Académique Documents
Professionnel Documents
Culture Documents
-t-chart. This
application is also suited similarly for the use of recuperator
burners. Not shown therein, but optionally available, the
burner unit can be equipped with an additional cooling-air
pipe and an additional cooling-air solenoid valve offering
the opportunity to operate the burner as cooling unit. The
cooling-air quantity supplied can be selected significantly
higher than the proper combustion-air quantity.
As a consequence of standard revision, direct burner
ignition at full power was limited to a maximum of 120 kW.
As far as certain preconditions have been met, the aforesaid
advantages can also be used moreover. In any case, the
combustion chamber and/or useable space, waste-gas
tracts as well as piping system must be configured so that
the maximum pressure rise is considered [1]. The relevant
evidence thereto must be furnished by the manufacturer
of thermoprocessing installation. The peak values of safety
times must be taken into account as well.
If direct ignition at full power is not possible, the stand-
ard offers some practical opportunities to limit the start
Fig. 2:
Standard application with-
out start-load limitation,
shown on the example of a
NOXMAT-HGBE high-velocity
burner (real and schematic
representation with V
-t-chart)
R
e
a
d
t
h
e
c
o
m
p
l
e
t
e
r
e
p
o
r
t
C
L
I
C
K
H
E
R
E