LGE Internal Use Only

HVAC & Energy Solution


25,May, 2011
BMS Gateway Introduction
AE Control Lab. AC Control 2Gr.
Haejin Kim(haejin0928.kim@lge.com)
Contents
1. Network Structure
2. V-Net Line Up
3. What is BMS?
4. BMS Biz Process
5. Lon Work Gateway
- Function
- Installation method
- Intro. to xif File & JMT List
6. BAC Net Gateway
- Function
- Installation method
- Intro. to JMT List
7. Regarding AHU
8. Other BMS GW
9. Practice
LGE Internal Use Only
HVAC & Energy Solution
VENT RAC
CAC PAC
1. Network Structure
Manage-
ment
(Integration)
& Control
Device
AC Manager
ACP
AC Smart AC Ez.(ing)
TMS BMS
485 Gateway
BACnet
LonWork/BACnet
Multi-V
LGAP
AC Station
(FCS)
DDC
HVAC
Facility
Lighting
Web
Gateway
(?)
Ethernet, TCP/IP
AC Smart
(?)
Ethernet, TCP/IP Ethernet, TCP/IP
LonWork
IO Module
(AI/AO/DI/DO)
Modbus
(ing)
LGE Internal Use Only
HVAC & Energy Solution
2. V-net Product Line Up
Central
Controller
Simple Central
Controller
ACP
Aircon Base
Controller
PQCSB101S0
PDI
(Power
Distribution
Indicator)
PQCPA11A0E (Version 4)
PQCPB11A0E(With IO)
PQCSC101S0
PQCSS520A0E
PQCSSA20A0
PQCSW320A0E
PQCSW320A1E
AC Manager
AC Smart
Others
BMS Gateway
BACnet
PQNFB17B0
LonWorks
PQNUD1S00
PQCSA001T0
128
Exp. Kit
On/Off Signal Thermostat
PI485
3rd
Link
PQCSD130A0
PHNFP14A0 PSNFP14A0 PMNFP14A0
PQCSE440U0
Do Kit
PQNFP00T0
Dry Contact
PMNFP14A1
PQNFB16A1
Web Based Controller
PC Software Program, Max 16 ACP Communication
Function
Controller
Scheduler
PQDSA/PQDSB
(AC220V)
PQDSBC
PQDSBNGCM1
PQDSB1
(AC24V)
Option
PQCSE342A0
AC-EZ
(AC-EZ)
PQCSE341A0
Web Web +PDI
KNX
(Under Testing)
Modbus
(UnderDeveloping)
ODU DC
PQDSBCDVM0
RCU(Room Control Unit)
PQDSBCGCD0
LGE Internal Use Only
HVAC & Energy Solution
3. What is BMS ?
Building management system (BMS) means a system designed to control, monitor and
optimize various building services, including lighting, heating, ventilation, cooling,
swimming pool pumps and water use in cooling towers.
/BNU-BN
LGE Internal Use Only
HVAC & Energy Solution
1. Test & Commissioning of Multi-V
2. Test & Commissioning of the LonWorks Gateway
1. Creation of control address table
2. Making Multi-V Lon Works Point list on project and pass it to BMS
1. Check BMS maker and confirm interoperability (JMT List on Global Web Site)
2. Check and list models of Multi-V
3. Prepare document: Point List of Lon Works Gateway (installation manual)
.xif File for Lon Work Gateway (Global Web Site)
Test & Commissioning
1. Technical meeting and JMT if necessary
Inquiry
Hand in estimate
Receive order
Installation
Refer to installation manual
BMS Maker Engineering Option :
1. In Real Site data transition
2. Pre_Engineering by using .xif File
4. BMS Biz Process / Lon Works
2. BMS Biz Process
LGE Internal Use Only
HVAC & Energy Solution
1. Test & Commissioning of Multi-V
2. Test & Commissioning of the BAC Net Gateway
1. Creation of control address table
2. Making Multi-V BAC Net object list on project and pass it to BMS
1. Check BMS maker and confirm interoperability (JMT List on Global Web Site)
2. Check and list models of Multi-V
3. Prepare document: PICS of BAC Net Gateway (Refer to installation manual)
Test & Commissioning
1. Technical meeting and JMT if necessary
Inquiry
Hand in estimate
Receive order
Installation
Refer to installation manual
PICS : BAC Net Protocol Implementation Conformance Statement
4. BMS Biz Process / BAC Net
2. BMS Biz Process
LGE Internal Use Only
HVAC & Energy Solution
4. BMS Biz Process
JMT(Joint Matching Test) has to be done at BMS maker side
Why :
- BAC Net has many choices of transmission flexibility.
- So, to minimize working procedure at local site
- Necessary for every independent BMS
- In the case that the BMS has updated, JMT will be required
LGE Internal Use Only
HVAC & Energy Solution
BNU-LW (LonWorks)
5. LonWorks Gateway
Model : PQNFB16A1
1. Function
2. Installation method
3. Intro. to xif File & JMT List
LGE Internal Use Only
HVAC & Energy Solution
5. LonWorks Gateway
Function(BMS Control/Monitoring Point)
Air conditioner Ventilation
LGE Internal Use Only
HVAC & Energy Solution
5.1 Function (Point List For BMS Engineering)
Air conditioner
SNVT : Standard Network Variable Type
nvi : network variable input (command), nvo : network variable output (monitoring)
LGE Internal Use Only
HVAC & Energy Solution
Ventilation
5.1 Function (Point List For BMS Engineering)
Point
No.
Name
Object Name
(nn : Air conditioner and
ventilation group/indoor
unit address
Object
Type
Unit
Code 0 Code 1 code2 Code3
Code
5
Code 9
1
ON/OFF
(setting)
SNVT_switch nviOnOff_nn Input Stop Operation
2 ON/OFF (status) SNVT_switch nvoOnOff_nn Output Stop Operation
3 Lock (setting) SNVT_switch nviLock_nn input Cancel Setting
4 Lock( status) SNVT_switch nvLock_nn Input Cancel Setting
5
Operation Mode
(setting)
SNVT_hvac_modenviHeatCo
ol_nn
output Auto
Heat
exchange
Normal
6
Operation Mode
(status)
SNVT_hvac_mode
nviHeatCool_nn
Output Auto
Heat
exchange
Normal
7
Fan speed
(setting)
SNVT_switch
nviFanSpeedCmd_nn
Input
Low
High
Very
high
8
Fan speed
(status)
SNVT_switch
nvoFanSpeed_nn
output Low High
Very
high
9 Error Code
SNVhvac_status
nvoUnitStatus_nn
output Refer to the LG Air Conditioner Error Code.
10
User Mode
(setting)
SNVT_count nviUser_nn Output Quick
Power
save
Heat
11
User Mode
(status)
SNVT_count nvoUser_nn output Quick
Power
save
heat
LGE Internal Use Only
HVAC & Energy Solution
5.2 LonWorks Gateway / Self Checking
Function (Web Access Commissioning )
Internet
Internet
Explorer
LGE Internal Use Only
HVAC & Energy Solution
STEP 1. Set unit address Assign a unique address to the unit being connected
address must be 00~3F
STEP 2. Set PI485 Install one PI485 for each outdoor unit, and set the DIP switch.
In Multi V Plus II system(Outdoor & Indoor series 2, Remocon : New Type),
PI485 Installation does not need.
STEP 3. Connect PI485 and Lon Works Gateway through the RS485 line.
STEP 4. Login to LonWorks Gateway through the Internet Explorer,
Check if all Indoor units are connected
Installation process
Refer to the Simple Central Controller Installation Method
Refer to the Simple Central Controller Installation Method
5.3. LonWorks Gateway /
LGE Internal Use Only
HVAC & Energy Solution
5.3. LonWorks Gateway
5.3.1 Installation method(system connection)
[ Indoor Address : 00~3F ]
LGE Internal Use Only
HVAC & Energy Solution
5.3. LonWorks Gateway
5.3.2 Wiring LonWorks Gateway to RS485 Line
LGE Internal Use Only
HVAC & Energy Solution
5.3. LonWorks Gateway
5.3.3 Check the connection through Web Access
192.168.1.101
LGE Internal Use Only
HVAC & Energy Solution
5.3. LonWorks Gateway
5.3.4 Check the connection through Web Access
LGE Internal Use Only
HVAC & Energy Solution
5.3. LonWorks Gateway
5.3.5 Check the connection through Web Access
LGE Internal Use Only
HVAC & Energy Solution
Commissioning Test
LGAP
Using web
browser
LonWorks
BMS
BMS Engineering Side
LG Engineering Side
1. Creating the A/C points.
2. Test of all units and
operations.
1. Confirm A/C connection
2. Test of operations
IP : 192.168.1.200
Subnet : 255.255.255.0
IP : 192.168.1.101
Subnet : 255.255.255.0
LonWorks
Router
5.3 Installation process
LGE Internal Use Only
HVAC & Energy Solution
5.4 .xif File & JMT List
- .xif File is for pre_engineering of BMS Company
- If this file is send to BMS company, BMS company can make BMS Graphic &
control windows (we call it pre-engineering)
- Can download on the Global Web site
( www.lgeaircon.com > Customer support > Download > Software )
- It include LG Air_conditioner Point List(control/monitoring property & data)
.xif File
JMT(Joint Matching Test) List of PQNFB16A1
No BMS Maker Model Version Date of JMT Location of JMT
1 T.A.C Vista 2005/09 Netherland
2 Andover 2006/12 Korea(Seoul)
3 SIEMENS RX Tool 2007/07 France
4 TRANE NL Util Node utility 4.5.8 2008/07 Munchen,German
5
List will be upgraded without inform, can refer on the Global Web site
( www.lgeaircon.com > Customer support > Download > Software )
LGE Internal Use Only
HVAC & Energy Solution
5.4 Lonwork Commissioning Methods
LGAP
LonWorks
BMS
1) Using Upload from device
2) Using XIF File for pre-engineering
Commissioning is to get device information of LonGW.
There are 2 commissioning methods in LonGW.
- One is upload from device, the other is using XIF
Device
information
LGAP
LonWorks
BMS
Device
information
XIF
(Dev Info)
LGE Internal Use Only
HVAC & Energy Solution
BNU-BAC(BAC Net)
Model : PQNFB17B0
6. BAC Net Gateway
4. BAC Net Gateway
1. Concept
2. Basic theory
1) Object
2) Device Instance No
3) Instance No of indoor
4) Service
5) BMS Communication sequence
3. Web access test
4. Installation Process
5. Wireshark HOWTO
6. VTS
LGE Internal Use Only
HVAC & Energy Solution
6. BAC Net Gateway / Concept
LGE Internal Use Only
HVAC & Energy Solution
6.1 BAC Net Gateway / Concept
LGE Internal Use Only
HVAC & Energy Solution
6.2 BAC Net Gateway/Basic Theory/1.Object
property
Temperature sensor
Object example
Important Property (need do remember..)
- object name, object type, present value
Q1
LGE Internal Use Only
HVAC & Energy Solution
Point
No
Name Object Name Object Type Indoor Vent
1 ON/OFF (setting) StartStopCommand_XX Binary Output 0 0
2 ON/OFF (status) StartStopStatus_XX Binary Input 0 0
3 Lock (setting) LockCommand_XX Binary Output 0 0
4 Lock (status) LockStatus_XX Binary Input 0 0
5 Filter Sign FilterSign_XX Binary Input X 0
6 Filter Sign reset FilterSignReset_XX Binary Value X 0
7 Operation Mode (setting) ModeCommand_XX Multistate Output 0 0
8 Operation Mode (status) ModeStatus_XX Multistate Input 0 0
9 Swing (setting) SwingCommand_XX Binary Output 0 X
10 Swing (status) SwingStatus_XX Binary Input 0 X
11 Fan speed (setting) FanSpeedCommand_XX Multistate Output 0 0
12 Fan speed (status) FanSpeedStatus_XX Multistate Input 0 0
13 Set Room Temperature SetRoomTemp_XX Analog Value 0 X
14 Room Temperature RoomTemp_XX Analog Input 0 X
15 Alarm Alarm_XX Binary Input 0 0
16 Error Code MalfunctionCode_XX Analog Input 0 0
17 User Mode (setting) UserModeCommand_XX Multistate Output X 0
18 User Mode (status) UserModeStatus_XX Multistate Input X 0
6.2 Function(BMS Control/Monitoring Point)
LGE Internal Use Only
HVAC & Energy Solution
6.2 Function(Object List)
Point
NO.
Product Name
Object Name
(XXX : Unit address_
Object
Type
Unit
Inactive Active
Text-0 Text-1 Text-2 Text-3 Text-4 Text-5
1
Indoor
& Vent
ON/OFF (setting) StartStopCommand_XXX BO Stop Start
2 ON/OFF (status) StartStopStatus_XXX BI Stop Run
3 Lock (setting) LockCommand_XXX BO Permit Prohibit
4 Lock (status) LockStatus_XXX BI Permit Prohibit
5
Vent
Filter Sign FilterSign_XXX BI Off On
6 Filter Sign reset FilterSignReset_XXX BV Reset (OFF) Vold (On)
7 Operation Mode (setting) ModeCommand_XXX MO Heat Exchange Auto Normal
8 Operation Mode (status) ModeStatus_XXX MI Heat Exchange Auto Normal
7
Indoor
Operation Mode (setting) ModeCommand_XXX MO Cool Dry Fan Auto Heat
8 Operation Mode (status) ModeStatus_XXX MI Cool Dry Fan Auto Heat
9 Swing (setting) SwingCommand_XXX BO Stop Run
10 Swing (status) SwingStatus_XXX BI Stop Run
11 Fan speed (setting)
FanSpeedCommand_XX
X
MO Low Middle High Auto
12 Fan speed (status) FanSpeedStatus_XXX MI Low Middle High Auto
11
Vent
Fan speed (setting)
FanSpeedCommand_XX
X
MO Low High Super High Auto
12 Fan speed (status) FanSpeedStatus_XXX MI Low High Super High Auto
13
Indoor
Set Room Temperature SetRoomTemp_XXX AV
14 Room Temperature RoomTemp_XXX AI
15 Indoor
& Vent
Alarm Alarm_XXX BI Normal Abnormal
16 Error Code MalfunctionCode_XXX AI Reference LG original Error Code
17
Vent
User Mode (setting)
UserModeCommand_XX
X
MO
Quick
operation
Energy
saving
Heat
18 User Mode (status) UserModeStatus_XXX MI
Quick
operation
Energy
saving
Heat
LGE Internal Use Only
HVAC & Energy Solution
6.2 BAC Net Gateway/Basic Theory/ 2.Device Instance & Network Number
Device is processing unit of BACnet protocol.
- One group is one device.
Device instance No Indoor unit address range
9000 00~0F
9001 10~1F
; ;
9015 F0~FF
Device instance number must be unique.
- Default first device instance number is 9000
- Change device instance number to be unique if necessary
(By using web page of BACnet GW)
Starting device Instance No.
(default no is 9000) Network(VNet) number must be unique
- Default value is 10
- Change Network number to be unique if necessary
(by using web page of BACnet GW)
network number setting (default = 10)
Device instance number setting
(default = 9000)
LGE Internal Use Only
HVAC & Energy Solution
6.2 BAC Net Gateway/Basic Theory/ 2.Device Instance & Network Number example
Device Instance Number & Network Number must be unique
HUB
BACnet/IP
192.168.0.100
Metasys ver4.1.5
192.168.0.106
NAE Controller
(Database, JAVA GUI)
192.168.0.107
BACnet GW#1
10(Network Number)
10
DevNo:1000 DevNo:1001 DevNo:1015
DevNo:2000 DevNo:2001DevNo:2015
192.168.0.108
BACnet GW#1
(00-0F) (10-1F) (F0-FF)
11
(01)
(00)
(0F)
(11)
(10)
(1F)
(F1)
(F0)
(FF)
Device (Group 0)
LGE Internal Use Only
HVAC & Energy Solution
6.2 BAC Net Gateway/Basic Theory/3.Instance Number of Indoor
2) Instance Number about Control & Monitoring Point of indoor unit
Instance Numbering Rule
type Indoor unit address Point no
0 7 8 15
Type = 0(indoor), 1(vent)
EX1) INDOOR UNIT = 0x01, startstop command (Point No = 1),
instance number = 0x0101 = 257
EX2) INDOOR UNIT = 0x01, lock status (Point No= 4),
instance number = 0x0104 = 260
16
Point No. example
16 bit
17 bit
LGE Internal Use Only
HVAC & Energy Solution
6.2 BAC Net Gateway/Basic Theory/4.Service
Service Contents
Who-Is Service used to determine the device object identifier and network addresses of all
devices on the network
I-Am Service used to respond to Who-Is service requests (device number)
ReadProperty Request the value of one property of one BACnet Object
ReadPropertyMultiple Request the values of one or more specified properties of one or more
BACnet objects.
WriteProperty Modify the value of a single specified property of a BACnet object
WritePropertyMultiple Modify the value of one or more specified properties of a BACnet object.
Basic BACnet Service
LGE Internal Use Only
HVAC & Energy Solution
6.3 BAC Net Gateway/Basic Theory/Service/4.WHO-IS and I-AM
AC Smart II
9000
Device
Number
(00) (01) (02)
(12) (11) (10)
(A0) (A1) (AF)
9001
9010
9016
(07)
Who-Is
I-Am(9000)
I-Am(9001)
I-Am(9010)
I-Am(9016)
LGE Internal Use Only
HVAC & Energy Solution
6.3 BAC Net Gateway/Basic Theory/Service/4.WHO-IS and I-AM
LGE Internal Use Only
HVAC & Energy Solution
6.3 BAC Net Gateway/Basic Theory/Service/4.RPM
Q2
LGE Internal Use Only
HVAC & Energy Solution
6.3 BAC Net Gateway/Basic Theory/5.BMS Communication Sequence
BMS BACnet GW
WHOIS (Unconfirmed req) WHOIS (Unconfirmed req)
IAM ACK (9000, Segmented_transmit)
ReadP(vendor id, system status, object_name, 9000)
ReadP ACK(vendor id = 432, system-status:operational, obj_name: LG HVAC Device 9000)
ReadMP(objid, max_apdu_length_accepted, seg_supported, vendor_id)
ReadMP ACK(objid:9000, max_apdu_leng_accepted:1496, seg_supported:segmented-transmit,
Vendor_id : 432)
ReadP(obj-list)
ReadP ACK(object 9000, BO 1, BI 2, . 787)
ReadP(1, object name)
ReadP ACK(1, obj_name : ac_startstopCmd_0
ReadMP(1, Inactive-text, active-text)
ReadMP ACK(1, Inactive text : stop, active text : start)
Device
Information
Information
Of indoor unit 00
Network Info
(broadcast)
LGE Internal Use Only
HVAC & Energy Solution
6. BAC Net Gateway
Function(Web Access Commissioning )
Internet
Internet
Explorer
LGE Internal Use Only
HVAC & Energy Solution
Installation process
6. BAC Net Gateway
STEP 1. Set unit address Assign a unique address to the unit being connected
STEP 2. Set PI485 Install one PI485 for each outdoor unit, and set the DIP switch.
In Multi V Plus II system, PI485 Installation does not need.
STEP 3. Connect PI485 and BAC Net Gateway through the RS485 line.
STEP 6. Login to BAC Net Gateway through the Internet Explorer,
Check if the all Indoor unit connected
STEP 4. Connect LAN Cable to BAC Net Gateway
STEP 5. Set the IP & Function of BAC Net Gateway by use of key & LCD
Refer to the ACP Installation Method, all same Method
LGE Internal Use Only
HVAC & Energy Solution
IP Address of BNU-BAC
1
2 Click that
6. BAC Net Gateway
Check the connection through Web Access
LGE Internal Use Only
HVAC & Energy Solution
Display windows for products
You can find the connected product status
If you cant , you must check the follows
- Communication line between each others
- Duplicated address of indoor
- Confirm the communication between BNU-BAC and indoor or ventilation
Check the connection through Web Access
6. Installation process
LGE Internal Use Only
HVAC & Energy Solution
Commissioning Test
LGAP
Using web
browser
BAC
Net
BMS
BMS Engineering Side
LG Engineering Side
HUB
1. Creating of the A/C points.
2. Test of all units and operations.
1. Confirm A/C connection
2. Test of operations
IP : 192.168.1.100
Subnet : 255.255.255.0
IP : 192.168.1.200
Subnet : 255.255.255.0
IP : 192.168.1.101
Subnet : 255.255.255.0
6. Installation process
LGE Internal Use Only
HVAC & Energy Solution
BNU-BAC(PQNFB17B0) JMT(Joint Matching Test) List
Check your BAC Net gateway Version in LCD , If not compatible to your site vendor,
Upgrade to the last version software, If need contact H.Q.
BMS Company
LG BAC Net G/W
Ver.
Date of
JMT
Location of JMT
Vendor Name S/W & Controller
Nao Digital
Version 1.0.0
2006/11 Seoul in Korea
A.L.C. - SW : Web CTRL 4.1 2007/04 Seoul in Korea
Siemens - S/W : Design insight 2.0 Version 1.0.2 2008/03 Seoul in Korea
Andover - S/W : Continuum 1.73
Version 1.1.3
2008/08 Melbourne in Australia
Delta Controls
- SW : ORCA View 3.33
- Controller : DCS-1212E
2008/08 Melbourne in Australia
- SW : ORCA View 3.33
- Controller : DAC-1146
2008/08 Melbourne in Australia
ALERTON
- S/W : Envision 2.0
- Controller : BCM-ETH
2008/08
Warramble in
Australia
Johnsons Controls
- Controller : Metasys
NCE v3.1
2008/08 Perth in Australia
- Controller : Metasys
NAE v2.2.0
2008/10 Columbia
- S/W : M3 Workstation
v5.4
2008/11
Seoul in
Korea,Greece
KDT - Cimon SCADA Ver. 2.5 Version 1.2.3 2008/11 Kwangju in Korea
6. Installation process
LGE Internal Use Only
HVAC & Energy Solution
0. Positioning to wire shark
Ref. How to use the wire shark program _ BAC Net test program
HUB
Case 1. BMS S/W is installed on PC
- Wire shark Program is executed on BMS PC
- It is best to capture the data through this program
HUB
Case 2. BMS S/W is installed on own controller
- Wire shark Program is executed on another PC
- It has got some restrictions to capture the data
it is not bad. We are helpful
PC
BNU-GW
BMS System
Controller
BNU-GW
PC
Wire shark Program
BMS System
LGE Internal Use Only
HVAC & Energy Solution
1. Execute the wire shark program and click the menu Capture->Interface
Ref. How to use the wire shark program _ BAC Net test program
LGE Internal Use Only
HVAC & Energy Solution
2. Click on the menu Capture Interface and confirm the network interface card
1
2
Ref. How to use the wire shark program _ BAC Net test program
LGE Internal Use Only
HVAC & Energy Solution
3. Enter bacnet at the Filter. Then you can see the BACnet data as below
Ref. How to use the wire shark program _ BAC Net test program
Display the BACnet Data
LGE Internal Use Only
HVAC & Energy Solution
4. Click the button Capture Stop for stopping capturing
Ref. How to use the wire shark program _ BAC Net test program
LGE Internal Use Only
HVAC & Energy Solution
5. Click on the menu File Save As for making the log file
1
3
2
4
Created file name BAC Net-log.pcap
Ref. How to use the wire shark program _ BAC Net test program
LGE Internal Use Only
HVAC & Energy Solution
7. AHU /
NO AHU Type AHU Model Contents Dry Contact PI485 Central Controller etc
1
Comm Kit
(Simple Control)
PUCKA0 Product:Universal PQDSBC PMNFP14A0
ACSmart, ACP,
BACnet, Lonwork
2 PRCKA0 Product : MultiV PQDSBNGCM0 PMNFP14A0/1
EEV KIT
(PRLK048A0)
3
Control Kit
(Simple Control
+ Damper
Control)
PRCKD20E Product : MultiV * 4 No
No need
(Embedded)
-
4 PRCKD40E Product : MultiV * 8 No
LGE Internal Use Only
HVAC & Energy Solution
7. AHU / Comm Kit /
BACnet/IP
LAN
LGNet0
Honeywell SymmetrE V310.1
(: WellTech)
BACnet GW
MV Plus II 4EA
Artcool Mirror
(ARNU09GSER2)
Artcool Gallery
(ARNU09GSF12)
Artcool Gallery
(ARNU07GSF12)
System Structure
TCP/IP
BNA-1C
CPU1
DI
Lonworks
(FT-10)
C-BUS
MV SyncII
RS485
LGNet2
LGNet1
Control Panel
Room Controller
AHU Comm Kit (PUCKA0, PRCKA0) operates as one of indoor unit.
So it can communicate with Central Controller through Outdoor unit(PI485).
It can be working with dry contact like indoor unit
AHU Comm
Kit
LGE Internal Use Only
HVAC & Energy Solution
7. AHU / Control Kit /
AHU Control Kit (PRCKD20E, PRCKD40E) communicate with Central Controller by itself
It doesnt work with dry contact at this moment
BACnet/IP
LAN
LGNet0
Honeywell SymmetrE V310.1
(: WellTech)
BACnet GW
MV Plus II 4EA
Artcool Mirror
(ARNU09GSER2)
Artcool Gallery
(ARNU09GSF12)
Artcool Gallery
(ARNU07GSF12)
System Structure
TCP/IP
BNA-1C
CPU1
DI
Lonworks
(FT-10)
C-BUS
RS485
FDD
LGNet1
Control Panel
Room Controller
(ACP_A/B)
AHU Control
Kit
LGE Internal Use Only
HVAC & Energy Solution
8. Other BMS Protocol / Modbus
Modbus GW
Management
Control
Device
BMS
485 Gateway
Multi-V
Ethernet
RS-485
PDI
Modbus
LGAP
Multi-V
Function Name Code Description
Read Coil Status 01h On/Off(status),Lock(status),
Swing(status), Alarm,
Read Holding
Registers
03h Mode(status),
Fan Speed(status),
Room Temp, Error Code,
Set Temp(status),
Force Single Coil 05h On/Off(setting),
Lock(setting),Swing(setting),
Preset Single
Registers
06h Mode(setting),
FanSpeed(setting),
Set Temp(setting),
Control & Monitoring Points
Changes (BACnet GW)
Contents AS-IS TO-BE
Protocol BACnet BACnet + Modbus
Compatible Unit AC, Vent,
AHU
AC, Vent, AHU
PDI
- Preparing new function around 30, May (Plan)
LGE Internal Use Only
HVAC & Energy Solution
9. Practice (Team Project)
BACnet/IP
LAN
LGNet0
BMS(PC)
BACnet GW or Lonworks GW
MV Plus II
System Structure
1) Prepare : Make connection as below (BNU(Lonwork & BACnet), ACSmart, 1 ODU, 2 Indoor Units)
- Only one BMS GW can be powered ON.
2) BNU-LW
A) Set indoor unit address as 01, 02
and set ACSmart as slave
B) Connect PC to Lonworks GW by LanCable
C) Set PC IP to 192.168.1.30
D) Access PC via internet explorer
E) Check whether Indoor units are monitored or not
F) Check control and monitoring function.
(01) (02)
3) BNU-LW
3.1) Web Page Function
A) Set indoor unit address as 01, 02 and Set ACSmart as slave
B) Connect PC to BACnet GW by LanCable
C) Set PC IP to 192.168.1.30
D) Access PC via internet explorer
E) Check whether Indoor units are monitored or not
F) Check control and monitoring function.
3.2) BMS Function
A) Run VTS (Visual Test Shell for BACnet) Program
(download it from internet first)
B) Set up Wireshark Program
C) Turn ON or OFF by VTS Program (INDOOR UNIT 01)
- Check the result by VTS Program
- Check the command by Remote controller or Web Page
- Analyze BACnet Protocol by wireshark Prog for ON/OFF command
AC-Smart
25%
50%
25%
LGE Internal Use Only
HVAC & Energy Solution
The End
2011 EU (Poland) BMS Gateway Seminar
Thank You