings associated with the unbalanced load protection are set
at addresses _____,_! and _____7_:$51 respectively.
IExample:
Negative sequence
factor K
If the machine manufacturer has indicated the loadability duration due to an unbalanced
load by means of the constant K = (I2/IN)2 ⋅ t, it is set immediately at the address
_____)$&725_.. The constant K is proportional to the permissible energy loss.
Conversion to secondary
values
The factor K can be derived from the unbalanced load characteristic according to figure
6-25 by reading the time corresponding to the )$&725_. at the point I2/IN = 1.
Example:
tperm =20 s for I2/IN =1
The constant KMachine = 20 s determined in this way is valid for the machine side.
The factor KMachine can be converted to the secondary side by means of the following
formula:
The asymmetry factor Ksec determined in this way is set as )$&725_. at address
____.
where I2 perm prim Permissible thermal inverse current of the machine
IN Machine Nominal machine current
ICT prim Primary nominal current of the current transformer
I2
I2perm prim
INMachine
---------------------------
INMachine
ICT prim
Pickup Setting = ⋅ -------------------------
Machine: IN Machine = 483 A
I2 perm prim / IN Machine = 11 % permanent (salient-pole
machine), see figure 6-25
Current
transformer:
IN CTprim = 500 A
Setting value I2 perm. = 11 % · (483 A/500 A) = 10.6 %
Example: IN Machine = 483 A
IN CT prim = 500 A
Factor KMachine = 20 s
Ksek KMachine
IN Machine
IN CTprim
------------------------
2
=⋅
Functions
7UM61 Manual 6-47
C53000-G1176-C127-1
Setting value at address ____:
Figure 6-25 Example of an unbalanced load characteristic specified by the machine manufacturer
Time for cool down The parameter _____7_&22/_'2:1 serves to specify the time elapsing until
the object
to be protected cools down to the original value, after a loading with the permissible
,_! unbalanced load. If the machine manufacturer does not provide any information
on this subject, the setting value can be found out by supposing an equal value
for the cool-down and the heating time of the object to be protected. The formula below
describes the relation between the K asymmetry factor and the cool-down time:
Example:
The following cool-down time results for a K = 20 s asymmetry factor and a I2/IN =
11 % permissible constant unbalanced load:
This value 7_&22/_'2:1 is set at address ____.
Definite time
elements
Asymmetrical faults also cause high negative phase-sequence currents. As, for reasons
of protection coordination, the thermal characteristic is limited to about ten times
the permissible negative phase-sequence current, an independent negative phase-
20 s 483 A
500 A
---------------
2
)$&725_. = ⋅ = 18.7 s
10 50 100 500 1000
0.06
1.0
0.5
0.4
0.3
0.1
0.2
0.11
t/s
I2/IN
maxim. permiss. I2/IN in permanent operation
maxim. permiss. I2/IN in case of a system fault
20 30 40
tcool down
K
(I2 ⁄ IN) 2
= ---------------------
tcool down
20 s
(0.11) 2
= ------------------- ≈ 1650 s
Functions
6-48 7UM61 Manual
C53000-G1176-C127-1
sequence current–stage characteristic _____,_!! can detect asymmetrical power
system short circuits. A setting to about 60 % to 65 % ensures that a trip is always performed
according to the thermal characteristic in case of a phase failure (unbalanced
load always < 100/√3 %, i.e. I2 < 58 %). On the other hand, a two-pole short circuit can
be supposed for an unbalanced load of more than 60 % to 65 %. The 7_,_!! time
delay (address ____) must be coordinated with the system grading of phase-tophase
short circuits.
Contrary to the time-overcurrent protection, the ,_!! stage is able to detect fault currents
at nominal current. The following conditions are valid:
− a phase-to-phase fault (I) results in the following negative sequence current:
− a phase-to-ground fault (I) corresponds to the following negative sequence current:
With an isolated starpoint, the I current value is particularly low and can be neglected.
With a low-resistance grounding, however, it is determined by the resistance.
6.5.2.1 Settings for unbalanced load protection
In the list below, the setting ranges and default setting values for the pickup currents
are for a device with a nominal current rating IN = 1 A. For a nominal current rating IN
= 5 A, multiply the setting options values and default setting values by 5. Consider the
current transformer ratios when setting the device with primary values.
I2
1
3
=------- ⋅ I=0.58 ⋅ I
I2
1
3
=--- ⋅ I=0.33 ⋅ I
Addr. Setting Title Setting Options Default Setting Comments
1701 UNBALANCE LOAD OFF
ON
Block relay for trip commands
OFF Unbalance Load Protection
1702 I2> 3.0..30.0 % 10.6 % Continously permissible current I2
1703 T WARN 0.00..60.00 sec 20.00 sec Warning Stage Time Delay
1704 FACTOR K 2.0..40.0 sec 18.7 sec Negativ sequence factor K
1705 T COOL DOWN 0..50000 sec 1650 sec Time for cool down
1706 I2>> 10..100 % 60 % I2>> Pickup
1707 T I2>> 0.00..60.00 sec 3.00 sec T I2>> Time Delay
Functions
7UM61 Manual 6-49
C53000-G1176-C127-1
6.5.2.2 Information list for unbalanced load protection
FNo Alarm Comments
5143 >BLOCK I2 >BLOCK I2 (Unbalance Load)
5146 >RM th.repl. >Reset memory for thermal replica I2
5151 I2 OFF I2 switched OFF
5152 I2 BLOCKED I2 is BLOCKED
5153 I2 ACTIVE I2 is ACTIVE
5158 RM th. repl. Reset memory of thermal replica I2
5156 I2> Warn Unbalanced load: Current warning stage
5165 I2> picked up I2> picked up
5159 I2>> picked up I2>> picked up
5160 I2>> TRIP Unbalanced load: TRIP of current stage
5161 I2 Θ TRIP Unbalanced load: TRIP of thermal stage
Functions
6-50 7UM61 Manual
C53000-G1176-C127-1
6.6 Underexcitation protection (ANSI 40)
General The underexcitation protection protects a synchronous machine from asynchronous
operation in the event of a malfunction in the excitation system and from local overheating
of the rotor. Furthermore, it prevents endangering of the network stability in
the case of underexcitation of large synchronous machines.
6.6.1 Functional description
Underexcitation
determination
In order to detect underexcitation, the unit processes all three phase currents and all
three voltages to form the stator circuit criterion. It also processes the excitation voltage
and/or the signal from an external excitation voltage monitor to form the rotor circuit
criterion.
For the stator circuit criterion, the admittance is calculated from the positive sequence
system of the currents and voltages. In the admittance plane, the stability limit of the
machine is independent of the voltage: thus, the protection characteristic can be optimally
matched to the stability characteristic of the machine. By evaluating the positive
sequence system, underexcitation conditions are reliably detected even during asymmetrical
faults within or outside of the machine.
Characteristics Figure 6-26 shows the loading diagram of the synchronous machine in the
admittance
plane (Iactive/U; Ireactive/U) with the steady-state stability limit which intersects the reactive
axis in close proximity to 1/Xd (reciprocal value of the synchronous direct reactance)
Figure 6-26 Admittance diagram of turbo generators
Ia
U
------ P
U2
= ------
IEN
UN
--------
IN
UN
-------
1
Xd
---------
Ir
U
---- Q
U2
= ------
ϑN
ϕN
UN rated voltage U terminal voltage
IN rated current Ia active current
IEN rated excitation current Ir reactive current
ϑ N rated pole angle P active power
ϕ N rated load angle Q reactive power
Xd synchronous reactance
underexcitated overexcitated
Functions
7UM61 Manual 6-51
C53000-G1176-C127-1
The 7UM61 underexcitation protection makes available three independent, freely
combinable characteristics. As illustrated in figure 6-27, it is, for example, possible to
model the static machine stability characteristic by means of two partial characteristics
with the same time delays (T CHAR. 1 = T CHAR. 2). The partial characteristics are
distinguished by the corresponding distance from the zero point (1/xd CHAR. 1) and
(1/xd CHAR. 2) the corresponding inclination angle α 1 and α 2.
If the resulting characteristic (1/xd CHAR.1)/α 1; (1/xd CHAR.2)/α 2 is exceed (in figure
6-27 to the left side), a delayed warning (e.g. by 10 s) or a trip signal are transmitted.
The delay is necessary to ensure that the voltage regulator can enhance the excitation
voltage.
Figure 6-27 Stator criterion: pick–up characteristic in admittance diagram
A further characteristic(1/xd CHAR. 3) /α 3 can be matched to the dynamic stability
characteristic of the synchronous machine. Since stable operation is impossible if this
characteristic is exceeded, immediate tripping is required in this case (7_&+$5____
time stage).
Excitation voltage
request
In case of a faulty voltage regulator or a failure of the excitation voltage, it is possible
to switch up with a short delay (time stage 7_6+57_8H[_, e.g. 1,5 s). For this purpose,
excitation voltage failure must be communicatee to the device via a binary input.
Undervoltage
blocking
The admittance calculation requires a minimum measurement voltage. During a severe
collapse (short-circuit) or failure of the stator voltages, the protection is therefore
blocked by an integrated a.c. voltage monitor.
Figure 6-28 illustrates the logic diagram of the underexcitation protection.
1/xd CHARl.1
characteristic 2
characteristic 3
characteristic1
α3 θ
α2
α1
Ia ⁄ U
Ir ⁄ U
E/U
I/U
1/xd CHAR.2
1/xd CHAR.3
Functions
6-52 7UM61 Manual
C53000-G1176-C127-1
Figure 6-28 Logic diagram of underexcitation protection
6.6.2 Functional settings
General The underexcitation protection is only effective and accessible if this function was set
within the framework of the protective function configuration (section 5.1, address
____, 81'(5(;&,7_ = (QDEOHG). If the funciton is not needed, it is set to 'LVDEOHG.
At address ____ 81'(5(;&,7__The function can be switched 21 and 2)). Additionally,
it is also possible to block only the trip command at this address (%ORFN_5HOD\).
The correct power system data input according to section 6.1.3 is another prerequisite
for the parameterization of the underexcitation protection.
FNr. 5328
OR
&
____ $1*/(__
____ __[G_&+$5___
>Char. 1 BLK.
FNo. 5329
____ $1*/(__
____ __[G_&+$5___
>Char. 2 BLK
FNo. 5330
____ $1*/(__
____ __[G_&+$5___
>Char. 3 BLK
FNo. 5327
>Uexc fail.
>Exc. BLOCK
FNo. 5323
&
&
____ 7_&+$5___
FNo. 5337
Excit < Pickup
FNo. 5344
Exc<1 TRIP
FNo. 5345
Exc< 2 TRIP
FNo. 5343
Exc<3 TRIP
____ 7_&+$5___
____ 7_&+$5___
OR
FNo. 5334
Exc. U< blk
FNo. 5332
Excit.BLOCKED
70LQ
75,3_&0'
Tripping
matrix
____ 7_6+57_8H[_
&
FNo. 5346
Exc<U<TRIP.
____ 8PLQ
Functions
7UM61 Manual 6-53
C53000-G1176-C127-1
The trip characteristics of the underexcitation protection in the admittance value diagram
are composed of straight lines which are respectively defined by their conductance
section 1/xd (= coordinate distance) and their inclination angle α . The straight
lines (1/xd CHAR.1)/ANGLE 1 (characteristic 1) and (1/xd CHAR. 2)/ANGLE 2) (characteristic
2) form the static underexcitation limit (see figure 6-29). (1/xd CHAR. 1) corresponds
to the reciprocal value of the related synchronous direct reactance.
If the voltage regulator of the synchronous machine features an underexcitation limiting,
the static caracteristics are set in a way that an intervention by means of the underexcitation
limiting is possible before characteristic 1 is reached (see figure 6-31).
Figure 6-29 Underexcitation protection characteristics in the admittance plane
Characteristiccurve
values
The setting can be performed immediately via the generator power diagram (see figure
6-30). If the axis sizes are divided by the nominal apparent power, the generator
diagram is indicated per unit (the latter diagram corresponds to a per unit representation
of the admittance diagram).
1
xd
----- 1
Xd
------
UN
3⋅ IN
= ⋅ -----------------
λ 3
λ 2
α 3 α 2
α 1
321 Ga
P SN ⁄
(U⁄ UN)2
= --------------------
1/xd CHAR.1
1/xd CHAR.2
1/λ x2d CHAR.3
Gr
Q SN ⁄
(U⁄ UN)2
= --------------------
Functions
6-54 7UM61 Manual
C53000-G1176-C127-1
.
:
Control During Operation
7-6 7UM61 Manual
C53000-G1176-C127-1
Figure 7-4 Selection of operational messages in DIGSI® 4
Figure 7-5 Example of operational messages in DIGSI® 4
7.1.1.3 Fault Messages (Trip Log)
Spontaneous Display
Messages
The spontaneous display messages appear automatically in the display, after a general
pick-up of the device. The most important data about a fault can be viewed on the
device front in the sequence shown in Figure 7-6.
Figure 7-6 Display of spontaneous messages in the display – example
The spontaneous display messages can be acknowledged by pressing the key.
After acknowledgment, the default display is shown.
Protective Function that picked up first;
Protective Function that dropped out last;
Running time from general pickup to dropout;
Running time from general pickup to the first trip command
8_!_SLFNHG_XS
6_(_)_75,3
38_7LPH______PV___
75,3_7LPH____PV
LED
Control During Operation
7UM61 Manual 7-7
C53000-G1176-C127-1
Retrieved
messages
The messages for the last eight network faults can be retrieved. The definition of a network
fault is such that the time period from fault detection up to final clearing of the
system fault is considered to be one network fault.
Altogether up to 600 indications can be stored. Oldest data are erased for newest data
when the buffer is full.
All available indications are displayed and explained in the Appendix. In a specific
case, of course, only the applicable messages appear on the display.
From the
Device Front
With a device ready for operation, first press the key. The 0$,1_0(18 appears.
The first menu item ($QQXQFLDWLRQ) is marked.
Press the key to enter the $1181&,$7,21 sub-menu (see Figure 7-1).
Using the key, select the sub-menu item 7ULS_/RJ and move to the Trip Log submenu
using the key. The 75,3_/2* selection appears.
In this sub-menu, the indications for the last 8 network faults can be selected, again
using the and keys. See the example in Figure 7-7.
If no messages are present for a fault, then entrance is denied and “/LVW_(PSW\” is
displayed.
The messages within a fault record are listed in chronological order and numbered,
from the oldest to the newest.
The inception of a fault is identified with the date and time in hours, minutes, and seconds
(resolution to ms). See the example in Figure 7-7.
The individual messages that are associated with the fault are tagged with a relative
time. At least one complete individual message always appears in the display.
Figure 7-7 Example of fault messages in the front display
Use the and keys to move up and down in the fault messages.
Use the key to move back into the 75,3_/2* level; or press the key to go back
to the 0$,1_0(18.
From PC with
DIGSI® 4
Click on $QQXQFLDWLRQ. The options appear in the data window (see Figure 7-2).
Double click on the desired message group in the data window, in this case the 7ULS_
/RJ. A list appears in the data window, as shown in Figure 7-8.
By double clicking on an entry in the list view, the associated contents of the network
fault is displayed in another window. The entries are chronologically listed with the
newest message appearing first.
MENU
___7_5_,_3___/_2_*________________________
!/DVW_)DXOW_____²!___
!_QG_/DVW_)DXOW_²!___
etc
_/_$_6_7___)_$_8_/_7______________________
___________________
1HWZRUN_)DXOW______21
MENU
:
Control During Operation
7-8 7UM61 Manual
C53000-G1176-C127-1
Figure 7-8 Selection of fault messages in DIGSI® 4
Figure 7-9 Example of fault messages in DIGSI® 4
7.1.1.4 Saving and Erasing the Messages
Normally, erasing the messages is not necessary because the oldest messages are
automatically erased when new events are entered, if the memory is full at the time.
However, erasure of the stored messages may be useful, for instance, after revision
of the plant, so that in the future the memory only contains information about actual
events. Erasing the memory takes place separately for each of the message groups.
Note:
When the fault messages are erased, then the fault records are erased, too, and all
corresponding counters are set to zero. If, however, a fault record is erased (cf. Sub-section
7.1.4), the fault messages are unaffected.
Control During Operation
7UM61 Manual 7-9
C53000-G1176-C127-1
From the
Device Front
If erasure is desired, first press the key. The 0$,1_0(18 appears. The first menu
item $QQXQFLDWLRQ is marked.
Press the key to enter the $1181&,$7,21 menu (see Figure 7-1).
Using the key, select the item 6HW_5HVHW, and switch to the sub-menu using the
key.
Here, select the message group to be erased using the key, and then press the
key. See Figure 7-10 as an example.
Password No. 5 (for setting changes) is required at this point. After entering the password
and confirming with the key, the safety question “$UH_\RX_VXUH?” appears.
The response “<(6” is the default (Figure 7-10). Confirm with the key, if
the message group should really be erased. If the message group should not be
erased, press the key so that the response “12” is highlighted, and confirm this answer
with the key. Before confirming with the key, the responses can be toggled
between “<(6” and “12” using the and keys. Alternatively, the key can
be pressed to cancel the erasure procedure.
Figure 7-10 Erasing messages from the front panel
From PC with
DIGSI® 4
When operating with DIGSI® 4, the device messages can be saved on the hard drive
of a personal computer before they are erased from the device. To do this, follow exactly
the same steps taken to retrieve the messages. Instead of double clicking on the
message group in the message list to open the group, select the option )LOH → 6DYH
in the DIGSI® 4 window menu bar. DIGSI® 4 then automatically creates a directory for
the messages — if one does not exist — and saves the message group in this directory.
For details, see the “DIGSI® 4 Device Operation” Handbook, order no. E50417–
H1176–C097, Section 9.4.
When all of the desired message groups have been saved on the PC, they can be
erased from the device as described above.
Of course, you can erase the saved data from the hard drive of your PC as every file.
MENU
ENTER
ENTER
ENTER
ENTER ENTER
ESC
_6_(_7___5_(_6_(_7________________________
!(YHQW_/RJ___________
!7ULS_/RJ____________
Etc
Select the associated message group or
press the associated number key to select
the messages to be erased.
$UH_\RX_VXUH"
!<HV______1R
Confirm “<HV” with the key and complete
the erasing of the selected messages,
or switch to “1R” with the key and
cancel the erasure with the key.
ENTER
ENTER
ENTER
3:_6HWWLQJV"
______ _______
Enter Password No. 5 (for setting change)
and confirm with ENTER
:
Control During Operation
7-10 7UM61 Manual
C53000-G1176-C127-1
7.1.1.5 General Interrogation
From PC with
DIGSI® 4
The present condition of a SIPROTEC® device can examined by using DIGSI® 4 to
view the contents of the “General Interrogation” annunciation.
The messages are found by double-clicking on $QQXQFLDWLRQ_(see Figure 7-2),
double-clicking on *HQHUDO_,QWHUURJDWLRQ, and double-clicking on the date and
time that appear in the right window. All of the messages that are needed for a general
interrogation are shown along with the actual values and states.
7.1.1.6 Spontaneous Messages
From PC with
DIGSI® 4
The spontaneous messages that can be retrieved using DIGSI® 4 represent the simultaneous
recording of presently occurring messages.
Find the message groups by clicking on $QQXQFLDWLRQ (Figure 7-2).
Double click 6SRQWDQHRXV_$QQXQFLDWLRQ in the data window. The date and time
appear in the data window. By double clicking on them, the Spontaneous Annunciation
window opens, as shown in the following figure. Each entering message appears immediately,
without requiring that an update be initiated.
Bild 7-11 Spontaneous annunciation window — example
7.1.2 Switching Statistics
The messages in switching statistics are, for example, counters for the accumulation
of interrupted currents by each of the breaker poles, the number of trips issued by the
device to the breaker. The interrupted currents are in primary terms.
Switching statistics can be viewed on the LCD of the device, or on a PC running
DIGSI® 4 and connected to the operating or service interface.
A password is not required to read switching statistics; however, a password is required
to change or delete the statistics.
:
:
Control During Operation
7UM61 Manual 7-11
C53000-G1176-C127-1
7.1.2.1 Viewing the Switching Statistics
For each trip command initiated by a protective element of the device, the magnitude
of interrupted current for each circuit breaker pole is determined and stored. The current
magnitudes are added to previously interrupted currents, and the accumulated
values are stored. The number of circuit breaker operations is counted in the device
based on the feedback information from the circuit breaker auxiliary contacts. A precondition
is that binary inputs are masked for counting.
In addition, the operating hours for the protected equipment are counted. The protected
equipment is considered to be in operation whenever the current threshold, set under
Address 0212 (%NU&ORVHG_,_0,1), is exceeded by at least one phase current.
The counter are retained during a loss of power supply voltage.
From the
Device Front
With a device ready for operation, first press the key. The 0$,1_0(18 appears.
The first menu item $QQXQFLDWLRQ is marked.
Press the key to enter the $1181&,$7,21 sub-menu (see Figure 7-1).
Use the key to select the item 6WDWLVWLF, and switch to the list of statistics values
using the key. The 67$7,67,& list appears. See Figure 7-12.
Figure 7-12 Switching statistics viewed from the front display
From PC with
DIGSI® 4
Under $QQXQFLDWLRQ (Figure 7-2), the switching statistics can be found by double
clicking. Double click on 6WDWLVWLF. The contents of the statistic counters is displayed
in another window. See Figure 7-13.
Figure 7-13 List of statistic values in DIGSI® 4 — example
MENU
_6_7_$_7_,_6_7_,_&_6______________________
_Σ ,/_ ____________N$
_Σ ,/_ ____________N$
Etc.
:
Control During Operation
7-12 7UM61 Manual
C53000-G1176-C127-1
7.1.2.2 Resetting and Setting the Switching Statistics
The memories and counters for switching statistics are secured against a loss of power
supply voltage. The values can, however, be set to zero, or to any desired value
within certain setting limits.
From the
Device Front
In the 67$7,67,& (see previous sub-section) sub-menu (see previous sub-section),
select the value to be set by using the key, and then press the key. See Figure
7-14 for an example of changing the trip counter. After a password is entered, the cursor
blinks and the number value is highlighted in a box. The number can be overwritten
using the number keys. If the new value is outside of the allowable range, either above
or below, then the maximum or minimum limit value appears at the bottom edge of the
screen. Confirm the change with the key.
Figure 7-14 Setting statistics values from the device front — example
From PC with
DIGSI® 4
In the 6WDWLVWLF window (see previous sub-section), mark the value that is to be set.
With the right mouse button, open a context menu and select 6HW. See Figure 7-15.
After the password for individual settings is entered, the previous value in the window
can be overwritten.
Figure 7-15 Setting statistic values in DIGSI® 4 — example
7.1.2.3 Setting Limit Values for the Statistics Counters
From the
Device Front
In the $1181&,$7,21 sub-menu, use the key to select the sub-item 6HW_5HVHW,
and enter this sub-menu. Use the key to select the item 6HW3RLQW_6WDW_ and
move with the key to set the Operating Hours Counter. See Figure 7-16. Then
press the key. After the password for individual settings is entered, the cursor
blinks and the counter value is highlighted with a box. The value can be overwritten
using the number keys. Confirm the change using the key.
ENTER
ENTER
2SHU__+UV_ ________
_0D[ 2147483648
ENTER 7ULS_&RXQW___
_
_6_7_$_7_,_6_7_,_&_6______________________
_∑,/_ _____________N$
_7ULS_&RXQW ______!__
:
ENTER
ENTER
Control During Operation
7UM61 Manual 7-13
C53000-G1176-C127-1
Figure 7-16 Setting the Limit Value, Example on the Front Display
The message “$UH_\RX_VXUH"” appears in the display, with the response “<HV” as
the default. Confirm with the key if a change to the limit value is really desired. If
a change to the limit value is not wanted, press the key so that the response “1R”
is higlighted, and confirm with the key. Before confirming with the key, the
and keys can be used to toggle between “<HV” and “1R.”
From PC with
DIGSI® 4
Move to the item 6HW_3RLQWV__6WDWLVWLF_ under 6WDWLVWLF in the
$QQXQFL_
DWLRQ. By double clicking, the associated contents are displayed in another window,
as shown in Figure 7-17. Overwriting the default value sets a new limit value. Entry of
password No. 5 for individual settings is required to do this.
Figure 7-17 Digsi® 4 Setting Statistics Values — Example
7.1.3 Measured and Metered Values
Operating measured values and metered values are determined in the background by
the processor system. They can be called up at the front of the device, read out via
the operating interface using a PC with DIGSI® 4, or transferred to a central master
station via the system interface (if available).
No password entry is required to view the measured or metered values. The values
are updated every few seconds.
Most measured values can be displayed in primary quantities, secondary quantities,
and percentages based on nominal values. A precondition for correct display is that
the nominal values be correctly set in the power system data.
ENTER 2S+UV_!______K
_6_(_7_3_2_,_1_7___6_7_$_7_________
2S+UV_!_!_____K
ENTER
ENTER ENTER
:
Control During Operation
7-14 7UM61 Manual
C53000-G1176-C127-1
7.1.3.1 Measured Values
Read-out of
Measured Values
In the 7UM61 with maximum functionality the following measured values are available:
• IL1, IL2, IL3, 3I0: phase currents and ground current, primary in A and kA, secondary
in A and in % of the device nominal current.
• IEE: ground current, primary in A and kA, secondary in A and in % of the device nominal
current.
• I1, I2: positive and negative sequence components of the currents, primary in A and
kA, secondary in A and in % of the device nominal current.
• UL1–E, UL2–E, UL3–E, U0: voltages, primary in kV, secondary in V sekundär and in %
of UN/√3.
• UL1–L2, UL2–L3, UL3–L1: voltages, primary in kV, secondary in V sekundär and in %
of UN.
• UE: displacement voltage, either directly measured or calculated as 3U0 = (UL1-E +
UL2-E + UL3-E), primary in kV, secondary in V and in % von UN/√3, provided that
phase–to–ground voltages are connected.
• U1, U2: positive and negative sequence components of the voltages, primary in kV,
secondary in V sekundär and in % of UN/√3.
• S, P, Q:Apparent, Real, and Reactive power; primary in in kVA or MVA or GVA, primary
in kW or MW or GW, primary in kVAR or MVAR or GVAR and in % of
SN = √3·UN·IN.
The active power is positive if address _____$&7,9(_32:(5 is set to = *HQHUD_
WRU for generator operation or = 0RWRU for motor operation, see Section 6.1).
• Power factor cosϕ:
The sign matches that of the real power.
• Power angle PHI between voltages and currents.
• f: frequency in Hz and in % of rated frequency.
• U/f: Over-excitation referred to the nominal excitation at UN and fN.
• U/f th.: Overtemperature calculated from the overexcitation, in % of the tripping temperature
rise.
• R, X: Resistance and reactance in Ω, primary and secondary.
• UE3h: Content of 3rd harmonic in the displacement voltage in V sekundär.
• Θ /Θ TRIP: Measured values of the overload protection for the stator winding per conductor,
in % of the tripping temperature rise.
• Igeg th.: Rotor overtemperature based on the negative-sequence component of the
currents in % of the tripping temperature rise.
• cooling medium temperature.
• Minimum and maximum values of the positive-sequence components I1 and U1, of
the active power P and the reactive power Q, of the frequency f, and of the content
of 3rd harmonic in the displacement voltage UE3h.
From the
Device Front
With a device ready for operation, first press the key. The 0$,1_0(18 appears.
Use the key to select the menu item 0HDVXUHPHQW, and switch to the list of measured
values using the key. The 0($685(0(17 selection appears. See figure 7-18.
MENU
Control During Operation
7UM61 Manual 7-15
C53000-G1176-C127-1
.
:
Control During Operation
7UM61 Manual 7-17
C53000-G1176-C127-1
8VHU_'HILQHG, i.e. measured values that have been defined by the user during
initial setting of the device (see section5.2),
(QHUJ\: see section 7.1.3.2
6HW_SRLQWV__0HDVXUHG_9DOXHV_: see section 7.1.3.3.
If a measured value is not available, then instead of the measured value, 3 dots appear.
If the value is undefined (e.g., cos ϕ , when no current is flowing), then “–––” appears
(3 horizontal bars). If the measured value overruns, then “” (3 asterisks)
are displayed.
Double click on the desired measure value group; e.g. 3ULPDU\_9DOXHV. The next
sub-group is displayed.
Double click on the desired sub-group; e.g. 2SHUDWLRQDO_YDOXHV__SULPDU\.
By double clicking on an entry in the list on the right side of the window, the associated
contents of the measured value group are displayed in another window, as shown in
Figure 7-21.
Figure 7-21 Example of measured values shown in DIGSI® 4
7.1.3.2 Energy, Metered Values
Retrieving of
Metered Values
In a 7UM61 device with the maximum configuration, counters are available that sum
the real and reactive energy (:S, :T) separately, according to reporting and recording
of the real energy and capacitive and inductive reactive energy, in the direction of the
protected object. This assumes that this direction is set as “forwards” (Address ____,
see Sub-section 6.1).
From the
Device Front
With a device ready for operation, first press the key. The 0$,1_0(18 appears.
Use the key to select the menu item 0HDVXUHPHQW, and switch to the list of measured
values using the key. The 0($685(0(17 selection appears. Select the item
MENU
Control During Operation
7-18 7UM61 Manual
C53000-G1176-C127-1
(QHUJ\ with the key and switch to the table of energy measurements using the
key.
Moving up and down in the table of energy measurements is done using the and
keys. The key can be used to return to the 0($685(0(17 level. Press the
key to return to the 0$,1_0(18.
From PC with
DIGSI® 4
The metered value groups can be found under 0HDVXUHPHQW (Figure 7-2) with a
double click.
Double click on 2WKHUV, then (QHUJ\.
By double clicking on an entry in the list view in the right side of the window, the associated
contents of the metered group are displayed in another window.
7.1.3.3 Setting and Retrieval of User Defined Set-points
In the 7UM61 measured value set-points can be configured with the user definable
logic CFC (see Section 5.3). If during normal operation a measured value reaches or
is above viz below one of these set-points, the device generates an alarm which is indicated
as an operational event. As is the case for all operational messages, it is also
possible in this case to output the information to LED and/or output relay and via the
interfaces.
When the 7UM61 is delivered from the factory, a low current monitor (,/_) for the
three phase currents is implemented only; further set-points can be defined, if their
measured and metered values have been configured accordingly with CFC (see section
5.3).
If such set-points were defined during the configuration of the device, they can be
viewed and — with password No. 5 — they can be changed:
From the
Device Front
With a device ready for operation, first press the key. The 0$,1_0(18 appears.
Use the key to select the menu item 0HDVXUHPHQW, and switch to the list of measured
values using the key. The 0($685(0(17 selection appears.
There, select the menu item 6HW_3RLQWV__09_ with the key, and switch to the
list of limit values using the key (see Figure 7-22).
MENU
:
MENU
Control During Operation
7UM61 Manual 7-19
C53000-G1176-C127-1
Figure 7-22 Setting Limit Values at the Front Panel — Example
To change a limit value, mark the specific value using the and keys, and then
press the key.
A request for Password No. 5 (for settings parameters) is given. After password entry
and confirmation with the key, the previous value appears in a box with a flashing
cursor. Overwrite the previous value with the desired new value using the number
keys. If the entered value is outside the allowable value range, then the maximum or
minimum limit value appears at the bottom of the display.
Press the key. The new value appears in the list of limit values.
Other limit values can be changed in the same manner.
Upon leaving this level using the or keys, the safety inquiry “$UH_\RX_VXUH"”
appears, with the default answer “<HV” (Figure 7-22). Confirm with the key if the
value should become effective. If a change to the value is not desired, press the
key so that the answer “1R” is marked, and confirm this with the key. To correct
the value, mark “(VFDSH”, confirm this with the key, and enter the value again.
From PC with
DIGSI® 4
Double click on 0HDVXUHPHQW (Figure 7-2). Select 2WKHU and then 6HW_3RLQWV_
_0HDVXUHG_9DOXHV_.
By double clicking on an entry in the list view in the right side of the window, the limit
values are loaded. Mark the number of the value that is to be changed. With the right
mouse button, open the context menu and click on 6HW, as shown in Figure 7-23. A
password inquiry (password for individual settings) occurs. Next, the dialogue field
6HW_0HWHUHG_9DOXH is opened. Enter the desired value in the entry field. Then click
on 2..
The entered value is transferred to the device and the display within the window in Figure
7-23 is updated.
_0_(_$_6_8_5_(_0_(_1_7___________________
!6HW_3RLQWV_09_______
!5HVHW_______________
Etc.
ENTER
_6_(_7___3_2_,_1_7_6_____0_9______________
,/_______!!_____
_FRVϕ __________
ENTER 3:_6HWWLQJV"
___ _______
Enter Password No. 5 (individual settings)
and confirm with ENTER
,/__________________
ENTER
$UH_<RX_6XUH"
!<(6_12_(VFDSH_
ENTER
ENTER
ENTER
MENU
ENTER
ENTER
ENTER
:
Control During Operation
7-20 7UM61 Manual
C53000-G1176-C127-1
Figure 7-23 Setting of set-points in DIGSI® 4 — example
7.1.3.4 Resetting Metered Values and Min/Max Values
Metered values and minimum/maximum values can be reset.
From the
Device Front
With a device ready for operation, first press the key. The 0$,1_0(18 appears.
Use the key to select the menu item 0HDVXUHPHQW, and switch to the list of measured
values using the key. The 0($685(0(17 selection appears.
Using the key, select the menu item 5HVHW and switch to the reset possibilities using
the key. See Figure 7-24.
Figure 7-24 Resetting Metered Values and Min/Max Values Using the Front Panel.
Moving up and down in the table is done with the and keys.
To reset a values, mark the values using the and keys, and then press the
key. The reset command is offered as “21”.
Press the key. The display confirms with “&KDQJH_2._&RQWLQXH”.
Confirm once again with the key. The reset is complete.
Other counters are reset in the same manner.
Use the key to return to the 0($685(0(17 sub-menu; press the key to return
to the 0$,1_0(18.
When the 7UM61 is delivered from the factory, function key 4 allows quick and simple
jumpingto the reset menu of the min/max values (see Figure 7-24).
MENU
_5_(_6_(_7______________________________
!5HV0LQ0D[______!_21
!0HWHU_UHV________21
ENTER
ENTER
ENTER
MENU
Control During Operation
7UM61 Manual 7-21
C53000-G1176-C127-1
From PC with
DIGSI® 4
Resetting of limit values, metered values, min/max values, or statistics values always
takes place in a group.
To set values to zero, right click on the group in the navigation to open a context menu.
Click on 5HVHW.
7.1.4 Fault Records
Waveform or rms data is stored in the device and can be graphically represented on
a personal computer using DIGSI® 4, together with the graphic program DIGRA® 4.
The settings associated with fault recording — such as duration and pre- and post-trigger
times — had been are set according to Chapter 6.
7.1.4.1 Viewing Fault Records
From PC with
DIGSI® 4
To view the fault recording data on a screen, one of the programs DIGRA® 4 or Comtrade
Viewer (included with SIMATIC Manager) is needed. Do the following:
Double click on 2VFLOORJUDSKLF_5HFRUGV (Figure 7-25). The folders listed in the
right window show an overview of oscillographic records. The records are identified
with a network fault number, a fault record number, and the date and time.
By double clicking on an fault record in the list view in the right side of the window, one
of the above programs is opened, and the selected waveform data are loaded. (See
also DIGSI® 4, Operating Handbook, order no. E50417–H1176–C097, Sub-section
8.3.3).
Figure 7-25 Retrieval of fault records in DIGSI® 4
:
Note:
By selecting the 5HVHW command, all values are reset to zero without further inquiry.
This procedure cannot be undone.
:
Control During Operation
7-22 7UM61 Manual
C53000-G1176-C127-1
DIGRA® 4 provides support in the analysis of faults on the power system. The program
graphically prepares the data recorded during a fault, and calculates additional
measurement quantities, such as impedances or rms values.
The quantities can be represented in these views:
• Time signals
• Phasor diagrams
• Locus diagrams
• Harmonics
Selection takes place using the menu bar (9LHZ), or clicking in the symbol bar above
the represented switching fields. Figure 7-26 shows all four views simultaneously.
The recorded data read into the PC memory are first shown in full on the screen. Current,
and possibly voltage, for each phase and the ground are represented separately.
The fault number, data and time, network, and feeder are also displayed.
Representation of primary or secondary quantities can be selected. The base values
for currents and voltages are the nominal values of the transformers (CTs or VTs). An
identical scale is used for all currents, relative to the largest occurring current value,
and for all voltages, relative to the largest occurring voltage value.
Figure 7-26 DIGRA 4, Diagrams in the Four Possible Views
During configuration any signal can be selected in its properties to be displayed in the
fault record. (See chapter 5.2.3.)
Further details about the many possibilities that DIGRA® 4 offers can be found in the
DIGRA handbook (Order No. E50417–H1176–C070).
Control During Operation
7UM61 Manual 7-23
C53000-G1176-C127-1
7.1.4.2 Saving the Fault Records
Storage of Fault
Recording Data
Oscillographic records that are received from the device are not automatically saved
in the PC. The data can, however, be saved in files.
For more details, see the DIGSI® 4 Operating Handbook, Order No. E50417–H1176–
C097, Section 9.4.
The oscillographic records stored in the device do not need to be erased, since the
data are stored in a revolving buffer. The oldest data are automatically overwritten by
the newest data.
Control During Operation
7-24 7UM61 Manual
C53000-G1176-C127-1
7.2 Control of Device Functions
You may change individual functions and messages in a 7UM61 while the device is inservice.
Some examples are given above, including erasing stored information (Subsection
7.1.1.4) and setting/resetting counters and set-points (Sub-sections 7.1.2.2
and 7.1.3.4). In this section, three other control capabilities are discussed. They are
correcting the date and time, changing the settings group, and affecting information at
the system interface during test operations.
7.2.1 Read and Set Date and Time
The 7UM61 device can be connected to an external clock source, binary input or use
the internal RTC for time and date stamping.
Time Status Besides the display of date and time, the status of these readings is also provided.
The
text of the status display can have the appearances given in Table 7-1, under regular
conditions of time control.
The text symbols, or “status bits”, for the time status have the following meanings:
Representation of
the Time
Various representations of the date and time stamp may be given in the '$7(_7,0(
sub-menu and in all messages stamped with the date and time. The year number
stored in the device and the values of the status bits “Not synchronized” and “Time er-
Table 7-1 Time Status
Status Bits No.
___________ 1
synchronized
_________67 2
______(5___ 3
______(5_67 4 not synchronized
___16_(5___ 5
___16______ 6
16 Not synchronized Time was neither set manually nor synchronized after
power-up.
(5 Time error At the moment, there is no cyclical synchronization
within the tolerance times (time can jump)
67 Daylight savings
time
The latest synchronization signal received supplied a
daylight savings time bit
Control During Operation
7UM61 Manual 7-25
C53000-G1176-C127-1
ror” determine the representations. The possible representations and the associated
causes are listed in Table 7-2.
? appearing in the date and time field indicate that the clock synchronisation has been lost.
Item 1 appears if the internal clock RTC did not have a valid time upon start-up. The
messages in the memory buffers are dated 01/01/1990.
Corrective action: Set the date and time manually (see margin header “Changing the
Time” below).
Item 2 appears if the time was actually set, but not synchronized. This can happen:
− briefly upon device power-up,
− if synchronization is lost; that is, if the cyclical synchronization is interrupted for a
time longer than the set tolerance time.
Corrective action: If an external synchronizing source is being used, check the source
and the connection.
Item 3 is displayed if the RTC had a valid value upon device start-up but the time was
neither manually set nor synchronized since.
Corrective action: Set the date and time manually, or wait until the cyclical synchronization
takes effect.
Item 4 displays the normal condition; that is, the time is synchronized cyclically according
to the type of operation.
Item 5 is displayed if synchronization via the system interface is marked as “invalid”.
Changing the Time The time can be changed
− By setting the time manually, using the integrated control panel or DIGSI® 4;
− By adjusting the settings for time control.
The date and time can be manually set during operation, provided the device allows
this. A precondition is that the appropriate type of operation for time control must be
selected (see Section 5.7).
When the source of time synchronisation is “internal” or “pulse via binary input” the
date and time can be manually set during operation at any instant. The annunciations
“time error ON” and “time error OFF” appear in the annunciation log to indicate time
synchronization and loss of time synchronization, respectively.
In the other operating modes, manual adjustments are only accepted if the synchronization
is momentarily lost. The messages “time error ON” and “time error OFF” are given
when manually changing the year in the IRIG B mode.
Table 7-2 Representations of Date and Time:
Item Display (Example) Year Time Error Time Invalid
Date Time
1 HH_HH_HHHH __"_____ Year = 1990 irrelevant
2 __________ __"_____
1990<Year<2090
Yes No
3 __"_______ __"_____ Yes Yes
4 __________ ________ No No
5 HH"HH_HHHH __"_____ No Yes
Control During Operation
7-26 7UM61 Manual
C53000-G1176-C127-1
Without healthy or external time synchronisation the free running date and time can
also be relatively adjusted (+/– 23:59:59) using the entry field 'LII_²WLPH.
This input possibility is not to be confused with the parameter 2IIVHW (see Section
5.7), which affects the specific general offset to the received synchronization time of
the radio clock receiver (e.g. local time vs. GMT time).
From the
Device Front
With a device ready for operation, first press the key. The 0$,1_0(18 appears.
Select 6HWWLQJV, and in the sub-menu 6(783_(;75$6. To set the date and time
manually, choose the selection 'DWH_7LPH and move to the '$7(_7,0( display using
the key. See Figure 7-27.
Figure 7-27 Manual date and time adjustment from the front panel
To change one of the previous settings (date, time, differential time), mark the item using
the and keys, and then press the key.
The actual setting appears in a frame with a blinking cursor. Overwrite this setting with
the desired new one using the number keys. Be careful to enter the format properly.
Confirm the change with the key.
To change the time offset or the tolerance time for a clock error signal, select &ORFN_
6HWXS under 6(783_(;75$6, as shown in Figure 7-28. Under 2IIVHW, the time offset
can be changed. Under (UURU_7LPH, the time delay for the alarm can be adjusted.
These adjustments are done in the same manner as setting the time, by overwriting
the displayed values and confirming with the key.
To return to the S(783_(;75$6 level, press the key, several times if necessary. To
return to the 0$,1_0(18, press the key.
Figure 7-28 Date and time settings from the front panel
From PC with
DIGSI® 4
To manually change the date and time of the device:
Click on 'HYLFH in the menu bar as shown in Figure 7-29. Select the command 6HW_
&ORFN.
MENU
_6_(_7_8_3___(_;_7_5_$_6________________
!'DWH_7LPH_____²!___
!&ORFN_6HWXS___²!___
'$7(_7,0(
6WDWXV______________
!___________________
'LII_²WLPH__________
ENTER
ENTER
ENTER
MENU
_6_(_7_8_3___(_;_7_5_$_6________________
!'DWH_7LPH_____²!___
!&ORFN_6HWXS___²!___ &/2&._6(783_________
____________________
_2IIVHW________!_PLQ
_(UURU_7LPH______PLQ
_6RXUFH_____,QWHUQDO
:
Control During Operation
7UM61 Manual 7-27
C53000-G1176-C127-1
Figure 7-29 Selecting the command 6HW_&ORFN in DIGSI® 4
A dialog field, 6HW_FORFN_ _GDWH_LQ_GHYLFH, is opened. The displayed values
are the present date and time. The day of the week is automatically derived from the
date — and cannot be edited.
• Edit the input fields 'DWH and 7LPH. The format depends on your regional settings
of the PC. See Figure 7-30.
Date: mm/dd/yyyy or dd.mm.yyyy
Time: hh.mm.ss
Click on 2. to transfer the entered values into the device. The previous values are
changed and the dialog field is closed.
Figure 7-30 Dialog Field: 6HW_FORFN_ _GDWH_LQ_GHYLFH
• To change the time offset or tolerance time for clock signal error, double click on
6HWWLQJV in the navigation window. See Figure 7-31.
Control During Operation
7-28 7UM61 Manual
C53000-G1176-C127-1
Figure 7-31 Setting window in DIGSI® 4
Double click on 7LPH_6\QFKURQL]DWLRQ in the data window. This give access to
change (Figure 7-32):
− Source of time synchronisation,
− Monitoring (Time delay for alarm),
− Time format for display,
− Time correction (offset to the time signal).
Figure 7-32 Time synchronization and time format settings in DIGSI® 4
Control During Operation
7UM61 Manual 7-29
C53000-G1176-C127-1
7.2.2 Switching Setting Groups
Two different setting groups for the protective functions may be available. The active
group can be changed onsite while the 7UM61 is in-service by using the integrated
operating field on the device or the operating interface on a PC running DIGSI® 4. Alternatively,
you may decide that the active setting group be remotely controlled via binary
inputs or the system interface.
Password No. 5 (password for individual settings) is required to change setting
groups.
The first setting group is called group A, the other is group B. If setting group changing
is to be used, then settings for the groups to be employed must have been entered
(see Section 6) and the switching process must be (QDEOHG under Address ____
*US_&KJH_237,21.
From the
Device Front
When the device is ready for operation, first press the key. The 0$,1_0(18 appears.
Using the key, select the menu item 6HWWLQJV and switch to the settings with the
key. The selection 6(77,1*6 appears.
Using the key, select the item &KDQJH_*URXS and move to the selection of groups
with the key. The sub-menu &+$1*(_*5283 appears, as shown in Figure 7-33.
The first Address ____ is marked. The address displays the setting group presently
in effect (in Figure 7-33, the active group is *URXS_$).
Using the key, select Address ____ and confirm with the key.
Enter the password for individual settings, and confirm.
Using the key, select one of the two groups A or B give control to another source.
If %LQDU\_,QSXW (activation using binary inputs) is selected, setting group switching
is controlled by binary inputs, provided appropriate configuration has been done and
the necessary physical connections are present (see Section 5.2).
If YLD_3URWRFRO is chosen, setting group changes can be controlled via the system
serial interface.
MENU
ENTER
Control During Operation
7-30 7UM61 Manual
C53000-G1176-C127-1
Figure 7-33 Switching setting groups from the front panel
Control of the setting groups can always be regained by switching to one of the groups
A or B.
The key can be used to return to the 6(77,1*6 sub-menu; the key can be
pressed to returns to the 0$,1_0(18.
From PC with
DIGSI® 4
By opening the 2QOLQH directory with a double click in DIGSI® 4, the operating functions
for the device appear in the left part of the window. See Figure 7-34.
Figure 7-34 Function selection window in DIGSI® 4
Double click on 6HWWLQJV to find &KDQJH_*URXS in the data window (Figure 7-34
right).
_&_+_$_1_*_(___*_5_2_8_3________________
_____$&7,9(_*5283___
_____*URXS_$
The currently-active setting group is displayed
under Address ____.
The setting group can be changed under Address
____: by pressing the key, after
entering the password, two possible alternatives
are displayed in a new window each
time:
Using the keys, select one of the alternatives
and confirm with the key;
The next question (“$UH_\RX_VXUH"”) is answered
with <HV and the selected alternative
is confirmed, or is answered with 1R using the
key and the change is cancelled with the
key.
ENTER
ENTER
ENTER
$UH_\RX_VXUH"
ENTER <HV________1R__
_____&+$1*(_WR_
____!*URXS_$
!*URXS_$
_*URXS_%
_YLD_%LQDU\_,QSXW
_YLD_3URWRFRO
MENU
:
Control During Operation
7UM61 Manual 7-31
C53000-G1176-C127-1
Double click on &KDQJH_*URXS. The &KDQJH_*URXS window is opened, as shown
in Figure 7-35.
Figure 7-35 Setting group switching in DIGSI® 4
The active setting group is displayed. To switch to another setting group, click on the
field 9DOXH and select the desired option from the drop-down list. Before closing the
window, transfer the change to the device. This is done by clicking on the button
'LJVL_→_'HYLFH. A request for Password No. 7 (password for setting groups) is
given. Enter the correct password, and then click on 2..
7.2.3 Controlling Information to the System Interface during Test Operation
You may influence the information transferred via the system interface from the device
to a central master control station.
Depending on the type of protocol, all messages and measured values transferred via
the system interface can be marked with an added “test mode”–bit while the device is
being tested onsite (test mode). This identification prevents the messages from being
incorrectly interpreted as resulting from an actual power system fault or event. As another
option, all messages and measured values normally transferred via the system
interface can be blocked during the testing (“data transmission block”).
These facilities can be accomplished by controlling binary inputs, by using the operating
panel on the device, or via DIGSI® 4.
If binary inputs are used, then the appropriate inputs must be configured.
The password for test and diagnostics is required to switch to “test mode” or “data
transmission block” from the device front or PC.
Control During Operation
7-32 7UM61 Manual
C53000-G1176-C127-1
From the
Device Front
With the device ready for operation, first press the key. The 0$,1_0(18 appears.
Using the key, highlight the menu item 7HVW_'LDJQRVH, and then press the
key to enter sub-menu. 7(67_',$*126( will appear at the top of the menu.
At this point, highlight the menu item 7HVW_(QDEOH using the key, and then press
the key to enter sub-menu. 7(67_(1$%/( will appear at the top of the menu. See
Figure 7-36.
Figure 7-36 Applying test mode from the front panel
To switch to test mode, press the key, enter the password for test and diagnostics,
and confirm with the key. A new window appears with the options 21 and
2)). Use the and keys to select the desired mode, and press the key. The
question “$UH_\RX_VXUH"” is displayed. Highlight the desired response and press
the key. If the mode is changed, the device responds with the message “&RQ_
WURO_([HFXWHG”.
Use the key to return to the 7(67_',$*126( level; press the key to return to
the 0$,1_0(18.
The procedure for changing the Block Data Transmission mode is the same. See Figure
7-37 (simplified).
Figure 7-37 Applying data transmission block from the front panel (simplified)
The settings for the test mode and the data transmission block are normally 2)). Definitions:
− 7HVW_PRGH – With the 21 setting, the “test mode“-bit is transferred for messages
compatible with IEC 60870–5–103.
− 'DWD6WRS – With the 21 setting, no messages or measured values are transferred
(“data tranmission block”).
From PC with
DIGSI® 4
Click on 'HYLFH in the menu bar to reach the commands %ORFN_'DWD_7UDQVPLV_
VLRQ or 7HVW_0RGH. See Figure 7-38.
MENU
_7_(_6_7___(_1_$_%_/_(_________
!7HVW_PRGH_______2))
_
_7_(_6_7___'_,_$_*_1_2_6_(______________
_'HYLFH_5HVHW__²!___
!7HVW_(QDEOH___²!___
_%ON_'DWD_7UDQV²!___
_+DUGZDUH_7HVW_²!___
_6HW_5HVHW_____²!___
ENTER
ENTER
ENTER
ENTER
MENU
_7_(_6_7___'_,_$_*_1_2_6_(______________
!%ON_'DWD_7UDQV²!___
_+DUGZDUH_7HVW_²!___ _%_/_.___'_$_7_$___7_5_$_1_6______
!'DWD6WRS_______2))
_
:
Control During Operation
7UM61 Manual 7-33
C53000-G1176-C127-1
Figure 7-38 Applying “Test Mode” or “Block Data Transmission” in DIGSI® 4
Click on %ORFN_'DWD_7UDQVPLVVLRQ to activate or deactivate the transfer block.
After entry of Password No. 4 for test and diagnostics, and confirmation with 2., the
setting change is complete.
Activation is indicated with a check mark in front of the command.
Follow the same procedure for the command 7HVW_0RGH, if this option is desired.
Note:
Remember to change the settings for Test Mode or Block Data Transmission back
to the desired, in-service settings (both typically 2))) when the tests are complete.
Control During Operation
7-34 7UM61 Manual
C53000-G1176-C127-1
7.3 Control of Switchgear
A SIPROTEC® 4 device 7UM61 contains control functions that allow for opening and
closing of power system switching devices (i.e. circuit breakers). Local control is possible
utilizing different elements of the 7UM61. Breaker control from a remote location
is also possible using the SCADA interface or DIGSI® 4. (Performing control functions
with a PC running DIGSI® 4, connected to the front serial port, is considered a “remote”
operation for breaker control purposes.) Some control actions from a 7UM61 include
unsynchronized commands for circuit breakers, circuit switchers, ground switches,
etc., and stepping commands for increasing or decreasing transformer LTC steps.
Safety mechanisms in the command path ensure a command can only take place if
the check of previously defined safety criteria is concluded positively.
If a power system switching device has auxiliary contacts that indicate the position of
the device and these contacts are connected to the 7UM61 and configured as doublepoint
indications then the switching device provides feedback indication that are monitored
for plausibility of control actions. If a switching device does not indicate either
the closed or open position, the display for the switching device indicates an unvalid
position in the 7UM61. All subsequent control operations to the equipment are interlocked.
Control from a 7UM61 to a power system equipment can originate from four sources:
− Local operation using the operator control panel,
− Binary inputs,
− Remote operation using the SCADA interface,
− Operation with a PC, via the operating interface and DIGSI® 4.
Switching priority for the four command sources is set using the Switching Authority.
For Interlocked Switching, all programmed interlocking conditions are checked before
a control operation is performed. If one of the conditions is not met, then the command
is rejected and an error message is recorded and displayed. Fixed, predefined, standard
interlocking features are implemented in the 7UM61 and can be configured (activated)
for the specific application. The following tests can be activated (on) or deactivated
(off) for a switching device:
• Device Position (check SCHEDULED = ACTUAL comparison).
• Substation controller,
• Zone controlled (Field interlocking e.g., logic in CFC),
• Blocking by protection (control operations blocked by protective functions),
• Double operation (blocking of multiple control operations),
• Switching authority (Local/Remote),
Control During Operation
7UM61 Manual 7-35
C53000-G1176-C127-1
7.3.1 Display Equipment Position and Control
From the
Device Front
With a device ready for operation, first press the key. The 0$,1_0(18 appears.
Using the key, select the menu item &RQWURO, and go to editing the control functions
with the key. The selection &21752/ appears (See Figure 7-39).
Figure 7-39 Control Selections from the Front Panel
Select, by means of the key, the item %UHDNHU_6ZLWFK, and continue with the
item by pressing the key. The selection %5($.(5_6:,7&+ appears. See Figure
7-40.
Select_'LVSOD\ (default) and press the key. The selection ',63/$< appears, in
which the positions of all planned switching devices can be read out.
Figure 7-40 Display of Switch Positions in the HMI (example)
The key can be used to return to %5($.(5_6:,7&+.
To control a switching device, select the option &RQWURO in the %5($.(5_6:,7&+
sub-menu and press the key to go to the table of operating resources that can be
controlled. See Figure 7-41. All planned switching devices appear. The actual position
of each switch is displayed first. Use the and keys to move to the desired
switch.
Figure 7-41 Control of Switching Devices from the Operator Control Panel
Select the switch to be controlled using the and keys and press the key.
MENU
_&_2_1_7_5_2_/__________________________
!%UHDNHU_6ZLWFK_²!__
_7DJJLQJ________²!__
_0_$_,_1___0_(_1_8______________________
_0HVVXUHPHQW____²!__
!&RQWURO________²!__
_'_,_6_3_/_$_<__________________________
!__%UHDNHU______23(1
!'LVF_6ZLW______&/26
_%_5_(_$_._(_5___6_:_,_7_&_+____________
!'LVSOD\_______²!___
!&RQWURO_______²!___
_%_5_(_$_._(_5___6_:_,_7_&_+_____________
!'LVSOD\________²!__
!&RQWURO________²!__ _&_2_1_7_5_2_/__________________________
___%UHDNHU_____!&/26
_'LVF_6ZLW______&/26
_*QG6ZLW________2))
ENTER
Control During Operation
7-36 7UM61 Manual
C53000-G1176-C127-1
Enter Password No. 1 (for interlocked switching) and acknowledge with the key.
Note: if the switching mode is 121²,17(5/2&.('__7HVW_ (Sub-section 7.3.7), all
switching operations are only possible with Password No. 2 (for non-interlocked
switching).
A new window appears. Depending on the operating and command type of the selected
switching device, various options are offered. Move between them using the and
keys.
Figure 7-42 Selection Window for Control Operations on the Front Panel (example)
To perform control, confirm with the key. A safety inquiry appears, “$UH_\RX_
VXUH"”. If the response is “<(6”, the switching operation is initiated (provided the Local
command is allowed). A message is displayed and recorded indicating the results
of the control action. Acknowledge this by pressing the key once again.
The command is not executed if the switching operation is restricted. The operation
may be restricted for reasons pertaining to, for example, switching authority (see Subsection
7.3.6) or interlocking (see Sub-section 7.3.7). A message is displayed and recorded
indicating the results of the control action. Acknowledge the message by
pressing the key. Parameters to set control properties can be examined in the
display. Refer to Sub-section 7.3.4.
The key can be used to return to %5($.(5_6:,7&+. Press the key to return
to the 0$,1_0(18.
From PC with
DIGSI® 4
When the 2QOLQH window in DIGSI® 4 is opened with a double click, the operating
functions for the device appear in the left part of the window (Figure 7-34). Clicking on
&RQWURO displays the associated function selection in the data window. See Figure 7-
43.
Figure 7-43 Window for Control of Operating Resources in DIGSI® 4
By double clicking on %UHDNHU_6ZLWFKHV, a dialog field is opened in which the
present status of each switch is visible. See Figure 7-44. Control can be performed
from this dialog box provided the switching authority is set to 5(027(.
ENTER
&_2_1_7_5___!_2_3_(_1___________________
___%U__&/26(______21
_'LVF__(VFDSH_____21
ENTER
ENTER
ENTER
MENU
:
Control During Operation
7UM61 Manual 7-37
C53000-G1176-C127-1
The switching authority is first transferred to DIGSI® 4 at the moment the control window
shown in Figure 7-44 is opened. The configuration matrix discussed in Section
5.2 determines the control devices that have information displayed in this field.
Figure 7-44 Dialog Box for Performing Control in DIGSI® 4
A description of the switching device is displayed in the left column of the dialog field.
This represents the contents of the /RQJ_7H[W column within the configuration matrix.
The actual position of the switch is displayed in the 6WDWXV column (23(1,_&/26(,
,QWHUPHGLDW). The switching possibilities are displayed in the 6FKHGXOHG column.
Four control fields are shown in the right part of the dialog field. If a check mark is displayed
in one of these fields, ,% (Block Input Acquisition), 7% (Transmission Block =
Serial Interface Blocked), 68 (Manual Overwriting), and '% (Chatter Block), the associated
block function is set or the feedback indications of the device have been simulated.
Normally, operating devices are switched in the LQWHUORFNHG__1RUPDO_ mode.
The configured interlocking conditions are checked before a control command is carried
out. As soon as a control command is entered in the 6FKHGXOHG column, Password
No. 1 for interlocked switching is requested for safety reasons. Further control
possibilities remain possible until the control dialog field is closed, or the switching
mode is changed.
If a control command is successfully executed, then the display of the actual condition
of the affected switch is updated in the window.
Operating resources can be switched without interlocking condition checks; however,
the correct Password No. 2 for non-interlocked switching must be entered. Mark the
option 8QORFN by clicking on the field.
DANGER!
Only highly qualified personnel who have an exact knowledge of the power system
conditions shall perform non-interlocked switching. Inappropriate switching
operations can lead to death, serious personnel injury and property damage.
Control During Operation
7-38 7UM61 Manual
C53000-G1176-C127-1
7.3.2 Manual Overwriting
When using the Control with Feedback feature, the device checks the feedback indications
(i.e. 52-a and 52-b) before and after a control command is issued. If for some
reason, the physical connection from a circuit breaker auxiliary contact to the binary
inputs of the device is broken, inadvertently shorted, or disconnected, commands may
be blocked. If this situation occurs, and the affected switching device is to be operated,
the desired device position indication can be simulated through “manual overwriting”
(Input Tagging). The entered device position indication in the 7UM61 can be used to
simulate and check interlocking conditions.
To accomplish manual overwriting in the 7UM61 the binary inputs of the affected device
must be decoupled first. ,% (Block Input Acquisition) This decoupling of the system
is accomplished by setting the respective status. The decoupling is discussed in
Sub-section 7.3.3.
From the
Device Front
To enter the desired position indication for a switching device:
With a 7UM61 ready for operation, first press the key. The 0$,1_0(18 appears.
Using the key, select the menu item &RQWURO and go to the control functions with
the key. The selection &21752/ appears.
By pressing the key, the %5($.(5_6:,7&+ sub-menu is entered (see Figure 7-
45).
Select the item 0DQ__2YHUZULWH using the key, and move to the next selection
using the key. 0$1__29(5:5,7( appears, as shown in Figure 7-45.
The actual position of each switching device is displayed. Move to the desired switch
using the and keys.
Figure 7-45 Manual Overwriting for Switching Devices from the Front Panel
By pressing the key, a selection window is opened for the marked switch, in
which manual overwriting can be done with the options 23(1_&/26(. See Figure 7-
46.
Make the selection using the and keys, and confirm with the key.
Enter Password No. 2 (for non-interlocked switching) and acknowledge with the
key.
MENU
_%_5_(_$_._(_5___6_:_,_7_&_+_____________
_'LVSOD\________³!__
_&RQWURO________²!__
!0DQ__2YHUZULWH_²!__
_6HW_VWDWXV_____³!___
_0_$_1_____2_9_(_5_:_5_,_7_(____________
___%UHDNHU_____!23(1
_'LVF_6ZLW______&/26
_*QG6ZLW________23(1
ENTER
ENTER
ENTER
Control During Operation
7UM61 Manual 7-39
C53000-G1176-C127-1
Figure 7-46 Selection Window for Manual Overwriting of a Switch Position, Front Panel
A safety inquiry appears: “$UH_\RX_VXUH"” Provided manual overwriting is allowed,
a response of “<(6” results in an appropriate message on the display. Acknowledge
the message by pressing the key again.
Manual overwriting is cancelled if the process is restricted because, for example, “LQ_
SXW_LJQRUHG” is not set (see Sub-section 7.3.3). Manual overwriting is also canceled
if the user aborts the procedure. The display provides an appropriate message if manual
overwriting is canceled. Acknowledge the message by pressing the key.
Return to the %5($.(5_6:,7&+ sub-menu using the key, or the 0$,1_0(18 by
pressing the key.
From PC with
DIGSI® 4
For safety reasons, manual overwriting is only possible locally using the keypad on the
front panel of the device. The feature is not available in DIGSI® 4.
7.3.3 Set Status
A feature of the 7UM61 that is especially useful during testing and commissioning of
the device is the capability of temporarily removing the coupling between a switching
device and the 7UM61, or between the SCADA and the 7UM61, without physically disconnecting
the equipment. This type of separation is also necessary, for instance, if a
switch position feedback message is not functioning properly (refer to Sub-section
7.3.2). The menu item 6(7_67$786 is used to perform the decoupling.
The menu displays a list of all planned switching devices and associated status information
identified by a letter. The letters have the following meanings:
• T Device is tagged (manually overwritten).
• I Input ignored, which means the acquisition of an input status is de-coupled from
the process (from the switch-gear).
• B Blocked, which means data transmissions to the central device (or SCADASCADA)
are blocked.
• C Chatter block active, which means, because of frequent message changes, the
chatter block was set.
• O Output block active, which means the command output is de-coupled from the
process (from the system).
• – None of the listed limitations is in effect.
_0_$_1_____2__!_2_3_(_1__________________
!__%UH__&/26___!23(1
!'LVF___________&/26
ENTER
ENTER
MENU
:
Control During Operation
7-40 7UM61 Manual
C53000-G1176-C127-1
From the
Device Front
With a device ready for operation, first press the key. The 0$,1_0(18 appears.
Using the key, select the menu item &RQWURO and go to editing the control functions
with the key. The selection &21752/ appears.
Enter the %5($.(5_6:,7&+ menu by pressing the key.
Select the item 6HW_6WDWXV with the key and switch to the next option using the
key. 6(7_67$786 appears, as shown in Figure 7-47.
Figure 7-47 Set Status at the Front Panel
Move the cursor, using the and keys, to each of the second (Input Ignore) and
fifth (Control Block) columns of the switching device for which a status change is desired.
Entries in this table can only be made in these two columns.
Press the key. A selection window is opened that displays the meaning of the
field and the change options that are available.
The second column is reserved for setting Input Ignore (I); the fifth for setting the output
block (O). The first, third, and fourth columns can only be read in this menu.
The example in Figure 7-47 shows the position for the circuit breaker (52) was tagged
(T) after the input ignore (I) was set, which means the message input was de-coupled
from the system. The output block is active (O), so the command output is also decoupled
from the system. For the disconnect switch and the ground switch, no limitations
are set.
Select the desired changes using the and keys, and confirm with the key.
Enter Password No. 2 (for non-interlocked switching) and acknowledge with the
key.
A safety inquiry appears: “$UH_\RX_VXUH"” If the response is “<(6”, and provided
the return routing is allowed, then the display gives an appropriate message.
To return to the %5($.(5_6:,7&+ level, press the key as necessary. Press the
key to return to the 0$,1_0(18.
Note:
Input ignored only works for physical inputs! Do not set the block for indications created
by CFC.
MENU
1. 2. 3. 4. 5. Column
_%_5_(_$_._(_5___6_:_,_7_&_+_____________
_'LVSOD\________³!__
_&RQWURO________²!__
!0DQ__2YHUZULWH_²!__
!6HW_VWDWXV_____³!___ _6_(_7___6_7_$_7_8_6_________________
___%UHDNHU_7_,_____2
_'LVF_6ZLW__!_______
_*QG6ZLW____________
ENTER
ENTER
ENTER
MENU
Control During Operation
7UM61 Manual 7-41
C53000-G1176-C127-1
From PC Using
DIGSI® 4
For safety reasons, Status changes are only possible locally using the keypad on the
front panel of the device. Status changes are not possible in DIGSI® 4.
7.3.4 Interlocking
Operating equipment such as circuit breakers, circuit switchers and ground switches
can be subject to interlocking conditions. These conditions can be viewed at the device
under the menu item ,17(5/2&.; however, the conditions cannot be changed.
The Interlock display has an object table similar to the one described for Set Status.
The table provides the set interlocking conditions, which prevent, or could prevent, a
local control operation. Letters identify the interlocking conditions. The meanings of
the letters are:
• L Local/Remote (Switching Authority),
• S Equipment is subject to System Interlocking (in Substation Controller). Commands
entered locally are sent to the central computer or controller,
• Z Zone controlled (Field- or Bay-Interlocking),
• P Check switch position (test actual vs. scheduled),
• B Blocking by picked-up protection elements,
• – Non-Interlocked.
From PC with
DIGSI® 4
With a device ready for operation, first press the key. The 0$,1_0(18 appears.
Using the key, select the menu item &RQWURO and move to editing the control functions
with the key. The selection &21752/ appears.
Select the item ,QWHUORFN with the key and switch to the next selection using the
key. The selection ,17(5/2&. appears. See Figure 7-48.
Figure 7-48 Example of Interlocking Conditions for Switching Equipment, Front Panel
From PC with
DIGSI® 4
Interlocking is set for each switching device during project planning (see Sub-section
5.2.4) using the matrix and the dialog box “Object Properties”. Readout of the actively
set interlocking is always possible, across the entire path, without a password.
If the 2QOLQH window in DIGSI® 4 is opened with a double click, the operating functions
for the device appear in the left part of the window (Figure 7-34). Double clicking
:
: MENU
_,_1_7_(_5_/_2_&_.______________________
!__%UHDNHU_/_²_=_3_%_
!'LVF6ZLW__/_²_=_3_%
_&_2_1_7_5_2_/__________________________
!7DJJLQJ_______²!____!
!,QWHUORFN_____²!___
1. 2. 3. 4. 5. Column
_*QG6ZLW___/_²_=_3_%
:
Control During Operation
7-42 7UM61 Manual
C53000-G1176-C127-1
on 6HWWLQJV brings up the function selection in the right side of the window. By double
clicking on 0DVNLQJ_,_2, the matrix is opened. Mark the switching device (in the
line for the operating message of the switching device). Using the right mouse key, the
properties of the switching device can now be called up. The conditions for ,QWHU_
ORFN_6ZLWFKLQJ, among other items, are recognizable in the dialog box that opens.
Active test conditions are identified with a check mark.
7.3.5 Tagging
To identify unusual operating conditions in the power system, tagging can be done.
The tagging can, for example, be entered as additional operating conditions in interlocking
checks, which are set up with CFC. Tagging is configured in the same way as
for operating devices.
From PC with
DIGSI® 4
With a device ready for operation, first press the key. The 0$,1_0(18 appears.
Using the key, select the menu item &RQWURO and move to editing the control functions
with the key. The selection &21752/ appears.
Select the item 7DJJLQJ with the key and switch to the next selection using the
key. The selection 7$**,1* appears. See Figure 7-49.
• The status of the tagging is displayed 7DJJLQJ → 'LVSOD\,
or changed using
• 7DJJLQJ → 6HW.
Figure 7-49 Tagging Equipment from the HMI
: MENU
_7_$_*_*_,_1_*____________________________
'LVSOD\_________²!___
6HW_____________²!___
_&_2_1_7_5_2_/______________________________
%UHDNHU_6ZLWFK__²!____
7DJJLQJ_________²!___
,QWHUORFN_______²!___
_0_$_,_1___0_(_1_8______________________
$QQXQFLDWLRQ___²!___
0HDVXUHPHQW____²!___
&RQWURO________²!___
Note:
The Manual Overwrite function is always done using the HMI on the SIPROTEC® 4
devices.
Control During Operation
7UM61 Manual 7-43
C53000-G1176-C127-1
7.3.6 Switching Authority
Switching authority determines the command sources that are permitted for control.
From the
Device Front
With a device ready for operation, first press the key. The_0$,1_0(18 appears.
Using the key, select the menu item &RQWURO and move to editing the control functions
with the key. The selection_&21752/ appears.
Here, select the menu item &RQWURO_$XWK_ with the key and switch to the next
selection using the key. The selection &21752/_$87+_ appears (see Figure 7-50).
Figure 7-50 Setting Switching Authority with the Operator Control Panel
Pressing the key opens a selection window in which the options /2&$/_5(027(
are offered.
Choose the desired option using the and keys, and confirm with the key.
Acknowledge the subsequent message pressing the key.
Use the key to return to the 6:,7&+_$87+ level; the key to return to the 0$,1_
0(18.
From PC with
DIGSI® 4
For safety reasons, switching authority can only be changed locally using the keypad
on the front panel of the device. Switching authority cannot be changed with DIGSI® 4.
To perform control with DIGSI® 4, switching authority at the device must be set to 5(_
027(, or the test conditions for remote control of switching authority must not be set
to active. Switching authority is first transferred to DIGSI® 4 when the control window
(see Figure 7-44) is opened.
7.3.7 Switching Mode
The switching mode can be changed during operation; so, for example, non-interlocked
switching can be enabled during the commissioning of the installed equipment.
MENU
_&_2_1_7_5_2_/__________________________
!,QWHUORFN_____–> 3
>&RQWURO_$XWK__–> 4 _&_2_1_7_5_2_/___$_8_7_+__________________
_6ZLWFK_$XWK_!_/RFDO
ENTER
3:_8QORFN_&RQWURO"
_____ _______
Enter password No. 2 (for non-interlocked
switching) and acknowledge with ENTER
ENTER
_&_2_1_7_5_2__!_5_H_P_R_W_H__________
_6ZLWF__/RFDO__/RFDO
ENTER
ENTER
ENTER
MENU
:
Control During Operation
7-44 7UM61 Manual
C53000-G1176-C127-1
From the
Device Front
With a device ready for operation, first press the key. The 0$,1_0(18 appears.
Using the key, select the menu item &RQWURO and move to editing the control functions
with the key. The selection &21752/ appears.
Here, select the menu item 6ZLWFK_0RGH with the key and switch to the next selection
using the key. The selection 6:,7&+_02'( appears (see Figure 7-51).
Figure 7-51 Operating Menu for Switching Mode Using Front Panel
Pressing the key opens a selection window in which the options ,17(5/2&.('_
121_,17(5/2&.(' are offered.
Make the choice using the and keys, and confirm with the key.
Acknowledge the safety inquiry that follows by again pressing the key. Use the
key to return to the &21752/ level. Press the key to return to the 0$,1_0(18.
From PC with
DIGSI® 4
When the 2Q_OLQH window in DIGSI® 4 is opened with a double click, the operating
functions for the device appear in the left part of the window (Figure 7-34). Clicking on
&RQWUROV brings up the function selection in the right side of the window (Figure 7-
43). By double clicking on %UHDNHU_6ZLWFKHV, a dialog field is opened in which,
among other options, the option for interlocked and non-interlocked (Unlock) switching
is offered.
To switch operating resources without a check of the associated interlocking conditions,
mark the option 8QORFN by clicking in that field, see section 7.3.1.
To set the switching mode for interlocked switching, the aforementioned option field
must not be marked. The marking is removed by clicking in the field again.
DANGER!
Only highly qualified personnel who have an exact knowledge of the power system
conditions shall perform non-interlocked switching. Inappropriate switching
operations can lead to death, serious personnel injury and property damage.
MENU
_&_2_1_7_5_2_/__________________________
!&RQWURO_$XWK__²!___
!&RQWURO_0RGH__²!___ _&_2_1_7_5_2_/___0_2_'_(_________
_0RGH/2&$/____!/2&.
ENTER 3:_8QORFN_&RQWURO"
_____ _______
Enter Password No. 2 (for non-interlocked
switching) and confirm with ENTER
_&_2_1_7__!_/RFNHG_______
_0RG___8QORFNHG_!/2&.__
________________
ENTER
ENTER
ENTER
MENU
:
Control During Operation
7UM61 Manual 7-45
C53000-G1176-C127-1
Further switching operations are possible until the dialog field %UHDNHU_6ZLWFKHV
is closed, or the switching mode is changed.
7.3.8 Control Messages
In the course of system control, the device generates several messages that document
the process. For example, messages may be given to report the end of a command
or provide the reason for a command denial. These messages and the associated
causes are listed in Table 7-3, together with other messages for the control of device
functions.
Table 7-3 Possible Control Messages
Message Text Message Cause
6\VWHP_(UURU Interruption by system error
0DQ_2YHUZULWH_2. Return routing carried out
0DQ_2YHUZULWH_)DLO Return routing cannot be carried out
&RQWURO_$ERUW_2. Command interruption carried out correctly
&RQWURO_$ERUW_)DLO Process cannot be interrupted because no command is issued,
command runs in different switching direction, or interruption is not
planned or set up.
&RQWURO_([HFXWHG Command was correctly executed and ended
&RQWURO_)DLOHG Refusal because the command number or the origination source is
not permitted
,QWHUORFNHG Refusal because the communication interface was blocked or the
command object is blocked by a protective function.
6ZLWFKJU_,QWORFNHG Refusal because the command object is subject to field interlocking
6ZLWFK_LQ_3RVLWLRQ Refusal because the present switch position = command direction
6HWWLQJ_(UURU Refusal because of a parameter fault, such as unknown command
type
1RW_$XWKRUL]HG Command from ON-SITE refused because command object is
subject to switching authority, which is set to REMOTE
&RQWURO_([SLUHG Refusal because command is too old (expiry monitor)
1R_&RQWURO_'HYLFH Information address is not planned as command output
&RQILJ__(UURU Refusal because no relay is assigned to this object, or the relay
jumpered in the device does not exist
&RQWURO_%ORFNHG Refusal because an output block is set
6\VWHP_2YHUORDG" Refusal because a relay to be controlled is already active (e.g., by
another command)
6:____WR_Q_HUURU" Refusal because another relay is already controlled
6\VWHP_2YHUORDG No more free timers available
8SSHU6HWW__/LPLW For transformer LTC step commands, highest level already
reached
/RZHU_6HWW__/LPLW For transformer LTC step commands, lowest level already reached
([HFXWLQJ_&RQWURO New command refused because a command is already in processing
Control During Operation
7-46 7UM61 Manual
C53000-G1176-C127-1
7.3.9 Other Commands
The device is equipped with a serial interface for connection to SCADA. From there,
the device can receive standardized commands (according to the supported protocol)
and transmit them to the respective switching devices, or activate internal functions,
e.g. block inputs/outputs or set tags (manual overwrite), or release processing of functions
in the CFC. This command processing is determined during project planning and
configuration of the matrix.
n
&RPPDQG_7LPHRXW Feedback indication missing
%LQDU\,QS__,JQRUHG Recording block set
&KDWWHU_$FWLYH Flutter block is active
6HWW_&KDQJH_$FWLYH Refusal because parameter loading process is running
6WDWXV_&KDQJH_2. Status FRPPDQG_H[HFXWHG
6WDWXV_&KDQJH_)DLO Status command cannot be executed
&KDQJH_2. Marking executed
&KDQJH_)DLOHG Marking cannot be executed
&KHFNLQJ_,QWHUORFN Command is sent to the central unit to check system interlocking
6HWWLQJV__DUH_2. Parameter change was correctly accepted
7LPH_/LPLW_([SLUHG Parameter change was interrupted because time expired
7HUPLQDWHG_3LFNXS Parameter change interrupted because a fault became active during
parameterization
5HVWRUH_3DUDPHWHUV As a reaction to a fault recognized during parameterization, the last
active parameter set is activated again
3OHDVH_:DLW« Initiated process running and requires some time
&KHFNLQJ_6HWWLQJV The changed parameters are tested before acceptance
6ZJU__)HHGEDFN_2. Return message: destination reached
6ZJU__)HHGEDFN_)DLO Return message: destination not reached
&KDQJH_5HMHFWHG Parameter change was rejected (e.g., because time expired, or abnormal
occurrence during parameterization)
&RQWURO_2. Positive conclusion message for commands
9DOXH_,QFRUUHFW Plausibility error in command
Table 7-3 Possible Control Messages
Message Text Message Cause
7UM61 Manual 8-1
C53000-G1176-C127-1
Holes
Device faulty
Reset
Min/Max
Bracket
Bracket
Device faulty
Reset
Min/Max
6,(0(16 3 4 5
(AD2)
(AD1)
(AD0)
from the device. Apply protective caps to the fibber ends and the communication ports
on the device.
These activities do not apply if the device is for surface mounting.
o Unfasten the screw-posts of the D-subminiature connector on the back panel at location
“A.”
This activity does not apply if the device is for surface mounting.
o If the device has more communication interfaces at locations “B” and/or “C” on the
rear, the screws located diagonally to the interfaces must be removed.
These activities are not necessary if the device is for surface mounting.
o Remove the corner covers on the front panel and loosen the screws that are holding
the front panel to the device case.
o Carefully pull off the front panel. The front panel is connected to the CPU board with
a short ribbon-cable.
On devices with detached operator panel, the front panel can be pulled off directly
(without a ribbon cable).
o Disconnect the ribbon-cable that links the front panel and the CPU board (å), at the
side of the front panel. To disconnect the cable, push up on the top latch of the plug
connector and push down on the bottom latch of the plug connector. Carefully set
aside the front panel.
For the surface mounted device, the 7-pin connector X16 must be disconnected from
the CPU board behind the D-subminiature port, and the ribbon-cable that runs to the
68-pin connector on the back must be detached.
o Disconnect the ribbon-cable between the CPU board and the I/O board.
o The boards can be removed and laid on the grounded mat to protect them from ESD
damage.
A greater effort is required to remove the CPU board from the device designed for surface
mounting, because of the type of connectors.
Replacing the
Power Supply Fuse
o Keep ready replacement fuse 5 x 20 mm. Verify the correct rating, correct characteristic
(T) as well as the correct coding.
This data is printed on the module next to the fuse (see Figure 9-5). The type of fuse
depends on the auxiliary supply voltage, e.g. for 24 to 48 VDC the fuse type
“T4H250V” according to IEC 60127–2 is required (refer to Table 9-1).
o Remove the CPU board. Place the board on the grounded mat for protection against
ESD damage.
A greater effort is required to remove the CPU board in a device designed for surfacemounting.
Place the board on the grounded mat.
o Remove the defective fuse. Figure 9-5 illustrates the fuse.
Routine Checks and Maintenance
7UM61 Manual 9-11
C53000-G1176-C127-1
Figure 9-5 Power supply mini-fuse on the CPU board
o Install the new fuse into the holder.
o Carefully install the CPU board in the case. The position for the board is shown in Figure
9-1.
For the version of the device designed for surface-mounting, use the metal lever to insert
the CPU board. The installation is then easier.
Reassembling the
Device
To reassemble the device:
o Connect the ribbon-cable between the I/O board and the CPU board. Be especially
careful not to bend any of the connector pins! Do not use force! Be sure the connectors
latch.
o Connect the ribbon-cable between the CPU board and the front panel. Be especially
careful not to bend any of the connector pins! Do not use force! Be sure the plug connectors
latch.
Carefully replace the front panel being mindful of the ribbon-cables. Fasten the front
panel to the case with the screws.
o Replace the covers.
Table 9-1 Assigning of the mini-fuse rating to the device auxiliary voltage rating
7UM61∗ Version Rated Auxiliary Voltages Fuse Type
–2∗∗∗∗–∗∗∗∗ 24 V to 48 V— T4H250V
–4∗∗∗∗–∗∗∗∗ 60 V to 125 V— T2H250V
–5∗∗∗∗–∗∗∗∗ 110 V to 250 V—, 115 V∼ T2H250V
F1
24 /48VDC T 4.0 / 250 G
60V-250VDC/230VAC
T 2.0/250 G
Technical Data 10
This chapter provides the technical data of the SIPROTEC® 4 7UM61 device and the
individual functions of the device, including the limiting values that under no circumstances
may be exceeded. The electrical and functional data for devices equipped
with all options are followed by the mechanical data with dimensional drawings.
10.1 General Device Data 10-2
10.2 Definite-Time Overcurrent Protection (ANSI 50, 67) 10-12
10.3 Inverse-Time Overcurrent Protection (ANSI 51) 10-13
10.4 Thermal Overload Protection (ANSI 49) 10-18
10.5 Unbalanced load protection (ANSI 46) 10-20
10.6 Underexcitation protection (ANSI 40) 10-22
10.7 Reverse power protection (ANSI 32R) 10-23
10.8 Forward active power supervision (ANSI 32F) 10-24
10.9 Impedance protection (ANSI 21) 10-25
10.10 Undervoltage protection (ANSI 27) 10-26
10.11 Overvoltage protection (ANSI 59) 10-27
10.12 Frequency Protection (ANSI 81) 10-28
10.13 Overexcitation protection U/f> (ANSI 24) 10-29
10.14 90–%–Stator earth fault protection (ANSI 59N, 64G, 67G) 10-31
10.15 Sensitive earth current detection (ANSI 51GN, 64F) 10-32
10.16 100–%–Stator earth fault protection with 3rd harm. (ANSI 27/59TN) 10-33
10.17 Breaker Failure Protection (ANSI 50BF) 10-34
10.18 Inadvertent energization (ANSI 50/27) 10-35
10.19 Additional Functions 10-36
10.20 Operating ranges of the protection functions 10-40
10.21 Dimensions 10-41
Technical Data
10-2 7UM61 Manual
C53000-G1176-C127-1
10.1 General Device Data
10.1.1 Analog Inputs
Nominal Frequency fN 50 Hz or 60 Hz (adjustable)
Current Inputs Nominal Current IN 1 A or 5 A
Ground Current, SensitiveIEE ≤ 1.6 A
Burden per Phase and Ground Path
– At IN = 1 A approx. 0.05 VA
– At IN = 5 A approx. 0.3 VA
– Sensitive Ground Fault Detection 1 A approx. 0.05 VA
AC Current Overload Capability
– Thermal (rms) 100 · IN < 1 s
30 · IN < 10 s
4 · IN continuous
– Dynamic (current pulse) 250 · IN for 0.5 cycle
AC Current Overload Capability for Sensitive Ground Fault Detection
– Thermal (rms) 300 A < 1 s
100 A < 10 s
15 A continuous
– dynamic (impulse) 750 A for 0.5 cycle
Voltage Inputs Secondary Nominal Voltage 100 V to 125 V AC
Measuring Range 0 V to 170 V AC
Burden at 100 V approx. 0.3 VA
AC Voltage Input Overload Capacity
– Thermal (rms) 230 V continuous
10.1.2 Power Supply
Direct Voltage Voltage Supply Via Integrated Converter
Permissible AC Ripple Voltage,
peak to peak ≤ 15 % of the power supply voltage
Power Consumption
7UM611 quiescent approx. 4 W
7UM612 approx. 4.5 W
Nominal Power Supply Direct Voltage VPS nom 24/48 VDC 60/110/125 VDC
Permissible Voltage Ranges 19 to 58 VDC 48 to 150 V DC
Nominal Power Supply Direct Voltage VPSnom 110/125/220/250 VDC
Permissible Voltage Ranges 88 to 300 V DC
Technical Data
7UM61 Manual 10-3
C53000-G1176-C127-1
7UM611 energized approx. 9.5 W
7UM612 approx. 12.5 W
Bridging Time for Failure/Short Circuit ≥ 50 ms at V ≥ 110 VDC
≥ 20 ms at V ≥ 24 VDC
Alternative Voltage Voltage Supply via Integrated Converter
Bridging Time for Failure/Short Circuit ≥ 200 ms
10.1.3 Binary Inputs and Outputs
Binary Inputs Number
7UM611*– 7 (configurable)
7UM612*– 15 (configurable)
Nominal Voltage Range 24 VDC to 250 VDC, bipolar
Current Consumption, Energized approx. 1.8 mA, independent of the
control voltage
Switching Thresholds adjustable voltage range with jumpers
Binary inputs BI 1 to BI 7: 2 ranges
– For Nominal Voltages 24/48/60/ UPU ≥ 19 VDC
110/125 VDC UDO ≤ 14 VDC
– For Nominal Voltages 110/125/ UPU ≥ 88 VDC
220/250 VDC UDO ≤ 66 VDC
Binary inputs BI 8 to BI 15: 3 ranges–
– For Nominal Voltages 24/48/60/ UPU ≥ 19 VDC
110/125 VDC UDO ≤ 14 VDC
– For Nominal Voltages 110/125/ UPU ≥ 88 VDC
220/250 VDC UDO ≤ 66 VDC
– For Nominal Voltages 220/250 VDC UPU ≥ 176 VDC
UDO ≤ 117 VDC
Maximum Permissible Voltage 300 V DC
Impulse Filter on Input 220 nF Coupling Capacitor at 220 V with
recovery time > 60 ms
Output Relays Output Relays for Commands/Annunciations
Number 7UM611*– 11 (configurable)
7UM612*– 19 (configurable)
Contacts per Relay 1 NO/form A
Nominal Power Supply Alternating Voltage
VPS AC
115 VAC
(50/60 Hz)
Permissible Voltage Ranges 92 to 132 VAC
Power Consumption, Quiescent approx. 4 VA
Power Consumption, Energized approx. 12 VA
Technical Data
10-4 7UM61 Manual
C53000-G1176-C127-1
1 Live Status Alarm Relay
Contacts 1 changeover contact/form C
Switching Capability MAKE 1000W/VA
BREAK 30 W/VA
40 W resistive
25 W at L/R ≤ 50 ms
Switching Voltage 250 V
Permissible Current per Contact 5 A continuous
and Total Current on common path 30 A for 0.5 s
10.1.4 Communications Interfaces
PC Front Interface – Connection front panel, non-isolated, RS 232,
9-pin DSUB port for connecting a personal
computer
– Operation with DIGSI® 4
– Transmission Speed min. 4800 Baud; max. 38400 Baud
Factory Setting: 38400 Baud; Parity: 8E1
– Maximum Distance of Transmission 15 meters / 49 feet
Rear Service–/Modem–
Interface
– Connection isolated interface for data transfer
– Operation with DIGSI® 4
– Transmission Speed min. 4800 Bd, max. 38400 Bd
Factory Setting: 38400 Bd
RS232/RS485 RS232/RS485 depends on order code
– Connection for flush mounted case rear panel, mounting location “C“
9 pin DSUB port
for panel-surface at the terminal on the case bottom
mounted case
– Test Voltage 500 V AC
RS232
– Maximum Distance of Transmission 15 meters / 49 feet
RS485
– Maximum Distance of Transmission 1 km / 3280 feet / 0.62 mile
Fibre Optical Link
– Connector Type ST–Connector
with flush-mounted case rear panel, mounting location “C“
with panel surfacemounted
case on the case bottom
– Optical Wavelength λ = 820 nm
– Laser Class 1 Under EN 60825–1/ –2 using glass fiber 50/125 µ m or
using glass fiber 62.5/125 µ m
Technical Data
7UM61 Manual 10-5
C53000-G1176-C127-1
– Optical Link Signal Attenuation max. 8 dB, with glass fiber 62.5/125 µ m
– Channel Distance max. 1.5 km (0.95 miles)
– Character Idle State selectable: factory setting “Light off”
SCADA Interface IEC 60870–5–103
RS232/RS485 floating interface for data transfer
depends on order code to a master terminal
RS232
– Connection for flush mounted case rear panel, mounting location “B“
9 pin DSUB port
for panel surface- at the terminal on the case bottom
mounted case
– Test Voltage 500 V AC
– Transmission Speed min. 4800 Bd, max. 38400 Bd
Factory Setting: 38400 Bd
– Maximum Distance of Transmission 15 meters / 49 feet
RS485
– Connection for Flush Mounted Case rear panel, installation location “B“
9 pin DSUB Port RS 485
for panel surface- at the terminal on the case bottom
mounted case Profibus cable
– Test Voltage 500 V AC
– Transmission Speed min. 4800 Bd, max. 38400 Bd
Factory Setting: 38400 Bd
– Maximum Distance of Transmission 1 km / 3280 feet / 0.62 mile
Fibre Optical Link
– Connector Type ST–Connector
with flush-mounted case rear panel, mounting location “B“
with panel surfacemounted
case on the case bottom
– Optical Wavelength λ = 820 nm
– Laser Class 1 Under EN 60825–1/ –2 using glass fiber 50/125 µ m or
using glass fiber 62.5/125 µ m
– Optical Link Signal Attenuation max. 8 dB, with glass fiber 62.5/125 µ m
– Channel Distance max. 1.5 km (0.95 miles)
– Character Idle State selectable: factory setting “Light off”
Profibus RS485 (FMS1) and DP)
– Connection for Flush Mounted Case rear panel, installation location “B“
9 pin DSUB Port RS 485
for panel surface- at the terminal on the case bottom
mounted case
– Test Voltage 500 V AC
1) on request
Technical Data
10-6 7UM61 Manual
C53000-G1176-C127-1
Transmission Speed up to 1.5 M Baud
– Maximum Distance of Transmission 1 km / 3280 feet / 0.62 mile at≤ 93.75 kBd
500 m /1640 feet /0.31 mile at≤ 187.5 kBd
200 m / 660 feet at ≤ 1.5 MBd
Profibus RS485
– Connection for Flush-Mounted Case rear panel, mounting location “B“
9 pin DSUB Port RS 485
For Panel Surface-
Mounted Case on the case bottom
– Test Voltage 500 V AC
– Transmission Speed up to 12 M Baud
– Maximum Distance of Transmission 1 km / 3280 feet / 0.62 mile at≤ 93.75 kBd
500 m /1640 feet /0.31 mile at≤ 187.5 kBd
200 m / 660 feet at ≤ 1.5 MBd
100 m /330 feet at ≤ 12 MBd
Profibus Fibre Optical Link
(FMS1) and DP)
– Connection ST–Connector,
for FMS single ring or twin ring, depending
on order; for DP only double ring
with flush-mounted case rear panel, mounting location “B“
with panel surfacemounted
case on the case bottom
– Transmission Speed up to 1.5 M Baud
recommended: > 500 k Baud
– Optical Wavelength λ = 820 nm
– Laser class 1 Under EN 60825–1/ –2 using glass fiber 50/125 µ m or
using glass fiber 62.5/125 µ m
– Optical Link Signal Attenuation max. 8 dB, with glass fiber 62.5/125 µ m
– Channel Distance max. 1.5 km (0.95 miles)
– Character Idle State selectable: factory setting “Light Off”
DNP3.0 RS4851)
– Connection for Flush-Mounted Case rear panel, mounting location “B“
9 pin DSUB Port RS 485
For Panel Surface-
Mounted Case on the case bottom
– Test Voltage 500 V AC
– Transmission Speed up to 19200 Baud
– Maximum Distance of Transmission 1 km
DNP3.0 Fibre Optical Link1)
– Connection ST–Connector,
with flush-mounted case rear panel, mounting location “B“
with panel surfacemounted
case on the case bottom
1) on request
Technical Data
7UM61 Manual 10-7
C53000-G1176-C127-1
– Transmission Speed up to 19200 Baud
– Optical Wavelength λ = 820 nm
– Laser class 1 Under EN 60825–1/ –2 using glass fiber 50/125 µ m or
using glass fiber 62.5/125 µ m
– Optical Link Signal Attenuation max. 8 dB, with glass fiber 62.5/125 µ m
– Channel Distance max. 1.5 km (0.95 miles)
MODBUS RS4851)
– Connection for Flush-Mounted Case rear panel, mounting location “B“
9 pin DSUB Port RS 485
For Panel Surface-
Mounted Case on the case bottom
– Test Voltage 500 V AC
– Transmission Speed up to 19200 Baud
– Maximum Distance of Transmission 1 km
MODBUS Fibre Optical Link1)
– Connection ST–Connector,
with flush-mounted case rear panel, mounting location “B“
with panel surfacemounted
case on the case bottom
– Transmission Speed up to 19200 Baud
– Optical Wavelength λ = 820 nm
– Laser class 1 Under EN 60825–1/ –2 using glass fiber 50/125 µ m or
using glass fiber 62.5/125 µ m
– Optical Link Signal Attenuation max. 8 dB, with glass fiber 62.5/125 µ m
– Channel Distance max. 1.5 km (0.95 miles)
1) on request
Clock – Time Synchronization DCF77/IRIG B–Signal
– Connection For Flush-mounted Case rear panel, mounting location “A“
9 - pin DSUB port
For Panel Surface- at the terminal on the case bottom
Mounted Case
– Signal Rated Voltage selectable 5 V, 12 V or 24 V
– Signal Levels and Burdens:
Rated Signal Voltage
5 V 12 V 24 V
VIHigh 6.0 V 15.8 V 31 V
VILow 1.0 V at IILow = 0.25 mA 1.4 V at IILow = 0.25 mA 1.9 V at IILow = 0.25 mA
IIHigh 4.5 mA to 9.4 mA 4.5 mA to 9.3 mA 4.5 mA to 8.7 mA
RI 890 Ω at VI = 4 V
640 Ω at VI = 6 V
1930 Ω at VI = 8.7 V
1700 Ω at VI = 15.8 V
3780 Ω at VI = 17 V
3560 Ω at VI = 31 V
Technical Data
10-8 7UM61 Manual
C53000-G1176-C127-1
10.1.5 Electrical Tests
Specifications Standards: IEC 60255 (Product Standards)
ANSI/IEEE C37.90.0,.C37.90.0.1 and
C37.90.0.2
DIN 57 435 Part 303
See also standards for individual functions
Insulation Tests Standards: IEC 60255–5, IEC 60870–2–1
– High Voltage Test (routine test) 2.5 kV (rms) AC
All circuits except power supply,
Binary Inputs, and
Communications Interface
– High Voltage Test (routine test) 3.5 kVDC
only power supply and binary inputs
– High Voltage Test (routine test) 500 V (rms) AC
Only Isolated Communications
and Time Synchronization Interfaces
– Impulse Voltage Test (type test) 5 kV (peak): 1.2/50 µ s: 0.5 Ws: 3 positive
All Circuits Except Communications and 3 negative surges in intervals of 5 s
and Time Synchronization Interfaces,
Class III
EMC Tests for Immunity
(Type Tests)
Standards: IEC 60255–6 and –22, (Product standards)
EN 50082–2 (Generic standard)
DIN 57 435 Part 303 ANSI/IEEE C37.90.1
and C37.90.2
– High Frequency Test 2.5 kV (Peak): 1 MHz: τ = 15 ms;
IEC 60255–22–1, Class III 400 Surges per s: Test Duration 2 s
and VDE 0435 Part 303, Class III Ri=200 Ω
– Electrostatic Discharge 8 kV contact discharge: 15 kV air-
IEC 60255–22–2 Class IV discharge, both polarities:150 pF:Ri=330 Ω
and IEC 61000–4–2, Class IV
– Irradiation with HF Field, 10 V/m: 27 MHz to 500 MHz
non-modulated
IEC 60255–22–3 (Report) Class III
– Irradiation with HF Field, 10 V/m: 80 MHz to1000 MHz: 80 % AM:
amplitude modulated 1 kHz
IEC 61000–4–3, Class III
– Irradiation with HF Field, 10 V/m: 900 MHz: repetition frequency
Pulse Modulated 200 Hz: duty cycle of 50 %
IEC 61000–4–3/ENV 50204, Class III
– Fast Transient Disturbance Variables/ 4 kV: 5/50 ns: 5 kHz: Burst length = 15 ms;
Burst IEC 60255–22–4 and repetition rate 300 ms: both polarities:
IEC 61000-4-4, Class IV Ri = 50 Ω : Test Duration 1 min
– High Energy Surge Voltages
(SURGE), IEC 61000–4–5
Installation Class 3
Power Supply common mode: 2 kV: 12 Ω : 9 µ F
Technical Data
7UM61 Manual 10-9
C53000-G1176-C127-1
diff. mode: 1 kV: 2 Ω : 18 µ F
Measuring Inputs, Binary Inputs common mode: 2 kV: 42 Ω : 0.5 µ F
and Relay Outputs diff. mode: 1 kV: 42 Ω : 0.5 µ F
– Line Conducted HF, amplitude modul. 10 V: 150 kHz to 80 MHz: 80 % AM: 1 kHz
IEC 61000–4–6, Class III
– Power System Frequency Magnetic 30 A/m continuous: 300 A/m for 3 s: 50 Hz
Field IEC 61000–4–8, Class IV 0.5 mT: 50 Hz
IEC 60255–6
– Oscillatory Surge Withstand Capability 2.5 to 3 kV (Peak Value): 1MHz to 1.5 MHz
ANSI/IEEE C37.90.1 damped wave: 50 surges per s:
duration 2 s: Ri = 150 Ω to 200 Ω
– Fast Transient Surge Withstand Cap. 4 kV to 5 kV: 10/150 ns: 50 Pulse per s;
ANSI/IEEE C37.90.1 both polarities: Duration 2 s: Ri = 80 Ω
– Radiated Electromagnetic Interference 35 V/m: 25 MHz to 1000 MHz
ANSI/IEEE C37.90.2 amplitude and pulse modulated
– Damped Oscillations 2.5 kV (Peak Value), polarity alternating
similar to IEC 60694–4–12, 100 kHz, 1 MHz, 10 MHz and 50 MHz,
IEC 61000–4–12 Ri = 200 Ω
EMC Tests For
Noise Emission
(type test)
Standard: EN 50081–1 (Generic Standard)
– Radio Noise Voltage to Lines, 150 kHz to 30 MHz
Only Power Supply Voltage Limit Class B
IEC–CISPR 22
– Radio Noise Field Strength 30 MHz to 1000 MHz
IEC–CISPR 22 Limit Class B
10.1.6 Mechanical Stress Tests
Vibration and
Shock Stress During
Operation
Standards: IEC 60255–21 and IEC 60068
– Vibration Sinusoidal
IEC 60255–21–1, Class 2 10 Hz to 60 Hz: ± 0.075 mm Amplitude;
IEC 60068–2–6 60 Hz to 150 Hz: 1 g acceleration
frequency sweep rate 1 Octave/min
20 cycles in 3 orthogonal axes.
– Shock Half-sine shaped
IEC 60255–21–2, Class 1 acceleration 5 g, duration 11 ms,
IEC 60068–2–27 3 shocks in each direction of
3 orthogonal axes
– Seismic Vibration Sinusoidal
IEC 60255–21–2, Class 1 1 Hz to 8 Hz ± 3.5 mm Amplitude
IEC 60068–3–3 (horizontal axis)
1 Hz to 8 Hz: ± 1.5 mm Amplitude
(Vertical axis)
8 Hz to 35 Hz: 1 g acceleration
(horizontale axis)
8 Hz to 35 Hz: 0.5 g acceleration
(Vertical axis)
Technical Data
10-10 7UM61 Manual
C53000-G1176-C127-1
Frequency Sweep Rate1 Octave/min
1 cycle in 3 orthogonal axes
Vibration and
Shock Stress During
Transport
Standards: IEC 60255–21 and IEC 60068–2
– Vibration Sinusoidal
IEC 60255–21–1, Class 2 5 Hz to 8 Hz: ± 7.5 mm Amplitude;
IEC 60068–2–6 8 Hz to 150 Hz: 2 g acceleration
Frequency sweep rate1 Octave/min
20 cycles in 3 orthogonal axes.
– Shock Half-sine shaped
IEC 60255–21–2, Class1 Acceleration 15 g, duration 11 ms,
IEC 60068–2–27 3 shocks in each direction of
3 orthogonal axes.
– Continuous Shock Half-sine shaped
IEC 60255–21–2, Class 1 Acceleration 10 g, duration 16 ms,
IEC 60068–2–29 1000 shocks in each direction of
3 orthogonal axes.
10.1.7 Climatic Stress Tests
Ambient Temperatures
Standards: IEC 60255–6
– Recommended operating temperature +23°F to +131°F or –5 °C to +55 °C
Visibility of display may be impaired at
+131°F and above
– Limiting, stand–by mode
operating temperatures – 4°F to +158°F or –20 °C to +70 °C
– Limiting temperatures for storage –13°F to +131°F or –25 °C to +55 °C
– Limiting temperatures for transport –13°F to +158°F or –25 °C to +70 °C
STORE AND TRANSPORT THE DEVICE WITH FACTORY PACKAGING.
Humidity Permissible Humidity Mean value per year ≤ 75% relative
humidity, on 56 days of the year up to 93%
relative humidity.
CONDENSATION MUST BE AVOIDED
Siemens recommends that all devices be installed such that they are not exposed to
direct sunlight, nor subject to large fluctuations in temperature that may cause condensation
to occur.
Technical Data
7UM61 Manual 10-11
C53000-G1176-C127-1
10.1.8 Service Conditions
The protective device is designed for use in an industrial environment and an electrical
utility environment. Proper installation procedures should be followed to ensure electromagnetic
compatibility (EMC). In addition, the following are recommended:
• All contactors and relays that operate in the same cubicle, cabinet, or relay panel
as the numerical protective device should, as a rule, be equipped with suitable
surge suppression components.
• For substations with operating voltages of 100 kV and above, all external cables
should be shielded with a conductive shield grounded at both ends. The shield must
be capable of carrying the fault currents that could occur. For substations with lower
operating voltages, no special measures are normally required.
• Do not withdraw or insert individual modules while the protective device is energized.
When handling the modules or the device outside of the case, standards for
components sensitive to electrostatic discharge (ESD) must be observed. The modules
and device are not endangered when inserted into the case.
10.1.9 Construction
Case 7XP20
Dimensions see dimensional drawings, Section 10.21
Weight (mass)
– In case for flush mounting, 1/3 of 19” 12 pounds (5.5 kg)
– In case for flush mounting, 1/2 of 19” 15.5 pounds (7.0 kg)
– In case for surface mounting, 1/3 of 19”16.5 pounds (7.5 kg)
– In case for surface mounting, 1/2 of 19”26.5 pounds (12 kg)
International Protection Under IEC 60529
– in the surface mounted case IP 51
– in the flush mounted case and in model
with the detached operator interface
Front IP 51
Back IP 50
– For human safety IP 2x Terminals covered with protection cap
Technical Data
10-12 7UM61 Manual
C53000-G1176-C127-1
10.2 Definite-Time Overcurrent Protection (ANSI 50, 67)
Pickup and Time
Delay Ranges/
Resolutions
Pickup Current 50–1 0.50 A to 40.00 A1) (increments 0.05 A)1)
Pickup Current 50–2 0.50 A to 40.00 A1) (increments 0.05 A)1)
Delay Times T 50–1, 50–2, 0.00 s to 60.00 s (increments 0.01 s)
or ∞ (does not expire)
Undervoltage seal–in U< 10.0 V to 125.0 V (increments 0.1 V)
Holding time of undervoltage seal–in 0.10 s to 60.00 s (increments 0.01 s)
Inclination of directional characteristic –90°el. to +90° el. (increments 1° el.)
The set times are pure delay times.
Inherent Operating
Times
Pickup times
50–1, 50–2
– Current = 2 x Pickup Value approx. 35 ms
– Current = 10x Pickup Value approx. 25 ms
Dropout Times
50–1, 50–2 approx. 50 ms
Dropout Dropout/Pickup (ratio) 50–1 approx. 0.95 for I/IN ≥ 0.3
Dropout/Pickup (ratio) 50–2 0.90 to 0.99 (increments 0.01)
Dropout/Pickup (ratio) U< approx. 1.05
Pickup value – Dropout value (∆ ϕ ) 2º electrical
Tolerances Pickup Current 50–1, 50–2 1 % of setting value or 50 mA1)
Undervoltage seal–in U< 1 % of setting value or 0.5 V
Delay Times T 1 % of setting value or 10 ms
Angle tolerance ϕ 1º electrical
Influencing Variables
for Pickup
Power supply direct voltage in range
0.8 ≤ VPS/ VPS nominal ≤ 1.15 1 %
Temperatur in range
23º F ≤ ϑ amb ≤ 131º F 0.06% /10º F
–5º C ≤ ϑ amb ≤ 55º C 0.5 %/10 K
Frequency in range
0.95 ≤ f/fN ≤ 1.05 < 1 %
Harmonic currents
– Up to 10 % 3. Harmonic < 1 %
– Up to 10 % 5. Harmonic < 1 %
1) For IN = 1 A, divide all limits and increments by 5.
Technical Data
7UM61 Manual 10-13
C53000-G1176-C127-1
10.3 Inverse-Time Overcurrent Protection (ANSI 51)
Pickup and Time
Multiplier Ranges/
Resolutions
Pickup Current 51 0.50 A to 20.00 A1) (Increments 0.05 A)1)
Time Multipliers for 51 Tp 0.05 s to 3.20 s (Increments 0.01 s)
IEC–Characteristics or ∞ (delay does not expire)
Time Multiplier for 51 D 0.50 to 15.00 (Increments 0.01)
ANSI characteristics or ∞ (delay does not expire)
Undervoltage release U< 10.0 V to 125.0 V (Increments 0.1 V)
Trip Time Characteristics
As Per IEC
As per IEC 60255-3, Section 3.5.2 or BS 142 (See also Figure 10-1)
The trip times for I/Ip ≥ 20 are identical to those for I/Ip = 20.
Pickup threshold approx. 1.10 · Ip
Dropout threshold approx. 1.05 · Ip for Ip/IN ≥ 0.3
Tolerances Pickup Currents Ip 1 % of setting value, or 50 mA1)
Voltage threshold U< 1 % of setting value, or 0,5 V
Trip Time for 2 ≤ I/Ip ≤ 20 5 % of reference (calculated) value + 1 %
current tolerance, respectively 40 ms
Influencing Variables
for Pickup
Power supply direct voltage in range
0.8 ≤ VPS/ VPS nominal ≤ 1.15 1 %
Temperature in range
23º F ≤ ϑ amb ≤ 131º F 0.06% /10º F
–5º C ≤ ϑ amb ≤ 55º C 0.5 %/10 K
Frequency in range
0.95 ≤ f/fN ≤ 1.05 < 1 %
Harmonic currents
– Up to 10 % 3. Harmonic < 1 %
– Up to 10 % 5. Harmonic < 1 %
1) For IN = 1 A, divide all limits and increments by 5.
t 0.14
(I ⁄ Ip) 0.02 – 1
_1250$/_,19(56( (Type A) = --------------------------------- ⋅ Tp
t
13.5
(I ⁄ Ip) 1 – 1
_9(5<_,19(5(6( (Type B) = --------------------------- ⋅ Tp
t 80
(I ⁄ Ip) 2 – 1
_(;75(0(/<_,19_ (Type C) = --------------------------- ⋅ Tp
For All Characteristics
t trip time in seconds
Tp setting value of the time multiplier
I fault current
Ip setting value of the pickup current
[s]
[s]
[s]
Technical Data
10-14 7UM61 Manual
C53000-G1176-C127-1
Figure 10-1 Trip Characteristics of the Inverse-time Overcurrent Protection, as per IEC 60755–3 (phases
and ground)
Extremely Inverse:
(Type C)
t 80 [s]
(I⁄ Ip)2
–1
= ---------------------------- ⋅ Tp
0,1
0,2
0,4
1,6
3,2
0,05
Extremely inverse:
(Type C)
I/Ip
1
0,3
0,1
1 2 3 5 10 20
100
20
10
5
2
0,5
0,2
0,05
Normal inverse: Very inverse:
(Type B)
Tp
t [s] t [s]
I/Ip I/Ip
1
0,3
0,1
1 2 3 5 10 20
100
20
10
5
2
0,5
0,2
0,05
[s] [s]
1 2 3 5 10 20
0,3
0,1
100
20
10
2
0,05
5
[s]
0,2
0,5
1
t [s]
3
3
30 30
3
t
0,14
(I ⁄ Ip)0,02
–1
= -------------------------------------- ⋅ Tp
(Type A)
t
13, 5
(I ⁄ Ip)1
–1
= ---------------------------- ⋅ Tp
t 80
(I ⁄ Ip)2
–1
= ---------------------------- ⋅ Tp
0,8
0,1
0,2
0,4
1,6
3,2
0,05
0,8
7
Tp
0,1 0,2
0,4
1,6
3,2
0,8
Tp
0,05
t trip time in seconds
Tp setting value of the time factor
I fault current
Ip setting value of the pickup current
Technical Data
7UM61 Manual 10-15
C53000-G1176-C127-1
Trip Time Characteristics
As Per
ANSI
As per ANSI/IEEE (see also Figures 10-2 and 10-3)
The trip times for I/Ip ≥ 20 are identical to those for I/Ip = 20.
Pickup Threshold approx. 1.10 · Ip
Dropout threshold approx. 1.05 · Ip for Ip/IN ≥ 0.3
corresponds to approx. [0.95 · pickup
threshold]
Tolerances Pickup Currents Ip 1 % of setting value, or 50 mA1)
Voltage threshold U< 1 % of setting value, or 0,5 V
Trip Time for 2 ≤ I/Ip ≤ 20 5 % of reference (calculated) value + 1 %
current tolerance, respectively 40 ms
Influencing Variables
for Pickup
Power supply direct voltage in range
0.8 ≤ VPS/ VPS nominal ≤ 1.15 1 %
Temperature in range
23º F ≤ ϑ amb ≤ 131º F 0.06% /10º F
–5º C ≤ ϑ amb ≤ 55º C 0.5 %/10 K
Frequency in range
0.95 ≤ f/fN ≤ 1.05 < 1 %
1) For IN = 1 A, divide all limits and increments by 5.
t 8.9341
(I ⁄ Ip) 2.0938 – 1
--------------------------------------- + 0.17966
,19(56( = ⋅ D
9(5<_,19(56(
(;75(0(/<_,19(56(
For all Characteristics
t = Trip time in seconds
D = Setting value of the time multiplier
I = Fault Current
Ip = Setting value of the pickup current
'(),1,7(_,19(56(
02'(5$7(/<_,19_ t 0.0103
(I ⁄ Ip) 0.02 – 1
--------------------------------- + 0.0228
=⋅ D
t 3.922
(I ⁄ Ip) 2 – 1
-------------------------- + 0.0982
=⋅ D
t 5.64
(I ⁄ Ip) 2 – 1
-------------------------- + 0.02434
=⋅ D
t 0.4797
(I ⁄ Ip) 1.5625 – 1
--------------------------------------- + 0.21359
=⋅ D
[s]
[s]
[s]
[s]
[s]
Technical Data
10-16 7UM61 Manual
C53000-G1176-C127-1
Figure 10-2 Trip Time Characteristics Of The Inverse-time Overcurrent Protection, As Per ANSI/IEEE
D [s]
I/Ip
1
2
5
10
15
0.5
2 3 5 10 20
0.3
0.1
500
20
10
2
0.05
5
0.2
0.5
1
t [s]
30
100
200
3
50
1
VERY INVERSE t 3, 922 [s]
(I ⁄ Ip)2
–1
---------------------------- +0,0982
=⋅ D
MODERATELY INVERSE t 0, 0103
(I ⁄ Ip)0,02
–1
-------------------------------------- + 0, 0228
=⋅ D
D [s]
I/Ip
1
2
5
10
15
0.5
2 3 5 10 20
0.3
0.1
500
20
10
2
0.05
5
0.2
0.5
1
t [s]
30
100
200
3
50
1
[s]
0.3
0.1
500
20
10
2
0.05
5
0.2
0.5
1
t [s]
30
100
200
3
50
5
2
1
0.5
10
D [s]
15
I/Ip
1 2 3 5 10 20
t 8, 9341
(I ⁄ Ip)2, 0938
–1
-------------------------------------------- + 0, 17966
INVERSE = ⋅ D [s]
t trip time in seconds
D setting value of the time factor
I fault current
Ip setting value of the pickup current
Technical Data
7UM61 Manual 10-17
C53000-G1176-C127-1
Figure 10-3 Trip Time Characteristics Of The Inverse-time Overcurrent Protection, As Per ANSI/IEEE
D [s]
I/Ip
1
2
5
10
15
0.5
2 3 5 10 20
0.3
0.1
500
20
10
2
0.05
5
0.2
0.5
1
t [s]
30
100
200
3
50
1
EXTREMELY INVERSE t 5, 64
(I ⁄ Ip)2
–1
---------------------------- + 0, 02434
= ⋅ D [s]
D [s]
I/Ip
1
2
5
15
0.5
1 2 3 5 10 20
DEFINITE INVERSE t 0,4797 [s]
(I ⁄ Ip)1, 5625 – 1
-------------------------------------------- + 0, 21359
=⋅ D
0.3
0.1
500
20
10
2
0.05
5
0.2
0.5
1
t [s]
30
100
200
3
50
10
t trip time in seconds
D setting value of the time factor
I fault current
Ip setting value of the pickup current
Technical Data
10-18 7UM61 Manual
C53000-G1176-C127-1
10.4 Thermal Overload Protection (ANSI 49)
Setting Ranges/
Resolutions
K-Factor per IEC 60255-8 0.50 to 2.50 (Increments 0.01)
Time Constant τ 30 sec to 32000 sec (Increments 1 sec)
Extension K-Factor kt - Factor 1.0 to 10.0 relative to the time constant for
when Machine Stopped the machine running (Increments 0.1)
Thermal Alarm Θ Alarm/Θ Trip 70% to 100% of the trip temperature rise
(Θ ALARM) (Increments 1%)
Current Overload IAlarm 0.50 A to 20.00 A1) (Increments 0.05 A)1)
Alarm (I ALARM)
Rated temperature rise 40° C to 200° C (Increments 1° C)
at rated sec. current 104° F to 392° F (Increments 1° F)
Cooling medium temperature 40° C to 300° C (Increments 1° C)
for scaling 104° F to 572° F (Increments 1° F)
Current limiting IMax therm. 2.50 A to 40.00 A1) (Increments 0.05 A)1)
Emergency Time 10 s to 15000 s (Increments 1 s)
Trip Characteristic
Curve
See also Figure 10-4
Dropout Relations Θ /Θ trip Drops out with Θ Alarm
Θ /Θ Alarm approx. 0.99
I/IAlarm approx. 0.95
Tolerances Referring to k · IN 1 % or 50 mA1); 2 % class per
IEC 60 255–8
Thermal trip and alarm times 3 % or 1 s for I/(k ·IN) > 1.25;
3 % class per IEC 60 255–8
Influencing Variables
Referring to
[k · IN]
Power supply DC voltage (VDC) in range
0.8 ≤ VPS/ VPS nominal ≤ 1.15 1 %
Temperature in range
23 °F≤ ϑ amb ≤ 131 °F 0.3% /10º F
–5º C ≤ ϑ amb ≤ 55º C 0.5 %/10 K
Frequency in range
0.95 ≤ f/fN ≤ 1.05 < 1 %
1) For IN = 1 A, divide all limits and increments by 5.
tτ
I
k ⋅ IN ------------
2 Ipre
k ⋅ IN ------------
2
–
I
k ⋅ IN ------------
2
–1
= ⋅ ln -------------------------------------------------
Trip Characteristic Curve
t trip time
τ Temperature rise time constant
I Load current
Ipre Pre-load current
k Setting factor per VDE 0435
Part 3011 and IEC 60255–8
IN Nominal current of the device
Where:
for (I/ k · IN) ≤ 8
Technical Data
7UM61 Manual 10-19
C53000-G1176-C127-1
Figure 10-4 Trip Time Characteristic Curves For The Thermal Overload Protection (49)
Willi Anwender
1
0.3
0.1
1 2 3 5 10 12
100
20
10
5
2
0.5
0.2
0.05
t [min] t [min]
I/k · IN
1000
1
0.3
0.1
100
20
10
5
2
0.5
0.2
0.05
[min]
3
30 30
3
Parameter:
Setting Value
of Time Constant
20
200
500
100
50
10
5
12
4678
50
tτ
I
k ⋅ IN -------------
2
I
k ⋅ IN -------------
2
–1
= ⋅ ln --------------------------------
without pre-load and with IMax therm.= 8 ⋅ k ⋅ IN:
I/k · IN
1 2 3 4 5 6 7 8 10 12
with 90 % pre-load and with IMax therm.= 8 ⋅ k ⋅ IN:
tτ
I
k⋅ IN -------------
2 Ipre
k⋅ IN -------------
2
–
I
k⋅ IN -------------
2
–1
=⋅ ln ---------------------------------------------------
50
Parameter:
Setting Value
of Time Constant
1000
500
200
100
50
20
1 2 5 10
τ [min]
τ [min]
[min]
Technical Data
10-20 7UM61 Manual
C53000-G1176-C127-1
10.5 Unbalanced load protection (ANSI 46)
Setting Ranges/
Resolutions
Permissible unbalanced load I2>/IN 3.0 % to 30.0 % (Increments 0.1 %)
(warn. level too)
Tripping stage (definite time)I2>>/IN 10 % to 100 % (Increments 1 %)
Time delays T(I2>), T(I2>>) 0.00 s to 60.00 s (Increments 0.01 s)
or ∞ (does not expire)
Asymmetry factor K 2.0 s to 40.0 s (Increments 0.1 s)
Time for cool down TCool down 0 s to 50000 s (Increments 1 s)
Trip characteristic refer also to Figure 10-5
Inherent Operating
Times
Pickup times
Warning stage I2>, tripping stage I2>> approx. 60 ms
Dropout Times
Warning stage I2>, tripping stage I2>> approx. 60 ms
Dropout Warning stage I2>, tripping stage I2>> approx. 0.95
Thermal replica drop-off at I2 < I2 perm.
Tolerances Pickup values I2>, I2>> 3 % of setting value or 1 % unbal. load
Delay Times T 1 % of setting value or 10 ms
Thermal replica for 2 ≤ I2/I2 perm.≤ 20 5 % of reference (calculated) value + 1 %
current tolerance, respectively 600 ms
Influencing Variables
for Pickup
Power supply direct voltage in range
0.8 ≤ VPS/ VPS nominal ≤ 1.15 1 %
Temperatur in range
23º F ≤ ϑ amb ≤ 131º F 0.06% /10º F
–5º C ≤ ϑ amb ≤ 55º C 0.5 %/10 K
Frequency in range
0.95 ≤ f/fN ≤ 1.05 1 %
Harmonic currents
– Up to 10 % 3. Harmonic 1 %
– Up to 10 % 5. Harmonic 1 %
t
K
(I2 ⁄ IN) 2
= ----------------------
Trip characteristic of the thermal replica
t – tripping time
K – Asymmetry factor
I2 – Negative sequence current
IN – Nominal current of the device
I2 perm. – continously permissible negative
– sequece current
Where:
for I2/I2 perm. ≤ 10
Technical Data
7UM61 Manual 10-21
C53000-G1176-C127-1
Figure 10-5 Trip characteristics of the thermal unbalanced load protection stage
1 2 3 4 5 6 7 8 9 10
1
2
3
4
6
10
20
30
40
100
I2/In
0.05 0.07 0.1 0.2 0.3 0.4 0.5 0.7 1
s
t
1
2
4
10
20
40
100
200
400
1000
2000
10000
Schieflast
t = f (I2/In)
tK
(I2 ⁄ IN) 2
= ---------------------- for I2/I2 Zul. ≤ 10
Parameter:
Setting value
FACTOR K
40 s
30 s
20 s
15 s
10 s
5s
2s
Unbalanced Load
Technical Data
10-22 7UM61 Manual
C53000-G1176-C127-1
10.6 Underexcitation protection (ANSI 40)
Setting Ranges/
Resolutions
Conductance sections 1/xd CHAR. 0.25 to 3.00 (Increments 0.01)
Angle of inclination α 1, α 2, α 3 50° to 120° (Increments 1°)
Time delays T 0.00 s to 60.00 s (Increments 0.01 s)
or ∞ (does not expire)
Undervoltage lock-out 10.0 V to 125.0 V (Increments 0.1 V
Inherent Operating
Times
Pickup times
– Stator criterion 1/xd CHAR., α approx. 60 ms
– Undervoltage lock-out U1< approx. 50 ms
Dropout – Stator criterion 1/xd CHAR., α approx. 0.95
– Undervoltage lock-out U1< approx. 1.1
Tolerances – Stator criterion 1/xd CHAR. 3 % of setting value
– Stator criterion α 1° electrical
– Undervoltage lock-out U1< 1 % of setting value
– Delay Times T 1 % of setting value or 10 ms
Influencing Variables
for Pickup
Power supply direct voltage in range
0.8 ≤ VPS/ VPS nominal ≤ 1.15 1 %
Temperatur in range
23º F ≤ ϑ amb ≤ 131º F 0.06% /10º F
–5º C ≤ ϑ amb ≤ 55º C 0.5 %/10 K
Frequency in range
0.95 ≤ f/fN ≤ 1.05 1 %
Harmonic currents
– Up to 10 % 3. Harmonic 1 %
– Up to 10 % 5. Harmonic 1 %
Technical Data
7UM61 Manual 10-23
C53000-G1176-C127-1
10.7 Reverse power protection (ANSI 32R)
Setting Ranges/
Resolutions
Reverse power Pr>/SN –0.50 % to 30.0 % (Increments 0.01 %)
Time delays T 0.00 s to 60.00 s (Increments 0.01 s)
or ∞ (does not expire)
Inherent Operating
Times
Pickup times
– Reverse power Pr> approx. 360 ms at 50 Hz
approx. 300 ms at 60 Hz
Drop-off times
– Reverse power Pr> approx. 360 ms at 50 Hz
approx. 300 ms at 60 Hz
Dropout – Reverse power Pr> approx. 0.6
Tolerances – Reverse power Pr> 0.25 % SN ± 3 % of set value
at Q < 0.5 SN
(SN....rated apparent power,
Q.......reactive power)
– Delay Times T 1 % of setting value or 10 ms
Influencing Variables
for Pickup
Power supply direct voltage in range
0.8 ≤ VPS/ VPS nominal ≤ 1.15 1 %
Temperatur in range
23º F ≤ ϑ amb ≤ 131º F 0.06% /10º F
–5º C ≤ ϑ amb ≤ 55º C 0.5 %/10 K
Frequency in range
0.95 ≤ f/fN ≤ 1.05 < 1 %
Harmonic currents
– Up to 10 % 3. Harmonic < 1 %
– Up to 10 % 5. Harmonic < 1 %
Technical Data
10-24 7UM61 Manual
C53000-G1176-C127-1
10.8 Forward active power supervision (ANSI 32F)
Setting Ranges/
Resolutions
Forward power Pf</SN 0.5 % to 120.0 % (Increments 0.1 %)
Forward power Pf>/SN 1.0 % to 120.0 % (Increments 0.1 %)
Time delays T 0.00 s to 60.00 s (Increments 0.01 s)
or ∞ (does not expire)
Inherent Operating
Times
Pickup times
– Forward power Pf<, Pf> approx. 360 ms at 50 Hz with high–accuapprox.
300 ms at 60 Hz racy measurement
approx. 60 ms at 50 Hz with high–speed
approx. 50 ms at 60 Hz measurement
Drop-off times
– Forward power Pf<, Pf> approx. 360 ms at 50 Hz with high–accuapprox.
300 ms at 60 Hz racy measurement
approx. 60 ms at 50 Hz with high–speed
approx. 50 ms at 60 Hz measurement
Dropout – Forward power Pf< approx. 1.10 or 0.5 % of SN
Pf> approx. 0.90 or –0.5 % of SN
Tolerances – Forward power Pf<, Pf> 0.25 % SN ± 3 % of set value
with high–accuracy measurement
0.5 % SN ± 3 % of set value
with high–speed measurement
(SN....rated apparent power)
– Delay Times T 1 % of setting value or 10 ms
Influencing Variables
for Pickup
Power supply direct voltage in range
0.8 ≤ VPS/ VPS nominal ≤ 1.15 1 %
Temperatur in range
23º F ≤ ϑ amb ≤ 131º F 0.06% /10º F
–5º C ≤ ϑ amb ≤ 55º C 0.5 %/10 K
Frequency in range
0.95 ≤ f/fN ≤ 1.05 < 1 %
Harmonic currents
– Up to 10 % 3. Harmonic < 1 %
– Up to 10 % 5. Harmonic < 1 %
Technical Data
7UM61 Manual 10-25
C53000-G1176-C127-1
10.9 Impedance protection (ANSI 21)
Overcurrent fault
detection
Pickup Current IMP I> 0.50 A to 40.00 A1)(increments 0.05 A)1)
Drop-off ratio approx. 0.95
Measuring tolerances according ± 3% of set value
VDE 0435 part 303
Undervoltage seal-in U< 10.0 V to 125.0 V (increments 0.1 V)
Drop-off ratio approx. 1.05
Measuring tolerances according ± 3% of set value
VDE 0435 part 303
1) For IN = 1 A, divide all limits and increments by 5.
Impedance measurement
Characteristic polygonal, 3 independent stages
Impedance Z1 (based on IN = 5 A2) 0.01Ω to 26.00 Ω (increments 0.01 Ω )
Impedance Z1B (based on IN = 5 A2) 0.01Ω to 13.00 Ω (increments 0.01 Ω )
Impedance Z2 (based on IN = 5 A2) 0.01Ω to 13.00 Ω (increments 0.01 Ω )
Measuring tolerances according ∆ Z/Z ≤ 5 % for 30° ≤ ϕ K ≤ 90° or 10mΩ
VDE0435 part 303
with sinusoidal quantities
2) Secondary values for IN = 5 A; for IN = 1 A multiply all values by 5; the increment is
always 0.01 Ω .
Times Shortest tripping time 35 ms
Typical tripping time 40 ms
Time delays T 0.00 s to 60.00 s (Increments 0.01 s)
Dropout Time approx. 50 ms
Holding time of undervoltage seal-in 0.00 s to 32.00 s (Increments 0.01 s)
Time expiry tolerances 1 % of set value or 10 ms
Influencing Variables
for Pickup
Power supply direct voltage in range
0.8 ≤ VPS/ VPS nominal ≤ 1.15 1 %
Temperatur in range
23º F ≤ ϑ amb ≤ 131º F 0.06% /10º F
–5º C ≤ ϑ amb ≤ 55º C 0.5 %/10 K
Frequency in range
0.95 ≤ f/fN ≤ 1.05 < 1 %
Harmonic currents
– Up to 10 % 3. Harmonic < 1 %
– Up to 10 % 5. Harmonic < 1 %
Technical Data
10-26 7UM61 Manual
C53000-G1176-C127-1
10.10 Undervoltage protection (ANSI 27)
Setting Ranges /
Resolution
Measurement Quantities: PositiveSequence Voltages
Pickup Voltage 27-1, 27-2 10.0 V to 125.0 V (Increments 0.1 V)
Dropout Ratio for 27-1, 27-2 1.01 to 1.20 (Increments 0.01)
Time Delay 27-Delay 0.00 s to 60.00 s (Increments 0.01 s)
or ∞ (does not expire)
The set time are pure delay times.
Inherent Operating
Times
Pickup Times
27-1, 27-2 approx. 50 ms
Dropout Times
27-1, 27-2 approx. 50 ms
Tolerances – Pickup Voltages 1% of set value, or 0.5 V
– Time Delays T 1% of set value, or 10 ms
Influencing Variables
Power supply DC voltage (VDC) in range
0.8 ≤ VPS/ VPS nominal ≤ 1.15 1%
Temperature in range
23º F ≤ ϑ amb ≤ 131º F 0.3 % /10º F
–5º C ≤ ϑ amb ≤ 55º C 0.5 %/10 K
Frequency in range
0.95 ≤ f/fN ≤ 1.05 < 1%
Harmonics
- Up to 10% 3rd harmonic < 1%
- Up to 10% 5th harmonic < 1%
Technical Data
7UM61 Manual 10-27
C53000-G1176-C127-1
10.11 Overvoltage protection (ANSI 59)
Setting Ranges /
Resolution
Measurement Quantities: maximum of the phase–to–phase voltages,
calculated from the phase–to–earth voltages
Pickup Voltage 59-1, 59-2 30.0 V to 170.0 V (Increments 0.1 V)
Dropout Ratio for 59-1, 59-2 0.90 to 0.99 (Increments 0.01)
Time Delay 59-Delay 0.00 s to 60.00 s (Increments 0.01 s)
or ∞ (does not expire)
The set time are pure delay times.
Inherent Operating
Times
Pickup Times
59-1, 59-2 approx. 50 ms
Dropout Times
59-1, 59-2 approx. 50 ms
Tolerances – Pickup Voltages 1% of set value, or 0.5 V
– Time Delays T 1% of set value, or 10 ms
Influencing Variables
Power supply DC voltage (VDC) in range
0.8 ≤ VPS/ VPS nominal ≤ 1.15 1%
Temperature in range
23º F ≤ ϑ amb ≤ 131º F 0.3 % /10º F
–5º C ≤ ϑ amb ≤ 55º C 0.5 %/10 K
Frequency in range
0.95 ≤ f/fN ≤ 1.05 < 1%
Harmonics
- Up to 10% 3rd harmonic < 1%
- Up to 10% 5th harmonic < 1%
Technical Data
10-28 7UM61 Manual
C53000-G1176-C127-1
10.12 Frequency Protection (ANSI 81)
Setting Ranges/
Resolutions
Number of Frequency Elements 4: each can be 81/O or 81/U
Pickup Frequency 81–1 to 81–4 40.00 Hz to 65.00 Hz (Increments 0.01 Hz)
Time Delay 81–1 0.00 s to 600.00 s (Increments 0.01 s)
81–2 to 81–4 0.00 s to 100.00 s (Increments 0.01 s)
Undervoltage Blocking Umin 10.0 V to 125.0 V (Increments 0.1 V)
(U1 positive sequence voltage)
The set times are pure delay times.
Inherent Operating
Times
Pickup Times 81/O or 81/U approx. 100 ms
Dropout Times 81/O or 81/U approx. 100 ms
Dropout Frequency ∆ f = | Pickup Value – Dropout Value | approx. 20 mHz
Dropout Voltage Dropout Ratio for
Undervoltage Blocking(U / Umin) approx. 1.05
Tolerances – Pickup Frequencies 81/O or 81U 10 mHz
– Undervoltage Blocking 1% of set value or 0.5 V
– Time Delays 81/O or 81/U 1% of set value or 10 ms
Influencing Variables
Power supply DC voltage (VDC) in range
0.8 ≤ VPS/ VPS nominal ≤ 1.15 0.1%
Temperature in range
23º F ≤ ϑ amb ≤ 131º F 0.06% /10º F
–5º C ≤ ϑ amb ≤ 55º C 0.5 %/10 K
Harmonics
- Up to 10% 3rd harmonic < 1%
- Up to 10% 5th harmonic < 1%
Technical Data
7UM61 Manual 10-29
C53000-G1176-C127-1
10.13 Overexcitation protection U/f> (ANSI 24)
Setting Ranges/
Resolutions Overexcitation (ratio ) 1.00 to 1.20 (Increments 0.01)
(warning stage)
Overexcitation (ratio ) 1.00 to 1.40 (Increments 0.01)
(stepped characteristic)
Time delay T 0.00 s to 60.00 s (Increments 0.01 s)
(warning stage
and stepped charact. or ∞ (does not expire)
Pair of values for
characteristic of U/f 1.10 / 1.15 / 1.20 / 1.25 / 1.30 / 1.35 / 1.40
thermal replica T 0 s to 20000 s (Increments 0.01 s)
Time for cool down TCOOL DOWN 0 s to 20000 s (Increments 1 s)
Inherent Operating
Times
Warning stage and stepped characteristic
– Pickup Times at 1.1 times setting valueapprox. 60 ms
– Dropout Times approx. 60 ms
Dropout Dropout/Pickup approx. 0.95
Tripping time characteristic
thermal replica according presettings refer Figure
Tolerances Pickup on U/f 3 % of setting value )
Delay Times T 1 % of setting value or 10 ms
thermal replica 5 %, related to U/f ± 600 ms
Influencing Variables
for Pickup
Power supply direct voltage in range
0.8 ≤ VPS/ VPS nominal ≤ 1.15 1 %
Temperatur in range
23º F ≤ ϑ amb ≤ 131º F 0.06% /10º F
–5º C ≤ ϑ amb ≤ 55º C 0.5 %/10 K
Frequency in range
0.95 ≤ f/fN ≤ 1.05 < 1 %
Harmonic currents
– Up to 10 % 3. Harmonic < 1 %
– Up to 10 % 5. Harmonic < 1 %
U / UN
f / fN
>
U / UN
f / fN
>
Technical Data
10-30 7UM61 Manual
C53000-G1176-C127-1
Figure 10-6Tripping time characteristic of thermal replica and of stepped stage of the overexcitation
protection (pre–settings)
1.1 1.2 1.3 1.4
1
2
3
5
10
20
30
50
100
200
300
500
1000
2000
3000
10000
t [s]
U⁄ f
UN ⁄ fN -----------------
T U/f>>
(Pickup/warning stage)
U/f> U/f>>
Technical Data
7UM61 Manual 10-31
C53000-G1176-C127-1
10.14 90–%–Stator earth fault protection (ANSI 59N, 64G, 67G)
Setting Ranges/
Resolutions
Displacement voltage U0> 5.0 V to 125.0 V (Increments 0.1 V)
Residual Current IE> 2 mA to 1000 mA (Increments 1 mA)
Inclination of directional characteristic 0° to 360° (Increments 1°)
Time delays T 0.00 s to 60.00 s (Increments 0.01 s)
or ∞ (does not expire)
The set times are pure delay times.
Inherent Operating
Times
– Pickup Times UE approx. 50 ms
IE approx. 50 ms
Direction approx. 70 ms
– Dropout Times UE approx. 50 ms
IE approx. 50 ms
Direction approx. 70 ms
Dropout Displacement voltage UE approx.0.70
Residual Current IE> approx. 0.70
Hysteresis of directional characteristic approx. 10°
Tolerances Displacement voltage UE 1 % of setting value or 0.5 V
Residual Current IE> 1 % of setting value or 0.5 mA
Delay Times T 1 % of setting value or 10 ms
Influencing Variables
for Pickup
Power supply direct voltage in range
0.8 ≤ VPS/ VPS nominal ≤ 1.15 1 %
Temperatur in range
23º F ≤ ϑ amb ≤ 131º F 0.06% /10º F
–5º C ≤ ϑ amb ≤ 55º C 0.5 %/10 K
Frequency in range
0.95 ≤ f/fN ≤ 1.05 < 1 %
Harmonic currents
– Up to 10 % 3. Harmonic < 1 %
– Up to 10 % 5. Harmonic < 1 %
Technical Data
10-32 7UM61 Manual
C53000-G1176-C127-1
10.15 Sensitive earth current detection (ANSI 51GN, 64F)
Setting Ranges/
Resolutions
Overcurrent pick-up IEE> 2 mA to 1000 mA (increments 1 mA)
Delay time TIEE> 0.00 s to 60.00 s (increments 0.01 s
or ∞ (does not expire)
Overcurrent pick-up IEE>> 2 mA to 1000 mA (increments 1 mA)
Delay time TIEE>> 0.00 s to 60.00 s (increments 0.01 s
or ∞ (does not expire)
Measured value supervision
when used as rotor earth
fault protection IEE< 1.5 mA to 50.0 mA (increments 0.1 mA)
or 0,0 mA (ineffective)
Inherent Operating
Times
– Pickup Times approx. 60 ms
– Dropout Times approx. 50 ms
– Measured value supervision approx. 2 s
Dropout Overcurrent pick-up IEE>, IEE>> approx.0.95 or 1 mA
Measured value superv. IEE< approx. 1.10
Tolerances Overcurrent pick-up 1 % of setting value or 0.5 V
Delay Times T 1 % of setting value or 10 ms
Influencing Variables
for Pickup
Power supply direct voltage in range
0.8 ≤ VPS/ VPS nominal ≤ 1.15 1 %
Temperatur in range
23º F ≤ ϑ amb ≤ 131º F 0.06% /10º F
–5º C ≤ ϑ amb ≤ 55º C 0.5 %/10 K
Frequency in range
0.95 ≤ f/fN ≤ 1.05 < 1 %
Harmonic currents
– Up to 10 % 3. Harmonic < 1 %
– Up to 10 % 5. Harmonic < 1 %
Note: For the purpose of high sensitivity, the linear range of the measuring input for
the sensitive ground fault acquisition is from 2 mA A to 1600 mA.
Technical Data
7UM61 Manual 10-33
C53000-G1176-C127-1
10.16 100–%–Stator earth fault protection with 3rd harm.
(ANSI 27/59TN)
Setting Ranges/
Resolutions
Pick–up value for 3rd harmonic
in undervoltage stage U0 3. HARM< 0.2 V to 40.0 V (increments 0.1 V)
Pick–up value for 3rd harmonic
in overvoltage stage U0 3. HARM> 0.2 V to 40.0 V (increments 0.1 V)
iDelay time TSEF 3. HARM.) 0.00 s to 60.00 s (increments 0.01 s)
oder ∞ (unwirksam)
Release threshold P/Pmin > 10 % to 100 % (increments 1 %)
or 0 (ineffective)
U/U1 min> 50.0 V to 125.0 V (increments 0.1 V)
or 0 (ineffective)
Inherent Operating
Times
– Pickup Times approx. 80 ms
– Dropout Times approx. 80 ms
Dropout Undervoltage stage U0 3. HARM< approx. 1,40
Overvoltage stage U0 3. HARM> approx. 0,60
Release thresholds P/Pmin > approx. 0,90
U/U1 min> approx. 0,95
Toleranzen – Displacement voltage 3 % of setting value or 0.1 V
– Delay time TSEF 3. HARM. 1 % of setting value or 10 ms
Influencing Variables
for Pickup
Power supply direct voltage in range
0.8 ≤ VPS/ VPS nominal ≤ 1.15 1 %
Temperatur in range
23º F ≤ ϑ amb ≤ 131º F 0.06% /10º F
–5º C ≤ ϑ amb ≤ 55º C 0.5 %/10 K
Frequency in range
0.95 ≤ f/fN ≤ 1.05 < %
Harmonic currents
– Up to 10 % 3. Harmonic < 1 %
– Up to 10 % 5. Harmonic < 1 %
Technical Data
10-34 7UM61 Manual
C53000-G1176-C127-1
10.17 Breaker Failure Protection (ANSI 50BF)
Pickup and Time
Delay Ranges/
Resolutions
Pickup of 50 Element CIRC.BR.I> 0.20 A to 5.00 A 1) (Increments 0.05 A)1)
Time Delay TRIP-Timer 0.06 s to 60.00 s (Increments 0.01 s)
or ∞ ( no trip)
Initiating Time Pickup Times (protection initiates)
- For Internal Start approx. 50 ms
- Using Controls approx. 50 ms
- For External Start approx. 50 ms
Reset Time approx. 50 ms
Tolerances Pickup Current CIRC.BR.I> 1% of set value, or 50 mA1)
Time Delay TRIP-Timer 1% or 10 ms
Influencing Variables
Power supply DC voltage (VDC) in range
0.8 ≤ VPS/ VPS nominal ≤ 1.15 1%
Temperature in range
23º F ≤ ϑ amb ≤ 131º F 0.3 % /10º F
–5º C ≤ ϑ amb ≤ 55º C 0.5 %/10 K
Frequency in range
0.95 ≤ f/fN ≤ 1.05 < 1%
Harmonics
- Up to 10% 3rd harmonic < 1%
- Up to 10% 5th harmonic < 1%
1) For IN = 1A, divide all limits by 5.
Technical Data
7UM61 Manual 10-35
C53000-G1176-C127-1
10.18 Inadvertent energization (ANSI 50/27)
Setting Ranges/
Resolutions
Overcurrent pick-up ISTAGE 0.5 A to 100.0 A1) (increments 0.1 A)1)
or ∞ (does not expire)
Release U1< 10.0 V to 125,0 V (increments 0,1 V)
Time delay PICK UP T U1< 0.00 s to 60.00 s (increments 0,01 s)
or ∞ (does not expire)
Drop Out time delay DROP OUT T U1<0.00 s to 60.00 s (increments 0,01 s)
or ∞ (does not expire)
Inherent Operating
Times
– Pickup Times approx. 25 ms
– Dropout Times approx. 35 ms
Dropout I>>> approx. 0.80 or 50 mA
Release threshold U1< approx. 1,05
Toleranzen Overcurrent pick-up I>>> 5 % of setting value or 100 mA1)
Release U1< 1 % of setting value or 0,5 V
Delay Times T 1 % of setting value or 10 ms
Influencing Variables
Power supply DC voltage (VDC) in range
0.8 ≤ VPS/ VPS nominal ≤ 1.15 1%
Temperature in range
23º F ≤ ϑ amb ≤ 131º F 0.3 % /10º F
–5º C ≤ ϑ amb ≤ 55º C 0.5 %/10 K
Frequency in range
0.95 ≤ f/fN ≤ 1.05 1%
1) For IN = 1A, divide all limits by 5.
Technical Data
10-36 7UM61 Manual
C53000-G1176-C127-1
10.19 Additional Functions
Operational Measured
Values
Operating Measured Values IL1, IL2, IL3
for Currents in A or kA primary; in A secondary,
or in % of INom
- Range 10 % to 200 % INom
- Tolerance 0.2 % of measured value or 10 mA ± 1 Digit
IEE and 3I0
in A or kA primary; in A and in % of INom
secondary
Positive sequence current I1
in A or kA primary; in A secondary,
or in % of INom
Negative sequence current I2
in A or kA primary; in A secondary,
or in % of INom
Operating Measured Values UL1, UL2, UL3
for Voltages (phase-ground) in kV primary; in V secondary
or in % of UNom
- Range 10 % to 120 % UNom
- Tolerance 0.2 % of measured value or ± 0.2 V ± 1 Digit
Operating Measured Values UL1-L2, UL2-L3, UL3-L1
for Voltages (phase-phase) in kV primary; in V secondary
or in % of UNom
- Range 10 % to 120 % UNom
- Tolerance 0.2 % of measured value or ± 0.2 V ± 1 Digit
Uen and 3U0
in kV primary; in V secondary
or in % of UNom
Positive sequence voltage U1 and
Negative sequence voltage U2
in kV primary; in V secondary or
in % of UNom
Operating Measured Values R, X
for Resistances and Reactances in Ω primary and secondary
- Tolerance 1 %
Operating Measured Values S, Apparent Power in kVA (MVA or GVA)
for Power primary, and in % SNom
- Range 0 % to 120% SNom
- Tolerance 1 % ± 0.25 % SN
with SNom = √3 · UNom · INom
P, Real power (with sign) in kW (MW or
GW) primary, and in % SNom
- Range 0 % to 120 % SNom
- Tolerance 1 % ± 0.25 % SN
with SNom = √3 · UNom · INom
Q, Reactive power (with sign) in kVAr
(MVAr or GVAr) primary and in % SNom
- Range 0 % to 120 % SNom
Technical Data
7UM61 Manual 10-37
C53000-G1176-C127-1
- Tolerance 1 % ± 0.25 % SN
with SNom = √3 · UNom · INom
Operating Measured Values cos ϕ
for Power Factor
- Range –1 to +1
- Tolerance 1 % ± 1 Digit
Operating Measured Values ϕ
for Power angle
- Range –90° to +90°
- Tolerance 0.1°
Counter Values for Energy Wp, Wq (real and reactive energy)
in kWh (MWh or GWh) and in kVARh
(MVARh or GVARh)
- Range 81/2 digits (28 bit) for VDEW protocol
91/2 digits (31 bit) in T103 mode
- Tolerance 1% ± 1 Digit
Operating Measured Values f in Hz
for Frequency
- Range 40 Hz < f < 65 Hz
- Tolerance 10 mHz at U > 0.5 ⋅ UN
Operating Measured Values for Θ S/Θ S Trip
Thermal Overload Protection
- Range 0 % to 400%
- Tolerance 5 % class accuracy per IEC 60255-8
Operating Measured Values for IEE in A or kA primary and in mA
Sensitive Ground Fault Protection secondary
- Range 0 mA to 1600 A
- Tolerance 0.2 % of measured value or 10 mA ± 1 Digit
Min/Max Report Report of Measured Values with date and time
Reset – Automatic Time of day adjustable (in minutes).
Time frame and starting time
adjustable (in days, 1 to 365 days, and ∞).
Reset – Manual Using binary input
Using keypad
Using communication
Min/Max Values for Current I1 (positive sequence)
Min/Max Values for Voltage U1 (positive sequence)
Min/Max Values for 3rd harmonics UE3H
in displacement voltage
Min/Max Values for Power/ Other P, Q
Min/Max Values for Frequency f
Measured Values
Supervision
Current Asymmetry Imax/Imin > I - balance factor, for
I > I - balance limit. Factor and limit are
adjustable.
Technical Data
10-38 7UM61 Manual
C53000-G1176-C127-1
Voltage Asymmetry Umax/Umin > U - balance factor, for
U > U - balance limit. Factor and limit are
adjustable.
Current Sum | iL1+iL2+iL3 | > I - sum threshold value,
adjustable.
Voltage Sum |UL1 + UL2 + UL3 + kU · UE | > SUM.thres. U,
with kU = Uph/Udelta
Current Phase Sequence Clockwise (L1, L2, L3)/
counter-clockwise (L1, L3, L2)
Voltage Phase Sequence Clockwise (L1, L2, L3)/
counter-clockwise (L1, L3, L2)
Limit Value Monitor can be configured with CFC
IL < Limit value LV (ANSI 37-1)
Trip Log Recording of indication of the last 8 power system faults
Time Stamping Resolution for Event Log 1 ms
(Operational Messages)
Resolution for Trip Log (Fault Records) 1 ms
Time Deviation (Internal Clock) Maximum 0.01%
Buffer Battery Lithium Battery, 3 V / 1 Ah, type CR 1/2 AA
Self-discharging time > 5 years
Message “Fail Battery” if
battery charge is low
Waveform Capture optionally instantaneous values or r.m.s.
values
– instantaneous values
− Recording Time Total of 5 s
Pre-event and post-event recording
and memory time adjustable
− Sampling Rate for 50 Hz 1 sample/1.25 ms (16 sam/cyc)
Sampling Rate for 60 Hz 1 sample/1.04 ms (16 sam/cyc)
– r.m.s. values
− Recording Time Total of 80 s
Pre-event and post-event recording
and memory time adjustable
− Sampling Rate for 50 Hz 1 sample/20 ms (1 sam/cyc)
Sampling Rate for 60 Hz 1 sample/16.67 ms (1 sam/cyc)
Statistics (Circuit
Breaker)
Saved Number of Trips Up to 9 digits
Accumulated Interrupted Current Up to 4 digits (kA) per pole
Operating Hours
Counter
Operating Hours Range Up to 6 digits
Criterion to Count Current exceeds an adjustable current
threshold (BkrClosed I MIN)
Trip Circuit Monitor
(74TC)
With one or two binary inputs.
Technical Data
7UM61 Manual 10-39
C53000-G1176-C127-1
Commissioning
Start-up Aids
Phase Rotation Field Check
Operating Measured Values
Circuit Breaker / Switching Device Test
Creation of a Test Measurement Report
Clock Time Synchronization IRIG-B/DCF77-signal
Binary signal
Communication
Technical Data
10-40 7UM61 Manual
C53000-G1176-C127-1
10.20 Operating ranges of the protection functions
1) thermical replica registers cooling-down
2) pick -up – when already present – is maintained
3) pick -up – when already present – is maintained, if the measured voltage is not too small
Operational condition
1
The frequency follow-up circuit can operate only , when at least one a.c. measured
quantity is present at one of the the analog inputs (uL1, uL2, uL3, iL1, iL2, iL3), with an
amplitude of at least 5 % of rated value (operational condition 1).
Operational condition
0
If no suitable a.c. measured values are present, or if the frequency is below 11 Hz or
above 70 Hz, the relay cannot operate (operational condition 0).
Table 10-1 Operating ranges of the protection functions
Operat. cond. 0 Operational condition 1 Operat. cond. 0
Protection function f ≤ 10 Hz 11 Hz ≤ f/Hz ≤ 40 40 Hz ≤ f/Hz ≤ 70 f ≥ 70 Hz
Definite-time overcurrent prot. (50, 51, 67) inactive active active inactive
Inverse-time overcurrent protection (51) inactive active active inactive
Thermal overload protection (49) inactive1) active active inactive1)
Unbalanced load protection (46) inactive1) active active inactive1)
Underexcitation protection (40) inactive active active inactive
Reverse power protection (32R) inactive active active inactive
Forward active power supervision (32F) inactive active active inactive
Impedance protection (21) inactive active active inactive
Undervoltage protection (27) inactive2) active active inactive2)
Overvoltage protection (59) inactive active active inactive
Overfrequency protection (81/O) inactive active active inactive3)
Underfrequency protection (81/U) inactive active active inactive
Overexcitation protection U/f> (24) inactive1) active active inactive1)
90–%–Stator earth fault prot. (59N, 64G, 67G) inactive active active inactive
100–%–S/E/F with 3rd harm. (27TN, 59TN) inactive active active inactive
Sensitive earth current detection (51GN, 64F) inactive active active inactive
Breaker Failure Protection (50BF) inactive active active inactive
Inadvertent energization (50/27) active active active active
External trip commands active active active active
Technical Data
7UM61 Manual 10-41
C53000-G1176-C127-1
10.21 Dimensions
Housing for Panel
Flush Mounting or
Cubicle Installation
(Size 1/3)
7UM611
Figure 10-7 Dimensions 7UM611 for panel flush mounting or cubicle installation (size 1/3)
Note: 2 mounting brackets (Order-No. C73165–A63–C200–2) are necessary to install
the 7UM61 in a rack.
244
266
2
29,5 172
34
150
145
146 +2
255,8 ± 0,3
245 + 1
5 oder M4
6
244
266
2
29,5 172 34 29 30
105 ± 0,5
131,5 ± 0,3
13,2
7,3
5,4
Mounting plate Mounting plate
Side view (with screwed terminals) Side view (with clamp terminals) Rear view
Panel cut-out
Dimensions in mm
Technical Data
10-42 7UM61 Manual
C53000-G1176-C127-1
Housing for Panel
Flush Mounting or
Cubicle Installation
(Size 1/2)
7UM612
Figure 10-8 Dimensions 7UM612 for panel flush mounting or cubicle installation (size 1/2)
225
220
Rear view
221 +2
5 or M4
6
Panel cut-out
255.8 ± 0.3
245 + 1
180 ± 0.5
206.5 ± 0.3
13.2
7.3
5.4
244
266
2
29.5 172
34
Monting plate
Side view (with screwed terminals)
244
266
2
29.5 172 34
Mounting plate
29 30
Side view (with clamp terminals)
Dimensions in mm
Technical Data
7UM61 Manual 10-43
C53000-G1176-C127-1
Panel Mounting
(Housing size 1/3)
7UM611
Figure 10-9 Dimensions 7UM611 for panel mounting (size 1/3)
Panel Mounting
(Housing size 1/2)
7UM612
Figure 10-10 Dimensions 7UM612 for panel mounting (size 1/2)
n
280
165
144
150
320
344
10,5 260
29,5
71
72 52
25
266
Front view Side view
9
31 45
46 60
1 15
16 30
Dimensions in mm
280
240
219
225
320
344
10,5 260
29,5
71
72 52
25
266
Front view Side view
9 1 25
26 50
51 75
76 100
Dimensions in mm
Technical Data
10-44 7UM61 Manual
C53000-G1176-C127-1
7UM61 Manual A-1
C53000-G1176-C127-1
Appendix A
This appendix is primarily a reference for the experienced user. This Chapter provides
ordering information for the models of 7UM61. General diagrams indicating the terminal
connections of the 7UM61 models are included. Connection examples show the
proper connections of the device to primary equipment in typical power system configurations.
Tables with all settings and all information available in a 7UM61 equipped
with all options are provided.
A.1 Ordering Information and Accessories A-2
A.2 General Diagrams A-6
A.3 Connection Examples A-10
A.4 Definition of the Active Power Measurement A-17
A.5 Overview of the masking features of the user defined informations A-19
A.6 Default Settings A-23
A.7 Interoperability List A-27
A.8 Settings A-29
A.9 List of Information A-41
A.10 Protocol-Dependent Functions A-76
Appendix
A-2 7UM61 Manual
C53000-G1176-C127-1
A.1 Ordering Information and Accessories
Housing, Number of Binary Inputs and Outputs
Housing 1/3 19”, 7 BI, 11 BA, 1 Live Status Contact 1
Housing 1/2 19”, 15 BI, 19 BA, 1 Live Status Contact 2
Nominal Current
IN = 1 A 1
IN = 5 A 5
Auxiliary Voltage (Power Supply, Pick-up Threshold of Binary Inputs)
DC 24 to 48 V, pick-up binary inputs 17 V 2
DC 60 to 125 V, pick-up binary inputs 17 V 4
DC 110 to 250 V, AC 115 V, pick-up binary inputs 73 V 5
Construction
Surface mounting housing for panel, 2 tier terminals top/bottom B
Flush mounting housing with plug-in terminals (2/3 pin connector) D
Flush mounting housing for panel/cubicle, screw-type terminals (ring lugs) E
Region-Specific Default/Language Settings and Function Versions
Region DE, 50 Hz, IEC, German language (may be changed) A
Region world, 50/60 Hz, IEC/ANSI, English language (may be changed) B
Region US, 60 Hz, ANSI, US-English language (may be changed) C
More languages upon request
System Interface (Rear Port)
no system interface 0
IEC protocol, electrical RS232 1
IEC protocol, electrical RS485 2
IEC protocol, optical 820 nm, ST-plug 3
Profibus FMS Slave, RS485 4
Profibus FMS Slave, optical, double ring, ST-plug*) 6
For more interface options see “Additional Information L” 9
Service Interface (DIGSI 4/Modem) (Rear Port)
no service interface 0
DIGSI 4, electrical RS232 1
DIGSI 4, electrical RS485 2
DIGSI 4, optical 820 nm, ST-plug 3
Mean and Min/Max Metering
without 0
mean values, min/max values 3
continued next page A-3
*) on request
7UM61 _
7 8 13 14 15 16
_
9 10 11 12
Multifunction Machine Protection
6
Appendix
7UM61 Manual A-3
C53000-G1176-C127-1
Protective Elements
Basic Elements, included in all versions A
Definite time overcurrent protection with undervoltage seal-in(ANSI 50) (I> + U<)
Definite time overcurrent protection (ANSI 67) (I>>)
Inverse time overcurrent protection (ANSI 51) (Ip)
Thermal overload protection (ANSI 49) (I2t)
Reverse power protection (ANSI 32R) (–P>)
Undervoltage protection (ANSI 27) (U<)
Overvoltage protection (ANSI 59) (U>)
Frequency protection (ANSI 81) (f<, f>)
Overflux protection (ANSI 24) (U/f)
Stator earth fault protection (ANSI 59N, 64G, 67G) (U0>, IE>)
Sensitive ground fault protection (ANSI 50/51GN, 64R) (IEE>)
Fuse Failure Monitor (FFM)
External trip signals
Trip circuit supervision2) (ANSI 74TC)
Basic Elements
+ Additional functions 1, comprising: B
Forward active power supervision (ANSI 32F) (+P>)
Underexcitation protection (ANSI 40) (–Q>)
Unbalanced load protection (ANSI 46) (I2>)
Breaker failure protection (ANSI 50BF) (BF)
Basic Elements
+ Additional functions 1
+ Additional functions 2, comprising: C
Impedance protection (ANSI 21) (Z<)
Stator earth fault 100 % protection with 3rd harmonic (ANSI 59TN, 27TN) (U0 3rd harmonic)
Dead machine protection (ANSI 50, 27)
1) only for block connection, i.e. non-directional earth fault protection
2) only in 7UM612
Additional Information L +
System Interface (Rear Port)
Profibus DP, RS485 0 A
Profibus DP, optical, double ring 0 B
Modbus RS485*) 0 D
Modbus , optical*) 0 E
More interfaces on request
Ordering example: 7UM6111–4EA91–0BA0 + L0B
here: Pos. 11 = 9 stands for L0B, i.e. version with Profibus DPsystem port on the rear optical, double ring
*) to be implemented in the next software release
L
_ 7UM61
7 8 13 14 15 16
_
9 10 11 12
Mulifunction Machine Protection
6
A0
Appendix
A-4 7UM61 Manual
C53000-G1176-C127-1
A.1.1 Accessories
Terminal Block
Covering Caps
Short Circuit Links
Pin Connectors
Mounting Rail for
19"-Racks
Battery
Interface Cable An interface cable is necessary for communication between the SIPROTEC
device
and a PC. Requirements for the computer are Windows 95 or Windows NT4 and the
operating software DIGSI® 4.
Operating Software
DIGSI® 4
Software for setting and operating SIPROTEC® 4 devices
Covering cap for terminal block type Order No.
18 terminal voltage, 12 terminal current block C73334-A1-C31-1
12 terminal voltage, 8 terminal current block C73334-A1-C32-1
Short circuit links for purpose/terminal type Order No.
Voltage connections, 18 terminal, or 12 terminal C73334-A1-C34-1
Current connections,12 terminal, or 8 terminal C73334-A1-C33-1
Connector Type Order No.
2 pin C73334-A1-C35-1
3 pin C73334-A1-C36-1
Name Order No.
Angle Strip (Mounting Rail) C73165-A63-C200-2
Lithium-Battery 3 V/1 Ah, Type CR 1/2 AA Order No
VARTA 6127 501 501
SONNENSCHEIN 1110 150 301
Interface cable between PC or SIPROTEC device Order No.
Cable with 9-pin male/female connections 7XV5100-4
Operating Software DIGSI® 4 Order No.
DIGSI® 4, basic version with license for 10 computers 7XS5400-0AA00
DIGSI® 4, complete version with all option packages 7XS5402-0AA0
Appendix
7UM61 Manual A-5
C53000-G1176-C127-1
Graphical Analysis
Program DIGRA
Software for graphical visualization, analysis, and evaluation of fault data. Option
package of the complete version of DIGSI® 4
Display Editor Software for creating basic and power system control pictures. Option package
of the complete version of DIGSI® 4
Graphic Tools Graphical Software to aid in the setting of characteristic curves and provide zone
diagrams
for overcurrent and distance protective devices. Option package of the complete
version of DIGSI® 4.
DIGSI REMOTE 4 Software for remotely operating protective devices via a modem (and possibly
a star
connector) using DIGSI® 4. (Option package of the complete version of DIGSI® 4.
SIMATIC CFC 4 Graphical software for setting interlocking (latching) control conditions and
creating
additional function is SIPROTEC 4 devices. Option package for the complete version
of DIGSI® 4.
Coupling Unit The sensitive earth fault protection can be used as rotor earth fault protection. The
system frequency bias voltage for the rotor circuit is generated and coupled to the rotor
circuit via a coupling unit.
Graphical analysis program DIGRA® Order No.
Full version with license for 10 machines 7XS5410-0AA0
Display Editor 4 Order No.
Full version with license for 10 machines 7XS5420-0AA0
Graphic Tools 4 Order No.
Full version with license for 10 machines 7XS5430-0AA0
DIGSI REMOTE 4 Order No.
Full version with license for 10 machines 7XS5440-1AA0
SIMATIC CFC 4 Order No.
Full version with license for 10 machines 7XS5450-0AA0
Coupling unit for rotor earth fault protection Order No.
Coupling unit for panel flush mounting 7XR6100-0CA00
Appendix
A-6 7UM61 Manual
C53000-G1176-C127-1
A.2 General Diagrams
FigureA-1 General diagram 7UM611*–
The connections for additional serial interfaces are taken from Figure A-2.
Power
System
interface
Time
Service
interface
B
C
A
Earthing at the
supply
rear wall
Operator
interface
Q1
Q2
IL1
Q7
Q8
IEE
Q3
Q4
IL2
Q5
Q6
IL3
R15
R17
UL1
F17
F18
BI7
UL2
F10
F11
BI1
F13
F15
F16
F14
F12
BI2
BI4
BI5
BI6
BI3
F7
F9
BO3
F6
F8
BO1
F5
BO2
F1
F2
(~ )
+
-
R7
R8
BO17
R9
R10
BO18
Life status F3
F4
contact 1
32
2
synchronization
Assignment of Pins of Interfaces,
refer to Table 8-6 and
8-7 in Subsection 8.2.1
15
30
12
27
14
29
13
28
26
25
52
39
35
49
50
51
38
37
36
Flush mounting
Surface mounting
R13
R14
UE
59
60
R18
R16
24 UL3
9
BO12
BO13
BO14
BO16
BO15
R11
R12
BO19
32
33
46
47
31
55
42
54
41
45
58
44
56
57
43
53
40
R1
R2
R3
R5
R4
R6
34
48
10
11
Earthing at Side
Wall of Housing
(16)
1
32
2
Interference suppression
capacitors at the
Ceramic, 4.7 nF, 250 V
relay contacts,
Appendix
7UM61 Manual A-7
C53000-G1176-C127-1
FigureA-2 General diagram 7UM611*–*B (panel surface mounting)
Time
Service
interface
17
2
18
3
1
19
20
21
22
23
optical
electrical
or
Channel C
synchronization
CTS
RS232 RS485
RTS
GND
TxD
RxD
B
–
GND
A
–
IN 12 V
COMMON
IN 5 V
IN 24 V
Screen
System
interface
Channel B
4
5
6
7
8
optical
electrical
or
Profibus
B
C
CTS
RS232 RS485 Profibus
RTS
GND
TxD
RxD
B RxD/TxD-N
–
GND
A
–
P5
GND
RxD/TxD-P
CTRL-A
Appendix
A-8 7UM61 Manual
C53000-G1176-C127-1
FigureA-3 General diagram 7UM612∗−
The connections for additional serial interfaces are taken from Figure A-4.
Power
System
interface
Time
Service
interface
B
C
A
Earthing at the
supply
rear wall
Operator
interface
Q1
Q2
IL1
Q7
Q8
IEE
Q3
Q4
IL2
Q5
Q6
IL3
R15
R17
UL1
F17
F18
BI7
UL2
F10
F11
BI1
F13
F15
F16
F14
F12
BI2
BI4
BI5
BI6
BI3
K9
K10
BO8
F6
F8
BO1
F5
BO2
F1
F2
(~ )
+
-
K11
K12
BO9
K13
K14
BO10
Life status F3
F4
contact 1
32
2
synchronization
25
50
22
47
24
49
23
48
20
19
83
59
55
80
81
82
58
57
56
Flush mounting
Surface mounting
R13
R14
UE
21
46
R18
R16
44 UL3
45
BO12
BO13
BO14
BO16
BO15
K15
K16
BO11
87
63
76
77
51
86
62
85
61
74
99
73
97
98
72
84
60
R1
R2
R3
R5
R4
R6
54
79
15
16
Earthing at Side
Wall of Housing
(26)
K17
K18
43 BI8
18
J1
J2
42 BI9
17
J7
J8
38 BI13
13
J9
J10
37 BI14
12
J11
J12
36 BI15
11
J3
J4
BI10
J5
J6
BI11
BI12
41
40
14
39
R7
R8
BO17
R9
R10
BO18
R11
R12
BA19
96
71
95
70
94
69
F7
F9
BO3
K3
K4
BO4
52
53
90
66
BO5
BO7
BO6
65
89
88
64
K6
K5
K7
K8
1
32
2
1
32
2
Interference suppression
capacitors at the
Ceramic, 4.7 nF, 250 V
relay contacts,
Assignment of Pins of Interfaces,
refer to Table 8-6 and
8-7 in Subsection 8.2.1
Appendix
7UM61 Manual A-9
C53000-G1176-C127-1
FigureA-4 General diagram 7UM612*–*B (panel surface mounting)
Time
Service
interface
27
2
28
3
1
29
30
31
32
33
optical
electrical
or
Channel C
synchronization
CTS
RS232 RS485
RTS
GND
TxD
RxD
B
–
GND
A
–
IN 12 V
COMMON
IN 5 V
IN 24 V
Screen
System
interface
Channel B
4
5
6
7
8
optical
electrical
or
Profibus
B
C
CTS
RS232 RS485 Profibus
RTS
GND
TxD
RxD
B RxD/TxD-N
–
GND
A
–
P5
GND
RxD/TxD-P
CTRL-A
9 Screen
34 Screen
Appendix
A-10 7UM61 Manual
C53000-G1176-C127-1
A.3 Connection Examples
FigureA-5 Bus–bar connection
Current and voltage connections to three transformers, core balance neutral current transformers and open
delta voltage transformers (e–n).
IEE
UE
UL1
UL2
UL3
IL1
IL2
IL3
R18
R16
R17
R15
Q8
Q7
R13
R14
Q1
Q2
Q3
Q4
Q5
Q6
k
l
7UM61
L1
L2
L3
RL
Appendix
7UM61 Manual A-11
C53000-G1176-C127-1
FigureA-6 Busbar System with Low-ohmic, Switchable Starpoint Resistors
Connection to three current transformers and three voltage transformers (phase-to-ground voltages) –earth
fault detection as differential current measuring by two CT sets; detection of displacement voltage at open
delta winding (e–n).
IEE
UE
UL1
UL2
UL3
IL1
IL2
IL3
R18
R16
R17
R15
Q8
Q7
R13
R14
Q1
Q2
Q3
Q4
Q5
Q6
7UM61
L1
L2
L3
Diff.-Schutz
Diff.-Schutz
niederohmig
falls erforderlich
(zum Schutz des Widerstandes)
hier nicht erden
RE
diff. protection
diff. protection
low resistance
if necessary
(for saving the resistor)
Appendix
A-12 7UM61 Manual
C53000-G1176-C127-1
FigureA-7 Busbar System with High-ohmic, Switchable Starpoint Resistors
Connection to three current transformers and three voltage transformers (phase-to-ground voltages) –earth
fault detection as differential current measuring between the starpoint current and the summation current
measured via cable CTs; detection of displacement voltage at open delta winding (e–n).
IEE
UE
UL1
UL2
UL3
IL1
IL2
IL3
R18
R16
R17
R15
Q8
Q7
R13
R14
Q1
Q2
Q3
Q4
Q5
Q6
k
l
7UM61
L1
L2
L3
k
l
ca. 10A, 10s
falls erforderlich
(zum Schutz des Widerstandes)
RE RL
oder
Nullpunktstransformator
approx. 10 A,
if necessary
(for saving the resistor)
or
10 sec. neutral transformer
Appendix
7UM61 Manual A-13
C53000-G1176-C127-1
FigureA-8 Block connection
Connection to three current transformers and three voltage transformers (phase-to-earth voltages) – with
additional source 7XR61 for injecting a test voltage between the rotor circuit and the earth and with
supervision
of the rotor ground insulation by sensitive earth fault detection; detection of displacement voltage at
open delta winding (e–n).
IEE
UE
UL1
UL2
UL3
IL1
IL2
IL3
R18
R16
R17
R15
Q8
Q7
R13
R14
Q1
Q2
Q3
Q4
Q5
Q6
7UM61
L1
L2
L3
7XR61
+
-
Erdungstransformator
mit Messwicklung
Yd5
4A1
4B1 2B1
1B3
1A1
1A3
1B1
RL
earthing transformer
with open delta winding
and measuring winding
Appendix
A-14 7UM61 Manual
C53000-G1176-C127-1
FigureA-9 Block connection
Connection to three current transformers and three voltage transformers (phase-to-earth voltages) – with
additional source 7XR61 for injecting a test voltage between the rotor circuit and the earth and with
supervision
of the rotor ground insulation by sensitive earth fault detection; detection of displacement voltage at
starpoint transformer.
IEE
UE
UL1
UL2
UL3
IL1
IL2
IL3
R18
R16
R17
R15
Q8
Q7
R13
R14
Q1
Q2
Q3
Q4
Q5
Q6
7UM61
L1
L2
L3
7XR61
+
-
Yd11
RL
max. 10A Nullpunktstransformator
4A1
4B1 2B1
1B3
1A1
1A3
1B1
RE
neutral transformer
Appendix
7UM61 Manual A-15
C53000-G1176-C127-1
FigureA-10 Generator with Neutral Conductor
IEE
UL1
UL2
UL3
IL1
IL2
IL3
R18
R16
R17
R15
Q8
Q7
Q1
Q2
Q3
Q4
Q5
Q6
7UM61
N L1 L2 L3
Appendix
A-16 7UM61 Manual
C53000-G1176-C127-1
FigureA-11 Voltage Transformer Connections for Two Voltage Transformers in V Connection
FigureA-12 Current Transformer Connections with only Two Plant-Side Current Transformers
UL1
UL2
UL3
R18
R16
R17
R15
7UM61
L1 L2 L3
IL1
IL2
IL3
Q1
Q2
Q3
Q4
Q5
Q6
7UM61
L1 L2 L3
Appendix
7UM61 Manual A-17
C53000-G1176-C127-1
A.4 Definition of the Active Power Measurement
The 7UM61 used the generator reference-arrow system. The power output is positive.
Figure A-13 Definition of Positive Direction of Reference Arrows
Table A-1 shows the operating ranges for synchronous and asynchronous machines.
Parameter _____$&7,9(_32:(5_is set to *HQHUDWRU. “Normal condition” shows
the active power under normal operating conditions: + means that a positive power is
displayed on the protective device, – that the power is negative.
Tabelle A-1 Operating ranges for synchronous and asynchronous machines
Synchronous generator Synchronous motor
Asynchronous generator Asynchronous motor
I
GU
ϕ
+P
+Q
I
Stability U
limit
underexcited overexcited
Reactive power Q is controlled by the excitation,
Normal condition: +P and +Q
+P
+Q
I
U
Stability
limit
underexcited overexcited
Reactive power Q is controlled by the excitation,
Normal condition: –P and +Q
ϕ
ϕ
+P
+Q
I
U
Reactive power is drawn from the system
to maintain the excitation;
Normal condition: +P and –Q
PBREAK P ϕ
+P
+Q
I
U
The motor draws both active and reactive
power from the system;
Normal condition: –P and –Q
PBREAK
P
Appendix
A-18 7UM61 Manual
C53000-G1176-C127-1
Table A-1 shows that the operating ranges in generator and motor operation are mirrored
around the reactive power axis. The measured power values also result from the
above definition.
If, for instance, the forward power monitoring or the reverse power protection is to be
used in a synchronous motor, parameter _____$&7,9(_32:(5 must be set to 0R_
WRU. As a result, the actual active power (according to the above definition) is multiplied
with –1. This means that the power diagram is mirrored around the reactive power
axis and that the interpretation of the active power changes. This effect must be
considered when evaluating the metered energy values.
If, for instance, positive power values are to be obtained in an asynchronous motor,
the current direction (parameter _____&7_67$532,17) must be reversed. Parameter
_____$&7,9(_32:(5 remains set to *HQHUDWRU. This means that because of the
generator reference-arrow system the earthing of the CTs that must be entered in the
device is the opposite of the actual earthing. This leads to results that are comparable
to those of a load reference-arrow system.
Appendix
7UM61 Manual A-19
C53000-G1176-C127-1
A.5 Overview of the masking features of the user defined
informations
Type of Information Source Destination CFC Task level
Binary Inputs
Function Keys
CFC
Binary Outputs
LED
CFC
Measurement
PLC1
(slow)
PLC
(fast)
Interlocking
• Annunciation:
Single Point
– SP Single Point Indication ON/OFF X – X X X X – X X –
– SP Single Point Indication Open/Close X – X X X X – X X –
Double Point
– DP Double Point Indication (Breaker indication “00” = not
valid/transmitted as “3”)
X – X – – X X1) X X X2)
– DP_I Double Point Indication (Breaker indication “00” =
intermediate/transmitted as “0”)
X – X – – X X1) X X X2)
Output Slow
– OUT Output Indication ON/OFF – – X X X X X1) X X X2)
– OUT Output Indication Open/Close – – X X X X X1) X X X2)
Output Fast
– OUT Protection ON/OFF – – X X X X – X X X2)
– OUT Protection Open/Close – – X X X X – X X X2)
Tagging
– IntSP Internal Single Point Indication ON/OFF – X X X X X X1) X X X2)
– IntSP Internal Single Point Indication Open/Close – X X X X X X1) X X X2)
– IntDP Internal Double Point Indication (Breaker indication
“00” = not valid/transmitted as “3”)
– – X – – X X1) X X X2)
– IntDP_I Internal Double Point Indication (Breaker indication
“00” = intermediate/transmitted as “0”)
– – X – – X X1) X X X2)
Tap Changer
– TxTap Transformer Tap Changer X – – – – – – – – –
• Control Commands without feedback:
Single Controls
– C_S ON/OFF – – X X – X – X X X
– C_S Open/Close – – X X – X – X X X
1) Only for measurement setpoints (is processed cyclically every 600 ms); do not use for binary inputs.
2) Only for commands (is triggered by commands only).
Appendix
A-20 7UM61 Manual
C53000-G1176-C127-1
Single Controls negated
– C_SN ON/OFF – – X X – X – X X X
– C_SN Open/Close – – X X – X – X X X
Double Controls 1 Trip 1 Close
– C_D2 ON/OFF – – X X – X – X X X
– C_D2 Open/Close – – X X – X – X X X
– C_D2 Transformer Tap Changer – – X X – X – X X X
Double Controls 1 Trip 1 Close 1 Common
– C_D3 ON/OFF – – X X – X – X X X
– C_D3 Open/Close – – X X – X – X X X
– C_D3 Transformer Tap Changer – – X X – X – X X X
Double Controls 2 Trip 2 Close
– C_D4 ON/OFF – – X X – X – X X X
– C_D4 Open/Close – – X X – X – X X X
– C_D4 Transformer Tap Changer – – X X – X – X X X
Double Controls 1 Trip 2 Close
– C_D12 ON/OFF – – X X – X – X X X
– C_D12 Open/Close – – X X – X – X X X
– C_D12 Transformer Tap Changer – – X X – X – X X X
Double Controls negated
– C_D2N ON/OFF – – X X – X – X X X
– C_D2N Open/Close – – X X – X – X X X
– C_D2N Transformer Tap Changer – – X X – X – X X X
Type of Information Source Destination CFC Task level
Binary Inputs
Function Keys
CFC
Binary Outputs
LED
CFC
Measurement
PLC1
(slow)
PLC
(fast)
Interlocking
1) Only for measurement setpoints (is processed cyclically every 600 ms); do not use for binary inputs.
2) Only for commands (is triggered by commands only).
Appendix
7UM61 Manual A-21
C53000-G1176-C127-1
Type of Information Source Destination CFC Task level
Binary Inputs
Function Keys
CFC
Binary Outputs
LED
CFC
Measurement
PLC1
(slow)
PLC
(fast)
Interlocking
• Control Commands with feedback:
Single Controls
– CF_S Single Point Indication ON/OFF Control – – X X – X – X X X
– SP Feedback X – X X X X – X X X
– CF_S Single Point Indication Open/Close Control – – X X – X – X X X
– SP Feedback X – X X X X – X X X
– CF_S Double Point Indication (Breaker indication “00”
= not valid/transmitted as “3”)
Control – – X X – X – X X X
– DP Feedback X – X – – X – X X X
– CF_S Double Point Indication (Breaker indication
“00” = intermediate/transmitted as “0”)
Control – – X X – X – X X X
– DP_I Feedback X – X – – X – X X X
Double Controls 1 Trip 1 Close
– CF_D2 Single Point Indication ON/OFF Control – – X X – X – X X X
– SP Feedback X – X X X X – X X X
– CF_D2 Single Point Indication Open/Close Control – – X X – X – X X X
– SP Feedback X – X X X X – X X X
– CF_D2 Double Point Indication (Breaker indication “00”
= not valid/transmitted as “3”)
Control – – X X – X – X X X
– DP Feedback X – X – – X – X X X
– CF_D2 Double Point Indication (Breaker indication
“00” = intermediate/transmitted as “0”)
Control – – X X – X – X X X
– DP_I Feedback X – X – – X – X X X
– CF_D2 Transformer Tap Changer Control – – X X – X – X X X
– TxTap Feedback – – – – – – – – – –
Double Controls 1 Trip 1 Close 1 Common
– CF_D3 Single Point Indication ON/OFF Control – – X X – X – X X X
– SP Feedback X – X X X X – X X X
– CF_D3 Single Point Indication Open/Close Control – – X X – X – X X X
– SP Feedback X – X X X X – X X X
– CF_D3 Double Point Indication (Breaker indication “00”
= not valid/transmitted as “3”)
Control – – X X – X – X X X
– DP Feedback X – X – – X – X X X
– CF_D3 Double Point Indication (Breaker indication
“00” = intermediate/transmitted as “0”)
Control – – X X – X – X X X
– DP_I Feedback X – X – – X – X X X
– CF_D3 Transformer Tap Changer Control – – X X – X – X X X
– TxTap Feedback – – – – – – – – – –
Double Controls 2 Trip 2 Close
– CF_D4 Single Point Indication ON/OFF Control – – X X – X – X X X
– SP Feedback X – X X X X – X X X
– CF_D4 Single Point Indication Open/Close Control – – X X – X – X X X
– SP Feedback X – X X X X – X X X
– CF_D4 Double Point Indication (Breaker indication “00”
= not valid/transmitted as “3”)
Control – – X X – X – X X X
– DP Feedback X – X – – X – X X X
Appendix
A-22 7UM61 Manual
C53000-G1176-C127-1
– CF_D4 Double Point Indication (Breaker indication
“00” = intermediate/transmitted as “0”)
Control – – X X – X – X X X
– DP_I Feedback X – X – – X – X X X
– CF_D4 Transformer Tap Changer Control – – X X – X – X X X
– TxTap Feedback – – – – – – – – – –
Double Controls 1 Trip 2 Close
– CF_D12 Single Point Indication ON/OFF Control – – X X – X – X X X
– SP Feedback X – X X X X – X X X
– CF_D12 Single Point Indication Open/Close Control – – X X – X – X X X
– SP Feedback X – X X X X – X X X
– CF_D12 Double Point Indication (Breaker indication “00”
= not valid/transmitted as “3”)
Control – – X X – X – X X X
– DP Feedback X – X – – X – X X X
– CF_D12 Double Point Indication (Breaker indication
“00” = intermediate/transmitted as “0”)
Control – – X X – X – X X X
– DP_I Feedback X – X – – X – X X X
– CF_D12 Transformer Tap Changer Control – – X X – X – X X X
– TxTap Feedback – – – – – – – – – –
Double Controls 1 Trip 1 Close negated
– CF_D2N Single Point Indication ON/OFF Control – – X X – X – X X X
– SP Feedback X – X X X X – X X X
– CF_D2N Single Point Indication Open/Close Control – – X X – X – X X X
– SP Feedback X – X X X X – X X X
– CF_D2N Double Point Indication (Breaker indication “00”
= not valid/transmitted as “3”)
Control – – X X – X – X X X
– DP Feedback X – X – – X – X X X
– CF_D2N Double Point Indication (Breaker indication
“00” = intermediate/transmitted as “0”)
Control – – X X – X – X X X
– DP_I Feedback X – X – – X – X X X
– CF_D2N Transformer Tap Changer Control – – X X – X – X X X
– TxTap Feedback – – – – – – – – – –
• Measured Values:
– MV Measured Value – – – – – X X – – –
– MVU Measured Value, User Defined – – X – – – X – – –
– LV Limit Value – – – – – X X – – –
– LVU Limit Value, User Defined – – – – – X X – – –
• Metered Values:
– MVMV Metered Value of Measured Values – – – – – – – – – –
– PMV Pulse Metered Values X – – – – – – – – –
Type of Information Source Destination CFC Task level
Binary Inputs
Function Keys
CFC
Binary Outputs
LED
CFC
Measurement
PLC1
(slow)
PLC
(fast)
Interlocking
Appendix
7UM61 Manual A-23
C53000-G1176-C127-1
A.6 Default Settings
A.6.1 Binary Inputs
1) for busbar connection
2) 7UM612 only
A.6.2 Binary Outputs (output relays)
1) 7UM612 only
Binary input Abbreviation FNo Type of
information
Description
Binary input 1 !69_WULSSHG ____ SP O/O >Stop valve tripped
Binary input 2 !8H[F_IDLO_ ____ SP >Exc. voltage failure recognized
Binary input 3 !%/2&._I_
!%/2&._8_
!6_(_)_,HH_RII__
____
____
______
SP O/O
SP O/O__
SP
Generator circuit breaker open__
Binary input 4 !)$,/_)HHGHU_97
!8VHDO_LQ_%/.
!%/2&._8_9
____
____
____
SP O/O
SP O/O
SP
Voltage transformer protective switch tripped
Binary input 5 !([W_WULS__ ____ SP O/O External trip signal 1
Binary input 6 !([W_WULS__ ____ SP O/O External trip signal 2
Binary input 7 !7ULJ_:DYH_&DS_ ____ SP >Trigger Waveform Capture
Binary input 8....142) /LVW_(PSW\ ____ ---- No functions configured (reserve)
Binary output Abbreviation FNo Type Description
Output relay 1 (UURU_3ZU6XSSO\
)DLO_%DWWHU\
____
____
OUT O/O
OUT O/O
General indication: Internal monitoring
Output relay 2 5HOD\_75,3 ____ Relay trip
Output relay 3 /LVW_(PSW\ ____ ---- No functions configured (reserve)
Output relays 4..111) /LVW_(PSW\ ____ ---- No functions configured (reserve)
Output relay 12 ,!_75,3 ____ OUT O/O Trip by overcurrent time protection (stage I>)
Output relay 13 ,((!_75,3
8__!_75,3
6_(_)_75,3
____
____
____
OUT O/O
OUT O/O
OUT O/O
Trip by earth fault protection
Output relay 14 8__75,3
8!_75,3
8!!_75,3
____
____
____
OUT O/O
OUT O/O
OUT O/O
Trip by voltage protection
Output relay 15 I__75,3
I__75,3
____
____
OUT O/O
OUT O/O
Trip by frequency protection
Appendix
A-24 7UM61 Manual
C53000-G1176-C127-1
FigureA-14 Tripping matrix — pre–settings
Binary output Abbreviation FNo Type Description
Output relay 16 ([F___75,3
([F_8_75,3
____
____
OUT O/O
OUT O/O
Trip by underexcitation protection
Output relay 17 I__75,3
I__75,3
,!_75,3
8!!_75,3
3U_75,3
3U_69_75,3
6_(_)_75,3
,__Θ 75,3
([F___75,3
([F_8_75,3
____
____
____
____
____
____
____
____
____
____
OUT O/O
OUT O/O
OUT O/O
OUT O/O
OUT O/O
OUT O/O
OUT O/O
OUT O/O
OUT O/O
OUT O/O
Marshalled via the tripping matrix:
Generator circuit breaker
Output relay 18 I__75,3
,!_75,3
8!!_75,3
3U_69_75,3
6_(_)_75,3
,__Θ 75,3
([F___75,3
([F_8_75,3
____
____
____
____
____
____
____
____
OUT O/O
OUT O/O
OUT O/O
OUT O/O
OUT O/O
OUT O/O
OUT O/O
OUT O/O
Marshalled via the tripping matrix:
De–excitation Generator
Output relay 19 I__75,3
,!_75,3
6_(_)_75,3
,__Θ 75,3
____
____
____
____
OUT O/O
OUT O/O
OUT O/O
OUT O/O
Marshalled via the tripping matrix:
Stop valve
Generator circuit breaker
De–excitation
Stop valve
IEE>> TRIP
IEE> TRIP
BrkFailure TRIP
ThOverload TRIP
I>> TRIP
I> TRIP
O/C Ip TRIP
Imp.Z1< TRIP
Imp.Z1B< TRIP
Imp.Z2< TRIP
Imp.T3> TRIP
Ext 1 Gen.TRP
Ext 2 Gen.TRP
Ext 3 Gen.TRP
Ext 4 Gen.TRP
Pr TRIP
Pr+SV TRIP
Pf< TRIP
Pf> TRIP
FNo 1223
FNo 1900
FNo 3977
FNo 3978
FNo 3979
FNo 3980
FNo 4537
FNo 4557
FNo 4577
FNo 4597
FNo 5097
FNro 5098
FNo 5128
FNo 5129
FNo 1809
FNo 1521
FNo 1471
FNo 1226
FNo 1815 Generator circuit breaker
De–excitation
Stop valve
I2 Θ TRIP
S/E/F TRIP
f1 TRIP
f2 TRIP
f3 TRIP
f4 TRIP
Exc<3 TRIP
Exc<1 TRIP
Exc<2 TRIP
Exc<U< TRIP
U/f> TRIP
U/f>th. TRIP
I.En. TRIP
SEF 3H TRIP
U< TRIP
U<< TRIP
U> TRIP
I2>> TRIP
FNo 5239
FNo 5343
FNo 5344
FNo 5345
FNo 5346
FNo 5371
FNo 5372
FNo 5548
FNo 5568
FNo 6539
FNo 6540
FNo 6570
FNo 5160
FNo 5237
FNo 5236
FNo 5193
FNo 5161
FNo 5238
FNo 5187 U0 > TRIP
FNo 6573 U>> TRIP
Relay 17
Relay 18
Relay 19
Relay 17
Relay 18
Relay 19
Appendix
7UM61 Manual A-25
C53000-G1176-C127-1
A.6.3 LED Indicators
1) 7UM612 only
LED Abbreviation FNo Type of
information
Description
LED 1 5HOD\_75,3 ____ OUT O/O Protective relay has tripped
LED 2 5HOD\_3,&.83 ____ OUT O/O Protective relay has picked up
LED 3 ,!_)DXOW_/_ ____ OUT O/O Fault L1
LED 4 ,!_)DXOW_/_ ____ OUT O/O Fault L2
LED 5 ,!_)DXOW_/_ ____ OUT O/O Fault L3
LED 6 ,((!_75,3
8_!_75,3
6_(_)_75,3
____
____
____
OUT O/O
OUT O/O
OUT O/O
Earth fault
LED 7 (UURU_3ZU6XSSO\
)DLO_%DWWHU\
____
____
OUT O/O
OUT O/O
Hardware failure
LED 8...141) /LVW_(PSW\ ____ ---- No functions configured (reserve)
Appendix
A-26 7UM61 Manual
C53000-G1176-C127-1
A.6.4 Pre–defined CFC–charts
Some CFC Charts are already supplied with the SIPROTEC® device:
Device and System
Logic
The single-point indication “!'DWD6WRS“ that can be injected by binary inputs is converted
by means of a NEGATOR block into an indication “8QORFN'7“ that can be processed
internally (internal single point indication, IntSP), and assigned to an output.
This would not be possible directly, i.e. without the additional block.
:
Figure A-15 Logical Link between Input and Output
Set points Using modules on the running sequence “measured value processing”, a low current
monitor for the three phase currents is implemented. The output message is set high
as soon as one of the three phase currents falls below the set threshold:
FigureA-16 Undercurrent monitoring
_*HQHUDO_!'DWD6WRS_63 287_'HYLFH__8QORFN'7_,QW63
,1__'HYLFH_
IN: Set points IL< LV
IN: Measurement IL1 = MV
IN: Set points IL< LV
IN: Measurement IL2 = MV
IN: Set points IL< LV
IN: Measurement IL3 = MV
OUT: Set points SP. I< OUT
Appendix
7UM61 Manual A-27
C53000-G1176-C127-1
A.7 Interoperability List
1. Physical layer
1.1 Electrical interface
EIA RS-485 Number of loads for one equipment: 32
1.2 Optical interface
Glass fibre F-SMA type connector
Plastic fibre BFOC/2,5 type connector
1.3 Transmission speed
9600 bit/s 19200 bit/s
2. Link layer
There are no choices for the link layer
3. Application layer
3.1 Transmission mode for application data Mode 1 (least significant octet first) as defined in 4.10
of
IEC 60870-5-4
3.2 Common address of ASDU
One common address of ADSU More than one common address of ASDU
(identical with station address)
3.3 Selection of standard information numbers in monitor direction
3.3.1 System functions in monitor direction
0 End of general interrogation 0 Time synchronization
2 Reset FCB 3 Reset CU
4 Start/restart 5 Power on
3.3.2
3.3.3
3.3.4 see separate table in the device manual (Information List in the following section)
3.3.5
3.3.6
3.3.7 Measurands in monitor direction
144 Measurand I 145 Measurands I, V
146 Measurand I, V, P, Q 147 Measurands IN, VEN
148 Measurands IL1,2,3, VL1,2,3, P, Q, f
3.3.8 Generic functions in monitor direction
240 Read headings of all defined groups 241 Read values of all entries of one group
243 Read directory of a single entry 244 Read value of a single entry
245 End of general interrogation generic 249 Write entry with confirmation
data
250 Write entry with execution 251 Write entry aborted
3.4 Selection of standard information numbers in control direction
3.4.1 System functions in control direction
0 Initiation of general interrogation 0 Time synchronization
3.4.2 General commands in control direction
16 Auto-recloser on / off 17 Teleprotection on / off
18 Protection on / off 19 LED reset
23 Activate characteristic 1 24 Activate characteristic 2
25 Activate characteristic 3 26 Activate characteristic 4
XX
X
XX
XX
X
XX
XX
XX
X
XX
X
XX
Appendix
A-28 7UM61 Manual
C53000-G1176-C127-1
3.4.3 Generic functions in control direction
240 Read headings of all defined groups 241 Read values of all entries of one group
243 Read directory of a single entry 244 Read value of a single entry
245 General interrogation of generic data 248 Write entry
249 Write entry with confirmation 250 Write entry with execution
251 Write entry abort
3.5 Basic application functions
Test mode Blocking of monitor direction
Disturbance data Generic services
Private data
3.6 Miscellaneous
Measurand max. value = rated value x
1.2 2.4
Current L1
Current L2
Current L3
Voltage L1-E
Voltage L2-E
Voltage L3-E
Voltage L1-L2
Active power P
Reactive power Q
Frequency f
XX
X
X
Appendix
7UM61 Manual A-29
C53000-G1176-C127-1
A.8 Settings
NOTE: The following table lists all data which are available in the maximum complement of the
device. Dependent on the ordered model, only those data
may be present which are valid for the individual version.
Addr. Setting Title Function Setting Options Default Setting Comments
201 CT Starpoint Power System Data 1 CT starpoint towards machine
CT starpoint towards starpoint
CT starpoint towards machine CT Starpoint
202 Unom PRIMARY Power System Data 1 0.10..400.00 kV 6.30 kV Rated Primary Voltage
203 Unom SECONDARY Power System Data 1 100..125 V 100 V Rated Secondary Voltage (Ph-Ph)
204 CT PRIMARY Power System Data 1 10..50000 A 500 A CT Rated Primary Current
205 CT SECONDARY Power System Data 1 1A
5A
1A CT Rated Secondary Current
206 Uph / Udelta Power System Data 1 1.00..3.00 1.73 Matching Ratio Ph.-VT to Broken-
Delta-VT
207 CT ANGLE W0 Power System Data 1 -5.00..5.00 ° 0.00 ° Correction Angle CT W0
208 FACTOR IEE Power System Data 1 1.0..300.0 60.0 CT Ratio Prim./Sec. Iee
209 PHASE SEQ. Power System Data 1 L1 L2 L3
L1 L3 L2
L1 L2 L3 Phase Sequence
210 TMin TRIP CMD Power System Data 1 0.01..32.00 sec 0.15 sec Minimum TRIP Command Duration
211 UE CONNECTION Power System Data 1 UE connected to neutral transformer
UE connected to broken delta winding
not connected
UE connected to any VT
UE connected to neutral transformer
UE Connection
212 BkrClosed I MIN Power System Data 1 0.04..1.00 A 0.04 A Closed Breaker Min. Current
Threshold
213 SCHEME Power System Data 1 Direct connected to busbar
Unit transformer connected
Direct connected to busbar Scheme Configuration
214 Rated Frequency Power System Data 1 50 Hz
60 Hz
50 Hz Rated Frequency
217 STAR-POINT Power System Data 1 Starpoint earthing: high resistance
Starpoint earthing: low resistance
Starpoint earthing: high resistance Earthing of Machine Starpoint
Appendix
A-30 7UM61 Manual
C53000-G1176-C127-1
218 FACTOR UE Power System Data 1 1.0..2500.0 36.4 VT Ratio Prim./Sec. Ue
302 CHANGE Change Group Group A
Group B
Binary Input
Protocol
Group A Change to Another Setting Group
401 WAVEFORMTRIGGER
Oscillographic Fault
Records
Save with Pickup
Save with TRIP
Start with TRIP
Save with Pickup Waveform Capture
402 WAVEFORM DATA Oscillographic Fault
Records
Fault event
Power System fault
Fault event Scope of Waveform Data
403 MAX. LENGTH Oscillographic Fault
Records
0.30..5.00 sec 1.00 sec Max. length of a Waveform Capture
Record
404 PRE. TRIG. TIME Oscillographic Fault
Records
0.05..1.30 sec 0.10 sec Captured Waveform Prior to Trigger
405 POST REC. TIME Oscillographic Fault
Records
0.05..0.50 sec 0.10 sec Captured Waveform after Event
406 BinIn CAPT.TIME Oscillographic Fault
Records
0.10..5.00 sec 0.50 sec Capture Time via Binary Input
1101 U PRIMARY OP. Power System Data 2 0.10..400.00 kV 6.30 kV Primary Operating Voltage
1102 I PRIMARY OP. Power System Data 2 10..50000 A 483 A Primary Operating Current
1108 ACTIVE POWER Power System Data 2 Generator
Motor
Generator Measurement of Active Power for
1201 O/C I> O/C I> (with undervoltage
seal-in)
ON
OFF
Block relay for trip commands
OFF Overcurrent Time Protection I>
1202 I> O/C I> (with undervoltage
seal-in)
0.10..8.00 A 1.35 A I> Pickup
1203 T I> O/C I> (with undervoltage
seal-in)
0.00..60.00 sec 3.00 sec T I> Time Delay
1204 U< SEAL-IN O/C I> (with undervoltage
seal-in)
ON
OFF
OFF State of Undervoltage Seal-in
1205 U< O/C I> (with undervoltage
seal-in)
10.0..125.0 V 80.0 V Undervoltage Seal-in Pickup
Addr. Setting Title Function Setting Options Default Setting Comments
Appendix
7UM61 Manual A-31
C53000-G1176-C127-1
1206 T-SEAL-IN O/C I> (with undervoltage
seal-in)
0.10..60.00 sec 4.00 sec Duration of Undervoltage Seal-in
1207 I> DOUT RATIO O/C I> (with undervoltage
seal-in)
0.90..0.99 0.95 I> Drop Out Ratio
1301 O/C I>> O/C I>> (with direction)
ON
OFF
Block relay for trip commands
OFF Overcurrent Time Protection I>>
1302 I>> O/C I>> (with direction)
0.10..8.00 A 4.30 A I>> Pickup
1303 T I>> O/C I>> (with direction)
0.00..60.00 sec 0.10 sec T I>> Time Delay
1304 Phase Direction O/C I>> (with direction)
Forward
Reverse
Reverse Phase Direction
1305 LINE ANGLE O/C I>> (with direction)
-90..90 ° 60 ° Line Angle
1401 O/C Ip Inverse O/C Time
Protection
ON
OFF
Block relay for trip commands
OFF Inverse O/C Time Protection Ip
1402 Ip Inverse O/C Time
Protection
0.10..4.00 A 1.00 A Ip Pickup
1403 T Ip Inverse O/C Time
Protection
0.05..3.20 sec 0.50 sec T Ip Time Dial
1404 TIME DIAL: TD Inverse O/C Time
Protection
0.50..15.00 5.00 TIME DIAL: TD
1405 IEC CURVE Inverse O/C Time
Protection
Normal Inverse
Very Inverse
Extremely Inverse
Normal Inverse IEC Curve
1406 ANSI CURVE Inverse O/C Time
Protection
Very Inverse
Inverse
Moderately Inverse
Extremely Inverse
Definite Inverse
Very Inverse ANSI Curve
Addr. Setting Title Function Setting Options Default Setting Comments
Appendix
A-32 7UM61 Manual
C53000-G1176-C127-1
1407 VOLT. INFLUENCE Inverse O/C Time
Protection
without
Voltage controlled
Voltage restraint
without Voltage Influence
1408 U< Inverse O/C Time
Protection
10.0..125.0 V 75.0 V U< Threshold for Release Ip
1601 Ther. OVER LOAD Thermal Overload
Protection
OFF
ON
Block relay for trip commands
Alarm Only
OFF Thermal Overload Protection
1602 K-FACTOR Thermal Overload
Protection
0.50..2.50 1.11 K-Factor
1603 TIME CONSTANT Thermal Overload
Protection
30..32000 sec 600 sec Thermal Time Constant
1604 Θ ALARM Thermal Overload
Protection
70..100 % 90 % Thermal Alarm Stage
1605 TEMP. RISE I Thermal Overload
Protection
40..200 °C 100 °C Temperature rise at rated sec. curr.
1606 TEMP. RISE I Thermal Overload
Protection
104..392 °F 212 °F Temperature rise at rated sec. curr.
1607 TEMP. INPUT Thermal Overload
Protection
Disabled
4-20 mA
Profibus DP
Disabled Temperature input
1608 TEMP. SCAL. Thermal Overload
Protection
40..300 °C 100 °C Temperature for scaling
1609 TEMP. SCAL. Thermal Overload
Protection
104..572 °F 212 °F Temperature for scaling
1610 I ALARM Thermal Overload
Protection
0.10..4.00 A 1.00 A Current Overload Alarm Setpoint
1612 Kτ -FACTOR Thermal Overload
Protection
1.0..10.0 1.0 Kt-Factor when Motor stops
1615 I MAX THERM. Thermal Overload
Protection
0.50..8.00 A 3.30 A Maximum Current for Thermal
Replica
1616 T EMERGENCY Thermal Overload
Protection
10..15000 sec 100 sec Emergency Time
Addr. Setting Title Function Setting Options Default Setting Comments
Appendix
7UM61 Manual A-33
C53000-G1176-C127-1
1701 UNBALANCE LOAD Unbalance Load
(Negative Sequence)
OFF
ON
Block relay for trip commands
OFF Unbalance Load Protection
1702 I2> Unbalance Load
(Negative Sequence)
3.0..30.0 % 10.6 % Continously permissible current I2
1703 T WARN Unbalance Load
(Negative Sequence)
0.00..60.00 sec 20.00 sec Warning Stage Time Delay
1704 FACTOR K Unbalance Load
(Negative Sequence)
2.0..40.0 sec 18.7 sec Negativ sequence factor K
1705 T COOL DOWN Unbalance Load
(Negative Sequence)
0..50000 sec 1650 sec Time for cool down
1706 I2>> Unbalance Load
(Negative Sequence)
10..100 % 60 % I2>> Pickup
1707 T I2>> Unbalance Load
(Negative Sequence)
0.00..60.00 sec 3.00 sec T I2>> Time Delay
3001 UNDEREXCIT. Underexcitation Protection
ON
OFF
Block relay for trip commands
OFF Underexcitation Protection
3002 1/xd CHAR. 1 Underexcitation Protection
0.25..3.00 0.41 Conductance Intersect Characteristic
1
3003 ANGLE 1 Underexcitation Protection
50..120 ° 80 ° Inclination Angle of Characteristic
1
3004 T CHAR. 1 Underexcitation Protection
0.00..60.00 sec 10.00 sec Characteristic 1 Time Delay
3005 1/xd CHAR. 2 Underexcitation Protection
0.25..3.00 0.36 Conductance Intersect Characteristic
2
3006 ANGLE 2 Underexcitation Protection
50..120 ° 90 ° Inclination Angle of Characteristic
2
3007 T CHAR. 2 Underexcitation Protection
0.00..60.00 sec 10.00 sec Characteristic 2 Time Delay
3008 1/xd CHAR. 3 Underexcitation Protection
0.25..3.00 1.10 Conductance Intersect Characteristic
3
Addr. Setting Title Function Setting Options Default Setting Comments
Appendix
A-34 7UM61 Manual
C53000-G1176-C127-1
3009 ANGLE 3 Underexcitation Protection
50..120 ° 90 ° Inclination Angle of Characteristic
3
3010 T CHAR 3 Underexcitation Protection
0.00..60.00 sec 0.30 sec Characteristic 3 Time Delay
3011 T SHRT Uex< Underexcitation Protection
0.00..60.00 sec 0.50 sec T-Short Time Delay (char. &
Uexc<)
3014 Umin Underexcitation Protection
10.0..125.0 V 25.0 V Undervoltage blocking Pickup
3101 REVERSE POWER Reverse Power Protection
ON
OFF
Block relay for trip commands
OFF Reverse Power Protection
3102 P> REVERSE Reverse Power Protection
-30.00..-.50 % -1.93 % P> Reverse Pickup
3103 T-SV-OPEN Reverse Power Protection
0.00..60.00 sec 10.00 sec Time Delay Long (without Stop
Valve)
3104 T-SV-CLOSED Reverse Power Protection
0.00..60.00 sec 1.00 sec Time Delay Short (with Stop Valve)
3105 T-HOLD Reverse Power Protection
0.00..60.00 sec 0.00 sec Pickup Holding Time
3201 FORWARD POWER Forward Power
Supervision
ON
OFF
Block relay for trip commands
OFF Forward Power Supervision
3202 Pf< Forward Power
Supervision
0.5..120.0 % 9.7 % P-forw.< Supervision Pickup
3203 Pf> Forward Power
Supervision
1.0..120.0 % 96.6 % P-forw.> Supervision Pickup
3204 T-Pf< Forward Power
Supervision
0.00..60.00 sec 10.00 sec T-P-forw.< Time Delay
3205 T-Pf> Forward Power
Supervision
0.00..60.00 sec 10.00 sec T-P-forw.> Time Delay
3206 MEAS. METHOD Forward Power
Supervision
Method accurate
Method fast
Method accurate Method of Operation
Addr. Setting Title Function Setting Options Default Setting Comments
Appendix
7UM61 Manual A-35
C53000-G1176-C127-1
3301 IMPEDANCE PROT. Impedance Protection ON
OFF
Block relay for trip commands
OFF Impedance Protection
3302 IMP I> Impedance Protection 0.10..8.00 A 1.35 A Fault Detection I> Pickup
3303 U< SEAL-IN Impedance Protection ON
OFF
OFF State of Undervoltage Seal-in
3304 U< Impedance Protection 10.0..125.0 V 80.0 V Undervoltage Seal-in Pickup
3305 T-SEAL-IN Impedance Protection 0.10..60.00 sec 4.00 sec Duration of Undervoltage Seal-in
3306 ZONE Z1 Impedance Protection 0.05..130.00 Ohm 2.91 Ohm Impedance Zone Z1
3307 T-Z1 Impedance Protection 0.00..60.00 sec 0.10 sec Impedance Zone Z1 Time Delay
3308 ZONE Z1B Impedance Protection 0.05..65.00 Ohm 4.99 Ohm Impedance Zone Z1B
3309 T-Z1B Impedance Protection 0.00..60.00 sec 0.10 sec Impedance Zone Z1B Time Delay
3310 ZONE Z2 Impedance Protection 0.05..65.00 Ohm 4.16 Ohm Impedanz Zone Z2
3311 ZONE2 T2 Impedance Protection 0.00..60.00 sec 0.50 sec Impedance Zone Z2 Time Delay
3312 T END Impedance Protection 0.00..60.00 sec 3.00 sec T END: Final Time Delay
4001 UNDERVOLTAGE Undervoltage Protection
OFF
ON
Block relay for trip commands
OFF Undervoltage Protection
4002 U< Undervoltage Protection
10.0..125.0 V 75.0 V U< Pickup
4003 T U< Undervoltage Protection
0.00..60.00 sec 3.00 sec T U< Time Delay
4004 U<< Undervoltage Protection
10.0..125.0 V 65.0 V U<< Pickup
4005 T U<< Undervoltage Protection
0.00..60.00 sec 0.50 sec T U<< Time Delay
4006 U< DOUT RATIO Undervoltage Protection
1.01..1.20 1.05 U< Drop Out Ratio
4101 OVERVOLTAGE Overvoltage Protection
OFF
ON
Block relay for trip commands
OFF Overvoltage Protection
Addr. Setting Title Function Setting Options Default Setting Comments
Appendix
A-36 7UM61 Manual
C53000-G1176-C127-1
4102 U> Overvoltage Protection
30.0..170.0 V 115.0 V U> Pickup
4103 T U> Overvoltage Protection
0.00..60.00 sec 3.00 sec T U> Time Delay
4104 U>> Overvoltage Protection
30.0..170.0 V 130.0 V U>> Pickup
4105 T U>> Overvoltage Protection
0.00..60.00 sec 0.50 sec T U>> Time Delay
4106 U> DOUT RATIO Overvoltage Protection
0.90..0.99 0.95 U> Drop Out Ratio
4107 VALUES U> Overvoltage Protection
Voltage protection with U1 (pos.seq.)
Voltage protection with U-Phase-Phase
Voltage protection with U-Phase-earth
Voltage protection with U-Phase-
Phase
Measurement Values for U>
4201 O/U FREQUENCY Frequency Protection OFF
ON
Block relay for trip commands
OFF Over / Under Frequency Protection
4202 f1 PICKUP Frequency Protection 40.00..65.00 Hz 48.00 Hz f1 Pickup
4203 f1 PICKUP Frequency Protection 40.00..65.00 Hz 58.00 Hz f1 Pickup
4204 T f1 Frequency Protection 0.00..600.00 sec 1.00 sec T f1 Time Delay
4205 f2 PICKUP Frequency Protection 40.00..65.00 Hz 47.00 Hz f2 Pickup
4206 f2 PICKUP Frequency Protection 40.00..65.00 Hz 57.00 Hz f2 Pickup
4207 T f2 Frequency Protection 0.00..100.00 sec 6.00 sec T f2 Time Delay
4208 f3 PICKUP Frequency Protection 40.00..65.00 Hz 49.50 Hz f3 Pickup
4209 f3 PICKUP Frequency Protection 40.00..65.00 Hz 59.50 Hz f3 Pickup
4210 T f3 Frequency Protection 0.00..100.00 sec 20.00 sec T f3 Time Delay
4211 f4 PICKUP Frequency Protection 40.00..65.00 Hz 52.00 Hz f4 Pickup
4212 f4 PICKUP Frequency Protection 40.00..65.00 Hz 62.00 Hz f4 Pickup
4213 T f4 Frequency Protection 0.00..100.00 sec 10.00 sec T f4 Time Delay
4214 THRESHOLD f4 Frequency Protection Freq. prot. stage automatic
Freq. prot. stage overfreqency
Freq. prot. stage underfreqency
Freq. prot. stage automatic Handling of Threshold Stage f4
Addr. Setting Title Function Setting Options Default Setting Comments
Appendix
7UM61 Manual A-37
C53000-G1176-C127-1
4215 Umin Frequency Protection 10.0..125.0 V 65.0 V Minimum required voltage for operation
4301 OVEREXC. PROT. Overexcitation Protection
ON
OFF
Block relay for trip commands
OFF Overexcitation Protection
4302 U/f > Overflux Protection 1.00..1.20 1.10 U/f > Pickup
4303 T U/f > Overflux Protection 0.00..60.00 sec 10.00 sec T U/f > Time Delay
4304 U/f >> Overflux Protection 1.00..1.40 1.40 U/f >> Pickup
4305 T U/f >> Overflux Protection 0.00..60.00 sec 1.00 sec T U/f >> Time Delay
4306 t(U/f=1.10) Overflux Protection 0..20000 sec 6000 sec U/f = 1.10 Time Delay
4307 t(U/f=1.15) Overflux Protection 0..20000 sec 240 sec U/f = 1.15 Time Delay
4308 t(U/f=1.20) Overflux Protection 0..20000 sec 60 sec U/f = 1.20 Time Delay
4309 t(U/f=1.25) Overflux Protection 0..20000 sec 30 sec U/f = 1.25 Time Delay
4310 t(U/f=1.30) Overflux Protection 0..20000 sec 19 sec U/f = 1.30 Time Delay
4311 t(U/f=1.35) Overflux Protection 0..20000 sec 13 sec U/f = 1.35 Time Delay
4312 t(U/f=1.40) Overflux Protection 0..20000 sec 10 sec U/f = 1.40 Time Delay
4313 T COOL DOWN Overflux Protection 0..20000 sec 3600 sec Time for cool down
5001 S/E/F PROT. Stator Earth Fault
Protection
ON
OFF
Block relay for trip commands
OFF Stator Earth Fault Protection
5002 U0> Stator Earth Fault
Protection
5.0..125.0 V 10.0 V U0> Pickup
5003 3I0> Stator Earth Fault
Protection
2..1000 mA 5 mA 3I0> Pickup
5004 DIR. ANGLE Stator Earth Fault
Protection
0..360 ° 15 ° Angle for Direction Determination
5005 T S/E/F Stator Earth Fault
Protection
0.00..60.00 sec 0.30 sec T S/E/F Time Delay
5101 O/C PROT. Iee> Sensitiv Earth Current
Protection
OFF
ON
Block relay for trip commands
OFF Sensitive O/C Protection Iee>
Addr. Setting Title Function Setting Options Default Setting Comments
Appendix
A-38 7UM61 Manual
C53000-G1176-C127-1
5102 IEE> Sensitiv Earth Current
Protection
2..1000 mA 10 mA Iee> Pickup
5103 T IEE> Sensitiv Earth Current
Protection
0.00..60.00 sec 5.00 sec T Iee> Time delay
5104 IEE>> Sensitiv Earth Current
Protection
2..1000 mA 23 mA Iee>> Pickup
5105 T IEE>> Sensitiv Earth Current
Protection
0.00..60.00 sec 1.00 sec T Iee>> Time Delay
5106 IEE< Sensitiv Earth Current
Protection
1.5..50.0 mA 0.0 mA Iee< Pickup (Interrupted Circuit)
5201 SEF 3rd HARM. Stator Earth Fault
Protection 3rdHarm.
ON
OFF
Block relay for trip commands
OFF Stator Earth Fault Protection
3rdHarm.
5202 U0 3.HARM< Stator Earth Fault
Protection 3rdHarm.
0.2..40.0 V 1.0 V U0 3rd Harmonic< Pickup
5203 U0 3.HARM> Stator Earth Fault
Protection 3rdHarm.
0.2..40.0 V 2.0 V U0 3rd Harmonic> Pickup
5204 T SEF 3. HARM. Stator Earth Fault
Protection 3rdHarm.
0.00..60.00 sec 0.50 sec T SEF 3rd Harmonic Time Delay
5205 P min > Stator Earth Fault
Protection 3rdHarm.
10..100 % 40 % Release Threshold Pmin>
5206 U1 min > Stator Earth Fault
Protection 3rdHarm.
50.0..125.0 V 80.0 V Release Threshold U1min>
7001 BREAKER FAILURE Breaker Failure Protection
OFF
ON
Block relay for trip commands
OFF Breaker Failure Protection
7002 TRIP INTERN Breaker Failure Protection
OFF
Start Breaker Failure with Bin.Outp.3
Start Breaker Failure with CFC
OFF Start with Internal TRIP Command
7003 CIRC. BR. I> Breaker Failure Protection
0.04..1.00 A 0.20 A Supervision Current Pickup
7004 TRIP-Timer Breaker Failure Protection
0.06..60.00 sec 0.25 sec TRIP-Timer
Addr. Setting Title Function Setting Options Default Setting Comments
Appendix
7UM61 Manual A-39
C53000-G1176-C127-1
7101 INADVERT. EN. Inadvertent Energisation
OFF
ON
Block relay for trip commands
OFF Inadvertent Energisation
7102 I STAGE Inadvertent Energisation
0.1..20.0 A 0.3 A I Stage Pickup
7103 RELEASE U1< Inadvertent Energisation
10.0..125.0 V 50.0 V Release Threshold U1<
7104 PICK UP T U1< Inadvertent Energisation
0.00..60.00 sec 5.00 sec Pickup Time Delay T U1<
7105 DROP OUT T U1< Inadvertent Energisation
0.00..60.00 sec 1.00 sec Drop Out Time Delay T U1<
7110 FltDisp.LED/LCD Device Display Targets on every Pickup
Display Targets on TRIP only
Display Targets on every Pickup Fault Display on LED / LCD
8001 FUSE FAIL MON. Measurement Supervision
ON
OFF
OFF Fuse Failure Monitor
8101 MEASURE. SUPERV Measurement Supervision
OFF
ON
OFF Measurement Supervision
8102 BALANCE U-LIMIT Measurement Supervision
10..100 V 50 V Voltage Threshold for Balance
Monitoring
8103 BAL. FACTOR U Measurement Supervision
0.58..0.90 0.75 Balance Factor for Voltage Monitor
8104 BALANCE I LIMIT Measurement Supervision
0.10..1.00 A 0.50 A Current Balance Monitor
8105 BAL. FACTOR I Measurement Supervision
0.10..0.90 0.50 Balance Factor for Current Monitor
8106 Σ I THRESHOLD Measurement Supervision
0.05..2.00 A 0.10 A Summated Current Monitoring
Threshold
8107 Σ I FACTOR Measurement Supervision
0.00..0.95 0.10 Summated Current Monitoring
Factor
8108 SUM.thres. U Measurement Supervision
10..200 V 10 V Summation Thres. for Volt. Monitoring
8109 SUM.Fact. U Measurement Supervision
0.60..0.95 0.75 Factor for Volt. Sum. Monitoring
Addr. Setting Title Function Setting Options Default Setting Comments
Appendix
A-40 7UM61 Manual
C53000-G1176-C127-1
8201 TRIP Cir. SUP. Trip Circuit Supervision
ON
OFF
OFF TRIP Circuit Supervision
8601 EXTERN TRIP 1 External Trip Functions
ON
OFF
Block relay for trip commands
OFF External Trip Function 1
8602 T DELAY External Trip Functions
0.00..60.00 sec 1.00 sec Ext. Trip 1 Time Delay
8701 EXTERN TRIP 2 External Trip Functions
ON
OFF
Block relay for trip commands
OFF External Trip Function 2
8702 T DELAY External Trip Functions
0.00..60.00 sec 1.00 sec Ext. Trip 2 Time Delay
8801 EXTERN TRIP 3 External Trip Functions
ON
OFF
Block relay for trip commands
OFF External Trip Function 3
8802 T DELAY External Trip Functions
0.00..60.00 sec 1.00 sec Ext. Trip 3 Time Delay
8901 EXTERN TRIP 4 External Trip Functions
ON
OFF
Block relay for trip commands
OFF External Trip Function 4
8902 T DELAY External Trip Functions
0.00..60.00 sec 1.00 sec Ext. Trip 4 Time Delay
Addr. Setting Title Function Setting Options Default Setting Comments
Appendix
7UM61 Manual A-41
C53000-G1176-C127-1
A.9 List of Information
NOTE: The following table lists all data which are available in the maximum complement of the
device. Dependent on the ordered model, only those data
may be present which are valid for the individual version.
The symbol ’ > ’ indicates that the source of the indication is a binary input.
F.No. Description Function Type Log-Buffers Configurable in
Matrix
IEC 60870-5-103
Event Log On/Off
Trip (Fault) Log On/Off
Ground Fault Log On/
Off
Marked in Oscill.
Record
LED
Binary Input
Function Key
Binary Output
Event Log
Type
Information-No
Data Unit (ASDU)
General Interrogation
3 >Synchronize Internal Real Time Clock (>Time
Synch)
Device SP_Ev * * LED BI BO 135 48 1 GI
4 >Trigger Waveform Capture (>Trig.Wave.Cap.) Oscillographic Fault
Records
SP * * M LED BI BO 135 49 1 GI
5 >Reset LED (>Reset LED) Device SP * * LED BI BO 135 50 1 GI
7 >Setting Group Select Bit 0 (>Set Group Bit0) Change Group SP * * LED BI BO 135 51 1 GI
15 >Test mode (>Test mode) Device SP * * LED BI BO 135 53 1 GI
16 >Stop data transmission (>DataStop) Device SP * * LED BI BO 135 54 1 GI
51 Device is Operational and Protecting (Device
OK)
Device OUT ON OFF * LED BO 135 81 1 GI
52 At Least 1 Protection Funct. is Active (ProtActive)
Device IntSP ON OFF * LED BO 70 18 1 GI
55 Reset Device (Reset Device) Device OUT ON * LED BO
56 Initial Start of Device (Initial Start) Device OUT ON * LED BO 70 5 1
60 Reset LED (Reset LED) Device OUT_Ev ON * LED BO 70 19 1
Appendix
A-42 7UM61 Manual
C53000-G1176-C127-1
67 Resume (Resume) Device OUT ON * LED BO
68 Clock Synchronization Error (Clock SyncError) Device OUT ON OFF * LED BO
69 Daylight Saving Time (DayLightSavTime) Device OUT ON OFF * LED BO
70 Setting calculation is running (Settings Calc.) Device OUT ON OFF * LED BO 70 22 1 GI
71 Settings Check (Settings Check) Device OUT * * LED BO
72 Level-2 change (Level-2 change) Device OUT ON OFF * LED BO
110 Event lost (Event Lost) Device OUT_Ev ON * LED BO 135 130 1
113 Flag Lost (Flag Lost) Device OUT ON * M LED BO 135 136 1 GI
125 Chatter ON (Chatter ON) Device OUT ON OFF * LED BO 135 145 1 GI
140 Error with a summary alarm (Error Sum Alarm) Device OUT * * LED BO
147 Error Power Supply (Error PwrSupply) Device OUT ON OFF * LED BO
160 Alarm Summary Event (Alarm Sum Event) Device OUT * * LED BO 70 46 1 GI
161 Failure: General Current Supervision (Fail I
Superv.)
Measurement Supervision
OUT ON OFF * LED BO 70 32 1 GI
162 Failure: Current Summation (Failure Σ I) Measurement Supervision
OUT ON OFF * LED BO 135 182 1 GI
163 Failure: Current Balance (Fail I balance) Measurement Supervision
OUT ON OFF * LED BO 135 183 1 GI
164 Failure: general Voltage Supervision (Fail U
Superv.)
Measurement Supervision
OUT ON OFF * LED BO 70 33 1 GI
165 Failure: Voltage Summation Phase-Earth (Fail Σ
U Ph-E)
Measurement Supervision
OUT ON OFF * LED BO 135 184 1 GI
F.No. Description Function Type Log-Buffers Configurable in
Matrix
IEC 60870-5-103
Event Log On/Off
Trip (Fault) Log On/Off
Ground Fault Log On/
Off
Marked in Oscill.
Record
LED
Binary Input
Function Key
Binary Output
Event Log
Type
Information-No
Data Unit (ASDU)
General Interrogation
Appendix
7UM61 Manual A-43
C53000-G1176-C127-1
167 Failure: Voltage Balance (Fail U balance) Measurement Supervision
OUT ON OFF * LED BO 135 186 1 GI
171 Failure: Phase Sequence (Fail Ph. Seq.) Measurement Supervision
OUT ON OFF * LED BO 70 35 1 GI
175 Failure: Phase Sequence Current (Fail Ph. Seq.
I)
Measurement Supervision
OUT ON OFF * LED BO 135 191 1 GI
176 Failure: Phase Sequence Voltage (Fail Ph. Seq.
U)
Measurement Supervision
OUT ON OFF * LED BO 135 192 1 GI
177 Failure: Battery empty (Fail Battery) Device OUT ON OFF * LED BO
181 Error: A/D converter (Error A/D-conv.) Device OUT ON OFF * LED BO
191 Error: Offset (Error Offset) Device OUT ON OFF * LED BO
192 Error:1A/5Ajumper different from setting
(Error1A/5Awrong)
Device OUT ON OFF * LED BO
193 Alarm: NO calibration data available (Alarm NO
calibr)
Device OUT ON OFF * LED BO
194 Error: Neutral CT different from MLFB (Error
neutralCT)
Device OUT ON OFF * LED BO
197 Measurement Supervision is switched OFF
(MeasSup OFF)
Measurement Supervision
OUT ON OFF * LED BO 135 197 1 GI
203 Waveform data deleted (Wave. deleted) Oscillographic Fault
Records
OUT_Ev ON * LED BO 135 203 1
272 Set Point Operating Hours (SP. Op Hours>) Set Points (Statistic) OUT ON OFF * LED BO 135 229 1 GI
284 Set Point I< alarm (SP. I<) Set Points (Measured
Values)
OUT on off * LED BO 135 244 1 GI
F.No. Description Function Type Log-Buffers Configurable in
Matrix
IEC 60870-5-103
Event Log On/Off
Trip (Fault) Log On/Off
Ground Fault Log On/
Off
Marked in Oscill.
Record
LED
Binary Input
Function Key
Binary Output
Event Log
Type
Information-No
Data Unit (ASDU)
General Interrogation
Appendix
A-44 7UM61 Manual
C53000-G1176-C127-1
361 >Failure: Feeder VT (MCB tripped)
(>FAIL:Feeder VT)
Power System Data 1 SP ON OFF * LED BI BO 150 38 1 GI
394 >UE 3rd Harm. MIN/MAX Buffer Reset
(>MiMaUE3h res.)
Min/Max Measurement
Setup
SP ON * BI BO
396 >I1 MIN/MAX Buffer Reset (>I1 MiMaReset) Min/Max Measurement
Setup
SP ON * BI BO
399 >U1 MIN/MAX Buffer Reset (>U1 MiMa Reset) Min/Max Measurement
Setup
SP ON * BI BO
400 >P MIN/MAX Buffer Reset (>P MiMa Reset) Min/Max Measurement
Setup
SP ON * BI BO
402 >Q MIN/MAX Buffer Reset (>Q MiMa Reset) Min/Max Measurement
Setup
SP ON * BI BO
407 >Frq. MIN/MAX Buffer Reset (>Frq MiMa
Reset)
Min/Max Measurement
Setup
SP ON * BI BO
409 >BLOCK Op Counter (>BLOCK Op Count) Statistics SP ON OFF * LED BI BO
533 Primary fault current IL1 (IL1 =) Power System Data 2 OUT * ON OFF 150 177 4
534 Primary fault current IL2 (IL2 =) Power System Data 2 OUT * ON OFF 150 178 4
535 Primary fault current IL3 (IL3 =) Power System Data 2 OUT * ON OFF 150 179 4
601 I L1 (IL1 =) Measurement MV 134 147 9
602 I L2 (IL2 =) Measurement MV 134 147 9
603 I L3 (IL3 =) Measurement MV 134 147 9
605 I1 (positive sequence) (I1 =) Measurement MV 134 147 9
606 I2 (negative sequence) (I2 =) Measurement MV 134 147 9
F.No. Description Function Type Log-Buffers Configurable in
Matrix
IEC 60870-5-103
Event Log On/Off
Trip (Fault) Log On/Off
Ground Fault Log On/
Off
Marked in Oscill.
Record
LED
Binary Input
Function Key
Binary Output
Event Log
Type
Information-No
Data Unit (ASDU)
General Interrogation
Appendix
7UM61 Manual A-45
C53000-G1176-C127-1
621 U L1-E (UL1E=) Measurement MV 134 147 9
622 U L2-E (UL2E=) Measurement MV 134 147 9
623 U L3-E (UL3E=) Measurement MV 134 147 9
624 U L12 (UL12=) Measurement MV
625 U L23 (UL23=) Measurement MV
626 U L31 (UL31=) Measurement MV
627 Uen (Uen =) Measurement MV 134 147 9
629 U1 (positive sequence) (U1 =) Measurement MV 134 147 9
630 U2 (negative sequence) (U2 =) Measurement MV
639 UE 3rd Harmonic Voltage Minimum (UE3h
min=)
Min/Max Measurement
Setup
MVT
640 UE 3rd Harmonic Voltage Maximum (UE3h
max=)
Min/Max Measurement
Setup
MVT
641 P (active power) (P =) Measurement MV 134 147 9
642 Q (reactive power) (Q =) Measurement MV 134 147 9
644 Frequency (Freq=) Measurement MV 134 147 9
645 S (apparent power) (S =) Measurement MV
650 Uen 3rd harmonic (Uen3h =) Measurement MV
765 Overflux (U/Un) / (f/fn) (U/f =) Measurement MV 134 147 9
766 Calculated temperature (U/f) (U/f th=) Measurement MV
801 Temperat. rise for warning and trip (Θ /Θ trip =) Measurement MV
F.No. Description Function Type Log-Buffers Configurable in
Matrix
IEC 60870-5-103
Event Log On/Off
Trip (Fault) Log On/Off
Ground Fault Log On/
Off
Marked in Oscill.
Record
LED
Binary Input
Function Key
Binary Output
Event Log
Type
Information-No
Data Unit (ASDU)
General Interrogation
Appendix
A-46 7UM61 Manual
C53000-G1176-C127-1
802 Temperature rise for phase L1 (Θ /Θ tripL1=) Measurement MV
803 Temperature rise for phase L2 (Θ /Θ tripL2=) Measurement MV
804 Temperature rise for phase L3 (Θ /Θ tripL3=) Measurement MV
830 Senstive Earth Fault Current (IEE =) Measurement MV 134 147 9
831 3Io (zero sequence) (3I0 =) Measurement MV
832 3U0 (zero sequence) (3U0 =) Measurement MV
857 Positive Sequence Minimum (I1 Min=) Min/Max Measurement
Setup
MVT
858 Positive Sequence Maximum (I1 Max=) Min/Max Measurement
Setup
MVT
874 U1 (positive sequence) Voltage Minimum (U1
Min =)
Min/Max Measurement
Setup
MVT
875 U1 (positive sequence) Voltage Maximum (U1
Max =)
Min/Max Measurement
Setup
MVT
876 Active Power Minimum (PMin=) Min/Max Measurement
Setup
MVT
877 Active Power Maximum (PMax=) Min/Max Measurement
Setup
MVT
878 Reactive Power Minimum (QMin=) Min/Max Measurement
Setup
MVT
879 Reactive Power Maximum (QMax=) Min/Max Measurement
Setup
MVT
882 Frequency Minimum (fMin=) Min/Max Measurement
Setup
MVT
F.No. Description Function Type Log-Buffers Configurable in
Matrix
IEC 60870-5-103
Event Log On/Off
Trip (Fault) Log On/Off
Ground Fault Log On/
Off
Marked in Oscill.
Record
LED
Binary Input
Function Key
Binary Output
Event Log
Type
Information-No
Data Unit (ASDU)
General Interrogation
Appendix
7UM61 Manual A-47
C53000-G1176-C127-1
883 Frequency Maximum (fMax=) Min/Max Measurement
Setup
MVT
901 Power Factor (PF =) Measurement MV 134 147 9
902 Power angle (PHI=) Measurement MV
903 Resistance (R=) Measurement MV
904 Reactance (X=) Measurement MV
910 Calculated rotor temp. (unbal. load) (Therm-
Rep.=)
Measurement MV
911 Cooling medium temperature (AMB.TEMP=) Measurement MV
1020 Counter of operating hours (Op.Hours=) Statistics OUT
1021 Accumulation of interrupted current L1 (Σ L1 =) Statistics OUT
1022 Accumulation of interrupted current L2 (Σ L2 =) Statistics OUT
1023 Accumulation of interrupted current L3 (Σ L3 =) Statistics OUT
1202 >BLOCK IEE>> (>BLOCK IEE>>) Sensitiv Earth Current
Protection
SP ON OFF * LED BI BO 151 102 1 GI
1203 >BLOCK IEE> (>BLOCK IEE>) Sensitiv Earth Current
Protection
SP ON OFF * LED BI BO 151 103 1 GI
1221 IEE>> Pickup (IEE>> Pickup) Sensitiv Earth Current
Protection
OUT * ON OFF LED BO 151 121 2 GI
1223 IEE>> TRIP (IEE>> TRIP) Sensitiv Earth Current
Protection
OUT * ON M LED BO 151 123 2 GI
1224 IEE> Pickup (IEE> Pickup) Sensitiv Earth Current
Protection
OUT * ON OFF LED BO 151 124 2 GI
F.No. Description Function Type Log-Buffers Configurable in
Matrix
IEC 60870-5-103
Event Log On/Off
Trip (Fault) Log On/Off
Ground Fault Log On/
Off
Marked in Oscill.
Record
LED
Binary Input
Function Key
Binary Output
Event Log
Type
Information-No
Data Unit (ASDU)
General Interrogation
Appendix
A-48 7UM61 Manual
C53000-G1176-C127-1
1226 IEE> TRIP (IEE> TRIP) Sensitiv Earth Current
Protection
OUT * ON M LED BO 151 126 2 GI
1231 >BLOCK sensitiv earth current prot. (>BLOCK
Sens. E)
Sensitiv Earth Current
Protection
SP * * LED BI BO
1232 Earth current prot. is swiched OFF (IEE OFF) Sensitiv Earth Current
Protection
OUT ON OFF * LED BO 151 132 1 GI
1233 Earth current prot. is BLOCKED (IEE
BLOCKED)
Sensitiv Earth Current
Protection
OUT ON OFF ON OFF LED BO 151 133 1 GI
1234 Earth current prot. is ACTIVE (IEE ACTIVE) Sensitiv Earth Current
Protection
OUT ON OFF * LED BO 151 134 1 GI
1403 >BLOCK breaker failure (>BLOCK BkrFail) Breaker Failure Protection
SP * * LED BI BO
1422 >Breaker contacts (>Break. Contact) Breaker Failure Protection
SP ON OFF * LED BI BO 166 120 1 GI
1423 >ext. start 1 breaker failure prot. (>ext.start1 B/
F)
Breaker Failure Protection
SP ON OFF * LED BI BO 166 121 1 GI
1441 >ext. start 2 breaker failure prot. (>ext.start2 B/
F)
Breaker Failure Protection
SP ON OFF * LED BI BO 166 122 1 GI
1442 >int. start breaker failure prot. (>int. start B/F) Breaker Failure Protection
SP ON OFF * LED BI BO 166 123 1 GI
1443 Breaker fail. started intern (int. start B/F) Breaker Failure Protection
OUT ON OFF * LED BO 166 190 1 GI
1444 Breaker failure I> (B/F I>) Breaker Failure Protection
OUT ON OFF * LED BO 166 191 1 GI
F.No. Description Function Type Log-Buffers Configurable in
Matrix
IEC 60870-5-103
Event Log On/Off
Trip (Fault) Log On/Off
Ground Fault Log On/
Off
Marked in Oscill.
Record
LED
Binary Input
Function Key
Binary Output
Event Log
Type
Information-No
Data Unit (ASDU)
General Interrogation
Appendix
7UM61 Manual A-49
C53000-G1176-C127-1
1451 Breaker failure is switched OFF (BkrFail OFF) Breaker Failure Protection
OUT ON OFF * LED BO 166 151 1 GI
1452 Breaker failure is BLOCKED (BkrFail BLOCK) Breaker Failure Protection
OUT ON OFF ON OFF LED BO 166 152 1 GI
1453 Breaker failure is ACTIVE (BkrFail ACTIVE) Breaker Failure Protection
OUT ON OFF * LED BO 166 153 1 GI
1455 Breaker failure protection: picked up (B/F picked
up)
Breaker Failure Protection
OUT * ON OFF LED BO 166 155 2 GI
1471 Breaker failure TRIP (BrkFailure TRIP) Breaker Failure Protection
OUT * ON M LED BO 166 171 2 GI
1503 >BLOCK thermal overload protection (>BLK
ThOverload)
Thermal Overload
Protection
SP * * LED BI BO
1506 >Reset memory for thermal replica (>RM
th.repl.Θ )
Thermal Overload
Protection
SP ON OFF * LED BI BO
1507 >Emergency start of motors (>EmergencyStart) Thermal Overload
Protection
SP ON OFF * LED BI BO 167 7 1 GI
1508 >Failure temperature input (>Fail.Temp.inp) Thermal Overload
Protection
SP ON OFF * LED BI BO 167 8 1 GI
1511 Thermal Overload Protection OFF (Th.Overload
OFF)
Thermal Overload
Protection
OUT ON OFF * LED BO 167 11 1 GI
1512 Thermal Overload Protection BLOKKED
(Th.Overload BLK)
Thermal Overload
Protection
OUT ON OFF ON OFF LED BO 167 12 1 GI
1513 Overload Protection ACTIVE (Overload ACT) Thermal Overload
Protection
OUT ON OFF * LED BO 167 13 1 GI
F.No. Description Function Type Log-Buffers Configurable in
Matrix
IEC 60870-5-103
Event Log On/Off
Trip (Fault) Log On/Off
Ground Fault Log On/
Off
Marked in Oscill.
Record
LED
Binary Input
Function Key
Binary Output
Event Log
Type
Information-No
Data Unit (ASDU)
General Interrogation
Appendix
A-50 7UM61 Manual
C53000-G1176-C127-1
1514 Failure temperature input (Fail.Temp.inp) Thermal Overload
Protection
OUT ON OFF * LED BO 167 14 1 GI
1515 Overload Current Alarm (I alarm) (O/L I Alarm) Thermal Overload
Protection
OUT ON OFF * LED BO 167 15 1 GI
1516 Thermal Overload Alarm (O/L Θ Alarm) Thermal Overload
Protection
OUT ON OFF * LED BO 167 16 1 GI
1517 Thermal Overload picked up (O/L Th. Pickup) Thermal Overload
Protection
OUT ON OFF * LED BO 167 17 2 GI
1519 Reset memory for thermal replica (RM
th.repl.Θ )
Thermal Overload
Protection
OUT ON OFF * LED BO 167 19 1 GI
1521 Thermal Overload TRIP (ThOverload TRIP) Thermal Overload
Protection
OUT * ON M LED BO 167 21 2 GI
1720 >BLOCK direction I>> stage (>BLOCK dir.) O/C I>> (with direction)
SP ON OFF * LED BI BO 60 18 1 GI
1721 >BLOCK I>> (>BLOCK I>>) O/C I>> (with direction)
SP * * LED BI BO
1722 >BLOCK I> (>BLOCK I>) O/C I> (with undervoltage
seal-in)
SP * * LED BI BO
1801 O/C fault detection stage I>> phase L1 (I>>
Fault L1)
O/C I>> (with direction)
OUT * ON OFF LED BO 60 46 2 GI
1802 O/C fault detection stage I>> phase L2 (I>>
Fault L2)
O/C I>> (with direction)
OUT * ON OFF LED BO 60 47 2 GI
1803 O/C fault detection stage I>> phase L3 (I>>
Fault L3)
O/C I>> (with direction)
OUT * ON OFF LED BO 60 48 2 GI
F.No. Description Function Type Log-Buffers Configurable in
Matrix
IEC 60870-5-103
Event Log On/Off
Trip (Fault) Log On/Off
Ground Fault Log On/
Off
Marked in Oscill.
Record
LED
Binary Input
Function Key
Binary Output
Event Log
Type
Information-No
Data Unit (ASDU)
General Interrogation
Appendix
7UM61 Manual A-51
C53000-G1176-C127-1
1806 O/C I>> direction forward (I>> forward) O/C I>> (with direction)
OUT * ON OFF LED BO 60 208 2 GI
1807 O/C I>> direction backward (I>> backward) O/C I>> (with direction)
OUT * ON OFF LED BO 60 209 2 GI
1808 O/C prot. I>> picked up (I>> picked up) O/C I>> (with direction)
OUT * ON OFF LED BO 60 210 2 GI
1809 O/C I>> TRIP (I>> TRIP) O/C I>> (with direction)
OUT * ON M LED BO 60 211 2 GI
1811 O/C fault detection stage I> phase L1 (I> Fault
L1)
O/C I> (with undervoltage
seal-in)
OUT * ON OFF LED BO 60 50 2 GI
1812 O/C fault detection stage I> phase L2 (I> Fault
L2)
O/C I> (with undervoltage
seal-in)
OUT * ON OFF LED BO 60 51 2 GI
1813 O/C fault detection stage I> phase L3 (I> Fault
L3)
O/C I> (with undervoltage
seal-in)
OUT * ON OFF LED BO 60 52 2 GI
1815 O/C I> TRIP (I> TRIP) O/C I> (with undervoltage
seal-in)
OUT * ON M LED BO 60 71 2 GI
1883 >BLOCK inverse O/C time protection (>BLOCK
O/C Ip)
Inverse O/C Time Protection
SP * * LED BI BO
1891 O/C protection Ip is switched OFF (O/C Ip OFF) Inverse O/C Time Protection
OUT ON OFF * LED BO 60 180 1 GI
1892 O/C protection Ip is BLOCKED (O/C Ip
BLOCKED)
Inverse O/C Time Protection
OUT ON OFF ON OFF LED BO 60 181 1 GI
1893 O/C protection Ip is ACTIVE (O/C Ip ACTIVE) Inverse O/C Time Protection
OUT ON OFF * LED BO 60 182 1 GI
F.No. Description Function Type Log-Buffers Configurable in
Matrix
IEC 60870-5-103
Event Log On/Off
Trip (Fault) Log On/Off
Ground Fault Log On/
Off
Marked in Oscill.
Record
LED
Binary Input
Function Key
Binary Output
Event Log
Type
Information-No
Data Unit (ASDU)
General Interrogation
Appendix
A-52 7UM61 Manual
C53000-G1176-C127-1
1896 O/C fault detection Ip phase L1 (O/C Ip Fault
L1)
Inverse O/C Time Protection
OUT * ON OFF LED BO 60 184 2 GI
1897 O/C fault detection Ip phase L2 (O/C Ip Fault
L2)
Inverse O/C Time Protection
OUT * ON OFF LED BO 60 185 2 GI
1898 O/C fault detection Ip phase L3 (O/C Ip Fault
L3)
Inverse O/C Time Protection
OUT * ON OFF LED BO 60 186 2 GI
1899 O/C Ip picked up (O/C Ip pick. up) Inverse O/C Time Protection
OUT * ON OFF LED BO 60 183 2 GI
1900 O/C Ip TRIP (O/C Ip TRIP) Inverse O/C Time Protection
OUT * ON M LED BO 60 187 2 GI
1950 >O/C prot. : BLOCK undervoltage seal-in
(>Useal-in BLK)
O/C I> (with undervoltage
seal-in)
SP ON OFF * LED BI BO 60 200 1 GI
1955 O/C prot. stage I>> is switched OFF (I>> OFF) O/C I>> (with direction)
OUT ON OFF * LED BO 60 205 1 GI
1956 O/C prot. stage I>> is BLOCKED (I>>
BLOCKED)
O/C I>> (with direction)
OUT ON OFF ON OFF LED BO 60 206 1 GI
1957 O/C prot. stage I>> is ACTIVE (I>> ACTIVE) O/C I>> (with direction)
OUT ON OFF * LED BO 60 207 1 GI
1965 O/C prot. stage I> is switched OFF (I> OFF) O/C I> (with undervoltage
seal-in)
OUT ON OFF * LED BO 60 215 1 GI
1966 O/C prot. stage I> is BLOCKED (I> BLOCKED) O/C I> (with undervoltage
seal-in)
OUT ON OFF ON OFF LED BO 60 216 1 GI
1967 O/C prot. stage I> is ACTIVE (I> ACTIVE) O/C I> (with undervoltage
seal-in)
OUT ON OFF * LED BO 60 217 1 GI
F.No. Description Function Type Log-Buffers Configurable in
Matrix
IEC 60870-5-103
Event Log On/Off
Trip (Fault) Log On/Off
Ground Fault Log On/
Off
Marked in Oscill.
Record
LED
Binary Input
Function Key
Binary Output
Event Log
Type
Information-No
Data Unit (ASDU)
General Interrogation
Appendix
7UM61 Manual A-53
C53000-G1176-C127-1
1970 O/C prot. undervoltage seal-in (U< seal in) O/C I> (with undervoltage
seal-in)
OUT * ON OFF LED BO 60 220 2 GI
3953 >BLOCK impedance protection (>Imp. BLOCK) Impedance Protection SP * * LED BI BO
3956 >Zone 1B extension for impedance prot.
(>Extens. Z1B)
Impedance Protection SP ON OFF * LED BI BO 28 222 1 GI
3958 >Imp. prot. : BLOCK undervoltage seal-in
(>Useal-in BLK)
Impedance Protection SP ON OFF * LED BI BO 28 30 1 GI
3961 Impedance protection is switched OFF (Imp.
OFF)
Impedance Protection OUT ON OFF * LED BO 28 226 1 GI
3962 Impedance protection is BLOCKED (Imp.
BLOCKED)
Impedance Protection OUT ON OFF ON OFF LED BO 28 227 1 GI
3963 Impedance protection is ACTIVE (Imp. ACTIVE) Impedance Protection OUT ON OFF * LED BO 28
228 1 GI
3966 Impedance protection picked up (Imp. picked
up)
Impedance Protection OUT * ON OFF LED BO 28 229 2 GI
3967 Imp.: Fault detection , phase L1 (Imp. Fault L1) Impedance Protection OUT * ON OFF LED BO 28 230
2 GI
3968 Imp.: Fault detection , phase L2 (Imp. Fault L2) Impedance Protection OUT * ON OFF LED BO 28 231
2 GI
3969 Imp.: Fault detection , phase L3 (Imp. Fault L3) Impedance Protection OUT * ON OFF LED BO 28 232
2 GI
3970 Imp.: O/C with undervoltage seal in (Imp. I> &
U<)
Impedance Protection OUT * ON OFF LED BO 28 233 2 GI
3977 Imp.: Z1< TRIP (Imp.Z1< TRIP) Impedance Protection OUT * ON M LED BO 28 240 2 GI
3978 Imp.: Z1B< TRIP (Imp.Z1B< TRIP) Impedance Protection OUT * ON M LED BO 28 241 2 GI
3979 Imp.: Z2< TRIP (Imp. Z2< TRIP) Impedance Protection OUT * ON M LED BO 28 242 2 GI
3980 Imp.: T3> TRIP (Imp.T3> TRIP) Impedance Protection OUT * ON M LED BO 28 243 2 GI
F.No. Description Function Type Log-Buffers Configurable in
Matrix
IEC 60870-5-103
Event Log On/Off
Trip (Fault) Log On/Off
Ground Fault Log On/
Off
Marked in Oscill.
Record
LED
Binary Input
Function Key
Binary Output
Event Log
Type
Information-No
Data Unit (ASDU)
General Interrogation
Appendix
A-54 7UM61 Manual
C53000-G1176-C127-1
4523 >Block external trip 1 (>BLOCK Ext 1) External Trip Functions
SP * * LED BI BO
4526 >Trigger external trip 1 (>Ext trip 1) External Trip Functions
SP ON OFF * LED BI BO 51 126 1 GI
4531 External trip 1 is switched OFF (Ext 1 OFF) External Trip Functions
OUT ON OFF * LED BO 51 131 1 GI
4532 External trip 1 is BLOCKED (Ext 1 BLOCKED) External Trip Functions
OUT ON OFF ON OFF LED BO 51 132 1 GI
4533 External trip 1 is ACTIVE (Ext 1 ACTIVE) External Trip Functions
OUT ON OFF * LED BO 51 133 1 GI
4536 External trip 1: General picked up (Ext 1 pick.
up)
External Trip Functions
OUT * ON OFF LED BO 51 136 2 GI
4537 External trip 1: General TRIP (Ext 1 Gen.TRP) External Trip Functions
OUT * ON LED BO 51 137 2 GI
4543 >BLOCK external trip 2 (>BLOCK Ext 2) External Trip Functions
SP * * LED BI BO
4546 >Trigger external trip 2 (>Ext trip 2) External Trip Functions
SP ON OFF * LED BI BO 51 146 1 GI
4551 External trip 2 is switched OFF (Ext 2 OFF) External Trip Functions
OUT ON OFF * LED BO 51 151 1 GI
4552 External trip 2 is BLOCKED (Ext 2 BLOCKED) External Trip Functions
OUT ON OFF ON OFF LED BO 51 152 1 GI
4553 External trip 2 is ACTIVE (Ext 2 ACTIVE) External Trip Functions
OUT ON OFF * LED BO 51 153 1 GI
F.No. Description Function Type Log-Buffers Configurable in
Matrix
IEC 60870-5-103
Event Log On/Off
Trip (Fault) Log On/Off
Ground Fault Log On/
Off
Marked in Oscill.
Record
LED
Binary Input
Function Key
Binary Output
Event Log
Type
Information-No
Data Unit (ASDU)
General Interrogation
Appendix
7UM61 Manual A-55
C53000-G1176-C127-1
4556 External trip 2: General picked up (Ext 2 pick.
up)
External Trip Functions
OUT * ON OFF LED BO 51 156 2 GI
4557 External trip 2: General TRIP (Ext 2 Gen.TRP) External Trip Functions
OUT * ON LED BO 51 157 2 GI
4563 >BLOCK external trip 3 (>BLOCK Ext 3) External Trip Functions
SP * * LED BI BO
4566 >Trigger external trip 3 (>Ext trip 3) External Trip Functions
SP ON OFF * LED BI BO 51 166 1 GI
4571 External trip 3 is switched OFF (Ext 3 OFF) External Trip Functions
OUT ON OFF * LED BO 51 171 1 GI
4572 External trip 3 is BLOCKED (Ext 3 BLOCKED) External Trip Functions
OUT ON OFF ON OFF LED BO 51 172 1 GI
4573 External trip 3 is ACTIVE (Ext 3 ACTIVE) External Trip Functions
OUT ON OFF * LED BO 51 173 1 GI
4576 External trip 3: General picked up (Ext 3 pick.
up)
External Trip Functions
OUT * ON OFF LED BO 51 176 2 GI
4577 External trip 3: General TRIP (Ext 3 Gen.TRP) External Trip Functions
OUT * ON LED BO 51 177 2 GI
4583 >BLOCK external trip 4 (>BLOCK Ext 4) External Trip Functions
SP * * LED BI BO
4586 >Trigger external trip 4 (>Ext trip 4) External Trip Functions
SP ON OFF * LED BI BO 51 186 1 GI
4591 External trip 4 is switched OFF (Ext 4 OFF) External Trip Functions
OUT ON OFF * LED BO 51 191 1 GI
F.No. Description Function Type Log-Buffers Configurable in
Matrix
IEC 60870-5-103
Event Log On/Off
Trip (Fault) Log On/Off
Ground Fault Log On/
Off
Marked in Oscill.
Record
LED
Binary Input
Function Key
Binary Output
Event Log
Type
Information-No
Data Unit (ASDU)
General Interrogation
Appendix
A-56 7UM61 Manual
C53000-G1176-C127-1
4592 External trip 4 is BLOCKED (Ext 4 BLOCKED) External Trip Functions
OUT ON OFF ON OFF LED BO 51 192 1 GI
4593 External trip 4 is ACTIVE (Ext 4 ACTIVE) External Trip Functions
OUT ON OFF * LED BO 51 193 1 GI
4596 External trip 4: General picked up (Ext 4 pick.
up)
External Trip Functions
OUT * ON OFF LED BO 51 196 2 GI
4597 External trip 4: General TRIP (Ext 4 Gen.TRP) External Trip Functions
OUT * ON LED BO 51 197 2 GI
5002 Suitable measured quantities present (Operat.
Cond.)
Power System Data 1 OUT ON OFF * LED BO 71 2 1 GI
5010 >BLOCK fuse failure monitor (>FFM BLOCK) Measurement Supervision
SP ON OFF ON OFF LED BI BO 71 7 1 GI
5011 >FFM extern undervoltage (>FFM U< extern) Measurement Supervision
SP ON OFF * LED BI BO 71 8 1 GI
5012 Voltage UL1E at trip (UL1E=) Power System Data 2 OUT * ON OFF 71 38 4
5013 Voltage UL2E at trip (UL2E=) Power System Data 2 OUT * ON OFF 71 39 4
5014 Voltage UL3E at trip (UL3E=) Power System Data 2 OUT * ON OFF 71 40 4
5015 Active power at trip (P=) Power System Data 2 OUT * ON OFF 71 41 4
5016 Reactive power at trip (Q=) Power System Data 2 OUT * ON OFF 71 42 4
5017 Frequency at trip (f=) Power System Data 2 OUT * ON OFF 71 43 4
5083 >BLOCK reverse power protection (>Pr
BLOCK)
Reverse Power Protection
SP * * LED BI BO
5086 >Stop valve tripped (>SV tripped) Reverse Power Protection
SP ON OFF * LED BI BO 70 77 1 GI
F.No. Description Function Type Log-Buffers Configurable in
Matrix
IEC 60870-5-103
Event Log On/Off
Trip (Fault) Log On/Off
Ground Fault Log On/
Off
Marked in Oscill.
Record
LED
Binary Input
Function Key
Binary Output
Event Log
Type
Information-No
Data Unit (ASDU)
General Interrogation
Appendix
7UM61 Manual A-57
C53000-G1176-C127-1
5091 Reverse power prot. is switched OFF (Pr OFF) Reverse Power Protection
OUT ON OFF * LED BO 70 81 1 GI
5092 Reverse power protection is BLOKKED (Pr
BLOCKED)
Reverse Power Protection
OUT ON OFF ON OFF LED BO 70 82 1 GI
5093 Reverse power protection is ACTIVE (Pr
ACTIVE)
Reverse Power Protection
OUT ON OFF * LED BO 70 83 1 GI
5096 Reverse power: picked up (Pr picked up) Reverse Power Protection
OUT * ON OFF LED BO 70 84 2 GI
5097 Reverse power: TRIP (Pr TRIP) Reverse Power Protection
OUT * ON M LED BO 70 85 2 GI
5098 Reverse power: TRIP with stop valve (Pr+SV
TRIP)
Reverse Power Protection
OUT * ON M LED BO 70 86 2 GI
5113 >BLOCK forward power supervision (>Pf
BLOCK)
Forward Power Supervision
SP * * LED BI BO
5116 >BLOCK forw. power superv. Pf< stage (>Pf<
BLOCK)
Forward Power Supervision
SP ON OFF * LED BI BO 70 102 1 GI
5117 >BLOCK forw. power superv. Pf> stage (>Pf>
BLOCK)
Forward Power Supervision
SP ON OFF * LED BI BO 70 103 1 GI
5121 Forward power supervis. is switched OFF (Pf
OFF)
Forward Power Supervision
OUT ON OFF * LED BO 70 106 1 GI
5122 Forward power supervision is BLOKKED (Pf
BLOCKED)
Forward Power Supervision
OUT ON OFF ON OFF LED BO 70 107 1 GI
5123 Forward power supervision is ACTIVE (Pf
ACTIVE)
Forward Power Supervision
OUT ON OFF * LED BO 70 108 1 GI
F.No. Description Function Type Log-Buffers Configurable in
Matrix
IEC 60870-5-103
Event Log On/Off
Trip (Fault) Log On/Off
Ground Fault Log On/
Off
Marked in Oscill.
Record
LED
Binary Input
Function Key
Binary Output
Event Log
Type
Information-No
Data Unit (ASDU)
General Interrogation
Appendix
A-58 7UM61 Manual
C53000-G1176-C127-1
5126 Forward power: Pf< stage picked up (Pf< picked
up)
Forward Power Supervision
OUT * ON OFF LED BO 70 109 2 GI
5127 Forward power: Pf> stage picked up (Pf> picked
up)
Forward Power Supervision
OUT * ON OFF LED BO 70 110 2 GI
5128 Forward power: Pf< stage TRIP (Pf< TRIP) Forward Power Supervision
OUT * ON M LED BO 70 111 2 GI
5129 Forward power: Pf> stage TRIP (Pf> TRIP) Forward Power Supervision
OUT * ON M LED BO 70 112 2 GI
5143 >BLOCK I2 (Unbalance Load) (>BLOCK I2) Unbalance Load (Negative
Sequence)
SP * * LED BI BO
5145 >Reverse Phase Rotation (>Reverse Rot.) Power System Data 1 SP ON OFF * LED BI BO 71 34 1 GI
5146 >Reset memory for thermal replica I2 (>RM
th.repl.)
Unbalance Load (Negative
Sequence)
SP ON OFF * LED BI BO
5147 Phase Rotation L1L2L3 (Rotation L1L2L3) Power System Data 1 OUT ON OFF * LED BO 70 128 1 GI
5148 Phase Rotation L1L3L2 (Rotation L1L3L2) Power System Data 1 OUT ON OFF * LED BO 70 129 1 GI
5151 I2 switched OFF (I2 OFF) Unbalance Load (Negative
Sequence)
OUT ON OFF * LED BO 70 131 1 GI
5152 I2 is BLOCKED (I2 BLOCKED) Unbalance Load (Negative
Sequence)
OUT ON OFF ON OFF LED BO 70 132 1 GI
5153 I2 is ACTIVE (I2 ACTIVE) Unbalance Load (Negative
Sequence)
OUT ON OFF * LED BO 70 133 1 GI
5156 Unbalanced load: Current warning stage (I2>
Warn)
Unbalance Load (Negative
Sequence)
OUT ON OFF * LED BO 70 134 1 GI
F.No. Description Function Type Log-Buffers Configurable in
Matrix
IEC 60870-5-103
Event Log On/Off
Trip (Fault) Log On/Off
Ground Fault Log On/
Off
Marked in Oscill.
Record
LED
Binary Input
Function Key
Binary Output
Event Log
Type
Information-No
Data Unit (ASDU)
General Interrogation
Appendix
7UM61 Manual A-59
C53000-G1176-C127-1
5158 Reset memory of thermal replica I2 (RM th.
repl.)
Unbalance Load (Negative
Sequence)
OUT ON OFF * LED BO 70 137 1 GI
5159 I2>> picked up (I2>> picked up) Unbalance Load (Negative
Sequence)
OUT * ON OFF LED BO 70 138 2 GI
5160 Unbalanced load: TRIP of current stage (I2>>
TRIP)
Unbalance Load (Negative
Sequence)
OUT * ON M LED BO 70 139 2 GI
5161 Unbalanced load: TRIP of thermal stage (I2 Θ
TRIP)
Unbalance Load (Negative
Sequence)
OUT * ON M LED BO 70 140 2 GI
5165 I2> picked up (I2> picked up) Unbalance Load (Negative
Sequence)
OUT * ON OFF LED BO 70 150 2 GI
5173 >BLOCK stator earth fault protection (>S/E/F
BLOCK)
Stator Earth Fault Protection
SP * * LED BI BO
5176 >Switch off earth current detec.(S/E/F) (>S/E/F
Iee off)
Stator Earth Fault Protection
SP ON OFF * LED BI BO 70 152 1 GI
5181 Stator earth fault prot. is switch OFF (S/E/F
OFF)
Stator Earth Fault Protection
OUT ON OFF * LED BO 70 156 1 GI
5182 Stator earth fault protection is BLOCK. (S/E/F
BLOCKED)
Stator Earth Fault Protection
OUT ON OFF ON OFF LED BO 70 157 1 GI
5183 Stator earth fault protection is ACTIVE (S/E/F
ACTIVE)
Stator Earth Fault Protection
OUT ON OFF * LED BO 70 158 1 GI
5186 Stator earth fault: U0 picked up (U0> picked up) Stator Earth Fault Protection
OUT * ON OFF LED BO 70 159 2 GI
5187 Stator earth fault: U0 stage TRIP (U0> TRIP) Stator Earth Fault Protection
OUT * ON M LED BO 70 160 2 GI
F.No. Description Function Type Log-Buffers Configurable in
Matrix
IEC 60870-5-103
Event Log On/Off
Trip (Fault) Log On/Off
Ground Fault Log On/
Off
Marked in Oscill.
Record
LED
Binary Input
Function Key
Binary Output
Event Log
Type
Information-No
Data Unit (ASDU)
General Interrogation
Appendix
A-60 7UM61 Manual
C53000-G1176-C127-1
5188 Stator earth fault: I0 picked up (3I0> picked up) Stator Earth Fault Protection
OUT * ON OFF LED BO 70 168 2 GI
5189 Earth fault in phase L1 (Uearth L1) Stator Earth Fault Protection
OUT * ON OFF LED BO 70 169 2 GI
5190 Earth fault in phase L2 (Uearth L2) Stator Earth Fault Protection
OUT * ON OFF LED BO 70 170 2 GI
5191 Earth fault in phase L3 (Uearth L3) Stator Earth Fault Protection
OUT * ON OFF LED BO 70 171 2 GI
5193 Stator earth fault protection TRIP (S/E/F TRIP) Stator Earth Fault Protection
OUT * ON M LED BO 70 173 2 GI
5203 >BLOCK frequency protection (>BLOCK Freq.) Frequency Protection SP * * LED BI BO
5206 >BLOCK stage f1 (>BLOCK f1) Frequency Protection SP ON OFF * LED BI BO 70 177 1 GI
5207 >BLOCK stage f2 (>BLOCK f2) Frequency Protection SP ON OFF * LED BI BO 70 178 1 GI
5208 >BLOCK stage f3 (>BLOCK f3) Frequency Protection SP ON OFF * LED BI BO 70 179 1 GI
5209 >BLOCK stage f4 (>BLOCK f4) Frequency Protection SP ON OFF * LED BI BO 70 180 1 GI
5211 Frequency protection is OFF (Freq. OFF) Frequency Protection OUT ON OFF * LED BO 70 181 1 GI
5212 Frequency protection is BLOCKED (Freq.
BLOCKED)
Frequency Protection OUT ON OFF ON OFF LED BO 70 182 1 GI
5213 Frequency protection is ACTIVE (Freq.
ACTIVE)
Frequency Protection OUT ON OFF * LED BO 70 183 1 GI
5214 Frequency protection undervoltage Blk (Freq
UnderV Blk)
Frequency Protection OUT ON OFF ON OFF LED BO 70 184 1 GI
5232 f1 picked up (f1 picked up) Frequency Protection OUT * ON OFF LED BO 70 230 2 GI
F.No. Description Function Type Log-Buffers Configurable in
Matrix
IEC 60870-5-103
Event Log On/Off
Trip (Fault) Log On/Off
Ground Fault Log On/
Off
Marked in Oscill.
Record
LED
Binary Input
Function Key
Binary Output
Event Log
Type
Information-No
Data Unit (ASDU)
General Interrogation
Appendix
7UM61 Manual A-61
C53000-G1176-C127-1
5233 f2 picked up (f2 picked up) Frequency Protection OUT * ON OFF LED BO 70 231 2 GI
5234 f3 picked up (f3 picked up) Frequency Protection OUT * ON OFF LED BO 70 232 2 GI
5235 f4 picked up (f4 picked up) Frequency Protection OUT * ON OFF LED BO 70 233 2 GI
5236 f1 TRIP (f1 TRIP) Frequency Protection OUT * ON M LED BO 70 234 2 GI
5237 f2 TRIP (f2 TRIP) Frequency Protection OUT * ON M LED BO 70 235 2 GI
5238 f3 TRIP (f3 TRIP) Frequency Protection OUT * ON M LED BO 70 236 2 GI
5239 f4 TRIP (f4 TRIP) Frequency Protection OUT * ON M LED BO 70 237 2 GI
5323 >BLOCK underexcitation protection (>Exc.
BLOCK)
Underexcitation Protection
SP * * LED BI BO
5327 >BLOCK underexc. prot. char. 3 (>Char. 3
BLK.)
Underexcitation Protection
SP ON OFF * LED BI BO 71 53 1 GI
5328 >Exc. voltage failure recognized (>Uexc fail.) Underexcitation Protection
SP ON OFF * LED BI BO 71 54 1 GI
5329 >BLOCK underexc. prot. char. 1 (>Char. 1
BLK.)
Underexcitation Protection
SP ON OFF * LED BI BO 71 64 1 GI
5330 >BLOCK underexc. prot. char. 2 (>Char. 2
BLK.)
Underexcitation Protection
SP ON OFF * LED BI BO 71 65 1 GI
5331 Underexc. prot. is switched OFF (Excit. OFF) Underexcitation Protection
OUT ON OFF * LED BO 71 55 1 GI
5332 Underexc. prot. is BLOCKED (Excit.BLOCKED) Underexcitation Protection
OUT ON OFF ON OFF LED BO 71 56 1 GI
5333 Underexc. prot. is ACTIVE (Excit.ACTIVE) Underexcitation Protection
OUT ON OFF * LED BO 71 57 1 GI
F.No. Description Function Type Log-Buffers Configurable in
Matrix
IEC 60870-5-103
Event Log On/Off
Trip (Fault) Log On/Off
Ground Fault Log On/
Off
Marked in Oscill.
Record
LED
Binary Input
Function Key
Binary Output
Event Log
Type
Information-No
Data Unit (ASDU)
General Interrogation
Appendix
A-62 7UM61 Manual
C53000-G1176-C127-1
5334 Underexc. prot. blocked by U< (Exc. U< blk) Underexcitation Protection
OUT ON OFF ON OFF LED BO 71 58 1 GI
5336 Exc. voltage failure recognized (Uexc failure) Underexcitation Protection
OUT * ON OFF LED BO 71 59 1 GI
5337 Underexc. prot. picked up (Exc< pikked up) Underexcitation Protection
OUT * ON OFF LED BO 71 60 2 GI
5343 Underexc. prot. char. 3 TRIP (Exc<3 TRIP) Underexcitation Protection
OUT * ON M LED BO 71 63 2 GI
5344 Underexc. prot. char. 1 TRIP (Exc<1 TRIP) Underexcitation Protection
OUT * ON M LED BO 71 66 2 GI
5345 Underexc. prot. char. 2 TRIP (Exc<2 TRIP) Underexcitation Protection
OUT * ON M LED BO 71 67 2 GI
5346 Underexc. prot. char.+Uexc< TRIP
(Exc<U<TRIP)
Underexcitation Protection
OUT * ON M LED BO 71 68 2 GI
5353 >BLOCK overexcitation protection (>U/f
BLOCK)
Overflux Protection SP * * LED BI BO
5357 >Reset memory of thermal replica U/f (>RM
th.repl.)
Overflux Protection SP ON OFF * LED BI BO
5361 Overexcitation prot. is swiched OFF (U/f> OFF) Overflux Protection OUT ON OFF * LED BO 71 83 1
GI
5362 Overexcitation prot. is BLOCKED (U/f>
BLOCKED)
Overflux Protection OUT ON OFF ON OFF LED BO 71 84 1 GI
5363 Overexcitation prot. is ACTIVE (U/f> ACTIVE) Overflux Protection OUT ON OFF * LED BO 71 85 1 GI
5367 Overexc. prot.: U/f warning stage (U/f> warn) Overflux Protection OUT ON OFF * LED BO 71 86 1 GI
F.No. Description Function Type Log-Buffers Configurable in
Matrix
IEC 60870-5-103
Event Log On/Off
Trip (Fault) Log On/Off
Ground Fault Log On/
Off
Marked in Oscill.
Record
LED
Binary Input
Function Key
Binary Output
Event Log
Type
Information-No
Data Unit (ASDU)
General Interrogation
Appendix
7UM61 Manual A-63
C53000-G1176-C127-1
5369 Reset memory of thermal replica U/f (RM th.
repl.)
Overflux Protection OUT ON OFF * LED BO 71 88 1 GI
5370 Overexc. prot.: U/f> picked up (U/f> picked up) Overflux Protection OUT * ON OFF LED BO 71 89 2 GI
5371 Overexc. prot.: TRIP of U/f>> stage (U/f>>
TRIP)
Overflux Protection OUT * ON M LED BO 71 90 2 GI
5372 Overexc. prot.: TRIP of th. stage (U/f> th.TRIP) Overflux Protection OUT * ON M LED BO 71 91 2 GI
5373 Overexc. prot.: U/f>> picked up (U/f>> pick.up) Overflux Protection OUT * ON OFF LED BO 71 92 2 GI
5396 Failure R/E/F protection Iee< (Fail. REF Iee<) Sensitiv Earth Current
Protection
OUT ON OFF * LED BO 71 126 1 GI
5533 >BLOCK inadvertent energ. prot. (>BLOCK
I.En.)
Inadvertent Energisation
SP * * LED BI BO
5541 Inadvert. Energ. prot. is swiched OFF (I.En.
OFF)
Inadvertent Energisation
OUT ON OFF * LED BO 72 31 1 GI
5542 Inadvert. Energ. prot. is BLOCKED (I.En.
BLOCKED)
Inadvertent Energisation
OUT ON OFF ON OFF LED BO 72 32 1 GI
5543 Inadvert. Energ. prot. is ACTIVE (I.En. ACTIVE) Inadvertent Energisation
OUT ON OFF * LED BO 72 33 1 GI
5546 Release of the current stage (I.En. release) Inadvertent Energisation
OUT ON OFF * LED BO 72 34 1 GI
5547 Inadvert. Energ. prot.: picked up (I.En. picked
up)
Inadvertent Energisation
OUT * ON OFF LED BO 72 35 2 GI
5548 Inadvert. Energ. prot.: TRIP (I.En. TRIP) Inadvertent Energisation
OUT * ON M LED BO 72 36 2 GI
F.No. Description Function Type Log-Buffers Configurable in
Matrix
IEC 60870-5-103
Event Log On/Off
Trip (Fault) Log On/Off
Ground Fault Log On/
Off
Marked in Oscill.
Record
LED
Binary Input
Function Key
Binary Output
Event Log
Type
Information-No
Data Unit (ASDU)
General Interrogation
Appendix
A-64 7UM61 Manual
C53000-G1176-C127-1
5553 >BLOCK SEF with 3.Harmonic (>SEF 3H
BLOCK)
Stator Earth Fault Protection
3rdHarm.
SP * * LED BI BO
5561 SEF with 3.Harm. is switched OFF (SEF 3H
OFF)
Stator Earth Fault Protection
3rdHarm.
OUT ON OFF * LED BO 72 51 1 GI
5562 SEF with 3.Harm. is BLOCKED (SEF 3H
BLOCK)
Stator Earth Fault Protection
3rdHarm.
OUT ON OFF ON OFF LED BO 72 52 1 GI
5563 SEF with 3.Harm. is ACTIVE (SEF 3H ACTIVE) Stator Earth Fault Protection
3rdHarm.
OUT ON OFF * LED BO 72 53 1 GI
5567 SEF with 3.Harm.: picked up (SEF 3H pick.up) Stator Earth Fault Protection
3rdHarm.
OUT * ON OFF LED BO 72 54 2 GI
5568 SEF with 3.Harm.: TRIP (SEF 3H TRIP) Stator Earth Fault Protection
3rdHarm.
OUT * ON M LED BO 72 55 2 GI
6503 >BLOCK undervoltage protection (>BLOCK U/
V)
Undervoltage Protection
SP * * LED BI BO
6506 >BLOCK undervoltage protection U< (>BLOCK
U<)
Undervoltage Protection
SP ON OFF * LED BI BO 74 6 1 GI
6508 >BLOCK undervoltage protection U<<
(>BLOCK U<<)
Undervoltage Protection
SP ON OFF * LED BI BO 74 8 1 GI
6513 >BLOCK overvoltage protection (>BLOCK O/V) Overvoltage Protection
SP * * LED BI BO
6516 >BLOCK overvoltage protection U> (>BLOCK
U>)
Overvoltage Protection
SP ON OFF * LED BI BO 74 20 1 GI
6517 >BLOCK overvoltage protection U>> (>BLOCK
U>>)
Overvoltage Protection
SP ON OFF * LED BI BO 74 21 1 GI
F.No. Description Function Type Log-Buffers Configurable in
Matrix
IEC 60870-5-103
Event Log On/Off
Trip (Fault) Log On/Off
Ground Fault Log On/
Off
Marked in Oscill.
Record
LED
Binary Input
Function Key
Binary Output
Event Log
Type
Information-No
Data Unit (ASDU)
General Interrogation
Appendix
7UM61 Manual A-65
C53000-G1176-C127-1
6530 Undervoltage protection switched OFF (Undervolt.
OFF)
Undervoltage Protection
OUT ON OFF * LED BO 74 30 1 GI
6531 Undervoltage protection is BLOCKED (Undervolt.
BLK)
Undervoltage Protection
OUT ON OFF ON OFF LED BO 74 31 1 GI
6532 Undervoltage protection is ACTIVE (Undervolt.
ACT)
Undervoltage Protection
OUT ON OFF * LED BO 74 32 1 GI
6533 Undervoltage U< picked up (U< pikked up) Undervoltage Protection
OUT * ON OFF LED BO 74 33 2 GI
6537 Undervoltage U<< picked up (U<< picked up) Undervoltage Protection
OUT * ON OFF LED BO 74 37 2 GI
6539 Undervoltage U< TRIP (U< TRIP) Undervoltage Protection
OUT * ON M LED BO 74 39 2 GI
6540 Undervoltage U<< TRIP (U<< TRIP) Undervoltage Protection
OUT * ON M LED BO 74 40 2 GI
6565 Overvoltage protection switched OFF (Overvolt.
OFF)
Overvoltage Protection
OUT ON OFF * LED BO 74 65 1 GI
6566 Overvoltage protection is BLOCKED (Overvolt.
BLK)
Overvoltage Protection
OUT ON OFF ON OFF LED BO 74 66 1 GI
6567 Overvoltage protection is ACTIVE (Overvolt.
ACT)
Overvoltage Protection
OUT ON OFF * LED BO 74 67 1 GI
6568 Overvoltage U> picked up (U> picked up) Overvoltage Protection
OUT * ON OFF LED BO 74 68 2 GI
6570 Overvoltage U> TRIP (U> TRIP) Overvoltage Protection
OUT * ON M LED BO 74 70 2 GI
F.No. Description Function Type Log-Buffers Configurable in
Matrix
IEC 60870-5-103
Event Log On/Off
Trip (Fault) Log On/Off
Ground Fault Log On/
Off
Marked in Oscill.
Record
LED
Binary Input
Function Key
Binary Output
Event Log
Type
Information-No
Data Unit (ASDU)
General Interrogation
Appendix
A-66 7UM61 Manual
C53000-G1176-C127-1
6571 Overvoltage U>> picked up (U>> pikked up) Overvoltage Protection
OUT * ON OFF LED BO 74 71 2 GI
6573 Overvoltage U>> TRIP (U>> TRIP) Overvoltage Protection
OUT * ON M LED BO 74 73 2 GI
6575 Voltage Transformer Fuse Failure (VT Fuse
Failure)
Measurement Supervision
OUT ON OFF * LED BO 74 74 1 GI
6851 >BLOCK Trip circuit supervision (>BLOCK
TripC)
Trip Circuit Supervision
SP * * LED BI BO
6852 >Trip circuit supervision: trip relay (>TripC trip
rel)
Trip Circuit Supervision
SP ON OFF * LED BI BO 170 51 1 GI
6853 >Trip circuit supervision: breaker relay (>TripC
brk rel.)
Trip Circuit Supervision
SP ON OFF * LED BI BO 170 52 1 GI
6861 Trip circuit supervision OFF (TripC OFF) Trip Circuit Supervision
OUT ON OFF * LED BO 170 53 1 GI
6862 Trip circuit supervision is BLOCKED (TripC
BLOCKED)
Trip Circuit Supervision
OUT ON OFF ON OFF LED BO 153 16 1 GI
6863 Trip circuit supervision is ACTIVE (TripC
ACTIVE)
Trip Circuit Supervision
OUT ON OFF * LED BO 153 17 1 GI
6864 Trip Circuit blk. Bin. input is not set (TripC Prog-
Fail)
Trip Circuit Supervision
OUT ON OFF * LED BO 170 54 1 GI
6865 Failure Trip Circuit (FAIL: Trip cir.) Trip Circuit Supervision
OUT ON OFF * LED BO 170 55 1 GI
>Back Light on (>Light on) Device SP ON OFF * LED BI BO
Clock Synchronization (SynchClock) Device IntSP_Ev * *
F.No. Description Function Type Log-Buffers Configurable in
Matrix
IEC 60870-5-103
Event Log On/Off
Trip (Fault) Log On/Off
Ground Fault Log On/
Off
Marked in Oscill.
Record
LED
Binary Input
Function Key
Binary Output
Event Log
Type
Information-No
Data Unit (ASDU)
General Interrogation
Appendix
7UM61 Manual A-67
C53000-G1176-C127-1
Control Authority (Cntrl Auth) Control Authorization IntSP ON OFF * LED 101 85 1 GI
Controlmode LOCAL (ModeLOCAL) Control Authorization IntSP ON OFF * LED 101 86 1 GI
Controlmode REMOTE (ModeREMOTE) Control Authorization IntSP ON OFF * LED
Error Systeminterface (SysIntErr.) Protocol IntSP ON OFF * LED BO
Fault Recording Start (FltRecSta) Oscillographic Fault
Records
IntSP ON OFF * LED BO
Group A (Group A) Change Group IntSP ON OFF * LED BO 70 23 1 GI
Group B (Group B) Change Group IntSP ON OFF * LED BO 70 24 1 GI
Hardware Test Mode (HWTestMod) Device IntSP ON OFF * LED BO
IL< under current (IL<) Set Points (Measured
Values)
LV
Interlock.: User Double Command 1-CLOSE
(UsrDC1-CL)
Protocol IntSP
Interlock.: User Double Command 2-CLOSE
(UsrDC2-CL)
Protocol IntSP
Interlock.: User Double Command 3-CLOSE
(UsrDC3-CL)
Protocol IntSP
Interlock.: User Double Command 4-CLOSE
(UsrDC4-CL)
Protocol IntSP
Interlocking: User Double Command 1-OPEN
(UsrDC1-OP)
Protocol IntSP
Interlocking: User Double Command 2-OPEN
(UsrDC2-OP)
Protocol IntSP
F.No. Description Function Type Log-Buffers Configurable in
Matrix
IEC 60870-5-103
Event Log On/Off
Trip (Fault) Log On/Off
Ground Fault Log On/
Off
Marked in Oscill.
Record
LED
Binary Input
Function Key
Binary Output
Event Log
Type
Information-No
Data Unit (ASDU)
General Interrogation
Appendix
A-68 7UM61 Manual
C53000-G1176-C127-1
Interlocking: User Double Command 3-OPEN
(UsrDC3-OP)
Protocol IntSP
Interlocking: User Double Command 4-OPEN
(UsrDC4-OP)
Protocol IntSP
Stop data transmission (DataStop) Device IntSP ON OFF * LED BO 70 20 1 GI
Test mode (Test mode) Device IntSP ON OFF * LED BO 70 21 1 GI
Unlock data transmission via BI (UnlockDT) Device IntSP
User CFC-SinglePointIndication(input) 1
(UsCfcSpI1)
Protocol IntSP * * LED BI BO C
B
User CFC-SinglePointIndication(input) 10
(UsCfcSpI10)
Protocol IntSP * * LED BI BO C
B
User CFC-SinglePointIndication(input) 11
(UsCfcSpI11)
Protocol IntSP * * LED BI BO C
B
User CFC-SinglePointIndication(input) 12
(UsCfcSpI12)
Protocol IntSP * * LED BI BO C
B
User CFC-SinglePointIndication(input) 13
(UsCfcSpI13)
Protocol IntSP * * LED BI BO C
B
User CFC-SinglePointIndication(input) 14
(UsCfcSpI14)
Protocol IntSP * * LED BI BO C
B
User CFC-SinglePointIndication(input) 15
(UsCfcSpI15)
Protocol IntSP * * LED BI BO C
B
User CFC-SinglePointIndication(input) 16
(UsCfcSpI16)
Protocol IntSP * * LED BI BO C
B
F.No. Description Function Type Log-Buffers Configurable in
Matrix
IEC 60870-5-103
Event Log On/Off
Trip (Fault) Log On/Off
Ground Fault Log On/
Off
Marked in Oscill.
Record
LED
Binary Input
Function Key
Binary Output
Event Log
Type
Information-No
Data Unit (ASDU)
General Interrogation
Appendix
7UM61 Manual A-69
C53000-G1176-C127-1
User CFC-SinglePointIndication(input) 2
(UsCfcSpI2)
Protocol IntSP * * LED BI BO C
B
User CFC-SinglePointIndication(input) 3
(UsCfcSpI3)
Protocol IntSP * * LED BI BO C
B
User CFC-SinglePointIndication(input) 4
(UsCfcSpI4)
Protocol IntSP * * LED BI BO C
B
User CFC-SinglePointIndication(input) 5
(UsCfcSpI5)
Protocol IntSP * * LED BI BO C
B
User CFC-SinglePointIndication(input) 6
(UsCfcSpI6)
Protocol IntSP * * LED BI BO C
B
User CFC-SinglePointIndication(input) 7
(UsCfcSpI7)
Protocol IntSP * * LED BI BO C
B
User CFC-SinglePointIndication(input) 8
(UsCfcSpI8)
Protocol IntSP * * LED BI BO C
B
User CFC-SinglePointIndication(input) 9
(UsCfcSpI9)
Protocol IntSP * * LED BI BO C
B
User CFC-SinglePointIndication(output)1
(UsCfcSpO1)
Protocol SP * * LED BI BO C
B
User CFC-SinglePointIndication(output)10
(UsCfcSpO10)
Protocol SP * * LED BI BO C
B
User CFC-SinglePointIndication(output)11
(UsCfcSpO11)
Protocol SP * * LED BI BO C
B
User CFC-SinglePointIndication(output)12
(UsCfcSpO12)
Protocol SP * * LED BI BO C
B
F.No. Description Function Type Log-Buffers Configurable in
Matrix
IEC 60870-5-103
Event Log On/Off
Trip (Fault) Log On/Off
Ground Fault Log On/
Off
Marked in Oscill.
Record
LED
Binary Input
Function Key
Binary Output
Event Log
Type
Information-No
Data Unit (ASDU)
General Interrogation
Appendix
A-70 7UM61 Manual
C53000-G1176-C127-1
User CFC-SinglePointIndication(output)13
(UsCfcSpO13)
Protocol SP * * LED BI BO C
B
User CFC-SinglePointIndication(output)14
(UsCfcSpO14)
Protocol SP * * LED BI BO C
B
User CFC-SinglePointIndication(output)15
(UsCfcSpO15)
Protocol SP * * LED BI BO C
B
User CFC-SinglePointIndication(output)16
(UsCfcSpO16)
Protocol SP * * LED BI BO C
B
User CFC-SinglePointIndication(output)2
(UsCfcSpO2)
Protocol SP * * LED BI BO C
B
User CFC-SinglePointIndication(output)3
(UsCfcSpO3)
Protocol SP * * LED BI BO C
B
User CFC-SinglePointIndication(output)4
(UsCfcSpO4)
Protocol SP * * LED BI BO C
B
User CFC-SinglePointIndication(output)5
(UsCfcSpO5)
Protocol SP * * LED BI BO C
B
User CFC-SinglePointIndication(output)6
(UsCfcSpO6)
Protocol SP * * LED BI BO C
B
User CFC-SinglePointIndication(output)7
(UsCfcSpO7)
Protocol SP * * LED BI BO C
B
User CFC-SinglePointIndication(output)8
(UsCfcSpO8)
Protocol SP * * LED BI BO C
B
User CFC-SinglePointIndication(output)9
(UsCfcSpO9)
Protocol SP * * LED BI BO C
B
User Double Command 1 (UsrDC1) Protocol CF_D4 ON OFF * BO
F.No. Description Function Type Log-Buffers Configurable in
Matrix
IEC 60870-5-103
Event Log On/Off
Trip (Fault) Log On/Off
Ground Fault Log On/
Off
Marked in Oscill.
Record
LED
Binary Input
Function Key
Binary Output
Event Log
Type
Information-No
Data Unit (ASDU)
General Interrogation
Appendix
7UM61 Manual A-71
C53000-G1176-C127-1
User Double Command 1 (UsrDC1) Protocol DP ON OFF * BI C
B
User Double Command 2 (UsrDC2) Protocol CF_D2 ON OFF * BO
User Double Command 2 (UsrDC2) Protocol DP ON OFF * BI C
B
User Double Command 3 (UsrDC3) Protocol CF_D2 ON OFF * BO
User Double Command 3 (UsrDC3) Protocol DP ON OFF * BI C
B
User Double Command 4 (UsrDC4) Protocol CF_D2 ON OFF * BO
User Double Command 4 (UsrDC4) Protocol DP ON OFF * BI C
B
User Single Command 1 (UsrSC1) Protocol CF_S ON OFF * BO
User Single Command 1 (UsrSC1) Protocol SP ON OFF * BI C
B
User Single Command 10 (UsrSC10) Protocol C_S ON OFF * BO
User Single Command 11 (UsrSC11) Protocol C_S ON OFF * BO
User Single Command 12 (UsrSC12) Protocol C_S ON OFF * BO
User Single Command 13 (UsrSC13) Protocol C_S ON OFF * BO
User Single Command 14 (UsrSC14) Protocol C_S ON OFF * BO
User Single Command 15 (UsrSC15) Protocol C_S ON OFF * BO
User Single Command 16 (UsrSC16) Protocol C_S ON OFF * BO
User Single Command 17 (UsrSC17) Protocol C_S ON OFF * BO
F.No. Description Function Type Log-Buffers Configurable in
Matrix
IEC 60870-5-103
Event Log On/Off
Trip (Fault) Log On/Off
Ground Fault Log On/
Off
Marked in Oscill.
Record
LED
Binary Input
Function Key
Binary Output
Event Log
Type
Information-No
Data Unit (ASDU)
General Interrogation
Appendix
A-72 7UM61 Manual
C53000-G1176-C127-1
User Single Command 18 (UsrSC18) Protocol C_S ON OFF * BO
User Single Command 19 (UsrSC19) Protocol C_S ON OFF * BO
User Single Command 2 (UsrSC2) Protocol CF_S ON OFF * BO
User Single Command 2 (UsrSC2) Protocol SP ON OFF * BI C
B
User Single Command 20 (UsrSC20) Protocol C_S ON OFF * BO
User Single Command 21 (UsrSC21) Protocol C_S ON OFF * BO
User Single Command 22 (UsrSC22) Protocol C_S ON OFF * BO
User Single Command 3 (UsrSC3) Protocol CF_S ON OFF * BO
User Single Command 3 (UsrSC3) Protocol SP ON OFF * BI C
B
User Single Command 4 (UsrSC4) Protocol CF_S ON OFF * BO
User Single Command 4 (UsrSC4) Protocol SP ON OFF * BI C
B
User Single Command 5 (UsrSC5) Protocol C_S ON OFF * BO
User Single Command 6 (UsrSC6) Protocol C_S ON OFF * BO
User Single Command 7 (UsrSC7) Protocol C_S ON OFF * BO
User Single Command 8 (UsrSC8) Protocol C_S ON OFF * BO
User Single Command 9 (UsrSC9) Protocol C_S ON OFF * BO
UserSinglePointIndication(ON/OFF) 11 (Usr-
SpO/O11)
Protocol SP * * LED BI BO C
B
F.No. Description Function Type Log-Buffers Configurable in
Matrix
IEC 60870-5-103
Event Log On/Off
Trip (Fault) Log On/Off
Ground Fault Log On/
Off
Marked in Oscill.
Record
LED
Binary Input
Function Key
Binary Output
Event Log
Type
Information-No
Data Unit (ASDU)
General Interrogation
Appendix
7UM61 Manual A-73
C53000-G1176-C127-1
UserSinglePointIndication(ON/OFF) 12 (Usr-
SpO/O12)
Protocol SP * * LED BI BO C
B
UserSinglePointIndication(ON/OFF) 13 (Usr-
SpO/O13)
Protocol SP * * LED BI BO C
B
UserSinglePointIndication(ON/OFF) 14 (Usr-
SpO/O14)
Protocol SP * * LED BI BO C
B
UserSinglePointIndication(ON/OFF) 15 (Usr-
SpO/O15)
Protocol SP * * LED BI BO C
B
UserSinglePointIndication(ON/OFF) 16 (Usr-
SpO/O16)
Protocol SP * * LED BI BO C
B
UserSinglePointIndication(ON/OFF) 17 (Usr-
SpO/O17)
Protocol SP * * LED BI BO C
B
UserSinglePointIndication(ON/OFF) 18 (Usr-
SpO/O18)
Protocol SP * * LED BI BO C
B
UserSinglePointIndication(ON/OFF) 19 (Usr-
SpO/O19)
Protocol SP * * LED BI BO C
B
UserSinglePointIndication(ON/OFF) 20 (Usr-
SpO/O20)
Protocol SP * * LED BI BO C
B
UserSinglePointIndication(ON/OFF) 21 (Usr-
SpO/O21)
Protocol SP * * LED BI BO C
B
UserSinglePointIndication(ON/OFF) 22 (Usr-
SpO/O22)
Protocol SP * * LED BI BO C
B
UserSinglePointIndication(ON/OFF) 23 (Usr-
SpO/O23)
Protocol SP * * LED BI BO C
B
F.No. Description Function Type Log-Buffers Configurable in
Matrix
IEC 60870-5-103
Event Log On/Off
Trip (Fault) Log On/Off
Ground Fault Log On/
Off
Marked in Oscill.
Record
LED
Binary Input
Function Key
Binary Output
Event Log
Type
Information-No
Data Unit (ASDU)
General Interrogation
Appendix
A-74 7UM61 Manual
C53000-G1176-C127-1
UserSinglePointIndication(ON/OFF) 24 (Usr-
SpO/O24)
Protocol SP * * LED BI BO C
B
UserSinglePointIndication(ON/OFF) 25 (Usr-
SpO/O25)
Protocol SP * * LED BI BO C
B
UserSinglePointIndication(ON/OFF) 26 (Usr-
SpO/O26)
Protocol SP * * LED BI BO C
B
UserSinglePointIndication(ON/OFF) 27 (Usr-
SpO/O27)
Protocol SP * * LED BI BO C
B
UserSinglePointIndication(ON/OFF) 28 (Usr-
SpO/O28)
Protocol SP * * LED BI BO C
B
UserSinglePointIndication(ON/OFF) 29 (Usr-
SpO/O29)
Protocol SP * * LED BI BO C
B
UserSinglePointIndication(ON/OFF) 30 (Usr-
SpO/O30)
Protocol SP * * LED BI BO C
B
UserSinglePointIndication(ON/OFF) 31 (Usr-
SpO/O31)
Protocol SP * * LED BI BO C
B
UserSinglePointIndication(ON/OFF) 32 (Usr-
SpO/O32)
Protocol IntSP * * LED BI BO C
B
UserSinglePointIndication(ON/OFF) 33 (Usr-
SpO/O33)
Protocol IntSP * * LED BI BO C
B
UserSinglePointIndication(ON/OFF) 34 (Usr-
SpO/O34)
Protocol IntSP * * LED BI BO C
B
UserSinglePointIndication(ON/OFF) 35 (Usr-
SpO/O35)
Protocol IntSP * * LED BI BO C
B
F.No. Description Function Type Log-Buffers Configurable in
Matrix
IEC 60870-5-103
Event Log On/Off
Trip (Fault) Log On/Off
Ground Fault Log On/
Off
Marked in Oscill.
Record
LED
Binary Input
Function Key
Binary Output
Event Log
Type
Information-No
Data Unit (ASDU)
General Interrogation
Appendix
7UM61 Manual A-75
C53000-G1176-C127-1
UserSinglePointIndication(ON/OFF) 36 (Usr-
SpO/O36)
Protocol IntSP * * LED BI BO C
B
UserSinglePointIndication(ON/OFF) 37 (Usr-
SpO/O37)
Protocol IntSP * * LED BI BO C
B
UserSinglePointIndication(OPEN/CLOSE) 1
(UsrSpO/C1)
Protocol SP * * LED BI BO C
B
UserSinglePointIndication(OPEN/CLOSE) 10
(UsrSpO/C10)
Protocol IntSP * * LED BI BO C
B
UserSinglePointIndication(OPEN/CLOSE) 2
(UsrSpO/C2)
Protocol SP * * LED BI BO C
B
UserSinglePointIndication(OPEN/CLOSE) 3
(UsrSpO/C3)
Protocol SP * * LED BI BO C
B
UserSinglePointIndication(OPEN/CLOSE) 4
(UsrSpO/C4)
Protocol SP * * LED BI BO C
B
UserSinglePointIndication(OPEN/CLOSE) 5
(UsrSpO/C5)
Protocol SP * * LED BI BO C
B
UserSinglePointIndication(OPEN/CLOSE) 6
(UsrSpO/C6)
Protocol SP * * LED BI BO C
B
UserSinglePointIndication(OPEN/CLOSE) 7
(UsrSpO/C7)
Protocol SP * * LED BI BO C
B
UserSinglePointIndication(OPEN/CLOSE) 8
(UsrSpO/C8)
Protocol SP * * LED BI BO C
B
UserSinglePointIndication(OPEN/CLOSE) 9
(UsrSpO/C9)
Protocol IntSP * * LED BI BO C
B
F.No. Description Function Type Log-Buffers Configurable in
Matrix
IEC 60870-5-103
Event Log On/Off
Trip (Fault) Log On/Off
Ground Fault Log On/
Off
Marked in Oscill.
Record
LED
Binary Input
Function Key
Binary Output
Event Log
Type
Information-No
Data Unit (ASDU)
General Interrogation
Appendix
A-76 7UM61 Manual
C53000-G1176-C127-1
A.10 Protocol-Dependent Functions
n
Protocol → IEC 60870–5–103 Profibus FMS
(on request)
Profibus DP DNP3.0
(not yet supported)
Modbus ASCII/RTU Additional interface
(optional)
Function ⇓
Operational measured
values
Yes Yes Yes Yes Yes Yes
Metered values Yes Yes Yes Yes Yes Yes
Fault recording Yes Yes No. Only via additional
service interface
No. Only via additional service
interface
No. Only via additional service
interface
Yes
Remote relay setting No. Only via additional
service interface
Yes No. Only via additional
service interface
No. Only via additional service
interface
No. Only via additional service
interface
Yes
User-defined messages
and switching objects
Yes Yes Pre-defined “User-defined
messages” in CFC
Pre-defined “User-defined
messages” in CFC
Pre-defined “User-defined
messages” in CFC
Yes
Time synchronization Via protocol;
DCF77/IRIG B;
Interface;
Binary input
Via protocol;
DCF77/IRIG B;
Interface;
Binary input
Via DCF77/IRIG B;
Interface;
Binary input
Via protocol;
DCF77/IRIG B;
Interface;
Binary input
Via DCF77/IRIG B;
Interface;
Binary input
–
Messages with time stamp Yes Yes No Yes No Yes
Commissioning aids
• Measured value indication
blocking
Yes Yes No No No Yes
• Creating test messages
Yes Yes No No No Yes
Physical mode Asynchronous Asynchronous Asynchronous Asynchronous Asynchronous –
Transmission mode Cyclically/Event Cyclically/Event Cyclically Cyclically/Event Cyclically –
Baudrate 4800 to 38400 Up to 1.5 MBaud Up to 1.5 MBaud 2400 to 19200 2400 to 19200 2400 to 38400
Type RS232
RS485
Optical fibre
RS485
Optical fibre
• Single ring
• Double ring
RS485
Optical fibre
• Double ring
RS485
Optical fibre
RS485
Optical fibre
RS232
RS485
Optical fibre
Index
7UM61 Manual Index-1
C53000-G1176-C127-1
Index
Numerics
100–%–stator earth fault protection with 3rd
harm. 6-103, 10-33
21 6-65, 10-25
24 6-86, 10-29
27 6-75, 6-112, 10-26, 10-35
27TN (3.H.) 6-103, 10-33
32F 6-62, 10-24
32R 6-58, 10-23
40 6-50, 10-22
46 6-43, 10-20
49 6-34, 10-18
50 6-18, 6-112, 10-12, 10-35
50BF 6-107, 10-34
50GN 6-99
51 6-18, 6-27, 10-13
51GN 10-32
59 6-78, 10-27
59N 6-91, 10-31
59TN 6-103, 10-33
64F 10-32
64G 6-91, 10-31
64R 6-99
67 6-18, 10-12
67G 6-91, 10-31
74TC 10-38
81 6-81, 10-28
90–%–stator earth fault protection 6-91, 10-31
A
Accessories A-4
Ambient temperature 6-39
Analog Inputs 1-2, 10-2
Annunciations 4-9
Auxiliary and Reference Voltages 6-118
Auxiliary contact of VT protective switches 8-26
Auxiliary voltage supply 8-23
B
Battery A-4
Battery Replacement 9-4
Binary Inputs 1-3, 10-3
Binary Inputs and Outputs 1-3
Binary Outputs 1-3, 10-3
Block connection 6-3
Blocking Data Transmission 8-20
Breaker Control 6-150
Breaker Failure Protection 1-10, 6-107, 6-
110, 10-34
Breaker Failure Scheme 8-29
Buffer Battery 6-119
Bus Address 8-14, 8-16
Busbar connection 6-3
C
Calibrating the impedance protection 8-35
Calibrating the reverse power protection 8-48
CFC 4-15, 4-23, 4-24, 5-30
CFC–charts A-26
Changeover Contact for BO 17 8-15
Changing Setting Groups with Binary Inputs 8-6
Chatter Blocking 5-28
Chatter Suppression 5-16
Check
Overexcitation 8-37
Phase rotation 8-35
Phase sequence 8-37
Checking Connections 8-19
Checking the correct connection polarity 8-46
Checking the earth fault protection 8-38
Checking the voltage circuits 8-36
Climatic Stress Tests 10-10
Clock 10-7, 10-39
Command Sequence 6-151
Commands 5-7
Communication 4-3
Communications Interfaces 10-4
Configuration Matrix 4-7, 4-21, 5-10
Configuration of Functions 5-2
Configuration of Inputs and Outputs 4-21
Configuring
an Indication Buffer as a Destination 5-25
Control Display as a Destination for
Command Initiation 5-26
Default Display and Control Diagram as a
Destination 5-26
Measured Value Window as a Destination 5-
26
Index
Index-2 7UM61 Manual
C53000-G1176-C127-1
Metered Value Window as a Destination 5-
26
SCADA Interface as a Destination 5-25
Connection Examples A-10
Connections 8-5
Consistency check 5-34
Construction 10-11
Control 4-14
Control Functions 1-6
Control Messages 7-45
Control of Switchgear 7-34
Control Voltages for Binary Inputs 8-8
Coolant temperature 6-39
Correction angle 6-10
Coupling Unit A-5
Covering Caps 2-9
CT’s Nominal Values 6-10
Cubicle Mounting 2-2
Current and Voltage Rotation 6-122
Current Flow Monitoring 6-12
Current Inputs 10-2
Current limiting 6-35, 6-39
Current Symmetry 6-121
Current Terminals 2-8
D
Date and Time Setting 3-11
Date and Time Stamping 5-47
DCF77 4-30
Default Settings A-23
Binary Inputs A-23
Binary Outputs A-23
LED Indicators A-25
Definite-Time Overcurrent Protection 10-12
Definition of the Active Power Measurement A-
17
Destination 5-14
DIGSI REMOTE 4 A-5
DIGSI® 4 Tool 4-7
Dimensions 10-41
Directional check with c.t.'s in Holmgreen
connection 8-44
Disassembling the Device 9-9
Displacement voltage 6-11, 6-91
Display 4-6
Display Contrast 3-5
Display Contrast Setting 3-5
Display Editor A-5
DNP3.0 4-3, 4-31
DNP3.0 LWL 10-6
DNP3.0 RS485 10-6
E
Earth differential protection 6-94
Earth short-circuit protection 6-102
Electrical Check 3-3
Electrical Communication Interfaces 2-14
Electrical Tests 10-8
EMC Tests for Immunity 10-8
EMC Tests For Noise Emission 10-9
Emergency starting 6-39
Energy 7-17
Energy count values 6-146
ENTER Key 2-3, 2-15
ESC Key 2-3, 2-15
Establishing Information Properties 5-14
Event Log 3-5, 3-10
Event Messages 3-5, 3-10
Exiting the Setting Mode 6-6
Extension of Time Constants 6-39
External trip commands 6-133
F
Filtering 5-16
Forward active power supervision 6-62, 10-24
Frequency follow-up circuit 1-3, 8-33
Frequency Protection 1-9, 6-81, 6-83, 10-28,
10-34
Front Elements 1-3
Function Keys 2-3, 2-15, 4-22
Fuse-Failure-Monitor 6-116
G
General Device Pickup 6-138
General Diagrams A-6
Graphic Tools A-5
Graphical Analysis Program DIGRA A-5
H
Hardware Monitoring 6-118
Hardware Test Dialog Box 8-27
HMI 4-5
Index
7UM61 Manual Index-3
C53000-G1176-C127-1
I
IEC 60870-5-103 4-3
Iee transformation ratio 6-11
Impedance protection 6-65, 10-25
Impedance stages 6-70
Inadvertent energization 6-112, 10-35
Indications 5-6
Information 5-13
Initialize device 9-7
Installation 8-2
Instantaneous values 6-147
Insulation Tests 10-8
Interface Cable A-4
Interlocking 6-152, 7-41
Interoperability List A-27
Inverse Time Overcurrent Protection 10-13
IRIG B 4-30
J
Jumpers on the Printed Circuit Boards 8-8
K
k- factor 6-37
Keys 2-3, 2-15, 4-6
L
LED Key 2-3, 2-16
LEDs 2-3, 2-16, 4-6
List of Information A-41
Live StatusContact 8-11
Loop selection 6-65
M
Manual Overwriting 4-16, 7-38
Measured Values 10-36
Measured Values Monitoring 6-118
Measured Values Supervision 10-37
Measurement Viewing 3-5, 3-9
Measurements 4-11, 6-144
Measuring voltage failure 6-116
Mechanical Stress Tests 10-9
Memory Components 6-119
MENU Key 2-3, 2-15
Metered Values 5-18, 7-17
Microcomputer System 1-3
Min/Max Report 10-37
Minimum and Maximum Values 6-146, 6-147
MODBUS 8-17
MODBUS ASCII/RTU 1-6, 4-3, 4-31
MODBUS LWL 10-7
MODBUS RS485 10-7
Monitoring Functions 1-10
Monitoring of External Current Transformer
Circuits 6-121
Mounting Rail for 19"-Racks A-4
N
No Trip – No Flag 6-140
NO/NC Contact R4 8-13
Nominal Currents 8-7
Nominal rated values 6-16
Numerical Keys 2-3
Numerical Values 6-5
O
Operating Hours Counter 10-38
Operating mode 6-12
Operating Panel 4-5
Operating range of the protection functions 8-33
Operating Serial Interface 4-6
Operating Software DIGSI® 4 A-4
Operator Control Panel 3-4
Optical Communication Interfaces 2-13, 2-18
Optical Fibers 8-20
Ordering Information A-2
Ordering Number 3-3, 3-4
Oscillographic Recordings 8-33
Output Relays 10-3
Overcurrent Protection 6-18, 6-20, 10-12
Overexcitation (Overflux) protection 6-86, 10-
29
Overview of the masking features A-19
Overvoltage protection 6-78, 10-27
P
Packing 3-2
Panel Flush Mounting 2-2, 8-2
Panel Surface Mounting 2-15, 8-5
Password 4-15, 4-33
Index
Index-4 7UM61 Manual
C53000-G1176-C127-1
PC Front Interface 8-19, 10-4
Performing Configuration 5-20
Phase Rotation 6-11, 6-136
Pin Connectors A-4
Plug & Play 3-7
Plug-In Terminals 2-10, 2-11
Polarity of Current Transformers 6-10
Power Supply 1-4, 10-2
Power Supply Voltage 8-7
Power System Data 4-26
Power System Data 1 6-10
Power System Data 2 6-16
Power-Up 3-3
Pre–defined CFC–charts A-26
Preset Configurations 5-27
PROFIBUS 4-3, 4-31, 8-17
PROFIBUS DP 1-6
PROFIBUS FMS 1-6
Programmable Logic CFC 4-24
Protective Functions 1-6
Protocol-Dependent Functions A-76
R
R.m.s. values 6-147
Rack Mounting 8-3
Rated Frequency 6-12
Rear Service–/Modem– Interface 10-4
Reassembling the Device 8-18, 9-11
Regionalization 6-2
Repairs 9-9
Replacing the Battery 9-4
Replacing the Power Supply Fuse 9-10
Restoring Factory Settings 6-16
Return 9-13
Reverse power protection 6-58, 10-23
Rotor earth fault protection 6-99
Routine Checks 9-3
RS232 10-4, 10-5
RS485 10-4, 10-5
Run-Time Properties 5-30
S
SCADA Interface 8-19, 10-5
Sensitive earth current protection 6-99, 10-32
Serial Interfaces 4-31, 5-39, 8-8
Service Conditions 10-11
Set Status 7-39
Setting Groups 4-27, 6-14, 6-16, 8-6
Settings A-29
Short Circuit Links 2-8, A-4
SIMATIC CFC A-5
Software Monitoring 6-120
Source 5-14
Spill current 8-45
Spontaneous Messages 6-138
Starpoint earthing 6-12
Statistical Counters 6-141, 7-12
Statistics 10-38
Stator earth fault protection 6-101
Stop valve 6-58, 8-48
Storage 3-12
Switching Authority 6-155, 7-43
Switching Mode 6-156, 7-43
T
Tagging 4-16, 7-42
Terminal Block Covering Caps A-4
Terminating resistors 8-16
Termination 8-20
Test Dialogue Box 8-21
Test Mode 8-20
Text Values 6-5
Thermal measured values 6-146
Thermal Overload Protection 6-34, 10-18
Threaded Terminals 2-6, 2-17
Time Constant 6-38
Time for cool down 6-47, 6-89
Time Stamping 10-38
Time Synchronization 4-30
Time Synchronization Interface 8-20
Transferring Metering Values 5-27
Trip and Close Command Duration 6-12
Trip Circuit Monitoring 8-6, 10-38
Trip Log 10-38
Trip Time Characteristics
As Per ANSI 10-15
As Per IEC 10-13
Tripping Logic of the Entire Device 6-139
Troubleshooting 9-7
U
UE transformation ratio 6-11
Unbalanced load protection 6-43, 10-20
Underexcitation protection 6-50, 10-22
Undervoltage blocking 6-51
Undervoltage protection 6-75, 10-26
Index
7UM61 Manual Index-5
C53000-G1176-C127-1
Undervoltage seal–in 6-18, 6-65
Unpacking 3-2
Uph/Udelta adaptation factor 6-11
User Defined Functions with CFC 5-30
User Interface 3-4
Using DIGSI® 4 3-7
V
Vibration and Shock Stress 10-9, 10-10
Voltage Inputs 10-2
Voltage Protection 1-9, 6-75
Voltage Symmetry 6-121
Voltage Terminals 2-7
W
Watchdog 6-120
Waveform Capture 4-4, 4-13, 6-147, 10-38
Z
Z1B overreach zone 6-72
Zone Controlled/Bay Interlocking 6-153
Index
Index-6 7UM61 Manual
C53000-G1176-C127-1
Corrections
7UM61 Manual
C53000-G1176-C127-1
To
Siemens AG
Dept. EV S SUP2
D–13623 Berlin
Germany
Dear reader,
printing errors can never be entirely eliminated:
therefore, should you come across any when reading
this manual, kindly enter them in this form together
with any comments or suggestions for improvement
that you may have.
From
Name:
Company/Dept.:
Address:
Phone no.: Fax no.:
Corrections/Suggestions
Subject to technical alteration
Copying of this document and giving it to others and the use
or communication of the contents thereof, are forbidden without
express authority. Offenders are liable to the payment of
damages. All rights are reserved in the event of the grant of
a patent or the registration of a utility model or design.
Order-no.: C53000-G1176-C127-1
Available from: LZF Fürth-Bislohe
Printed in Germany/Imprimé en Allemagne
AG 0900 0.2 FO 538 En
Siemens Aktiengesellschaft