Transformerless Inverters for Grid Connected Solar Photovoltaic

Applications
Pre-first Stage Report
to fulfill the partial requirements of
Master of Technology
in
Energy Systems Engineering
By
Vivek Annepu
(Roll no. 133170015)

Under the Guidance of
Prof. B. G. Fernandes

Department of Energy Science and Engineering

Indian Institute of Technology Bombay

Mumbai, 400076

July, 2014


ACKNOWLEDGEMENT

This report titled Transformerless Inverters for Grid Connected Solar Photovoltaic
Applications under the guidance of Prof. B. G. Fernandes represents the work done by me
and proper citations were given wherever necessary.


July, 2014 Vivek Annepu

i

ABSTRACT

Renewable Energy Generation is what everyone is talking about, mainly, through solar
photovoltaic systems and the government policies has made this affordable to every household in
the country. The photovoltaic power generated can be given to the grid whenever an excess
power is generated. So, the grid integration is necessary which is done using an inverter along
with a transformer which costly. To reduce the cost of the PV system, TRANSFORMERLESS
INVERTERS came into the picture with improved efficiency and reduced size. But by
removing the transformer, these systems lose the advantage of having galvanic isolation. High
Leakage Current flows in the circuit in absence of isolation which causes safety issues, DC
current injection into the grid and electromagnetic interference (EMI). The leakage current was
brought down by maintaining the common mode voltage constant. Several existing topologies
were analyzed and a new "Neutral Point Clamped (NPC)" topology was studied and simulated in
this report which tries to overcome the above mentioned limitations.










ii

Abstract
Table of contents
List of figures
List of Tables
List Symbols
1. Introduction 1
1.1. Power generation through solar PV 1
1.2. Annual PV capacity additions 2
1.3. Grid Integration through power electronic converter 2
1.4. Outline of the report 2
2. Transformerless Inverter topologies 3
2.1. Parasitic capacitance of the PV arrays 3
2.2. Leakage ground current of Transformerless inverter 4
2.3. Transformerless Inverter Topologies 5
2.3.1 Topologies derived from H bridge inverter 5
2.3.1.1 H bridge with bipolar modulation 5
2.3.1.2 H bridge with unipolar modulation 6
2.3.1.3 H 5 topology 6
2.3.1.4 H6 with AC bypass (HERIC) topology 7
2.3.2 Topologies derived from the NPC converter 8
2.3.2.1 oH5 Topology 9
2.3.2.2 H bridge with zero voltage rectifier (HB-ZVR) 11
2.3.2.3 Full bridge PV bypass topology (FB - DCBP) 11
2.3.3 Half Bridge topologies 12
2.3.4 Comparison of various transformerless topologies 13


iii

3. Novel H6 NPC topology 14
3.1. Modes of operation 14
3.2. Simulation results 17
3.2.1. Ground leakage current and common mode voltage 17
3.2.2. Voltages across the stray capacitances at the negative and positive bus of the
inverter 17
4. Conclusion and Future work 18
4.1. Limitations and future work 18
References 19



















iv


List of Figures
Figure No. Title Page no.
1.1 Global Cumulative Installed capacity, 2001-2011 1
2.1 Simplified equivalent circuit of a H-Bridge transformerless
inverter [3]
4
2.2 Basic H-Bridge topology showing a PV source, an inverter and the grid 5
2.3 H5 topology derived from H bridge inverter by SMA 6
2.4 HERIC topology derived from H bridge inverter 7
2.5 (a) An optimized version of H5 topology oH5 topology 9
2.5 (b) oH5 topology in its mode I with grid current positive 10
2.6 H-Bridge Zero Voltage Rectifier (HB - ZVR) 11

2.7 Full Bridge PV bypass topology (FB-DCBP) 12
2.8 Typical Half Bridge inverter 13
3.1 Modified H6 Neutral Point clamped PV bypass Transformerless
topology

14
3.2 The operation of improved H6-DCBP topology under Mode I


15
3.3 Mode II operation, the freewheeling mode 16
3.4 Path showing the direction of grid current in the negative half
cycle
16
3.5 The grid current during the freewheeling period and the clamping
current through D- and C
PV2
in Mode IV
1
3.6 Common mode voltage and ground leakage current 17
3.7 The voltages of positive DC bus and negative PV bus w.r.t ground 17






v

List of Tables
Table No. Table Title Page No.
2.1 Comparison among various topologies which are derived from H-Bridge and
NPC
20



















vi

List of Symbols
V
cm
/ U
cm
Common mode voltage in volts (V)
V
dm
/ U
dm
Differential voltage of the inverter in volts (V)
V
AN,
V
BN
The potential of points A and B w. r. t negative bus of the PV link in volts (V)
L
1,
L
2
Filter Inductors in the phase and neutral connection of the grid (mH)
C
f


Filter Capacitor connected to the grid in F
V
PV
Voltage at the output of a large PV array
C
PV
Capacitor connected across the PV panel in F
f
s
Switching frequency of the inverter in kHz
V
g
Voltage of the grid in volts (V)
I
g
Grid current in Amperes (A)
C
off
Parasitic Capacitance of the Insulated Gate bipolar transistor
P Active Power in Watts (W)

1

Chapter 1

Introduction

The Photovoltaic Industry experienced a very large growth compared to the other fossil
fuels in the last fifteen years [1]. Due to the increasing demand, there is a huge deficit in power
which led to the exploration of new forms of energy. Energy sources like wind, solar etc., are the
cleanest sources available in the earths atmosphere. Energy generation from renewable sources
has become one of the most successful one both commercially as well as on a small scale. The
Renewable energy sources are less reliable and the generation systems are very less efficient.
Say, the highest conversion efficiency achieved for a solar cell in the laboratory is less than 20%
(approx.). With these problems at bay, it is difficult to utilize the resources to a fuller extent.
Similarly, the form of energy obtained from the solar photovoltaic cell is a variable quantity with
time. To extract maximum power available at that time of the day, tracking of the panel is being
done (Maximum power point tracking, MPPT). And the power available at the output terminals
of the PV panel may not be suitable for all purposes. So, this power available is processed or
conditioned in a desired way. Here comes the need of efficient energy systems.

1.1 Power generation through Solar PV:

One of the fastest growing renewable energy technologies is the PV. It is going to
become the major contributor to the global electricity generation. Because of some the attractive


Fig 1.1 Global Cumulat ive Installed capacit y, 2001-2011[2]
2





policies, the total installation capacity of PV has risen to 67.4 GW in 2011 from 1.8GW in 2000.
A growth rate of 44% was registered during the past decade. And a new capacity of 27.7 GW
was added in the year 2010 [2]. The cost of the system has been reduced significantly during the
years.


1.2 Annual PV capacity additions:

Most of the installations are from Germany and Italy. But only 0.2% of electricity
generation is from PV. Around 80% of the global demand is from the European market. Apart
from these two countries, the major emerging markets are China, the Middle East, South Korea,
India and other Southeast-Asian countries.

1.3 Grid Integration through the power electronic converter:

In the 90s, most of the applications (telecommunications, rural electric supply) used to
get the power from the stand-alone PV systems. And there are a lot of grid connections
available. The reduction in the overall cost of the system has led to such a change. The grid
connection is possible only through a DC to AC converter which supports the interconnection of
the distributed generation systems, storage systems, and renewable energy systems to the electric
power system.

Grid converter is mainly a semiconductor based circuit technology which inverts the
incoming signal (i.e., AC-DC and DC-AC). The rise in power demand has led to the creation of
new control methods such as more voltage levels leading to much more complex topologies. For
example, a normal H-Bridge converter modified to multilevel converters or interleaved
structures etc.

1.4 Outline of the Report:

The work presented in this report focuses on analyzing various transformerless
topologies for the photovoltaic systems regarding the common mode voltage and leakage current
issues in the absence of galvanic isolation.

The main objective of this report is to analyze and verify the existing topologies along
with various pulse width modulation techniques which help reduce the effect of common mode
voltage.


3

Chapter 2

The Transformerless Inverter Topologies


The efficiency of a PV panel is close to 20% which is very less [3]. So, the PV system
will be having an efficiency lesser than the efficiency of a PV panel. This is due to the losses
incurred in the several stages of the entire system. The typical grid connected PV system
constitutes the source, DC-DC conversion stage with maximum power point tracking stage, a
DC to sinusoidal AC conversion stage and an isolation transformer at the inverter output or a
high frequency transformer in the DC-DC convertor. The efficiency can be improved by either
removing the transformer which will improve the efficiency by 2% [3] or improve the converter
efficiency by reducing the number of stages. In this chapter, various problems associated with
the transformerless converters were discussed and some of the standard topologies were
discussed.
2.1 Parasitic Capacitance of the PV Arrays:

The PV panel comes with a metallic frame which when charged by an external voltage
signal, the metallic frame forms a capacitance with ground as the other surface and air as
dielectric. So, the stray capacitance which when energized with a high frequency signal allows a
significant current to pass through it. This value of this capacitance depends on various factors
like:

1. Total surface area of the PV array and ground frame
2. The space between the two surfaces
3. Atmospheric conditions like dust and humidity [4]

2.2 Leakage Ground Current:

In the grid connected system, the PV panel terminals will be connected directly to the
grid. There is no galvanic isolation from the grid. As a result, current will flow through the
parasitic capacitance which is the case in almost all the single phase transformerless inverter.
Half the amplitude of the grid voltage will appear across the terminals of a PV array oscillating
with grid frequency. For a three-phase system, the voltage oscillations are very less resulting in
lesser leakage currents. For the safety purposes, the grid neutral is connected to the negative
terminal of the DC bus. For all the neutral point clamped converters, the neutral point is
connected to the neutral of the grid which is to be grounded.

Depending on the PWM techniques used, a high frequency voltage may appear across the
resonant circuit formed by the stray capacitances of the transistor switches, PV array and the
filter inductor. As a consequence, large currents will flow in the circuit. The allowable limit for
the root mean square value of the leakage current is 30mA and the peak current allowable is
4

50mA according to the German VDE0126-1-1 standard [4] and it also suggests the installation of
residual current monitoring units (RCMUs). And the system should be disconnected from the grid
within 0.3s after the rise.

2.2 Leakage Current analysis of a Transformerless inverter:

The leakage current is found out by the simple circuit analysis wherein the equivalent
network is evaluated to find the expression of current. Here, the leakage current analysis was
done for a single-phase H-bridge inverter which can be done in the same fashion.
The equivalent circuit of the H-Bridge inverter is shown in the figure 2.1, where L
1
and L
2
are
the filter inductances on the phase and neutral neglecting the grid inductance. V
cm
, V
dm

represents the common mode voltage and the differential mode voltage of the inverter given by
the expressions:

U
cm
= V
AN
+ V
BN
(2.1)
U
dm
= V
AN
V
BN
(2.2)


Fig. 2.1 Simplified equivalent circuit of a H-Bridge transformerless inverter [3]


Where, V
AN
and V
BN
are the voltages across the points A and B with respect to the negative bus.
The equivalent circuit derived from the H bridge circuit is shown in the figure 2.1. The
equivalent voltages and the total equivalent voltages are derived in [3].

The equivalent common mode voltage is given by
Uecm = Ucm + Udm
Udm
2
LB-LA
LB+LA

(2.3)

If both the filter inductors possess the same value, then the common mode voltage depends only
on V
AN
and V
BN
.

From the circuit if the common mode voltage constant, then the current eventually die
down to zero. So, it is advisable to maintain the common mode voltage constant as the current
due to the grid voltage is very less compared to the common mode current. Some of the very
popular topologies were discussed in the next section.
5

2.3 Transformerless Inverter Topologies:

Various transformerless topologies were proposed for the elimination of leakage ground
current and its effect. Of these, most of the topologies addressed the problems related to the
single phase inverter because the fluctuations in the three phase system are considerably less.
These topologies were classified into two types;

Topologies derived from the H-Bridge topologies and,
Those which are derived from neutral point clamped inverter (NPC)
2.3.1 Topologies derived from H-Bridge converter

The topologies derived from the basic H-Bridge converter (Fig 2.2) are discussed below
by modifying it in order to provide a galvanic isolation. Some pulse width modulation
techniques are investigated on the basis of common mode voltage and leakage current.

The topologies include:
1) H-Bridge with bipolar modulation
2) H-Bridge with unipolar modulation



Fig 2.2 Basic H-Bridge topology showing a PV source, an inverter and the grid [1]

3) H5 topology (H-Bridge with DC bypass)
4) H6 topology (H-Bridge with AC bypass or HERIC topology)

2.3.1.1 H-Bridge with bipolar modulation:

In figure 2.2, the switches S1 S2, S3 - S4

are complementary, where no two switches
are on at the same time. In this topology, the common mode voltage is constant value +V
PV
. In
bipolar pulse width modulation, the inverter output voltage varies from +V
PV
to V
PV
. The total
6

change in the voltage is +2V
PV
, as a result the current ripple in the filter inductor. This results in
more losses. The FFT analysis provide with information of the presence of a significant
component at the switching frequency to design the filter. Though the common mode voltage is a
constant, the efficiency is low due to the losses in the core.

2.3.1.2 H-Bridge with unipolar modulation:

In this modulation technique, the inverter has three levels in its output voltage i.e., +V
PV
,
0, -V
PV
having a dominant harmonic component at 2f
s
where f
s
is the switching frequency used in
the bipolar modulation technique. The inverter is disconnected from the grid during the zero
voltage state which is obtained in two situations: S
1
ON S
3
ON (or) S
2
ON S
4
ON.
The filter size reduces to half. The change in the inverter output voltage is unipolar in nature
hence, reduced losses. But, the common mode voltage varies with switching frequency resulting
in high leakage current.

2.3.1.3 H5 topology (H-Bridge with DC bypass):

As a replacement to the transformer, an extra series switch is connected on the DC side
of the inverter Fig 2.3. This inverter was proposed by SMA and named it as H5 topology for
having 5 switches in it. The extra switch is used to separate the grid and the DC side of the
inverter which does not allow the current to flow through the stray capacitance. The upper two
switches S1 and S3 are switched with grid frequency and are complementary to each other. On
the other hand, the switches S2 and S4 are switched at switching frequency when S1 and S3 are
on respectively and S5 operates along with S2 during the positive half-cycle and S4 during the
negative half-cycle. The inverter operates in four modes as,





Fig. 2.3 H5 topology derived from H bridge inverter by SMA [1]

Mode I: i
g
> 0, V
ab
= +V
PV


7

S1 conducts continuously in the positive half-cycle, S2 and S5 are ON. The current
passes through DC link voltage source, S5 - S1 - L
1
- V
g
L
2
- S2 and back to the DC source.

Mode II: i
g
< 0, V
AB
=

0 V

S1 conducts and S2 and S5 are OFF. But, the current in the inductor cannot change
suddenly so the current passes through S
1
L
1
V
g
L
2
- D
3
S
1
. During this stage, the grid is
totally isolated from the inverter.

Mode III: i
g
> 0, V
AB
= -V
PV

S3 is ON for the entire negative half-cycle. In this mode S4 and S5 are ON. The current
passes through S5 S3 L
2
V
g
L
1
S4 V
PV
(Source). In this mode the grid side elements
are isolated from the DC link side.

Mode IV: i
g
< 0, V
AB
= 0V

S3 conducts and S4 and S5 are OFF. But, the current in the inductor cannot change
suddenly so the current passes through S
3
L
2
V
g
L
1
D
1
S
3
. During this stage, the grid is
totally isolated from the inverter.

The voltage is unipolar in nature and the voltage at the DC link terminals is a sinusoidal
while having the same conversion efficiency as of the unipolar modulation topology.

Note: The common mode voltage during the powering mode is V
PV
/3 and during the free-
wheeling mode, the voltage is V
PV
/2 which is achieved after a finite time equal to 5 times the time
constant of the circuit. The V
cm
is not constant which results in a significant current.

2.3.1.4 H6 with AC bypass (HERIC- Highly Efficient and Reliable Inverter concept):

In 2006, this topology was patented by the Sunways by adding two switched leg on the
AC side of the inverter shown in the figure 2.4

Fig. 2.4 HERIC topology derived from H bridge inverter [1]
8

Mode I: i
g
> 0, V
AB
= +V
PV


In this mode, switches S1 and S2 are turned on with output voltage +V
PV
. The voltages
V
an
and V
bn
are calculated assuming that all the switches used here are ideal.

V
an
= +V
PV
V
bn
= 0V
V
cm
= (V
an
+ V
bn
)/2 = +V
PV
/2

Mode II: i
g
> 0, V
AB
= 0V,

The switching of either S5 or S6 depends on the direction of the grid current. For positive
grid current, switch S5 is turned on. The path of the grid current is along S5 D6 L
2
grid
L
2
S5.
The common-mode voltage is calculated by assuming parasitic capacitance across each
switch which is open. Hence, V
AN
= V
PV
/2; V
BN
= V
PV
/2. Hence, V
cm
= V
PV
/2

Mode III: i
g
< 0, V
AB
= -V
PV

Switches S3 and S4 are turned on and the grid current is negative direction. S5 and S6 are
open. V
AN
= 0V; V
BN
= V
PV
; V
cm
= V
PV
/2.

Mode IV: i
g
< 0, V
AB
= 0V

Here S6 will be switched on and the current path is S6 D5 L
1
grid L
2
S6. The
common mode voltage is same as V
PV
.

The grid current passes through two switches in the powering mode (Mode I & III) and
one switch with a frequency of grid and a diode (S6, D5 or S5, D6) in the free-wheeling modes
(Mode II & IV). So the switching losses in the inverter are very less compared to the other
proposed topologies, hence the name Highly Efficient and Reliable Inverter Concept (HERIC).
Also, the switches on the grid side isolate the DC link side during the zero voltage periods hence
the name of the topology H6 with AC bypass.

2.3.2 Topologies derived the from the NPC converter

The converter topologies discussed in the previous section assumes no parasitic
capacitance for the switches used. But when the inverter is switched at a very high frequency,
say, 20 kHz, the effect of the stray capacitance is significant. So, during the zero voltage period
these elements along with the filter inductors (grid inductance neglected) forms a resonant
circuit. Due to the oscillations performed during the zero voltage stage, the point a (b) is in
floating stage. At this instant, common mode voltage oscillates leading to the rise in ground
leakage current.

During the zero voltage modes, the voltage of midpoint of the leg A or B to the
negative bus has to be maintained constant. This is done by connecting a switch across the
9

midpoint of the DC link and the zero voltage point. This clamps the voltage of the floating point
to +V
PV
/2 maintaining the V
cm
constant.

The only disadvantage is that these topologies require two dc sources for the two
capacitors. Again, efficiency of the inverter depends on the losses in the inverter.
Some of the few popular topologies were discussed as follows:

1) oH5 topology
2) H-Bridge Zero voltage rectifier (HB-ZVR)
3) Full Bridge DC bypass topology (FB-DCBP)

2.3.2.1 o-H5 (Optimized H5 topology) Topology

This is an optimized version of the H5 topology[4] fig. 2.5. Here, a split capacitor leg is
incorporated so that the mid-point of the inverter leg is connected to it. This connection is made
using an extra switch in between the points. In this way the common mode voltage is maintained
constant.


Fig. 2.5(a) An optimized version of H5 topology oH5 topology [4]

Mode I: i
g
> 0, V
g
> 0;

A small dead time has to be provided between the switching instants of the series switch
(S5) and the clamping switch (S6). Otherwise, C
dc1
will be closed by a very low impedance path
(short-circuit) which will damage the source.

In this mode, when both the grid current and voltage are same, switches S1, S2 and S5
are on. And the inverter voltage will be V
PV
. The grid current slowly rises to its maximum and
then starts falling down similar to the grid voltage. S6 is kept open. The current path is C
PV1
S5
S1 L
1
V
g
L
2
S3 C
PV2
. The common mode voltage equals +V
PV
/2.

Mode II: i
g
> 0, V
g
= 0;

All the switches are open and S6 is closed small time after switch S5 is open in order to
avoid any damage to the device. At this instant, when S6 is closed the voltage V
3N
and V
4N
are
clamped to +V
PV
/2 resulting in V
cm
= V
PV
/2. If the voltages at the points A, B are greater than
10

the voltage at O, then the passage of current is through the diode D6. So, the path of current is
from the point O A (B) C5 C
PV1
.

Mode III: i
g
< 0, V
g
< 0;

Switches S2, S4 and S5 are switched on and the path of the current is C
PV1
S3 S1 L
1

V
g
L
2
S5 C
PV1
and the common mode voltage is maintained to be +V
PV
/2.

Mode IV: i
g
< 0, V
g
< 0;

S6 is switched on and S3 continues to be on in the negative half of the grid voltage. In
this mode, two cases are possible; if the voltage at O is lesser than that of A (B) current flows
through the switch S6 and in the opposite case, the current flows through the anti-parallel diode
of the switch S6 as shown in the figure 2.9(f). And the voltage of the mid-point of the inverter
leg gets clamped to +V
PV
/2 maintaining the common-mode voltage V
PV
/2.

Effect of Dead time in oH5 topology:

Certain dead time is provided between the gating signals for S5 and S6. So, the common
mode voltage is not +V
PV
/2 and it depends on the parasitic elements in the circuit.



Fig 2.5(b) shows the effect of dead time on the potential of the freewheeling path [10]

As all the switches are open, there is no freewheeling path for the grid current to flow.
So, it flows through the stray capacitances of the switches as shown in the figure 2.5(b). This
allows a large leakage current to flow through the circuit.

As all the switches are open, there is no freewheeling path for the grid current to flow.
So, it flows through the stray capacitances of the switches as shown in the figure 2.5(b). This
allows a large leakage current to flow through the circuit.



11

2.3.2.2 H-Bridge Zero Voltage Rectifier (HB - ZVR)

Another way of limiting the leakage current by keeping the common mode voltage
constant is by inserting an extra power-electronic switch with a diode bridge rectifier as shown
in the figure 2.10. The grid is isolated from the source from the AC side. So, this method is
proposed for AC decoupling. The bi-directional diode bridge is clamped to the mid-point of DC
link capacitor using a diode. The decoupling element is shown in the figure 2.6.



Fig. 2.6 H-Bridge Zero Voltage Rectifier (HB - ZVR) [3]

The positive vector is achieved by switching S1-S2 and negative vector by S3-S4. The
zero-vector is achieved by switching on the S5 by providing a small dead time of 2s to avoid
short-circuit of the input capacitor.

During the zero states, current passes through the diodes of the bridge rectifier and the
S5. During the dead time all the switches would be in OFF state, which allows the free-wheeling
current to flow through the parasitic capacitance of the switches into the DC link capacitors.

The peak current in this topology is greater than 50ms. The current during the zero
voltage free cycles across the bridge rectifier. During the dead time, the time duration between
the zero voltage stage and the active stage, the grid current find a way through two diodes which
incurs more losses. Hence, this topology is less efficient than the HERIC topology. Also six
extra diodes are incorporated for implementing this topology

2.3.2.3 Full Bridge DC bypass topology (FB-DCBP)

Fig. 2.7 shows the proposed topology which consists of six switches, of them, two
switches are connected in series on the either side of the DC link. The blocking voltage of the
switches S1 and S2 are halved due to the capacitor divisor formed by the diodes. Hence, the
saturation voltages are reduced. This inverter topology can also inject power with cos other
than unity.

12


Fig. 2.7 Full Bridge PV bypass topology (FB-DCBP) [3]

Modes of Operation: The output of the inverter produced is a three level voltage with
considerable conduction losses compared to the other NPC topologies.

Mode I:

In the positive half cycle of the grid voltage, switches S1 and S4 are switched on. The
switches S5 and S6 are switched at switching frequency. The switches S2 and S3 are switched
complementary to the switches S5-S6. This mode produces an active voltage vector +V
PV
. And
V
an
= +V
PV
and V
an
= 0 V. Hence, V
cm
= V
PV
/2.

Mode II:

In the free-wheeling mode, the voltage V
AB
= 0 V and the switches S3 and S2 will be
conducting along with S1-S4. So, all the four switches will be conducting, The inductor current
freewheels through the diodes D2 - D3 and the switches S1 S4. So, the conduction loss is
limited to only two switches.

Mode III and Mode IV have the similar operation in the negative half of the grid voltage.
The roles of S1 - S4 and S2 S3 gets interchanged

The efficiency of this inverter is very less due to the conduction of four switches during
the active voltage vector. But even this topology is reducing the oscillations in the common
mode voltage.

2.3.3 Half Bridge Topologies

The half-bridge converter shown in the figure fig. 2.8 uses two switches to do the dc-ac
conversion by connecting to either the negative or the positive bus wherein the neutral is always

13



Fig. 2.8 Typical Half Bridge inverter [3]

connected to the middle point of the capacitors.
The main disadvantage is the usage of two dc sources whereas the H-Bridge topology
requires only one source. Also the voltage rating of each switch should be twice that of the H-
Bridge topology. But the output voltage is bipolar in nature which generates a constant common
mode voltage. So, this topology is suitable as a transformerless topology, but source voltage of
1000V or more is practically not available. So this option is not viable.

2.3.4 Comparison of Various Transformerless Topologies
The consumer buys a product by searching for its pros and cons of it. Then he will
compare all the variants available in the market and make the best choice out of them. Similarly,
the various transformerless inverters are compared on the basis of their cost, efficiency,
common-mode voltage and the leakage current characteristics by the following table.

Table 2.1 Comparison among various topologies which are derived from H-Bridge and NPC



Topology

Type of Inverter
output
(Unipolar/Bipolar)

O/P
Voltage
Levels
No. of Devices
Conducting
(S/D)

Constant
Common-
mode Voltage
(Y/N)


Efficiency

Active
Free
Wheeling
(order)
H-Bridge Bipolar 2 2/0 - Y 6
H-Bridge Unipolar 3 2/0 1/1 N 4
H-5 Unipolar 3 3/0 1/1 N 5
HERIC Unipolar 3 2/0 1/1 Y 1
oH5 Unipolar 3 3/0 1+1
*
/1+1
*
N 3
HB-ZVR Unipolar 3 2/0 1/2 Y 2
HB-
DCBP
Unipolar 3 4/0 2/2 Y 7

(* Note: The number represents either a diode or a transistor switch)
14

Chapter 3
Improved H6 DC Bypass NPC Topology

The NPC topology aims at maintaining constant common mode voltage even during the
freewheeling mode of operation. Various topologies derived from NPC such as oH5, HB ZVR
and HB DCBP were discussed in the previous chapter. A new topology was derived from the
H6 DCBP topology by shifting the switch S6 from the negative DC bus. The branch consisting
of switch S6 is connected to the mid-point of the DC link and the point B with the help of a
diode as shown in the figure 3.1.



Fig. 3.1 Modified H6 Neutral Point clamped PV bypass Transformerless Topology

The various modes of operation are discussed in detail in absence of parasitic elements.
The switches S1-S6 are operated at grid frequency in the positive half cycle of grid current.
Also, S3 is operated at grid frequency but complementary to the S1-S6 pair. Extra diodes D
+

used to protect the source from short-circuiting and D
-
used to clamp the freewheeling path to
+V
PV
/2. Modes I and II are related to the inverter operation in the positive half cycle of the grid
current. And, Modes III and IV are discussed for the grid current in its negative half cycle.

3.1 Modes of Operation:

Mode I: V
g
> 0, i
g
> 0,

The switches S1, S2, S5 and S6 are switched on so that the voltage across the inverter output
terminals V
AB
= +V
PV
. The path of current is along C
PV1
/2 S5 S1 L1 grid L2 S2
C
PV2
C
PV1
(fig 3.2). Even though S6 is kept on, the current does not flow through it as the
diode D
-
is reverse biased by the voltage across C
PV2
. The voltages V
AO
= V
PV
and V
BO
= 0 V.
The common mode voltage is given by (V
AO
+ V
BO
)/2 = V
PV
/2.
15




Fig 3.2 The operation of improved H6-DCBP topology under Mode I


Mode II: V
AB
= 0 V, i
g
> 0,

The switches S1 and S6 remains in the on position but the switches S2, S5, S3, S4 are
switched off. The path for the freewheeling current is along S1 L1 grid L2 D3 S3. A
part of the freewheeling current flows through the diodes D
-
- C
PV2
D2.

i
g
= i
D-
+ i
D3
(3.1)

V
AO
= V
PV
/2, V
BO
= V
PV
/2 (3.2)

So, the common mode voltage is the average of both the voltages V
AO
and V
BO
given by,

V
cm
= +V
PV
/2 (3.3)

During the powering mode, the potential at A with respect to O is V
PV
and that of B is
0V. When the grid is disconnected from the inverter PV side, the potential at A starts falling and
the potential at the point B starts rising. As a result of some parasitic elements in the circuit, the
potentials start oscillating. When the potential of B is greater than the potential at O, then the
voltage of the freewheeling path gets clamped to V
PV
/2 equal to the common mode voltage.

Mode III: V
AB
= -V
PV
, i
g
< 0,

Switches S3, S4, S5 are switched on and the remaining switches are kept in off position.
The switch S6 should be switched in complementary with S5. Both S5 and S6 should be
switched with a small dead time in between their gating signals. Otherwise, it will damage the
C
PV1
source.

16


Fig. 3.3 Mode II operation, the freewheeling mode




Fig. 3.4 Path showing the direction of grid current in the negative half cycle


Fig. 3.5 The grid current during the freewheeling period and the clamping current
through D
-
and C
PV2
in Mode IV

Mode IV: V
AB
= 0V, i
g
< 0,

17

Similar switching pattern was followed here, S3 and S6 are switched on and remaining
are switched on (See Fig. 3.5). The phenomenon of voltage clamping happens as explained in
the Mode II. Hence, the common mode voltage gets fixed to +V
PV
/2.

3.2 Simulation Results:

The operation of the proposed topology was verified by simulation it in MATLAB/SIMULINK.
The following figures show the plots of Grid current, Grid Voltage, Common mode voltage and
Leakage current.

3.2.1 Ground Leakage Current and Common mode Voltage:

The rms value of leakage current is 19mA which is well under the limits.



Fig. 3.6 Common mode voltage and ground leakage current

3.2.2. Voltages across the stray capacitances at the negative and positive bus of the
inverter:


Fig 3.7 The voltages of the positive PV bus and negative PV bus w.r.t ground
18

Chapter 4
Conclusions and Future Work


The transformerless topologies were analyzed on the basis of common mode voltage and
ground leakage current. The two basic pulse width modulation techniques namely, Bipolar and
Unipolar pulse width modulation techniques for H-Bridge inverter were discussed along with
their advantages and disadvantages for incorporating them in the transformerless photovoltaic
systems connected to the grid.

Various topologies derived from the H bridge inverter were discussed which are suitable
for the requirement. Comparisons were made with respect to the common mode voltage and
losses in the inverter system. Some of the very popular topologies were discussed in detail and
verified the topologies in MATLAB

/SIMULINK.

4.1 Limitations and Future Work:

The topologies were verified by assuming that the power is injected into the grid at unity
power factor. Issues related to the operation other than unity power factor is not considered here.

The voltage across the capacitors was taken to be constant while performing the
simulations and only the current control was done. Also, the parasitic nature of the switches was
neglected while simulating various topologies.

The new topology based on the NPC topology needs to be verified considering the device
parasitic and the efficiency calculations are yet to be made.

Simulation results will be verified through hardware experimentation for the new
topology and the results would be analyzed and compared with the existing topologies.












19

References

[1] Remus Teodorescu, Liserre M., Grid connected converters for Photovoltaic and wind power
systems, John Wiley and Sons, The Atrium, Southern Gate, Chichester, West Sussex, UK,
2011.
[2] IRENA working paper, Renewable energy technologies: Cost Analysis series, Vol.1: Power
sector Issue 4(5), Solar photovoltaics.
[3] Bo Yang, Li W., Gu Y., Cui W., He X., Improved Transformerless Inverter With
Common-Mode Leakage Current Elimination for a Photovoltaic Grid-Connected Power
System, IEEE Transactions on Power Electronics, Vol. 27, No. 2, Feb. 2012, pp. 752-762.
[4] Anandbabu Ch., Fernandes B. G., Improved Full-Bridge Neutral Point Clamped
Transformerless Inverter for Photovoltaic Grid-Connected System, Industrial Electronics
Society, IECON 2013 - 39th Annual Conference of the IEEE , vol., no., pp.7996,8001, 10-13
Nov. 2013
[5] Tams Kerekes, Analysis and Modeling of Transformerless Photovoltaic Inverter Systems,
Ph. D. Thesis, Institute of Energy Technology, Aalborg University, Denmark, 2009.
[6] M. Calais and V. Agelidis; Multilevel converters for single-phase grid connected
photovoltaic systems, an overview, IEEE International Symposium on Industrial Electronics,
7-10 Jul. 1998, pp. 224-229.
[7] Li Zhang, Kai Sun, Lanlan Feng, Hongfei Wu, Yan Xing, A Family of Neutral Point
Clamped Full-Bridge Topologies for Transformerless Photovoltaic Grid-Tied Inverters, IEEE
Transactions on Power Electronics, Vol. 28, No. 2 Feb. 2013, pp. 732-739.
[8] Gonzlez R., Lpez J., Sanchis P., Luis M., Transformerless Inverter for Single-Phase
Photovoltaic Systems, IEEE Transactions on Power Electronics, Vol. 22, No. 2, Mar. 2007, pp.
693-697.
[9] Kerekes T., Teodorescu R., Rodrguez P., Vzquez G., Aldabas E., A New High-Efficiency
Single-Phase Transformerless PV Inverter Topology, IEEE Transactions on Power Electronics,
Vol. 58, No. 1, Jan. 2011, pp. 184-191.
[10] Li Zhang, Sun K., Xing Y., Xing M., H6 Transformerless Full-Bridge PV Grid-Tied
Inverters, IEEE Transactions on Power Electronics, Vol. 29, No. 3, pp. 1229-1238.

Vous aimerez peut-être aussi