Multifunctional

Digital Timers
One and Two Module Types
Instruction Manual
4TD
Series
.2
.4
.6
.8
4
T
D
1
C
L
I
P
S
A
L
.1
2 of 4
4TD Series Digital Timer Instruction Manual
Clipsal Australia Pty Ltd
4TD Series Digital Timers
Industrial circuit control is a snap with 4TD Series Digital Timers.
Clipsal 4TD Series Digital Timers offer exceptional control of complex electrical circuits associated with
air conditioning, material handling, lighting, motor starting and process control.
These double and multifunctional devices have time ranges selectable from one second to 10 hours
and feature accuracy of 0.5%. All models are extremely compact and simply snap onto DIN rails for fast
installation. Time delays are easy to set, even after installation, because all adjustments are made on the
front fascia.
Functions Terms
ON D ON delay U Supply voltage
ON DP ON delay with pulse control S Control input
OFF D OFF delay R Switched output
INT Interval timer
INT P Interval with pulse control
INT OFF P Interval with OFF pulse control
APR Asymmetric pulse recycler
AWR Asymmetric work recycler
SPR Symmetric pulse recycler
SWR Symmetric work recycler
IC Inhibit controller
MF
Multifunction - includes functions
ON D, OFF D, INT, ON DP, INT P, INT OFF P, SPR and IC
Clipsal Cat No. Function Contacts
4TD1 ON D + OFF D 1 CO
4TD2 ON D + INT 1 CO
4TD3 SPR + SWR 1 CO
4TD4 APR + AWR 2 CO
4TD5 MF 1 CO
4TD6 MF 2 CO
Contacts
Number of contacts 1 CO or 2 CO
Contact type Single throw
Rated voltage 250V a.c.
Rated current 8A
Rated breaking capacity 2000 VA (resistive load)
Contact material AgNi.
NOTE: Timers not suitable for switching uorescent loads without additional Clipsal Contactor.
Selectable Time Ranges
1 second 10 seconds 1 minute 10 minutes 1 hour 10 hours
3 of 4 Clipsal Australia Pty Ltd
4TD Series Digital Timer Instruction Manual
Installation Instructions
1. Select appropriate timer for application.
2. Fit timer to DIN rail.
3. Connect power supply, wire switch control input, where appropriate, load to switch terminals.
4. Adjust TIME dial to appropriate number, set ROTARY DIAL SELECTOR switches to required setting (x1/
x10 time; seconds, minutes or hours), set ROTARY FUNCTION SELECTOR switch to required setting.
NOTE: Function on 4TD4 set by connecting a wire loop.
Example: 4TD1 (ON D) on delay. To delay switching load by eight seconds, adjust red time dial to .8 and set
DIP switches as follows:
10
s
r
T
IM
E
F
U
N
C
.2
.4
.6
.8
TIME
Function Diagram Description
ON D
ON delay
On application of the supply voltage, the timer starts to run.
After the time t has elapsed, the relay switches ON.
ON DP
ON delay with
pulse control
Supply voltage must remain ON. Function is controlled by the control
input. When the control input goes ON, the timer starts to run. After
the time t has elapsed, the relay switches ON. When the control
input goes OFF, the timing run is broken and the relay trips out. This
function enables control of switching delays by a small current - for
example via a sensor.
OFF D
OFF delay
Supply voltage must remain ON. Function is controlled by the control
input. When the control input goes ON, the relay turns ON. When the
control input goes OFF, the timer starts to run. After the time t has
elapsed, the relay switches OFF. If the control input goes back to ON
before the time t expires, the time already elapsed is cancelled and
restarts from zero on the next cycle.
INT
Interval timer
On application of the supply voltage, the relay immediately switches
and the timer starts to run. After the time t has elapsed, the relay
switches OFF.
INT P
Interval with
pulse control
Supply voltage must remain ON. Function is controlled by the control
input. On a signal from the control input independent of duration this
signal pulse is converted to a xed duration delay. Timing starts on
the positive going edge of control input, the timer starts to run and
the relay switches ON immediately. The relay turns OFF after the
time t has elapsed. During the timing period, changes to the control
input are ineffective.
INT OFF P
Interval with
OFF pulse
control
Supply voltage must remain ON. Function is controlled by the control
input. When the control input goes ON, a dened pulse length is
generated. Starting at the negative going edge of the control input,
the relay switches ON and trips at the end of the timing run. During
the time period, changes on the control input are ineffective.
SPR
Symmetrical
recycler, pause
start
On application of the supply voltage, the relay cycles pulse start
between ON and OFF for the preset time, beginning with the
ON phase.
SWR
Symmetrical
recycler, start
On application of the supply voltage, the relay cycles pulse between
ON and OFF for the preset time, beginning with the ON phase.
CLIPCOM/17619 July 2008
F231/04
Clipsal Australia Pty Ltd reserves the right to change specifications,
modify designs and dis con tin ue items without incurring obligation
and whilst every effort is made to ensure that descriptions,
specifications and other in for ma tion in this catalogue are correct, no
warranty is given in respect thereof and the company shall not be
liable for any error therein.
Clipsal Australia Pty Ltd. The identied trademarks and copyrights
are the property of Clipsal Australia Pty Ltd unless otherwise noted.
Product of Clipsal Australia Pty Ltd
A member of Schneider Electric
Contact us: clipsal.com/feedback
National Customer Care Enquiries:
Tel 1300 2025 25
Fax 1300 2025 56
clipsal.com
APR
Asymmetrical
recycler, pulse
start
On application of the supply voltage, the relay cycles between ON
and OFF for the preset time, beginning with the OFF phase. The ON
and OFF times are separately adjustable.
AWR
Asymmetrical
recycler, pulse
start
On application of the supply voltage, the relay cycles between ON
and OFF for the preset time, beginning with the ON phase. The ON
and OFF times are separately adjustable.
IC
Inhibit
controller
On application of the supply voltage, the relay switches ON,
regardless of the state of the control input at this point in time. After
that, the rst positive going edge of the control input starts the timer.
Each subsequent positive going edge (provided that it occurs before
the timing run is completed) resets the timer for a further period.
At the end of the timing run, the relay switches OFF. The device is
then inhibited against further control inputs. Resetting can only occur
by removing and reconnecting the supply.
MF
Multifunction
Include functions: ON D, ON D P, INT, INT P, OFF P, INT OFF P,
SPR, and IC.
Technical Data
Design according to OVE-EN 60669
Rated voltage 24V a.c./d.c.; 110 to 240 V~ a.c.
Admissible voltage range 10%
Time ranges selectable 1s - 10 hr
Additional adjustment by potentiometer 5 - 100%
Time delay range 0,05 s - 1 hr
Accuracy 0,5%
Reset time 100 ms
Repeat accuracy to full scale value 0,5%
Minimum impulse duration 50 ms
Ambient operating temperature -25 - +55C
Temperature coefcient 0,01 %/K
Degree of protection IP40
Mechanical Data
Frame size 45mm
Socket size 87.5mm
Module width 17.5mm (1 CO), 35mm (2 CO)
Mounting Quick fastening with 2 lock-in positions on DIN rail EN50022
Upper and lower terminals Lift terminals
Terminal protection Finger and hand touch safe
Terminal capacity 1-6mm
NOTE: Segregation requirements AS/NZS 3000 Wiring Rules