Rotor recognized after 10 measurements. - no starting magnet (SM+L1) recognized when calculating the rotational speed. - Rational speed for the measurement is not reached, abortion after 12 sec. The motor or the frequency converter could be defective. - check / replace motor cap incl. Speed sensor, check connections. - replace "control" PCB, check connections at plug X10.
Rotor recognized after 10 measurements. - no starting magnet (SM+L1) recognized when calculating the rotational speed. - Rational speed for the measurement is not reached, abortion after 12 sec. The motor or the frequency converter could be defective. - check / replace motor cap incl. Speed sensor, check connections. - replace "control" PCB, check connections at plug X10.
Rotor recognized after 10 measurements. - no starting magnet (SM+L1) recognized when calculating the rotational speed. - Rational speed for the measurement is not reached, abortion after 12 sec. The motor or the frequency converter could be defective. - check / replace motor cap incl. Speed sensor, check connections. - replace "control" PCB, check connections at plug X10.
3 Error lists / Troubleshooting Error list 58XX Display Cause Remedy Error 1 Error in measurement system for rotational speed. No rotor recognized after 10 measurements. No starting magnet (SM+L1) recognized when calculating the rotational speed. Rational speed for the measurement is not reached, abortion after 12 sec. The motor or the frequency converter could be defective. The time for one rotation is < 4 ms (errors). Device brakes. After repair: False connection of cable U2/V2/W2 from motor to converter. Check the rotational system on the rotor. Service program 8. Check/replace motor cap incl. speed sensor, check connections. Replace "Control" PCB, check connections at plug X10. Service program 9 converter motor run. Customer service program 9 Check connections. MSTM/0408 Centrifuge 5804/5804 R and 5810/5810 R 3 Error lists / Troubleshooting 3-2 Error lists/Troubleshooting Error 2 Imbalance sensor is defective. The idle value is outside of the limits or the measuring value is absolutely incor- rect. Error occurs only if an incorrect idle value is applied for at least 3 sec. Device does not start or brake. The old Imbalance-recognition PCB is still in use (cable colors at plug X 10: white/black/red/blue). Is the customers rotor damaged or loaded asymmetrically? Is the centrifuge placed on a horizontal, stable and resonance-free work surface? Was the centrifuge moved and just put into operation? If so, let the centrifuge run at maximum speed. Is the sensor idle value stable and within the tolerance (670 100)? Adjust imbalance PCB and carry out imbalance adjustment. Replace imbalance PCB in case of no success. Was the imbalance PCB adjusted correctly after being replaced or after the motor being replaced? Following replacement of the motor, the PCB Imbalance or the PCB Control, was a fresh imbalance calibration performed? Was the correct rotor with the correct weighs used for an imbalance adjustment? Was the plug reconnected correctly to the PCB after a repair? Check plug X10. Use new Imbalance-recognition PCB from -02 onwards (cable colors at plug X 10: White/brown/green/yellow). Display Cause Remedy MSTM/0408 Error lists/Troubleshooting 3-3 Centrifuge 5804/5804 R and 5810/5810 R 3 Error lists / Troubleshooting Error 3 no rotor No rotor pulses during run or acceleration. Missing rotor, measuring system for rotational speed defective, drive defective. Rotor not fastened. No pulses after start. Device brakes for 10 sec. Pulse failure during run. Free deceler- ation requires 8 min! Error remains active after a power supply interruption. Software version 3.3 to 3.7 when using brake level "0" or "1". Fasten rotor. Keep device switched on and start again after > 12 min. Service program 8. Check the state of the rotational speed sensor and its connections, replace if necessary. Service program 9 Check converter, replace if necessary. Check motor, replace if necessary. Replace "Control" PCB, check connector X10 on PCB "Con- trol". Install software version as of 3.8. Error 4 Sensor for lid locking mechanism (Hall sensor, position recognition) defective. During run device brakes. At standstill with the lid closed, start is not possible. Service program 4. The voltage on the sensor should be approx. 2.5 V 0.2 V without the influence of a magnetic field ("Control 58XX" PCB). Check the sensor position. Error 5 No report from lid during run. Changed measuring value of Hall sensor. Device brakes, even when the lid is open. Service program 4. Check the fastening and the adjustment of the microswitches. Carry out a continuity check of the microswitches while they are closed. Check the state of the magnets on the junction plate. Display Cause Remedy MSTM/0408 Centrifuge 5804/5804 R and 5810/5810 R 3 Error lists / Troubleshooting 3-4 Error lists/Troubleshooting Error 6 Overload Undervoltage or overvoltage. Error in frequency converter (FC), thermal overload. Not ready after switching on the frequency converter. FC has carried out a RESET, caused by mains interruption. Device stops without braking Check mains supply! (Does starting of rotor or cooling aggregate cause deviations?) Customer service program 9 view the error table of the converter. Check ribbon cable from converter to X9 of the PCB Control. Check the overtemperature sensor of the motor and its connections to the converter. Check the brake resistors, replace them if necessary (150 each). Check motor fan, replace if necessary. Service program 6. (Only present in refrigerated centrifuges.) Check the converter, replace it if necessary. Customer service program 3. See "Problems with defective frequency converter, motor, brake resistors, overload, Error 6", page 3-17. Error 7 Overspeed monitoring. Maximum rotational speed of the rotor is exceeded. There are regulator deviations of 800 1/min from the nominal value. Perhaps resulting error from Error 25. Device stops without braking. Service program 9. Check the motor, replace it if necessary. Replace the converter if necessary. Display Cause Remedy MSTM/0408 Error lists/Troubleshooting 3-5 Centrifuge 5804/5804 R and 5810/5810 R 3 Error lists / Troubleshooting Error 8 Acceleration ramps are not met. Slippage monitoring (comparison rotational field-actual rotational speed) during acceleration. Device brakes. Service program 11. Determination of the acceleration time. Replace the converter if necessary. Check the motor, replace it if necessary. Error 9 Writing error EEPROM. Re-initialize the EEPROM with service program 5. Replace the "Control" PCB. Error 10 Reading error EEPROM. Error display and setting of standard settings. If there is an error when reading the setting for imbalance the device cannot start (error 2!). Writing and reading operations are only carried out when the device is at a standstill (after switching on, after a run, manual rotor recognition) Re-initialize the EEPROM with service program 5. Replace the "Control" PCB. Error 11 Watchdog reset, software or hardware error. No actions possible, after a reset the port lines are constantly reset to 1. Replace the EPROM or the PROCESSOR (IC1). Replace the "Control" PCB. Error 12 EDP error Serial PC interface: error during trans- mission. Device can be operated by hand. Check the interface PCB and the plug connections for correct positioning. Display Cause Remedy MSTM/0408 Centrifuge 5804/5804 R and 5810/5810 R 3 Error lists / Troubleshooting 3-6 Error lists/Troubleshooting Error 13 EDP error Serial PC interface: reception error, parity error, wrong code number, check sum error. Check the interface PCB and the plug connections for correct positioning. Error 14 EPROM check sum error after mains on. Error program memory, EPROM defective. No further actions possible. Replace the EPROM or the PROCESSOR (IC1). Replace the "Control" PCB. Error 15 Rotor Imbalance error at n > 2000 1/min Device brakes with normal ramp; device was pushed or rotor not fixed. refer to ERROR 2. Rotor not fixed tightly. Device was pushed. Table is not stable. Error 16 Error during request to FC. FC not ready, drive relay has dropped. Error after telegram repetition. Device switches off stops without braking. Customer service program 9 view the error table of the converter. Check cable and connections at plug X9 and X2. Check the overtemperature sensor of the motor and its connections to the converter. Display Cause Remedy MSTM/0408 Error lists/Troubleshooting 3-7 Centrifuge 5804/5804 R and 5810/5810 R 3 Error lists / Troubleshooting Error 17 Error during transmission of select telegram to FC. Queue overflow FC telegrams. Error after 3 repetitions of a select telegram. Device switches off stops without braking. Customer service program 9 view the error table of the converter. Check cable and connections at plug X9 and X2. Check the overtemperature sensor of the motor and its connections to the converter . Error 18 overtemp. Overtemperature of the rotor chamber. After the regulation (temp.) the interval of 5 C is exceeded. Coolant can not be aspirated, ambient temperature is too low. After starting a run, the chamber tem- perature exceeds the nominal value or during a run, the chamber tempera- ture exceeds the value (nominal value + 10 C). Refrigeration aggregate does not work. An FC with extended temperature range was replaced by an old FC. Rotor chamber temperature > 50 C. Device switches off braked stop. Room temperature too high? Direct sunlight? Wait 4 hours following transport. Bring the centrifuge into a room with a room temperature of 22 C. Is ventilation ensured by sufficient clearence at the sides of the device? Which rotor is used? Can the desired temperature be achieved with this rotor and this adapters? (See Operating manual/Accessories guide) Is the lid sealing damaged? Is the lid closed correctly? (Air entry may lead to heavy icing in the rotor chamber. The regulation is interfered, full performance is not reached). Is the condenser fan contaminated, defective? Check with service program 6. Service program 6, check temperature sensors, condenser and bottom of rotor chamber. PCB Control defective? Display Cause Remedy MSTM/0408 Centrifuge 5804/5804 R and 5810/5810 R 3 Error lists / Troubleshooting 3-8 Error lists/Troubleshooting Error 19 Overtemperature at the condenser tem- perature > 75 C. Fan is blocked / does not start, air intake is covered. Temperature sensor defective. Device switches off braked stop, the refrigeration aggregate is switched off, the fan keeps running. Let the refrigeration aggregate cool down, check the air intake. Check whether the condenser fan rotates when the aggregate is switched on. Service program 6. Check temperature sensors, condenser and bottom of rotor chamber. Check the condenser fan, replace it if necessary. Check all plug connections X3, X5, X10. Check whether the refrigeration aggregate is filled. Error 20 Temperature sensor in the rotor chamber is defective. Device switches off braked stop. Refrigeration aggregate switches off. Service program 6. Check sensor in rotor chamber. Replace the sensor or the "Control" PCB. Error 21 Temperature sensor on condenser defective (NTC). Measuring value is not within < 8 C > 91 C. Device switches off braked deceleration, refrigeration keeps running. Service program 6. Check temperature sensor at condenser. Replace the sensor or the "Control" PCB. Error 22 No 50 Hz signals for fan control. During run and stand-by. The fan is controlled with full power. After mains on: The device is not rec- ognized as a refrigerated device!! In case of sporadic occurrence: Interference in the environment, caused, for example, by other devices. Interference frequencies on the power line. Replace the "Control" PCB. Remove interference in the environ- ment. Test the centrifuge in another room with a different device circuit. Display Cause Remedy MSTM/0408 Error lists/Troubleshooting 3-9 Centrifuge 5804/5804 R and 5810/5810 R 3 Error lists / Troubleshooting Error 24 Clear Memory Program memory is full. Erase program if required, or start new run with Start or Prog. Error 25 Interrupt Interrupt. Mains interrupted during a run. Is mains voltage generally too low or too high? Do deviations exist? Cable in the device is damaged, e.g. after replacement of the motor cap/rotational speed sensor or PCB imbalance detection. Restart. Check mains supply (during start of cooling aggregate as well). Check cables in the device and look for cable damage, particularly near the motor. Error 31 x 0: Timeout while closing the lid. 1: Timeout while opening the lid. 2: Undefined position when opening. 3: Monitoring of microswitches for lid. 4: Released lid does not open. 5: Error during lid test after power-on. Check the connections on the sensor board and plug X10. Display Cause Remedy MSTM/0408 Centrifuge 5804/5804 R and 5810/5810 R 3 Error lists / Troubleshooting 3-10 Error lists/Troubleshooting Errors from the service programs Display Cause Error 32 Hardware error: imbalance measuring system. Check the connections on the sensor board and plug X10. Error 33 Measuring values outside of the measuring range, too little space between sensor and magnet. Check the connections on the sensor board and plug X10. Error 34 Faulty measuring series. Mean value not within limits or distance too short. Scattering run 13 too great. Scattering run 46 too great. Distance sensor magnet too great. Rotor is unbalanced during imbalance adjustment. Motor continues to vibrate. Check the connections on the sensor board and STV X10. See Error 2. Adjust distance Sensor Magnet, see Sec. 4. Clean pegs and nuts of the rotor/ bucket and grease slightly with Eppendorf pivot grease. Test another rotor. When using Rotor A-4-81: use magnet carrier imbalance detection with 9x13 mm magnet. Speed sensor cable jammed. Replace shock mounts for motor. Perform imbalance calibration on a solid bench. Error 35 Imbalance sensor idle value exceeds the limit (670 100). Check the connections on the sensor board and plug X10. see Error 34 MSTM/0408 Error lists/Troubleshooting 3-11 Centrifuge 5804/5804 R and 5810/5810 R 3 Error lists / Troubleshooting Error 36 EEPROM not yet initialized. Reinitialize EEPROM with service program 5. Change PCB "Control". Error 37 Voltage version of frequency converter and Centrifuge do not correspond. undefined display, no background illumination Display module or 26-pole cable defective, 5 V power supply faulty Check all cables. Change PCB Control pad or PCB Control. Display Cause MSTM/0408 Centrifuge 5804/5804 R and 5810/5810 R 3 Error lists / Troubleshooting 3-12 Error lists/Troubleshooting Warnings / Error displays (are not stored in the EEPROM) Display Cause Voltage false W-Error 27 Mains voltage of FC incorrect. Check voltage version. SPEED W-Error 29 SPEED the set rotational speed is faster than the nominal rotational speed of the rotor in use. The device stops the run after rotor recognition. Enter new nominal speed. 200 rpm New rotor was used in devices with older soft- ware Install new software and carry out imbalance adjustment. IMBAL W-Error 30 IMBAL Imbalance at < 2000 1/min. The device brakes. No imbalance calibration was carried out after installing rotor A-4-81. Check rotor and loading. Test buckets and adapters with a scale. Clean pegs and nuts of the rotor/ bucket and grease slightly with Eppendorf pivot grease. Test another rotor. Carry out imbalance calibration. Rotor See Error 15. Caution with open lid locking mechanism is actuated! Risk of squeezing! MSTM/0408 Error lists/Troubleshooting 3-13 Centrifuge 5804/5804 R and 5810/5810 R 3 Error lists / Troubleshooting Press open LIFT LID W-Error 31 The locking mechanism for the lid is in an undefined position. Lid is released and does not lift up automatically. Actuate the OPEN button. Open lid manually via emergency release using the rotor key. Bring lid mechanism into different position via emergency release using the rotor key. Lid mat/reinforcement may be warped. Align manually, or replace if required. Smooth locking eye of lid mat/ reinforcement using fine sandpaper. Sealing of rotor chamber may have become rigid. Replace if required. The gas spring is too sluggish. Grease with "Esso S420", or replace if required. Grease lid mechanism (i.e. with "Molykote") in the area of the Y-slider and the two Pertinax plates (there might be a roughness). Replace motor of lid latch. Replace Control PCB (too little power). Magnets on Y-slider fell off. Replace Y-slider. CLOSE LID W32 Command to close the lid. Close lid again firmly. Display Cause MSTM/0408 Centrifuge 5804/5804 R and 5810/5810 R 3 Error lists / Troubleshooting 3-14 Error lists/Troubleshooting Overload Drive overloaded. See Error 6. Mains voltage too low. CLEAn ro W-Error 32 200 runs Error appears after run 200/201/202 (from software 2.0 onwards). Clean rotor, rotor cone, motor cone and chamber, grease rotor axle slightly! With the swing-bucket rotor, lightly grease the pivots and grooves of the bucket with pivot grease. Open lid. Standby off Centrifuge not used for 6 hours (from software 2.0 onwards). Open lid and close again. Display Cause MSTM/0408 Error lists/Troubleshooting 3-15 Centrifuge 5804/5804 R and 5810/5810 R 3 Error lists / Troubleshooting Change rotor W-Error 28 Load-cycle count of 100.000 reached (from software 3.0 onwards with PCB in SMD technology). The warning is displayed 3 times following the run after 98,000, 99,000 and 99,600 runs. It appears after every run after 100,000 runs. Notes: The "Change rotor" message is conceived of as a warning and provides the customer and the service technician the opportunity to evaluate the condition of the rotor. Use of a rotor with load change limitation that has exceeded the 100,000th load change is not permitted! It must be noted that the load change numbers (CLyy) can only be reliably evaluated when: 1. In case of repairs the data of the defective PCB Control has been taken over by the new PCB Control. (Saving does not take place in the EPROM program, but instead only on the PCB.) 2. The load change counter has been reset while exchanging a rotor. 3. The customer uses only a rotor of the same type in the centrifuge. 4. The customer uses several centrifuges and each rotor is allocated to one centrifuge. 5. The fixed-angle rotors CL13 and 17 have no load change limitation. It is not necessary to discontinue operation. Only the fixed-angle rotors CL14 and 18 and all swing-bucket rotors have a load change limitation. Only centrifuges equipped with the PCB Control in SMD technology as of software version 3.0 enable a load change number (CLxx).). Evaluate the load change table with service program SE 14. The load change numbers (CLyy) are measured separately for each rotor type. Immediately discontinue operation of the rotor if necessary, see notes. Prior to using a new rotor, delete the load change table for the rotor type with service program SE 14. Display Cause MSTM/0408 Centrifuge 5804/5804 R and 5810/5810 R 3 Error lists / Troubleshooting 3-16 Error lists/Troubleshooting no rotor See Error 3. Over- temp. See Error 18. CCI false An old FC with software 2.1 was used. Use new FC with extended temperature range. Clear Memory See Error 24. Display Cause MSTM/0408 Error lists/Troubleshooting 3-17 Centrifuge 5804/5804 R and 5810/5810 R 3 Error lists / Troubleshooting Problems with defective frequency converter, motor, brake resistors, overload, Error 6 1. Mains voltage stable at customers site? (Error 25 possible.) Mains voltage generally too low or too high? 2. Room temperature too high, max. 35C ? Direct sunlight? 3. Sufficient space for air ventilation at sides of device? Minimum 15 cm at both sides and 10 cm at rear side. 4. Do the brake resistors still have approx. 150 Ohm each? 5. Is the motor fan working (only present in refrigerated centrifuges)? 6. Service Manual, "Service function, Program 13, Viewing the error table". 7. Service Manual, "Customer service program 7, Last error report". 8. Turn motor by hand and listen to ball bearing noise. A sluggish or loud motor may result in higher current, thus damaging the frequency con- verter and/or the brake resistors! 9. Service Manual, "Customer service program 2, FC current during a run". xx Phase current in phase line to motor 230 V:Typical value after start is xx = 42 (4.2 A) and after reaching maximum speed xx = 24 (2.4 A). 120 V:Typical value after start is xx = 84 (8.4 A) and after reaching maximum speed xx = 48 (4.8 A). 10. With Error 6: Service Manual, Customer service program 9, current error indication (selectable via cursor key only directly after error) xx error number e.g. 06 zz 0 =no error message7=overcurrent FC 1 =undervoltage8=interference EPROM FC 2 =overvoltage10=no release 4 =overtemperature FCFA=reset by internal software or hardware 5 =overtemperature motorFF=serial interface time out Check the non-refrigerated centrifuges 5804/5810 to see whether the foam parts in the device are still suitable to maintain the required ventilation flow for cooling. 2 : x x y y y z z z z z 9 : E r x x y y z z MSTM/0408 Centrifuge 5804/5804 R and 5810/5810 R 3 Error lists / Troubleshooting 3-18 Error lists/Troubleshooting Customer service programs By actuating simultaneously the PLUS and MINUS buttons (cursor keys) the device is switched over to the service indication mode. This does not depend on the operational mode the device is currently in. The run of the centrifuge is not influenced by this. The indications are continued by pressing the PLUS button. During a run only the indications no. 1...6 are accessible (from START to opening the lid or resetting to the nominal value indication with START). During a fault the indication automatically jumps to 9. After that you can start again switching to different indications (error indication with display of the error location and for error 6 of the FC error numbers). The FC parameters can be checked during a standstill and while the lid is closed (FC on!) with the indication 2 and by actuating the MINUS button. 1: Temperatures Devices without refrigeration system Devices with refrigeration system x.x Condenser temperature, refrigeration aggregate switches off at 75 C * means the refrigeration aggregate is switched on yy.y nominal temperature rotor chamber sensor zz.z corrected nominal value = regulator value. Rotor-dependant! 2: FC parameters current during a run xx Motor current 33 3.3 A (phase current in the phase line to the motor) y F = FC on, display for fixed-angle rotor (only for factory setting) yyy parameter 9, display for swing-bucket rotor (only for factory setting) zzzzz parameter 3 rotational field - rotational speed/control value (only for factory setting) 2: FC parameter during a standstill (for factory settings only) 1 : 1 : x x * y y y z z z 2 : x x y y y z z z z z 2 : P x x V = y y y y y = ^ MSTM/0408 Error lists/Troubleshooting 3-19 Centrifuge 5804/5804 R and 5810/5810 R 3 Error lists / Troubleshooting 3: FC parameters temperature during a run xxx temperature frequency converter FC oldxxx =digital value displayed (switching off at 128, value for 20 C = approx. 83) FC newxxx =display in C x factor 10 (switching off at approx. 75 C, display for 20 C = 200) * FC temperature warning yyy parameter 4: acceleration ramp (for factory checks only) zzz parameter 5:braking ramp (for factory checks only) 4: Rotor recognition xxx Rotor relation (rotor table, rotor relations, see last page of Section 3) y number of recognition measurements zz Rotor number (rotor table, rotor relation, see last page of Section 3) 5: Imbalance monitoring xxx Imbalance value (current sensor idle value during standstill) Recommended service setting = 670 30 Please note, important! Max. tolerance during standstill = 670 100 Please note, important! zzz saved idle value of sensor (from last imbalance calibration) with lid opened 5: Imbalance monitoring with lid closed xxx Imbalance value (current sensor idle value during standstill) Recommended service setting = 670 30 Please note, important! Max. tolerance during standstill = 670 100 Please note, important! xxx imbalance value during run = current sensor value (cannot be evaluated during a run) yyy maximum appeared imbalance (only active during run) zzz imbalance cut-off value for the rotor used 3 : x x x * y y y z z z 4 : x x x y z z 5 : x x x r u = z z z 5 : x x x y y y z z z MSTM/0408 Centrifuge 5804/5804 R and 5810/5810 R 3 Error lists / Troubleshooting 3-20 Error lists/Troubleshooting 6: Lid locking uuu mean value of sensor lid locking position x1,x2 lid report left and right yy O = locking mechanism in upper dead centre=closed U = locking mechanism in lower dead centre=open = undefined position zzz actual sensor value (Hall sensor junction plate) 7: Last error report ww last error xx error report before last etc. 8: Version xxx voltage version set yy software version zzzzz checksum EPROM (for factory settings only) 9: Current error indication (selectable via cursor key only directly after error) xx error number yy no. for locating the cause (for factory settings only) zz FC error number, if the frequency converter switches off with error 6 0 =no error message 1 =undervoltage 2 =overvoltage 4 =overtemperature FC 5 =overtemperature motor 7 =overcurrent FC 8 =interference EEROM FC 10 =no release FA =reset by internal software and hardware FF =serial interface timeout 6 : u u u x1 x2 y z z z 7 : w w x x y y z z 8 : x x x y y z z z z 9 : E r x x y y z z MSTM/0408 Error lists/Troubleshooting 3-21 Centrifuge 5804/5804 R and 5810/5810 R 3 Error lists / Troubleshooting Service programs 58XX General description The service programs run independently from the normal operating modes. You enter the program selection by simultaneously pressing the PLUS-/MINUS key and switching the centrifuge on. Display: xx Service program number The required program number can be set by actuating the PLUS or MINUS key. You can open the lid with the OPEN button. All programs are started with the START button. Indicated errors can be erased with the START button. If "error 36" is displayed immediately after calling up the service programs the EEPROM must be initialized (see section Initializing). The service mode can only be quit by switching off the device. S E x x MSTM/0408 Centrifuge 5804/5804 R and 5810/5810 R 3 Error lists / Troubleshooting 3-22 Error lists/Troubleshooting Program overview Program no. Program contents 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 Setting the serial address Setting the voltage version Checking the display and the keypad Testing the lid function / lid switches Initializing Test refrigeration aggregate / fan / temperature sensor Cycle test Rotor recognition Test frequency converter Calibration imbalance sensor Determination of the acceleration and braking times Overspeed cut-off test Viewing the error table Display of the number of starts / the number of runs / load-cycle display Display of the switching off values for imbalance / sensor idle value / power supply Deleting of the operating hours / error table (factory only) (factory only) MSTM/0408 Error lists/Troubleshooting 3-23 Centrifuge 5804/5804 R and 5810/5810 R 3 Error lists / Troubleshooting Description of the individual service programs Setting of the serial interface START Program 1 (optional) xxxxx = RS232 BBUS Selection by means of the PLUS button disable Factory setting: disable Start next step xx device address 20...29 (Hex) Factory setting: 20 H By actuating the PLUS button the address to be set is continuously counted upwards. Acknowledgement of the selected device address with START. END end of program actuate the START button. Voltage version (set after replacing PCB Control) START Program 2 Start SE 2 Voltage version is displayed Button PLUS Selection of the voltage version 230 115 100 Button PROG Value is stored in the EEPROM (display 'ok') Button START/STOP End of program Check of the display and keypad START Program 3 1. Check of the display 1.5-s sound on and all digits displaying the pattern 0 0 0 0 2. Check of the keypad Input request '>' the button designation is displayed as text. End of program by means of the STOP button (as a last button). 1 x x x x x 2. n x x S P x x x MSTM/0408 Centrifuge 5804/5804 R and 5810/5810 R 3 Error lists / Troubleshooting 3-24 Error lists/Troubleshooting Lid function test START Program 4 l, r left and right limit switch (1 = pressed / 0 = open) ss position OT in upper dead centre UT in lower dead centre un undefined intermediate position xxx current sensor value yyy sensor idle value (mean value) Keys: OPEN lid open/closed normal function PLUS pulse by pulse forwards MINUS pulse by pulse backwards SPEED erase counter for continuous lid latch test. STOP end of program Initializing START Program 5 STOP button no initializing, return to program selection PROG button initializing is carried out The nominal values set and the operating conditions are stored in the EEPROM after each run of the centrifuge. The limits for switching off (imbalance) and statistical data and fixed programs are also stored in the EEPROM. When calling up the program via the serial interface code no. 64, additionally the interface is set to 20 H/disable. y y y l r s s x x x I n i t 2 The following is deleted: The following is not deleted: Error table Imbalance cut-off values (SE 10) Number of connections (IO) Number of load changes per rotor (Clyy) Operating hours (h) Voltage version Total number of centrifuge runs (CL) Interface setting Programmed customer fixed programs MSTM/0408 Error lists/Troubleshooting 3-25 Centrifuge 5804/5804 R and 5810/5810 R 3 Error lists / Troubleshooting Switching the aggregates / temperature sensor test (only for refrigerated devices) START Program 6 Switching the aggregates Key: TEMP refrigerating aggregate on/off PROG motor fan on/off SPEED frequency converter on/off (no control of FC, only relay on PCB audible) TIME Condenser fan on/off xx fan step (0...16) the step can be changed by means of the PLUS and MINUS buttons Fast coolswitching over to temperature display xx.x temperature of sensor in rotor chamber yy condenser temperature room temperature when centrifuge in standby Procedure for cooling problems: Does the refrigerating aggregate switch? Does the condenser fan start? Fan level 016 Does the sensor in rotor chamber work? (Check with thumb, replace if necessary) Is the condenser temperature sensor working? Check refrigerating system: 5804 R, Rotor A4-44, 5000 rpm 5810 R, Rotor A4-62, 4000 rpm Fill 50-ml tubes with "ethylene glycol". Start program, select temperature +6 C, "Fast Temp" Start run measure after 45 min with 5804 R approx. +4 C to +8 C 5810 R approx. +4 C to +8 C Observe customer service program 1 xx = condenser temperature approx. +40 C to +50 C (refrigerating aggregate switches off at +75 C) * = refrigerating aggregate is switched on yyy = actual temperature of sensor in rotor chamber zzz = correction nominal value (not important for service) K A L M F U L K S = x x T e m p = x x x T K = y y 1 : x x * y y y z z z MSTM/0408 Centrifuge 5804/5804 R and 5810/5810 R 3 Error lists / Troubleshooting 3-26 Error lists/Troubleshooting Is the refrigerating system tight? Does the valve switch? Repair if necessary and refill cooling agent Quantity cooling agent R134A 5804 R 400 g 5810 R 470 g Repairing the refrigerating system The spare parts are mounted at your own risk! Repair must be carried out by a specialist for refrigerating devices! Observe safety regulations of your country! Cycle program START Program 7 This program is used for a continuous test (e.g. factory test) of the centrifuge. Always 3 runs with a subsequent interval of 1 min are carried out. After the 4th run the interval is 10 min. The FC is switched off after each run. The nominal values of the run can be changed after the start of the service program (pre-setting: nominal rotational speed of the rotor, 10 min, 4 C). Display of the pre-set nominal values, it is possible to change them Start cycle run Display after each run xx interval time in min/s An individual run can be aborted by means of the STOP button. The lid can be opened during the interval. You can only quit the cycle program by switching off the device. 4 0 4 0 0 0 1 0 P A U S E x x MSTM/0408 Error lists/Troubleshooting 3-27 Centrifuge 5804/5804 R and 5810/5810 R 3 Error lists / Troubleshooting Rotor recognition test / rotor pulses START Program 8 Slowly rotate the rotor < 100 1/min SPEED pulse display _ gap passes the sensor magnet passes the sensor STOP end of pulse display Turn rotor slowly < 100 rpm TIME display of rotor relation xxx rotor relation y number of measurements (2 y < 10) zz rotor number 1...20 STOP ends subprogram and SE 8 Frequency converter test (FC) When the upper part of the housing has been taken off, the check must be done without the rotor! START Program 9 Check voltage version before entering FC parameters (differing data records)! Actuation SPEED buttonswitching FC on/off PLUS button Run at approx. 120 rpm, lid opened, FC must be switched on. MINUS buttonbraking b converter ready, from switching on the FC to READY indication approx. 1 s will pass xxx FC on/off yyy rotational field speed, if FC is switched on End = STOP button; the FC is switched off, return to program selection r o t a t e _ _ _ _ _ _ _ _ _ _ _ r v = x x x y z z F U b x x x y y y MSTM/0408 Centrifuge 5804/5804 R and 5810/5810 R 3 Error lists / Troubleshooting 3-28 Error lists/Troubleshooting Imbalance calibration carried out by a service technician START Program 10 The centrifuge determines the imbalance cut-off value of the individual rotors from all rotors in a rotor group. One angled rotor (W) and one swing-bucket rotor (A) must be used from each rotor group. As a rule, this should be carried out with the standard rotors. Exception: Use (A) Rotor A-4-81 if avaliable. Standard rotors: Centrifuge 5804 / 5804R (W) F34-6-38 and (A) Rotor A-4-44 Standard rotors: Centrifuge 5810 / 5810R (W) F34-6-38 and (A) Rotor A-4-62 Prepare the weights: G1/G2/G3 It is possible to weigh the weights yourself using Eppendorf tubes. Filled 2.0 ml tubes (approx. 3.2 g) are recommended. The weight of the tube must also be taken into consideration. With swing-bucket rotors, these should be placed flat, loose and without an adapter on the bottom of the swing-bucket. With the angled rotor F34-6-38, water should be pipetted directly into the empty bores. MTP rotors can be loaded and then filled with one MTP each. Procedure for imbalance calibration 1. Insert fixed-angle rotor (W). (Use the present rotor lid). 2. Call up the service program: Hold down both cursor keys and switching on the device. Display : SE 1 3. Using the cursor key, call up SE 10 4. Insert the tube with G1. 5. Close lid. Start run: Start 6. Three calibration runs are performed automatically. The lid opens automatically. 7. Insert weight G2. 8. Close the lid and wait until three further calibration runs have been performed. Lid opens automatically. 9. Insert weight G3. Close lid. Start run: Start (Centrifuge must show "Imbal" and switch off.) 10. Open lid: Open. 11. Remove fixed-angle rotor (W) and insert swing-bucket rotor (A). 12. Using the corresponding imbalance amounts G1, G2, G3, carry out the procedure described in points 2. to 9 13. Switch off the device. Remove the imbalance weights and then switch on the centrifuge again as normal. Note: An imbalance adjustment must be carried out every time the motor, PCB Control or PCB Imbalance is replaced or when the rotor is inserted! After the motor has been replacedl or when the centrifuge has not been used for a long period, it should run for approximately five minutes at maximum speed in order to ensure that the vibration mounts have the normal degree of hardness. MSTM/0408 Error lists/Troubleshooting 3-29 Centrifuge 5804/5804 R and 5810/5810 R 3 Error lists / Troubleshooting Overview of rotors required and weights: G1/G2/G3 Fixed-angle rotors (W) Centrifuges: 5804 / 5804 R / 5810 / 5810 R Swing-bucket rotors (A) Centrifuges: 5804 Centrifuges: 5804 R Centrifuges: 5810 / 5810 R Rotor designation G1 G2 G3 W F-34-6-38 6g 10g 12g W F-45-30-11 6g 10g 15g W FA-45-30-11 6g 10g 15g W T-60-11 7.5g 15g 22.5g W F-45-48-PCR Without PCR strips a PCR strip filled with water Not required Rotor designation G1 G2 G3 A A-4-44 16g 22g 25g A A-2-DWP 16g 22g 25g A A-2-MTP 16g 22g 25g Rotor designation G1 G2 G3 A A-4-44 12g 18g 25g A A-2-DWP 12g 18g 25g A A-2-MTP 12g 18g 25g Rotor designation G1 G2 G3 A A-4-62 16g 22g 30g A A-4-44 16g 22g 30g A A-2-DWP 16g 22g 30g A A-4-62 MTP 16g 22g 30g A A-2-MTP 16g 22g 30g A A-4-81 16g 22g 30g A A-4-81 MTP 16g 22g 30g A A-4-81 Flex 16g 22g 30g MSTM/0408 Centrifuge 5804/5804 R and 5810/5810 R 3 Error lists / Troubleshooting 3-30 Error lists/Troubleshooting Determination of the acceleration and braking times (for factory checks) START Program 11 completely equip the rotor (the measured rotational speed is calculated by the program after the rotor recognition = 97 % of the max. rotational speed of the rotor in use) close the lid START run Display of the acceleration time in seconds (at 97 % of the rotational speed nominal value) STOP start of the measurement of the braking time Display braking time STOP return to the program selection Overspeed cut-off test (Test with Rotor) START Program 12 Close the lid The software sets a rotational speed above the switching-off limit. If the device operates correctly, it switches itself off when reaching the switching-off rotational speed and stops without braking. If the device is not switched off, the run must be stopped immediately by hand! The device must be switched off! On switching on again the centrifuge brakes and is then again in the normal operational mode. Overspeed cut-off: The overspeed cut-off is about 300 1/min above the nominal speed of the rotor in use. 3 0 0 2 0 0 0 1 1 H L x x x B L x x x MSTM/0408 Error lists/Troubleshooting 3-31 Centrifuge 5804/5804 R and 5810/5810 R 3 Error lists / Troubleshooting Viewing the error table START Program 13 The error that occurred first during a run is stored. display of the errors during a run PROG transition to the step mode START continuing step by step STOP return to the program selection xx error no. yyy no. of errors Display for the number of starts / number of runs valid for centrifuges incl. software version 2.1 START Program 14 xxxx no. of starts START next display xxxx no. of runs STOP return to program selection E r r o r x x y y y E A x x x x C L x x x x MSTM/0408 Centrifuge 5804/5804 R and 5810/5810 R 3 Error lists / Troubleshooting 3-32 Error lists/Troubleshooting valid for centrifuges with software from version 3.0 onwards The load cycles are recorded separately for each rotor type. START Program 14 xxx no. of starts START next display xxxx no. of runs completely Key PROG erases the number START next display yy rotor number CL xxxx no. of load cycles per rotor type START next rotor number CL Key PROG erases the number n for this rotor only Cursor keyschange the number of load cycles in steps of 500 START next display xxxx no. of operating hours START end of program E A x x x x C L x x x x x x C L y y x x x x x x h x x x x x MSTM/0408 Error lists/Troubleshooting 3-33 Centrifuge 5804/5804 R and 5810/5810 R 3 Error lists / Troubleshooting Viewing the values stored in the EEPROM (for factory checks) START program 15 yy rotor number xxx switching-off values for all rotors (no. 2, 3, 4, 5, 8, 13, 14, 17, 18) always continue switching with START START xxx idle value imbalance sensor (measurement during the imbalance calibration) Start xxx max. imbalance value for 30g-run G3 with rotor A-4-81 (from software 3.4 onwards) Start xx rotor number calibration rotor fixed-angle rotor Start xx rotor number calibration rotor swing-bucket rotor Start xx idle value position sensor locking mechanism for lid Start xxx voltage version U y y x x x U r x x x U 3 x x x R W x x R A x x D V x x S P x x x MSTM/0408 Centrifuge 5804/5804 R and 5810/5810 R 3 Error lists / Troubleshooting 3-34 Error lists/Troubleshooting Start XX P0, P1, PL test words (check of the test process) STOP return to the program selection Deleting the error table START program 16 PROG error table and the operating hours are being erased acknowledgement display ok STOP abortion without deleting X X y y E r a s e E r r o r MSTM/0408 Error lists/Troubleshooting 3-35 Centrifuge 5804/5804 R and 5810/5810 R 3 Error lists / Troubleshooting Rotor table, Rotor relations * 1 Usable from software version 3.0 onwards * 2 From software version 3.3 onwards allowed up to 3700 rpm as well for older rotors labeled 3600 rpm * 3 Can be used from software version 3.5 onwards * 4 Usable from software version 3.7 onwards * 5 Centrifuge 5804 / 5804 R / 5810 only 11000 rpm Rotor num- ber CL max. speed/rcf max. radius Rotor designation Rotor relation 1 2 3700 / 2250 147 mm A-2-DWP * 1 * 2 153.9 143...163 3 4000 / 2253 126 mm A-2-MTP 192.3 182...202 4 4000 / 3220 180 mm A-4-62 (rectangular bucket) 230.7 220...240 4 4000 / 2750 154 mm A-4-62 (MTP carrier) 230.7 220...240 5 4000 / 3220 180 mm A-4-81 * 3 (rectangular buckets) 269.2 255...283 5 4000 / 2915 163 mm A-4-81 * 3 (MTP carrier) 269.2 255...283 5 4000 / 2900 153 mm A-4-81 * 3 (Flex bucket) 269.2 255...283 6 7 8 5000 / 4500 161 mm A-4-44 384.6 375...395 9 10 11 12 13 12000 / 15294 95 mm F-45-48-PCR * 4 577 563...591 14 12000 * 5 / 18514 115 mm F-34-6-38 * 5 615.4 605...625 15 16 17 14000 / 20817 95 mm F-45-30-11 FA-45-30-11 730.7 721...741 18 14000 / 16435 75 mm T-60-11 * 1 769.2 759...779 19 20 MSTM/0408 Centrifuge 5804/5804 R and 5810/5810 R 3 Error lists / Troubleshooting 3-36 Error lists/Troubleshooting MSTM/0408