RELATED WORK
A. 01810
1.2
SUBMITTALS
A.
PART 2 PRODUCTS
2.1
TEST EQUIPMENT
A.
PART 3 EXECUTION
3.1
3.2
TESTING REQUIREMENTS
A.
The Commissioning Authority will prepare testing procedures using the Design Intent
Document, the testing requirements listed in these specifications, and commissioning
data submitted by the contractors in accordance with these specifications. The testing
procedures will require the following minimum information:
1.
Test number.
2.
3.
Indication of whether the record is for a first test or retest following correction of
a problem or issue.
4.
5.
Conditions under which the test was conducted, including (as applicable)
ambient conditions, set points, override conditions, and status and operating
conditions that impact the results of the test.
6.
Expected performance of the systems and assemblies at each step of the test.
7.
01812-1
B.
8.
Notation to indicate whether the observed performance at each step meets the
expected results.
9.
10.
Dated signatures of the person performing the test and of the witness.
This is a performance test to verify lighting system operation, light levels, and energy usage.
1.
2.
3.
4.
(3)
(4)
b.
Verify that all specified functions and features are set up,
debugged and fully operable.
(2)
Verify that delays and ramp times are set and functioning so
that the speed of change of light fixture output is slow enough to
not bother occupants and in compliance with the specifications.
(3)
(4)
Verify that the controls and sensors are not easily overridden
or disabled by occupants.
01812-2
(5)
c.
d.
e.
Lighting Power Density. Perform the test with all interior lighting turned
on and any manual or automatic controls temporarily overridden. The
lighting power shall be measured at the buildings electrical panels.
Measurements shall be taken at least 1 minute after all lighting in the
building is on.
5.
6.
Acceptance Criteria
7.
a.
Lighting Controls: For the conditions, sequences and modes tested, the
dimming/occupancy/photocell/timing controls, integral components and
related equipment respond to changing conditions and parameters
appropriately as expected, as specified and according to acceptable
operating practice.
b.
Illumination Levels: Average light levels in the tested space at the work
plane elevation shall not be less than 10% below nor greater than 30%
above the specified light level range for the space.
c.
b.
Illumination Levels: At least 50% of all space zones and rooms shall be
verified to be realizing proper light levels, chosen by the Owner. If 25%
of the spaces in the first sample fail the functional performance tests,
test another 10% of the group (the 2nd sample). If 10% of the spaces in
the 2nd sample fail, test all remaining spaces, fully at the contractors
expense.
c.
01812-3
C.
D.
E.
Emergency Generator
1.
F.
END OF SECTION