0 évaluation0% ont trouvé ce document utile (0 vote)
331 vues23 pages
This document provides guidance on estimating electrical load and lighting power for various types of residential and commercial buildings. It outlines the following:
1. Estimated power densities for economic, moderate, and luxurious residential buildings ranging from 2-10 KVA/100m2.
2. Lighting power estimation guidelines for different building types such as residential (10 VA/m2), offices (20 VA/m2), and malls (40 VA/m2).
3. Two methods for estimating allowed lighting power in commercial buildings - the complete building method based on primary use, and the area category method which assigns values based on space functions.
Description originale:
Titre original
Load Estimation in Buildings__(Electrical-Engineering-world.blogspot.com)
This document provides guidance on estimating electrical load and lighting power for various types of residential and commercial buildings. It outlines the following:
1. Estimated power densities for economic, moderate, and luxurious residential buildings ranging from 2-10 KVA/100m2.
2. Lighting power estimation guidelines for different building types such as residential (10 VA/m2), offices (20 VA/m2), and malls (40 VA/m2).
3. Two methods for estimating allowed lighting power in commercial buildings - the complete building method based on primary use, and the area category method which assigns values based on space functions.
This document provides guidance on estimating electrical load and lighting power for various types of residential and commercial buildings. It outlines the following:
1. Estimated power densities for economic, moderate, and luxurious residential buildings ranging from 2-10 KVA/100m2.
2. Lighting power estimation guidelines for different building types such as residential (10 VA/m2), offices (20 VA/m2), and malls (40 VA/m2).
3. Two methods for estimating allowed lighting power in commercial buildings - the complete building method based on primary use, and the area category method which assigns values based on space functions.
Visit Us electrical-engineering-world.blogspot.com
Join Us on Facebook Facebook.com/elec.eng.world Electric Load Estimation
For High Rise Buildings Total Electric Load Estimation For residential Buildings In general for the first estimation of the total power required for residential buildings 1- Economic Residential Building Power density = 2 4 KVA / 100 m2 2- Moderate Residential Building Power density = 5 7 KVA / 100 m2 3- Luxurious Residential Building Power density = 8 10 KVA / 100 m2
Lighting Indoor Lighting Electrical-Engineering-World.blogspot.com Lighting Power Estimation 1- Residential Buildings, Pd = 10 VA / m2 2- Offices, Pd = 20 VA / m2 3- Malls, Pd = 40 VA /m2 4- Colleges and Schools, Pd = 25 VA / m2 5- Hospitals, Pd = 20 VA / m2
Electrical-Engineering-World.blogspot.com Allowed lighting power There are two Methods to estimate the lighting power in commercial buildings:
A. Complete Building Method. B. Area Category Method.
Electrical-Engineering-World.blogspot.com A. Complete Building Method The building must consist of one type of use for a minimum of 90% of the floor area of the entire building (in determining the area of the primary type of use, include the following areas if they serve as support for the primary type of use: lobbies, corridors, restrooms and storage closets). Electrical-Engineering-World.blogspot.com
TYPE OF USE ALLOWED LIGHTING POWER
Auditoriums 17 Convention centers 14 Financial institutions 12 General commercial and industrial work buildings High bay 12 Low bay 11 Grocery stores 17 Hotel 15 Industrial and commercial storage buildings 8.0 Medical buildings and clinics 12 Office buildings 12 Parking Garages 5.0 Religious facilities 17 Restaurants 13 Retail and wholesale stores* 17 Schools 14 Theaters 15 All others 7.0
Table 1 Complete Building Method Lighting Power Density Values (Watts/m) Electrical-Engineering-World.blogspot.com Example: Complete Building Method
A 1000-m medical clinic building is to be built. What is its allowed lighting power under the complete building approach?
Answer
From Table the Standards, medical buildings and clinics are allowed 12 w/m2. The allowed lighting power is 1000 x 12 = 12000 W. = 12 KW. Electrical-Engineering-World.blogspot.com B. Area Category Method For purposes of the area category method, an "area" is defined as all contiguous spaces that accommodate or are associated with a single primary function as listed in Standards Table Electrical-Engineering-World.blogspot.com Table 2 Standards Table for Area Category Method - Lighting Power Density Values (Watts/m)
PRIMARY FUNCTION ALLOWED LIGHTING POWER Auditorium 17* Auto repair 13 ** Classrooms, lecture, training, vocational room 14 Civic Meeting Place 15* Commercial and industrial storage 7.0 Convention, conference, multipurpose and meeting centers 16* Corridors, restrooms, stairs and support areas 7.0 Dining 12* Electrical, mechanical rooms 8 ** Exercise center, gymnasium 11 Exhibit, museum 20 Financial transactions 13* General commercial and industrial work High bay 12** Low bay 11 ** Precision 15 *** Grocery sales 18 Housing, Public and Commons Areas Multi-family 11 Dormitory, Senior Housing 16 Hotel function area 16* Electrical-Engineering-World.blogspot.com Table 2 Standards Table for Area Category Method - Lighting Power Density Values (Watts/m) Kitchen, food preparation 18 Laundry 10 Library Reading areas 14 Stacks 18
Stacks 18 Lobbies Hotel lobby 12* Main entry lobby 18* Locker/dressing room 10 Lounge/recreation 12 Malls and atria 14* Medical and clinical care 14 Office 14 Parking garage 5.0 Religious worship 16* Retail merchandise sales, wholesale showrooms 20 Tenant lease space 11 Transportation function 12 Theaters Motion picture 10* Performance 16* Waiting area 13* All other 7.0
Electrical-Engineering-World.blogspot.com Table 2 Standards Table for Area Category Method - Lighting Power Density Values (Watts/m) Lobbies Hotel lobby 12* Main entry lobby 18* Locker/dressing room 10 Lounge/recreation 12 Malls and atria 14* Medical and clinical care 14 Office 14 Parking garage 5.0 Religious worship 16* Retail merchandise sales, wholesale showrooms 20 Tenant lease space 11 Transportation function 12 Theaters Motion picture 10* Performance 16* Waiting area 13* All other 7.0 Electrical-Engineering-World.blogspot.com Example: Area Category Method A small bank building has the following area distribution: Corridors 80 m2 Main Entry Lobby 20 m2 Financial Transactions 120 m2 Managers Office 20 m2 What is the allowed lighting power for this building under the area category method? Answer The following Lighting Power Densities apply (from Table 2): Space LPD Area Allowed Watts
Corridors 7.0 W 80 m2 560 Main Entry 16 W 20 m2 320 Financial Transactions 13 W 120 m2 1560 Managers Office 14 W 20 m2 280 ______ Total 2720 W
A 1000-m2 multi-use building is to be built consisting of: A) 50 m2 main entry lobby, B) 200 m2 corridors and restroom, C) 300 m2 grocery store, D) 250 m2 retail, and E) 200 m2 future development. What is the allowed lighting power under the area category method? Electrical-Engineering-World.blogspot.com Normal Sockets In general sockets can arranged in the free spaces between furniture OR One socket can be assigned for each 5 m The power of a normal socket can be taken as 250 VA
Electrical-Engineering-World.blogspot.com Power Sockets Power sockets can be put in the kitchens and offices
The power of the power sockets can be 1 KVA 2 KVA 3 KVA
OR as required
Electrical-Engineering-World.blogspot.com UPS Sockets For the information technology equipments it is required to use UPS to supply the sockets supplies these equipments. Electrical-Engineering-World.blogspot.com Air Conditioning Power Estimation Houses, Pd = 65 w/m2
Offices, Pd = 70 w / m2
Shops, Pd = 90 w / m2
Malls, Pd = 80 w / m2
Colleges and Schools, Pd = 100 w / m2 Electrical-Engineering-World.blogspot.com Air Conditioning Power Estimation
OR From 3.5 to 5.5 ton / 100 m2 Power in Kw = No. of tons x (1.6 2.5) Kw Electrical-Engineering-World.blogspot.com Elevators The number and type of the elevators will be determined by the architecture engineer. To estimate the power required for the elevators
P elev. = 15 25 Kw Electrical-Engineering-World.blogspot.com Pumps Number and size of the water pump can be determined by the mechanical engineer
To estimate the power required for the pumps
1- Water pump power = 5 KVA 2- Fire pump power = 15 KVA Electrical-Engineering-World.blogspot.com To get more Electrical Engineering Books For Free Download