Electromagnetic Stresses On Busbar System
Electromagnetic Stresses On Busbar System (photo credit: teknomega.com)
Introduction
When a conductor carries a current it creates a magnetic field which interacts with any other magnetic field
present to produce a force. When the currents flowing in two adjacent conductors are in the same direction the
force is one of attraction, and when the currents are in opposite directions a repulsive force is produced.
In most busbar systems the current-carrying conductors are usually straight and parallel to one another.
The force produced by the two conductors is proportional to the products of their currents.
Normally in most busbar systems the forces are very small and can be neglected, but under short-circuit
conditions, they become large and must be taken into account together with the conductor material fibre stresses
when designing the conductor insulator and its associated supports to ensure adequate safety factors.
The factors to be taken into account may be summarised as follows:
1. Stresses due to direct lateral attractive and repulsive forces.
2. Vibrational stresses.
3. Longitudinal stresses resulting from lateral deflection.
Figure 1 Short-circuit current waveform
4. Twisting moments due to lateral deflection.
In most cases the forces due to short-circuits are applied very suddenly. Direct currents give rise to unidirectional
forces while alternating currents produce vibrational forces.
Maximum stresses
When a busbar system is running normally the interphase forces are normally very small with the static weight of
the busbars being the dominant component.
Under short-circuit conditions this is very often not the case as the current rises to a peak of some thirty
times its normal value, falling after a few cycles to ten times its initial value.
These high transitory currents create large mechanical forces not only in the busbars themselves but also in their
supporting system.
This means that the support insulators and their associated steelwork must be designed to withstand these high
loads as well as their normal structural requirements such as wind, ice, seismic and static loads.
The peak or fully asymmetrical short circuit current is dependent on the power factor (cos ) of the busbar system
and its associated connected electrical plant. The value is obtained by multiplying the r.m.s. symmetrical current
by the appropriate factor given in Balanced three-phase short-circuit stresses.
If the power factor of the system is not known then a factor of 2.55 will normally be close to the actual system
value especially where generation is concerned. Note that the theoretical maximum for this factor is 22 or 2.828
where cos = 0. These peak values reduce exponentially and after approximately 10 cycles the factor falls to
1.0, i.e., the symmetrical r.m.s. short circuit current.
The peak forces therefore normally occur in the first two cycles (0.04 s) as shown in Figure 1 below.
In the case of a completely
asymmetrical current wave, the forces
will be applied with a frequency equal
to that of the supply frequency and
with a double frequency as the wave
becomes symmetrical. Therefore in
the case of a 50 Hz supply these
forces have frequencies of 50 or 100
Hz.
The maximum stresses to which a
bus structure is likely to be subjected
would occur during a short-circuit on a
single-phase busbar system in which
the line short-circuit currents are
displaced by 180.
In a three-phase system a short-
circuit between two phases is almost
identical to the single- phase case and
although the phase currents are
normally displaced by 120, under short-circuit conditions the phase currents of the two phases are almost 180
out of phase. The effect of the third phase can be neglected.
In a balanced three-phase short-circuit, the resultant forces on any one of the three phases is less than in
the single-phase case and is dependent on the relative physical positions of the three phases.
In the case of a single-phase short-circuit, the forces produced are unidirectional and are therefore more severe
than those due to a three-phase short-circuit, which alternate in direction. The short-circuit forces have to be
absorbed first by the conductor. The conductor therefore must have an adequate proof strength to carry these
forces without permanent distortion.
Copper satisfies this requirement as it has high strength compared with other conductor materials (Table 2 below).
Table 2 Typical relative properties of copper and aluminium
Properties of Cu and Al Copper(CW004A) Aluminium (1350) Units
Electrical conductivity (annealed) 101 61 % IACS
Electrical resistivity (annealed) 1.72 2.83 cm
Temperature coefficient of resistance(annealed) 0.0039 0.004 / C
Thermal conductivity at 20C 397 230 W/mK
Coefficient of expansion
17 x 10
6
23 x 10
6
/ C
Tensile strength (annealed) 200 250 50 60
N/mm
2
Tensile strength (halfhard) 260 300 85 100
N/mm
2
0.2% proof stress (annealed) 50 55 20 30
N/mm
2
0.2% proof stress (halfhard) 170 200 60 65
N/mm
2
Elastic modulu 116 130 70
kN/mm
2
Specific heat 385 900 J/kg K
Density 8.91 2.70
g/cm
3
Melting point 1083 660 C
Because of the high strength of copper, the insulators can be more widely spaced than is possible with lower-
strength materials.
Methods of reducing conductor stresses
In cases where there is a likelihood of vibration at normal currents or when subjected to short- circuit forces
causing damage to the conductor, the following can he used to reduce or eliminate the effect:
a) Reduce the span between insulator supports.
This method can be used to reduce the effects of both continuous vibration and that due to short-circuit forces.
b) Increase the span between insulator supports.
This method can only be used to reduce the effects of vibration resulting from a continuous current. It will increase
the stresses due to a short-circuit current.
c) Increase or decrease the flexibility of the conductor supports.
This method will reduce the effects of vibration due to continuous current but has very little effect on that due to
short-circuit forces.
d) Increase the conductor flexibility.
This can only be used to reduce the effects of vibration due to a continuous current. The short-circuit effect is
increased.
e) Decrease the conductor flexibility.
This method will reduce the effects of vibration due to either a continuous current or a short-circuit.
It will be noted that in carrying out the various suggestions above, changes can only be made within the
overall design requirements of the busbar system.
Reference: Fundamentals of Power System Protection
Edvard - Electrical engineer, programmer and founder of EEP. Highly specialized for design of
LV high power busbar trunking (<6300A) in power substations, buildings and industry fascilities.
Designing of LV/MV switchgears. Professional in AutoCAD programming and web-design.
Present on Google+.
RSS Feed for Comments
7 Comments
RSS Feed for Comments
Leave a Comment

Vous aimerez peut-être aussi