Vous êtes sur la page 1sur 7

8.

5 A room with a fire and explosion hazard


8.5.1 General
8.5.1.1 The provisions of this article apply to the electrical installations in the location and dangerous
space classified because there are or there may be a mixture of air and gases, vapors or dust fibers are
flammable or explosive.
NOTE:
a) The word space in this article to mean "location".
b) The placement of the electrical equipment in Zone 0 installations should be avoided, unless the
The equipment is very important for the process or placement elsewhere not profitable.
With proper installation planning, often the majority of the equipment may be placed in the room
wheres not dangerous, and thus reduce the specific equipment required by this chapter. Sometimes the
danger can be reduced by ventilation adequate source of clean air coming from, along with effective
safeguards against failure ventilation.
c) The word dangerous space means a room with a fire and explosion hazard.
8.5.1.2 The provisions of this article shall not apply to electrical installations are designed to meet
specific requirements, thus declared safe and can be used in space
dangerous.
Secure Installation should not be able to release of electrical energy or heat
(Under normal circumstances or abnormal) that can ignite a dangerous mixture of air
concentrations of flammable easily.
The definition of an abnormal situation, is the installation of an unexpected breakdown
due to failure of electrical components, the presence of voltage, setting error and
maintenance, and other similar circumstances.
NOTE safe electrical installation may be used for instrumentation and
telecommunications, including remote control and telemeter with a small electrical current.
8.5.2 Classification of space
Space with an explosion hazard classified in zone based on the frequency of occurrence
and duration of the presence of explosive gases in the atmosphere as follows:
Zone 0: An area where there is an explosive gas atmosphere is continuously or in a long time.
Zone 1: An area where explosive gas atmospheres may occur in normal operation.
Zone 2: An area where there may be no explosive gas atmospheres in operation
normal and, if this happens, not often and only likely to be
takes place in a short time.
NOTE classification of this space should be determined by qualified personnel
in the field of combustible materials, processes and equipment, if necessary in order to set
in consultation with security guards, electrical and other technical personnel.
8.5.3 Group fixtures
Equipment for use in zone 0, zone 1 or zone 2, then grouped
as follows:
Group I: Equipment for use in mining (methane gas).
NOTE 1: The use of electrical equipment of Group I are not included in this regulation.
Group II: Equipment for use in other industries.
For the use of gas in Group II, then Group II is divided into:
Group IIA: The atmosphere containing acetone, ammonia, etylen alcohol, gasoline,
methane, propane, and gases or vapors with equivalent hazard.
Group IIB: Atmospheric containing acetaldehid, etylen, and gases or vapors with
equivalent hazard.
Group IIC: atmospheres containing Acetylene, hydrogen, and gas or vapors with
equivalent hazard.
NOTE 2: To get a list of hazardous gases and vapors, so refer to Publication
IEC 79-12.
8.5.4 The use and labeling
8.5.4.1 Use
Equipment intended to be used for Zone 0 can be use in Zone 1 or Zone 2
with the same gas group.
Equipment intended to be used for Zone 1 Zone 2 with
groups of the same gas.
8.5.4.2 Marking
Equipment that will be placed in a chamber containing explosive gas should
have an ID, to show the zone, gas group and temperature class
based on ambient temperature of 40 C.
NOTE electrical equipment to be operated in ambient temperatures over 40 C
must have identification to a maximum temperature of their surroundings, or the range of temperature
at temperatures
round.
8.5.5 Selection of electrical equipment
To use electrical equipment in a space where there are explosive gas, it is necessary
note the following:
a) Classification of hazardous area (see 8.5.2);
b) Temperature flame gas or vapor present in the chamber (see Pub. IEC 79-12);
c) The enclosure of the equipment in accordance with the gas or vapor present in the chamber;
SNI 04-0225-2000
364
d) External influences and ambient temperature.
For the selection of the appropriate equipment with service temperature of gases or vapors exist,
appropriate equipment must be worn in Table 8.5-5 below:
Table 8.5-5 Relationship between temperature class equipment, surface temperature
and ignition temperature
Temperature class
electrical equipment
Surface temperature
Maximum equipment
Ignition Temperature
gas or vapor
T1
T2
T3
T4
T5
T6
450 oC
300 oC
200 oC
135 oC
100 oC
85 oC
> 450 oC
> 300 oC
> 200 oC
> 135 oC
> 100 oC
> 85 C
8.5.6 Equipment used in each zone
Zone 0: In the Zone 0 area may be used only electrical equipment that has
identification as follows:
a) the equipment is intrinsically safe with the category of "it"
b) other equipment specifically designed for use in Zone 0
Zone 1: In the Zone 1 area should only be used electrical equipment for Zone 0, and
or supplies with types that have the mark according to the type of protection
security as follows:
a) enclosed fireproof "d" (see IEC 79-1)
b) enclosed pressurized "p" (see IEC 79-2)
c) supplies of sand "q" (see IEC 79-5)
d) equipment in the oil "o" (see IEC 79-6)
e) provision of enhanced security "E" (refer to IEC 79-7)
f) intrinsic safety "i" ("he" or "ib") (see IEC 79-11)
Zone 2: In a room Zone 2 electrical equipment must be installed as follows:
a) electrical equipment for Zone 0 and Zone I, or
b) electrical equipment with pressurized sheath for Zone 2, or
c) special electrical equipment designed for Zone 2 (eg, type of protection
"N") (see IEC 79-15).
SNI 04-0225-2000
365
d) other electrical equipment in accordance with other standards, which in operation
normally do not cause arcing which can heat or ignition
surface.
Electrical equipment does not require a special mark, but must be determined
by skilled personnel.
8.5.7 Protection from dangerous arcing
a) The dangers of live parts. To prevent arcing can
ignite an explosive gas atmosphere, it should avoid any contact with the
voltage other than the part that is intrinsically safe.
b) Flow disturbance to the earth on the chassis or enclosure should be limited (big and duration)
and prevent an increase in the potential at any potential equalizing conductor bond.
c) If the TN system is used, it should be applied to the system TN-S, with a neutral
separately and installed protective conductor throughout the system. In a dangerous space,
neutral conductor must not be connected together, or combined in a single
conductor.
TN-C system, which has a neutral conductor combined to function and function
protection in the form of a conductor, should not be used in a hazardous area.
If using a TT system (system earthing conductor separate from the
open-conductive) used in Zone 1, it must use protective devices
residual current (GPAs), also for extra-low voltage circuits (below 50 V).
TT system should not be applied in Zone 0.
d) If the use of IT systems (separate neutral from earth or earthed through
impendans), then the device should be installed at an early stage monitors to determine interference
earth. Installation in Zone 0 must be disconnected immediately after an earth fault
First, by the monitoring device isolation or by GPAs.
e) For installation in Zone 0 which uses various voltages must be considered,
that the earth fault current as small as possible in magnitude and duration. Should
earth fault protection is installed for a specific use in Zone 1.
Potential equalizing 8.5.8
To prevent dangerous arcing between the metal frame, then
equalizing potential needs to be installed for installation in Zone 0 and Zone 1 and may
also required for installation in Zone 2. therefore all conductive parts
open bonding conductor must be connected to the equalizing potential. Bonding system can
consists of a conductor protection, metal conduit, wiring enclosures from metal, steel protective
cable, all of the metal frame, but should not be attributed to a neutral conductor.
Conductor size between the metal part of the frame should be the smallest size 10 mm2
copper.
8.5.9 System wiring
a) In designing the wiring system and its components, it must be estimated
environmentally harmful gases, including mechanical factors, chemical and thermal.
SNI 04-0225-2000
366
b) single-core cable without sheath (eg, HIS) should not be used as
conductor voltage, unless the panels are mounted on the circuit,
enclosure or conduit system.
c) The connection cable and conduit to the electrical appliance should be carried out in accordance with
the type of
relevant protection.
d) hole for the cable or conduit entry points on the power tools should be covered with
sealing in accordance with the relevant type of protection.
e) The cable and conduit must be sealing, if necessary, so as to prevent water or
incoming gas.
f) Line entry system wiring from one zone to another zone, or zone
hazardous to non-hazardous zone, must inhibit the entry of gas vapors
or flammable liquids from one room to the other and prevent
collection of gases, vapors or flammable liquids in the channel. Prevention
This may be the installation of the sealing on branching, duct or pipe and
good ventilation or filling sand into the channel.
08/05/10 Cable System
8.5.10.1 metal sheathed cables, thermoplastic or elastomeric, including cable
mineral insulated cables can be used for permanent wiring.
Pleated metallic sheathed cables or cable with protective steel wire
plaited only be used, if it has a water-resistant casing.
8.5.10.2 For equipment that is portable and can be moved, with no voltage
more than 1000 V a.b. inter-phase (or 600 V to earth) or 1500 V dc between the poles (or 900
V dc to earth), then the supply cable must be sheathed rubber strong enough, or cable
similar to the robust construction.
If necessary protective conductor, the conductor is in its own isolation by means
the same as for other conductors and integrated into the supply cable sheath,
unless it is woven protective conductor.
Electrical equipment with a rated current of no more than 6 A for use in
space with no voltage over 250 V to earth should be connected to the cable
The usual rubber sheathed strong, strong polypropylene regular cable, or cable
have the same robust construction.
Copper conductor must be a minimum size of 1.5 mm2.
This cable should not be for equipment that is portable and can be moved to get
heavy mechanical stress, eg stair lights, switch legs.
For portable power tools or can be moved, or woven flexible cord protector
metallic should not be used as the main earthing, except konduktansnya enough and
not interrupted.
Copper wires were attached to the buffer and cables for telecommunications
The minimum size of 0.75 mm2.
SNI 04-0225-2000
367
8.5.10.3 flexible cable in hazardous area must be chosen from the following:
a) rubber sheathed flexible cable usual strong
b) sheathed flexible cable polichloroprene usual strong,
c) rubber sheathed flexible cable strong and heavy,
d) sheathed cables polichloroprene strong and heavy,
e) equivalent plastic insulated cables with rubber sheathed flexible cable strong
usual.
8.5.10.4 sheathed cables which are not planted in the ground or in the conduit
contains sand or not protected against fire must be fire-resistant cables
(Eg according to IEC 332).
8.5.11 Conduit systems for fire-resistant enclosures
8.5.11.1 sealing
Rigid metal conduit should be used. Must be made of solid conduit that
withdrawn without connection or with elongated connection with power
corresponding to withstand blast pressure. Conduit must be fitted with a sealing plug
as follows:
a) at the point of entry or exit from the danger area;
b) sealing 450 mm are most distant from all enclosures where there Ignition
during normal operation;
c) in any enclosure where there is branching, connection or termination
conduit with a diameter of 50 mm or more;
d) to reduce the impact of the buildup of pressure by several gases.
8.5.11.2 At a minimum there should be a conduit five threaded, so that between the enclosure and
conduit
connected with five threaded. Conduit shall be tightened so that all incoming thread.
8.5.11.3 If conduit is used as a protective conductor, the connection
Threaded must be able to drain noise current will flow if the circuit is secured
with a safety breaker melting or load.
8.5.11.4 If the conduit is installed in a space that is corrosive, it must be done
appropriate protection.
8.5.11.5 After all cables installed inside conduit, sealing fittings are required
with a compound that can not shrink when dry and waterproof and is not
can be damaged due to the chemicals contained in the danger area. Fitting
and sealing compound is used to limit the pressure to accumulate, to
prevent hot gases entering the system through a conduit from the enclosure that contains the source
ignition, and prevent the introduction of harmful gases into the space that is not
dangerous.
SNI 04-0225-2000
368
The thickness of the sealing compound in the fittings should be equal to the size of the conduit, but
should not be less than 16 mm.
8.5.11.6 Cable is not sheathed single-core and many may be installed in the
conduit. However, if the conduit is installed in more than two wires, then the number of
sectional area of the cable, including the insulation, should not be more than 40% of the cross sectional
area
conduit.
08.05.12 Signs
Electrical equipment installed in hazardous area shall have a sign
identifier as follows:
a) The name and manufacturer or brand;
b) Identify the manufacturer;
c) Ex symbol, which indicates that the electrical equipment is manufactured and tested to
explosive gas atmospheres or conditions incorporated in the apparatus in question,
d) Signs for every type of protection:
o to officials in the oil;
p for pressurized enclosures;
q for the apparatus filled with sand;
d apparatus for fire-resistant enclosures;
e for enhanced security;
he is a category for intrinsic safety;
ib for intrinsic safety category b;
e) The symbol for electrical equipment groups:
1) I for electrical equipment in mines where there is a mine gas
2) II or IIA or IIB or IIC for electrical equipment in explosive gas atmospheres, Letter
A, B or C is used in accordance with the conditions of the gas.
If the electrical equipment should only be used for a specific gas, then
II symbol followed by the chemical formula or name of gas.
For group II, the symbol indicating the temperature class or maximum surface temperature
in C or both. If marked for both, then the temperature class must
written in brackets, for example as follows:
T1 or 450 C or 450 C (T1)
f) for Group II equipment surface temperature exceeds 450 C has
temperature of signs alone.
g) If necessary, the serial number, but not for:
1) accessory connection,
2) small equipment.
SNI 04-0225-2000
369
h) If the testing has been certified, the certification mark imprinted,
should be in the following order: year of certification, then followed with serial number
certification that year.

Vous aimerez peut-être aussi