Medium Voltage Products

SHS2
Gas-insulated switching and
isolating apparatus
1
Index
2 1. Description
7 2. Operating mechanisms
9 3. Accessories
14 4. Type available
20 5. Overall dimensions
22 6. Fuses
24 7. Electrical diagrams
34 8. Switchgear applications
2
1
2
3
4 2 2 2
5 6
7 7 7 8 9 7
1. Description
Technical characteristics
The SHS2 switch-disconnectors and isolators are made up
of a stainless steel cylindrical housing, a set of three top
insulators and a set of three bottom insulators made of epoxy
resin, and a front operating mechanism.
The blade contacts for isolation, breaking, closing and
earthing are arranged inside the cylinder in SF6 gas at a
pressure of 125 kPa absolute.
The unit is the sealed for life type complying with the IEC
60694 Standards.
It is therefore free from any problems of gas tightness.
A gas exhaust valve is located in the rear part of the cylinder
for any over-pressure.
The contacts can take up three positions: CLOSED - OPEN -
EARTHED.
The position of the contacts can be verified from the front of
the operating mechanism by means of a reliable indication, in
compliance with IEC 62265-1 and CEI 17-4 and with the IEC
62271-102 and CEI EN 60129 Standards.
The three top insulators act as a support for the fixed
contacts and allow fixing of the main busbars.
The three bottom insulators act as a support for the moving
contacts and allow connection of the cables or of the
busbars.
1 Moving contact
operating shaft
2 Top insulator
3 Upper xed contact
4 Gas exhaust valve
5 Stainless steel
housing
6 Operating mechanism
7 Bottom insulator
8 Moving contact
9 Earth contact
General
The SHS2 switching and isolating apparatus consist of gas-
insulated switch-disconnectors and isolators, suitable for use
in medium voltage metal-enclosed switchgear.
They are used in secondary distribution substations for
supplying lines, power transformers and ring networks.
3
Closed Open Earthed
Furthermore, the metal segregation provided by the housing
considerably reduces the possibility of a short-circuit between
the phases and between the upper and lower contacts of the
same phase due to leakage currents.
The stainless steel housing provides a metal earthed
segregation between the busbar compartment and the feeder
compartment of the unit the apparatus is installed in.
This characteristic ensures maximum personnel safety
during any intervention in the feeder compartment, such as
replacement of one or more fuses or cable maintenance, even
with the main busbars energised.
4
1. Description
Electrical characteristics
Switch-disconnector Isolator Earthing switch
IEC 60265-1 IEC 62271-102 IEC 62271-102
Feeder
Earthing Switch
Feeder
Earthing Switch
(SHS2 ES)
Unit without fuses Unit with fuses Unit without fuses Unit with fuses
Rated voltage kV 24 - - 24 - - -
Rated Normal Current (40 C) A 400-630 - - 400-630 - - -
Frequency Hz 50/60 - - 50/60 - - -
Rated making capacity on short-circuit
Without external earthing switch kAp 31.5-40-50-62.5 31.5-40-50-62.5 N.O. - - N.O. N.O.
With external earthing switch (
1
) kAp - - 2.5 - - 2.5 kA 62.5 kA
Rated short time withstand current - 1s (
1
) kA 12.5-16- 20-25 12.5-16- 20-25 1 12.5-16- 20-25 (
2
) 12.5-16- 20-25 (
2
) 1 12.5-16-20-25
Rated breaking capacity
Mainly resistive load service A 400-630 - - - - - -
No-load transformer service A 4...16 - - - - - -
No-load line service A 25 - - - - - -
No-load cable service A 50 - - - - - -
Ring circuit service A 400 - - - - - -
Operating Mechanism T1-T1M-T2-T2M T1-T1M-T2-T2M T2-T2M T3-V1 T3-V1 - T4
Test parameters for making capacity, breaking capacity and
making capacity under short circuit - rms (IEC 60265-1)
Test Duties
1-2-3-4-5-6-7
- - - - - -
Electrical life E3 E1 E1 - E1 E1 E1
Transfer current secondo IEC 62271-105 A N.O. N.O. Ask ABB N.O. N.O. N.O. N.O.
Maximum overtemperature test under normal load C IEC 60694 - - IEC 60694 - - -
Mechanical life M1 M1 M1
Atmospheric impulse withstand voltage (BIL 1.2/50 s) (BIL 1.2/50 s) (BIL 1,2/50 s)
Phase-Phase towards earth kVp 125 125 125
Between open contacts kVp 145 145 145
Withstand voltage at industrial frequency
Phase-Phase towards earth kVrms/1 min 50 50 50
Between open contacts kVrms/1 min 60 60 60
(
1
) For different values contact ABB.
(
2
) Up to 16 kA for V1 operating mechanism.
Compliance with Standards
Isolator
IEC 60694
CEI EN 60694
Common requirements for high voltage switching
and control apparatus.
IEC 62271-102
CEI 17.4
Isolators and earthing switches with alternating
current and voltage higher than 1000 V.
Switch-disconnector
IEC 60694
CEI EN 60694
Common requirements for high voltage switching
and control apparatus.
IEC 60265-1
CEI 17-9/1
Control circuit-breakers and switch-disconnectors
for high voltage.
Part 1: Control circuit-breakers and switch-
disconnectors for rated voltages higher than 1 kV
and lower than 52 kV.
Switch-disconnector
combined with fuses
IEC 62271-105
CEI EN 60420
Switch-disconnectors combined with high voltage
fuses for alternating current.
The fuses must comply with DIN Standards.
IEC 60694
CEI EN 60694
Common requirements for high voltage switching
and control apparatus.
IEC 60282.1
CEI EN 60282.1
Fuses with voltage higher than 1000 V.
Part 1: current-limiting fuses.
Degrees of protection
Stainless steel enclosure IP65
Operating mechanism IP3X
5
Electrical characteristics
Switch-disconnector Isolator Earthing switch
IEC 60265-1 IEC 62271-102 IEC 62271-102
Feeder
Earthing Switch
Feeder
Earthing Switch
(SHS2 ES)
Unit without fuses Unit with fuses Unit without fuses Unit with fuses
Rated voltage kV 24 - - 24 - - -
Rated Normal Current (40 C) A 400-630 - - 400-630 - - -
Frequency Hz 50/60 - - 50/60 - - -
Rated making capacity on short-circuit
Without external earthing switch kAp 31.5-40-50-62.5 31.5-40-50-62.5 N.O. - - N.O. N.O.
With external earthing switch (
1
) kAp - - 2.5 - - 2.5 kA 62.5 kA
Rated short time withstand current - 1s (
1
) kA 12.5-16- 20-25 12.5-16- 20-25 1 12.5-16- 20-25 (
2
) 12.5-16- 20-25 (
2
) 1 12.5-16-20-25
Rated breaking capacity
Mainly resistive load service A 400-630 - - - - - -
No-load transformer service A 4...16 - - - - - -
No-load line service A 25 - - - - - -
No-load cable service A 50 - - - - - -
Ring circuit service A 400 - - - - - -
Operating Mechanism T1-T1M-T2-T2M T1-T1M-T2-T2M T2-T2M T3-V1 T3-V1 - T4
Test parameters for making capacity, breaking capacity and
making capacity under short circuit - rms (IEC 60265-1)
Test Duties
1-2-3-4-5-6-7
- - - - - -
Electrical life E3 E1 E1 - E1 E1 E1
Transfer current secondo IEC 62271-105 A N.O. N.O. Ask ABB N.O. N.O. N.O. N.O.
Maximum overtemperature test under normal load C IEC 60694 - - IEC 60694 - - -
Mechanical life M1 M1 M1
Atmospheric impulse withstand voltage (BIL 1.2/50 s) (BIL 1.2/50 s) (BIL 1,2/50 s)
Phase-Phase towards earth kVp 125 125 125
Between open contacts kVp 145 145 145
Withstand voltage at industrial frequency
Phase-Phase towards earth kVrms/1 min 50 50 50
Between open contacts kVrms/1 min 60 60 60
(
1
) For different values contact ABB.
(
2
) Up to 16 kA for V1 operating mechanism.
6
1. Description
Health and Safety Management System
Complies with ISO 18001 Standards, certified by an
independent organisation.
Test Laboratory
Complies with UNI CEI EN ISO/IEC 17025 Standards,
accredited by an independent organisation.
Quality System
Complies with ISO 9001 Standards, certified by an
independent organisation.
Environmental Management System
Complies with ISO 14001 Standards, certified by an
independent organisation.
7
6
1
5
2
7
4
3
2. Operating mechanism
1 Switch-disconnector operating seat
2 Earthing switch operating seat
3 Interlocking lever between switch-disconnector and earthing
switch
4 Mechanical position indicators of the mimic diagram
5 Voltage indicator lamps (on request)
6 Key locks on switch-disconnector operation (on request)
7 Key locks on earthing switch operation (on request)
General
The switch-disconnectors use T1-T1M and T2-T2M type
operating mechanisms with separate operating seats for the
isolation and earthing operations.
The isolators use T3 and V1 type operating mechanisms
with separate operating seats for the isolation and earthing
operations and T4 with a single operating seat.
With the T1-T2-T3-T4 operating mechanisms, the opening
and closing operations are carried out manually locally by
means of the operating lever provided.
For the T2 operating mechanism it is also possible to carry
out the opening operation remotely by means of a special
shunt
opening release.
With the T1M and T2M motor operators, the closing and
opening operations are carried out remotely. However, in case
of emergency, they can also be carried out manually locally
using the operating lever provided, or electrically by means of
the special pushbuttons.
The normal power supply voltages for the T1M and T2M
motor operators are:
24 (*) - 48 - 110-220 V DC;
48 - 110 - 220 V AC 50 - 60 Hz.
(*) Only T1M
T1-T1M Operating mechanism with independent
operation on exceeding dead centre
This allows rapid manual or motorized closing and opening of
the switch-disconnector with operating speed independent of
the operator, obtained by using a single spring.
Closing or opening takes place by charging the above-
mentioned spring (either manually of by means of a motor)
until the dead centre is exceeded.
It also carries out rapid manual closing of the earthing switch
with operating speed independent of the operator.
It is used in the SHS2/T1, SHS2/T1/N, SHS2/T1M and SHS2/
T1M/N type of switch-disconnectors.
T2-T2M Operating mechanism with independent stored
energy operation
Allows rapid manual closing of the switch-disconnector with
operation independent of the operator, obtained by means of
a charged spring up to exceeding dead centre.
SHS2/T1M switch-disconnector operating mechanism.
8
4
2
1
5
6
3
2. Operating mechanism
During the closing operation, a separate spring is charged
automatically which stores the energy for opening.
Switch-disconnector opening can be carried out by means of:
the operating lever
a shunt opening release (applied onto the operating
mechanism itself) on request
the release system, activated by the striker fuse in the case
of even a single fuse blowing (only for SHS2/T2F
- SHS2/T2F/N - SHS2/T2MF - SHS2/T2MF/N).
It also carries out rapid manual closing of the earthing switch
with operating speed independent of the operator.
It is used in the SHS2/T2, SHS2/T2/N, SHS2/T2F, SHS2/
T2F/N type switch-disconnectors and in the corresponding
SHS2/T2M - SHS2 T2M/N SHS2/T2MF - SHS2/T2MF/N
motorized versions.
With the T2M operating mechanism, the closing operation can
be carried out from remote or by means of the operating lever.
T3-V1 Operating mechanisms with dependent operation
These allow manual closing of the isolator and earthing switch
with operation speed dependent on the operator.
Closing and opening are obtained by working on the
operating lever. The lever can only be removed after
completion of the operation.
The T3 type operating mechanism is used in the SHS2/I,
SHS2/I/N, SHS2/IF and SHS2/IB type isolators.
The type V1 operating mechanism is used in the SHS2/A type
isolator.
T4 Operating mechanisms with independent operation
These allow manual closing of the earthing switch with
operating speed independent of the operator.
The opening and closing operations are carried out locally
manually by means of an operating lever provided. The lever
can only be removed after completion of the operation.
The type T4 operating mechanism is used in the SHS2/ES
type earthing switch.
1 Isolator and earthing switch operating seat
2 Key locks on isolator and earthing switch
operation (on request)
3 Key locks on earthing switch operation
(on request)
4 Key interlock between isolator and
circuit-breaker
5 Mechanical position indicators of the
mimic diagram
6 Voltage indicator lamps (on request)
SHS2/IB isolator operating mechanism (type T3).
9
Optional accessories
Operating
mechanism
Type
of isolator
S
w
i
t
c
h
-
d
i
s
c
o
n
n
e
c
t
o
r
-
i
s
o
l
a
t
o
r

k
e
y

l
o
c
k
s
E
a
r
t
h
i
n
g

s
w
i
t
c
h

k
e
y

l
o
c
k
s
S
h
u
n
t

o
p
e
n
i
n
g

r
e
l
e
a
s
e
M
i
c
r
o
s
w
i
t
c
h

f
o
r

i
n
d
i
c
a
t
i
o
n

o
f

f
u
s
e

b
l
o
w
n
A
u
x
i
l
i
a
r
y

c
o
n
t
a
c
t
s
D
o
o
r

l
o
c
k
B
u
s
-
s
i
d
e

v
o
l
t
a
g
e

i
n
d
i
c
a
t
o
r

l
a
m
p
s
C
a
b
l
e
-
s
i
d
e

v
o
l
t
a
g
e

i
n
d
i
c
a
t
o
r

l
a
m
p
s

I
n
s
u
l
a
t
o
r

c
r
o
s
s
p
i
e
c
e

w
i
t
h

o
r

w
i
t
h
o
u
t

c
a
p
a
c
i
t
i
v
e

d
i
v
i
d
e
r
s
S
p
a
c
e
d

e
a
r
t
h
i
n
g

s
w
i
t
c
h
F
u
s
e

a
d
a
p
t
e
r
s
R
e
t
r
o

t

K
i
t
T1
SHS2/T1 C C

C C C C C
C
SHS2/T1/N C C C C C C C C
SHS2/T1M C C C C C C C C
SHS2/T1M/N C C C C C C C C
T2
SHS2/T2F C C C ABB C C C C C C
SHS2/T2F/N C C C ABB C C C C C C
SHS2/T2 C C C C C C C C C
SHS2/T2/N C C C C C C C C C
T1-T3-V1
SHS2/IF C C C C C C C C
SHS2/I C C C C C C C C
SHS2/I/N C C C C C C C C
SHS2/IB C C C C C C C C C
SHS2/A C C C C C C C C C
T4
SHS2/ES C C C C C C C
SHS2/T2M C C C C C C C C C
SHS2/T2M/N C C C C C C C C C
SHS2/T2MF C C C ABB C C C C C C
SHS2/T2MF/N C C C ABB C C C C C C
C Assembly by the customer.
ABB Assembly by ABB.
Accessory always supplied.
Not available.
3. Accessories
10
1 Key locks
SHS2 - T1, T2, T3 and V1 operating mechanism (*):
Line-side isolator operation
1 free key IMS open
1 free key IMS closed
1 free key IMS open + 1 free key IMS closed
2 free keys IMS open
2 free keys IMS closed
Earthing switch operation
1 free key ST open
1 free key ST closed
1 free key ST open + free key ST closed
2 free keys ST open
2 free keys ST closed
SHS2/ES - (T4 operating mechanism)
1 free key earthing switch open
1 free key earthing switch open + 1 free key earthing switch closed
1 free key earthing switch closed
2 free keys earthing switches closed
2 free keys earthing switches open
IMS Switch-disconnector.
ST Earthing switch.
(*) A key interlock, with the key free with the line-side isolator closed, is always sup-
plied as a compulsory application.
2 Auxiliary contacts
3 Shunt opening release (only T2-T2M operating mechanism)
These allow the apparatus to be locked in the closed or open
position.
It is possible to combine a maximum of four key locks for T1,
T2 and T3 operating mechanisms, and a maximum of two key
locks for T4 operating mechanisms.
If key locks are not requested, a pre-assembled extension
is supplied which allows the use of padlocks to lock the
operations.
These signal the position of the apparatus state.
These signal the position of the apparatus state.
It is possible to combine a maximum of two closing or
opening contacts for each position (closed/open/earthed).
This is an electromechanical device which, following
energisation of an electromagnet, activates the release lever
of the operating mechanism making the switch-disconnector
open.
Power supply voltages:
24-48-110-220 V DC
24-48-110-220 V AC. 50-60 Hz.
3. Accessories
11
4 Voltage indicator lamps
These can be supplied with one or two sets of three lamps
integrated in the operating mechanism casing.
The device is prepared for verification of concordance of the
phase with fibre optics.
It can be combined with the crosspiece with capacitive
insulators.
This can be supplied to complete the switchgear in the
versions with pole insulators or, alternatively, with pole
capacitive insulators.
Should voltage indicator lamps be requested on the cable
side, it is necessary to install a crosspiece with capacitive
insulators.
The crosspiece is always present in the versions fitted with
fuses.
5 Crosspiece with insulators
This is a mechanical device which does not allow the unit door to
be opened with the earthing switch open.
6 Door lock
This is tted with:
transmission;
interlock;
auxiliary contacts: two closing or opening contacts.
The spaced earthing switch is standard for: SHS2/T2F, SHS2/
T2MF, SHS2/T2MF/N, SHS2/IF, SHS2/ES.
In the SHS2/IB isolator, the earthing switch with making
capacity (62.5 kAp) is available.
7 Earthing switch
12
e
DIN
3. Accessories
8 Contact signalling fuse blown
9 Adapters for fuses
10 Field diffusers
The kit includes all the accessories needed to adapt and mount
three fuses according to DIN Standards with dimension e less
than 442 mm.
Different adapters are available for 292 mm and 192 mm fuses.
The kit includes three eld diffusers to be applied to the end of the
busbars in correspondence with the switchgear closure sheet.
The kit is optional and assembly is by the customer.
The kit must be used, for insulation reasons, in 375 mm units
(should the switchgear manufacturer not provide alternative
solutions).
This solution is already used in ABB UniMix switchgear and
application of the kit requires a busbar cross-section similar to that
of the UniMix switchgear.
When a fuse blows, special kinematics activate a signalling
contact.
13
The kit includes the lateral supports to be assembled on the
stainless steel structure to allow fixing in panels built for SHS2
switch-disconnectors and isolators of the first series.
With regard to the auxiliary electrical connections, it is
necessary to carry out the panel retrofit according to the
electric circuit diagrams, available on request.
11 Retrofit Kit 13 Two-level pressure switch
The device allows the internal pressure of the SHS2 switch-
disconnector to be monitored.
There are two contacts in the device which allow the
operating pressure (contact 1) and the minimum pressure
below which operation is not guaranteed (contact 2).
12 Gas topping up valve
The SHS2 switch-disconnector is sealed and has a life of 30
years.
In the case of extraordinary maintenance, topping up of the
SF6 gas is done through the front valve.
14
SHS2/T1
SHS2/T2
SHS2/T1/N
SHS2/T2/N
SHS2/T1M
SHS2/T1M/N
SHS2/T2M SHS2/
T2M/N
4. Types Available
Switch-disconnectors
SHS2/T1, SHS2/T1/N: three-position switch-disconnector
with manual operating mechanism on exceeding dead
centre.
It is normally used for incoming/outgoing units. (Fig. 1).
SHS2/T2, SHS2/T2/N: three-position switch-disconnector
with manual stored energy operating mechanism. It is
normally used for incoming/outgoing units and can be fitted
with a shunt opening release. (Fig. 1).
SHS2/T2F, SHS2/T2F/N: three position switch-
disconnector with manual stored energy operating
mechanism, fuse-holder frame, release device for fuse
blown, and earthing switch on the load side of the fuse-
holder frame.
It is normally used to make transformer protection units and
can be fitted with a shunt opening release (Fig. 2).
SHS2/T1M, SHS2/T1M/N: three-position switch-
disconnector with motor operator.
It is normally used to make incoming/outgoing units (Fig. 1).
SHS2/T2M, SHS2/T2M/N: switch-disconnector with three
positions with stored energy motor operator.
It is normally used to make incoming/outgoing units and
can be fitted with a shunt opening release (Fig. 1).
SHS2/T2MF, SHS2/T2MF/N: switch-disconnector with
three positions with stored energy motor operator, fuse-
holder frame, release device for fuse blowing and earthing
switch on the load side of the fuse-holder frame.
It is normally used to make transformer protection units and
can be fitted with a shunt opening release (Fig. 2).
Fig. 1 - UniMix P3
15
SHS2/T2F
SHS2/T2F/N
SHS2/T2F
SHS2/T2MF/N
SHS2/I
SHS2/I/N
Earthing switches

SHS2/ES: earthing switch with manual operating mechanism
with independent operation. It is normally used for incoming/
outgoing units (Fig. 7). It has making capacity up to 62.5 kAp.
Isolators
SHS2/I, SHS2/I/N: three-position line-side isolator with
manual operating mechanism with dependent operation.
It is normally used for incoming/outgoing units (Fig. 3).
SHS2/IF: three-position line-side isolator with fuse-holder
frame and earthing switch on the load side of the fuse-
holder frame, both with manual operating mechanism with
dependent operation.
It is normally used for measurement units (Fig. 4).
SHS2/IB: three-position line-side isolator and spaced
earthing switch, interlocked, with manual operating
mechanism with dependent operation.
It is normally used for incoming/outgoing units with fixed
circuit-breakers (Fig. 5).
The spaced earthing switch can be assembled to allow the
use of fixed circuit-breakers with current sensors on board
(standard version), or can be assembled for use of current
transformers according to DIN Standards, installed in
switchgear.
SHS2/A: earthing switch upended with three positions and
spaced earthing switch, interlocked with manual operating
mechanism with dependent operation. It is normally used to
make an incoming unit with fixed circuit-breaker (Fig. 6).
Fig. 2 - UniMix P2 Fig. 3 - UniMix ASR
16
SHS2/IF
SHS2/IB
HD4/UniMix-F
VD4/UniMix-F
SHS2/A
4. Types Available
Fig. 6 - UniMix P1A Fig. 4 - UniMix M Fig. 5 - UniMix P1F Fig. 7 - UniMix A
17
Type Dimensions U [kV] In [A]
Icw [kA]
Unit
Width
UniMix
Unit
UniMix
SHS2/T1 24.04.12 1VCD003305 24 400 12,5 500 P3
SHS2/T1 24.04.16 1VCD003305 24 400 16 500 P3
SHS2/T1 24.06.16 1VCD003305 24 630 16 500 P3
SHS2/T1 24.06.20 1VCD003305 24 630 20 500 P3
SHS2/T1 24.06.25 1VCD003305 24 630 25 500 P3
SHS2/T1/N 24.04.12 1VCD003307 24 400 12,5 375 P3
SHS2/T1/N 24.04.16 1VCD003307 24 400 16 375 P3
SHS2/T1/N 24.06.16 1VCD003307 24 630 16 375 P3
SHS2/T1/N 24.06.20 1VCD003307 24 630 20 375 P3
SHS2/T1/N 24.06.25 1VCD003307 24 630 25 375 P3
SHS2/T2 24.04.12 1VCD003309 24 400 12,5 500 P3
SHS2/T2 24.04.16 1VCD003309 24 400 16 500 P3
SHS2/T2 24.06.16 1VCD003309 24 630 16 500 P3
SHS2/T2 24.06.20 1VCD003309 24 630 20 500 P3
SHS2/T2 24.06.25 1VCD003309 24 630 25 500 P3
SHS2/T2/N 24.04.12 1VCD003311 24 400 12,5 375 P3
SHS2/T2/N 24.04.16 1VCD003311 24 400 16 375 P3
SHS2/T2/N 24.06.16 1VCD003311 24 630 16 375 P3
SHS2/T2/N 24.06.20 1VCD003311 24 630 20 375 P3
SHS2/T2/N 24.06.25 1VCD003311 24 630 25 375 P3
SHS2/T2F 24.04.12 1VCD003313 24 400 12,5 500 P2
SHS2/T2F 24.04.16 1VCD003313 24 400 16 500 P2
SHS2/T2F 24.06.16 1VCD003313 24 630 16 500 P2
SHS2/T2F 24.06.20 1VCD003313 24 630 20 500 P2
SHS2/T2F 24.06.25 1VCD003313 24 630 25 500 P2
SHS2/T2F/N 24.04.12 1VCD003315 24 400 12,5 375 P2
SHS2/T2F/N 24.04.16 1VCD003315 24 400 16 375 P2
SHS2/T2F/N 24.06.16 1VCD003315 24 630 16 375 P2
SHS2/T2F/N 24.06.20 1VCD003315 24 630 20 375 P2
SHS2/T2F/N 24.06.25 1VCD003315 24 630 25 375 P2
SHS2/T1M 24.04.12 1VCD003306 24 400 12,5 500 P3
SHS2/T1M 24.04.16 1VCD003306 24 400 16 500 P3
SHS2/T1M 24.06.16 1VCD003306 24 630 16 500 P3
SHS2/T1M 24.06.20 1VCD003306 24 630 20 500 P3
SHS2/T1M 24.06.25 1VCD003306 24 630 25 500 P3
SHS2/T1M/N 24.04.12 1VCD003308 24 400 12,5 375 P3
SHS2/T1M/N 24.04.16 1VCD003308 24 630 16 375 P3
SHS2/T1M/N 24.06.16 1VCD003308 24 630 16 375 P3
SHS2/T1M/N 24.06.20 1VCD003308 24 630 20 375 P3
SHS2/T1M/N 24.06.25 1VCD003308 24 630 25 375 P3
SHS2/I 24.04.12 1VCD003318 24 400 12,5 500 ASR
SHS2/I 24.04.16 1VCD003318 24 400 16 500 ASR
SHS2/I 24.06.16 1VCD003318 24 630 16 500 ASR
SHS2/I 24.06.20 1VCD003318 24 630 20 500 ASR
SHS2/I 24.06.25 1VCD003318 24 630 25 500 ASR
SHS2/I/N 24.04.12 1VCD003319 24 400 12,5 500 ASR
SHS2/I/N 24.04.16 1VCD003319 24 400 16 500 ASR
SHS2/I/N 24.06.16 1VCD003319 24 630 16 500 ASR
SHS2/I/N 24.06.20 1VCD003319 24 630 20 500 ASR
SHS2/I/N 24.06.25 1VCD003319 24 630 25 500 ASR
18
Type Dimensions U [kV] In [A]
Icw [kA]
Unit
Width
UniMix
Unit
UniMix
SHS2/IF 24.04.12 1VCD003317 24 400 12,5 500 M
SHS2/IF 24.04.16 1VCD003317 24 400 16 500 M
SHS2/IF 24.06.16 1VCD003317 24 630 16 500 M
SHS2/IF 24.06.20 1VCD003317 24 630 20 500 M
SHS2/IF 24.06.25 1VCD003317 24 630 25 500 M
SHS2/T2M 24.04.12 1VCD003310 24 400 12,5 500 P3
SHS2/T2M 24.04.16 1VCD003310 24 400 16 500 P3
SHS2/T2M 24.06.16 1VCD003310 24 630 16 500 P3
SHS2/T2M 24.06.20 1VCD003310 24 630 20 500 P3
SHS2/T2M 24.06.25 1VCD003310 24 630 25 500 P3
SHS2/T2M/N 24.04.12 1VCD003312 24 400 12,5 375 P3
SHS2/T2M/N 24.04.16 1VCD003312 24 400 16 375 P3
SHS2/T2M/N 24.06.16 1VCD003312 24 630 16 375 P3
SHS2/T2M/N 24.06.20 1VCD003312 24 630 20 375 P3
SHS2/T2M/N 24.06.25 1VCD003312 24 630 25 375 P3
SHS2/T2M/F 24.04.12 1VCD003314 24 400 12,5 500 P3
SHS2/T2M/F 24.04.16 1VCD003314 24 400 16 500 P3
SHS2/T2M/F 24.06.16 1VCD003314 24 630 16 500 P3
SHS2/T2M/F 24.06.20 1VCD003314 24 630 20 500 P3
SHS2/T2M/F 24.06.25 1VCD003314 24 630 25 500 P3
SHS2/T2MF/N 24.04.12 1VCD003316 24 400 12,5 375 P2
SHS2/T2MF/N 24.04.16 1VCD003316 24 400 16 375 P2
SHS2/T2MF/N 24.06.16 1VCD003316 24 630 16 375 P2
SHS2/T2MF/N 24.06.20 1VCD003316 24 630 20 375 P2
SHS2/T2MF/N 24.06.25 1VCD003316 24 630 25 375 P2
SHS2/IB 24.04.12 1VCD003320 24 400 12,5 750 P1F
SHS2/IB 24.04.16 1VCD003320 24 400 16 750 P1F
SHS2/IB 24.06.16 1VCD003320 24 630 16 750 P1F
SHS2/IB 24.06.20 1VCD003320 24 630 20 750 P1F
SHS2/IB 24.06.25 1VCD003320 24 630 25 750 P1F
SHS2/IB 24.04.12+kit 2CT 1VCD003320 24 400 12,5 750 P1F
SHS2/IB 24.04.16+kit 2CT 1VCD003320 24 400 16 750 P1F
SHS2/IB 24.06.16+kit 2CT 1VCD003320 24 630 16 750 P1F
SHS2/IB 24.06.20+kit 2CT 1VCD003320 24 630 20 750 P1F
SHS2/IB 24.06.25+kit 2CT 1VCD003320 24 630 25 750 P1F
SHS2/IB 24.04.12+kit 3CT 1VCD003320 24 400 12,5 750 P1F
SHS2/IB 24.04.16+kit 3CT 1VCD003320 24 400 16 750 P1F
SHS2/IB 24.06.16+kit 3CT 1VCD003320 24 630 16 750 P1F
SHS2/IB 24.06.20+kit 3CT 1VCD003320 24 630 20 750 P1F
SHS2/IB 24.06.25+kit 3CT 1VCD003320 24 630 25 750 P1F
SHS2/ES 24.12 1VCD003321 24 12,5 500 A
SHS2/ES 24.16 1VCD003321 24 16 500 A
SHS2/ES 24.20 1VCD003321 24 20 500 A
SHS2/ES 24.25 1VCD003321 <24 25 500 A
SHS2/A 24.04.12 1VCD003322 24 400 12,5 750 P1A
SHS2/A 24.04.16 1VCD003322 24 400 16 750 P1A
SHS2/A 24.06.16 1VCD003322 24 630 16 750 P1A
4. Types Available
19
MIX - LM MIX - U MIX - T
IMS-ST1
ST2
IMS-ST1
ST2
MIX - L
IMS-ST
Switch-disconnectors approved by Enel
Can only be ordered together with a complete UniMix unit
in the fixed configuration and with the accessories indicated
below.
Mix-L: three-position switch-disconnector with manual
operating mechanism on exceeding dead centre, with
operation independent of the operator .
It is normally used to make 1L type units according to
DY803/1 and DY 803/116.
Mix-T: three-position switch-disconnector with manual
stored energy operating mechanism, with operation
independent of the operator, fuse-holder frame, release
device for fuse blown, earthing switch on the load side of
the fuse-holder frame.
It is normally used to make 1T type units according to
DY803/2 and DY 803/216.
Mix-U: three-position switch-disconnector with manual
operating mechanism on exceeding dead centre and
Type
Standardised
unit table
U [kV] In [A] Icw [kA]
Mix-L 24.04.12 DY 803/1 24 400 12,5
Mix-L 24.04.16 DY 803/116 24 400 16
Mix-T 24.04.12 DY 803/2 24 400 12,5
Mix-T 24.04.16 DY 803/216 24 400 16
Mix-U 24.04.12 DY 803/3 24 400 12,5
Mix-U 24.04.16 DY 803/316 24 400 16
Mix-Lm 24.04.12 DY 803/4 24 400 12,5
Mix-Lm 24.04.16 DY 803/416 24 400 16
spaced earthing switch, both with operation independent of
the operator.
It is normally used to make 1UT type units according to
DY803/3 and DY 803/316.
Mix-LM: three-position switch-disconnector with motor
operator (24 V DC auxiliary voltage) on exceeding dead
centre.
It is normally used to make 1LE type units according to
DY803/4 and DY 803/416.
20
SHS2/.../N for units 375 mm wide
The SHS2 switch-disconnectors and isolators have been
designed with a 230 mm pole centre distance.
As an example, the gure shows the dimensions of the SHS2/T1
type of switch-disconnector.
The overall dimensions of the different apparatus are available on
request. For detailed information and other types of apparatus,
please contact us.
5. Overall dimensions
21
SHS2 for units 500 mm wide
22
F (N)
60
50
40
30
20
10
10 20 30 40 S (mm)
F = Striker force.
S = Striker run.
Three fuses for transformer protection can be connected in
series with the SHS2 switch-disconnector, with dimensional
characteristics complying with DIN 43625 Standards.
The fuse striker must have the force and run shown in the
diagram.
Selection of the fuse according to the voltage and power of
the transformer must be made in conformity with the data
indicated in the table.
6. Fuses
Transformer protection and selection of fuses
When the isolators are used to control and protect
transformers, they are fitted with a particular type of current-
limiting fuses which guarantee selectivity with other protection
devices and can take the high transformer connection
currents without deteriorating.
In this case, protection against overcurrents on the medium
voltage side of the transformer is not indispensable since
this task is carried out by the protection provided on the low
voltage side.
The protection on the medium voltage side can be entrusted
just to the fuse, which must be selected taking into account
the no-load connection current, which can take on values
equal to or higher than 10 times the rated current according
to the power of the transformer and to the type of laminations
used (hot laminated or with orientated crystals).
There is the maximum connection current when circuit-
breaker closing takes place corresponding to the voltage
passing through zero.
A further result to be guaranteed is protection against faults in
the low voltage winding and in the stretch of the connection
from this to the circuit-breaker positioned on the secondary,
avoiding the use of fuses with rated current which is too high,
in order to ensure tripping within a short time even under
these fault conditions.
23
Table for selecting fuses for transformer protection (*)
Un
network
Rated power of the transformer (kVA)
25 40 50 63 80 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000
(kV) Rated normal current of the fuse IN (A)
3 10 16 25 25 40 40 40 63 63 63 80 100 100
5 6 10 16 16 25 25 25 40 40 63 63 63 80 100 100
6 6 6 16 10 16 25 25 40 40 40 63 63 63 80 100 100
10 6 6 10 10 16 16 16 25 25 25 40 40 63 63 63 80 100 100
12 6 6 10 10 10 16 16 16 25 25 25 40 40 63 63 63 80 100
15 6 6 10 10 10 16 16 16 16 25 25 25 40 40 63 63 63 80 80
20 6 6 10 6 6 10 16 16 16 16 25 25 25 40 40 63 63 63 63
24 6 6 10 6 6 10 10 16 16 16 16 25 25 25 40 40 63 63 63
(*) ABB CEF type fuses. Increases in the rated normal current of the fuses must be foreseen in the case of transformer overload or in the case of ambient temperature higher than
40 C.
A rapid check of the short-circuit current at the secondary
terminals of the transformer and on the supply side of the
circuit-breaker on the secondary - if placed at a significant
distance, allows the trip time to be verified on the fuse
blowing curve.
The usage table given below takes both the required
conditions into account, i.e. sufficiently high rated current to
avoid untimely fuse blowing during the no-load connection
stage and, in any case, of a value which guarantees protection
of the machine against faults on the low voltage side.
24
7. Electric circuit diagram
SHS2/T1 electric circuit diagram
Control circuit of the switch-disconnector (24 V DC)
Control circuit of the switch-disconnector (48-110 V DC 110 V AC)
Continues on page 25
25
SHS2/T1 electric circuit diagram
Control circuit of the switch-disconnector (48-110 V DC 110 V AC)
Control circuit of the switch-disconnector (220 V DC / V AC)
Continues on page 26
26
7. Electric circuit diagram
SHS2/T1 electric circuit diagram
Control circuit of the switch-disconnector (220 V DC 220 V AC)
Circuit of the shunt opening release (see note C)
27
SHS2/T2 electric circuit diagram
Circuit of the closing motor
Circuit of the shunt opening release
28
SHS2/T1 - SHS2/T1M - SHS2/N-T1 - SHS2/N-T1M electric circuit diagram
Control circuit of the switch-disconnector
Switch-disconnector and earthing switch auxiliary contacts
7. Electric circuit diagram
29
SHS2/T4 electric circuit diagram
Auxiliary contacts of the earthing switch
Circuit for indication of voltage present busbars and line
30
Circuit for indicating voltage present on the line for the
SHS2/T1, SHS2/T2, SHS2/T3 and SHS2/T4 isolators
Auxiliary contacts of the isolator (see note C), for the SHS2/T1, SHS2/T2 and SHS2/T3 type isolators.
7. Electric circuit diagram
31
Circuit for signalling voltage present on the earth for the
SHS2/T1 and SHS2/T3 isolators
Circuit for signalling fuse blown for the SHS2/T1 and SHS2/
T2 isolators
32
Note: To take development of the product into account it is, in
any case, always useful to refer to the electric circuit diagram
provided with each circuit-breaker.
State of operation shown
The diagram is shown under the following conditions:
switch-disconnector open
earthing switch open
circuits de-energised.
Caption
= Number of diagram figure
* = See the note indicated by the letter
A1 = Switch-disconnector operating mechanism
applications
A4 = Switchgear applications (indicative apparatus and
connections for operating mechanism and signals)
AK = Switch-disconnector auxiliary circuit diagram
-B80/12 = Earthing switch position contact
-B80/L = Position contact open during manual operation of
earthing switch -Q80
-B80-90/12 = Position contact open during manual operation of
earthing switch -Q80 and during manual operation of
the switch-disconnector
-B90/13 = Switch-disconnector position contacts
-B90/C = Position contact open with switch-disconnector
closed
-B90/E = Contact activated by the key lock
-B90/L = Position contact open during manual operation of
switch-disconnector Q90
-B90/O = Position contact open with the switch-disconnector
open
-BE7 = Position contact open during manual operation of the
earthing switch
-BF = Contact signalling medium voltage fuse blown
-BI1...4 = Position contact open with switch-disconnector
closed
-BI2...5 = Position contact open with switch-disconnector open
-BI7 = Position contact open during manual operation of the
switch-disconnector
BI51...53 = Position contacts open with switch-disconnector
BI411...412 = Position contacts of the switch-disconnector
BI413 = Earthing switch position contacts
BI421...422 = Line earth-open position contacts
BI431...432 = Earthing switch-QE position contacts
-BK = Contact activated by the key lock
-BU1...3 = Capacitive dividers located on phases L1, L2, L3 of
the line
-BU1...6 = Capacitive dividers located on phases L1, L2, L3
-BU4...6 = Capacitive dividers located on phases L1, L2, L3 of
the busbars
-C1/L1...L3 = Capacitive dividers located on phases L1, L2, L3 of
the line
-C2/L1...L3 = Capacitive dividers located on phases L1, L2, L3 of
the busbars
-F1-F3 = Medium voltage fuses
-FF13 = Medium voltage fuses
-KC = Auxiliary relay for closing the switch-disconnector
-KO = Auxiliary relay for opening the switch-disconnector
-KD = Auxiliary relay for with two contacts delayed at
attraction and two instantaneous contacts
-MI4 = Motor for operating the switch-disconnector
-MM = Motor for operating the switch-disconnector
-MO = Shunt opening release (see note C)
-MS = Motor for operating the switch-disconnector
-PGN = Lamp for signalling switch-disconnector open
-PRD = Lamp for signalling switch-disconnector closed
-PU1...2 = Voltage indicator located on phases L1, L2, L3 of the
line/busbars
-PUD1 = Voltage indicator located on the line
-PUD2 = Voltage indicator located on the busbars
-Q80 = Earthing switch
-Q90 = Switch-disconnector
-QE = Earthing switch
-QI4 = Switch-disconnector
-RR12 = Suppressors of transients
-S75F = Contact signalling medium voltage fuse blown
-SC = Pushbutton for local switch-disconnector closing
-SO = Pushbutton for local switch-disconnector opening
-SS = Local/remote selector
-TR = Converter
-TR12 = Rectifier
-X = Interface connector with the feeder (outside the unit)
-X1-X3 = Terminal boxes of the operating mechanism
applications
-XB1 = Terminal boxes for the switch-disconnector auxiliary
circuits
-XB2 = Terminal boxes for the circuits inside the switch-
disconnector
XB91...94 = Terminal boxes of the operating mechanism
applications
-XB93 = Terminal boxes of operating mechanism application
7. Electric circuit diagram
33
M
U
M
Delayed movement
Mechanical interlock
between two pieces of
apparatus
Rotary handle operating
mechanism
Pushbutton operating
mechanism
Electric motor operator
Earth (general symbol)
Three conductors
Connection of
conductors
Socket and plug
(female and male)
Motor (general symbol)
Rectier with two
half-waves (with bridge)
Make contact
Break contact
Closing position contact
(limit switch)
Opening position
contact
(limit switch)
Isolator
Switch-disconnector
Control coil
(general symbol)
Control coil of a
relay with delay on
attraction
Lamp (general symbol)
Capacitive divider
Interruttore di
manovra-sezionatore
a doppia interruzione
Graphic symbols for electrical diagrams (IEC 60617 and CEI 3-14 ... 3-26 Standards)
Resistor depending on
the voltage, varistor
34
Fuses
Fuses according to DIN Standards
are available to be combined with
the SHS2 apparatus.
The SHS2 switch-disconnectors and isolators have mechanical,
electrical and layout characteristics ideal for constructing
medium voltage metal-enclosed type switchgear for secondary
distribution substations.
They can be used in standard or arc-proof version units. ABB
is able to offer all the apparatus and components needed to
complete the switchgear units.
Please contact us for further detailed information.
SHS2 switch-disconnector.
Complete with fuse-holder
frame and earthing switch
on load side of the fuses.
SHS2 isolator.
Complete with earthing
switch on load side of
the circuit-breaker.
Circuit-breakers
Both the HD4/R series SF6 gas
insulated medium voltage circuit-
breaker and the VD4/R vacuum circuit-
breaker, with right lateral operating
PR521and REF601
switchgear protection devices
These are provided on board
the HD4/R and VD4/R circuit-
breakers combined with current
sensors of dedicated type. The
REF601 CEI 0-16 version is
also available, specially made to
comply with CEI 0-16 standards.
For further information, please
contact us.
Example of unit with
switch-disconnector
and fuses
8. Switchgear applications
35
REF542plus micro-
processor-based unit
The REF542plus unit carries
out integration of all the
secondary functions relative
to a switchgear unit.
PR512 switchgear protection devices
The PR512 are devices of the self-supplied type and ensure complete protection of the installation
without an auxiliary power supply.
Combined voltage-
current sensors
A range of sensors
is available which
optimally covers the
characteristics of
new generations
of instruments and
of the REF542plus
unit in particular.
The current sensors conform with the
IEC 60044-8 (CDV) Standard, the voltage
sensors with the IEC 60044-7 Standard.
Their dimensions are according to
DIN 42600 Standards.
Current
transformers
The current
transformers
are of the resin
insulated type.
They comply with
the IEC 60044-1
Standards.
Their dimensions are normally according
to DIN 42600 Standards.
Voltage
transformers
The voltage
transformers
are of the resin
insulated type.
They comply with
the IEC 60044-2
Standards.
Their dimensions are normally according
to DIN 42600 Standards.
Example of
unit with
circuit-breaker.
Toroidal cable
type transformers
are also available.
mechanism and
230 mm pole centre
distance, are available
to make units with a
circuit-breaker.
36
Notes
ABB S.p.A.
Power Products Division
Unit Operativa Sace-MV
Via Friuli, 4
I-24044 Dalmine
Tel.: +39 035 6952 111
Fax: +39 035 6952 874
e-mail: sacetms.tipm@it.abb.com
www.abb.com
Contact us
The data and illustrations are not binding. We reserve the
right to make changes without notice in the course of
technical development of the product.
Copyright 2010 ABB.