Chapter : Drafting For additional information on this subject, contact
File Reference: AGE10803 N. H. Alahaimer on 874-0876
Engineering Encyclopedia
Saudi Aramco DeskTop Standards
Drafting Instrument Loop Diagrams
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards
CONTENTS PAGES
Information
Instrument Loop Diagram 1
Ild Symbols And Abbreviations 1
Interpreting Ilds 29
Interpret An Ild For A Pneumatic Instrument Control Loop 37
Interpret An Ild For An Electronic Instrument Control Loop 44
Tracing Current Flow In Control Loops 57
Computer Relays 59
Computer Relay Symbols 59
Instrument Systems 67
Foxboro Spec 200 67
The Honeywell Vutronik Control Loop 83
The Honeywell Vutronik Alarm Card 96
Examples Of Honeywell Cards 100
Honeywell Resistance To Current Converter Card 102
Work Aids 104
Glossary 119
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 1
Instrument Loop Diagram
Every process control loop has an instrument loop diagram (ILD) drawn for it. ILDs give
more information about control loops than any other drawing. Although they are of interest
mainly to instrumentation engineers and tech-nicians they are one of the most common
drawings seen in Saudi Aramco.
ILD Symbols And Abbreviations
Handout No. 1 (Drawing No. 990-J-36492 Sheets 1 and 2) shows common ILD symbols and
abbreviations. Some of them will be described in detail in this module.
Orifice Plate. Figure 1 shows the symbol for a flow element orifice plate. Figure 2 shows an
orifice plate.
FIGURE I. FLOW ELEMENT, ORIFICE PLATE
1.550

F
L
O
W

ORIFICE PLATE
CORRECT SIZE
NUMBER MUST MATCH
BORE SHOWN ON ILD
CORRECT DIRECTION
NUMBER ON PLATE
MUST FACE UPSTREAM
MARK NO.
BORE
FLOW ELEMENT
ORIFICE PLATE
LINE NUMBER
H L
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 2
ILD Symbols and Abbreviations(Cont'd)
Orifice Plate(Cont'd). An orifice plate is placed into a pipeline to cause a pressure differential
between its upstream and downstream flow. H and L stand for High and Low. They indicate
the high and low pressure sides of the plate. The difference in pressure is used to indicate
flow rate. Pressure differential varies as the square of the flow rate. Therefore, the square
root of the pressure differential reading is needed in order to obtain the linear value of the
flow rate.
Process variable measuring devices, such as orifice plates, are sometimes called elements.
The mark number, seen in Figure 1, is the identification, or tag, number given to the flow
element. Bore is the size of the hole, in inches, in the orifice plate. The line number is the
identification number of the pipeline.
Control Valve. Figure 3 shows the symbol for a control valve. The letter S above the small
triangle means there is an air supply to open or close the valve. The abbreviation INST means
that an instrument air signal is supplied to the valve positioner. The positioner is shown by
the square block.
The output air signal is shown going to the top of the valve. Therefore, the valve operates by
air pushing down onto the diaphragm.
The mark number for this valve would be PCV, TCV, LCV, or FCV (for pressure,
temperature, level or flow control valve) followed by the loop number.
Size rating is the size, in inches, of the valve inlet and outlet bore.
A. F. ACTION, sometimes shown only as ACTION, says what the valve will do if there is an
Air Failure (AF). The word OPEN or CLOSE will be shown after A.F. ACTION.
LINE NUMBER
DIAPHRAGM OPERATED GLOBE
VALVE WITH POSITIONER
FIGURE 3. CONTROL VALVE
MARK NO.
SIZE RATING
A. F. ACTION
OUTPUT
INST.
S
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 3
ILD Symbols and Abbreviations(Cont'd)
Electrical Switches. Figures 4 and 5 show electrical switches. In Figure 4, NO means Normally
Open. NC means Normally Closed.
The letter C on its own means Common. By operating the Hand Switch, C can be connected
either to NO or to NC.
Mark No. is the identification of the switch.
In Figure 5, SET AT is the value of the process variable at which the switch will automatically
trip open or close. The value will be shown in psi, F, or %, depending on the type of switch
used (that is, the type of process variable that is being controlled). The symbol % is often
used in level control. Level may be given not as a dimension but as a percentage of the vessel
capacity. For example the set point may be 75% to show that the vessel should be kept at
75% full.
HAND SWITCH
FIGURE 4
NO
OR
NC
C
MARK NO.
SET AT
SWITCH ( SINGLE )
FIGURE 5. LEVEL SWITCH ( SINGLE )
L
I
N
E

O
F

E
Q
U
I
P
M
E
N
T
M
A
R
K

N
O
.
MARK NO.
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 4
ILD Symbols and Abbreviations(Cont'd)
Lamps And Lights. Figure 6 shows the symbols used for lamps and lights.
FIGURE 6
RUNNING LIGHTS
MARK NO.
RED
GREEN
LAMP
MARK NO.
When a light is not identified by a color, the light will usually be white. The mark number
will give the number of the instrument loop to which the light is connected.
ILD Line Symbols. Figure 7 shows ILD line symbols. Lines may be broken to avoid drawing
over equipment or information. The line may then be continued on the other side of the
equipment or information.
PROCESS LINES
INSTRUMENT AIR LINES
INSTRUMENT ELECTRIC LINES
INSTRUMENT CAPILLARY TUBES
LINE
BREAK
LINE
CONTINUES
FIGURE 7. ILD LINE SYMBOLS
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 5
ILD Symbols and Abbreviations(Cont'd)
Air Supply. Figure 8 shows more ILD abbreviations. Those on the left indicate air supply.
Those on the right are as stated.
FIGURE 8. ILD ABBREVIATIONS
AIR SUPPLY S
A / S
EITHER SYMBOL MAY BE USED.
D / P
+
_
AO / AFS
AC / AFO
H
L
GND
DIFFERENTIAL PRESSURE
POSITIVE TERMINAL
NEGATIVE TERMINAL
AIR OPEN / AIR FAILURE CLOSE
AIR CLOSE / AIR FAILURE OPEN
HIGH PRESSURE
LOW PRESSURE
GROUND
Electrical Signal Lines. Figure 9 shows ILD Electrical Signal Lines.
SHIELDED CABLE
THIS SYMBOL
INDICATES A SHIELD
FIGURE 9. ILD ELECTRICAL SIGNAL LINES
RED
WHITE
BLACK
GREY
WIRE
COLORS
The wires are color coded to show which wires must be connected to terminal posts.
Instrument cables that carry low voltage signals are shielded to prevent outside electrical
energy from interfering with the signals.
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 6
ILD Symbols and Abbreviations(Cont'd)
Box and Cable numbering. Figure 10 shows box and cable numbering. The Junction Box (JB)
or Terminal Box (TB) number is located at the top of the box symbol shown in Figure 10.
Connections, called terminal posts, inside the block are numbered.
FIGURE 10. BOX AND CABLE NUMBERING
CONDUIT OR
CABLE NUMBER
JB OR TB NUMBER
TERMINAL BOX WITH
TERMINALS
TERMINAL NUMBERS
SHOWN HERE
CONDUIT OR CABLE
NUMBER SHOWN HERE
The conduit or cable number will be written in the block near the electrical line symbol.
Cables are always identified in pairs, or groups of pairs, of wire.
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 7
ILD Symbols and Abbreviations(Cont'd)
Local Indicators. Figure 11 shows the symbols for Local Indicators. Range means the range of
the indicator scale.
The letters B and E in the Foxboro local indicator symbol give the polarity of the input signal
(+ve or -ve). (Foxboro is the name of one of the manufacturers of instruments used by Saudi
Aramco. Another manufacturer is named Honeywell.)
FIGURE 11. LOCAL INDICATORS
FOXBORO LOCAL
INDICATOR CONNECTIONS
LOCAL INDICATOR
MARK NO.
RANGE
+
_
B E
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 8
ILD Symbols and Abbreviations(Cont'd)
Temperature Sensing Elements. Figure 12 shows the symbols for Temperature Sensing
Elements.
The Range is usually from zero to the maximum process temperature the Resistance
Temperature Element (RTE) will measure in its loop, for example, 0 to 250F.
Type on the thermocouple symbol identifies the metals in the thermocouple, for example,
IRON/CON would mean iron and constantan.
RESISTANCE TEMPERATURE
ELEMENT
FIGURE 12. TEMPERATURE SENSING ELEMENTS
MARK NO.
RANGE
E
Q
U
I
P
M
E
N
T
N
U
M
B
E
R
MARK NO.
TYPE
E
Q
U
I
P
M
E
N
T

O
R
L
I
N
E

N
U
M
B
E
R
THERMOCOUPLE TEMPERATURE
ELEMENT
Transducer. Figure 13 shows the symbol used for a transducer. The figure shows that the
transducer is changing an electrical input signal to a pneumatic output signal. Other symbols
may show the transducer changing a pneumatic input to an electrical output.
TRANSDUCER
FIGURE 13. TRANSDUCER
MARK NO.
+
_
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 9
ILD Symbols and Abbreviations(Cont'd)
Level Transmitters. Figure 14 shows the ILD symbols for Level Transmitters. All four
symbols are very similar and all show the vessel in which the level is being controlled. Note
the symbol for an accumulator, which is shown with the dry leg transmitters. The
accumulator is used to remove liquid from the dry leg.
LEVEL TRANSMITTER WITH AIR SUPPLY
CONNECTION ( D / P CELL )
MARK NO.
RANGE
DRY LEG
L
H
N
S
VESSEL NO. OUT
SUPPRESSION
ELEVATION
LEVEL TRANSMITTER
( D / P CELL )
MARK NO.
RANGE
SUPPRESSION
ELEVATION
WET LEG
L
H
VESSEL NO.
_
+
RED
GREY
MARK NO.
RANGE
DRY LEG
L
H
VESSEL NO.
SUPPRESSION
ELEVATION
_
+
RED
GREY
LEVEL TRANSMITTER WITH AIR SUPPLY
CONNECTION ( D / P CELL )
MARK NO.
RANGE
SUPPRESSION
ELEVATION
WET LEG
L
H
VESSEL NO.
OUT
S
FIGURE 14. LEVEL TRANSMITTERS WITH D / P CELLS
1
2
3
4
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 10
All four transmitter types use differential pressure to measure level. Types 1 and 3 are the
same except that 1 is pneumatic and 3 is electronic. Both use dry legs.
Types 2 and 4 are the same except that 2 is electrical and 4 is pneumatic. Both use wet legs.
Pressure measurement is sometimes expressed as the height of a column of water. This is
because a column of water one foot high produces a known pressure of 0.433 psi.
Alternatively, a column of water 27.7 inches high produces a pressure of 1.0 psi.
We can use this information to convert liquid pressure measurements into liquid level
measurements.
DP transmitters can be fitted with a biasing spring kit. The spring can be used to adjust or
balance out certain differential pressure readings in order to give us the actual readings we
require. When the bias acts to oppose pressure on the high side, it is called suppression.
When it acts to assist pressure on the high side, it is called elevation. An example is shown
below.
15 psig
3 psig
SEAL
LEG
100 '' WC
0 '' WC
P
1
P
2
H L
LOW
SIDE
HIGH
SIDE
BIAS
P
2
P
1
The pressure of liquid in the seal (or wet) leg is not needed for determining the liquid level in
the tank. Therefore, bias can be applied to balance out this pressure. Because bias in this
case is assisting pressure on the high side, we have elevation.
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 11
ILD Symbols and Abbreviations(Cont'd)
Level Transmitters (Cont'd). Figure 15 shows how a differential pressure transmitter is used to
measure level in a vessel open to the atmosphere.
Atmospheric pressure acts on the top of the water and also on the low pressure side of the DP
cell. Therefore, the difference in pressure between the high and low sides of the cell is equal
only to the pressure exerted by the water level.
Example: If the DP cell senses a pressure differential of 10 psi it means that the level of water
is 10 x 27.7 inches.
FIGURE 15. LEVEL MEASUREMENT USING A DP CELL
AIR PRESSURE
OPEN TANK LEVEL MEASUREMENT
WATER
H
E
I
G
H
T
LOW PRESSURE
SIDE VENTED TO
ATMOSPHERE
H L
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 12
ILD Symbols and Abbreviations(Cont'd)
Level Transmitters (Cont'd). Figure 16 shows how a DP transmitter measures level in a closed
vessel.
FIGURE 16. LEVEL MEASUREMENT USING DP CELL
TANK PRESSURE
WATER
H L
DP CELL
100 ''
200 ''
200 ''
DRY LEG
In order to obtain a differential pressure that depends only on the liquid level, the pressure of
the tank atmosphere must be cancelled out. This is done by connecting the low side of the DP
cell to the top of the tank. This connection is called a dry leg.
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 13
ILD Symbols and Abbreviations(Cont'd)
Level Transmitters (Cont'd). Figure 17 shows why wet legs are sometimes used.
FIGURE 17. LEVEL MEASUREMENT USING DP CELL
AIR
WATER
H L
DP CELL
100 ''
200 ''
200 ''
WET LEG
The atmosphere in a tank may carry vapor from the liquid. If a dry leg DP cell is being used,
some of the vapor will condense in the leg. After a time, liquid at varying levels could collect
in the leg. This would cause differential pressure readings that do not represent only the
height of liquid in the vessel.
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 14
ILD Symbols and Abbreviations(Cont'd)
To overcome this problem the wet legs are made to a known height, then filled with liquid.
Because the liquid level in the leg is constant, the pressure it exerts on the low side of the DP
cell is constant. This pressure can be taken into account when reading differential pressure.
Figure 17 shows that it is possible for the low side pressure to be greater than the high side
pressure. DP cells are always connected with their high side to the vessel.
Temperature Transmitters. Figure 18 shows the symbols for Temperature Transmitters. Range
gives the temperature range of the transmitter, for example 0 to 250F.
TEMPERATURE TRANSMITTER.
RESISTANCE TEMPERATURE DETECTOR
WITH RTD / mA CONVERTER
FIGURE 18. TEMPERATURE TRANSMITTERS
MARK NO.
RANGE
E
Q
U
I
P
M
E
N
T

O
R

L
I
N
E

N
U
M
B
E
R
MARK NO.
RANGE
E
Q
U
I
P
M
E
N
T

O
R

L
I
N
E

N
U
M
B
E
R
TEMPERATURE TRANSMITTER.
THERMOCOUPLE WITH INTEGRAL
ELECTRONIC mV / mA CONVERTER
+
_
+
_
GREY
RED
GREY
RED
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 15
ILD Symbols and Abbreviations(Cont'd)
Pressure and Flow Transmitters. Figure 19 shows two kinds of transmitters, one for pressure and
one for flow. The difference is in the connection to the process. Pressure measurement
requires only one connection. Flow measurement requires two connections; one for the high
pressure side of the orifice plate, and one for the low side.
FLOW TRANSMITTER WITH AIR
SUPPLY CONNECTION
FIGURE 19
MARK NO.
RANGE
MARK NO.
RANGE
PRESSURE TRANSMITTER
E
Q
U
I
P
M
E
N
T

O
R
L
I
N
E

N
U
M
B
E
R
+
_
GREY
RED
OUT
IN
S
Note that the flow transmitter has two input lines (on the left). This is because the flow
transmitter is using differential pressure.
Range will show the calibrated range of each transmitter. Examples would be:
0 - 100 psi (for pressure transmitter)
0 - 100" W.C. (inches water column) - [for flow transmitter]
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 16
ILD Symbols and Abbreviations(Cont'd)
Controller. Figure 20 shows the ILD symbol for a controller.
FIGURE 20. ILD CONTROLLER SYMBOL
MARK NO.
SET POINT
CONTROLLER
S
P. BAND
RESET
DERIVATIVE
ACTION
OUT
IN
The meaning of the terms shown on the controller are explained below.
Mark No. identifies the process variable or loop number which is being controlled.
Set Point is the process variable value to which the controller has been set. It is the value
needed for efficient and safe operation. The set point setting can be altered by the operator
when necessary.
P Band means proportional band. This is a setting which determines the amount the variable
measurement must change from the set point for the control valve to move through 100% of
its travel. For example, suppose the total travel of a control valve is 6" (that is from fully
closed to fully open is a travel of 6"). If a total deviation of the process variable from set
point is also 6" (that is 3" below set point to 3" above set point) then the P Band is 100%
(because a 6" movement of the variable causes a 6" movement of the valve).
Note that the controller has a constant pressure air supply. The output of this supply depends
on the input being received from the transmitter (which signal depends on the process variable
measurement).
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 17
ILD Symbols and Abbreviations(Cont'd)
Level Control. Figure 21 shows a level control system. The valve is fully closed when the
level is 3" above its set point. It is fully open when the level is 3" below its set point.
Therefore, the level must travel through its full range in order to move the valve through
100% of its travel (6"). Therefore, P (Proportional) Band is 100%.
PB PB PB
200 % 100 % 50 %
6 '' FLOAT
MOVEMENT
6 '' VALVE
MOVEMENT
1.5 FEET 1.5 FOOT
VALVE A
VALVE B
FIGURE 21. LEVEL CONTROL SYSTEM
SET POINT
3 ''
3 ''
SPAN
ZERO
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 18
ILD Symbols and Abbreviations(Cont'd)
Level Control (Cont'd). Figure 22 shows the arrangement for a P Band of 50%. A total
deviation from the set point of 3" causes a 6" movement of the control valve. The P Band is,
therefore, 50%.
PB PB PB
200 % 100 % 50 %
3 '' FLOAT
MOVEMENT
6 '' VALVE
MOVEMENT
2 FEET 1 FOOT
VALVE A
VALVE B
FIGURE 22
SET POINT
1.5 ''
1.5 ''
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 19
ILD Symbols and Abbreviations(Cont'd)
Level Control (Cont'd). Figure 23 shows the arrangement for a P Band of 200%. A total set
point deviation of 12" causes a 6" movement of the control valve.
PB PB PB
200 % 100 % 50 %
12 '' FLOAT
MOVEMENT
6 '' VALVE
MOVEMENT
2 FEET 1 FOOT
VALVE A
VALVE B
FIGURE 23. PIVOT TO THE LEFT
SET POINT
6 ''
6 ''
SPAN
SPAN
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 20
ILD Symbols and Abbreviations(Cont'd)
Level Control (Cont'd). Reset may have a time value next to it. Reset is used with proportional
control to return a variable back to its set point. (Reset is also sometimes called Gain.)
For example, Figure 24 shows a stable process. The level is at set point and 50 gpm is
entering and leaving the tank.
50 GPM
FIGURE 24. STABLE PROCESS
SET POINT
WATER
OUT
WATER
IN
MINIMUM LEVEL
MAXIMUM LEVEL
50 GPM
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 21
ILD Symbols and Abbreviations(Cont'd)
Level Control (Cont'd). If for some reason the flow leaving the tank increases to 60 gpm the
level will fall. The float will then cause the control valve to open and input flow will increase.
However, the valve cannot adjust until after the level has deviated from set point. Hence, a
new stable condition may exist which is not at set point, as shown in Figure 25. The
difference between the new level and the set point is called offset.
60 GPM
FIGURE 25. STABLE BUT OFFSET
60 GPM
OFFSET
WATER
OUT
SET POINT
WATER
IN
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 22
ILD Symbols and Abbreviations(Cont'd)
Level Control (Cont'd). Reset is used to help the proportional control to bring the variable back
to set point. It does this by sending an extra signal to the control valve. The signal adjusts the
control valve until set point is reached. Then the reset signal stops.
The reset mechanism is part of the controller. It has a scale on which different times can be
set, for example from 0.1 to 50 minutes. A setting of 0.5 means that the control valve will be
adjusted every 0.5 minutes until set point is reached.
Derivative also may have a time value next to it. It is usually used only in Temperature
Control Loops. Derivative is sometimes called Rate Action or Integral.
Derivative is necessary because proportional plus reset control may take a long time to correct
temperature deviations from set point. Derivative action is concerned with how fast a
temperature is changing from set point.
If temperature is deviating only slowly from set point, the controller will make only small
adjustments to the control valve. Derivative action senses the speed of the change
immediately the change begins (unlike reset, which responds after the change has occurred
and caused offset).
If the rate of change is high, derivative immediately causes a large adjustment to be made to
the control valve to bring the temperature under control.
Derivative action stops when the temperature stops changing.
The derivation mechanism is also a part of the controller. It uses the same kind of time scale
as the reset unit.
Action will have Direct or Reverse next to it. Direct means that if the input signal to an
instrument is increased, the output signal from the instrument will also increase. Reverse
means that if the input signal increases, the output signal decreases.
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 23
ILD Symbols and Abbreviations(Cont'd)
Indicating Controller. Figure 26 shows the symbols used for an indicating controller. They are
the same as for a basic controller except that a scale range for the variable will be given.
Scales may be linear or square root.
Linear scales are used for those process variables which change in direct proportion to
changes in instrument output signals, e.g. level, temperature, pressure. Flow measurements,
however, are taken from differential pressure readings at an orifice plate. Differential
pressure changes in proportion to the square of the flow rate. Therefore, the square root of the
differential pressure must be found (or extracted) from a differential pressure signal in order
to find the flow rate. This is why some scales are square root.
FIGURE 26. INDICATING CONTROLLERS
INDICATING
CONTROLLER
S
INDICATING CONTROLLER
WITH MANUAL CONTROL UNIT
MARK NO.
SET POINT
P. BAND
RESET
DERIVATIVE
ACTION
OUT
IN
SCALE RANGE
IN
MARK NO.
SET POINT
P. BAND
RESET
DERIVATIVE
ACTION
SET
OUT
SCALE RANGE
( IND. CONTROL )
( MANUAL CONTROL
UNIT )
S
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 24
ILD Symbols and Abbreviations(Cont'd)
Panel-Mounted Indicator. Figure 27 shows the symbol for a panel-mounted indicator. Range
gives the range for the indicator scale.
FIGURE 27. PANEL MOUNTED INDICATOR
INDICATOR
( 1 TO 3 POINTERS )
MARK NO.
RANGE
IN
Strip Chart Recorder. Figure 28 shows the symbol for a strip chart recorder. Mark numbers
and Range are given for each pen.
If more than one instrument loop is being recorded, additional input line symbols are added
for each loop. Notes may be given to explain more about the symbols.
GND, L1 and L2 mean Ground, Line 1 and Line 2, respectively.
MARK
RANGE
RECORDER
( 1 TO 3 PENS )
GND
IN
L 1
L 2
MARK
RANGE
MARK
RANGE
1 ST. PEN
2 Dn. PEN
3 Dr. PEN
1 ST. PEN
2 Dn. PEN
3 Dr. PEN
FIGURE 28
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 25
ILD Symbols and Abbreviations(Cont'd)
Two-Purpose Instrument Devices. Figure 29 shows the ILD symbols for two components of a
loop combined into one.
The top output signal goes to a level transmitter or controller. The bottom output signal goes
to a final control element, such as a control valve.
LEVEL TRANSMITTER /
CONTROLLER
WITH AIR SUPPLY
CONNECTION ( DISPLACER )
OUT
S
VESSEL NO. IN
MARK NO.
SET POINT
P BAND
RESET
AND
OUT
MARK NO.
RANGE
FIGURE 29. TWO - PURPOSE INTRUMENT DEVICES
TRANSMITTER CONTROLLER
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 26
ILD Symbols and Abbreviations(Cont'd)
Level Transmitter/Controller. Figure 30 shows the symbols used to denote a transmitter or a
controller. In each case, the appropriate information blocks would be filled in and the other
blocks left blank.
FIGURE 30. LEVEL TRANSMITTER / CONTROLLER
PRESSURE TRANSMITTER
OR CONTROLLER WITH AIR
SUPPLY CONNECTION
OR
MARK NO.
RANGE
TRANSMITTER
S
OUT
IN
E
Q
U
I
P
M
E
N
T

O
R

L
I
N
E

N
U
M
B
E
R
MARK NO.
RANGE
SET POINT
P BAND
RESET
DERIVATIVE
ACTION
TEMPERATURE TRANSMITTER
OR CONTROLLER WITH AIR
SUPPLY CONNECTION
OR
MARK NO.
RANGE
TRANSMITTER
S
OUT
IN
E
Q
U
I
P
M
E
N
T

O
R

L
I
N
E

N
U
M
B
E
R
MARK NO.
RANGE
SET POINT
P BAND
RESET
DERIVATIVE
ACTION
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 27
ILD Symbols and Abbreviations(Cont'd)
Three-Way Solenoid Valve. Figure 31 gives the symbol for a three-way solenoid valve. This
symbol is usually connected to the symbol for the final control element. Most solenoid valves
are not very large. They are commonly used to shut off instrument air supply to control
valves.
MARK NO.
SOLENOID OPERATED
THREE - WAY VALVE
ENERGIZED P - A
DEENERGIZED A - E
FIGURE 31.
P
E
A
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 28
ILD Symbols and Abbreviations(Cont'd)
Three-Way Valve Operation. Figure 32 shows the normal operation of a three-way valve. When
the coil is energized, air flows to the control valve actuator without interruption.
When the solenoid coil is de-energized (which is what happens when the Emergency Shut
Down (ESD) button is pressed) the three-way valve closes. This blocks the flow of air to the
control valve. At the same time, the 3-way valve allows the air which is operating the control
valve to vent to the atmosphere. This causes the control valve to close.
FIGURE 32
TO
ACTUATOR
AIR
SUPPLY
A
E
P
ENERGIZED
FROM
ACTUATOR
AIR
SUPPLY
A
E
P
DEENERGIZED
P - PRESSURE A - ACTUATOR E - EXHAUST
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 29
INTERPRETING ILDS
Handout No. 2 (Drawing 461-J-NA-942815) is a simplified ILD. The Title Block, shown in
Figure 33 below, identifies the loop that is on the drawing.
It is Flow Control Loop 101 (FC-101). The block says that FC-101 is part of a crude oil
pipeline at Berri-3 Plant, Ras Tanura, The Plant Number is 461.
The index letter, J, is the standard index letter for Instrument Loop Diagrams.
The Reference Drawing Block gives the drawing numbers of P&IDs and Instrument
Installation Schedules on which FC-101 can be found.
Reference is also made to the drawing numbers of Rack Power Distribution (Rack Pwr Dist.)
and ILD PC-301.
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 30
INTERPRETING ILDS (Cont'd)
Handout No. 2 shows that the ILD is divided into four parts: FIELD, FIELD JUNCTION
BOX, CONTROL ROOM PANEL REAR and CONTROL ROOM PANEL FRONT. (Large
junction boxes are sometimes called Marshalling Boxes.)
When reading an ILD, it is usual to start at the sensing element. In Handout No. 2, this is an
orifice plate, as shown in Figure 34.
Note: The Figures given inside the circles are for this module reference only. They do not
appear on an actual ILD.
1
7
3
2
6
5
4
8
9
ILD SENSOR AND TRANSMITTER
FIELD
FIGURE 34
MARK NO. FT - 101
RANGE
H L
0-100''WC
10'' - P - 145 - 1A1
MARK NO.
BORE
FE - 101
6''
E-9007
4-20 m ADC
J O B O R D E R N O . I N D E X P L A N T N O . S H TD R A W I N G N O . R E V . N O .
6 1 8 4 5 J 4 6 1 N A - 9 4 2 8 1 5 4 7
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 31
INTERPRETING ILDS (Cont'd)
1
The mark number (which is the same as a tag or identification number) of the
flow element is 101 (that is, FE-101). The BORE of the flow element is 6"
(that is, the hole through the orifice plate is 6" diameter).

H and L show on which side of the orifice plate high and low pressures are
sensed.

The pipeline is 10" pipe and the pipeline number is 10"-P-145-1A1.

The Mark Number for the Flow Transmitter is 101 (that is, FT-101). The
pressure measuring range of the transmitter is 0-100" water column (WC).

Auxiliary process lines take high and low pressure to the flow transmitter.

This is an electrically operated flow transmitter, as shown by the electric signal
lines .

The electrical signal lines are shielded all the way from the transmitter to the
next loop component.

E-3007 is the identification number of the electrical signal line cable.

Electronic loops use standard instrument signals of either 4 to 20 mA or 10 to
50 mA, direct current. The drawing shows that 4-20 mA DC is being used.
2
At
3
4
5
6
7
8
9
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 32
INTERPRETING ILDS (Cont'd)
Figure 35 shows the JUNCTION BOX and CONTROL ROOM PANEL REAR instrument
signal wire line connections.
(1) Shows JUNCTION BOX-200 (J.B. 200). The left side cables come from the flow
transmitter and enter Terminals 1 and 2. Terminal 3 is used to ground the shielding on
the signal line.
(2) C-8101 identifies the signal line cable coming from JB 200.
(3) J. B. 320 is located behind the control room panel, that is, panel rear.
(4) CC-517 identifies the wire cable from JB 320 that goes to Flow Recorder (FR-101) on
the Control Room front panel.
(5) The wire line symbol shows a connection between Terminals 12 and 13. This is done
in order to complete a circuit.
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 33
INTERPRETING ILDS (Cont'd)
Figure 36 gives information about control panel instruments.
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 34
INTERPRETING ILDS (Cont'd)
(1) These are the incoming signals from JB 320.
(2) This is the ILD symbol for a three-pen recorder.
(3) Mark No. 1st Pen is for flow recorder FR-101. 0-10 identifies the part of the strip
chart which is recording the flow in loop 101. The square root sign () shows that a
square root scale is being used.
(4) The 2nd Pen is recording the pressure in control loop PC-301. The range 0-100 refers
to the part of the strip chart that is recording pressure. The note symbol,
2
, refers to
the reference drawing in the Legend block.
(5) These are incoming signals from JB 320 to flow indicating controller, FIC-101.
(6) This is the basic ILD symbol for an indicating controller.
(7) These are the outgoing symbols from FIC-101.
(8) CC-518 identifies the cable between the FIC-101 and JB 320.
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 35
INTERPRETING ILDS (Cont'd)
Figure 37 below shows again the wiring terminations In the junction box and rear panels.
(Reference should be made to the ILD as a whole.)
(1) The outgoing signals from FIC-101 go to the same JB 320 as do the incoming signals
to FIC-101. Different terminals in JB 320 are used for the incoming and outgoing
signal wires.
(2) C-8101 is the same cable that has the incoming signal lines.
(3) This is JB 200. It has the signal lines from the flow transmitter, FT-101. It also has
the outgoing signals wired to terminals 5 and 6.
(4) E-1115 identifies the signal cable wires from JB 200 to the field instruments.
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 36
INTERPRETING ILDS (Cont'd)
Figure 38 below shows the field-mounted instruments which complete the control loop.
FIGURE 38. ILD TRANSDUCER AND CONTROL VALVE
10''- P - 145 - 1A1
S
MARK NO.
SIZE RATING
A. F. ACTION
FCV - 101
10'' GLOBE
CLOSE
MARK NO. FTd - 101
S
1
2
3
4
5
6
(1) These are the signal lines from JB 200.
(2) This is the symbol for a transducer. Mark No. identifies it as Ftd-101.
(3) The transducer changes the incoming electrical signal to an outgoing pneumatic signal.
(4) This is the basic ILD symbol for a control valve.
(5) The information block shows that the control valve is Flow Control Valve FCV-101.
It is a 10" globe valve. A.F. Action Close means it will close if there is an air failure.
(6) This is the pipeline number. It is 10" pipe, line number S-145.
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 37
INTERPRET AN ILD FOR A PNEUMATIC INSTRUMENT CONTROL LOOP
Figure 39 shows a simplified section of a P&ID. Control Loop number 113 is controlling the
level of tempered water in the surge drum 139-D-211.
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 38
INTERPRET AN ILD FOR A PNEUMATIC INSTRUMENT CONTROL LOOP
(Cont'd)
The level in the drum is sensed by the level transmitter, LT-113. The transmitter sends
pneumatic signals to a level indicating controller, LIC-113, and to two level switches LS-
113A and
LS-113B.
In turn, LIC-113 sends pneumatic signals to a level control valve, LCV-113. If the level in
the drum goes low, the signals cause the control valve to open. This allows more make-up
water to flow into the drum. If the level goes high, the signals cause the valve to close. This
reduces the make-up water flow rate.
The level switches are connected to high and low alarms (XA-3-32 and XA-3-33). The
switches are set to operate if the drum level goes dangerously high or dangerously low. They
are operated by the pneumatic signals coming from the level transmitter. The 3 refers to the
row number on the control panel. The 32 and 33 respectively refer to the column numbers.
They give the locations on the control panel where the alarms can be found.
Figure 40 shows how the level control loop would look on an ILD.
The ILD is shown in sections in Figure 41 through 44
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 39
INTERPRET AN ILD FOR A PNEUMATIC INSTRUMENT CONTROL LOOP
(Cont'd)
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 40
INTERPRET AN ILD FOR A PNEUMATIC INSTRUMENT CONTROL LOOP
(Cont'd)
Figure 41 is the ILD symbol for the level indicating controller LIC-113. The range is from 0-
100. Because it is a level controller, the scale range is a percentage. Levels are usually
indicated as a percentage of the vessel capacity. 0 to 100, therefore, is the range from
completely empty to completely full. Note the triangle and letter S to indicate air supply.
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 41
INTERPRET AN ILD FOR A PNEUMATIC INSTRUMENT CONTROL LOOP
(Cont'd)
Figure 42 is the symbol for a level transmitter. The symbol P/P means that the differential,
pressure (P) sensed by the transmitter is sent to the loop controller as a pressure (P). It will
be sent as a pneumatic pressure signal of 3 to 15 psi.
The figure shows that the transmitter senses the differential pressure at equipment number
139-D-211. This is the surge drum shown on the P & ID.
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 42
INTERPRET AN ILD FOR A PNEUMATIC INSTRUMENT CONTROL LOOP
(Cont'd)
Figure 43 shows the level control valve. 3"-SC-160-IAIA identifies the make-up water
pipeline. This is the line the level control loop uses to control the level in the surge drum.
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 43
INTERPRET AN ILD FOR A PNEUMATIC INSTRUMENT CONTROL LOOP
(Cont'd)
Figure 44 shows the level switches in the control loop. LS-113A is the high level alarm
switch. It is set to open when it receives a 12-psi signal from the level transmitter.
LS-113B is the low-level alarm switch. It will open when it receives a 6-psi signal from the
level transmitter.
Figure 40 shows that the switches are connected to alarms XA-3-32 and XA-3-33 on the front
panel of the control room. The alarms can be seen on windows 3-32 and 3-33
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 44
INTERPRET AN ILD FOR AN ELECTRONIC INSTRUMENT CONTROL LOOP
Handout No. 3 (Drawing Number J-415-NB-582636) shows an electronic instrument control
loop. Electronic loops are more complicated than pneumatic loops. There are two reasons for
this:
Loop components are both field mounted and located in the control room. Also, the
instruments may be great distances away from each other. They must be connected
together by electric wires. The wires may pass through one or more junction boxes.
The electric wiring connections between instruments must be done in such a way that
complete electric circuits are formed.
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 45
INTERPRET AN ILD FOR AN ELECTRONIC INSTRUMENT CONTROL LOOP
(Cont'd)
The top of Handout No. 3 shows a pressure control loop, shown again below in Figure 45.
The symbol for a control valve can be seen. It has Tag No. PCV-51. It is connected to
pipeline 4"-5-304-6A1 and has a 20-psig air supply.
Fig 45
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 46
INTERPRET AN ILD FOR AN ELECTRONIC INSTRUMENT CONTROL LOOP
(Cont'd)
Figure 46 shows the symbol for the transducer. You can tell it is a transducer because it has
two electrical connections, an air supply and a pneumatic output line. The two electric wires
are part of the control loop electric circuit. The current through the transducers varies with
changes in process variable values. Air at a constant pressure of 20 psig is supplied to the
transducer. The output value of the air pressure varies with changes in the transducer current.
Hence, electric signals are converted to pneumatic signals.
The symbol for a transducer is sometimes drawn as a square, but Foxboro, the company
which makes the instrument, draw it as a circle.
The letters E and B identify the terminal connections inside the transducer junction box. Note
again that the transducer needs a 20-psig air supply. The symbols shown in Figure 47 are for
locally-mounted air regulators.
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 47
INTERPRET AN ILD FOR AN ELECTRONIC INSTRUMENT CONTROL LOOP
(Cont'd)
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 48
INTERPRET AN ILD FOR AN ELECTRONIC INSTRUMENT CONTROL LOOP
(Cont'd)
Figure 48 shows the symbols for the field-mounted pressure indicator (PI-51) and the field-
mounted pressure transmitter (PT-51).
The transmitter is shown to be connected to a pipeline identified as 4"-S-305-3A1. The
circular symbol marked 'IND' shows that the transmitter has an indicator mounted on it.
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 49
INTERPRET AN ILD FOR AN ELECTRONIC INSTRUMENT CONTROL LOOP
(Cont'd)
Figure 49 shows the field junction box. All the instruments of Loop P-51 are wired into this
box. The box is identified as ETB3. The number that follows the ETB3 symbol is the
terminal number for the wire inside the terminal box.
The symbol marked 503 is a shield for the cable coming out of the junction box. It shields the
cable from outside electrical interference.
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 50
INTERPRET AN ILD FOR AN ELECTRICAL INSTRUMENT CONTROL LOOP
(Cont'd)
Figure 50 shows that the wiring goes from the junction box, through a marshalling box, and to
a panel interconnection junction box in the control room.
A marshalling box (MB) is simply a big junction box. It is usually located just inside the
control room building. It is a collection point for field wiring that comes into the control
room from many parts of the plant. From the marshalling box, the instrument loop wiring is
organized and routed to various display areas and panels in the control room.
The number of marshalling boxes in a plant depends on the size of the plant. Each box is
numbered. Figure 50 shows that on this ILD the marshalling box is MB7. The number that
follows each MB7 is the terminal number inside the box. There may be hundreds of wires in
each box.
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 51
INTERPRET AN ILD FOR AN ELECTRICAL INSTRUMENT CONTROL LOOP SET
Figure 51 shows, at the left, numbered blocks between the marshalling block and the panel
interconnection junction box. These are the individual wire numbers between the boxes.
The panel interconnection junction box is located behind the control room panel. It is usually
close to the loop controller. A short cable connects the controller to the junction box. The
cable carries a number of wires each insulated from the others. The wires are color coded.
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 52
INTERPRET AN ILD FOR AN ELECTRONIC INSTRUMENT CONTROL LOOP
(Cont'd)
The panel interconnection junction box symbols are shown in Figure 52.
The colors identify wires inside the connecting cable. Each of the lines below the colors
represents one wire inside the cable. The letter indicates the connection point on the cable
plug. For example, the violet wire in the cable is connected to point F in the cable plug. You
can also see from the figure that the violet wire is connected to the terminal strip at connection
number 5. Figure 53 shows the cable plug.
The letters BK at the top of the numbers column identify the terminal strip inside the panel
interconnection junction block. The ILD shows the identification of other terminal strips,
such as BH1, EA1 and so on.
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 53
INTERPRET AN ILD FOR AN ELECTRONIC INSTRUMENT CONTROL LOOP
(Cont'd)
The (+) and (-) signs indicate the polarity of each numbered terminal that is being used.
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 54
INTERPRET AN ILD FOR AN ELECTRONIC INSTRUMENT CONTROL LOOP
(Cont'd)
Figure 54 shows that there is a 100-ohm resistor connected across terminals 3 and 4 in the
junction box. Resistors are needed whenever an input signal is too high for other instruments
in the control loop.
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 55
INTERPRET AN ILD FOR AN ELECTRONIC INSTRUMENT CONTROL LOOP
(Cont'd)
Figure 55 shows the symbol for the pressure controller.
The controller needs a 118V 60Hz power supply. FOP No. F3-10 means that the instrument
is located on the Face Of Panel F3, in position 10. On other ILDs the abbreviation BOP
(Back of Panel) may sometimes be seen.
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 56
INTERPRET AN ILD FOR AN ELECTRONIC INSTRUMENT CONTROL LOOP
(Cont'd)
Figure 56 shows the recorder and its connections.
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 57
TRACING CURRENT FLOW IN CONTROL LOOPS
The symbol at the bottom right-hand corner of Figure 56 is for a three-pen recorder. Pen
number 2 records pressure values on PR-51. The recorder operates with a 118V, 60Hz
supply.
In order to record pressure values, the recorder must be connected to the pressure control
loop. It must receive signals that indicate the pressure values.
A study of the ILD, on Handout No. 3, shows that the power to operate the pressure
transmitter, PT-51, is supplied by the pressure controller, PC-51. The controller also operates
with a 118V, 60Hz supply. The ILD shows that a multi-wire cable connects the pressure
controller output to terminal 1 on terminal strip BK. A wire connects terminal 1 to the
positive side of the pressure transmitter, PT-51. The transmitter acts as a variable resistor. Its
resistance depends on the value of the process variable. Therefore, the current flowing
through the control loop changes as the transmitter resistance changes. And this change is a
measure of the process variable.
From the transmitter, the current flows through the pressure indicator, PI-51. From there it
goes to terminal BK-3. From BK-3 the current flows through a 100- ohm resistor to BK-4. A
wire connects BK-4 to BH-6. A wire from the multi-wire cable connects BH-6 to the plug.
The ILD shows this connection to be letter H on the plug (a violet colored wire). The current
goes to operate PR-51.
In order for the current to flow, there must be a complete circuit. Therefore, the current that
operates PR-51 must be returned to its source, PC-51. The ILD shows that this is done by
connecting a wire from the multi-wire cable (a brown wire) to terminal 7 on terminal strip
BH. This wire acts as a return wire. It takes the return current from PR-51 to BH-7. A wire
connects BH-7 to terminal 2 on terminal strip BK. A wire from the multi-cable wire is
connected to BK-2. The IDL shows this to be connection U on the plug (a grey color wire).
The connection completes the circuit.
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 58
INTERPRET AN ILD FOR A PNEUMATIC INSTRUMENT CONTROL LOOP
(Cont'd)
Figure 57 shows the symbol for a panel-mounted alarm. The numbers 1 - 10 identify the
location of the alarm in the alarm display panel, i.e., Row 1, Column 10.
Tracing the wires from the alarm shows that it is connected to the multi-wire cable plug at
terminals 6 and 7 on terminal strip EO. Temperature switch TS-54 is connected by the multi-
wire cable (connections J and B) to these same terminals. Hence, the current passing through
TS-54 can also pass through alarm XA-1-10. If the supply fails, the switch will trip and set
off the alarm.
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 59
Computer Relays
Computer Relay Symbols
Symbols are used to show Computer Relays on ILDs. Details of other information related to
the relays may also be given. This section of the module covers the symbols and related
information.
Manufacturer's Symbols. Saudi Aramco uses instrumentation supplied by two manufacturers,
Foxboro and Honeywell. Relays supplied by these companies are drawn differently on ILDs.
An example is shown in Figure 58. The symbols are for adder/subtractor cards.
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 60
Computer Relays (Cont'd)
Manufacturer's Symbols(Cont'd). Foxboro instruments use the words "adder" or "summer" on
their cards (from "sum" meaning 'add').
Foxboro summer card output terminals are always the number 2 terminals. Honeywell
adder/subtracter card output terminals are always the number 6 terminals.
TP (terminal panel) followed by a mark number is used to identify terminals on Honeywell
Computer Relays.
Handout No. 4 (Drawing No. R84-A-NA-B44995 Sheet 1) is a P&ID for a deethanizer
system. Handout No. 5 (Drawing No. R84-J-NB46327 Sheet 1 A) is the ILD for Flow
Control Loop F-010 shown on the P&ID.
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 61
Computer Relays (Cont'd)
Manufacturer's Symbols(Cont'd). The ILD on Handout No. 5 shows that Honeywell relay
instruments are being used.
The ILD shows that the following instruments are to be found in the field (that is, out in the
plant area).
Flow Transmitter, FT-010 NOTE: On this ILD the mark
Flow Element, FE-010 numbers also include the Plant
Flow Indicator, FI-010 number (R84).
Flow Transducer, FTd-010
Flow Control Valve, FCV-010
It also shows that the following instruments are found on the front of Control Panel CP-R84-
101.
Flow Recorder, FR-010
Flow Totalizer, FQI-010
Flow Indicating Controller, FIC-010
Note that the flow indicator, FI-010, has a (non-linear) square root scale. This is because the
indicator is connected in series with the flow transmitter, FT-010, and the transmitter's
differential pressure signals have not yet passed through the square root extractor.
The auxiliary rack section shows that there are three Computer Relays being used. These are:
FY-010A - a multiplier/divider card
FY-010B - a square root extractor
FQ-010 - a flow integrator card.
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 62
Computer Relays(Cont'd)
Computer Relay Symbols (Cont'd). Note that the function of the relays is shown at the top, as
shown in Figure 59.
The square root sign () indicates a square root extractor. The multiplication sign (X)
indicates a multiplier/divider card which is performing multiplication. (If a division sign ( )
were above the relay, the card would be performing a division function.) The integral sign (_)
indicates an integrator card.
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 63
Computer Relays (Cont'd)
Computer Relay Symbols(Cont'd). Figure 60 shows where the other information about the relays
was obtained from the ILD.
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 64
Computer Relays (Cont'd)
Computer Relay Symbols(Cont'd). A study of the ILD (Figure 60) shows the symbol
2
10-TT-016-12
The arrow enters the multiplier card at terminal number 8.
10-TT-016 tells us that a temperature transmitter, TT-016, is sending a signal to the multiplier
card. The 12 tells us that a wire from terminal 12 on the transmitter is connected to terminal 8
on the multiplier.
The number 2 in the box refers us to the Reference Drawings given on the right-hand side of
the ILD.

2
refers to ILD NB-B46327, sheet 35.
This kind of information is characteristic of ILDs. They show where an input signal comes
from and, if necessary, will make reference to another ILD to show the destination of the
signal.
Block number 7, just above TPAI-1, shows that the output from terminal 3 goes to 10TY-
010B. The reference drawing section refers to ILD NB-B46327 sheet 29. Sheet 29 is shown
in Handout No. 6. (Drawing No. R84-J-B46327 Sheet 29.) It shows that a TYPE E
thermocouple is used to sense the temperature in line 16"-P-1002-3A1. It also shows that a
3", globe type temperature control valve is fitted into line 3"-SC-1001-3A1C.
The symbols shown at the center of the auxiliary rack section of the ILD are for a computer
system. They are shown in Figure 61.
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 65
Computer Relays (Cont'd)
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 66
Computer Relays (Cont'd)
Computer Relay Symbols(Cont'd)
Note that the symbol MV/I represents the temperature transmitter TT-10. MV/I means it is
converting millivolts to current. Two input signals are shown entering the transmitter. One is
from TE-010; the other is from TE-015. Block 3 says that TE-015 is found on Sheet 34.
17/C cable, in the Rack Section, means 17 conductor cable. It is a cable containing 17
conductor wires. The cables are connected to the control instruments.
The ILD shows that lines 7 and 10 out of TPA-2-2 can be traced to the computing relays TY-
010A and TY-010B respectively.
TY-010A is the signal selector. The symbol above the card (<) is the mathematical symbol
for less than. In this case, the symbol means that the card is a low signal selector. If the
symbol was >, which means greater than, the card would be operating as a high signal
selector.
TY-010B is the adder/subtractor card. The Greek letter, capital sigma (_) above the card
means the sum of. It shows that the card is operating as an adder or subtractor, depending on
how the card is set. If a plus sign (+) is over the card, it means that the card is only adding.
The Greek capital letter delta () or a minus sign (-) is used to indicate a subtractor card.
Note that the input signal to terminal 5 on the adder/subtractor card comes from TPA1-1-3.
This shows again how ILDs are used to trace electric circuits from one drawing to another.
Other connections are shown going to sockets and pins for the computer control of the
temperature.
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 67
Instrument Systems
Saudi Aramco uses two control systems that are manufactured as complete units. The
systems are shown on ILDs. One of the systems is the Foxboro Spec 200 and the other is the
Honeywell Vutronic.
Foxboro Spec 200
'Spec' is an abbreviation for Simplified Package for Electronic Control. The basic
arrangement of the Spec 200 is shown in Figure 62.
FIGURE 62
BASIC ARRANGEMENT OF A SPEC 200 LOOP
PROCESS
TRANSMITTER
ALARMS
CONTROL
FUNCTION
OUTPUT
BUFFER AND
SIGNAL
CONVERSION
INPUT
BUFFER AND
SIGNAL
CONVERSION
4 - 20 mA
10 - 50 mA
RTD
THERMOCOUPLE
mV
VOLTAGE
P
I
0 - 10V 0 - 10V
10 - 50 mA
4 - 20 mA
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 68
Instrument Systems(Cont'd)
Foxboro Spec 200 (Cont'd)
The system is a closed loop. The block symbol marked I/P (Figure 63) is used to show Spec
200 transducers. These transducers convert current energy (I) to pressure energy (P).
FIGURE 63
I
P
Input signals such as 4-20 mA, 10-50 mA, millivolts and ohms can be used by the system.
These signals are converted to 0 - 10 Volts DC signals by input signal converters. The 0 - 10
V signals are used by rack and panel mounted instruments, such as controllers, indicators,
recorders and alarms. Using small voltage signals makes the system safe to work on.
All Spec 200 instruments are connected in parallel. This allows components to be removed
from the loop without breaking up the system. It also means that the same voltage is applied
to all components.
Output signal converters are used to send 4-20 mA and 10-50 mA signals to field instruments.
The Spec 200 system consists of two areas: the display area and the nest area, as shown in
Figure 64.
The display area contains the recorders and indicators, and provides all the information
needed by operators.
The nest area contains the circuit cards for the control, computing, input and output
converters, alarm and conditioning units.
Nest units are fitted into sections called racks.
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 69
Instrument Systems(Cont'd)
Foxboro Spec 200 (Cont'd)
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 70
Instrument Systems(Cont'd)
Foxboro Spec 200 (Cont'd)
Figure 65 shows the operation of the Spec 200.
FIGURE 65
INPUT SIGNAL DISTRIBUTION
PROCESS
TRANSMITTER
ALARMS
CONTROL
FUNCTION
OUTPUT
BUFFER AND
SIGNAL
CONVERSION
INTPUT
BUFFER AND
SIGNAL
CONVERSION
4 - 20 mA
P
I
5 VOLTS
5 VOLTS
0 - 10V
0 - 10V
0 - 50 mA
0 - 20 mA
5 VOLTS 5 VOLTS
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 71
Instrument Systems(Cont'd)
Foxboro Spec 200 (Cont'd)
Suppose the following: A process control loop is for pressure control; the set point is 15 psi;
the transmitter has a range of 0-30 psi; the current range for the transmitter is 4-20 milliamps.
From the above it follows that a set point of 15 psi is equal to 50% of the transmitter's range.
This gives a signal of 12 mA (i.e. 50% of 4-20 mA range). As long as the process pressure
remains steady at 15 psi, the transmitter sends a 12 mA signal. When the 12 mA signal
reaches the input buffer and signal converter relay card in the nest unit, it is changed to a
voltage signal.
Spec 200 operates on 0-10 V. Since 12 mA is exactly half the transmitter range, the voltage
signal would also be exactly half its range, that is, 5 V. Therefore, the relay card in the
converter sends a 5 V signal to all other components in the control loop. For example, 5 volts
will be sent to the recorder and this will be seen as 15 psi on the recorder graph.
The transducer operates on a milliamp range. Therefore, the voltage signal must be converted
back to an amperage signal before it enters the transducer. This is done by the card in the
output buffer and signal converter in the nest unit.
The Spec 200 cards are used for specific functions. Some of these functions are described
below.
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 72
Foxboro Spec 200 (Cont'd)
The Function of the 2AI-I2V Current to Voltage Converter Card. The Foxboro current converter
card Model No. 2AI-I2V is a solid state component located in the nest assembly. 2AI-I2V
stands for:
2 - A Spec 200 component
A - Analog signals in and out
I - Input instrument
I - Current signals in
2 - This is an isolated card
V - Voltage signals out
The 2AI-I2V card has only one function. It receives 4 to 20 mA signals from a field
transmitter and changes them to 0 to 10-volt signals. These are the signals needed by the
Spec 200 system. The voltage output is proportional to the current input.
The card can operate with two inputs and two outputs for dual operation. This means that the
card can receive and convert 4-20 mA signals from two transmitters.
The input (current signals) sides of the card circuit are isolated electrically from the output
sides (voltage signals). The two circuits are not connected by wires, but the input influences
the output because it passes through a transformer. This induces a proportional voltage in the
output side of the transformer coils.
Isolated cards are used because they give more protection to the cards. For example, a short
circuit in the transmitter circuit will not damage the card.
If the figure 3 were shown in place of the 2, it would mean that the card was not isolated.
The Function of the Controller Card 2AX+45. The Foxboro controller card, 2AX+45, has
electronic circuits that receive the input signals and modify them according to the control
settings. The card sends an electronic output signal to control a final control element, usually
a control valve.
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 73
Foxboro Spec 200 (Cont'd)
The Function of 2AP+ALM-AR Alarm Card. Alarm cards cause alarms to sound in the plant
control room if operating conditions become abnormal.
The Foxboro 2AP+ALM-AR is a dual alarm card. That means that it can monitor two
different variables at the same time. 2AP+ALM-AR stands for:
2 - Spec 200 component
A - Analog signals in and out
P - Process component module
ALM- Alarm
AR - Dual absolute alarm - relay output
The card can be set to send output signals to two different alarm lights. For example, the
2AP+ALM-AR alarm card could monitor pressure for a low condition and temperature for a
high condition. The card can also be set to monitor both high and low conditions for the
same process variable. It could do this using only one input signal.
The alarm card is a solid state function card that slides into a module in the nest unit. The
card has two single alarm circuits with a common power supply. Each alarm has one input,
one set point, and one output. Alarm points are calibrated from zero to 100% of scale.
The alarm card receives voltage signals from other function cards, such as a square root
extractor, or a resistance-to-voltage temperature card. It has two relays built into it, one for
each alarm circuit. When the alarm is off, the relays on the alarm card are energized. The
relay contacts are normally open (NO) and this gives a no-alarm condition, as shown in
Figure 66.
FIGURE 66
TERMINAL NUMBERS
+ -
POWER SUPPLY
TERMINAL NUMBERS
- 4
- 2
+ 2
NC
COM
NO
LAMP
OFF
RELAY CONTACTS OPEN
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 74
Foxboro Spec 200 (Cont'd)
The Function of 2AP+ALM-AR Alarm Card (Cont'd. So long as the process variable that the alarm
card is monitoring stays within its set-point range, the relay will stay energized.
Imagine that the alarm circuit is monitoring a pressure control loop. The alarm is set to come
on if the pressure goes too high. At this condition, the voltage signal coming into the alarm
card will be at the value for which the alarm card has been set. This will cause the relay to be
deenergized. When this happens the NC contacts close, as shown in Figure 67, and the alarm
light comes on.
FIGURE 67
TERMINAL NUMBERS
+ -
POWER SUPPLY
TERMINAL NUMBERS
- 4
- 2
+ 2
NC
COM
NO
LAMP
ON
RELAY CONTACTS CLOSED
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 75
Foxboro Spec 200 (Cont'd)
The Function of the 2AO-V2I V/I Card The Foxboro voltage to current (V/I) card is a solid state
component located in the nest assembly. 2AO-V2I stands for:
2 - Spec 200 component
A - Analog signals in and out
O - Output instrument
V - Voltage signals in
2 - This is an isolated card
I - Current signals out
The 2AO-V2I card has only one function. It receives input voltage signals from the controller
card and converts these 0 to 10 volts to a 4 to 20 mA output signal. This output signal is sent
to a field mounted transducer. The current output is proportional to the voltage input.
The Function of the 2AI-P2VR/V Converter Card. The Foxboro 2AI-P2V resistance to voltage
converter card is a solid state component located in the nest assembly. It produces an output
voltage signal that is proportional to the temperature of a resistance temperature detector
(RTD). 2AI-P2V stands for:
2 - Spec 200 component
A - Analog signals in and out
I - Input
P - Platinum resistance bulb
2 - An isolated card
V - Voltage output
The converter card has two inputs and two outputs for dual operation with a common power
supply.
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 76
Foxboro Spec 200 (Cont'd)
The Function of the 2AI-P2VR/V Converter Card (Cont'd). A resistance temperature detector
(RTD) is used to monitor the temperature of a process. The resistance measured by the RTD
is sent into the converter card. The card changes the measured resistance from ohms into
volts. The card is calibrated so that the low end of the temperature range corresponds to zero
volts. The high end of the temperature range is calibrated to correspond to 10 volts.
Output signals from the converter card can go to a loop controller, a temperature indicator, a
temperature recorder, and to an alarm card.
NOTE: Some cards may be identified as 2AI -N2V, where the N stands for nickel. RTDs
operate on the principle that some metals increase their electrical resistance when heated.
Other abbreviations often seen on Spec 200 cards are:
I/P for input
O/P for output
DS for Distribution
P/I means differential pressure (P) input, current (I) output.
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 77
Foxboro Spec 200 (Cont'd)
Nest Unit Card Symbols. Symbols used on Saudi Aramco ILDs for Nest Unit cards on the Spec
200 are as shown in Figure 68. Handout No. 7 (Drawing No. 490-J-674433) Shows an ILD
with Spec 200 control.
FIGURE 68
NEST UNIT CARD SYMBOLS
A: (PY - 101A)
B: PY - 102A
C:
D: REC. DIST.
E: 4 - 2 - /
F: 2AX + DSI
+ 1
- 1
+ 4
- 4
+ 2
- 2
A: (PY - 101A)
B: PY - 102A
C:
D: ANALOG INPUT
E: 4 - 5 - 3
F: 2AI - 13V
28
29
30
Note the word analog on some of the card symbols. This means that the card is operating
with numbers that are represented by directly measurable quantities, such as voltage,
amperage. That is, the numbers are analogous to physical quantities. Compare this with
digital which means that operation is made with numbers and is represented by numbers.
Note also the letters A, B, C, D, E and F. These will be given as a legend on ILDs for Spec
200. They identify each function of the card in the rack area. See Figure 69. A, B and C tell
us the Tag Numbers of the respective loops. 'D' tells us the function of the card. For example
in Figure 68 one card is an analog input card and the other is a recorder distribution card. 'E'
tells us the location of the card. For example, 4-5-3 means that the card is in rack 4, nest 5
and is card 3. 'F' tells us how to identify the card in a nest unit. For example, 2AI-13V will
be printed on the card near the bottom.
LEGEND
A : TAG NO. LOOP A
B : TAG NO. LOOP B
C : TAG NO. LOOP C
D : FUNCTION
E : LOCATION REF.
F : MODEL NO.
FIGURE 69. LEGEND
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 78
Interpreting Foxboro Spec 200 ILD's(Cont'd)
Handout No. 8 (Drawing No. 490-J-NB-67483) shows a Spec 200 loop ILD. It is for a level
control loop L-360 at Ras Tanura Refinery.
Figure 70 shows part of the ILD.
The variable being measured is the level in vessel 4900 - 14. The ILD shows (inside the
vessel) the high level alarm (HLA) is 3 feet and the low level alarm (LLA) is 1 foot 8 inches.
The level transmitter (LT-360) senses the level in the vessel. The ILD shows that the
transmitter output is a pneumatic signal. The signal will vary between 3 and 15 psi. The level
measurement is indicated on a locally mounted indicator, LI-360. The same pneumatic signal
that indicates the level value is sent to a transducer, LTd-360A, Model E11GM. The ILD
shows that LTd - 360A converts the pressure signals to Milliamp signals (i.e., 3 - 15 psi
pneumatic signals are converted to 4 - 20mA signals).
FIGURE 70. INPUT CIRCUIT
TAG
MODEL
RANGE
2500T-2495
60 "
LT - 360
TAG
MODEL
CAL.RANGE
EIIGM
3 - 15#
LTd. - 360 A
RED
GREY
P / I
+
-
ASHCROFT 1279A
TAG
MODEL
CAL.RANGE 0 - 1000
LI - 360
LOCATED NEAR
LCV - 360
IND.
FISHER
LEVEL
TRANSMITTER
67 FR
S
490D-14
HLA
LLA
3
'
-

0
"
1
'
-

8
"
L
I
N
E

N
O
.
4
"

-

C

-

4
6

-

3
A
I
FIELD
JUNCTION
BOX
MARSHALLING
BOX
MTC #2
A : LY - 358
B : LY - 360A
C :
D : ANALOG INPUT
E : 8 - B6
F : 2AI - 13V
0
-1
+1
+3
+2
-2
0
+4
-3
-4
DATA LOGGING
CONNECTOR 8
LDL - 360
23
24
8 -12+
8 -12-
368
369
23
24
ETB
#6
RACK AREA
FIELD
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 79
Interpreting Foxboro Spec 200 ILD's(Cont'd)
Tracing the two output wires from LTd - 360A shows that they are connected to terminals +2
and -2 on card 2AI - I3V. This card has two inputs and two outputs. The card model number
indicates that the card is not isolated electrically.
The 4-20 mA input at terminals 2 is found as an output at terminals +4 and -4 of the card.
Figure 71 shows that one pair of wires goes to a data logging connector (Level Data Logging
(LDL-360). This is for a computer connection. The computer receives and records the level
signal, but it does not control anything in the loop.
Another pair of wires goes to terminals +1 and -1 on the alarm card 2AP - ALM - A. The
terminals are jumped to terminals +3 and -3. This gives a single input to both alarm circuits
(+3B is LS-360 (H); -3 is LS-360 (L) .)
One alarm circuit responds to a high level. The other responds to a low level. As long as the
process level remains between the high and low set points, no alarm will be given.
FIGURE 71. 2AI - I3V OUTPUT
FIELD
JUNCTION
BOX
MARSHALLING
BOX
MTC #2
8 -12+
8 -12-
368
369
23
24
ETB #6
DATA LOGGING
CONNECTOR 8
23
A : LY - 358
B : LY - 360A
C :
D : ANALOG INPUT
E : 8 - B6
F : 2AI - 13V
0
-1
+1 +3
+2
-2
0
+4
-3
-4
RACK AREA NO. 8
LDL - 360
24
A : LS - 360 ( H )
B : LS - 360A ( L )
C :
D : ALARM
E : 8 - E9
F : 2AP - ALM - A
-1
+1 +3
+2
-2
+4
-3
-4
+5
-5
-1
+1
TO FY - 360A
NB - 674434
1
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 80
Interpreting Foxboro Spec 200 ILD's(Cont'd)
Figure 72 shows the outputs. It can be seen on the symbols that terminal 9 refers to the high
(H) alarm, and terminal 10 to the low (L) alarm.
FIGURE 72. ALARM CIRCUIT
A: 9: X A -2 -3 (H)
+12
-12
+10
-11
+11
-10
-9
+9
+8
-8
-7
+7
B: 10: X A -2 -4 (L)
D: ALARM DIST.
C:
E: 8 - F10
F: 2AX + DSI
+1
-1
-2
+3
+2
-6
-3
+4
-4
+5
-5
+6
A: 9: X A -2 -3 (H)
-5
+5
+4
-4
-3
+3
B: 10: X A -2 -4 (L)
D: ALARM
C:
E: 8 - E9
F: 2AP - ALM -A
+1
-1
-2
+2
TO FY-360 A
NB - 674434
+1
-1
TO ALARM
RACK 15
Terminals +2 and -2 are for output 1. The wires from terminal 2 can be traced to the alarm
distribution card 2AX +DSI, terminals +9 and -9. This is the high level signal input.
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 81
Interpreting Foxboro Spec 200 ILD's(Cont'd)
Terminals +5 and -5 on 2AP - ALM - A are wired to terminals +10 and -10 on 2AX + DSI.
These are the low-level input terminals.
If there is a high or low alarm, the distribution card will send a signal to Alarm Rack 15,
through a standard 2AK cable. The ILD shows that the annunciator XA - 2 - 3 illuminates for
a high-level alarm. Annunciator XA - 2 - 4 lights up for a low-level alarm.
Figure 73 shows the 2AP - ALM - A card. It shows that input terminals +3 and -3 have two
additional pairs of wires connected to it.
FIGURE 73. CONTROL INPUT CIRCUIT
A : LY - 360
B :
C :
D : ANALOG CNTRL.
E : 8 - D5
F : 2AC + A4
-1
+1 +3
+2
-2
+4
-3
-4
A : LS - 360 ( H )
B : LS - 360A ( L )
C :
D : ALARM
E : 8 - E9
F : 2AP - ALM - A
-1
+1 +3
+2
-2
+4
-3
-4
+5
-5
-1
+1
TO FY - 360A
NB - 674434
TAG LIC - 360
MODEL 230SM
LOCATION P10 - 8
SET PIONT
P. BAND
RESET
ACTION REVERSE
+5
-5
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 82
Interpreting Foxboro Spec 200 ILD's(Cont'd)
One pair goes to a computing relay FY - 360A which can be seen on drawing NB - 674434.
The other pair goes to terminals +1 and -1 on the top of controller card 2AC + A4. It is these
two connections that provide the O - 10v signal for the controller.
The output signals of the control card are +2 and -2 as shown in Figure 74.
The O - 10 volt signal enters the voltage to current connector card 2AO - V2I + P + P at
terminals +4 and -4. The 4 - 20mA output signals leave from terminals +2 and -2. After
passing through the marshalling and field junction boxes, the mlliamp signals enter the
transducer LTd - 360B. The transducer converts the current signals to 3 - 15 psi pneumatic
signals to operate control valve LCV - 360.
FIGURE 74. OUTPUT CIRCUIT
TAG
MODEL
CAL.RANGE
3 "
AO / AFC
LCV - 360
69TA - I
TAG
MODEL
CAL.RANGE 3 - 15 PSI
LTd - 360B
RED
GREY
+
-
S
8 -10+
8 -10-
370
371
25
26
ETB
#6
A : LY - 356C
B : LY - 360C
C :
D : ANALOG INPUT
E : 8 - CI
F : 2AO - V3I + P + P
0
-1
+1 +3
+2
-2
0
+4
-3
-4
S
A : LC - 360
B :
C :
D : ANALOG CNTRL.
E : 8 - D5
F : 2AC +A4
-1
+1 +3
+2
-2
+4
-3
-4
-5
+5
-5
+5
LINE NO. 4 '' - C - 33 - 3AI
OUT
67 FR
67 FRS
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 83
The Honeywell Vutronik Control Loop
Honeywell manufacture a process control system called the Vutronik. It can be used to
control a complete system in a plant. The system is made up of five categories, as shown in
Figure 75.
FIGURE 75. VUTRONIK SYSTEM
ACCESSORY
EQUIPMENT
FIELD
EQUIPMENT
ELECTRONIC
AUXILIARY
UNIT
CONTRX
SYSTEM
CONTROL
AND
NONCONTROL
STATION
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 84
The Honeywell Vutronik Control Loop(Cont'd)
Electronic Auxiliary Units. Electronic auxiliary components are used for performing monitoring
and computing functions. The components are printed circuit cards mounted in a single-card
file. The cards provide such functions as:
alarm switches
square root extraction
millivolt to current conversion (mV/I)
resistance to current conversion (/)
Saudi Aramco uses single-card files (cases) to house auxiliary cards. The cases are mounted
behind the control panel or in a rack. Figure 76 shows a file case.
Input signals are transmitted to the card circuit through a flat flexible circuit and card-edge
selector.
Note that the case has a 16-point terminal block for connecting signal wiring.
The card receives the input signal and then performs the function for which it was set (i.e.
square root extraction, mV to I conversion, etc.). The output signals are transmitted back
through the edge connector and flexible circuit to the terminal block. Wires transmit the
signals to the control instruments in the field and control room.
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 85
The Honeywell Vutronik Control Loop(Cont'd)
Contrx System. Contrx is a plug-in system. It connects the Vutronik display panel instruments
to the field instruments. The connections are made through termination panels similar to the
one shown in Figure 77.
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 86
The Honeywell Vutronik Control Loop(Cont'd)
Contrx System (Cont'd). Signals from field instruments pass from the terminals through
multiconductor cables to the control room instruments, as shown in Figure 78.
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 87
The Honeywell Vutronik Control Loop(Cont'd)
Accessory Equipment. The Vutronik system includes accessories such as power supplies,
Zenner barriers and standby control modules.
The power supplies provide the voltages for operating Vutronik devices. A Zenner barrier is
a connection device that keeps loop current below an unsafe limit. It limits current surges and
prevents sparking due to short circuits. Standby control modules can be plugged into a loop
to allow a Vutronik controller to be removed without upsetting the process.
Field Equipment. Field equipment used on the Vutronik system include:
Flow measurement instruments
Pressure measurement instruments
Level measurement instruments
Transducers
Valve positioners
Control valves.
Vultronik transmitters use a 4 to 20mA current loop. Other devices in the system use 1 to
5vdc. Therefore, the current signal being used by the transmitters must be converted to a
voltage signal.
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 88
The Honeywell Vutronik Control Loop(Cont'd)
Changing Current Signals to Voltage Signals. Figure 79 shows a Vutronik terminal block (TPA).
Terminal number 4 is the signal common (that is, it is the terminal to which all signals return).
You saw earlier that there are eight terminal blocks on a Vutronik termination panel (TPA).
ALL number 4 terminals on a TPA are connected together internally. This produces a circuit
that carries a common voltage signal through the TPA (that is, through all eight terminals.)
FIGURE 79
1 2 3 4 5 6 7
8
9 10 11 12 13 14
+25V
DC
PV
SC
+V
-V
1 - 5V
OUT
LL
RL
# 1
AL
AL
COM
# 2
AL
RSP
TPA TERMINAL BLOCK
TRANSMITTER
250
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 89
The Honeywell Vutronik Control Loop(Cont'd)
Changing Current Signals to Voltage Signals (Cont'd). Terminal number 1 on each terminal block
is connected to a 25v dc supply. The power supply is not shown on ILDs. Terminal number
2 is the process variable input to the controller.
A jumper lead is connected across terminals 2 and 3. A 250-ohm resistor is connected across
terminals 3 and 4. The resistor helps to reduce the 25 vdc to a 1 - 5 vdc potential across
terminal 3 and the signal common. This arrangement is shown in Figure 80.
FIGURE 80
1 2 3 4 5 6 7 8 9 10 11 12 13 14
TRANSMITTER
4 - 20 mA
250
+
_
25 vdc
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 90
The Honeywell Vutronik Control Loop(Cont'd)
Changing Current Signals to Voltage Signals (Cont'd). Figure 81 is a reminder of what is meant by
signal common. It is the common point on a parallel circuit through which current is returned
to its source.
FIGURE 81
R
1 2
R
3
R
CONVENTIONAL DRAWING
OF CIRCUIT
SIGNAL COMMON
3
R
2
R R
1
UNCONVENTIONAL DRAWING
OF CIRCUIT
SIGNAL COMMON
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 91
The Honeywell Vutronik Control Loop(Cont'd)
Changing Current Signals to Voltage Signals (Cont'd). Return connections from control
instruments to the signal common at terminal 4 are NOT shown on ILDs.
Note the following from Figure 79: Current flows:
from terminal 1 to the transmitter
from the transmitter to terminal 2
from terminal 2 across the jumper lead to terminal 3
through the 250 ohm resistor to terminal 4, the signal common.
Remember that Vutronik transmitters operate with 4 - 20mA. If a 4-mA current signal is
received from the transmitter, then Ohm's Law says that the voltage drop across the 250-ohm
resistor is 1 volt, since V = IR = 0.004 x 250 = 1 V.
If a 20-mA current signal is received from the transmitter, then from 0.020 x 250, there is a 5-
v drop across the 250-ohm resistor.
4 - 20 mA is the range of current flow through the transmitter. This is proportional to a 1-5 v
signal at the signal common.
Figure 82 shows a Vutronik system for level control loop 3010. The system is operating a
level recorder, a level indicating controller and an alarm.
Note the symbol [-||-] that is used to denote a switch card.
As an example, we will trace the signal that operates the level recorder, LR - 3010.
A 25 - vdc power supply producing 4 - 20 mA is connected to terminal 1 on TPAI-2. This
supply is not shown on the ILDs. (Remember that other connections, such as the internal
connections between all terminal 4 and the return connections from instruments to terminals 4
are also not shown on ILDs.)
A wire connects terminal 1 on TPAI-2 to the positive side of the transmitter, LT-3010. The
connection is made through CA-41 and FA-1 on the BACK AUXILIARY RACK, RK-D28-
3001-1. From FA-1 the wire goes to TB-E-3007 in the junction box, terminal 1. The wire is
shielded and is earthed at terminal 3.
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 92
Tracing Signals
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 93
The Honeywell Vutronik Control Loop(Cont'd)
Tracing Signals (Cont'd). From TB-E-3007 the current goes to the positive side of the
transmitter. The transmitter acts like a variable resistor: the resistance depends on the process
variable measurement it is receiving. Therefore, the current that passes through the
transmitter depends on the process variable measurement.
The current flows from the negative terminal of the transmitter, through TB-E-3007 terminal
2, FA terminal 2, CA terminal 42 and to TPAI-3 terminal 2.
Terminal 2 on TPAI-3 is wired to terminal 2 on TPAI-2. This terminal is jumped to terminal
3. Terminal 3 is connected by a 250-ohm resistor to terminal 4. The voltage drop across the
resistor will be between 1 and 5 volts, depending on the value of the current which the
process variable has allowed to flow through the system. But, remember, terminals number 4
are connected together, internally, even though this is not shown on the ILD. Therefore, the
voltage across terminals 2 and 4 in TPAI-2 and TPAI-3 is 1-5 v, as shown in Figure 83.
FIGURE 83. ILD DETAIL
+
_
1 2 3 4 5
1 2 3 4 5
FROM TRANSMITTER
V
VOLTMETER WILL
INDICATE 1 TO 5 vdc
INTERNAL
CONNECTION
+ 25 vdc
TO TRANSMITTER
250
TPA1- 3
TPA1- 2
4 - 20 m A
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 94
Tracing Signals (Cont'd)
Suppose a connection is made between terminal 2 on TPAI-3 and the input of the recorder,
and then from the output of the recorder to terminal 4 on TPAI-3. The voltage across the
recorder terminals will be between 1 and 5 vdc, proportional to the value of the process
variable. Hence the voltage operating the recorder will be in accordance with the value of the
process variable.
The connections between the terminal blocks and the instruments are made by wires or
cables. These connections are not shown on ILDs. The same wires or cables connect the
instruments to terminal 4, the signal common, in order to complete the circuit.
The ILD shows that the output signals from the level indicating controller come from
terminals 5 and 6 on TPAI-2. These are the standard terminals used on Honeywell TPAs for
output signals. (Remember that the output signals of a controller are proportional to the input
signals it receives from the transmitter. In this case the input signals will be between 1 - 5 V
dc and the output signals will be between 4 - 20 mA DC.)
The wire from terminal 5 goes to transducer LTd-3010. The current signal is converted to a
pneumatic signal to open or close control valve LCV-3010. The negative terminal of the
transducer is connected to terminal 6 of TAPAI-2. This terminal is connected to the negative
terminal of the controller and so completes the circuit.
The schematic in Figure 84 shows the circuits we have been discussing.
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 95
The Honeywell Vutronik Control Loop(Cont'd)
Tracing Signals (Cont'd)
FIGURE 84
+ -
+
-
+
-
4 - 20 mA
LT - 30 10
+ 25 vdc
POWER
SUPPLY
LTd - 3010
4 - 20 mA
LCV - 3010
LS-3010-1/ 2
LIC - 3010
250
1 - 5vdc
LR - 3010
SIGNAL
COMMON
SC
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 96
The Honeywell Vutronik Alarm Card
The Honeywell alarm card monitors a process variable and trips an alarm if the variable goes
beyond preset limits. The alarm card may trip a circuit to start or stop a pump, open or close a
valve, or trip a plant's ESD system.
The Honeywell dual alarm card has two input circuits. Each input circuit needs a 1 to 5 vdc
input signal.
Figure 85 shows a simple illustration of how the alarm card operates as part of an alarm
circuit.
FIGURE 85. DUAL ALARM CIRCUIT
OUTPUT 1A
OUTPUT 1B
OUTPUT 2A
OUTPUT 2B ALARM
CIRCUIT 2B
ALARM
CIRCUIT 2A
ALARM
CIRCUIT 1B
ALARM
CIRCUIT 1A
ALARM
ALARM
ALARM
ALARM
INPUT 1
1 - 5 vdc
INPUT 2
1 - 5 vdc
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 97
The Honeywell Vutronik Alarm Card(Cont'd)
Each input has two outputs. Each output is a set of relay contacts. They act as the switch part
of the alarm card. Figure 86 shows how a relay operates.
A relay is an electrically-operated switch. Figure 86 shows a relay that is normally open. A
spring keeps the relay contacts apart. When current flows through the coil the soft iron core
becomes a magnet. The magnetic force pulls the armature down and the contacts close.
When the current stops flowing through the coil, the spring pulls the contacts apart. Now
return again to the dual alarm system (Figure 85.) When the input voltage signal goes beyond
a preset limit, the relays will operate. They will activate an alarm in the control room.
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 98
The Honeywell Vutronik Alarm Card(Cont'd)
Figure 85 showed that the card provides two separate alarms for each input signal. Thus, for
example, both a high and low alarm can be set for the input from a level transmitter.
Handout No. 9 (Drawing No. U54-J-XB-B19079) shows an ILD for level control loop L-020.
The alarm card is located on the auxiliary rack RX-454-1. The card is a level switch LS-020
A and B.
The card receives two 1 to 5 vdc signals from terminals 2 and 7 on TPAI-7. They are
connected to terminals 3 and 5 on the alarm card. The mark number of input 1 is LS-020A.
Its alarm settings are 2.1 volts high/1.0 volt low. These are alarms 1A and 1B respectively.
Input 2 has a mark number of L-020B. It uses only one alarm setting, which is 3.0 v high.
This is alarm 2A.
Tracing the connections from the alarms back to the switch card shows that the alarm output
terminals for these three alarms are:
Output for Alarm 1A - Terminals 2 and 6
Output for Alarm 1B - Terminals 7 and 8
Output for Alarm 2A - Terminals 10 and 11
These connections are made through terminal strips TBC and TBA.
Alarm 1A operates XA-1-37
Alarm 1B operates XA-1-43
Alarm 2A operates XA-1-30
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 99
The Honeywell Vutronik Alarm Card(Cont'd)
Note that alarm circuits 1B is not a complete circuit on the ILD. This is because alarm 1B is
also connected to TBA-78, which is seen to be shown on drawing number XB-B-19078 sheet
B. (A study of this drawing shows that alarm 1B is part of the ESD system.)
The ILDs will not always show the inputs and outputs on an alarm card. When they are not
shown, you must refer to the vendor manual. This gives the inputs and outputs of all the
alarms.
Note the bracket around terminals 14, 15 and 16. This means that the terminals act as a single
unit case only.
A study of the ILD for loop 020 shows that when the level transmitter LT-020 senses a low
level in U54-D-052 the light in window panel 1-43 on the control room panel will come on.
When the level is high the light in window 1-37 will come on. (Note that terminals 82 and 83
on TBA are jumped together to form a complete circuit.)
Summary
Alarm cards can be used to monitor any process variable. The mA output from any
transmitter is converted to 1 to 5 vdc and used to operate the cards. The cards can monitor
two different variables at the same time. Both input signals are independent of each other.
Each set of output contacts on the card can be set at high or low alarms.
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 100
Examples of Honeywell Cards
Honeywell mV/I Converter Card. The Honeywell mV/I converter card is mounted in a
single card file. The card has two separate converter circuits. It can be used in two different
loops at the same time. Each output is 4-20 mA.
Figure 87 shows an ILD for a temperature control loop.
A thermocouple (Type J) measures temperature in the field. The thermocouple develops
millivolt signals, the values of which depend on the temperature measurement. Wires carry
the mV input signal to input number 1 on the mV/I converter card, TY-304. Note that the
input terminals are on the card, not on the card file terminal strip. The ILD shows that the
converter is in the auxiliary rack in the control room.
The card converts the mV signal to a 4-20 mA signal. The output of TY-304 is shown to be
at terminal 12. The 250-ohm resistor on TB 1 converts the mA output signal to 1-5 vdc.
Remember that the power supply and some connections are not shown on ILDs. These
include the internal connections that link all terminals number 4 together, and the wire or
cable connections that take the 1-5 vdc signal to the control instruments.
The 1-5 vdc signal goes to TR-304 (Recorder). The same voltage also exists across terminals
3 and 4 on TB 2. From these the voltage is sent to TI-304 (Indicator).
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 101
Honeywell mV/I Converter Card (Cont'd)
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 102
Honeywell Resistance to Current Converter Card
Figure 88 shows a temperature control loop in which a Resistance Temperature Detector
(RTD) is used to measure temperature. The RTD is a variable resistor. Its resistance changes
according to changes in temperature.
TY-305 converts the resistance signal to a 4-20 mA signal. The 250 ohm resistor on TB 7
causes a voltage drop of 1-5 vdc. This voltage is used by TR-305 and TI-305.
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 103
Honeywell Resistance to Current Converter Card (Cont'd)
Figure 89 show an ILD using square root extractor card, SQ-301. The operation of the circuit
is similar to those already discussed.
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 104
WORK AIDS
ILDs use standard symbols to depict various control instruments. These symbols, taken from
Saudi Aramco Standard Drawing numbers 990-J-AD-036491, 990-J-AB-36492 and 990-J-
AB-36493 are shown below:
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 105
WORK AIDS (Cont'd)
01500H
01500E
01500D
01500C
MARK NO.
MARK NO.
SIZE
FLOW ELEMENT :
' ANNUBAR ' TYPE
FLOW INSTRUMENT:
PD : POSITIVE DISPLACEMENT
METER.
T : TURBINE METER
TRANSMITTER WITH
INTEGAL ORIFICE
PISTON OPERATED BALL VALVE
POSITIONER, SWITCHING VALVES
AND VOLUME TANK.
LINE NUMBER
L
H
LINE NUMBER
LINE NUMBER
PD / T
LINE NUMBER
S
OUT
PD OR T
MARK NO.
SIZE/RATING
A.F. ACTION
HOOK UP DWG. AB 036560
S
INSTR.
2
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 106
WORK AIDS (Cont'd)
001500
01500A
SAFETY SHUT OFF VALVE
WITH TWO CYLINDERS AND
TWO LIMIT SWITCHES
MARK NO.
SIZE
MARK NO.
DIAPHRAGM OPERATED
GLOBE VALVE WITH
POSITIONER
LINE NUMBER
S
OUTPUT
INSTR.
SIZE /RATING
A.F. ACTION
DIAPHRAGM - OPERATED
GLOBE
VALVE WITH POSITIONER
MARK NO.
SIZE/RATING
LINE NUMBER
M
MARK NO.
CONT. PSTN
MOTOR
JUNCTION
BOX
TYPE
VALVE PSTN
MARK NO.
MARK NO.
CONT. POS
CONT. POS
LINE NUMBER
VALVE POS
VALVE POS
NC OR NO
NC OR NO
C
3
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 107
WORK AIDS (Cont'd)
MARK NO.
5 1 4
3 2
HAND OPERATED SPRING
RETURN 4 WAY PILOT VALVE
MARK NO.
5 1 4
3 2
DIAPHRAGM OPERATED
4 WAY PILOT VALVE
MARK NO.
SET AT
L
I
N
E

O
R


E
Q
U
I
P
M
E
N
T
M
A
R
K

N
O
.
SWITCH ( SINGLE )
NO OR NC
C
SAFETY SHUT OFF VALVE
WITH ONE CYLINDERS AND
TWO LIMIT SWITCHES
MARK NO.
CONT. POS VALVE POS
MARK NO.
CONT. POS VALVE POS
NO OR NC
C
LINE NUMBER
MARK NO.
SIZE
NO OR NC
C
4
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 108
WORK AIDS (Cont'd)
TERMINAL BOX WITH
TERMINALS
RB NUMBER
RELAY BOX OR SHUTDOWN
SYSTEM
MARK NO.
SW1 SET AT
L
I
N
E

O
R


E
Q
U
I
P
M
E
N
T
M
A
R
K

N
O
.
SWITCH ( DUAL )
NO OR NC
C
NO OR NC
C
SW2 SET AT
JB OR TB NUMBER
CONDUIT OR CABLE
NUMBER
CHECK VALVE
PNEUMATIC TERMINAL
5
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 109
WORK AIDS (Cont'd)
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 110
WORK AIDS (Cont'd)
PROXIMITY VIBRATION
PICK - UP ELEMENT
MOTOR OPERATED
VALVE
MARK NO.
RANGE
EQUIPMENT
MARK NO.
SHIELD
COAX
EQUIPMENT
MARK NO.
SHIELD
MARK NO.
RANGE
MTG. POS.
BLACK
RED
GREEN
WHITE
A
B
C
D
SEISMIC VIBRATION
PICK - UP ELEMENT
MOTOR J. B.
MARK NO.
SIZE
M
LINE NUMBER
7
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 111
WORK AIDS (Cont'd)
SPEED TRANSMITTER
WITH INTEGRAL SPEED
INDICATOR
MARK NO.
RANGE
INSTRUMENT PROCESS LINES
INSTRUMENT AIR LINES
INSTRUMENT ELECTRIC LINES
INSTRUMENT CAPILLARY TUBES
1
2
7
8
9
10
3
4
5
6
SPARE
RECORDER ( 1 TO 3 PENS )
MARK 1st PEN
RANGE 1st PEN
MARK 2nd PEN
MARK 3rd PEN
RANGE 2nd PEN
RANGE 3rd PEN
DWG. NO.
IN
GND.
L1
L 2
8
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 112
WORK AIDS (Cont'd)
CONTROLLER
INDICATOR ( 1 TO 3 POINTERS
INDICATING CONTROLLER
MARK NO.
SET POINT
P. BAND
RESET
DERIVATIVE
ACTION
MARK NO.
RANGE
MARK NO.
SET POINT
P. BAND
RESET
DERIVATIVE
ACTION
SCALERANGE
S
OUT
IN
IN
S
IN
OUT
9
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 113
WORK AIDS (Cont'd)
INDICATING CONTROLLER
WITH MANUAL CONTROL UNIT
TERMINAL STRIP WITH
CORD SET
THE TERMINAL STRIP COLOR
CODE AND CORD SET SHALL
BE IN ACCORDANCE WITH
VENDOR DRAWINGS.
MARK NO.
SET POINT
P. BAND
RESET
DERIVATIVE
ACTION
SCALE RANGE
S
IN
OUT
INDICATING CONTROLLER
MARK NO.
SET POINT
P. BAND
RESET
DERIVATIVE
ACTION
SCALERANGE
S
IN
OUT
SET
( IND. CONTROL )
( MANUAL
CONTROL UNIT )
COLOR CODE
'' ''
'' ''
'' ''
'' ''
'' ''
'' ''
'' ''
'' ''
'' ''
1
2
3
4
5
6
7
8
9
10 9 CORES
TIED BACK
1
0
0

TYPICAL
10
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 114
WORK AIDS (Cont'd)
CONTROLLER
MARK NO.
SET POINT
P. BAND
RESET
DERIVATIVE
ACTION
DWG. NO.
INDICATOR ( 1 TO 3 POINTERS )
MARK NO.
RANGE
DWG. NO.
ALARM UNIT
MARK NO.
SET POINT
DWG. NO.
EMF / RTD TO CURRENT
CONVERTER
MARK NO.
RANGE IN
DWG. NO.
RANGE OUT
11
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 115
WORK AIDS (Cont'd)
12
VIBRATION MONITOR
SEISMIC TYPE OR PROXIMITY TYPE
MARK NO.
PRE ALARM
S. D. SET AT
SCALE RANGE
10
9
8
7
6
5
4
3
2
1
11
12
13
14
15
16
17
18
19
20
GRND.
L2
L1 DWG. NO.
MULTIPOINT TEMPERATURE
RECORDER
MARK NO.
RANGE
SCALE
L1
L2 DWG. NO.
GRND.
MULTIPOINT TEMPERATURE
INDICATOR
MARK NO.
RANGE
SCALE
L1
L2
DWG. NO.
GRND.
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 116
WORK AIDS (Cont'd)
13
TEMPERATURE MONITOR
MASTER MODULE
MARK NO.
SCALE RANGE
NO
NC
H
TEMPERATURE SWITCH
ANNUNCIATOR ALARM
SINGLE SET POINT
MODULE
MARK NO.
SET AT
NO
NC
H
ACTION
TEMPERATURE SWITCH
ANNUNCIATOR ALARM
DUAL SET POINT MODULE
FOR FRONT OF PANEL
MOUNTING.
HI. SET AT
HI. HI. SET AT
NO
NC
H
ACTION
TEMPERATURE SWITCH
ANNUNCIATOR ALARM
DUAL SET POINT FOR
REMOTE RACK
MOUNTING.
MARK NO.
HI. SET AT
ACTION
ACTION
HI. SET AT
NO
NC
C
NO
NC
C
NO
NC
C
NO
NC
C
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 117
WORK AIDS (Cont'd)
ANNUNCIATOR WINDOW TERMINAL
ONE COMMON TERMINAL FOR ALL
ANNUNCIATOR LIGHTS
COMMON
MARK NO.
WINDOW
ANNUNCIATOR WINDOW TERMINAL
MARK NO.
WINDOW
MARK NO. MARK NO.
PUSH BUTTONS
MARK NO.
RANGE
SPEED INDICATOR
14
MARK NO.
HAND SWITCH
NO
OR
NC
C
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 118
WORK AIDS (Cont'd)
LAMP
MARK NO.
RUNNING LIGHTS
MARK NO.
DIODE
15
GREEN
RED
MARK NO.
1
2
TELEPHONE JACK
Engineering Encyclopedia Drafting
Drafting Instrument Loop Diagrams
Saudi Aramco DeskTop Standards 119
GLOSSARY
Derivative The name given to the control procedure that is concerned
with
(or Rate Action): how quickly a process variable (usually temperature) is changing
its value.
Offset: The difference between the actual value of a process variable
and its set point value.
Proportional band: The ration, as a percentage, of the deviation of a process
variable from set point divided by the amount of control valve
stem movement the deviation causes.
Reset (or gain): The name given to the control procedure which is designed to
bring a process variable back to its set point.