Vous êtes sur la page 1sur 27

OMICRON Page 1 of 27

Application Note
How to handle Zero Sequence Elimination
in Test Universe
Author
Ren Mathis | rene.mathis@omicron.at
Date
Sept 25th, 2012
Related OMICRON Products
Test Universe, CMC Test Sets
Application Area
Protection Testing (Differential Protection)
Keywords
Zero Sequence Elimination, Calculation, Reference Winding
Version
v1.2
Document ID
ANS_11013_ENU




OMICRON 2012 Page 2 of 27
Content


Introduction to zero sequence elimination ........................................................................................ 3 1
Why is zero sequence elimination necessary?.............................................................................. 3 1.1
YD interposing transformers .......................................................................................................... 5 1.2
Calculating the corrected output currents ......................................................................................... 6 1.2.1
Example calculations of YD1 interposing transformers ..................................................................... 9 1.2.2
YDY interposing transformers ....................................................................................................... 9 1.3
General ............................................................................................................................................. 9 1.3.1
Example calculation of YDY0 interposing transformers: ................................................................. 10 1.3.2
IL-I0 Numerical Zero Sequence Elimination ................................................................................ 11 1.4
Formulas of commonly used interposing transformers ............................................................... 12 1.5
Effect of different zero sequence elimination settings on the calculation ................................... 14 2
Importance of zero sequence elimination setting for testing the I
DIFF
/I
BIAS
characteristic ............ 14 2.1
Zero sequence elimination setting in Diff Operating Characteristic module (example) .............. 15 2.2
Zero sequence elimination setting in the Diff Configuration module ........................................... 17 2.3
Choosing the correct Reference Winding ........................................................................................ 19 3
Configuring the Test Object with interposing transformers .......................................................... 21 4
Working with Ground Current Measurement inputs (CT)............................................................... 21 5
General ........................................................................................................................................ 21 5.1
Simulating the additional CT with the CMC ................................................................................. 22 5.2
Appendix ............................................................................................................................................. 23 6
Where the factor comes from ................................................................................................. 23 6.1
Interposing CT selection guide .................................................................................................... 24 6.2

























Please use this note only in combination with the related product manual which contains several important safety
instructions. The user is responsible for every application that makes use of an OMICRON product.


OMICRON electronics GmbH including all international branch offices is henceforth referred to as OMICRON.

OMICRON 2011. All rights reserved. This application note is a publication of OMICRON.
All rights including translation reserved. Reproduction of any kind, for example, photocopying, microfilming, optical
character recognition and/or storage in electronic data processing systems, requires the explicit consent of OMICRON.
Reprinting, wholly or in part, is not permitted.
The product information, specifications, and technical data embodied in this application note represent the technical
status at the time of writing and are subject to change without prior notice.
We have done our best to ensure that the information given in this application note is useful, accurate and entirely
reliable. However, OMICRON does not assume responsibility for any inaccuracies which may be present.
OMICRON translates this application note from the source language English into a number of other languages. Any
translation of this document is done for local requirements, and in the event of a dispute between the English and a non-
English version, the English version of this note shall govern.

OMICRON 2012 Page 3 of 27
Introduction to zero sequence elimination 1
Why is zero sequence elimination necessary? 1.1
An example where zero sequence elimination is necessary can be seen in Figure 1. There is an outside
earth fault which causes the relay to trip because of a measured differential current. Please note that a
differential protection relay must not trip in case of outside faults!
In this example, the current magnitudes in Figure 1 are displayed by the number of arrows. Also, assume
that the ratios between HV side and LV side of the transformer and as well the CT ratios are one. If the
currents on the HV Side are compared with the currents on the LV side, it can be seen that the currents
flowing into the relay are not equal. This unbalanced sum of currents can only occur when one side of the
transformer is grounded. The reason for that can be explained with the following example. Think about a
fault on the LV side like in Figure 1, the fault current from the LV side will be transferred to the HV side. Now
the sum of currents in the star point has to be zero after Kirchhoff's 1
st
law. Therefore the half of the
transformed fault current will flow back through the healthy phases. This will lead to differential currents,
because the currents in the healthy phases of the LV side are 0.
As shown in Figure 1, the reference arrows indicate the direction towards the protected object on both sides.
This definition is valid for the whole document and as well for all settings in the Test Universe Advanced
Differential Modules.


Figure 1: YYN0 transformer with a fault on the LV-side
In the event of a line-neutral fault, the circuit for the zero sequence component of the fault current closes via
the grounded star point of the transformer on the LV side, which lies within the transformer differential
protection zone.
Therefore, this zero sequence component appears as a differential current in the measuring system of the
differential protection relay. For this reason, the zero sequence component of the three-phase system must
be eliminated from the phase currents on the LV side. The following calculation examples show how the
relay behaves if the zero sequence component is eliminated, and what happens if the zero sequence
component is not eliminated. This elimination is done either by the relay or by an interposing transformer. [1]
The amount of current is again displayed by the number of arrows.


OMICRON 2012 Page 4 of 27
Current on HV side

); Current on LV side

);


Calculation without elimination of the zero sequence component:

Bias current:

| |

| (

) (

) (

)

Differential current:

| |(

) (

)| (

)

The differential relay would trip

The result of the differential current calculation would lead to a trip of the differential protection relay,
although the fault is located outside of the protected area. In case of outside faults the relay should not
determine a differential current.


Calculation with elimination of the zero sequence component:

Zero sequence current:

) (

);

) (

)

Corrected HV current:

) (

) (

)

Corrected LV current:

) (

) (

)

Bias current:

| |

| (

) (

) (

)

Differential current:

| |(

) (

)| (

)

The differential relay would not trip


Therefore, the zero sequence elimination function is necessary in order to distinguish a real fault inside the
transformer from an outside fault.

It is recommended to use the Advanced Differential modules for testing three-phase differential protection
systems, because these modules are able to automatically calculate the adequate output currents. They
take into consideration the vector group, type of zero sequence elimination, I
BIAS
calculation, and others.
Please note that it is also possible to use the State Sequencer or QuickCMC modules for these tests, but
then all calculations must be done manually.

The goal of this application note is to provide assistance with choosing the correct zero sequence elimination
settings in Test Universe.

OMICRON 2012 Page 5 of 27
In general, there are two possibilities for how this zero sequence elimination can be done. The relay can do
it with an implemented numerical algorithm, or it can be done physically by using an interposing transformer
in the current path before the relay. As we already had a small example (Figure 1) of how the mathematical
zero sequence elimination can be done with help of the symmetrical components (I
L
-I
0
), we want to have a
more detailed look at interposing transformers.

As the name suggests, an interposing transformer is installed between the secondary winding of the main
CT and the relay in order to correct the current flowing to the relay. The interposing transformer can be used
on the high voltage side and/or the low voltage side of the power transformer being protected. If it is used on
the grounded side, it provides a convenient method for establishing a delta connection for the elimination of
zero sequence currents.
It is important to find out which zero sequence elimination method is used in the protection system in order
to be able to choose the correct settings in Test Universe as seen in Figure 2. In the following chapters,
there is further information on how to deal with interposing transformers.


Figure 2: Zero Sequence Elimination settings in the Test Object
YD interposing transformers 1.2
Before the invention of digital relays, interposing transformers were mainly used together with
electromechanical relays for phase-matching, amplitude correction and zero sequence elimination purposes
as seen in Figure 3. However, they can also be found in transformer protection systems with newer relays.
The reason for this is often that an older relay has been replaced with a digital one. When this occurs, the
YD interposing transformer is still in place, and the zero sequence elimination done internally by the relay is
not necessary. Additionally, they are often used when the relay simulates this YD interposing transformers
internally by software in order to perform the phase matching and zero sequence elimination.

OMICRON 2012 Page 6 of 27


Figure 3: YD interposing transformers with protection relay
There are also some relays which can simulate YD interposing transformers internally:

SEL relays
Toshiba GRT100 (beta compensation method)
Reyrolle DUOBIAS
GE Multilin SR745 and T60
AREVA KBCH
Calculating the corrected output currents 1.2.1

In Figures 4-5, the equivalent circuit diagram of a YD1 interposing transformer is displayed. In this chapter, a
description is provided of how the transmission formulas from a YD1 transformer can be derived.



Figure 4: Equivalent circuit diagram of YD1 interposing transformer on HV-side







OMICRON 2012 Page 7 of 27

Figure 5: Secondary Winding of YD1 interposing transformer on HV-side
Here are the equations after Kirchhoffs 1
st
law:

I:



II:



III:




I:

)

II:

)

III:

)


(

[



] (

)


n... ratio
I
HVLx
... currents on the main CT secondary side (before interposing-transformer)
I
HVLx
... corrected currents on the relay side (after interposing-transformer)
... Chapter 6.1 explains this factor



OMICRON 2012 Page 8 of 27
Figure 6 shows the corresponding vector diagram of the YD1 interposing transformer on the HV side.


Figure 6: Vector diagram (primary and secondary values) of YD1 interposing transformer on HV-side

With the aid of the vector diagram in Figure 6, it is possible to determine the corrected currents (I
HVLx
)
graphically.


Figure 7: Graphical determination of



The graphical calculation above leads to the following formula:



OMICRON 2012 Page 9 of 27
Example calculation of YD1 interposing transformer on HV-side 1.2.2


Figure 8: YD1 interposing transformer (single-phase fault)

YDY interposing transformers 1.3
General 1.3.1
YDY interposing transformers have the same function as YD interposing transformers. They are also used in
the secondary current path of the main CT. An example can be seen in Figure 9.



Figure 9: YDY interposing transformers + protection relay


OMICRON 2012 Page 10 of 27
Because YDY0 interposing transformers are very commonly used for zero sequence elimination, the
corresponding transformation formulas for this interposing transformer type are below. In this case these
formulas are valid for the HV-side.

)

The following example calculation is based on these formulas.


Example calculation of YDY0 interposing transformer on HV-side 1.3.2


Figure 10: YDY0 interposing transformer (single-phase fault)



OMICRON 2012 Page 11 of 27
IL-I0 Numerical Zero Sequence Elimination 1.4

The IL-I0 zero sequence elimination method is a numerical method which is very often used in digital relays.
This method requires the relay to measure the 3 phase currents and calculate the zero sequence
component

with the aid of the following formula:


)

Next, the relay subtracts the zero sequence component

from the phase currents in order to do the


necessary zero sequence elimination. Ultimately, the relay uses the following current values for the I
BIAS

calculation and I
DIFF
calculation.

......... Corrected phase currents without zero sequence component



The IL-I0 method and YDY0 interposing transformers provide two different ways to eliminate zero sequence
currents. They both provide corrected output currents that are equal and will not cause a differential relay to
trip. The following relays work with the IL-I0 zero sequence elimination method:

AREVA 63x and 64x relay series
SEL relays
ABB RET relays
Toshiba GRT100 (alpha method)
SIEMENS 7UT6xx


OMICRON 2012 Page 12 of 27
Formulas of commonly used interposing transformers 1.5

Table 1 shows further interposing transformer types. The equations in this table always result in the
corrected output current without zero sequence component for the YDx and YYx vector groups.


Table 1: Further interposing transformers [2]


OMICRON 2012 Page 13 of 27


Table 2: Further interposing transformers part 2 [2]


OMICRON 2012 Page 14 of 27
Effect of different zero sequence elimination settings on the calculation 2
If the zero sequence elimination method is changed from "none" to e.g. "IL-I0" in the Test Object, the output
currents visible in the vector view (Figure 11) of the CMC may change as well. This chapter explains why the
output currents of the CMC change if the zero sequence elimination setting in the Test Object is changed.


Figure 11: Vector View (Output currents)
In order to explain this behavior, let's have a closer look at the Diff Operating Characteristic module:

The Diff Operating Characteristic module is used to test the operating characteristic of differential relays. The
basic principle is that the operating characteristic represents the ratio between the stabilization current, I
BIAS
,

and differential current, I
DIFF
. Therefore, the CMC has to output current values on the primary side and
secondary side which are related to the I
BIAS
/ I
DIFF
values in the operating characteristic.
Importance of zero sequence elimination setting for testing the I
DIFF
/I
BIAS
2.1
characteristic
The operating characteristic of a differential protection relay is tested with specific I
DIFF
/ I
BIAS
values. The test
set cannot directly output these I
DIFF
and I
BIAS
values to the relay; it can only output phase currents on the
secondary side of the HV- and LV-winding of the transformer.
By using the zero sequence elimination functionality in the relay, or an interposing transformer to correct the
phase currents, the relay would not calculate the same I
DIFF
and I
BIAS
values that were chosen based on the
characteristic alone. This is due to the correction, which is done by the relay or the interposing transformer.
This will probably lead to failed test results because the I
DIFF
and I
BIAS
values in TU are not equal to the
calculated I
DIFF
and I
BIAS
values from the relay. Therefore, it is very important to know the interposing device
of the differential protection system so that the software correctly calculates the output currents.

Additionally, it is important to note that the software does not simulate these interposing transformers; it just
considers the correction system, so that the characteristic can be tested properly. As a consequence, if the
relay is connected to interposing transformers and interposing transformers for zero-sequence elimination
are selected in the Test Object, then the test currents need to be injected into these interposing
transformers, and not directly into the relay (see chapter 4).
Ultimately, the I
DIFF
and I
BIAS
values calculated from the relay and the values visible in Test Universe have to
be equal.

OMICRON 2012 Page 15 of 27
Zero sequence elimination setting in Diff Operating Characteristic module (example) 2.2
For further explanations, please follow the next example in the Diff Operating Characteristic module:

First, select Generator as the Protected Object, because when the Protected Object is a YY0 transformer, a
shorted delta winding is assumed between the HV- and the LV-winding. The transformer simulated is shown
in Figure 12. Nominal values are set according to Figure 12.
The CT ratios in the CT tab have to be set to one on both sides of the transformer. The "Reference Winding"
in the Protection Device tab has to be set to the "High Voltage" side as seen in Figure 16. Additionally, use
the following

formula in the Protection Device tab:

||






Figure 12: Protected Object-tab (Differential RIO-block)
Next, set the test shot for I
DIFF
= 1A and I
BIAS
= 2A (Fault type = L1-E) in the Test View of this module. Then,
open the Vector View shown in Figure 13 and look at the output currents:

OMICRON 2012 Page 16 of 27


Figure 13: Vector View in Diff Operating Characteristic module
If the output currents of the CMC were calculated according to the selected test point (I
DIFF
and I
BIAS
value),
we should be able to calculate this expected point of the characteristic such that I
DIFF
= 1A and I
BIAS
= 2A.

| | |

||



||||



Now, if the Protected Object is changed to Transformer and the Zero Sequence Elimination-type to YDY-
interposing transformer, the output values change to those shown in Figure 14.

If the I
DIFF
and I
BIAS
calculations are done with the values in Figure 14, the calculated I
DIFF
and I
BIAS
values
from the relay and the values in TU are different. This is because these values are not the actual values that
the relay will use to calculate I
DIFF
and I
BIAS
. This is shown more clearly in the following calculation.

| | |


||



||||



When the calculated values from the relay are compared to the test point in Test Universe, it can be seen
that they are different, which should not be the case.

Explanation of why these values are different:

In reality the relay measures the 3 phase currents and afterwards it does all the necessary corrections
including amplitude correction, phase matching, and if necessary, zero sequence elimination. This means
that the relay always takes the corrected phase currents for the calculation of I
DIFF
and I
BIAS
.

In this case, we want to test a certain point on the characteristic. In order to get a positive assessment, the
relay has to determine exactly the same point as we wanted to test. Because the ratios of the transformer
and the CTs are the same, no amplitude correction is necessary. Furthermore, the vector group index of the
transformer model (YY0) is 0, which means that no phase matching has to be done. However, the zero
sequence component of the HV side phase currents has to be eliminated before the calculation of I
DIFF
and

OMICRON 2012 Page 17 of 27
I
BIAS
is done. In order to get the same values for I
DIFF
and I
BIAS
in the relay and in the Test Universe, this zero
sequence component correction has to be considered by Test Universe.


Figure 14: YY0 Transformer (Zero Sequence Elimination type: YDY interposing transformer)
Now, take the output values of the test set shown in Figure 14 and make use of the formulas mentioned in
chapter 1.3 YDY interposing transformers to calculate the output currents of the YDY0 interposing transformer,
which are similar to the input currents of the relay. For this calculation, note that a phase shift of 180 is
equivalent to changing the sign of the value.

High Voltage Side correction with interposing transformer:

( () )

( () )

( () )

Low Voltage Side correction with interposing transformer:

( () ())

( () ())

( () ())

By using the corrected phase current values to calculate the differential current I
DIFF
and the stabilization
current I
BIAS
, it can be seen that the relay would correctly calculate the values that were originally selected in
the Diff Operating Characteristic module of Test Universe.

| | |

|

||

|



||||




OMICRON 2012 Page 18 of 27
Zero sequence elimination setting in the Diff Configuration module 2.3
The Diff Configuration module is not used to test the relay with specified I
DIFF
and I
BIAS
values like it is done in
the Diff Operating Characteristic module. In this module, it is only necessary to enter a test current on the
fault side, and the module automatically calculates the current values of the other side according to the
settings in the Adv. Differential RIO-block (Vector group, CT ratio, etc.). These values do not change if the
Zero Sequence Elimination-type in the Adv. Differential RIO-block is changed, because the aim of the
module is to verify proper (non-tripping) operation at through-fault conditions and not to test specified points
of the operating characteristic. In these tests, the I
DIFF
calculated from the relay has always to be zero.


Figure 15: Diff Configuration Module
Example:
We want to output a test current of 1A on the LV side as seen in Figure 15 and the Zero Sequence
Elimination-type in the Adv. Differential RIO-Block is set to "none."
The red zig-zag flash in the diagram indicates that the LV side is the side where the L1-E fault
occurs.
The currents on the HV side (Supply side) are automatically calculated according to the settings in
the Adv. Differential RIO-block. Especially the transformer model and current transformer settings
are important for this calculation. The Zero Sequence Elimination-type in the Adv. Differential RIO-
block is not important for this calculation.
In this test, the relay must not detect a differential current because an outside fault is simulated.
Outside faults should not lead to a trip of the relay because the fault is not within the protected area.
If the Zero Sequence Elimination-type is changed from "none" to "e.g. YD transformer" in the Adv.
Differential RIO-block, no changes regarding the output currents should be noticeable. If an outside
fault leads to a trip of the relay, the settings in the Adv. Differential RIO-block are either incorrectly
entered or the zero sequence elimination function of the relay is not activated.






OMICRON 2012 Page 19 of 27
Choosing the correct Reference Winding 3

Figure 16 shows the setting "Reference Winding" in the Test Object: (Diff RIO block)


Figure 16: Reference Winding (Protection Device-tab)
This information can be found in the manual of the relay, and it is very important to enter this setting in
accordance with the relay manual. In most cases, this information is located in the chapters which explain
how the relay does phase matching and zero sequence elimination.

The reference winding in the Test Universe software is always the side where the fault is simulated.
Therefore, it is not possible to create a test case with a zero sequence component if the reference side is not
grounded.

For these cases, it is necessary to use the Diff Configuration module in order to verify if the relay eliminates
the zero sequence current on the star point grounded sides correctly.


OMICRON 2012 Page 20 of 27
Reference side = star point grounded side:


Figure 17: Reference side = star point grounded side
In Figure 17, the reference side (reference winding) is the HV side (e.g. AREVA P630C), which means that
the reference side is equal to the star point grounded side of the transformer. This allows us to simulate
single-phase faults with a zero sequence component in the Advanced Differential modules.

Reference side star point grounded side:


Figure 18: Reference side star point grounded side
In Figure 18, the reference side is also the HV side (e.g. AREVA P630C), which means that the reference
side is not equal to the star point grounded side of the transformer. Please note that it is still possible to
simulate single-phase faults, but without a zero sequence component because the earth connection is
missing. As already mentioned in such a case, the Diff Configuration module must be used to verify proper
zero sequence elimination.


OMICRON 2012 Page 21 of 27
Configuring the Test Object with interposing transformers 4
In most cases, interposing transformers are simulated in the relay itself, which means that the relay uses
mathematical formulas to simulate the behavior of "interposing transformers" by software (e.g. AREVA P6xx,
SEL787).
However, physical interposing transformers can be implemented in the substation. In this case, it is very
important that the current injection is done before this interposing transformer because this "correction
device" is responsible for phase matching and zero sequence elimination. If the current injection is done
after the interposing transformer, the relay will get wrong current values which can lead to failed test results.

The "Adv. Differential RIO-block" does not know whether the relay simulates the interposing transformer
internally by software or if the interposing transformer is physically implemented in the substation. It is just
important that the settings in the test object are correct for the interposing transformer type.

Working with Ground Current Measurement inputs (CT) 5
General 5.1
Occasionally, the Advanced Differential modules require the "Ground Current Measurement Inputs". This
option can be found in the CT tab in the Test Object as shown in Figure 19.
There are two cases where a "Ground Measurement CT" has to be simulated from the test set in order to do
the tests successful.


Figure 19: Ground Current Measurement Inputs (CT) in Test Object



OMICRON 2012 Page 22 of 27
1. Some relays (e.g. Siemens 7UTxx) are able to measure the star point current directly via an
additional ground current CT and therefore the ground current needs also to be simulated in order to
test the relay properly
2. When a Restricted Earth Fault (REF) protection function and a stabilized differential protection
scheme are working in parallel. During testing of the stabilized differential protection characteristic,
the relay may trip because of the REF functionality when the ground connection is not configured.
Therefore, it is important to enable the checkbox "Use Ground Current Measurement inputs" and to
connect an additional CMC output to the ground measurement CT input of the relay. An example of
a REF scheme can be seen in Figure 20.


Figure 20: Restricted earth fault
Simulating the additional CT with the CMC 5.2
Because all 6 CMC current outputs are used for the stabilized differential protection test an additional
amplifier (CMA156 or CMS156) is necessary to get the 7
th
current output to simulate the neutral current for
the ground current measurement input.

Another option is to deselect this checkbox in the Test Object and to do the wiring manually. As a first step,
the current outputs of the CMC have to be connected to the current inputs of the relay. Next, the feedback
has to be connected to a star and afterwards to be reentered again into the "Ground CT" measurement input
of the relay. Please be aware that this only works in case that the CT ratio of the neutral phase is equal to
the CT ratio of the line phases. A diagram of this can be seen in Figure 21. For proper connection of the
ground current relay input regarding current polarity make sure to check the relay manual.


Figure 21: Building current summation for grounding CT input of protective relay

OMICRON 2012 Page 23 of 27
Appendix 6
Where the factor comes from 6.1


Figure 22: HV-Winding (Y) Figure 23: LV- Winding (D1)


The transferred voltage in a star connection is not the phase-phase voltage (e.g. U
HV12
) but the phase-
neutral voltage (e.g. U
HV1
). This voltage is smaller by the factor of . The problem in this case is that the
transferred voltage of the HV-winding (U
HV1
= phase-neutral voltage) to the LV-Winding is equivalent to the
phase-phase voltage (U
LV12
) of the LV-Winding. Therefore the factor of must be considered in the ratio
calculation of voltages and currents.




OMICRON 2012 Page 24 of 27
Interposing CT selection guide (e.g. Reyrolle DUOBIAS-M) 6.2


Figure 24: Interposing CT selection guide part 1 [3]


OMICRON 2012 Page 25 of 27

Figure 26: Interposing CT selection guide part 2 [3]






OMICRON 2012 Page 26 of 27
List of Literature

[1] MiCOM30 Series Transformer Differential Protection, Application Guide (Issue F, June 2003),
Page 8
[2] Reyrolle DUOBIAS-M reference manual (2 Description of Operation / Figure 3 - Vector Group
Compensation)
[3] Reyrolle DUOBIAS-M reference manual (6 Applications Guide / 7.0 DUOBIAS-M, Interposing CT
Selection Guide)











OMICRON is an international company serving the electrical power
industry with innovative testing and diagnostic solutions. The application of
OMICRON products provides users with the highest level of confidence in
the condition assessment of primary and secondary equipment on their
systems. Services offered in the area of consulting, commissioning,
testing, diagnosis, and training make the product range complete.
Customers in more than 140 countries rely on the company's ability to
supply leading edge technology of excellent quality. Broad application
knowledge and extraordinary customer support provided by offices in
North America, Europe, South and East Asia, and the Middle East,
together with a worldwide network of distributors and representatives,
make the company a market leader in its sector.
Europe, Middle East, Africa
OMICRON electronics GmbH
Oberes Ried 1
6833 Klaus, Austria
Phone: +43 5523 507-0
Fax: +43 5523 507-999
info@omicron.at
Asia-Pacific
OMICRON electronics Asia Limited
Suite 2006, 20/F, Tower 2
The Gateway, Harbour City
Kowloon, Hong Kong S.A.R.
Phone: +852 3767 5500
Fax: +852 3767 5400
info@asia.omicron.at
Americas
OMICRON electronics Corp. USA
12 Greenway Plaza, Suite 1510
Houston, TX 77046, USA
Phone: +1 713 830-4660
+1 800-OMICRON
Fax: +1 713 830-4661
info@omicronusa.com

For addresses of OMICRON offices with customer service
centers, regional sales offices or offices for training,
consulting and commissioning please visit our web site. www.omicron.at www.omicronusa.com

Vous aimerez peut-être aussi