Single-pole thermal-magnetic trip units

Series C types EHD, FD, and HFD 15A


(SC-4423-88A) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Series C types EHD, FD, and HFD 20A
(SC-4424-88A) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Series C types EHD, FD, and HFD 25A
(SC-4425-88A) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Series C types EHD, FD, and HFD 30A
(SC-4426-88A) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Series C types EHD, FD, and HFD 35A
(SC-4427-88A) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Series C types EHD, FD, and HFD 40A
(SC-4428-88A) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Series C types EHD, FD, and HFD 45A
(SC-4429-88A) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Series C types EHD, FD, and HFD 50A
(SC-4430-88A) . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Series C types EHD, FD, and HFD 60A
(SC-4431-88A) . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Series C types EHD, FD, and HFD 70A
(SC-4432-88A) . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Series C types EHD, FD, and HFD 80A
(SC-4433-88A) . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Series C types EHD, FD, and HFD 90A
(SC-4434-88A) . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Series C types EHD, FD, and HFD 100A
(SC-4435-88A) . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Series C types FD and HFD 110A
(SC-4436-88A) . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Series C types FD and HFD 125A
(SC-4437-88A) . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Series C types FD and HFD 150A
(SC-4438-88A) . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Effective May 2009
Supersedes June 2006 Trip Curves TC01200002E
Series C F-frame circuit breaker
time current curves
ote: N Time/current characteristic curves for Series C
F-frame circuit breakersvoltages shown in curve
headings are maximum at which the breaker may be
applied. Interrupting capacity of individual breaker is
tabulated on each curve.
Contents
Description Page Description Page
2
Trip Curves TC01200002E
Effective May 2009
Series C F-frame circuit breaker
time current curves

EATON CORPORATION www.eaton.com
Two-, three-, and four-pole thermal-magnetic trip units
Series C types ED, EHD, FDB, FD, and HFD
15A (SC-4134-87B) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
Series C types ED, EHD, FDB, FD, and HFD
20A (SC-4135-87B) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
Series C types ED, EHD, FDB, FD, and HFD
25A (SC-4136-87B) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
Series C types ED, EHD, FDB, FD, and HFD
30A (SC-4137-87B) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
Series C types ED, EHD, FDB, FD, and HFD
35A (SC-4138-87B) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
Series C types ED, EHD, FDB, FD, and HFD
40A (SC-4139-87B) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
Series C types ED, EHD, FDB, FD, and HFD
45A (SC-4140-87B) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
Series C types ED, EHD, FDB, FD, and HFD
50A (SC-4141-87B) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
Series C types ED, EHD, FDB, FD, and HFD
60A (SC-4142-87B) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
Series C types ED, EHD, FDB, FD, and HFD
70A (SC-4143-87B) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28
Series C types ED, EHD, FDB, FD, and HFD
80A (SC-4144-87B) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
Series C types ED, EHD, FDB, FD, and HFD
90A (SC-4145-87B) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
Series C types ED, EDB, EDS, EDH, EDC, EHD,
FDB, FD, and HFD 100A (SC-4146-87B) . . . . . . . . . . . . . . . . . . . . .31
Series C types ED, EDB, EDS, EDH, EDC, FDB,
FD, and HFD 110A (SC-4147-87B) . . . . . . . . . . . . . . . . . . . . . . . . .32
Series C types ED, EDB, EDS, EDH, EDC, FDB,
FD, and HFD 125A (SC-4148-87B) . . . . . . . . . . . . . . . . . . . . . . . . .33
Series C types ED, EDB, EDS, EDH, EDC, FDB, FD,
and HFD 150A (SC-4149-87B) . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34
Series C types FD and HFD 175225A
(SC-6970-98) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .35
Series C types ED, EDH, EDC, EDB, and EDS
175225A (SC-5805-94A) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36
Series C type FDC 15A (SC-5516-93A) . . . . . . . . . . . . . . . . . . . . . .37
Series C type FDC 20A (SC-5517-93A) . . . . . . . . . . . . . . . . . . . . . .38
Series C type FDC 25A (SC-5518-93A) . . . . . . . . . . . . . . . . . . . . . .39
Series C type FDC 30A (SC-5519-93A) . . . . . . . . . . . . . . . . . . . . . .40
Series C type FDC 35A (SC-5520-93A) . . . . . . . . . . . . . . . . . . . . . .41
Series C type FDC 40A (SC-5521-93A) . . . . . . . . . . . . . . . . . . . . . .42
Series C type FDC 45A (SC-5522-93A) . . . . . . . . . . . . . . . . . . . . . .43
Series C type FDC 50A (SC-5523-93A) . . . . . . . . . . . . . . . . . . . . . .44
Series C type FDC 60A (SC-5524-93A) . . . . . . . . . . . . . . . . . . . . . .45
Series C type FDC 70A (SC-5525-93A) . . . . . . . . . . . . . . . . . . . . . .46
Series C type FDC 80A (SC-5526-93A) . . . . . . . . . . . . . . . . . . . . . .47
Series C type FDC 90A (SC-5527-93A) . . . . . . . . . . . . . . . . . . . . . .48
Series C type FDC 100A (SC-5528-93A) . . . . . . . . . . . . . . . . . . . . .49
Series C type FDC 110A (SC-5529-93A) . . . . . . . . . . . . . . . . . . . . .50
Series C type FDC 125A (SC-5530-93A) . . . . . . . . . . . . . . . . . . . . .51
Series C type FDC 150A (SC-5531-93A) . . . . . . . . . . . . . . . . . . . . .52
Series C type FDC 175225A (SC-6971-98) . . . . . . . . . . . . . . . . . .53
Three-pole electronic trip units
Series C type FDE, HFDE, and FDCE 225A,
long/short delay (TC01203015E) . . . . . . . . . . . . . . . . . . . . . . . . . . .54
Series C type FDE, HFDE, and FDCE 225A,
Long/short delay and I
2
t (TC01203016E) . . . . . . . . . . . . . . . . . . . . .55
Series C type FDE, HFDE, and FDCE 225A,
LSIG (TC01203017E) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .56
Contents (continued)
Description Page Description Page
3
Trip Curves TC01200002E
Effective May 2009
Series C F-frame circuit breaker
time current curves

EATON CORPORATION www.eaton.com
Single-pole thermal-magnetic trip units
AB DE-ION circuit breakers
Figure 1. Types EHD, FD, and HFD 15ACurve No. SC-4423-88A
Minimum Maximum
Interrupting
rating
determines
end of curve
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
T
IM
E
IN
S
E
C
O
N
D
S
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
1
0
0
0
0
8
0
0
0
6
0
0
0
9
0
0
0
7
0
0
0
5
0
0
0
4
0
0
0
3
0
0
0
2
0
0
0
1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
80 60 90 70 50 40 30 20 10 9 8 7 5 6
T
IM
E
IN
S
E
C
O
N
D
S
10,000
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
CURRENT IN AMPERES
1
0
0
0
0
8
0
0
0
6
0
0
0
9
0
0
0
7
0
0
0
5
0
0
0
4
0
0
0
3
0
0
0
2
0
0
0
1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
80 60 90 70 50 40 30 20 10 9 8 7 5 6
15A
Maximum single-
pole trip ti mes
at 25C 1
CURRENT IN AMPERES
Maximum interrupting ti me

Circuit breaker time/current curves


Series C

F-frame circuit breakers


Catalog types EHD, FD and HFD circuit breakers, single-pole.
For application and coordination purposes only.
Based on 40C ambient, cold start. Connected with four (4) feet of
rated wire (60C up to 100A, 75C above 125A) per terminal.
Tested in open air.
Maximum Vac : 277 at 50/60 Hz
Maximum Vdc: 125
Breaker rating
Continuous
Instantaneous trip, amperes amperes
15A See curve
Breaker
type
Symmetrical RMS amperes (kA)
14
35
65
EHD
FD
HFD
10
10
10
Single-pole test data at 25C based on NEMA procedures
(AB 4-2003) for verifying performance of molded case
circuit breakers.
277V
DC amps
125V
Interrupting rating (UL/CSA listed)
4
Trip Curves TC01200002E
Effective May 2009
Series C F-frame circuit breaker
time current curves

EATON CORPORATION www.eaton.com
Figure 2. Types EHD, FD, and HFD 20ACurve No. SC-4424-88A
Minimum Maximum
Interrupting
rating
determines
end of curve
Maximum
interrupting
time
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
T
I
M
E
I
N
S
E
C
O
N
D
S
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
1
0
0
0
0
8
0
0
0
6
0
0
0
9
0
0
0
7
0
0
0
5
0
0
0
4
0
0
0
3
0
0
0
2
0
0
0
1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
80 60 90 70 50 40 30 20 10 9 8 7 5 6
T
I
M
E
I
N
S
E
C
O
N
D
S
10,000
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
CURRENT IN AMPERES
1
0
0
0
0
8
0
0
0
6
0
0
0
9
0
0
0
7
0
0
0
5
0
0
0
4
0
0
0
3
0
0
0
2
0
0
0
1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
80 60 90 70 50 40 30 20 10 9 8 7 5 6
20A
Maximum single-
pole trip times
at 25C 1
CURRENT IN AMPERES
Circuit breaker time/current curves
Series C

F-frame circuit breakers


Catalog types EHD, FD and HFD circuit breakers, single-pole.
For application and coordination purposes only.
Based on 40C ambient, cold start. Connected with four (4) feet of
rated wire (60C up to 100A, 75C above 125A) per terminal.
Tested in open air.
Maximum Vac: 277 at 50/60 Hz
Maximum Vdc: 125
Breaker rating
Continuous
Instantaneous trip, amperes amperes
20A See curve
Breaker
type
Symmetrical Rms amperes (kA )
14
35
65
EHD
FD
HFD
10
10
10
Single-pole test data at 25C based on NEMA procedures
(AB 4-2003) for verifying performance of molded case
circuit breakers.
277V
DC amps
125V
Interrupting rating (UL/CSA listed)

5
Trip Curves TC01200002E
Effective May 2009
Series C F-frame circuit breaker
time current curves

EATON CORPORATION www.eaton.com
Figure 3. Types EHD, FD, and HFD 25ACurve No. SC-4425-88A
Interrupting
rating
determines
end of curve
Minimum Maximum
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
T
I
M
E
I
N
S
E
C
O
N
D
S
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
1
0
0
0
0
8
0
0
0
6
0
0
0
9
0
0
0
7
0
0
0
5
0
0
0
4
0
0
0
3
0
0
0
2
0
0
0
1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
80 60 90 70 50 40 30 20 10 9 8 7 5 6
T
I
M
E
I
N
S
E
C
O
N
D
S
10,000
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
CURRENT IN AMPERES
1
0
0
0
0
8
0
0
0
6
0
0
0
9
0
0
0
7
0
0
0
5
0
0
0
4
0
0
0
3
0
0
0
2
0
0
0
1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
80 60 90 70 50 40 30 20 10 9 8 7 5 6
25A
Maximum single-
pole t rip ti mes
at 25C 1
CURRENT IN AMPERES
Maximum interrupting time

Circuit breaker time/current curves


Series C

F-frame circuit breakers


Catalog types EHD, FD and HFD circuit breakers, single-pole.
For application and coordination purposes only.
Based on 40C ambient, cold start. Connected with four (4) feet of
rated wire (60C up to 100A, 75C above 125A) per terminal.
Tested in open air.
Maximum Vac: 277 at 50/60 Hz
Maximum Vdc: 125
Breaker rating
Continuous
Instantaneous trip, amperes amperes
25A See curve
Breaker
type
Symmetrical Rms amperes (kA )
14
35
65
EHD
FD
HFD
10
10
10
Single-pole test data at 25C based on NEMA procedures
(AB 4-2003) for verifying performance of molded case
circuit breakers.
277V
DC amps
125V
Interrupting rating (UL/CSA listed)
6
Trip Curves TC01200002E
Effective May 2009
Series C F-frame circuit breaker
time current curves

EATON CORPORATION www.eaton.com
Figure 4. Types EHD, FD, and HFD 30ACurve No. SC-4426-88A
Interrupting
rating
determines
end of curve
Minimum Maximum
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
T
I
M
E
I
N
S
E
C
O
N
D
S
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
1
0
0
0
0
8
0
0
0
6
0
0
0
9
0
0
0
7
0
0
0
5
0
0
0
4
0
0
0
3
0
0
0
2
0
0
0
1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
80 60 90 70 50 40 30 20 10 9 8 7 5 6
T
I
M
E
I
N
S
E
C
O
N
D
S
10,000
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
CURRENT IN AMPERES
1
0
0
0
0
8
0
0
0
6
0
0
0
9
0
0
0
7
0
0
0
5
0
0
0
4
0
0
0
3
0
0
0
2
0
0
0
1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
80 60 90 70 50 40 30 20 10 9 8 7 5 6
30A
Maximum single-
pole trip times
at 25C 1
CURRENT IN AMPERES
Maximum interrupting time

Circuit breaker time/current curves


Series C

F-trame circuit breakers


Catalog types EHD, FD and HFD circuit breakers, single-pole
For application and coordination purposes only.
Based on 40C ambient, cold start. Connected with four (4) feet of
rated wire (60C up to 100A, 75C above 125A) per terminal.
Tested in open air.
Maximum Vac : 277 at 50/60 Hz
Maximum Vdc: 125
Breaker rating
Continuous Instantaneous trip, amperes
amperes
30A See Curve
Breaker
type
Symmetrical Rms amperes (kA )
14
35
65
EHD
FD
HFD
10
10
10
Single-pole test data at 25C based on NEMA procedures
(AB 4-2003) for verifying performance of molded case circuit
breakers.
277V
DC amps
125V
Interrupting rating (UL/CSA listed)
7
Trip Curves TC01200002E
Effective May 2009
Series C F-frame circuit breaker
time current curves

EATON CORPORATION www.eaton.com
Figure 5. Types EHD, FD, and HFD 35ACurve No. SC-4427-88A
Interrupting
rating
determines
end of curve
Maximum
interrupting
time
Minimum Maximum
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
T
I
M
E
I
N
S
E
C
O
N
D
S
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
1
0
0
0
0
8
0
0
0
6
0
0
0
9
0
0
0
7
0
0
0
5
0
0
0
4
0
0
0
3
0
0
0
2
0
0
0
1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
80 60 90 70 50 40 30 20 10 9 8 7 5 6
T
I
M
E
I
N
S
E
C
O
N
D
S
10,000
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
CURRENT IN AMPERES
1
0
0
0
0
8
0
0
0
6
0
0
0
9
0
0
0
7
0
0
0
5
0
0
0
4
0
0
0
3
0
0
0
2
0
0
0
1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
80 60 90 70 50 40 30 20 10 9 8 7 5 6
35A
Maximum single-
pole trip times
at 25C 1
CURRENT IN AMPERES

Circuit breaker time/current curves


Series C

F-frame circuit breakers


Catalog types EHD, FD and HFD circuit breakers, single-pole.
For application and coordination purposes only.
Based on 40C ambient, cold start. Connected with four (4) feet of
rated wire (60C up to 100A, 75C above 125A) per terminal.
Tested in open air.
Maximum Vac : 277 at 50/60 Hz
Maximum Vdc: 125
Breaker rating
Continuous
amperes Instantaneous trip, amperes
35A See curve
Breaker
type
Symmetrical Rms amperes (kA )
14
35
65
EHD
FD
HFD
10
10
10
Single-pole test data at 25C based on NEMA procedures
(AB 4-2003) for verifying performance of molded case
circuit breakers.
277V
DC amps
125V
Interrupting rating (UL/CSA listed)
8
Trip Curves TC01200002E
Effective May 2009
Series C F-frame circuit breaker
time current curves

EATON CORPORATION www.eaton.com
Figure 6. Types EHD, FD, and HFD 40ACurve No. SC-4428-88A
Interrupting
rating
determines
end of curve
Minimum Maximum
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
T
I
M
E
I
N
S
E
C
O
N
D
S
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
1
0
0
0
0
8
0
0
0
6
0
0
0
9
0
0
0
7
0
0
0
5
0
0
0
4
0
0
0
3
0
0
0
2
0
0
0
1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
80 60 90 70 50 40 30 20 10 9 8 7 5 6
T
I
M
E
I
N
S
E
C
O
N
D
S
10,000
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
CURRENT IN AMPERES
1
0
0
0
0
8
0
0
0
6
0
0
0
9
0
0
0
7
0
0
0
5
0
0
0
4
0
0
0
3
0
0
0
2
0
0
0
1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
80 60 90 70 50 40 30 20 10 9 8 7 5 6
40A
Maximum single-
pole trip times
at 25C 1
CURRENT IN AMPERES
Maximum interrupting time

Circuit breaker time/current curves


Series C

F-frame circuit breakers


Catalog types EHD, FD and HFD circuit breakers, single-pole.
For application and coordination purposes only.
Based on 40C ambient, cold start. Connected with four (4) feet of
rated wire (60C up to 100A, 75C above 125A) per terminal.
Tested in open air.
Maximum Vac: 277 at 50/60 Hz
Maximum Vdc: 125
Breaker rating
Continuous
amperes Instantaneous trip, amperes
40A See curve
Breaker
type
Symmetrical Rms amperes (kA )
14
35
65
EHD
FD
HFD
10
10
10
Single-pole test data at 25C based on NEMA procedures
(AB 4-2003) for verifying performance of molded case
circuit breakers.
277V
DC amps
125V
Interrupting rating (UL/CSA listed)
9
Trip Curves TC01200002E
Effective May 2009
Series C F-frame circuit breaker
time current curves

EATON CORPORATION www.eaton.com
Figure 7. Types EHD, FD, and HFD 45ACurve No. SC-4429-88A
Interrupting
rating
determines
end of curve
Minimum Maximum
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
T
I
M
E
I
N
S
E
C
O
N
D
S
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
1
0
0
0
0
8
0
0
0
6
0
0
0
9
0
0
0
7
0
0
0
5
0
0
0
4
0
0
0
3
0
0
0
2
0
0
0
1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
80 60 90 70 50 40 30 20 10 9 8 7 5 6
T
I
M
E
I
N
S
E
C
O
N
D
S
10,000
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
CURRENT IN AMPERES
1
0
0
0
0
8
0
0
0
6
0
0
0
9
0
0
0
7
0
0
0
5
0
0
0
4
0
0
0
3
0
0
0
2
0
0
0
1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
80 60 90 70 50 40 30 20 10 9 8 7 5 6
45A
Maximum single-
pole trip times
at 25C 1
CURRENT IN AMPERES
Maximum interrupting time

Circuit breaker time/current curves


Series C

F-frame circuit breakers


Catalog types EHD, FD and HFD circuit breakers, single-pole.
For application and coordination purposes only.
Based on 40C ambient, cold start. Connected with four (4) feet of
rated wire (60C up to 100A, 75C above 125A) per terminal.
Tested in open air.
Maximum Vac: 277 at 50/60 Hz
Maximum Vdc: 125
Breaker rating
Continuous
amperes Instantaneous trip, amperes
45A See curve
Breaker
type
Symmetrical Rms amperes (kA )
14
35
65
EHD
FD
HFD
10
10
10
Single-pole test data at 25C based on NEMA procedures
(AB 4-2003) for verifying performance of molded case
circuit breakers.
277V
DC amps
125V
Interrupting rating (UL/CSA listed)
10
Trip Curves TC01200002E
Effective May 2009
Series C F-frame circuit breaker
time current curves

EATON CORPORATION www.eaton.com
Figure 8. Types EHD, FD, and HFD 50ACurve No. SC-4430-88A
Interrupting
rating
determines
end of curve
Minimum Maximum
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
T
I
M
E
I
N
S
E
C
O
N
D
S
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
1
0
0
0
0
8
0
0
0
6
0
0
0
9
0
0
0
7
0
0
0
5
0
0
0
4
0
0
0
3
0
0
0
2
0
0
0
1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
80 60 90 70 50 40 30 20 10 9 8 7 5 6
T
I
M
E
I
N
S
E
C
O
N
D
S
10,000
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
CURRENT IN AMPERES
1
0
0
0
0
8
0
0
0
6
0
0
0
9
0
0
0
7
0
0
0
5
0
0
0
4
0
0
0
3
0
0
0
2
0
0
0
1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
80 60 90 70 50 40 30 20 10 9 8 7 5 6
50A
Maximum single-
pole trip times
at 25C 1
CURRENT IN AMPERES
Maximum interrupting ti me

Circuit breaker time/current curves


Series C

F-frame circuit breakers


Catalog types EHD, FD and HFD circuit breakers, single-pole.
For application and coordination purposes only.
Based on 40C ambient, cold start. Connected with four (4) feet of
rated wire (60C up to 100A, 75C above 125A) per terminal.
Tested in open air.
Maximum Vac: 277 at 50/60 Hz
Maximum Vdc: 125
Breaker rating
Continuous
amperes Instantaneous trip, amperes
50A See curve
Breaker
type
Symmetrical Rms amperes (kA )
14
35
65
EHD
FD
HFD
10
10
10
Single-pole test data at 25C based on NEMA procedures
(AB 4-2003) for verifying performance of molded case
circuit breakers.
277V
DC amps
125V
Interrupting rating (UL/CSA listed)
11
Trip Curves TC01200002E
Effective May 2009
Series C F-frame circuit breaker
time current curves

EATON CORPORATION www.eaton.com
Figure 9. Types EHD, FD, and HFD 60ACurve No. SC-4431-88A
Interrupting
rating
determines
end of curve
Minimum Maximum
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
T
I
M
E
I
N
S
E
C
O
N
D
S
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
1
0
0
0
0
8
0
0
0
6
0
0
0
9
0
0
0
7
0
0
0
5
0
0
0
4
0
0
0
3
0
0
0
2
0
0
0
1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
80 60 90 70 50 40 30 20 10 9 8 7 5 6
T
I
M
E
I
N
S
E
C
O
N
D
S
10,000
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
CURRENT IN AMPERES
1
0
0
0
0
8
0
0
0
6
0
0
0
9
0
0
0
7
0
0
0
5
0
0
0
4
0
0
0
3
0
0
0
2
0
0
0
1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
80 60 90 70 50 40 30 20 10 9 8 7 5 6
60A
Maximum single-
pole trip times
at 25C 1
CURRENT IN AMPERES
Maximum interrupting time

Circuit breaker time/current curves


Series C

F-frame circuit breakers


Catalog types EHD, FD and HFD circuit breakers, single-pole.
For application and coordination purposes only.
Based on 40C ambient, cold start. Connected with four (4) feet of
rated wire (60C up to 100A, 75C above 125A) per terminal.
Tested in open air.
Maximum Vac: 277 at 50/60 Hz
Maximum Vdc: 125
Breaker rating
Continuous
amperes Instantaneous trip, amperes
60A See curve
Single-pole test data at 25C based on NEMA procedures
(AB 4-2003) for verifying performance of molded case
circuit breakers.
Breaker
type
Symmetrical Rms amperes (kA )
14
35
65
EHD
FD
HFD
10
10
10
277V
DC amps
125V
Interrupting rating (UL/CSA listed)
12
Trip Curves TC01200002E
Effective May 2009
Series C F-frame circuit breaker
time current curves

EATON CORPORATION www.eaton.com
Figure 10. Types EHD, FD, and HFD 70ACurve No. SC-4432-88A
Interrupting
rating
determines
end of curve
Minimum Maximum
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
T
I
M
E
I
N
S
E
C
O
N
D
S
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
1
0
0
0
0
8
0
0
0
6
0
0
0
9
0
0
0
7
0
0
0
5
0
0
0
4
0
0
0
3
0
0
0
2
0
0
0
1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
80 60 90 70 50 40 30 20 10 9 8 7 5 6
T
I
M
E
I
N
S
E
C
O
N
D
S
10,000
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
CURRENT IN AMPERES
1
0
0
0
0
8
0
0
0
6
0
0
0
9
0
0
0
7
0
0
0
5
0
0
0
4
0
0
0
3
0
0
0
2
0
0
0
1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
80 60 90 70 50 40 30 20 10 9 8 7 5 6
70A
Maximum single-
pole trip times
at 25C 1
CURRENT IN AMPERES
Maximum
interrupting
time

Circuit breaker time/current curves


Series C

F-frame circuit breakers


Catalog types EHD, FD and HFD circuit breakers, single-pole.
For application and coordination purposes only.
Based on 40C ambient, cold start. Connected with four (4) feet of
rated wire (60C up to 100A, 75C above 125A) per terminal.
Tested in open air.
Maximum Vac: 277 at 50/60 Hz
Maximum Vdc: 125
Breaker rating
Continuous
amperes Instantaneous trip, amperes
70A See curve
Single-pole test data at 25C based on NEMA procedures
(AB 4-2003) for verifying performance of molded case
circuit breakers.
Breaker
type
Symmetrical Rms amperes (kA )
14
35
65
EHD
FD
HFD
10
10
10
277V
DC amps
125V
Interrupting rating (UL/CSA listed)
13
Trip Curves TC01200002E
Effective May 2009
Series C F-frame circuit breaker
time current curves

EATON CORPORATION www.eaton.com
Figure 11. Types EHD, FD, and HFD 80ACurve No. SC-4433-88A
Interrupting
rating
determines
end of curve
Minimum Maximum
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
T
I
M
E
I
N
S
E
C
O
N
D
S
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
1
0
0
0
0
8
0
0
0
6
0
0
0
9
0
0
0
7
0
0
0
5
0
0
0
4
0
0
0
3
0
0
0
2
0
0
0
1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
80 60 90 70 50 40 30 20 10 9 8 7 5 6
T
I
M
E
I
N
S
E
C
O
N
D
S
10,000
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
CURRENT IN AMPERES
1
0
0
0
0
8
0
0
0
6
0
0
0
9
0
0
0
7
0
0
0
5
0
0
0
4
0
0
0
3
0
0
0
2
0
0
0
1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
80 60 90 70 50 40 30 20 10 9 8 7 5 6
80A
Maximum single-
pole trip times
at 25C 1
CURRENT IN AMPERES
Maximum
interrupting
time

Circuit breaker time/current curves


Series C

F-frame circuit breakers


Catalog types EHD, FD and HFD circuit breakers, single-pole.
For application and coordination purposes only.
Based on 40C ambient, cold start. Connected with four (4) feet of
rated wire (60C up to 100A, 75C above 125A) per terminal.
Tested in open air.
Maximum Vac: 277 at 50/60 Hz
Maximum Vdc: 125
Breaker rating
Continuous
amperes Instantaneous trip, amperes
80A See curve
Single-pole test data at 25C based on NEMA procedures
(AB 4-2003) for verifying performance of molded case
circuit breakers.
Breaker
type
Symmetrical Rms amperes (kA )
14
35
65
EHD
FD
HFD
10
10
10
277V
DC amps
125V
Interrupting rating (UL/CSA listed)
14
Trip Curves TC01200002E
Effective May 2009
Series C F-frame circuit breaker
time current curves

EATON CORPORATION www.eaton.com
Figure 12. Types EHD, FD, and HFD 90ACurve No. SC-4434-88A
Interrupting
rating
determines
end of curve
Minimum Maximum
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
T
I
M
E
I
N
S
E
C
O
N
D
S
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
1
0
0
0
0
8
0
0
0
6
0
0
0
9
0
0
0
7
0
0
0
5
0
0
0
4
0
0
0
3
0
0
0
2
0
0
0
1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
80 60 90 70 50 40 30 20 10 9 8 7 5 6
T
I
M
E
I
N
S
E
C
O
N
D
S
10,000
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
CURRENT IN AMPERES
1
0
0
0
0
8
0
0
0
6
0
0
0
9
0
0
0
7
0
0
0
5
0
0
0
4
0
0
0
3
0
0
0
2
0
0
0
1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
80 60 90 70 50 40 30 20 10 9 8 7 5 6
90A
Maximum single-
pole trip times
at 25C 1
CURRENT IN AMPERES
Maximum
interrupting
time

Circuit breaker time/current curves


Series C

F-frame circuit breakers


Catalog types EHD, FD and HFD circuit breakers, single-pole.
For application and coordination purposes only.
Based on 40C ambient, cold start. Connected with four (4) feet of
rated wire (60C up to 100A, 75C above 125A) per terminal.
Tested in open air.
Maximum Vac: 277 at 50/60 Hz
Maximum Vdc: 125
Breaker rating
Continuous
amperes Instantaneous trip, amperes
90A See curve
Single-pole test data at 25C based on NEMA procedures
(AB 4-2003) for verifying performance of molded case circuit
breakers.
Breaker
type
Symmetrical Rms amperes (kA )
14
35
65
EHD
FD
HFD
10
10
10
277V
DC amps
125V
Interrupting rating (UL/CSA listed)
15
Trip Curves TC01200002E
Effective May 2009
Series C F-frame circuit breaker
time current curves

EATON CORPORATION www.eaton.com
Figure 13. Types EHD, FD, and HFD 100ACurve No. SC-4435-88A
Interrupting
rating
determines
end of curve
Minimum Maximum
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
T
I
M
E
I
N
S
E
C
O
N
D
S
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
1
0
0
0
0
8
0
0
0
6
0
0
0
9
0
0
0
7
0
0
0
5
0
0
0
4
0
0
0
3
0
0
0
2
0
0
0
1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
80 60 90 70 50 40 30 20 10 9 8 7 5 6
T
I
M
E
I
N
S
E
C
O
N
D
S
10,000
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
CURRENT IN AMPERES
1
0
0
0
0
8
0
0
0
6
0
0
0
9
0
0
0
7
0
0
0
5
0
0
0
4
0
0
0
3
0
0
0
2
0
0
0
1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
80 60 90 70 50 40 30 20 10 9 8 7 5 6
100A
Maximum single-
pole trip times
at 25C 1
CURRENT IN AMPERES
Maximum
interrupting
time

Circuit breaker time/current curves


Series C

F-frame circuit breakers


Catalog types EHD, FD and HFD circuit breakers, single-pole.
For application and coordination purposes only.
Based on 40C ambient, cold start. Connected with four (4) feet of
rated wire (60C up to 100A, 75C above 125A) per terminal.
Tested in open air.
Maximum Vac: 277 at 50/60 Hz
Maximum Vdc: 125
Breaker rating
Continuous
amperes Instantaneous trip, amperes
100A See curve
Single-pole test data at 25C based on NEMA procedures
(AB 4-2003) for verifying performance of molded case
circuit breakers.
Breaker
type
Symmetrical Rms amperes (kA )
14
35
65
EHD
FD
HFD
10
10
10
277V
DC amps
125V
Interrupting rating (UL/CSA listed)
16
Trip Curves TC01200002E
Effective May 2009
Series C F-frame circuit breaker
time current curves

EATON CORPORATION www.eaton.com
Figure 14. Types FD and HFD 110ACurve No. SC-4436-88A
Interrupting
rating
determines
end of curve
Minimum Maximum
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
T
I
M
E
I
N
S
E
C
O
N
D
S
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
1
0
0
0
0
8
0
0
0
6
0
0
0
9
0
0
0
7
0
0
0
5
0
0
0
4
0
0
0
3
0
0
0
2
0
0
0
1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
80 60 90 70 50 40 30 20 10 9 8 7 5 6
T
I
M
E
I
N
S
E
C
O
N
D
S
10,000
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
CURRENT IN AMPERES
1
0
0
0
0
8
0
0
0
6
0
0
0
9
0
0
0
7
0
0
0
5
0
0
0
4
0
0
0
3
0
0
0
2
0
0
0
1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
80 60 90 70 50 40 30 20 10 9 8 7 5 6
110A
Maximum single-
pole trip times
at 25C 1
CURRENT IN AMPERES
Maximum
interrupting
time

Circuit breaker time/current curves


Series C

F-frame circuit breakers


Catalog types FD & HFD circuit breakers, single-pole.
For application and coordination purposes only.
Based on 40C ambient, cold start. Connected with four (4) feet of
rated wire (60C up to 100A, 75C above 125A) per terminal.
Tested in open air.
Maximum Vac: 277 at 50/60 Hz
Maximum Vdc: 125
Breaker rating
Continuous
amperes Instantaneous trip, amperes
110A See curve
Single-pole test data at 25C based on NEMA procedures
(AB 4-2003) for verifying performance of molded case
circuit breakers.
Breaker
type
Symmetrical Rms amperes (kA )
35
65
FD
HFD
10
10
277V
DC amps
125V
Interrupting rating (UL/CSA listed)
17
Trip Curves TC01200002E
Effective May 2009
Series C F-frame circuit breaker
time current curves

EATON CORPORATION www.eaton.com
Figure 15. Types FD and HFD 125ACurve No. SC-4437-88A
Interrupting
rating
determines
end of curve
Minimum Maximum
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
T
I
M
E
I
N
S
E
C
O
N
D
S
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
1
0
0
0
0
8
0
0
0
6
0
0
0
9
0
0
0
7
0
0
0
5
0
0
0
4
0
0
0
3
0
0
0
2
0
0
0
1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
80 60 90 70 50 40 30 20 10 9 8 7 5 6
T
I
M
E
I
N
S
E
C
O
N
D
S
10,000
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
CURRENT IN AMPERES
1
0
0
0
0
8
0
0
0
6
0
0
0
9
0
0
0
7
0
0
0
5
0
0
0
4
0
0
0
3
0
0
0
2
0
0
0
1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
80 60 90 70 50 40 30 20 10 9 8 7 5 6
125A
Maximum single-
pole trip times
at 25C 1
CURRENT IN AMPERES
Maximum
interrupting
time

Circuit breaker time/current curves


Series C

F-frame circuit breakers


Catalog types FD and HFD circuit breakers, single-pole.
For application and coordination purposes only.
Based on 40C ambient, cold start. Connected with four (4) feet of
rated wire (60C up to 100A, 75C above 125A) per terminal.
Tested in open air.
Maximum Vac: 277 at 50/60 Hz
Maximum Vdc: 125
Breaker rating
Continuous
amperes Instantaneous trip, amperes
125A See curve
Single-pole test data at 25C based on NEMA procedures
(AB 4-2003) for verifying performance of molded case
circuit breakers.
Breaker
type
Symmetrical Rms amperes (kA )
35
65
FD
HFD
10
10
277V
DC amps
125V
Interrupting rating (UL/CSA listed)
18
Trip Curves TC01200002E
Effective May 2009
Series C F-frame circuit breaker
time current curves

EATON CORPORATION www.eaton.com
Figure 16. Types FD and HFD 150ACurve No. SC-4438-88A
Interrupting
rating
determines
end of curve
Minimum Maximum
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
T
I
M
E
I
N
S
E
C
O
N
D
S
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
1
0
0
0
0
8
0
0
0
6
0
0
0
9
0
0
0
7
0
0
0
5
0
0
0
4
0
0
0
3
0
0
0
2
0
0
0
1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
80 60 90 70 50 40 30 20 10 9 8 7 5 6
T
I
M
E
I
N
S
E
C
O
N
D
S
10,000
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
CURRENT IN AMPERES
1
0
0
0
0
8
0
0
0
6
0
0
0
9
0
0
0
7
0
0
0
5
0
0
0
4
0
0
0
3
0
0
0
2
0
0
0
1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
80 60 90 70 50 40 30 20 10 9 8 7 5 6
150A
Maximum single-
pole trip times
at 25C 1
CURRENT IN AMPERES
Maximum
interrupting
time

Circuit breaker time/current curves


Series C

F-frame circuit breakers


Catalog types FD and HFD circuit breakers, single-pole.
For application and coordination purposes only.
Based on 40C ambient, cold start. Connected with four (4) feet of
rated wire (60C up to 100A, 75C above 125A) per terminal.
Tested in open air.
Maximum Vac: 277 at 50/60 Hz
Maximum Vdc: 125
Breaker rating
Continuous
amperes Instantaneous trip, amperes
150A See curve
Single-pole test data at 25C based on NEMA procedures
(AB 4-2003) for verifying performance of molded case
circuit breakers.
Breaker
type
Symmetrical Rms amperes (kA )
35
65
FD
HFD
10
10
277V
DC amps
125V
Interrupting rating (UL/CSA listed)
19
Trip Curves TC01200002E
Effective May 2009
Series C F-frame circuit breaker
time current curves

EATON CORPORATION www.eaton.com
AB DE-ION Circuit Breakerstwo-, three-, and four-poles
Figure 17. Types ED, EHD, FDB, FD, and HFD 15ACurve No. SC-4134-87B
Minimum Maximum
Maximum interrupting time
Interrupting
rating
determines
end of curve
(see above)
1
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
T
IM
E
IN
S
E
C
O
N
D
S
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
CURRENT IN AMPERES
1
0
0
0
0
8
0
0
0
6
0
0
0
9
0
0
0
7
0
0
0
5
0
0
0
4
0
0
0
3
0
0
0
2
0
0
0
1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
80 60 90 70 50 40 30 20 10 9 8 7 5 6
T
IM
E
IN
S
E
C
O
N
D
S
10,000
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
CURRENT IN AMPERES
1
0
0
0
0
8
0
0
0
6
0
0
0
9
0
0
0
7
0
0
0
5
0
0
0
4
0
0
0
3
0
0
0
2
0
0
0
1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
80 60 90 70 50 40 30 20 10 9 8 7 5 6
15A
Maximum single-
pole trip times
at 25C 1
Circuit breaker time/current curves
Series C

F-frame circuit breakers


Catalog types ED, EHD, FDB, FDand HFDcircuit breakers, two-, three-
and four-poles.
For application and coordination purposes only.
Based on 40C ambient, cold start. Connected with four (4) feet of
rated wire (60C up to 125A, 75C above 125A) per terminal.
Tested in open air with current in all poles.
Maximum Vac: 600 at 50/60 Hz
Maximum Vdc: 250
Breaker rating
Continuous amperes Instantaneous trip amperes
15A See curve
18
18
65
100
EHD
FDB
FD
HFD
14
14
35
65

14
18
25
10
10
10
22
Single-pole test data at 25C based on NEMA procedures
(AB 4-2003) for verifying performance of molded case
circuit breakers.
ED 65
Interrupting Rating (UL/CSA Listed)
Breaker Symmetrical Rms amperes (KA) Amps (KA)
type @ 240 Vac @ 480 Vac @ 600 Vac 250 Vac 125V

10

20
Trip Curves TC01200002E
Effective May 2009
Series C F-frame circuit breaker
time current curves

EATON CORPORATION www.eaton.com
Figure 18. Types ED, EHD, FDB, FD, and HFD 20ACurve No. SC-4135-87B
Minimum
Maximum interrupting time
Interrupting
rating
determines
end of curve
(see above)
Maximum single-
pole trip times
at 25C 1
20A
1
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
T
IM
E
IN
S
E
C
O
N
D
S
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
CURRENT IN AMPERES
1
0
0
0
0
8
0
0
0
6
0
0
0
9
0
0
0
7
0
0
0
5
0
0
0
4
0
0
0
3
0
0
0
2
0
0
0
1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
80 60 90 70 50 40 30 20 10 9 8 7 5 6
T
IM
E
IN
S
E
C
O
N
D
S
10,000
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
CURRENT IN AMPERES
1
0
0
0
0
8
0
0
0
6
0
0
0
9
0
0
0
7
0
0
0
5
0
0
0
4
0
0
0
3
0
0
0
2
0
0
0
1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
80 60 90 70 50 40 30 20 10 9 8 7 5 6
Maximum
Circuit breaker time/current curves
Series C

F-frame circuit breakers


Catalog types ED, EHD, FDB, FDand HFDcircuit breakers, two-, three-
and four-poles.
For application and coordination purposes only.
Based on 40C ambient, cold start. Connected with four (4) feet of
rated wire (60C up to 125A, 75C above 125A) per terminal.
Tested in open air with current in all poles.
Maximum Vac: 600 at 50/60 Hz
Maximum Vdc: 250
Breaker rating
Continuous amperes Instantaneous trip amperes
20A See curve
18
18
65
100
EHD
FDB
FD
HFD
14
14
35
65

14
18
25
10
10
10
22
Single-pole test data at 25C based on NEMA procedures
(AB 4-2003) for verifying performance of molded case
circuit breakers.
Interrupting rating (UL/CSA listed)
Breaker Symmetrical Rms amperes (KA) Amps (KA)
type @ 240 Vac @ 480 Vac @ 600 Vac 250 Vdc 125 Vdc
ED 65 10

21
Trip Curves TC01200002E
Effective May 2009
Series C F-frame circuit breaker
time current curves

EATON CORPORATION www.eaton.com
Figure 19. Types ED, EHD, FDB, FD, and HFD 25ACurve No. SC-4136-87B
Minimum Maximum
Maximum interrupting time
Interrupting
rating
determines
end of curve
(see above)
Maximum single-
pole trip times
at 25C 1
25A
1
18
18
65
100
EHD
FDB
FD
HFD
14
14
35
65

14
18
25
10
10
10
22
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
T
IM
E
IN
S
E
C
O
N
D
S
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
CURRENT IN AMPERES
1
0
0
0
0
8
0
0
0
6
0
0
0
9
0
0
0
7
0
0
0
5
0
0
0
4
0
0
0
3
0
0
0
2
0
0
0
1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
80 60 90 70 50 40 30 20 10 9 8 7 5 6
T
IM
E
IN
S
E
C
O
N
D
S
10,000
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
CURRENT IN AMPERES
1
0
0
0
0
8
0
0
0
6
0
0
0
9
0
0
0
7
0
0
0
5
0
0
0
4
0
0
0
3
0
0
0
2
0
0
0
1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
80 60 90 70 50 40 30 20 10 9 8 7 5 6
Circuit breaker time/current curves
Series C

F-frame circuit breakers


Catalog types ED, EHD, FDB, FDand HFDcircuit breakers, two-, three-
and four-poles.
For application and coordination purposes only.
Based on 40C ambient, cold start. Connected with four (4) feet of
rated wire (60C up to 125A, 75C above 125A) per terminal.
Tested in open air with current in all poles.
Maximum Vac: 600 at 50/60 Hz
Maximum Vdc: 250
Breaker rating
Continuous amperes Instantaneous trip amperes
25A See curve
Single-pole test data at 25C based on NEMA procedures
(AB 4-2003) for verifying performance of molded case
circuit breakers.
Interrupting rating (UL/CSA listed)
Breaker
type
Symmetrical Rms amperes (KA) Amps (KA)
@ 240 Vac @ 480 Vac @ 600 Vac 250 Vdc 125 Vdc
ED 65 10

22
Trip Curves TC01200002E
Effective May 2009
Series C F-frame circuit breaker
time current curves

EATON CORPORATION www.eaton.com
Figure 20. Types ED, EHD, FDB, FD, and HFD 30ACurve No. SC-4137-87B
Maximum
Maximum interrupting time
Interrupting
rating
determines
end of curve
(see above)
Maximum single-
pole trip times
at 25C 1
Minimum
30A
1
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
T
IM
E
IN
S
E
C
O
N
D
S
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
CURRENT IN AMPERES
1
0
0
0
0
8
0
0
0
6
0
0
0
9
0
0
0
7
0
0
0
5
0
0
0
4
0
0
0
3
0
0
0
2
0
0
0
1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
80 60 90 70 50 40 30 20 10 9 8 7 5 6
T
IM
E
IN
S
E
C
O
N
D
S
10,000
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
CURRENT IN AMPERES
1
0
0
0
0
8
0
0
0
6
0
0
0
9
0
0
0
7
0
0
0
5
0
0
0
4
0
0
0
3
0
0
0
2
0
0
0
1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
80 60 90 70 50 40 30 20 10 9 8 7 5 6
Circuit breaker time/current curves
Series C

F-frame circuit breakers


Catalog types ED, EHD, FDB, FDand HFDcircuit breakers, two-, three-
and four-poles.
For application and coordination purposes only.
Based on 40C ambient, cold start. Connected with four (4) feet of
rated wire (60C up to 125A, 75C above 125A) per terminal.
Tested in open air with current in all poles.
Maximum Vac: 600 at 50/60 Hz
Maximum Vdc: 250
Breaker Rating
Continuous amperes Instantaneous trip amperes
30A See curve
18
18
65
100
EHD
FDB
FD
HFD
14
14
35
65

14
18
25
10
10
10
22
Single-pole test data at 25C based on NEMA procedures
(AB 4-2003) for verifying performance of molded case
circuit breakers.
Interrupting rating (UL/CSA listed)
Breaker Symmetrical RMS amperes (KA) Amps (KA)
type @ 240 Vac @ 480 Vac @ 600 Vac 250 Vdc 125 Vdc
ED 65

10
23
Trip Curves TC01200002E
Effective May 2009
Series C F-frame circuit breaker
time current curves

EATON CORPORATION www.eaton.com
Figure 21. Types ED, EHD, FDB, FD, and HFD 35ACurve No. SC-4138-87B
Minimum
Maximum interrupting time
Interrupting
rating
determines
end of curve
(see above)
Maximum single-
pole trip times
at 25C 1
35A
Maximum
1
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
T
IM
E
IN
S
E
C
O
N
D
S
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
CURRENT IN AMPERES
1
0
0
0
0
8
0
0
0
6
0
0
0
9
0
0
0
7
0
0
0
5
0
0
0
4
0
0
0
3
0
0
0
2
0
0
0
1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
80 60 90 70 50 40 30 20 10 9 8 7 5 6
T
IM
E
IN
S
E
C
O
N
D
S
10,000
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
CURRENT IN AMPERES
1
0
0
0
0
8
0
0
0
6
0
0
0
9
0
0
0
7
0
0
0
5
0
0
0
4
0
0
0
3
0
0
0
2
0
0
0
1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
80 60 90 70 50 40 30 20 10 9 8 7 5 6
Circuit breaker time/current curves
Series C

F-frame circuit breakers


Catalog types ED, EHD, FDB, FD and HFD circuit breakers, two-, three-
and four-poles.
For application and coordination purposes only.
Based on 40C ambient, cold start. Connected with four (4) feet of
rated wire (60C up to 125A, 75C above 125A) per terminal.
Tested in open air with current in all poles.
Maximum Vac: 600 at 50/60 Hz
Maximum Vdc: 250
Breaker rating
Continuous amperes Instantaneous trip amperes
35A See curve
18
18
65
100
EHD
FDB
FD
HFD
14
14
35
65

14
18
25
10
10
10
22
Single-pole test data at 25C based on NEMA procedures
(AB 4-2003) for verifying performance of molded case
circuit breakers.
Interrupting rating (UL/CSA listed)
Breaker Symmetrical Rms amperes (KA) Amps (KA)
type @ 240 Vac @ 480 Vac @ 600 Vac 250 Vdc 125 Vdc
ED 65 10

24
Trip Curves TC01200002E
Effective May 2009
Series C F-frame circuit breaker
time current curves

EATON CORPORATION www.eaton.com
Figure 22. Types ED, EHD, FDB, FD, and HFD 40ACurve No. SC-4139-87B
Minimum Maximum
Maximum interrupting time
Interrupting
rating
determines
end of curve
(see above)
Maximum single-
pole trip times
at 25C 1
40A
1
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
T
IM
E
IN
S
E
C
O
N
D
S
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
CURRENT IN AMPERES
1
0
0
0
0
8
0
0
0
6
0
0
0
9
0
0
0
7
0
0
0
5
0
0
0
4
0
0
0
3
0
0
0
2
0
0
0
1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
80 60 90 70 50 40 30 20 10 9 8 7 5 6
T
IM
E
IN
S
E
C
O
N
D
S
10,000
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
CURRENT IN AMPERES
1
0
0
0
0
8
0
0
0
6
0
0
0
9
0
0
0
7
0
0
0
5
0
0
0
4
0
0
0
3
0
0
0
2
0
0
0
1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
80 60 90 70 50 40 30 20 10 9 8 7 5 6
Circuit breaker time/current curves
Series C

F-frame circuit breakers


Catalog types ED, EHD, FDB, FDand HFDcircuit breakers, two-, three -
and four-poles.
For application and coordination purposes only.
Based on 40C ambient, cold start. Connected with four (4) feet of
rated wire (60C up to 125A, 75C above 125A) per terminal.
Tested in open air with current in all poles.
Maximum Vac: 600 at 50/60 Hz
Maximum Vdc: 250
Breaker Rating
Continuous amperes Instantaneous trip amperes
40A See curve
18
18
65
100
EHD
FDB
FD
HFD
14
14
35
65

14
18
25
10
10
10
22
Single-pole test data at 25C based on NEMA procedures
(AB 4-2003) for verifying performance of molded case
circuit breakers.
Interrupting rating (UL/CSA listed)
Breaker Symmetrical Rms amperes (KA) Amps (KA)
type @ 240 Vac @ 480 Vac @ 600 Vac 250 Vdc 125 Vdc
ED 65 10

25
Trip Curves TC01200002E
Effective May 2009
Series C F-frame circuit breaker
time current curves

EATON CORPORATION www.eaton.com
Figure 23. Types ED, EHD, FDB, FD, and HFD 45ACurve No. SC-4140-87B
Minimum Maximum
Maximum interrupting time
Interrupting
rating
determines
end of curve
(see above)
45A
1
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
T
IM
E
IN
S
E
C
O
N
D
S
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
CURRENT IN AMPERES
1
0
0
0
0
8
0
0
0
6
0
0
0
9
0
0
0
7
0
0
0
5
0
0
0
4
0
0
0
3
0
0
0
2
0
0
0
1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
80 60 90 70 50 40 30 20 10 9 8 7 5 6
T
IM
E
IN
S
E
C
O
N
D
S
10,000
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
CURRENT IN AMPERES
1
0
0
0
0
8
0
0
0
6
0
0
0
9
0
0
0
7
0
0
0
5
0
0
0
4
0
0
0
3
0
0
0
2
0
0
0
1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
80 60 90 70 50 40 30 20 10 9 8 7 5 6
Maximum single-
pole trip times
at 25C 1
Circuit breaker time/current curves
Series C

F-frame circuit breakers


Catalog types ED, EHD, FDB, FDand HFDcircuit breakers, two-, three-
and four-poles.
For application and coordination purposes only.
Based on 40C ambient, cold start. Connected with four (4) feet of
rated wire (60C up to 125A, 75C above 125A) per terminal.
Tested in open air with current in all poles.
Maximum Vac: 600 at 50/60 Hz
Maximum Vdc: 250
Breaker rating
Continuous amperes Instantaneous t rip amperes
45A See curve
18
18
65
100
EHD
FDB
FD
HFD
14
14
35
65

14
18
25
10
10
10
22
Single-pole test data at 25C based on NEMA procedures
(AB 4-2003) for verifying performance of molded case
circuit breakers.
Interrupting rating (UL/CSA lsted)
Symmetrical Rms amperes (KA) Amps (KA) Breaker
type @ 240 Vac @ 480 Vac @ 600 Vac 250 Vdc 125 Vdc
ED 65 10

26
Trip Curves TC01200002E
Effective May 2009
Series C F-frame circuit breaker
time current curves

EATON CORPORATION www.eaton.com
Figure 24. Types ED, EHD, FDB, FD, and HFD 50ACurve No. SC-4141-87B
Minimum Maximum
Maximum interrupting time
Interrupting
rating
determines
end of curve
(see above)
Maximum single-
pole trip times
at 25C 1
50A
1
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
T
IM
E
IN
S
E
C
O
N
D
S
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
CURRENT IN AMPERES
1
0
0
0
0
8
0
0
0
6
0
0
0
9
0
0
0
7
0
0
0
5
0
0
0
4
0
0
0
3
0
0
0
2
0
0
0
1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
80 60 90 70 50 40 30 20 10 9 8 7 5 6
T
IM
E
IN
S
E
C
O
N
D
S
10,000
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
CURRENT IN AMPERES
1
0
0
0
0
8
0
0
0
6
0
0
0
9
0
0
0
7
0
0
0
5
0
0
0
4
0
0
0
3
0
0
0
2
0
0
0
1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
80 60 90 70 50 40 30 20 10 9 8 7 5 6
Circuit breaker time/current curves
Series C

F-frame circuit breakers


Catalog types ED, EHD, FDB, FD and HFD circuit breakers, two-, three-
and four-poles.
For application and coordination purposes only.
Based on 40C ambient, cold start. Connected with four (4) feet of
rated wire (60C up to 125A, 75C above 125A) per terminal.
Tested in open air with current in all poles.
Maximum Vac: 600 at 50/60 Hz
Maximum Vdc: 250
Breaker rating
Continuous amperes Instantaneous trip amperes
50A See curve
18
18
65
100
EHD
FDB
FD
HFD
14
14
35
65
--
14
18
25
10
10
10
22
Single-pole test data at 25C based on NEMA procedures
(AB 4-2003) for verifying performance of molded case
circuit breakers.
ED 65
Interrupting rating (UL/CSA listed)
Symmetrical Rms amperes (KA) Amps (KA) Breaker
type @240Vac @480Vac @600Vac 250Vdc 125Vdc

10

27
Trip Curves TC01200002E
Effective May 2009
Series C F-frame circuit breaker
time current curves

EATON CORPORATION www.eaton.com
Figure 25. Types ED, EHD, FDB, FD, and HFD 60ACurve No. SC-4142-87B
Minimum Maximum
Maximum interrupting time
Interrupting
rating
determines
end of curve
(see above)
Maximum single-
pole trip times
at 25C 1
60A
1
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
T
IM
E
IN
S
E
C
O
N
D
S
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
CURRENT IN AMPERES
1
0
0
0
0
8
0
0
0
6
0
0
0
9
0
0
0
7
0
0
0
5
0
0
0
4
0
0
0
3
0
0
0
2
0
0
0
1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
80 60 90 70 50 40 30 20 10 9 8 7 5 6
T
IM
E
IN
S
E
C
O
N
D
S
10,000
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
CURRENT IN AMPERES
1
0
0
0
0
8
0
0
0
6
0
0
0
9
0
0
0
7
0
0
0
5
0
0
0
4
0
0
0
3
0
0
0
2
0
0
0
1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
80 60 90 70 50 40 30 20 10 9 8 7 5 6
Circuit breaker time/current curves
Series C

F-frame circuit breakers


Catalog types ED, EHD, FDB, FD and HFD circuit breakers, two-, three-
and four-poles.
For application and coordination purposes only.
Based on 40C ambient, cold start. Connected with four (4) feet of
rated wire (60C up to 125A, 75C above 125A) per terminal.
Tested in open air with current in all poles.
Maximum Vac: 600 at 50/60 Hz
Maximum Vdc: 250
Breaker rating
Continuous amperes Instantaneous trip amperes
60A See curve
18
18
65
100
EHD
FDB
FD
HFD
14
14
35
65

14
18
25
10
10
10
22
Single-pole test data at 25C based on NEMA procedures
(AB 4-2003) for verifying performance of molded case
circuit breakers.
Interrupting rating (UL/CSA listed)
Breaker Symmetrical Rms amperes (KA) Amps (KA)
type @ 240 Vac @ 480 Vac @ 600 Vac 250 Vdc 125 Vdc
ED 65 10

28
Trip Curves TC01200002E
Effective May 2009
Series C F-frame circuit breaker
time current curves

EATON CORPORATION www.eaton.com
Figure 26. Types ED, EHD, FDB, FD, and HFD 70ACurve No. SC-4143-87B
Maximum single-
pole trip times
at 25C 1
70A
Interrupting
rating
determines
end of curve
(see above)
Maximum Minimum
1
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
T
IM
E
IN
S
E
C
O
N
D
S
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
CURRENT IN AMPERES
1
0
0
0
0
8
0
0
0
6
0
0
0
9
0
0
0
7
0
0
0
5
0
0
0
4
0
0
0
3
0
0
0
2
0
0
0
1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
80 60 90 70 50 40 30 20 10 9 8 7 5 6
T
IM
E
IN
S
E
C
O
N
D
S
10,000
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
CURRENT IN AMPERES
1
0
0
0
0
8
0
0
0
6
0
0
0
9
0
0
0
7
0
0
0
5
0
0
0
4
0
0
0
3
0
0
0
2
0
0
0
1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
80 60 90 70 50 40 30 20 10 9 8 7 5 6
Circuit breaker time/current curves
Series C

F-frame circuit breakers


Catalog types ED, EHD, FDB, FD and HFD circuit breakers, two-, three-
and four-poles.
For application and coordination purposes only.
Based on 40C ambient, cold start. Connected with four (4) feet of
rated wire (60C up to 125A, 75C above 125A) per terminal.
Tested in open air with current in all poles.
Maximum Vac: 600 at 50/60 Hz
Maximum Vdc: 250
Breaker rating
Continuous amperes Instantaneous trip amperes
70A See curve
18
18
65
100
EHD
FDB
FD
HFD
14
14
35
65

14
18
25
10
10
10
22
Single-pole test data at 25C based on NEMA procedures
(AB 4-2003) for verifying performance of molded case
circuit breakers.
Interrupting rating (UL/CSA listed)
Symmetrical Rms amperes (KA) Amps (KA) Breaker
type @240Vac @480Vac @600Vac 250Vdc 125Vdc
ED 65 10

Maximum interrupting time


29
Trip Curves TC01200002E
Effective May 2009
Series C F-frame circuit breaker
time current curves

EATON CORPORATION www.eaton.com
Figure 27. Types ED, EHD, FDB, FD, and HFD 80ACurve No. SC-4144-87B
Maximum interrupting time
Maximum Minimum
Maximum single-
pole trip times
at 25C 1
80A
Interrupting
rating
determines
end of curve
(see above)
1
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
T
IM
E
IN
S
E
C
O
N
D
S
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
CURRENT IN AMPERES
1
0
0
0
0
8
0
0
0
6
0
0
0
9
0
0
0
7
0
0
0
5
0
0
0
4
0
0
0
3
0
0
0
2
0
0
0
1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
80 60 90 70 50 40 30 20 10 9 8 7 5 6
T
IM
E
IN
S
E
C
O
N
D
S
10,000
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
CURRENT IN AMPERES
1
0
0
0
0
8
0
0
0
6
0
0
0
9
0
0
0
7
0
0
0
5
0
0
0
4
0
0
0
3
0
0
0
2
0
0
0
1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
80 60 90 70 50 40 30 20 10 9 8 7 5 6
Circuit breaker time/current curves
Series C

F-frame circuit breakers


Catalog types ED, EHD, FDB, FD and HFD circuit breakers, two-, three-
and four-poles.
For application and coordination purposes only.
Based on 40C ambient, cold start. Connected with four (4) feet of
rated wire (60C up to 125A, 75C above 125A) per terminal.
Tested in open air with current in all poles.
Maximum Vac: 600 at 50/60 Hz
Maximum Vdc: 250
Breaker rating
Continuous amperes Instantaneous trip amperes
80A See curve
18
18
65
100
EHD
FDB
FD
HFD
14
14
35
65

14
18
25
10
10
10
22
Single-pole test data at 25C based on NEMA procedures
(AB 4-2003) for verifying performance of molded case
circuit breakers.
Interrupting rating (UL/CSA listed)
Symmetrical Rms amperes (KA) Amps (KA) Breaker
type @ 240 Vac @ 480 Vac @ 600 Vac 250 Vdc 125 Vdc
ED 65 10

30
Trip Curves TC01200002E
Effective May 2009
Series C F-frame circuit breaker
time current curves

EATON CORPORATION www.eaton.com

Figure 28. Types ED, EHD, FDB, FD, and HFD 90ACurve No. SC-4145-87B
Maximum Minimum
Maximum single-
pole trip times
at 25C 1
Maximum interrupting time
90A
Interrupting
rating
determines
end of curve
(see above)
1
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
T
IM
E
IN
S
E
C
O
N
D
S
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
CURRENT IN AMPERES
1
0
0
0
0
8
0
0
0
6
0
0
0
9
0
0
0
7
0
0
0
5
0
0
0
4
0
0
0
3
0
0
0
2
0
0
0
1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
80 60 90 70 50 40 30 20 10 9 8 7 5 6
T
IM
E
IN
S
E
C
O
N
D
S
10,000
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
CURRENT IN AMPERES
1
0
0
0
0
8
0
0
0
6
0
0
0
9
0
0
0
7
0
0
0
5
0
0
0
4
0
0
0
3
0
0
0
2
0
0
0
1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
80 60 90 70 50 40 30 20 10 9 8 7 5 6
Circuit breaker time/current curves
Series C

F-frame circuit breakers


Catalog types ED, EHD, FDB, FD and HFD circuit breakers, two-, three-
and four-poles.
For application and coordination purposes only.
Based on 40C ambient, cold start. Connected with four (4) feet of
rated wire (60C up to 125A, 75C above 125A) per terminal.
Tested in open air with current in all poles.
Maximum Vac: 600 at 50/60 Hz
Maximum Vdc: 250
Breaker rating
Continuous amperes Instantaneous trip amperes
90A See curve
18
18
65
100
EHD
FDB
FD
HFD
14
14
35
65

14
18
25
10
10
10
22
Single-pole test data at 25C based on NEMA procedures
(AB 4-2003) for verifying performance of molded case
circuit breakers.
Interrupting rating (UL/CSA listed)
Breaker Symmetrical Rms amperes (KA) Amps (KA)
type @ 240 Vac @ 480 Vac @ 600 Vac 250 Vdc 125 Vdc
ED 65 10

31
Trip Curves TC01200002E
Effective May 2009
Series C F-frame circuit breaker
time current curves

EATON CORPORATION www.eaton.com
Figure 29. Types ED, EDB, EDS, EDH, EDC, EHD, FDB, FD, and HFD 100ACurve No. SC-4146-87B
Maximum Minimum
Maximum single-
pole trip times
at 25C 1
Maximum interrupting time
100A
Interrupting
rating
determines
end of curve
(see above)
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
T
IM
E
IN
S
E
C
O
N
D
S
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
CURRENT IN AMPERES
1
0
0
0
0
8
0
0
0
6
0
0
0
9
0
0
0
7
0
0
0
5
0
0
0
4
0
0
0
3
0
0
0
2
0
0
0
1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
80 60 90 70 50 40 30 20 10 9 8 7 5 6
T
IM
E
IN
S
E
C
O
N
D
S
10,000
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
CURRENT IN AMPERES
1
0
0
0
0
8
0
0
0
6
0
0
0
9
0
0
0
7
0
0
0
5
0
0
0
4
0
0
0
3
0
0
0
2
0
0
0
1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
80 60 90 70 50 40 30 20 10 9 8 7 5 6
Circuit breaker time/current curves
Series C

F-frame circuit breakers


Catalog types ED, EDB, EDS, EDH, EDC, EHD, FDB, FD and HFD circuit
breakers, two-, three- and four-poles.
For application and coordination purposes only.
Based on 40C ambient, cold start. Connected with four (4) feet of
rated wire (60C up to 125A, 75C above 125A) per terminal.
Tested in open air with current in all poles.
Single-pole test data at 25C based on NEMA procedures
(AB 4-2003) for verifying performance of molded case
circuit breakers.
Maximum Vac: 600 at 50/60 Hz
Maximum Vdc: 250
Breaker rating
Continuous amperes Instantaneous trip amperes
100A See curve
Interrupting rating (UL/CSA listed)
Breaker Symmetrical Rms amperes (KA) Amps (KA)
type @ 240 Vac @ 480 Vac @ 600 Vac 250 Vdc 125 Vdc
1
ED
EDB
HFD
FD
FDB
EHD
EDS
EDH
EDC
100 65 25 22
65 35 18 10
18 14 14 10
18 14 10
200 10
100 10
42 10
22 10
65 10
32
Trip Curves TC01200002E
Effective May 2009
Series C F-frame circuit breaker
time current curves

EATON CORPORATION www.eaton.com
Figure 30. Types ED, EDB, EDS, EDH, EDC, FDB, FD, and HFD 110ACurve No. SC-4147-87B
Maximum Minimum
Maximum interrupting time
Maximum single-
pole trip times
at 25C 1
110A
Interrupting
rating
determines
end of curve
(see above)
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
T
IM
E
IN
S
E
C
O
N
D
S
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
CURRENT IN AMPERES
1
0
0
0
0
8
0
0
0
6
0
0
0
9
0
0
0
7
0
0
0
5
0
0
0
4
0
0
0
3
0
0
0
2
0
0
0
1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
80 60 90 70 50 40 30 20 10 9 8 7 5 6
T
IM
E
IN
S
E
C
O
N
D
S
10,000
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
CURRENT IN AMPERES
1
0
0
0
0
8
0
0
0
6
0
0
0
9
0
0
0
7
0
0
0
5
0
0
0
4
0
0
0
3
0
0
0
2
0
0
0
1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
80 60 90 70 50 40 30 20 10 9 8 7 5 6
Circuit breaker time/current curves
Series C

F-frame circuit breakers


Catalog types ED, EDB, EDS, EDH, EDC, FDB, FD and HFD circuit
breakers, two-, three- and four-poles.
For application and coordination purposes only.
Based on 40C ambient, cold start. Connected with four (4) feet of
rated wire (60C up to 125A, 75C above 125A) per terminal.
Tested in open air with current in all poles.
Single-pole test data at 25C based on NEMA procedures
(AB 4-2003) for verifying performance of molded case
circuit breakers.
1
Maximum Vac: 600 at 50/60 Hz
Maximum Vdc: 250
Breaker rating
Continuous amperes Instantaneous trip amperes
110A See curve
Interrupting rating (UL/CSA listed)
Breaker Symmetrical Rms amperes (KA) Amps (KA)
type @ 240 Vac @ 480 Vac @ 600 Vac 250 Vdc 125 Vdc
HFD
FD
FDB
ED
EDB
EDS
EDH
EDC
100 65 25 22
65 35 18 10
18 14 14 10
200 10
100 10
42 10
22 10
65 10
33
Trip Curves TC01200002E
Effective May 2009
Series C F-frame circuit breaker
time current curves

EATON CORPORATION www.eaton.com
Figure 31. Types ED, EDB, EDS, EDH, EDC, FDB, FD, and HFD 125ACurve No. SC-4148-87B
Maximum Minimum
Maximum single-
pole trip times
at 25C 1
Maximum interrupting t ime
125A
Interrupting
rating
determines
end of curve
(see above)
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
T
IM
E
IN
S
E
C
O
N
D
S
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
CURRENT IN AMPERES
1
0
0
0
0
8
0
0
0
6
0
0
0
9
0
0
0
7
0
0
0
5
0
0
0
4
0
0
0
3
0
0
0
2
0
0
0
1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
80 60 90 70 50 40 30 20 10 9 8 7 5 6
T
IM
E
IN
S
E
C
O
N
D
S
10,000
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
CURRENT IN AMPERES
1
0
0
0
0
8
0
0
0
6
0
0
0
9
0
0
0
7
0
0
0
5
0
0
0
4
0
0
0
3
0
0
0
2
0
0
0
1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
80 60 90 70 50 40 30 20 10 9 8 7 5 6
Circuit breaker time/current curves
Series C

F-frame circuit breakers


Catalog types ED, EDB, EDS, EDH, EDC, FDB, FD and HFD circuit
breakers, two-, three- and four-poles.
For application and coordination purposes only.
Based on 40C ambient, cold start. Connected with four (4) feet of
rated wire (60C up to 125A, 75C above 125A) per terminal.
Tested in open air with current in all poles.
Single-pole test data at 25C based on NEMA procedures
(AB 4-2003) for verifying performance of molded case
circuit breakers.
Maximum Vac: 600 at 50/60 Hz
Maximum Vdc: 250
Breaker rating
Continuous amperes Instantaneous trip amperes
125A See curve
Interrupting rating (UL/CSA listed)
Symmetrical Rms amperes (KA) Amps (KA) Breaker
@ 240 Vac @ 480 Vac @ 600 Vac 250 Vdc 125 Vdc type
1
HFD
FD
FDB
100 65 25 22
65 35 18 10
18 14 14 10
ED
EDB
EDS
EDH
EDC
65 10
22 10
42 10
100 10
200 10
34
Trip Curves TC01200002E
Effective May 2009
Series C F-frame circuit breaker
time current curves

EATON CORPORATION www.eaton.com
Figure 32. Types ED, EDB, EDS, EDH, EDC, FDB, FD, and HFD 150ACurve No. SC-4149-87B
Maximum Minimum
Maximum single-
pole trip times
at 25C 1
Maximum interrupting t ime
150A
Interrupting
rating
determines
end of curve
(see above)
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
T
IM
E
IN
S
E
C
O
N
D
S
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
CURRENT IN AMPERES
1
0
0
0
0
8
0
0
0
6
0
0
0
9
0
0
0
7
0
0
0
5
0
0
0
4
0
0
0
3
0
0
0
2
0
0
0
1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
80 60 90 70 50 40 30 20 10 9 8 7 5 6
T
IM
E
IN
S
E
C
O
N
D
S
10,000
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
CURRENT IN AMPERES
1
0
0
0
0
8
0
0
0
6
0
0
0
9
0
0
0
7
0
0
0
5
0
0
0
4
0
0
0
3
0
0
0
2
0
0
0
1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
80 60 90 70 50 40 30 20 10 9 8 7 5 6
Circuit breaker time/current curves
Series C

F-frame circuit breakers


Catalog types ED, EDB, EDS, EDH, EDC, FDB, FD and HFD circuit
breakers, two-, three- and four-poles.
For application and coordination purposes only.
Based on 40C ambient, cold start. Connected with four (4) feet of
rated wire (60C up to 125A, 75C above 125A) per terminal.
Tested in open air with current in all poles.
Single-pole test data at 25C based on NEMA procedures
(AB 4-2003) for verifying performance of molded case
circuit breakers.
1
Maximum Vac: 600 at 50/60 Hz
Maximum Vdc: 250
Breaker rating
Continuous amperes Instantaneous trip amperes
150A See curve
Interrupting rating (UL/CSA listed)
Breaker Symmetrical Rms amperes (KA) Amps (KA)
type @ 240 Vac @ 480 Vac @ 600 Vac 250 Vdc 125 Vdc

HFD
FD
FDB
100 65 25 22
65 35 18 10
18 14 14 10
ED
EDB
EDS
EDH
EDC
65 10
22 10
42 10
100 10
200 10
35
Trip Curves TC01200002E
Effective May 2009
Series C F-frame circuit breaker
time current curves

EATON CORPORATION www.eaton.com
Figure 33. Types FD and HFD 175225ACurve No. SC-6970-98
Maximum single-
pole trip times
at 25C
Maximum
trip time
Minimum
trip time
175 A
200 A
225 A
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
T
I
M
E
I
N
S
E
C
O
N
D
S
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
T
I
M
E
I
N
S
E
C
O
N
D
S
10,000
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
175225A
Circuit breaker time/current curves
molded-case circuit breakers
Catalog types FD/HFD circuit breakers, two-, three- and four-poles.
For application and coordination purposes only.
Based on 40C ambient, cold start. Connected with four (4) feet of rated
wire (75C) per terminal. Tested in open air with current in all poles.
Maximum Vac: 600 at 50/60 Hz
Maximum Vdc: 250
Breaker rating
I
n
amperes Instantaneous pick-up, amperes Rms
175 2400
200 2400
225 2400
Breaker
type
Symmetrical Rms amperes (kA), I
cu
FD
HFD
Fixed inverse time overcurrent release.
Single-pole test data at 25 C based on NEMA procedures (AB 4-2003)
for verifying performances of molded case circuit breakers.
Total operation time.
terrupting rating determines end of curve.
In this interruption region:
The curve is drawn for I
n
= 200A. For I
n
200A, the end points in this
region are displaced along the current-axis by a factor (200A/I
n
)
240 Vac
Interrupting ratings
65
100
480 Vac
35
65
600 Vac
18
25
250 Vac
10
22
CURRENT IN MULTIPLES OF I
n
CURRENT IN MULTIPLES OF I
n
Notes:
1 8 6 9 7 5 4 3 2 1 0 8 0 60 90 70 50 40 30 20
1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
1 8 6 9 7 5 4 3 2 1 0 8 0 60 90 70 50 40 30 20 1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
1
2
3
4



36
Trip Curves TC01200002E
Effective May 2009
Series C F-frame circuit breaker
time current curves

EATON CORPORATION www.eaton.com
Figure 34. Types ED, EDH, EDC, EDB, and EDS 175225ACurve No. SC-5805-94A
1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
80 60 90 70 50 40 30 20
Interrupting
rating
determines
end of curve
(see above)
Total clearing time
Minimum Maximum
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
T
IM
E
IN
S
E
C
O
N
D
S
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
T
IM
E
IN
S
E
C
O
N
D
S
10,000
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
CURRENT IN MULTIPLES OF I n
10 1
Circuit breaker time/current curves
Series C

F-frame circuit breakers


Catalog types ED, EDB, EDS, EDH and EDC circuit breakers, two- and
For application and coordination purposes only.
Based on 40C ambient, cold start. Connected with four (4) feet of
rated wire (75C) per terminal. Tested in open air with current in all
poles.
Maximum Vac: 240 at 50/60 Hz
Maximum Vdc: 125
Breaker rating
Continuous amperes Instantaneous trip amperes
175, 200, 225A See curve
CURRENT IN MULTIPLES OF I n
1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
80 60 90 70 50 40 30 20 8 6 9 7 5 4 3 2
10 1 8 6 9 7 5 4 3 2
Interrupting rating (UL/CSA listed)
Breaker
Notes:
Single-pole test data at 25C based on NEMA procedures
(AB 4-2003) for verifying performances of molded case
circuit breakers.
Symmetrical Rms amperes (KA) Amps (KA)
type @ 240 Vac 125 Vdc
ED 65 10
EDH 100 10
EDC 200 10
EDB 22 10
EDS 42 10
three-poles.

Maximum single-
pole trip times
at 25C
37
Trip Curves TC01200002E
Effective May 2009
Series C F-frame circuit breaker
time current curves

EATON CORPORATION www.eaton.com
Figure 35. Type FDC 15ACurve No. SC-5516-93A
.02
.01
.005
.003
.002
1
0
0
,0
0
0
8
0
,0
0
0
6
0
,0
0
0
9
0
,0
0
0
7
0
,0
0
0
5
0
,0
0
0
4
0
,0
0
0
3
0
,0
0
0
2
0
,0
0
0
1
0
,0
0
0
2
0
0
,0
0
0
Minimum
Maximum single-
pole trip times
at 25C 1
Maximum interrupting time
15A
Interrupting
rating
determines
end of curve
(see above)
240V
480V
600V
Maximum
1
Breaker
type
Symmetrical Rms amperes (KA) Amps (KA)
@ 240 Vac @ 480 Vac @ 600 Vac 250 Vdc
200 FDC 100 35 22
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
T
I
M
E
I
N
S
E
C
O
N
D
S
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
CURRENT IN AMPERES
1
0
0
0
0
8
0
0
0
6
0
0
0
9
0
0
0
7
0
0
0
5
0
0
0
4
0
0
0
3
0
0
0
2
0
0
0
1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
80 60 90 70 50 40 30 20 10 9 8 7 5 6
T
I
M
E
I
N
S
E
C
O
N
D
S
10,000
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
CURRENT IN AMPERES
1
0
0
0
0
8
0
0
0
6
0
0
0
9
0
0
0
7
0
0
0
5
0
0
0
4
0
0
0
3
0
0
0
2
0
0
0
1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
80 60 90 70 50 40 30 20 10 9 8 7 5 6
Circuit breaker time/current curves
Series C

F-frame circuit breakers


Catalog type FDC circuit breaker, two-, three- and four-poles.
For application and coordination purposes only.
Based on 40C ambient, cold start. Connected with four (4) feet of
rated wire (60C up to 125A, 75C above 125A) per terminal.
Tested in open air with current in all poles.
Maximum Vac: 600 at 50/60 Hz
Maximum Vdc: 250
Breaker rating
Continuous amperes Instantaneous trip amperes
15A See curve
Interrupting rating (UL/CSA listed)
Single-pole test data at 25C based on NEMA procedures
(AB 4-2003) for verifying performance of molded case
circuit breakers.
38
Trip Curves TC01200002E
Effective May 2009
Series C F-frame circuit breaker
time current curves

EATON CORPORATION www.eaton.com
Figure 36. Type FDC 20ACurve No. SC-5517-93A
Minimum
Maximum single-
pole trip times
at 25C 1
1
0
0
,0
0
0
8
0
,0
0
0
6
0
,0
0
0
9
0
,0
0
0
7
0
,0
0
0
5
0
,0
0
0
4
0
,0
0
0
3
0
,0
0
0
2
0
,0
0
0
1
0
,0
0
0
2
0
0
,0
0
0
.02
.01
.005
.003
.002
240V
600V
480V
Maximum interrupting time
Maximum
20A
1
Breaker
type
Symmetrical Rms amperes (KA) Amps (KA)
@ 240 Vac @ 480 Vac @ 600 Vac 250 Vdc
200 FDC 100 35 22
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
T
I
M
E
I
N
S
E
C
O
N
D
S
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
CURRENT IN AMPERES
1
0
0
0
0
8
0
0
0
6
0
0
0
9
0
0
0
7
0
0
0
5
0
0
0
4
0
0
0
3
0
0
0
2
0
0
0
1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
80 60 90 70 50 40 30 20 10 9 8 7 5 6
T
I
M
E
I
N
S
E
C
O
N
D
S
10,000
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
CURRENT IN AMPERES
1
0
0
0
0
8
0
0
0
6
0
0
0
9
0
0
0
7
0
0
0
5
0
0
0
4
0
0
0
3
0
0
0
2
0
0
0
1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
80 60 90 70 50 40 30 20 10 9 8 7 5 6
Interrupting
rating
determines
end of curve
(see above)
Circuit breaker time/current curves
Series C

F-frame circuit breakers


Catalog type FDC circuit breaker, two-, three- and four-poles.
For application and coordination purposes only.
Based on 40C ambient, cold start. Connected with four (4) feet of
rated wire (60C up to 125A, 75C above 125A) per terminal.
Tested in open air with current in all poles.
Maximum Vac: 600 at 50/60 Hz
Maximum Vdc: 250
Breaker rating
Continuous amperes Instantaneous trip amperes
20A See curve
Interrupting rating (UL/CSA listed)
Single-pole test data at 25C based on NEMA procedures
(AB 4-2003) for verifying performance of molded case
circuit breakers.
39
Trip Curves TC01200002E
Effective May 2009
Series C F-frame circuit breaker
time current curves

EATON CORPORATION www.eaton.com
Figure 37. Type FDC 25ACurve No. SC-5518-93A
Maximum interrupting time
Maximum single-
pole trip ti mes
at 25C 1
1
0
0
,0
0
0
8
0
,0
0
0
6
0
,0
0
0
9
0
,0
0
0
7
0
,0
0
0
5
0
,0
0
0
4
0
,0
0
0
3
0
,0
0
0
2
0
,0
0
0
1
0
,0
0
0
2
0
0
,0
0
0
.02
.01
.005
.003
.002
480V
240V
25A
Interrupting
rating
determines
end of curve
(see above)
600V
Maximum Minimum
1
Breaker
type
Symmetrical Rms amperes (KA) Amps (KA)
@ 240 Vac @ 480 Vac @ 600 Vac 250 Vdc
200 FDC 100 35 22
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
T
I
M
E
I
N
S
E
C
O
N
D
S
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
CURRENT IN AMPERES
1
0
0
0
0
8
0
0
0
6
0
0
0
9
0
0
0
7
0
0
0
5
0
0
0
4
0
0
0
3
0
0
0
2
0
0
0
1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
80 60 90 70 50 40 30 20 10 9 8 7 5 6
T
I
M
E
I
N
S
E
C
O
N
D
S
10,000
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
CURRENT IN AMPERES
1
0
0
0
0
8
0
0
0
6
0
0
0
9
0
0
0
7
0
0
0
5
0
0
0
4
0
0
0
3
0
0
0
2
0
0
0
1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
80 60 90 70 50 40 30 20 10 9 8 7 5 6
Circuit breaker time/current curves
Series C

F-frame circuit breakers


Catalog type FDC circuit breaker, two-, three- and four-poles.
For application and coordination purposes only.
Based on 40C ambient, cold start. Connected with four (4) feet of
rated wire (60C up to 125A, 75C above 125A) per terminal.
Tested in open air with current in all poles.
Maximum Vac: 600 at 50/60 Hz
Maximum Vdc: 250
Breaker rating
Continuous amperes Instantaneous trip amperes
25A See curve
Interrupting rating (UL/CSA listed)
Single-pole test data at 25C based on NEMA procedures
(AB 4-2003) for verifying performance of molded case
circuit breakers.
40
Trip Curves TC01200002E
Effective May 2009
Series C F-frame circuit breaker
time current curves

EATON CORPORATION www.eaton.com
Figure 38. Type FDC 30ACurve No. SC-5519-93A
Maximum interrupting time
Maximum single-
pole trip times
at 25C 1
1
0
0
,0
0
0
8
0
,0
0
0
6
0
,0
0
0
9
0
,0
0
0
7
0
,0
0
0
5
0
,0
0
0
4
0
,0
0
0
3
0
,0
0
0
2
0
,0
0
0
1
0
,0
0
0
2
0
0
,0
0
0
.02
.01
.005
.003
.002
480V
30A
Interrupting
rating
determines
end of curve
(see above)
240V
600V
Maximum Minimum
1
Breaker
type
Symmetrical Rms amperes (KA) Amps (KA )
@ 240 Vac @ 480 Vac @ 600 Vac 250 Vdc
200 FDC 100 35 22
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
T
I
M
E
I
N
S
E
C
O
N
D
S
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
CURRENT IN AMPERES
1
0
0
0
0
8
0
0
0
6
0
0
0
9
0
0
0
7
0
0
0
5
0
0
0
4
0
0
0
3
0
0
0
2
0
0
0
1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
80 60 90 70 50 40 30 20 10 9 8 7 5 6
T
I
M
E
I
N
S
E
C
O
N
D
S
10,000
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
CURRENT IN AMPERES
1
0
0
0
0
8
0
0
0
6
0
0
0
9
0
0
0
7
0
0
0
5
0
0
0
4
0
0
0
3
0
0
0
2
0
0
0
1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
80 60 90 70 50 40 30 20 10 9 8 7 5 6
Circuit breaker time/current curves
Series C

F-frame circuit breakers


Catalog type FDC circuit breaker, two-, three- and four-poles.
For application and coordination purposes only.
Based on 40C ambient, cold start. Connected with four (4) feet of
rated wire (60C up to 125A, 75C above 125A) per terminal.
Tested in open air with current in all poles.
Maximum Vac: 600 at 50/60 Hz
Maximum Vdc: 250
Breaker rating
Continuous amperes Instantaneous trip amperes
30A See curve
Interrupting rating (UL/CSA listed)
Single-pole test data at 25C based on NEMA procedures
(AB 4-2003) for verifying performance of molded case
circuit breakers.
41
Trip Curves TC01200002E
Effective May 2009
Series C F-frame circuit breaker
time current curves

EATON CORPORATION www.eaton.com
Figure 39. Type FDC 35ACurve No. SC-5520-93A
Minimum Maximum
Maximum interrupting time
1
0
0
,0
0
0
8
0
,0
0
0
6
0
,0
0
0
9
0
,0
0
0
7
0
,0
0
0
5
0
,0
0
0
4
0
,0
0
0
3
0
,0
0
0
2
0
,0
0
0
1
0
,0
0
0
2
0
0
,0
0
0
.02
.01
.005
.003
.002
600V
Maximum single-
pole trip times
at 25C 1
35A
Interrupting
rating
determines
end of curve
(see above)
480V
240V
1
Breaker
type
Symmetrical Rms amperes (KA) Amps (KA)
@ 240 Vac @ 480 Vac @ 600 Vac 250 Vdc
200 FDC 100 35 22
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
T
I
M
E
I
N
S
E
C
O
N
D
S
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
CURRENT IN AMPERES
1
0
0
0
0
8
0
0
0
6
0
0
0
9
0
0
0
7
0
0
0
5
0
0
0
4
0
0
0
3
0
0
0
2
0
0
0
1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
80 60 90 70 50 40 30 20 10 9 8 7 5 6
T
I
M
E
I
N
S
E
C
O
N
D
S
10,000
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
CURRENT IN AMPERES
1
0
0
0
0
8
0
0
0
6
0
0
0
9
0
0
0
7
0
0
0
5
0
0
0
4
0
0
0
3
0
0
0
2
0
0
0
1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
80 60 90 70 50 40 30 20 10 9 8 7 5 6
Circuit breaker time/current curves
Series C

F-frame circuit breakers


Catalog type FDC circuit breaker, two-, three- and four-poles.
For application and coordination purposes only.
Based on 40C ambient, cold start. Connected with four (4) feet of
rated wire (60C up to 125A, 75C above 125A) per terminal.
Tested in open air with current in all poles.
Maximum Vac: 600 at 50/60 Hz
Maximum Vdc: 250
Breaker rating
Continuous amperes Instantaneous trip amperes
35A See curve
Interrupting rating (UL/CSA listed)
Single-pole test data at 25C based on NEMA procedures
(AB 4-2003) for verifying performance of molded case
circuit breakers.
42
Trip Curves TC01200002E
Effective May 2009
Series C F-frame circuit breaker
time current curves

EATON CORPORATION www.eaton.com
Figure 40. Type FDC 40ACurve No. SC-5521-93A
Minimum Maximum
Maximum interrupting time
1
0
0
,0
0
0
8
0
,0
0
0
6
0
,0
0
0
9
0
,0
0
0
7
0
,0
0
0
5
0
,0
0
0
4
0
,0
0
0
3
0
,0
0
0
2
0
,0
0
0
1
0
,0
0
0
2
0
0
,0
0
0
.02
.01
.005
.003
.002
Maximum single-
pole trip times
at 25C 1
40A
Interrupting
rating
determines
end of curve
(see above)
480V
240V
600V
1
Breaker
type
Symmetrical Rms amperes (KA) Amps (KA)
@ 240 Vac @ 480 Vac @ 600 Vac 250 Vdc
200 FDC 100 35 22
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
T
I
M
E
I
N
S
E
C
O
N
D
S
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
CURRENT IN AMPERES
1
0
0
0
0
8
0
0
0
6
0
0
0
9
0
0
0
7
0
0
0
5
0
0
0
4
0
0
0
3
0
0
0
2
0
0
0
1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
80 60 90 70 50 40 30 20 10 9 8 7 5 6
T
I
M
E
I
N
S
E
C
O
N
D
S
10,000
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
CURRENT IN AMPERES
1
0
0
0
0
8
0
0
0
6
0
0
0
9
0
0
0
7
0
0
0
5
0
0
0
4
0
0
0
3
0
0
0
2
0
0
0
1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
80 60 90 70 50 40 30 20 10 9 8 7 5 6
Circuit breaker time/current curves
Series C

F-frame circuit breakers


Catalog type FDC circuit breaker, two-, three- and four-poles.
For application and coordination purposes only.
Based on 40C ambient, cold start. Connected with four (4) feet of
rated wire (60C up to 125A, 75C above 125A) per terminal.
Tested in open air with current in all poles.
Maximum Vac: 600 at 50/60 Hz
Maximum Vdc: 250
Breaker rating
Continuous amperes Instantaneous trip amperes
40A See curve
Interrupting rating (UL/CSA listed)
Single-pole test data at 25C based on NEMA procedures
(AB 4-2003) for verifying performance of molded case
circuit breakers.
43
Trip Curves TC01200002E
Effective May 2009
Series C F-frame circuit breaker
time current curves

EATON CORPORATION www.eaton.com
Figure 41. Type FDC 45ACurve No. SC-5522-93A
Minimum Maximum
Maximum interrupting time
1
0
0
,0
0
0
8
0
,0
0
0
6
0
,0
0
0
9
0
,0
0
0
7
0
,0
0
0
5
0
,0
0
0
4
0
,0
0
0
3
0
,0
0
0
2
0
,0
0
0
1
0
,0
0
0
2
0
0
,0
0
0
.02
.01
.005
.003
.002
Maximum single-
pole trip times
at 25C 1
45A
Interrupting
rating
determines
end of curve
(see above)
480V
240V
600V
1
Breaker
type
Symmetrical Rms amperes (KA) Amps (KA)
@ 240 Vac @ 480 Vac @ 600 Vac 250 Vdc
200 FDC 100 35 22
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
T
I
M
E
I
N
S
E
C
O
N
D
S
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
CURRENT IN AMPERES
1
0
0
0
0
8
0
0
0
6
0
0
0
9
0
0
0
7
0
0
0
5
0
0
0
4
0
0
0
3
0
0
0
2
0
0
0
1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
80 60 90 70 50 40 30 20 10 9 8 7 5 6
T
I
M
E
I
N
S
E
C
O
N
D
S
10,000
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
CURRENT IN AMPERES
1
0
0
0
0
8
0
0
0
6
0
0
0
9
0
0
0
7
0
0
0
5
0
0
0
4
0
0
0
3
0
0
0
2
0
0
0
1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
80 60 90 70 50 40 30 20 10 9 8 7 5 6
Circuit breaker time/current curves
Series C

F-frame circuit breakers


Catalog type FDC circuit breaker, two-, three- and four-poles.
For application and coordination purposes only.
Based on 40C ambient, cold start. Connected with four (4) feet of
rated wire (60C up to 125A, 75C above 125A) per terminal.
Tested in open air with current in all poles.
Maximum Vac: 600 at 50/60 Hz
Maximum Vdc: 250
Breaker rating
Continuous amperes Instantaneous trip amperes
45A See curve
Interrupting rating (UL/CSA listed)
Single-pole test data at 25C based on NEMA procedures
(AB 4-2003) for verifying performance of molded case
circuit breakers.
44
Trip Curves TC01200002E
Effective May 2009
Series C F-frame circuit breaker
time current curves

EATON CORPORATION www.eaton.com
Figure 42. Type FDC 50Curve No. SC-5523-93A
Minimum Maximum
Maximum interrupting time
1
0
0
,0
0
0
8
0
,0
0
0
6
0
,0
0
0
9
0
,0
0
0
7
0
,0
0
0
5
0
,0
0
0
4
0
,0
0
0
3
0
,0
0
0
2
0
,0
0
0
1
0
,0
0
0
2
0
0
,0
0
0
.02
.01
.005
.003
.002
Maximum single-
pole trip times
at 25C 1
50A
Interrupting
rating
determines
end of curve
(see above)
240V
480V
600V
1
Breaker
type
Symmetrical Rms amperes (KA) Amps (KA)
@ 240 Vac @ 480 Vac @ 600 Vac 250 Vdc
200 FDC 100 35 22
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
T
I
M
E
I
N
S
E
C
O
N
D
S
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
CURRENT IN AMPERES
1
0
0
0
0
8
0
0
0
6
0
0
0
9
0
0
0
7
0
0
0
5
0
0
0
4
0
0
0
3
0
0
0
2
0
0
0
1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
80 60 90 70 50 40 30 20 10 9 8 7 5 6
T
I
M
E
I
N
S
E
C
O
N
D
S
10,000
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
CURRENT IN AMPERES
1
0
0
0
0
8
0
0
0
6
0
0
0
9
0
0
0
7
0
0
0
5
0
0
0
4
0
0
0
3
0
0
0
2
0
0
0
1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
80 60 90 70 50 40 30 20 10 9 8 7 5 6
Circuit breaker time/current curves
Series C

F-frame circuit breakers


Catalog type FDC circuit breaker, two-, three- and four-poles.
For application and coordination purposes only.
Based on 40C ambient, cold start. Connected with four (4) feet of
rated wire (60C up to 125A, 75C above 125A) per terminal.
Tested in open air with current in all poles.
Maximum Vac: 600 at 50/60 Hz
Maximum Vdc: 250
Breaker rating
Continuous amperes Instantaneous trip amperes
50A See curve
Interrupting rating (UL/CSA listed)
Single-pole test data at 25C based on NEMA procedures
(AB 4-2003) for verifying performance of molded case
circuit breakers.
45
Trip Curves TC01200002E
Effective May 2009
Series C F-frame circuit breaker
time current curves

EATON CORPORATION www.eaton.com
Figure 43. Type FDC 60ACurve No. SC-5524-93A
Maximum interrupting time
1
0
0
,0
0
0
8
0
,0
0
0
6
0
,0
0
0
9
0
,0
0
0
7
0
,0
0
0
5
0
,0
0
0
4
0
,0
0
0
3
0
,0
0
0
2
0
,0
0
0
1
0
,0
0
0
2
0
0
,0
0
0
.02
.01
.005
.003
.002
Maximum single-
pole trip times
at 25C 1
Maximum Minimum
60A
Interrupting
rating
determines
end of curve
(see above)
240V
480V
600V
1
Breaker
type
Symmetrical Rms amperes (KA) Amps (KA)
@ 240 Vac @ 480 Vac @ 600 Vac 250 Vdc
200 FDC 100 35 22
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
T
I
M
E
I
N
S
E
C
O
N
D
S
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
CURRENT IN AMPERES
1
0
0
0
0
8
0
0
0
6
0
0
0
9
0
0
0
7
0
0
0
5
0
0
0
4
0
0
0
3
0
0
0
2
0
0
0
1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
80 60 90 70 50 40 30 20 10 9 8 7 5 6
T
I
M
E
I
N
S
E
C
O
N
D
S
10,000
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
CURRENT IN AMPERES
1
0
0
0
0
8
0
0
0
6
0
0
0
9
0
0
0
7
0
0
0
5
0
0
0
4
0
0
0
3
0
0
0
2
0
0
0
1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
80 60 90 70 50 40 30 20 10 9 8 7 5 6
Circuit breaker time/current curves
Series C

F-frame circuit breakers


Catalog type FDC circuit breaker, two-, three- and four-poles.
For application and coordination purposes only.
Based on 40C ambient, cold start. Connected with four (4) feet of
rated wire (60C up to 125A, 75C above 125A) per terminal.
Tested in open air with current in all poles.
Maximum Vac: 600 at 50/60 Hz
Maximum Vdc: 250
Breaker rating
Continuous amperes Instantaneous trip amperes
60A See curve
Interrupting rating (UL/CSA listed)
Single-pole test data at 25C based on NEMA procedures
(AB 4-2003) for verifying performance of molded case
circuit breakers.
46
Trip Curves TC01200002E
Effective May 2009
Series C F-frame circuit breaker
time current curves

EATON CORPORATION www.eaton.com
Figure 44. Type FDC 70ACurve No. SC-5525-93A
Maximum Minimum
600V
480V
240V
Maximum single-
pole trip times
at 25C 1
70A
1
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
T
I
M
E
I
N
S
E
C
O
N
D
S
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
T
I
M
E
I
N
S
E
C
O
N
D
S
10,000
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
1
0
0
80 60 90 70 50 1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
0
0
8
0
0
0
6
0
0
0
9
0
0
0
7
0
0
0
5
0
0
0
4
0
0
0
3
0
0
0
2
0
0
0
1
0
0
,0
0
0
8
0
,0
0
0
6
0
,0
0
0
9
0
,0
0
0
7
0
,0
0
0
5
0
,0
0
0
4
0
,0
0
0
3
0
,0
0
0
2
0
,0
0
0
CURRENT IN AMPERES
1
0
0
0
0
8
0
0
0
6
0
0
0
9
0
0
0
7
0
0
0
5
0
0
0
4
0
0
0
3
0
0
0
2
0
0
0
1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
80 60 90 70 50
1
0
0
,0
0
0
8
0
,0
0
0
6
0
,0
0
0
9
0
,0
0
0
7
0
,0
0
0
5
0
,0
0
0
4
0
,0
0
0
3
0
,0
0
0
2
0
,0
0
0
2
0
0
,0
0
0
CURRENT IN AMPERES
Maximum interrupting ti me
Circuit breaker time/current curves
Series C

F-frame circuit breakers


Catalog type FDC circuit breaker, two-, three- and four-poles.
For application and coordination purposes only.
Based on 40C ambient, cold start. Connected with four (4) feet of
rated wire (60C up to 125A, 75C above 125A) per terminal.
Tested in open air with current in all poles.
Maximum Vac: 600 at 50/60 Hz
Maximum Vdc: 250
Breaker rating
Continuous amperes Instantaneous trip amperes
70A See curve
Interrupting rating (UL/CSA listed)
Single-pole test data at 25C based on NEMA procedures
(AB 4-2003) for verifying performance of molded case
circuit breakers.
Breaker
type
Symmetrical Rms amperes (KA) Amps (KA)
@ 240 Vac @ 480 Vac @ 600 Vac 250 Vdc
200 FDC 100 35 22
47
Trip Curves TC01200002E
Effective May 2009
Series C F-frame circuit breaker
time current curves

EATON CORPORATION www.eaton.com
Figure 45. Type FDC 80ACurve No. SC-5526-93A
Maximum Minimum
600V
480V
240V
Maximum single-
pole trip times
at 25C 1
80A
Maximum interrupting time
1
Breaker
type
Symmetrical Rms amperes (KA) Amps (KA)
@ 240 Vac @ 480 Vac @ 600 Vac 250 Vdc
200 FDC 100 35 22
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
T
I
M
E
I
N
S
E
C
O
N
D
S
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
T
I
M
E
I
N
S
E
C
O
N
D
S
10,000
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
1
0
0
80 60 90 70 50 1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
0
0
8
0
0
0
6
0
0
0
9
0
0
0
7
0
0
0
5
0
0
0
4
0
0
0
3
0
0
0
2
0
0
0
1
0
0
,0
0
0
8
0
,0
0
0
6
0
,0
0
0
9
0
,0
0
0
7
0
,0
0
0
5
0
,0
0
0
4
0
,0
0
0
3
0
,0
0
0
2
0
,0
0
0
CURRENT IN AMPERES
1
0
0
0
0
8
0
0
0
6
0
0
0
9
0
0
0
7
0
0
0
5
0
0
0
4
0
0
0
3
0
0
0
2
0
0
0
1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
80 60 90 70 50
1
0
0
,0
0
0
8
0
,0
0
0
6
0
,0
0
0
9
0
,0
0
0
7
0
,0
0
0
5
0
,0
0
0
4
0
,0
0
0
3
0
,0
0
0
2
0
,0
0
0
2
0
0
,0
0
0
CURRENT IN AMPERES
Circuit breaker time/current curves
Series C

F-frame circuit breaker


Catalog type FDC circuit breaker, two-, three- and four-poles.
For application and coordination purposes only.
Based on 40C ambient, cold start. Connected with four (4) feet of
rated wire (60C up to 125A, 75C above 125A) per terminal.
Tested in open air with current in all poles.
Maximum Vac: 600 at 50/60 Hz
Maximum Vdc: 250
Breaker rating
Continuous amperes Instantaneous trip amperes
80A See curve
Interrupting rating (UL/CSA listed)
Single-pole test data at 25C based on NEMA procedures
(AB 4-2003) for verifying performance of molded case
circuit breakers.
48
Trip Curves TC01200002E
Effective May 2009
Series C F-frame circuit breaker
time current curves

EATON CORPORATION www.eaton.com
Figure 46. Type FDC 90ACurve No. SC-5527-93A
Maximum single-
pole trip times
at 25C 1
100A
1
Breaker
type
Symmetrical Rms amperes (KA) Amps (KA)
@ 240 Vac @ 480 Vac @ 600 Vac 250 Vdc
200 FDC 100 35 22
600V
480V
240V
Maximum interrupting time
Maximum Minimum
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
T
I
M
E
I
N
S
E
C
O
N
D
S
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
T
I
M
E
I
N
S
E
C
O
N
D
S
10,000
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
1
0
0
80 60 90 70 50 1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
0
0
8
0
0
0
6
0
0
0
9
0
0
0
7
0
0
0
5
0
0
0
4
0
0
0
3
0
0
0
2
0
0
0
1
0
0
,0
0
0
8
0
,0
0
0
6
0
,0
0
0
9
0
,0
0
0
7
0
,0
0
0
5
0
,0
0
0
4
0
,0
0
0
3
0
,0
0
0
2
0
,0
0
0
CURRENT IN AMPERES
1
0
0
0
0
8
0
0
0
6
0
0
0
9
0
0
0
7
0
0
0
5
0
0
0
4
0
0
0
3
0
0
0
2
0
0
0
1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
80 60 90 70 50
1
0
0
,0
0
0
8
0
,0
0
0
6
0
,0
0
0
9
0
,0
0
0
7
0
,0
0
0
5
0
,0
0
0
4
0
,0
0
0
3
0
,0
0
0
2
0
,0
0
0
2
0
0
,0
0
0
CURRENT IN AMPERES
Circuit breaker time/current curves
Series C

F-frame circuit breakers


Catalog type FDC circuit breaker, two-, three- and four-poles.
For application and coordination purposes only.
Based on 40C ambient, cold start. Connected with four (4) feet of
rated wire (60C up to 125A, 75C above 125A) per terminal.
Tested in open air with current in all poles.
Maximum Vac: 600 at 50/60 Hz
Maximum Vdc: 250
Breaker rating
Continuous amperes Instantaneous trip amperes
100A See curve
Interrupting rating (UL/CSA listed)
Single-pole test data at 25C based on NEMA procedures
(AB 4-2003) for verifying performance of molded case
circuit breakers.
49
Trip Curves TC01200002E
Effective May 2009
Series C F-frame circuit breaker
time current curves

EATON CORPORATION www.eaton.com
Figure 47. Type FDC 100ACurve No. SC-5528-93A
Maximum single-
pole trip times
at 25C 1
100A
1
Breaker
type
Symmetrical Rms amperes (KA) Amps (KA)
@ 240 Vac @ 480 Vac @ 600 Vac 250 Vdc
200 FDC 100 35 22
600V
480V
240V
Maximum interrupting time
Maximum Minimum
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
T
I
M
E
I
N
S
E
C
O
N
D
S
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
T
I
M
E
I
N
S
E
C
O
N
D
S
10,000
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
1
0
0
80 60 90 70 50 1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
0
0
8
0
0
0
6
0
0
0
9
0
0
0
7
0
0
0
5
0
0
0
4
0
0
0
3
0
0
0
2
0
0
0
1
0
0
,0
0
0
8
0
,0
0
0
6
0
,0
0
0
9
0
,0
0
0
7
0
,0
0
0
5
0
,0
0
0
4
0
,0
0
0
3
0
,0
0
0
2
0
,0
0
0
CURRENT IN AMPERES
1
0
0
0
0
8
0
0
0
6
0
0
0
9
0
0
0
7
0
0
0
5
0
0
0
4
0
0
0
3
0
0
0
2
0
0
0
1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
80 60 90 70 50
1
0
0
,0
0
0
8
0
,0
0
0
6
0
,0
0
0
9
0
,0
0
0
7
0
,0
0
0
5
0
,0
0
0
4
0
,0
0
0
3
0
,0
0
0
2
0
,0
0
0
2
0
0
,0
0
0
CURRENT IN AMPERES
Circuit breaker time/current curves
Series C

F-frame circuit breakers


Catalog type FDC circuit breaker, two-, three- and four-poles.
For application and coordination purposes only.
Based on 40C ambient, cold start. Connected with four (4) feet of
rated wire (60C up to 125A, 75C above 125A) per terminal.
Tested in open air with current in all poles.
Maximum Vac: 600 at 50/60 Hz
Maximum Vdc: 250
Breaker rating
Continuous amperes Instantaneous trip amperes
100A See curve
Interrupting rating (UL/CSA listed)
Single-pole test data at 25C based on NEMA procedures
(AB 4-2003) for verifying performance of molded case
circuit breakers.
50
Trip Curves TC01200002E
Effective May 2009
Series C F-frame circuit breaker
time current curves

EATON CORPORATION www.eaton.com
Figure 48. Type FDC 110ACurve No. SC-5529-93A
Maximum single-
pole trip times
at 25C 1
110A
1
Breaker
type
Symmetrical Rms amperes (KA) Amps (KA)
@ 240 Vac @ 480 Vac @ 600 Vac 250 Vdc
200 FDC 100 35 22
600V
480V
240V
Maximum interrupting time
Maximum Minimum
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
T
I
M
E
I
N
S
E
C
O
N
D
S
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
T
I
M
E
I
N
S
E
C
O
N
D
S
10,000
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
1
0
0
80 60 90 70 50 1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
0
0
8
0
0
0
6
0
0
0
9
0
0
0
7
0
0
0
5
0
0
0
4
0
0
0
3
0
0
0
2
0
0
0
1
0
0
,0
0
0
8
0
,0
0
0
6
0
,0
0
0
9
0
,0
0
0
7
0
,0
0
0
5
0
,0
0
0
4
0
,0
0
0
3
0
,0
0
0
2
0
,0
0
0
CURRENT IN AMPERES
1
0
0
0
0
8
0
0
0
6
0
0
0
9
0
0
0
7
0
0
0
5
0
0
0
4
0
0
0
3
0
0
0
2
0
0
0
1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
80 60 90 70 50
1
0
0
,0
0
0
8
0
,0
0
0
6
0
,0
0
0
9
0
,0
0
0
7
0
,0
0
0
5
0
,0
0
0
4
0
,0
0
0
3
0
,0
0
0
2
0
,0
0
0
2
0
0
,0
0
0
CURRENT IN AMPERES
Circuit breaker time/current curves
Series C

F-frame circuit breakers


Catalog type FDC circuit breaker, two-, three- and four-poles.
For application and coordination purposes only.
Based on 40C ambient, cold start. Connected with four (4) feet of
rated wire (60C up to 125A, 75C above 125A) per terminal.
Tested in open air with current in all poles.
Maximum Vac: 600 at 50/60 Hz
Maximum Vdc: 250
Breaker rating
Continuous amperes Instantaneous trip amperes
110A See curve
Interrupting rating (UL/CSA listed)
Single-pole test data at 25C based on NEMA procedures
(AB 4-2003) for verifying performance of molded case
circuit breakers.
51
Trip Curves TC01200002E
Effective May 2009
Series C F-frame circuit breaker
time current curves

EATON CORPORATION www.eaton.com
Figure 49. Type FDC 125ACurve No. SC-5530-93A
Maximum Minimum
Maximum single-
pole trip ti mes
at 25C 1
125A
1
Breaker
type
Symmetrical Rms amperes (KA) Amps (KA)
@ 240 Vac @ 480 Vac @ 600 Vac 250 Vdc
200 FDC 100 35 22
600V
480V
240V
Maximum interrupting time
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
T
I
M
E
I
N
S
E
C
O
N
D
S
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
T
I
M
E
I
N
S
E
C
O
N
D
S
10,000
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
1
0
0
80 60 90 70 50 1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
0
0
8
0
0
0
6
0
0
0
9
0
0
0
7
0
0
0
5
0
0
0
4
0
0
0
3
0
0
0
2
0
0
0
1
0
0
,0
0
0
8
0
,0
0
0
6
0
,0
0
0
9
0
,0
0
0
7
0
,0
0
0
5
0
,0
0
0
4
0
,0
0
0
3
0
,0
0
0
2
0
,0
0
0
CURRENT IN AMPERES
1
0
0
0
0
8
0
0
0
6
0
0
0
9
0
0
0
7
0
0
0
5
0
0
0
4
0
0
0
3
0
0
0
2
0
0
0
1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
80 60 90 70 50
1
0
0
,0
0
0
8
0
,0
0
0
6
0
,0
0
0
9
0
,0
0
0
7
0
,0
0
0
5
0
,0
0
0
4
0
,0
0
0
3
0
,0
0
0
2
0
,0
0
0
2
0
0
,0
0
0
CURRENT IN AMPERES
Circuit breaker time/current curves
Series C

F-frame circuit breakers


Catalog type FDC circuit breaker, two-, three- and four-poles.
For application and coordination purposes only.
Based on 40C ambient, cold start. Connected with four (4) feet of
rated wire (60C up to 125A, 75C above 125A) per terminal.
Tested in open air with current in all poles.
Maximum Vac: 600 at 50/60 Hz
Maximum Vdc: 250
Breaker rating
Continuous amperes Instantaneous trip amperes
125A See curve
Interrupting rating (UL/CSA listed)
Single-pole test data at 25C based on NEMA procedures
(AB 4-2003) for verifying performance of molded case
circuit breakers.
52
Trip Curves TC01200002E
Effective May 2009
Series C F-frame circuit breaker
time current curves

EATON CORPORATION www.eaton.com
Figure 50. Type FDC 150ACurve No. SC-5531-93A
Maximum Minimum
Maximum single-
pole trip times
at 25C 1
150A
1
Breaker
type
Symmetrical Rms amperes (KA) Amps (KA)
@ 240 Vac @ 480 Vac @ 600 Vac 250 Vdc
200 FDC 100 35 22
600V
480V
240V
Maximum interrupting ti me
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
T
I
M
E
I
N
S
E
C
O
N
D
S
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
T
I
M
E
I
N
S
E
C
O
N
D
S
10,000
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
1
0
0
80 60 90 70 50 1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
0
0
8
0
0
0
6
0
0
0
9
0
0
0
7
0
0
0
5
0
0
0
4
0
0
0
3
0
0
0
2
0
0
0
1
0
0
,0
0
0
8
0
,0
0
0
6
0
,0
0
0
9
0
,0
0
0
7
0
,0
0
0
5
0
,0
0
0
4
0
,0
0
0
3
0
,0
0
0
2
0
,0
0
0
CURRENT IN AMPERES
1
0
0
0
0
8
0
0
0
6
0
0
0
9
0
0
0
7
0
0
0
5
0
0
0
4
0
0
0
3
0
0
0
2
0
0
0
1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
80 60 90 70 50
1
0
0
,0
0
0
8
0
,0
0
0
6
0
,0
0
0
9
0
,0
0
0
7
0
,0
0
0
5
0
,0
0
0
4
0
,0
0
0
3
0
,0
0
0
2
0
,0
0
0
2
0
0
,0
0
0
CURRENT IN AMPERES
Circuit breaker time/current curves
Series C

F-frame circuit breakers


Catalog type FDC circuit breaker, two-, three- and four-poles.
For application and coordination purposes only.
Based on 40C ambient, cold start. Connected with four (4) feet of
rated wire (60C up to 125A, 75C above 125A) per terminal.
Tested in open air with current in all poles.
Maximum Vac: 600 at 50/60 Hz
Maximum Vdc: 250
Breaker rating
Continuous amperes Instantaneous trip amperes
150A See curve
Interrupting rating (UL/CSA listed)
Single-pole test data at 25C based on NEMA procedures
(AB 4-2003) for verifying performance of molded case
circuit breakers.
53
Trip Curves TC01200002E
Effective May 2009
Series C F-frame circuit breaker
time current curves

EATON CORPORATION www.eaton.com
Figure 51. Type FDC 175225ACurve No. SC-6971-98
Maximum single-
pole trip times
at 25C
Maximum
trip time
Minimum
trip time
175 A
200 A
225 A
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
T
I
M
E
I
N
S
E
C
O
N
D
S
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
T
I
M
E
I
N
S
E
C
O
N
D
S
10,000
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
1,000
500
300
200
5,000
3,000
2,000
1

H
O
U
R
1

M
I
N
U
T
E
2

H
O
U
R
S
175225A
Circuit breaker time/current curves
molded-case circuit breakers
Catalog types FD/HFD circuit breakers, two-, three- and four-poles.
For application and coordination purposes only.
Based on 40C ambient, cold start. Connected with four (4) feet of rated
wire (75C) per terminal. Tested in open air with current in all poles.
Maximum Vac: 600 at 50/60 Hz
Maximum Vdc: 250
Breaker rating
I
n
amperes Instantaneous pick-up, amperes Rms
175 2400
200 2400
225 2400
Breaker
type
Symmetrical Rms amperes (kA), I
cu
FD
HFD
Fixed inverse time overcurrent release.
Single-pole test data at 25 C based on NEMA procedures (AB 4-2003)
for verifying performances of molded case circuit breakers.
Total operation time.
terrupting rating determines end of curve.
In this interruption region:
The curve is drawn for I
n
= 200A. For I
n
200A, the end points in this
region are displaced along the current-axis by a factor (200A/I
n
)
240 Vac
Interrupting ratings
65
100
480 Vac
35
65
600 Vac
18
25
250 Vac
10
22
CURRENT IN MULTIPLES OF I
n
CURRENT IN MULTIPLES OF I
n
Notes:
1 8 6 9 7 5 4 3 2 1 0 8 0 60 90 70 50 40 30 20
1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
1 8 6 9 7 5 4 3 2 1 0 8 0 60 90 70 50 40 30 20 1
0
0
0
8
0
0
6
0
0
9
0
0
7
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
1
2
3
4



54
Trip Curves TC01200002E
Effective May 2009
Series C F-frame circuit breaker
time current curves

EATON CORPORATION www.eaton.com
Figure 52. Types FDE, HFDE, and FDCE 225ALong/Short Delay
.01
1
2
3
4
5
6
7
8
9
10
20
30
40
50
60
70
80
90
100
1000
900
800
700
600
500
400
300
200
2000
3000
4000
5000
6000
7000
8000
9000
10000
.02
.03
.04
.05
.06
.07
.08
.09
.1
.2
.3
.4
.5
.6
.7
.8
.9
1
3
4
5
6
7
8
9
10
20
30
40
50
60
70
80
90
100
1000
900
800
700
600
500
400
300
200
2000
3000
4000
5000
6000
7000
8000
9000
10000
1
M
I N
U
T
E
2
H
O
U
R
S
T
I
M
E
I
N
S
E
C
O
N
D
S
1
H
O
U
R
.01
.02
.03
.04
.05
.06
.07
.08
.09
.1
.2
.3
.4
.5
.6
.7
.8
.9
1
Available long delay time:
2,4,7,10,12,15,20,24 sec.
Shown @ 6x
2,4,7,15,24 seconds
+0 / 30%
I
r
T
I
M
E
I
N
S
E
C
O
N
D
S
Available short delay
pick up settings
28,10, x 5% 12 I
r
(See Note 7)
2
FDE
Circuit breaker time/current curves (phase current)
Long delay (LD) and short delay (SD) with fat response
: I Available sensors ( )
n
80A
160A
225A
Current in Multiples of (I ) r
Current in Multiples of (I ) r
1 2 3 4 5 7 10 20 30 40 50 70 100 2 3 4 5 7 10 20 30 40 50 70 100 .5 .7
1 2 3 4 5 7 10 20 30 .5 .7
Types FDE, FDCE, HFDE circuit breakers
8
Current in Multiples of (I ) n
Long delay response and short delay with fat response curve
12
10
4
.
.24
6
3
1.15
Notes:
Application determines
end of curve
Instantaneous
override (see Note 8)
7
.
5
.
300 ms
(P,Q,R)
120 ms
(M,N,O)
Inst.
(J,K,L)
15
7
.4
2
12 Ii
1. Curve accuracy applies from 20C to +55C ambient. Temperatures above +85C cause an over-
temperature protection trip. For possible continuous ampere dertaing for ambient above 40C,
refer to Eaton.
2. Application frequency is 50/60 Hz.
3. There is a memory effect that can act to shorten the long delay. The memory effect comes into play
if a current above the long delay pick up value exists for a time and then is cleared by the tripping of
a down stream device or the circuit breaker itself. A subsequent overload will cause the circuit breaker
to tripin shorter time than normal. The amount of time delay reduction is inverse to the amount of
time that has elapsed since the previous overload. Approximately five minutes is required between
overloads tocompletely reset memory.
4. The right portion of the curve is determined by the interrupting rating of the circuit breaker.
The left portion of the curve is shown as a multiple of the long delay setting.
(long delay pick up = 115% of I ). Range is 110%120%.
6. Total clearing times shown include the response times of the trip unit, the breaker opening, and the
interruption of the current.
7. The short delay pick up has nine settings/positions, 28, 10, 12.
8. For high fault current levels an additional fixed instantaneous hardware override is provided
(corresponding to SDPU position 9) at 12x (I ) and designated as 12I . Instantaneous tolerance is +/20%.
9. For LD response and SD with flat response (this curve): TC01203015E
10. For LD response and SD with I T response curve, see: TC01203016E
11. For ground fault delay response curve, see: TC01203017E
12. Digitrip RMS 310+ trip units are suitable for functional field testing with test kit Cat. No. MTST120V.
For field testing using primary injection methods, follow NEMA publication AB 4-2003.
2
n
n
Maximum total
clearing time
Minimum total
clearing time
I 80A 160A 225A I
A
B
C
D
E
F
G
H
15A
20A
30A
40A
50A
60A
70A
80A
60A
70A
80A
90A
100A
125A
150A
160A
100A
110A
125A
150A
160A
175A
200A
225A
i
Breaker
type
Symmetrical RMS amperes (kA) UL/CSA
FDE
HFDE
FDCE
240 V
Interrupting ratings50/60 Hz
65
100
200
480 V
35
65
100
600 V
18
25
35
r n
55
Trip Curves TC01200002E
Effective May 2009
Series C F-frame circuit breaker
time current curves

EATON CORPORATION www.eaton.com
Figure 53. Types FDE, HFDE, and FDCE 225ALong Short Delay and I
2
t
.01
1
2
3
4
5
6
7
8
9
10
20
30
40
50
60
70
80
90
100
1000
900
800
700
600
500
400
300
200
2000
3000
4000
5000
6000
7000
8000
9000
10000
.02
.03
.04
.05
.06
.07
.08
.09
.1
.2
.3
.4
.5
.6
.7
.8
.9
1
3
4
5
6
7
8
9
10
20
30
40
50
60
70
80
90
100
1000
900
800
700
600
500
400
300
200
2000
3000
4000
5000
6000
7000
8000
9000
10000
1
M
I N
U
T
E
2
H
O
U
R
S
T
I
M
E
I
N
S
E
C
O
N
D
S
1
H
O
U
R
.01
.02
.03
.04
.05
.06
.07
.08
.09
.1
.2
.3
.4
.5
.6
.7
.8
.9
1
Maximum total
clearing time
Available long delay t ime:
2,4,7,10,12,15,20,24 sec.
Shown @ 6x
2,4,7,15,24 seconds
+0 / 30%
I
r
2
T
I
M
E
I
N
S
E
C
O
N
D
S
Application determines
end of curve
Available short delay
pick up settings
28,10, x 5% 12 I
r
(see Note 7)
2
Instantaneous
override (see Note 10)
FDE
Circuit breaker time/current curves (phase current)
Long delay (LD) and short delay (SD) with I T response
2
Available sensors( ) : I
n
80A
160A
225A
Current in Multiples of ( I ) r
Current in Multiples of ( ) I
r
1 2 3 4 5 7 10 20 30 40 50 70 100 2 3 4 5 7 10 20 30 40 50 70 100 .5 .7
1 2 3 4 5 7 10 20 30 .5 .7
Types FDE, FDCE, HFDE circuit breakers
8
Current in Multiples of ( I ) n
Notes:
1. Curve accuracy applies from 20C to +55C ambient. Temperatures above +85C cause an over-
temperature protection trip. For possible continuous ampere derating for ambient above 40C, refer
to Eaton.
2. Application frequency is 50/60 Hz.
4. The right portion of the curve is determined by the interrupting rating of the circuit breaker.
5. The left portion of the curve is shown as a multiple of the long delay setting
(Long delay pick up = 115% of ). Range is 110%120%.
7. The short delay pick up has nine settings/positions: 28, 10, 12.
9. Breakpoint back to FLAT response occurs @ 8x for upper line of the I T curve.
10. For high fault current levels an additional fxed instantaneous hardware override is provided
(corresponding to SDPU position nine) at 12x and designated as 12 . Instant aneous tolerance is +/20%.
11. For LD response and SD with fat response curve, see: TC01203015E
12. For LD response and SD with I T response (this curve):
13. For ground fault delay response curve, see: TC01203017E
I
I
( I ) I
r
r
n
2
2
TC01203016E
Long Delay Response and Short Delay with I T Response Curve
2
12
I T
2
short delay
(see Note 8)
Minimum total
clearing time
10
7
5
4
.
.4
.
.
.24
6
.
3
1.15
See Note 9
12 Ii
67ms
15
7
I 80A 160A 225A
A 15A 60A 100A
B 20A 70A 10A
C 30A 80A 125A
D 40A 90A 150A
E 50A 100A 160A
F 60A 125A 175A
G 70A 150A 200A
H 80A 160A 225A
I
6. Total clearing times shown include the response times of the trip unit, the breaker opening, and the
interruption of the current.
2
8. Short delay I T band has a tolerance of +/15%.
Breaker
type
Symmetrical RMS amperes (kA) UL/CSA
FDE
HFDE
FDCE
240 V
Interrupting ratings50/60 Hz
65
100
200
480 V
35
65
100
600 V
18
25
35
3. There is a memory efect that can act to shroten the long delay. The memory efect comes into play
if a current above the long delay pick up value exists for a time and then is cleared by the tripping of a
down stream device or the circuit breaker itself. A subsequent overload will cause the circuit breaker to trip
in shorter time than normal. The amount of time delay reduction is inverse to the amount of time that
has elapsed since the previous overload. Approximately fve minutes is required between overloads to
completely reset memory.
i
14. Digitrip RMS 310+ trip units are suitable for functional feld testing with test kit Cat. No MTST120V.
For feld testing using primary injection methods, follow NEMA publication AB 4-2003.
r n
Eaton Corporation
Electrical Group
1000 Cherrington Parkway
Moon Township, PA 15108
United States
877-ETN-CARE (877-386-2273)
Eaton.com
2009 Eaton Corporation
All Rights Reserved
Printed in USA
Publication No. TC01200002E / Z8320
May 2009
PowerChain Management is a registered
trademark of Eaton Corporation.
All other trademarks are property of their
respective owners.
Trip Curves TC01200002E
Effective May 2009
Series C F-frame circuit breaker
time current curves

Figure 54. Types FDE, HFDE, and FDCE 225ALSIG
.01
2
3
4
5
6
8
10
20
30
40
50
60
70
80
90
100
1000
900
800
700
600
500
400
300
200
.02
.03
.04
.05
.06
.07
.08
.09
.1
.2
.3
.4
.5
.6
.7
.8
.9
1
7
9
2000
3000
4000
5000
6000
7000
8000
9000
10000
1
M
I N
U
T
E
S
D
N
O
C
E
S
N
I
E
M
I
T
.1 .2 .3 .4 .5 .7 1.0 2.0
.1 .2 .3 .4 .5 .7 1.0 2.0
FDE
10%)
.4X
120ms
(K,N,Q)
300ms
(L,O,R)
Inst.
(J,M,P)
.3X
.2X 1X .6X
.8X
Switch
Setting
J
K
L
M
N
O
P
Q
R
t
SD
Inst.
Inst.
Inst.
120
120
120
300
300
300
t
GF
Inst.
120
300
Inst.
120
300
Inst.
120
300
LSG
LSIG
In 80A 160A 225A
A 15A 60A 100A
B 20A 70A 110A
C 30A 80A 125A
D 40A 90A 150A
E 50A 100A 160A
F 60A 125A 175A
G 70A 150A 200A
H 80A 160A 225A
Ir
Note:
1. Cuve accuracy applies from 20C to +55C ambient. Temperatures above +85C cause an over-
temperature protection trip. For possible continuous ampere derating for ambient above 40C,
refer to Eaton.
2. Application frequency is 50/60 Hz.
3. Trip units are suitable for functional field testing with test kit style # 70C1056G52.
4. For LD response and SD with flat response curve, see: TC01203015E
5. For LD response and SD with I T response curve, see: TC01203016E
6. For ground fault delay response (this curve): TC01203017E
I
n
Ground current in multiple of ( )
Ground fault pickup settings
(tolerance
Ground fault delay response curve
Circuit breaker time/current curves (ground current)
Types FDE, FDCE, HFDE industrail circuit breakers
Ground fault delay response