G+2, CP07C, TEMPORARY SITE OFFICE

(STRUCTURAL ANALYSIS DESIGN REPORT)


I. Basic Data:
Reference Height , Z = 9.60 m.
Structure Width = 21.00 m.
Wall height = 8.60 m.
Roof Slope = 5.44 deg.
Ze, for external pressure = m.
Terrain category = III see Table 4.1
II. Basic Wind Velocity, v
b
:
Equation 4.1
Directional factor, c
dir
= 1.00 recommended value=1.0, Note 2, section 4.2
Seasonal factor, c
season
= 1.00 recommended value=1.0, Note 3, section 4.2
Fundamental wind velocity = 35.00 m/s
v
b
= 35.00 m/s
III. Mean Wind Velocity, v
m
(z) :
Equation 4.3
Orography factor, c
o
(z) = 1.00 recommended value=1.0
Roughness factor, c
r
(z)
Equation 4.4
Roughness length, z
0
= 0.300 m.
Z
0
for terrain category II, z
o,II
= 0.05 m. see Table 4.1
= 5.00 m.
= 9.60 m.
= 9.60 m.
Equation 4.5
therefore, k
r
= 0.21539
therefore, c
r
(z) = 0.74648
v
m
(z) = 26.127 m/s
IV. Wind Turbulence, l
v
(z) :
Equation 4.7
turbulence factor, k
1
= 1.00 recommended value = 1.0, Note 2, section 4.4
therefore, l
v
(z) = 0.28854
lv(z) = k
1
/(c
o
(z) x ln(z/z
o
))
WIND LOADING AS PER EN 1991-1-4:2005
v
b
= c
dir
x c
season
x v
b,o
v
m
(z) = c
r
(z) x c
o
(z) x v
b
c
r
(z) = k
r
x ln(z/zo)
k
r
= 0.19 x (z
o
/z
o,II
)
0.07
Area with regular cover of vegetation or buildings or with isolated
obstacles with separations of maximum 20 obstacle heights (such as
villages, suburban terrain, permanent forest).
Zmin
Z
use, Z
Page 1 of 3
G+2, CP07C, TEMPORARY SITE OFFICE
(STRUCTURAL ANALYSIS DESIGN REPORT)
V. Basic Velocity Pressure, q
b
:
air density,

air
= 1.25
kg/m
3
recommended value = 1.25, Note 2, section 4.5
therefore, q
b
= 765.63
Pa (N/m
2
)
VI. Peak Velocity Pressure, q
p
:
Equation 4.8, Note 1, section 4.5
where,
l
v
(z) = 0.28854

air
= 1.25
kg/m
3
v
m
(z) = 26.127 m/s
therefore,
q
p
(z) = 1288.34
Pa (N/m
2
)
q
p
(z) = 1.288
kPa (kN/m
2
)
VII. COMPUTATION OF WIND PRESSURE TO VERTICAL WALLS:
ALONG X : h/d = LONGITUDINAL DIRECTION
2h =
b =
e =
DESIGN WIND PRESSURE
Kpa
ALONG Z : : h/d = TRANSVERSE DIRECTION
2h =
b =
e =
Kpa
q
b
= 1/2 x
air
x v
b
2
q
p
(z) = [1 + 7l
v
(z)] x 1/2 x
air
x v
m
2
(z)
ZONE D ZONE E
0.700
0.90 -0.39
-0.300
ZONE D ZONE E
0.721 -0.343
CORR. COEFF.
-0.38
PRESSURE 0.93 -0.44
0.85 0.85
DESIGN PRESSURE 0.77 -0.33
19.2
21
19.2
PRESSURE
DESIGN PRESSURE 0.79
0.212
Cpe, 10
Cpe, 10
CORR. COEFF. 0.85 0.85
0.410
e = smaller value of 2h or b:
19.2
40.5
19.2
e = smaller value of 2h or b:
Page 2 of 3
G+2, CP07C, TEMPORARY SITE OFFICE
(STRUCTURAL ANALYSIS DESIGN REPORT)
VIII. LOAD COMPUTATION
ALONG X :
2F 92.4 m
2
- Projected Area
FF 88.2 m
2
- Projected Area
Total = 180.6 m
2
- Total projected Area
1.00 - sum of windward and leeward
91 - Number of Columns
2F - F= 1.11 KN - load per column
1F - F= 1.06 KN - load per column
ALONG Z :
2F 158 m
2
- Projected Area
FF 170.1 m
2
- Projected Area
Total = 328.1 m
2
- Total projected Area
1.06 - sum of windward and leeward
91 - Number of Columns
2F - F= 2.02 KN - load per column
1F - F= 2.18 KN - load per column
Cpnet
# COL =
Ap =
Cpnet
Ap =
# COL =