5 TO 50 TONS YORK CONDENSING UNITS


AND 7.5 TO 10 TONS HEAT PUMP WITH FAN
COILS
HA/HB R-22 7.5 to 50 Tons Condensing Units
EA R-22 7.5 & 10 Heat Pump Condensing Units
KE/LA/LB Fan Coils 5 to 50 Tons
have the following available benefits and options

Please, specify the following:


High/Low Pressure switch, Internal Protections
Filter Drier
Low Sound Operation with Low RPM Fans
5 Years Compressor Warranty
Standard Operation down to 35 F
T2950 365 Days Thermostat
BAS Networkable with free Web Software
ArmorGuard Stainless Steel 316 Corrosion Protection on coils
Steril-Aire UVC Lights
Please, call us!
Samy Rezine
Karine Leblanc
Maher Syada
Michelle Sangalang

310-420-6767
310-420-7066
626-255-6406
626-854-4613

Page 1

samy@rezine.net
karine@rezine.net
maher@rezine.net
michelle@rezine.net

http://www.rezine.net

http://www.rezine.net

LINE CARD

Full line of AC & controls


www.yorkupg.com

City Multi &


Ductless Mini Splits
www.mrslim.com

Custom Air Handlers


allianceairproducts.com

Armor Guard
Rooftop Accessories
www.micrometl.com

Fans all sizes


www.tcf.com

UVC lights for HVAC


www.steril-aire-usa.com

365 Days Various


Thermostats
www.thermostatusa.com
samy@rezine.net
310-420-6767

SS316 Corrosion Coating


www.armorguardss316.com

Quiet & Efficient High CFM


Air Handlers
www.miair.com

Boilers
www.raypak.com

Quietest Fan Coil in the


Market
www.aermec.com

Multi Fuel Absorption


Chillers
www.broad.com

karine@rezine.net
310-420-7066

maher@rezine.net
626-255-6406

Page 2

michelle@rezine.net
626-854-4613

http://www.rezine.net

036-21338-001-C-0703

DESCRIPTION

These Sunline 2000 units are completely assembled, piped and wired
at the factory to provide one-piece shipment and rigging. Each unit is
pressurized with a holding charge of refrigerant-22 for storage and/or
shipping.
The compact design, clean styling, low silhouette, and quiet operation
make these condensing units suitable for almost any outdoor location.
On rooftopsbecause they weigh much less than a single package
unit of similar capacity and are much easier to rig and support. At
ground levelbecause their ample sub-cooling capacity allows them
to be located 60 feet below the evaporator coil.

TECHNICAL GUIDE
SPLIT-SYSTEM
AIR-COOLED
CONDENSING UNITS

All sheet metal parts are constructed of commercial grade (G90) galvanized steel. After fabrication, each part is thoroughly cleaned to
remove any grease or dirt from its surfaces. The external parts are
coated with a powder paint to assure a quality finish for many years.
This UL approved coating system has passed the 750 hour, 20% salt
spray test per ASTM Standard B117.

MODELS: HA090

All models include a 1-year limited warranty on the complete unit. The
compressor carries an additional 4-year warranty.
A complete line of Evaporator Blower units is also offered to meet your
precise capacity and air handling requirements. Refer to Form 03621300-001 for more information on this air side equipment.

FEATURES

208/230/460

208/230/575

VOLT ONLY

VOLT ONLY

Condenser coil constructed of copper tubes and aluminum fins for


durability and long lasting efficient operation.

Permanently attached base rails with fork-lift slots and lifting


holes. This design allows for 3-way fork-lift access and overhead
rigging.

Both high and low pressure controls. Since these controls are
self-contained, there are no capillary lines to be damaged.

Compressor line-break motor protection and crankcase heaters.

Anti-short cycle timer to protect the compressor.

A lockout circuit to prevent the unit from cycling on safety control.

A 24-volt temperature control circuit.

Low ambient operation to 45F accessories for 0F low ambient


operation are available.

A filter-drier (shipped in the unit's compressor compartment for


field installation near the evaporator coil).

Service valves with a back-seating access port for pressure testing the system. Copper stub-outs are factory mounted on the suction and liquid service valves to simplify the field piping
connections.

Separate panel for easy access to the control box without affecting air flow across the condenser coil.

Gauge lines extend out from cabinet to facilitate servicing.

Packaging suitable for outdoor storage

Optional coil guard accessory protect coils with a decorative grille.

FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE

Page 3

http://www.rezine.net
036-21338-001-C-0703

TABLE OF CONTENTS
DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
SEQUENCE OF OPERATION . . . . . . . . . . . . . . . . . 7
GUIDE SPECIFICATIONS . . . . . . . . . . . . . . . . . . . 11
LIST OF FIGURES
Fig. #
1
2
3
4
5

LIST OF TABLES
Tbl. #
1
2
3
4
5

Pg. #

TYPICAL FIELD WIRING WITH AIR HANDLER . . . . . 8


POINT LOADS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
TYPICAL FIELD WIRING WITH 7-1/2 TON
FURNACE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
CENTER OF GRAVITY . . . . . . . . . . . . . . . . . . . . . . . 10
HA090 DIMENSIONS . . . . . . . . . . . . . . . . . . . . . . . . . 10

6
7
8
9

Pg. #

ARI RATINGS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
APPLICATION DATA . . . . . . . . . . . . . . . . . . . . . . . . . . 3
PHYSICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
ELECTRICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
UNIT COOLING CAPACITIES AND POWER
REQUIREMENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
SYSTEM COOLING CAPACITIES AND POWER
REQUIREMENTS (HA090/LA090) . . . . . . . . . . . . . . . . 5
HA090 CHARGING CURVE . . . . . . . . . . . . . . . . . . . . 6
CLEARANCES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
UNIT DIMENSIONS & CLEARANCES HA090 . . . . . . 9

Unitary Products Group

Page 4

http://www.rezine.net
036-21338-001-C-0703

TABLE 1: ARI RATINGS*


CONDENSING
UNIT MODEL

INDOOR BLOWER UNIT


MODEL

SYSTEM
MBH

SYSTEM EER

CONDENSING UNIT
SOUND
LEVEL(BELS)

HA090

LA090

90

10.7

8.9

*. Certified in accordance with Unitary Large Equipment certification program, which is based on ARI Standard
340/360

TABLE 2: APPLICATION DATA


LIMITATION

MIN.

MAX.

208/230-3-60

187V

252V

460-3-60

432V

504V

575-3-60

540V

630V

45F

125F

Voltage Variation *

Ambient Air on Condenser Coil

*. Rated in accordance with ARI Standard 110, utilization range A.


. Low Ambient accessories are available to permit stable system operation at ambient
temperatures down to 0F.
Note: Refer to Form 035-15407-001 for refrigerant piping limitations

TABLE 3: PHYSICAL DATA


Condenser
Compressor

Rating Cap.
Qty.
(Tons) (Stages)
090
*.
.
.
**.

Fan Motor*

Fan (Propeller)

Model
HA

7-1/2

Dia.
(in.)

Norm
CFM

24

7800

Blades
Qty. RPM
Qty Pitch
(Deg.)
3

26

1110

Unit
Weight
(Lbs.)

Coils

Finned
Rows
Face
HP Rotation
Area Length High
(in.)
3/4

CW

23.8

96

36

Charge,
Lbs,-Oz.
(Refrigerant-22)

Ship. Oper. Holding Oper.**


388

383

1-12

14.95

These PSC motors are directly connected to the condenser fans and have inherent protection, ball bearings and a 48 frame.
These condenser coils have 2 rows of 3/8 OD copper tubes and 16 aluminum fins per inch.
When viewing the shaft end of the motor.
Includes matched indoor blower unit but no piping.

Unitary Products Group

Page 5

http://www.rezine.net
036-21338-001-C-0703

TABLE 4: ELECTRICAL DATA


COMPRESSOR
MODEL
(HA)

090

VOLTAGE
CODE

CONDENSER FAN MOTOR

UNIT
AMPACITY
(AMPS)
FLA

MAX.
FUSE
SIZE*
(AMPS)

MIN.
WIRE
SIZE
(AWG)

POWER
SUPPLY

RLA

LRA

POWER
SUPPLY

HP

QTY

208/230-3-60

25.6

190

208/230-1-60

3/4

3.03

38.1

60

460-3-60

13.5

95

460-1-60

3/4

1.60

20.1

30

10

575-3-60

10.2

75

575-1-60

3/4

1.35

15.5

25

10

*. Dual element.
. Based on three, 60C insulated copper conductors in steel conduit.

TABLE 5: UNIT COOLING CAPACITIES AND POWER REQUIREMENTS


TEMPERATURE OF AIR ON CONDENSER COIL, F

SUCTION PRESS. &


CORRESPONDING
MODEL
TEMP.
@ SATURATION
HA
PSIG

090

65

75

85

MBH KW* MBH KW *

95

105

115

MBH

KW*

MBH

KW*

MBH

KW*

MBH

KW*

61.6

35

94

6.7

90

7.2

85

7.8

80

8.3

75

9.1

70

9.8

68.5

40

104

6.8

99

7.3

94

7.9

89

8.5

84

9.2

78

9.9

76.0

45

114

6.8

109

7.4

103

98

8.6

93

9.3

87

10

84.0

50

124

6.9

119

7.5

113

8.1

108

8.7

102

9.4

96

10.2

*. Includes compressor and condenser fan motor(s).

Unitary Products Group

Page 6

http://www.rezine.net
036-21338-001-C-0703

TABLE 6: SYSTEM COOLING CAPACITIES AND POWER REQUIREMENTS (HA090/LA090)


Temperature of on Air Condenser Coil
95 F

85
Air On Evaporator Coil

CFM
2250

2625

3000

3300

3600

WB(F)

Total
Capacity
(MBh)

Total
Input
(kW)

Sensible Capacity (MBh)


Return Dry Bulb (F)
86

83

80

77

74

71

68

Total
Capacity
(MBh)

Total
Input
(kW)

Sensible Capacity (MBh)


Return Dry Bulb (F)
86

83

80

77

74

71

68

72

99

7.1

58

51

45

38

32

95

7.7

56

49

43

37

30

67

90

6.9

70

63

57

50

44

38

31

87

7.6

68

62

55

49

43

36

30

62

83

6.7

80

74

68

61

55

48

42

80

7.4

78

72

65

59

52

46

40

57

79

6.6

79

79

72

66

59

53

47

76

7.3

76

76

69

63

56

50

44

72

102

7.1

63

55

48

40

32

98

7.8

61

54

46

39

31

67

93

7.0

76

68

60

53

45

38

30

90

7.6

75

67

60

52

44

37

29

62

85

6.8

84

79

72

64

57

49

42

82

7.5

82

78

70

63

55

47

40

57

81

6.7

81

81

77

69

62

54

47

79

7.4

79

79

74

67

59

52

44

72

105

7.2

68

59

51

42

33

101

7.8

67

58

50

41

32

67

96

7.0

82

73

64

55

47

38

29

93

7.6

81

73

64

55

46

38

29

62

88

6.8

88

85

76

68

59

50

41

85

7.5

85

84

75

66

58

49

40

57

84

6.7

84

84

82

73

64

55

47

81

7.4

81

81

80

71

62

53

45

72

106

7.2

72

63

53

43

33

103

7.8

71

62

52

42

32

67

97

7.0

87

77

67

57

48

38

28

95

7.7

86

76

67

57

47

37

28

62

89

6.9

89

88

80

70

60

51

41

87

7.5

87

86

79

69

59

49

40

57

85

6.7

85

85

84

74

65

55

45

83

7.4

83

83

82

72

63

53

43

72

108

7.2

77

66

55

45

34

105

7.9

76

65

54

43

33

67

99

7.0

92

81

70

59

49

38

27

97

7.7

91

80

70

59

48

37

27

62

91

6.9

91

91

84

73

62

51

41

88

7.6

88

88

82

71

61

50

39

57

87

6.7

87

87

87

76

65

54

44

84

7.5

84

84

84

74

63

52

41

Temperature of Air on Condenser Coil


105

Air On Evaporator Coil


Total
Capacity
(MBh)

CFM

WB(F)

2250

72

91

67

2625

3000

3300

3600

Total
Input
(kW)

115 F

Sensible Capacity (MBh)


Return Dry Bulb (F)

Total
Capacity
(MBh)

86

83

80

77

74

71

68

8.5

63

56

50

44

37

88

84

8.4

67

60

54

48

41

35

28

62

77

8.2

70

63

57

50

44

38

57

74

8.1

74

74

68

61

55

49

72

94

8.6

69

61

54

46

38

67

87

8.4

73

65

58

50

62

80

8.3

74

69

61

57

77

8.2

77

76

73

72

98

8.7

75

66

67

90

8.5

79

62

82

8.3

57

79

8.2

72

99

67

Total
Input
(kW)

Sensible Capacity (MBh)


Return Dry Bulb (F)
86

83

80

77

74

71

9.4

70

63

57

50

44

81

9.2

65

59

52

46

40

33

27

31

74

9.0

61

55

48

42

35

29

23

42

72

8.9

72

72

66

60

54

47

41

91

9.4

76

68

61

53

46

43

35

28

84

9.3

71

64

56

48

41

33

26

53

46

38

31

77

9.1

67

59

52

44

36

29

21

65

58

50

42

74

9.0

74

74

71

63

56

48

41

57

48

40

94

9.5

82

73

65

56

47

70

62

53

44

35

27

87

9.3

77

68

60

51

42

33

25

79

74

65

56

48

39

30

80

9.2

72

64

55

46

37

29

20

79

79

78

69

60

51

43

77

9.0

77

77

75

67

58

49

40

8.7

80

70

60

50

41

95

9.5

88

78

69

59

49

92

8.5

85

75

65

55

46

36

26

88

9.4

83

73

63

54

44

34

24

62

84

8.4

82

77

68

59

49

39

29

81

9.2

77

68

58

49

39

29

19

57

81

8.3

81

81

80

70

60

51

41

78

9.1

78

78

77

68

58

48

39

72

101

8.7

85

74

63

53

42

97

9.5

94

83

73

62

51

67

93

8.6

90

79

68

58

47

36

25

89

9.4

89

78

67

56

46

35

24

62

85

8.4

85

80

72

61

50

40

29

82

9.2

82

72

62

51

40

30

19

57

82

8.3

82

82

82

71

60

50

39

80

9.1

80

80

80

69

58

47

37

Unitary Products Group

68

Page 7

http://www.rezine.net
036-21338-001-C-0703

COOLING CAPACITIES AND POWER REQUIREMENTS (HA090/LA090) (CONTINUED)


Temperature of Air on Condenser Coil
125
Air On Evaporator Coil
Total Input
(kW)

84

67
62
57

70

72

87

67

80

62

74

57

72

72

90

67

83

62

77

57

CFM

WB(F)

2250

72

2625

3000

3300

3600

Sensible Capacity (MBh)

Total
Capacity
(MBh)

Return Dry Bulb (F)


86

83

80

77

74

71

68

10.2

77

70

64

57

51

77

10.0

64

57

51

45

38

32

25

72

9.8

53

46

40

33

27

21

14

9.7

70

70

65

59

52

46

39

10.2

83

76

68

60

53

10.1

69

62

54

47

39

32

24

9.9

59

50

42

35

27

20

12

9.8

72

72

69

62

54

46

39

10.3

90

81

72

63

55

10.2

75

66

58

49

40

31

23

10.0

66

54

45

36

27

19

10

75

9.9

75

75

73

65

56

47

38

72

92

10.4

92

87

77

67

58

67

84

10.2

81

71

62

52

42

32

23

62

78

10.0

73

59

48

38

29

19

57

76

9.9

76

76

75

65

56

46

36

72

93

10.4

93

93

82

71

61

67

86

10.2

86

77

66

55

44

34

23

62

79

10.0

79

65

52

41

30

19

57

77

9.9

77

77

77

66

56

45

34

TABLE 7: HA090 CHARGING CURVE


Charging Curve
HA090

330

Discharge Pressure

310

115F Ambient

290
270

105F Ambient

250

95F Ambient
230
210

85F Ambient

190

75F Ambient
170
60

65

70

75

80

85

90

95

100

Suction Pre ssure

Unitary Products Group

Page 8

http://www.rezine.net
036-21338-001-C-0703

SEQUENCE OF OPERATION
UNIT OPERATION - 7-1/2

SC provides a 90 second bypass of the low pressure switch


LP to prevent nuisance lockouts during unit start-up.

When the external control calls for cooling at terminal Y1:


The system controller (SC) is energized. The system controller starts the tandem compressors and enables the condenser fans by energizing contactor 1M (2M on the 208/230
volt models).
Condenser fan motor #1 is energized with the compressor.
Fan motor #2 operation is controlled through the Pressure
Switch (PS) which will de-energize the motor when the discharge pressure falls below 180 psi.
Safety Lockout: The system controller (SC) has a lockout circuit to prevent compressor short-cycling on a safety control
with automatic reset. If the high or low refrigerant pressure
switches (HP or LP) open, the SC will enter lockout mode.

Unitary Products Group

A malfunction light (24V, 2 A max. resistive load) can be energized through SC, by connecting the light between terminals
X and B on TB1.
NOTE: To reset the unit after a lockout:
a.

Turn the system switch on the thermostat to the OFF


position and back to theCOOL position.
OR

b.

Increase the set point of the room thermostat above the


temperature in the conditioned space and return it to its
original setting. If the unit continues to be shut down by
one of its safety controls, a service man should be called
to determine the cause of the problem. Repeated resetting of the lockout circuit may damage the unit.

Page 9

http://www.rezine.net
036-21338-001-C-0703

NOTE: USE COPPER CONDUCTORS ONLY


SIZE POWER WIRING
DICONNECT SWITCH, AND
FUSING PER ELECTRICAL
DATA TABLE

NOTE: Use thermostat 2ET0770010124


if the blower unit is equipped
with a 2-stage electric
heat accessory.
Use thermostat 2TH07701024
if the blower unit is equipped
with a hot water coil, a steam coil
or a 1-stage electric heat
accessory.
The field wiring connected to these
dummy terminals on TB1 can be
routed directly from the condensing
unit to the thermostat if desired.

FACTORY - MOUNTED
PIGTAILS ON TERMINAL
COMPRESSOR
CONTACTOR 1M

Y1

TERMINALS ON BLOCK
TB1 OF BLOWER UNIT

24 VOLT

53

60 66

WIRE IN ACCORDANCE WITH ALL LOCAL


AND NATIONAL ELECTRICAL CODES

FIGURE 1 - TYPICAL FIELD WIRING WITH AIR HANDLER

B
A
C

HA 090
D

UNIT
090

Total
505

A
110

4-POINT LOAD (lbs)


B
C
151
141

D
103

FIGURE 2 - POINT LOADS

Unitary Products Group

Page 10

http://www.rezine.net
036-21338-001-C-0703

TERMINAL STRIP
ON FURNACE
P-USB30N19031

TERMINAL STRIP
TB1 ON
HA090

R
Y1
B

THERMOSTAT*
TERMINALS

COIL

24-VOLT
ISOLATION RELAY
(FIELD SUPPLIED)

*24-volt thermostat

FIELD-INSTALLED ACCESSORIES - 0 FLOW AMBIENT KITS - An auto-transformer and temperature


control maintain stable system operation by reducing the speed of the condenser fan motor.

FIGURE 3 - TYPICAL FIELD WIRING WITH 7-1/2 TON FURNACE


TABLE 8: UNIT DIMENSIONS & CLEARANCES HA090

TABLE 9: CLEARANCES
Overhead (Top)*

120

Front (Piping and Access Panels)

30

Left Side

24

Right Side

24

Rear

24

Bottom

*. Units must be installed outdoors. Overhanging


structures or shrubs should not obstruct condenser air discharge.
. Adequate snow clearance must be provided if
winter operation.

Unitary Products Group

Page 11

http://www.rezine.net
036-21338-001-C-0703

DIM (In.)
UNIT
7-1/2 ) *
+ ,
Ton. 70-1/8 32 29-5/8 16-1/12
All dimensions are in inches. They are subject to
change without notice. Certified dimensions will
be provided upon request.
FIGURE 4 - CENTER OF GRAVITY

FIGURE 5 - HA090 DIMENSIONS

10

Unitary Products Group

Page 12

http://www.rezine.net
036-21338-001-C-0703

GUIDE SPECIFICATIONS
Furnish and install YORK Sunline air-cooled condensing
units or equivalent, suitable for ground or roof mounting.
Units shall have capacities and efficiencies as outlined in the
schedules shown on the plans and shall be installed in accordance with all applicable national and local codes.

the 3 phase power supply, thus minimizing phase imbalance on multiple unit installations.
c.

Fan motors shall be totally enclosed with permanently


lubricated ball-bearings for longer wear during start and
stop cycles.

I. GENERAL

d.

Fan motors shall have inherent overload protection.

a.

Units shall be manufactured in a facility registered under


the ISO 9002 manufacturing quality standard.

e.

b.

Units shall be UL and CSA approved.

Coil shall be constructed of rifled copper tubing mechanically expanded and bonded to louvered aluminum fins.
Coil shall include an integral subcooler.

c.

Unit shall be packaged to allow outdoor storage.

d.

Hermetic compressors shall be covered by a five year


limited warranty.

a.

Refrigeration system contains both high and low pressure cut-outs.

e.

All other unit parts shall be covered by a full year limited


warranty.

b.

Service valves to ease installation and recovery of refrigerant.

c.

External ports to accommodate gauge lines, allowing for


easy servicing of the unit.

d.

Each unit ships with a filter drier for field installation.

e.

Holding charge of R-22.

V. REFRIGERATION COMPONENTS

II. UNIT CABINET


a.

Cabinet shall be constructed of 18 gauge, zinc-coated


steel, finished with a powder paint process capable of
withstanding a minimum of 750 salt spray hours according to ASTM B117.

VI. CONTROLS

b.

Cabinet screws shall comply with the ASTM B117 salt


spray test for a minimum of 750 hours.

a.

Each unit is equipped with 24 volt control circuit with terminal blocks.

c.

Panels shall be removable for easy access to all internal


components during maintenance and service.

b.

Color-coded wiring for easy service and trouble shooting.

d.

Cabinet shall feature a separate access panel for the


controls so that unit airflow need not be disturbed during
servicing.

c.

Independent line break thermal protection for the condenser fans.

e.

Permanently attached base rails shall have 3-way fork lift


access and lifting holes for ease of installation.

d.

5 minute anti-short cycle timer to protect the compressor


from frequent cycling.

e.

Unit safety lockouts which automatically reset from the


thermostat once the anti-short cycle timer is satisfied.
Safety lockouts will also generate a 24 volt signal to the
"X" terminal, allowing notification to the user via the thermostat fault light (if present). These safety lockouts shall
include:

High refrigerant pressure.

Low refrigerant pressure (low refrigerant pressure shall


be bypassed for the first 90 seconds of operation to eliminate nuisance trips).

Compressor motor protection to automatically shutdown


the unit in the event of motor overcurrent or excessive
temperature conditions. Unit shall automatically restart
after the line break protector cools.

Low ambient operation down to 45F (7C) without a low


ambient kit. (Operation down to 0F with the optional low
ambient kit.)

III. COMPRESSOR
a.

Compressor shall be a scroll compressor with integral


motor overload protection.

b.

Compressors shall have an integral crankcase heater to


keep refrigerant from diluting the compressor oil in the
sump. Crankcase heater shall be field replaceable without removal of the charge.

c.

Compressor shall be mounted on isolators to limit the


transmission of sound and vibration.

IV. CONDENSER AND FANS


a.

b.

Fan motors shall be single phase, direct-drive with propeller-type condenser fans which discharge air vertically
upward.
Units with more than one condenser fan motor shall be
wired to distribute the single phase motor loads across

Unitary Products Group

11

Page 13

http://www.rezine.net

b.

VII. ELECTRICAL
a.

Units shall be ______ volts, 3 phase, with a single power


point connection.

b.

Unit control circuit shall have a 24 volt transformer, sized


sufficiently to operate the indoor fan.

c.

All condenser fan motors and the secondary of each


transformer shall be grounded.

IX. COIL GUARD

VIII. ACCESSORIES AND OPTIONS


a.

Shall include a condenser fan motor and an auto transformer to slow the speed of the condenser fan at low
ambient temperatures, allowing operation of the condensing unit down to 0F.

a.

Field installed decorative grille shall be placed on the


units to provide further coil protection.

b.

Phenolic Coating on Condenser Coil.

c.

Condenser coils shall be dipped in a four-coat phenolic


coating process to provide longer life in corrosive conditions.

Head Pressure Control

Subject to change without notice. Printed in U.S.A.


Copyright by Unitary Products Group 2003. All rights reserved.
Unitary
Products
Group

5005
York
Drive

Page 14

036-21338-001-C-0703
Supersedes: 036-21338-001-B-0402
Norman
OK
73069

http://www.rezine.net

036-21365-003-D-1105

DESCRIPTION

These outdoor condensing units are completely assembled, piped and


wired at the factory to provide one-piece shipment and rigging. Each
unit is pressurized with a holding charge of refrigerant-22 for storage
and/or shipping.
The compact design, clean styling, and quiet operation make these
condensing units suitable for almost any outdoor location. On rooftops
. . . because they weigh much less than a single package unit of similar capacity and are much easier to rig and support. At ground level. . .
because their ample sub-cooling capacity allows them to be located 18
meters (60 feet) below the evaporator coil.

TECHNICAL GUIDE
SPLIT-SYSTEM
AIR COOLED
CONDENSING UNITS

All sheet metal parts are constructed of commercial grade (G90) galvanized steel. Before painting, each part is thoroughly cleaned to
remove any grease or dirt from its surfaces. The external parts are
then coated with a powder paint to assure a quality finish for many
years. This coating system has passed the 100 hour, salt spray test
per ASTM Standard B117.

MODELS: HA120
10 NOMINAL TONS

All models include a 1-year limited warranty on the complete unit. The
compressor carries an additional 4-year warranty.
A matching line of Evaporator Blower units is also offered to meet your
precise capacity and air handling requirements.

FEATURES
O

Condenser coil constructed of rifled copper tubes and louvered


aluminum fins for durability and long lasting efficient operation.

Permanently attached base rails with fork lift slots and lifting
holes. This design allows for 3-way fork lift access and overhead
rigging.

Both high and low pressure controls.

Solid state motor protection to prevent the compressor from operating at an unsafe condition.

Ball bearing condenser fan motors with 1/2 inch shafts.

Color-coded power and control wiring for easier service and troubleshooting.

Anti-short cycle timer to protect the compressor.

A lockout circuit to prevent the unit from cycling on safety control.

A 24-volt temperature control circuit.

Standard unit low ambient operation to (35F).

A filter-drier (shipped in the unit's compressor compartment for


field installation near the evaporator coil).

Service valves with a back-seating access port for pressure testing the system. Copper stub-outs are factory mounted on the suction and liquid service valves to simplify the field piping
connections.

Exterior access to service pressure port connections.

Packaging suitable for outdoor storage.

An optional Phenolic coating is available where the condenser


coils are fully dipped in a phenolic coating process to provide
longer life in corrosive conditions.

FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE

Page 15

http://www.rezine.net
036-21365-003-D-1105

TABLE OF CONTENTS
DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
FIELD-INSTALLED ACCESSORIES. . . . . . . . . . . . . 4
OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

LIST OF FIGURES
Fig. #
1

UNIT DIMENSIONS & CLEARANCES AND


CENTER OF GRAVITY. . . . . . . . . . . . . . . . . . . . . . . . . 4

FIELD WIRING - HA120/LA120 . . . . . . . . . . . . . . . . . . 7

UNIT OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

GUIDE SPECIFICATION - HA120 . . . . . . . . . . . . . . . 9


GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
UNIT CABINET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
COMPRESSOR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
CONDENSER AND FANS . . . . . . . . . . . . . . . . . . . . . . 9

LIST OF TABLES
Tbl. #
1
2
3
4
5

REFRIGERATION COMPONENTS . . . . . . . . . . . . . . . 9
CONTROLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
ELECTRICAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
ACCESSORIES AND OPTIONS . . . . . . . . . . . . . . . . 10

Pg. #

6
7
8
9

Pg. #

ARI RATINGS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
UNIT APPLICATION DATA. . . . . . . . . . . . . . . . . . . . . . 3
PHYSICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
ELECTRICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
SYSTEM GROSS COOLING CAPACITIES AND
POWER REQUIREMENTS, HA120 WITH LA120 . . . . 5
CONDENSING UNIT ONLY COOLING CAPACITIES
AND POWER REQUIREMENTS . . . . . . . . . . . . . . . . . 7
SUCTION LINE DATA. . . . . . . . . . . . . . . . . . . . . . . . . . 8
LIQUID LINE DATA. . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
REFRIGERANT-22 LINE CHARGE . . . . . . . . . . . . . . . 8

Unitary Products Group

Page 16

http://www.rezine.net
036-21365-003-D-1105

TABLE 1: ARI RATINGS1


CONDENSING
UNIT MODEL

INDOOR BLOWER UNIT


MODEL

SYSTEM
MBH

SYSTEM EER

CONDENSING UNIT
SOUND
LEVEL2(DB)

HA120

LA120

1263

10.53

88.0

Certified in accordance with Unitary Large Equipment certification program, which is based on ARI Standard 340/
360.

Rated in accordance with ARI Standard 270.

Deduct 1.0 MBH for units operating at 208 volts.

TABLE 2: UNIT APPLICATION DATA


208/230-3-60
460-3-60
575-3-60
Ambient Air on Condenser Coil
Min. / Max.
Ambient Air on Condenser Coil
Min. / Max. with Head Pressure Control
Voltage Variation1
Min. / Max.

187 / 252
432 / 504
540 / 630
35 F2 / 125 F
0 - 125 F

Utilization range A in accordance with ARI Standard


110.

The minimum allowed ambient temperature for


mechanical cooling without the head pressure control
accessory installed must be raised if the indoor air flow
is less than the minimum value given in the capacity
tables.

TABLE 3: PHYSICAL DATA


Condenser
Compressor1

Model
Size
(Mbh)

HA120

Fan Motor2

24 Fan (Propeller)

Rating
(Tons)

Cap.
(Stgs)

Qty.

Blades/
Pitch
(Deg.)

Nom
CFM

10

3/26

8100

Pitch
(Deg.) Qty. HP
26

3/4

Unit
Weight
(Lbs.)

Coil

RPM

Rotation**

Fins
per
inch

Rows
Deep

1110

CW

20

Charge,
(Refrigerant-22)
Lbs,-Oz.

Ship. Oper. Holding3 Oper.4


731

741

2-0

27.85

Consists of one scroll compressor.

The ball bearing, 48 frame, single phase condenser fan motor have internal protection are directly connected to the condenser fans.

Holding charge is the amount in the unit as shipped from the factory.

Operating refrigerant charge is for the condensing unit and the matching York air handler, but does not include the charge in the
interconnecting piping.
See the Refrigerant Line Charge Table to determine the additional refrigerant charge required for interconnecting piping.
** When viewing the shaft end of the motor.

Unitary Products Group

Page 17

http://www.rezine.net
036-21365-003-D-1105

TABLE 4: ELECTRICAL DATA


Compressor
Model

Unit Power
Supply

Qty

RLA

Condenser Fan Motor

LRA

Qty

HP

FLA

Minimum
Circuit
Ampacity
(Amps)

Maximum
Fuse
Size1
(Amps)

Minimum
Disconnect
Size2
(Amps)

208/230/3/60

42

239.0

3/4

3.0

58.8

100

100

460/3/60

19.2

125.0

3/4

1.6

27.2

45

45

575/3/60

13.8

80.0

3/4

1.4

20.1

30

30

HA120

Dual element, time delay type.

Refer to NEC/NFPA No. 70, Articles 440-11, 12 for information on minimum disconnect sizing.

FIELD-INSTALLED ACCESSORIES

Unit

maintain stable system operation at ambient temperatures down to 0 F.

0 F LOW AMBIENT - A single phase condenser fan


motor and head pressure control to reduce its speed

Coil Guard - A decorative coil guard provides an additional level of protection for the condenser coils.

COMPRESSOR
FAN MOTOR ACCESS AND
CONTROL BOX ACCESS
EXTERNAL PRESSURE
GAUGE FITTINGS

AIR
OUT

AIR
OUT

All dimensions are in inches. They are subject to change without notice. Certified
dimensions will be provided upon request.

FAN MOTOR
ACCESS

Connection Size

Connection
Entry

10 Ton

Suction Line
O

F
AIR
IN

44-9/32

24-1/2

5-3/4

1-3/8 OD

Liquid Line

5/8 ID

Control Wiring

7/8 KO

Power Wiring

1-3/4 KO

Accessory Wiring

7/8 KO

Accessory Wiring

1-3/8 KO

CLEARANCES

Overhead (Top)1

120

Front
(Piping and Access Panels)

30

12-1/8
39 - 7/8

33-3/4
7-1/32
9-1/32

76-7/8

Left Side

24

Right Side

24

Rear

24

Bottom2

Units must be installed outdoors. Overhanging structures or shrubs should not obstruct condenser air discharge.
2 Adequate snow clearance must be provided if winter
operation is expected

FIGURE 1 - UNIT DIMENSIONS & CLEARANCES AND CENTER OF GRAVITY

Unitary Products Group

Page 18

http://www.rezine.net
036-21365-003-D-1105

TABLE 5: SYSTEM GROSS COOLING CAPACITIES AND POWER REQUIREMENTS, HA120 WITH LA120
TEMPERATURE OF AIR ON CONDENSER COIL
AIR ON
EVAPORATOR
COIL
CFM

3200

3600

4000

4400

4800

TOTAL
CAP.1
(MBH)

TOTAL
INPUT2
(kW)

72

140

67

129

62
57

WB
(F)

85F

95F

SENSIBLE CAPACITY (MBH)

SENSIBLE CAPACITY (MBH)

68

TOTAL
CAP.1
(MBH)

TOTAL
INPUT2
(kW)

RETURN DRY BULB (F)


86

83

80

77

74

71

9.0

83

74

65

56

47

141

8.8

102

93

84

75

66

57

48

124

118

8.6

118

109

100

91

82

73

63

117

8.6

117

117

107

98

89

80

71

72

143

9.4

90

79

69

59

48

67

132

9.2

110

100

89

79

68

58

62

120

9.1

120

116

106

96

85

75

64

57

119

9.1

119

119

114

104

93

83

72

RETURN DRY BULB (F)


86

83

80

77

74

71

68

10.8

90

80

71

62

53

10.6

100

91

82

73

64

55

46

117

10.5

117

117

110

101

92

83

74

118

10.5

118

118

116

107

98

89

80

141

10.8

92

82

71

61

50

48

124

10.6

103

92

82

72

61

51

40

117

10.5

117

117

110

100

89

79

69

118

10.5

118

118

116

106

96

85

75

72

146

9.9

96

85

73

61

50

141

10.8

95

83

71

60

48

67

135

9.7

118

106

94

83

71

59

48

128

10.7

114

102

91

79

67

56

44

62

123

9.5

123

123

112

101

89

77

66

117

10.5

117

117

110

98

87

75

63

57

122

9.5

122

122

121

109

97

86

74

118

10.5

118

118

116

105

93

81

70

72

149

10.0

102

89

76

63

50

147

10.9

105

92

79

66

53

67

137

9.7

125

112

99

86

73

60

47

129

10.7

117

104

91

78

65

52

39

62

126

9.6

126

126

117

104

91

78

65

122

10.5

122

122

119

106

93

80

67

57

124

9.6

124

124

124

111

98

85

72

123

10.6

123

123

122

109

96

83

70

72

152

10.0

108

94

80

65

51

153

11.0

116

102

87

73

59

67

140

9.8

132

117

103

89

74

60

46

134

10.7

129

115

101

86

72

58

43

62

128

9.6

128

128

122

108

94

79

65

127

10.6

127

127

127

113

99

84

70

57

127

9.6

127

127

127

113

98

84

70

128

10.7

128

128

128

114

100

85

71

TEMPERATURE OF AIR ON CONDENSER COIL


AIR ON
EVAPORATOR
COIL
CFM

3200

3600

4000

4400

4800

WB
(F)

105F

115F

SENSIBLE CAPACITY (MBH)


TOTAL
CAP.1
(MBH)

TOTAL
INPUT2
(kW)

SENSIBLE CAPACITY (MBH)

68

TOTAL
CAP.1
(MBH)

TOTAL
INPUT2
(kW)

86

83

80

77

74

RETURN DRY BULB (F)


86

83

80

77

74

71

RETURN DRY BULB (F)


71

68

72

133

11.9

84

75

66

57

47

125

13.0

78

69

60

51

42

67

119

11.7

98

89

80

71

62

53

43

115

12.8

96

87

78

69

60

51

41

62

111

11.5

111

110

102

93

84

75

66

105

12.5

105

103

94

85

76

67

57

57

113

11.6

113

112

106

97

88

79

70

107

12.6

107

105

96

87

78

69

60

72

134

11.9

88

78

67

57

47

127

13.0

84

74

64

53

43

67

120

11.7

103

93

82

72

62

51

41

116

12.8

103

93

83

72

62

51

41

62

112

11.5

112

111

105

94

84

74

63

106

12.5

106

105

100

89

79

68

58

57

113

11.6

113

113

109

99

88

78

68

108

12.6

108

108

102

92

81

71

60

72

135

12.0

93

81

69

58

46

129

13.1

91

79

67

56

44

67

121

11.7

108

96

85

73

61

50

38

118

12.8

111

99

87

76

64

52

41

62

113

11.5

113

113

108

96

84

73

61

108

12.6

108

108

105

94

82

70

59

57

114

11.6

114

114

112

100

89

77

65

110

12.7

110

110

108

96

84

73

61

72

139

12.0

101

88

75

62

49

131

13.1

97

84

71

58

41

67

125

11.8

117

104

91

78

65

53

40

120

12.9

117

105

92

79

66

53

40

62

116

11.6

116

116

114

101

88

75

62

110

12.6

110

110

109

96

83

70

57

57

118

11.7

118

118

117

104

91

78

65

112

12.7

112

112

111

98

85

72

59

72

143

12.1

109

95

81

66

52

134

13.2

103

88

74

60

45

67

129

11.8

126

113

98

84

70

55

41

123

12.9

123

110

96

82

67

53

39

62

120

11.6

120

120

120

105

91

77

62

112

12.7

112

112

112

98

83

69

55

57

121

11.7

121

121

121

107

93

78

64

114

12.7

114

114

114

100

86

71

57

Unitary Products Group

Page 19

http://www.rezine.net
036-21365-003-D-1105

TABLE 5: SYSTEM GROSS COOLING CAPACITIES AND POWER REQUIREMENTS, HF-10 WITH LF-10
(CONT.)
TEMPERATURE OF AIR ON CONDENSER COIL
AIR ON
EVAPORATOR
COIL
CFM

3200

3600

4000

4400

4800

125F
SENSIBLE CAPACITY (MBH)

Nominal Rating

TOTAL
CAP.1
(MBH)

TOTAL
INPUT2
(kW)

86

83

80

77

74

71

72

118

14.1

73

64

54

45

36

67

110

13.8

94

85

76

67

58

48

39

62

99

13.5

99

96

86

77

68

58

49

57

101

13.6

101

99

86

77

68

59

49

72

120

14.2

81

70

60

49

39

67

113

13.9

104

93

83

72

62

52

41

62

101

13.6

101

99

94

84

73

63

53

57

103

13.7

103

102

95

84

74

64

53

72

123

14.2

89

77

65

54

42

67

115

14.0

113

102

90

78

67

55

43

62

103

13.6

103

103

103

91

79

68

56

57

106

13.7

106

106

103

92

80

68

57

72

124

14.3

92

79

66

53

40

67

116

14.0

116

105

92

79

66

53

40

62

104

13.7

104

104

104

91

78

65

52

57

106

13.7

106

106

105

92

79

66

53

72

125

14.3

96

81

67

53

39

67

117

14.0

117

108

94

79

65

51

36

62

105

13.7

105

105

105

90

76

62

47

57

107

13.8

107

107

107

93

79

64

50

WB
(F)

RETURN DRY BULB (F)


68

- These capacities are gross ratings. For net


capacity, deduct air blower motor, MBh =
3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air
blower motor.

- These ratings include the condenser fan


motors (total 1 kW) and the compressor
motors but not the supply air blower motor.

Unitary Products Group

Page 20

http://www.rezine.net
036-21365-003-D-1105

TABLE 6: CONDENSING UNIT ONLY COOLING CAPACITIES AND POWER REQUIREMENTS


Suction Press &
Saturation
Temp
PSIG
F
61.6
35
68.5
40
76
45
84
50

Model

HA120

GROUND
LUG

Temperature of Air on Condenser Coil, F


65
MBH
128
139
151
163

75
KW
7.9
8
8.3
8.5

3-PHASE
LINE VOLTAGE
POWER SUPPLY

TB2
R B Y1

MBH
122
133
144
156

85
KW
8.5
8.7
8.9
9.1

MBH
116
127
138
149

SIZEPOWERWIRING,
DISCONNECTSWITCH, AND
FUSINGPERELECTIRICAL
DATATABLE

95
KW
9.2
9.4
9.6
9.9

MBH
110
120
131
142

105
KW
10
10.3
10.5
10.7

MBH
104
114
124
134

KW
11.1
11.3
11.4
11.7

115
MBH
97
107
117
127

KW
12.2
12.3
12.5
12.7

NOTE: USE COPPER


CONDUCTORS ONLY

FACTORY MOUNTED
PIGTAILS ON
TERMINALS OF
COMPRESSOR
CONTACTOR 1M
TERMINALS ON
BLOCK TB1 OF
BLOWER UNIT

24
VOLT

R B Y O W X 53 G 60 66

R Y G
THERMOSTAT

WIRE IN ACCORDANCE WITH


ALL LOCAL AND NATIONAL
ELECTRICAL CODES

The field wiring connected to these


dummy terminals on TB2 can be
routed directly from the condensing
unit to the thermostat if desired.

NOTE: SEE PN# 036-13335-002


FOR APPLICABLE THERMOSTATS.

FIGURE 2 - FIELD WIRING - HA120/LA120

OPERATION
Condenser fan motor #1 is energized with the compressor. Fan motor #2 operation is controlled through the
Pressure Switch (PS) which will de-energize the motor
when the discharge pressure falls below 180 PSI.

UNIT OPERATION
When the external control calls for cooling at terminal:
1.

The system controller (SC) is energized. The system


controller starts the compressor and enables the condenser fans by energizing contactor 1M (and 2M on the
208/230 volt models).

Unitary Products Group

2.

Safety Lockout: The system controller (SC) has a lockout


circuit to prevent compressor short-cycling on a safety
control with automatic reset. If the high or low refrigerant
pressure switches (HP or LP) open, the SC will enter
lockout mode.

Page 21

http://www.rezine.net
036-21365-003-D-1105

SC provides a 90 second bypass of the low pressure


switch LP to prevent nuisance lockouts during unit startup.

A.

Turn the system switch on the thermostat to the


OFF position and back to the COOL position.

OR
A malfunction light (24V, 2 A max. resistive load) can be
energized through SC, by connecting the light between
terminals X and B on TB1. Terminal X will energize when
SC locks out.
3.

Unit is equipped with an anti-short cycle timer to prevent


two successive compressor starts within 5 minutes. If the
compressor fails to start with a call for cooling and SC is
not locked out, wait at least 6 minutes for the anti-cycle
timer to reset.

B.

Increase the set point of the room thermostat above


the temperature in the conditioned space and return
it to its original setting.

If the unit continues to be shut down by one of its safety controls, service should be called to determine the cause of the
problem. Repeatedly resetting the lockout circuit may damage the unit.

NOTE: To reset the unit after a lockout:

TABLE 7: SUCTION LINE DATA1,2

1
2
3
4
5

Model
Designation

Nominal Capacity
(Tons)

HA120

10

Refrigerant

Type L
Copper tubing
(Inches O.D.)

Refrigerant Gas
Velocity
(FT./Min.)

Loss4,5
(PSI/100 Ft.)

30

1-3/8

2280

2.8

All horizontal suction lines should be pitched at least 1 inch every 20 feet in the direction of the refrigerant flow to aid the return of oil to the compressor.
Every vertical suction riser greater than 25 feet in height should have a P trap at the bottom to facilitate the return of oil to the compressor. Use short
radius fittings for these traps.
Based on Refrigerant-22 at the nominal capacity of the condensing unit, a suction temperature of 40 F and a liquid temperature of 105 F.
Although suction lines should be sized for a friction loss equivalent to a 2 F change in saturation temperature (or approximately 3 psi), sizing the
lines for the proper return of oil is more important.
These friction losses do not include any allowances for valves or fittings.

TABLE 8: LIQUID LINE DATA


Model

HA120
1

2
3

Friction

Flow Rate3
(Lbs./Min.)

TABLE 9: REFRIGERANT-22 LINE CHARGE1

Pressure Drop2
Nominal Refrigerant
Type L
Capacity Flow Rate1 Copper Tubing
Vertical Rise
Friction3
Tons
(Lbs/Min.) (Inches O.D.) (PSI/100 Ft.)
(PSI/Ft.)
10

30

5/8

5.8

0.5

Based on Refrigerant-22 at the nominal capacity of the condensing unit, a liquid temperature of 105 F and a suction temperature of 40 F.
These friction losses do not include any allowances for a
strainer, filter-drier, solenoid valve, isolation valve or fittings.
The total pressure drop of the liquid line for both friction and vertical rise must not exceed 40 PSI. if the pressure drop exceeds
40 PSI, the liquid refrigerant could flash before it reaches the
expansion valve. This flashing will not only cause erratic valve
operation and poor system performance, but could also damage the expansion valve.

Liquid Line2
Inches, O.D.

5/8

0.113 lb./ft.

Suction Line2
Inches, O.D.

1-3/8

0.013 lb./ft.

NOTE: Add the operating charge of the condensing unit, the evaporator coil
and the refrigerant lines to determine the total refrigerant charge of the
system.
1
2

Charges are based on 40 F suction temperature and a 105 F


liquid temperature.
Type L copper tubing.

Unitary Products Group

Page 22

http://www.rezine.net
036-21365-003-D-1105

GUIDE SPECIFICATION - HA120


GENERAL

C.

Coil shall be constructed of rifled copper tubing


mechanically expanded and bonded to louvered aluminum fins. Coil shall include an integral subcooler.

A.

Units shall be manufactured in a facility registered


under the ISO 9002 manufacturing quality standard.

B.

Units shall be UL listed to US and Canadian safety


standards.

High and low pressure cut-outs

C.

Unit shall be packaged to allow outdoor storage.

D.

Warranty shall be a full year limited parts warranty


on the complete unit with an additional 4-year warranty on the compressor.

Suction and liquid line service valves to ease installation


and recovery of refrigerant

External ports to accommodate gauge lines, allowing for


easy servicing

Unit shall be rated in accordance with ARI 360.

Filter drier shipped in unit for field installation

Holding charge of R-22

E.

Unit Cabinet
A.

B.
C.

Cabinet shall be constructed of 18 gauge, zinccoated steel, finished with a powder paint process
capable of withstanding a minimum of 750 salt spray
hours according to ASTM B117.
Cabinet screws shall comply with the ASTM B117
salt spray test for a minimum of 750 hours.
Panels shall be removable for easy access to all
internal components during maintenance and service.

D.

Cabinet shall feature a separate access panel for


the controls so that unit airflow need not be disturbed during servicing.

E.

Permanently attached base rails shall have 3-way


fork lift access and lifting holes for ease of installation.

Refrigeration Components - Refrigeration system shall


contain the following:

Controls - Unit controls shall include:


A.

24 volt control circuit with terminal blocks.

B.

Color-coded wiring for easy service and troubleshooting.

C.

Independent line break thermal protection for the


condenser fans.

D.

5 minute anti-short cycle timer to protect the compressor from frequent cycling.

E.

Unit safety lockouts which automatically reset from


the thermostat once the anti-short cycle timer is satisfied. Safety lockouts will also generate a 24 volt
signal to the X terminal, allowing notification to the
user via the thermostat fault light (if present). These
safety lockouts shall include:

Compressor
A.

Compressor shall be hermetic scroll.

B.

Compressor shall feature motor overload protection.

C.

A crankcase heater shall keep refrigerant from diluting the compressor oil in the sump. Crankcase
heater shall be field replaceable without removal of
the charge.

D.

Neoprene isolators shall be used to minimize the


transmission of sound and vibration.

Condenser and Fans

1.

High refrigerant pressure

2.

Low refrigerant pressure. Low refrigerant pressure shall be bypassed for the first 120 seconds
(approximate) of operation to eliminate nuisance trips.

F.

Compressor motor protection to automatically shutdown the unit in the event of motor overcurrent or
low control voltage conditions. Unit shall automatically restart after satisfying the anti-short cycle timer.

G.

Low ambient operation down to 35 F without a low


ambient kit. (Operation down to 0 F with the
optional low ambient kit.)

Electrical

A.

Fan motors shall be direct-drive with propeller-type


condenser fans which discharge air vertically
upward.

B.

Fan motors shall have permanently lubricated ballbearings for longer wear during start and stop cycles
and shall have inherent overload protection.

Unitary Products Group

A.

Units shall be ______ volts, 3 phase, with a single


power point connection.

B.

Unit control circuit shall have a 24 volt transformer,


sized sufficiently to operate the indoor fan.

C.

All condenser fan motors and the secondary of each


transformer shall be grounded.

Page 23

http://www.rezine.net
036-21365-003-D-1105

Accessories and Options


A.

B.

Head Pressure Control


Shall include a condenser fan motor and a pressure
controller, allowing operation of the condensing unit
down to 0F.

Coil Guard
Field installed decorative grille shall be placed on
the units to provide further coil protection.

C.

Phenolic Coating on Condenser Coil

Condenser coils shall be dipped in a four-coat phenolic coating process to provide longer life in corrosive conditions.

10

Unitary Products Group

Page 24

http://www.rezine.net

036-21371-001-B-0203

DESCRIPTION
YORK has combined the latest concepts in modern technology with
time-proven quality standards to design a split-system heat pump to
meet the demands of the energy-and quality-conscious commercial
market.

TECHNICAL GUIDE
SPLIT-SYSTEM
HEAT PUMPS

EA090/FA090

Both the outdoor and indoor units are completely piped and wired at
the factory. Only the interconnecting liquid and vapor lines are required
to complete the refrigerant circuit. Every unit is dehydrated, evacuated,
leak tested and pressure tested before being pressurized with a holding charge of refrigerant-22 for shipment and/or storage. The compressor, the fan motors and the controls are functionally tested after the
units are fabricated to assure a reliable start-up and years of dependable operation.
These units have been tested by Underwriters' Laboratories and will
be shipped with UL and CUL labels.

OUTDOOR UNIT
Every outdoor unit includes a heavy-duty compressor with a crankcase
heater, line break overload protection, a suction line accumulator with
a fusible plug, a 4-way reversing valve with a 24-volt solenoid, outdoor
fan motor(s) with inherent protection, and a copper tube/aluminum fin
coil that is positioned vertically for better drainage of the water that will
condense on it during the heating cycle.
They also include a filter-drier, an expansion valve and a distributor
that are only used during the heating cycle plus a check valve to provide the proper flow of refrigerant through the unit during both the cooling and heating cycles.
To eliminate the costly cabinet deterioration problems usually associated with outdoor equipment, all sheet metal parts are constructed of
commercial grade (G90) galvanized steel. After fabrication, each part
is thoroughly cleaned to remove any grease or dirt from its surfaces.
The parts that will be exposed to the weather are then coated with a
desert sand powder paint to assure a quality finish for many years.
This coating system has passed the 750 hour, salt spray test per
ASTM Standard B117. To assist in servicing, the high and low pressure
service connections are exterior to the cabinet, allowing simple
access.
The fan guards are vinyl-coated to provide additional rust protection.
An optional decorative coil guard is available to protect the coil on the
outdoor unit.

INDOOR UNIT

208/230/460
VOLT ONLY

Every indoor unit includes a well-insulated cabinet, a copper tube/aluminum fin coil, 1" throwaway filters, a centrifugal blower, a blower
motor, adjustable drive components, a blower motor contactor and a
small holding charge of refrigerant-22.
They also include a filter-drier, an expansion valve and a distributor
that are only used during the cooling cycle plus a check valve to provide the proper flow of refrigerant through the coil during both the cooling and heating cycles.
The units are shipped in the vertical position ready for field installation.
For horizontal installation, interchange the solid bottom panel and the
return air duct flange on the front of the unit.

FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE

Page 25

http://www.rezine.net
036-21371-001-B-0203

TABLE OF CONTENTS
LIST OF TABLES

DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
OUTDOOR UNIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
INDOOR UNIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
APPLICATION FLEXIBILITY . . . . . . . . . . . . . . . . . . . 3
Outdoor Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Indoor Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

SYSTEM FLEXIBILITY. . . . . . . . . . . . . . . . . . . . . . . . 5
ACCESSORIES (FIELD-INSTALLED) . . . . . . . . . . . 11

LIST OF FIGURES
Figure
No.
1
2
3
4
5
6
7

Description

Page
No.

EA090 Outdoor Units. . . . . . . . . . . . . . . . . . . . . . 3


FA090 Indoor Units . . . . . . . . . . . . . . . . . . . . . . . 3
FA090 Airflow Chart. . . . . . . . . . . . . . . . . . . . . . 10
Unit Dimensions & Clearances - Outdoor
Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Unit Dimensions & Clearances - Indoor
Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Field Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Accessory Dimensions . . . . . . . . . . . . . . . . . . . 15

Table
No.

Description

Page
No.

ARI Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

System Application Data . . . . . . . . . . . . . . . . . . . 4

Refrigerant Piping Limitations . . . . . . . . . . . . . . . 4

Cooling Capacity - EA090 . . . . . . . . . . . . . . . . . . 6

Heating Capacities . . . . . . . . . . . . . . . . . . . . . . . 8

Electric Heat Accessory . . . . . . . . . . . . . . . . . . . 9

Blower Motor and Drive Data . . . . . . . . . . . . . . . 9

Supply Air Blower Performance FA090. . . . . . . . 9

Supply Air Plenum Performance Data. . . . . . . . 10

10

Static Resistances for Unit Accessories (IWG) . 11

11

Physical Data (Outdoor Unit). . . . . . . . . . . . . . . 16

12

Physical Data (Indoor Unit) . . . . . . . . . . . . . . . . 16

13

Physical Data - Electric Heat Accessories . . . . 17

14

Electrical Data - Outdoor Unit . . . . . . . . . . . . . . 17

15

Indoor Unit - Heat Pump Only . . . . . . . . . . . . . . 17

16

Control Wire Sizing . . . . . . . . . . . . . . . . . . . . . . 17

17

Heat Pump With Electric Heat. . . . . . . . . . . . . . 18

Unitary Products Group

Page 26

http://www.rezine.net
036-21371-001-B-0203

APPLICATION FLEXIBILITY
OUTDOOR UNITS
These outdoor units are lightweight and can be installed on
almost any roof.

5 FT. MIN.

TYPICAL
RIGGING

Units can be lifted using nylon straps with hooks at the holes
provided in the base rails, or they may be lifted with a forklift
through the slotted openings in the base rails.
A quality appearance and low sound levels make these units
suitable for most ground level locations.
Remember that during heat and defrost cycles, condensate
will drip from the underside of the unit coils and that this condensate will freeze when the temperature of the outdoor air is
below 32F. A gravel bed or some other means of handling
this condensate may have to be provided.

FORK-LIFT
OPENINGS

INDOOR UNITS
These indoor units are shipped for vertical installation, but
may be field converted for horizontal applications by separating and repositioning the Blower Section. See product installation manual for for detail.

FIGURE 1: EA090 - OUTDOOR UNITS

The Supply Air Plenum and the Return Air Grille accessories can be used on either arrangement.

The Base accessory can only be used on the vertical


arrangement.

Units installed horizontally are designed for ceiling suspension. Four 3/8" - 16 weldnuts are provided in the angle supports on the front of the unit. Knockouts are provided in the
exterior panels for access to these weldnuts. The hanger
rods must be supplied in the field.

FIGURE 2: FA090 - INDOOR UNITS

Unitary Products Group

Page 27

http://www.rezine.net
036-21371-001-B-0203

TABLE 1: ARI RATINGS 1- COOLING, HEATING AND SOUND


Heating Capacity
Model

Cooling Capacity

High Outdoor
Temperature (47 F)

Low Outdoor
Temperature (17 F)

Outdoor
Unit

Indoor
Unit

MBH3

EER

MBH3

COP

MBH3

COP

EA090

FA090

90

10.67

87.7

3.25

55

2.34

1
2
3

Outdoor Unit

Sound Rating2
(bels)

EA090

8.9

Certified in accordance with the Unitary Large Equipment certification program, which is based on ARI Standard 340/360.
Rated in accordance with ARI Standard 270.
Deduct 1 MBH when a unit operates at 208 volts.

TABLE 2: SYSTEM APPLICATION DATA


Air Temperature on OUTDOOR Coil, F
Minimum

Air Temperature on INDOOR Coil, F

Maximum

Cool

Heat

40 db

db1

Cool

minimum
heat

115 db

Cool

75 db

Below 0F, the control circuit will lock out the compressor and allow the electric heat
accessory to cycle at its standby capacity.

Operation below this temperature is permissible for a short period of time when a
unit is required to heat the conditioned space up to 50F.

TABLE 3: REFRIGERANT PIPING LIMITATIONS1


System
(Tons)
7-1/2

Maximum
Vertical Rise,2
(Feet)

Maximum
Total Length
(Feet)

60

125

57 wb

Maximum
Heat
50 db

Cool

Heat

72 wb

80 db

Air Flow across INDOOR Coil, CFM (Min./Max.)


FA090

1
2

2400/3600

Refer to installation instruction Form 035-18474-000 for more


detailed information on refrigerant piping.
Based on the loss of static head in the liquid riser during the
heating cycle.

Unitary Products Group

Page 28

http://www.rezine.net
036-21371-001-B-0203

SYSTEM FLEXIBILITY
The coils for both the indoor and outdoor units are not only
circuited and headered for optimum heating and cooling performance, but also for ample subcooling during all modes of
operation. The sub-cooling permits the outdoor unit to be
mounted 60 feet over or under the indoor unit without any
danger of flashing liquid refrigerant during the heating or the
cooling cycle.
Refer to the REFRIGERANT PIPING table above for more
detailed information on refrigerant pipe limitations.

Unitary Products Group

A = 1-3/8" OD Vapor Line


B = 1-1/8" OD Vapor Line
C = Intermediate Trap - only required when a riser
exceeds 50 feet.
D = Inverted Trap - only required when the horizontal run
to the unit exceeds 25 feet.

Page 29

http://www.rezine.net
036-21371-001-B-0203

TABLE 4: COOLING CAPACITY - EA090


Temperature of Air on Condenser Coil
85F
Total
Total
Total
Total
Sensible Capacity (MBh)
Return Dry Bulb (F)
Capacity 1 Input 2
Capacity 1 Input 2
CFM WB(F)
(MBh)
(kW) 86 83 80 77 74 71 68
(MBh)
(kW)
72
99
7.0
59 52 45 39 32 96
7.7
67
91
6.9
73 66 59 52 46 39 32
88
7.6
2400
62
82
6.7
82 78 71 64 57 50 43
82
7.5
57
86
6.7
86 83 76 69 62 55 49
89
7.5
72
102
7.1
66 58 49 41 33 99
7.8
67
94
7.0
81 73 64 56 48 40 32
90
7.7
2850
62
84
6.8
84 82 77 69 61 52 44
84
7.5
57
88
6.8
88 87 83 74 66 58 50
91
7.5
72
105
7.2
73 63 53 44 34 101
7.9
67
96
7.1
89 79 70 60 50 41 31
92
7.7
3300
62
86
7.0
86 86 83 74 64 54 45
85
7.6
57
90
6.9
90 90 89 80 70 60 51
93
7.6
72
106
7.2
75 65 55 45 34 103
7.9
67
97
7.1
92 82 72 61 51 41 31
94
7.7
3450
62
87
7.0
87 87 86 75 65 55 45
87
7.6
57
91
6.9
91 91 91 81 71 60 50
94
7.6
72
107
7.2
78 67 56 45 35 104
7.9
67
99
7.1
95 84 73 63 52 41 31
95
7.7
3600
62
88
7.0
88 88 88 77 66 56 45
88
7.6
57
93
6.9
93 93 93 82 71 60 50
96
7.6

95F
Sensible Capacity (MBh)
Return Dry Bulb (F)
86 83 80 77 74 71 68
58 51 44 37 31 72 65 58 51 44 37 31
82 77 70 63 56 50 43
87 80 73 66 59 53 46
65 57 48 40 32 80 71 63 55 47 38 30
84 81 76 68 60 52 44
90 86 80 71 63 55 47
71 62 52 43 33 88 78 68 59 49 39 30
85 85 83 73 64 54 44
93 93 86 77 67 57 48
74 64 54 44 34 91 81 70 60 50 40 30
87 87 85 75 65 55 45
94 94 89 79 68 58 48
77 66 55 45 34 94 83 73 62 51 40 30
88 88 88 77 66 56 45
96 96 91 81 70 59 49

Temperature of Air on Condenser Coil


105F
Total
Total
Total
Total
Sensible Capacity (MBh)
Return Dry Bulb (F)
Capacity 1 Input 2
Capacity 1 Input 2
CFM WB(F)
(MBh)
(kW) 86 83 80 77 74 71 68
(MBh)
(kW)
72
93
8.5
56 49 42 35 29 89
9.3
67
83
8.4
70 63 56 49 42 36 29
79
9.3
2400
62
79
8.2
79 75 68 61 55 48 41
76
9.0
57
83
8.3
82 76 69 62 55 48 42
78
9.1
72
95
8.6
63 55 46 38 30 91
9.4
67
85
8.5
77 70 62 53 45 37 29
80
9.4
2850
62
81
8.3
81 79 75 67 59 50 42
78
9.1
57
85
8.3
84 81 76 67 59 51 43
79
9.1
72
97
8.7
70 60 51 41 31 92
9.5
67
87
8.6
85 77 67 58 48 38 29
82
9.4
3300
62
82
8.4
82 82 82 72 63 53 43
79
9.2
57
87
8.4
87 87 82 73 63 54 44
81
9.2
72
99
8.7
72 62 52 42 32 95
9.5
67
89
8.6
87 79 69 59 49 38 28
84
9.4
3450
62
84
8.4
84 84 84 73 63 53 43
81
9.2
57
88
8.4
88 88 85 74 64 54 44
83
9.2
72
100
8.7
75 64 53 43 32 97
9.5
67
90
8.6
90 82 71 60 49 39 28
86
9.4
3600
62
86
8.4
86 86 85 75 64 53 42
83
9.2
57
90
8.4
90 90 87 76 65 55 44
84
9.2

115F
Sensible Capacity (MBh)
Return Dry Bulb (F)
86 83 80 77 74 71 68
54 47 40 33 26 68 61 54 48 41 34 27
76 73 66 60 53 46 39
78 72 65 58 51 44 37
61 53 45 36 28 75 68 60 52 44 36 27
78 76 74 65 57 49 41
79 76 72 63 55 47 39
68 58 49 39 30 82 76 66 57 47 37 28
79 79 81 71 62 52 42
81 81 79 69 59 50 40
70 60 50 40 30 84 78 68 57 47 37 27
81 81 82 72 62 51 41
83 83 80 70 60 50 40
72 62 51 40 30 86 80 69 58 48 37 26
83 83 83 72 62 51 40
84 84 82 71 61 50 39

Air On
Evaporaor Coil

Air On
Evaporaor Coil

Unitary Products Group

Page 30

http://www.rezine.net
036-21371-001-B-0203

TABLE 4: COOLING CAPACITY - EA090 (CONT.)


Temperature of Air on Condenser Coil
125F
Total
Total
Sensible Capacity (MBh)
1
2
Return Dry Bulb (F)
Capacity Input
CFM WB(F)
86
83
80 77 74 71 68
(MBh)
(kW)
72
85
10.2 52 45 38 31 24 67
74
10.1 66 59 53 46 39 32 25
2400
62
74
9.8
74 71 65 58 51 44 37
57
72
9.9
72 67 61 54 47 40 33
72
87
10.3 59 51 43 34 26 67
76
10.2 73 67 59 51 42 34 26
2850
62
75
9.9
75 74 72 64 56 48 39
57
73
10.0 73 71 68 60 51 43 35
72
88
10.4 66 57 47 38 28 67
77
10.3 77 75 65 55 46 36 27
3300
62
76
10.0 76 76 76 70 61 51 41
57
75
10.1 75 75 75 65 56 46 37
72
90
10.4 68 58 48 38 28 67
79
10.3 79 76 66 56 46 36 25
3450
62
78
10.0 78 78 78 70 60 50 40
57
77
10.1 77 77 76 66 56 46 36
72
93
10.3 70 60 49 38 27 67
81
10.3 81 78 67 57 46 35 24
3600
62
80
9.9
80 80 80 70 59 48 38
57
79
10.0 79 79 78 67 56 45 35

Air On
Evaporaor Coil

Nominal Rating

1 - These capacities are gross


ratings. For net capacity, deduct
air blower motor, MBh = 3.415 x
kW. Refer to the appropriate
Blower Performance Table for the
kW of the supply air blower motor.

2 - These ratings include the


condenser fan motors (total 1 kW)
and the compressor motors but not
the supply air blower motor.

The capacities shown are gross ratings. For net capacities, determine the KW requirement of the supply air blower motor per the SUPPLY AIR BLOWER PERFORMANCE table. Convert KW to MBH by the following equation and deduct this equivalent heat from the gross cooling ratings.
Blower Motor Heat (MBH) = Blower Motor KW x 3.415
Apply the following correction factors to determine the unit performance at different CFM.
These ratings include the compressor KW and the following KW for the outdoor fan motor(s).
% Nominal Supply Air CFM
Total Capacity Correction Factor
Sensible Capacity Correction Factor
Kilowatt Correction Factor

80

90

100

110

120

0.963
0.935
0.981

0.981
0.965
0.992

1.000
1.000
1.000

1.015
1.049
1.008

1.030
1.098
1.019

NOTE: Sensible capacity can never exceed total capacity. A higher


corrected sensible capacity indicates a dry coil, and it should be
reduced to the corrected total capacity.
Outdoor Unit Size
Outdoor Fan Motor KW - 60 HZ

7-1/2 Ton
0.83

Blower motor KW is not included. Refer to the SUPPLY AIR BLOWER PERFORMANCE table for the KW rating of the supply air blower motor at the design
conditions and add this power requirement to the KW rating.

Unitary Products Group

Page 31

http://www.rezine.net
036-21371-001-B-0203

UNIT MODEL EA090


OUTDOOR TEMPERATURE (F) (72% RH)
CFM

ID DB

10

20

30

40

50

60

70

2400

60 MBH

12.237

28.142

44.048

59.954

75.859

91.765

107.671

123.576

2400

KW

2.090

3.179

4.268

5.357

6.447

7.536

8.625

9.714

2400

70 MBH

9.673

25.579

41.485

57.390

73.296

89.201

105.107

121.013

2400

KW

2.576

3.665

4.754

5.844

6.933

8.022

9.111

10.201

2400

80 MBH

9.589

25.495

41.401

57.306

73.212

89.118

105.023

120.929

2400

KW

3.352

4.441

5.530

6.619

7.709

8.798

9.887

10.976

3300

60 MBH

13.565

29.471

45.377

61.282

77.188

93.094

108.999

124.905

3300

KW

1.417

2.506

3.595

4.685

5.774

6.863

7.952

9.041

3300

70 MBH

10.826

26.732

42.637

58.543

74.449

90.354

106.260

122.166

3300

KW

1.852

2.941

4.030

5.119

6.209

7.298

8.387

9.476

3300

80 MBH

10.916

26.822

42.727

58.633

74.539

90.444

106.350

122.256

3300

KW

2.679

3.768

4.857

5.946

7.035

8.125

9.214

10.303

3600

60 MBH

14.284

30.189

46.095

62.001

77.906

93.812

109.718

125.623

3600

KW

1.353

2.442

3.531

4.620

5.710

6.799

7.888

8.977

3600

70 MBH

11.720

27.626

43.531

59.437

75.343

91.248

107.154

123.060

3600

KW

1.839

2.928

4.018

5.107

6.196

7.285

8.374

9.464

3600

80 MBH

11.636

27.542

43.448

59.353

75.259

91.165

107.070

122.976

3600

KW

2.615

3.704

4.793

5.883

6.972

8.061

9.150

10.239

THE MBH AND KW VALUES DO NOT INCLUDE THE SUPPLY AIR BLOWER MOTOR.
FOR NET CAPACITY, ADD THE SUPPLY AIR BLOWER MOTOR HEAT (MBH = 3.415 x KW)
These ratings are based on an outdoor relative humidity of 72%. They include an allowance for defrost but not for the supply air blower motor heat. Refer to the
BLOWER PERFORMANCE table for the KW rating of the supply air blower motor at the design conditions. Convert this KW rating to MBH using the following
equation and add this equivalent heat to the heating capacity.
Blower Motor Heat (MBH) = Blower Motor KW x (3.415 MBH/KW)
Use the following equation to determine the C.O.P. at any operating condition.
C.O.P. = Total MBH (including Blower Motor Heat)/[Total KW (including Blower Motor KW) x 3.415]
correct the MBH and KW ratings with the following factors for different supply air CFMs.
These ratings include the compressor KW and the following KW for the outdoor fan motor(s).
Correction Factor
MBH
KW

80

90

100

110

120

0.96
1.030

0.98
1.015

1.00
1.000

1.02
0.985

1.04
0.970

NOTE: Apply these factors to the above ratings before correcting for the supply air blower heat and power requirements.
.
Outdoor Unit Size
7-1/2 Ton
Outdoor Fan Motor KW - 60 HZ

0.96

Blower motor KW is not included. Refer to the SUPPLY AIR BLOWER PERFORMANCE table for the KW rating of the supply air blower motor at the design
conditions and add this power requirement to the KW rating.

Unitary Products Group

Page 32

http://www.rezine.net
036-21371-001-B-0203

TABLE 5: ELECTRIC HEAT ACCESSORY


Heating Capacity
Heater Model

2HS045010

2HS045016
2HS045026
2HS045036
1
2

Nominal Voltage

25A

2401

46A

4802

25A

2401

46A

4802

25A

2401

46A

4802

25A

2401

46A

4802

Nominal

Defrost

Supplemental

Standby and Emergency

KW

MBH

KW

MBH

KW

MBH

KW

MBH

10

34.2

10

34.2

10

34.2

10

34.2

16

54.7

10

34.2

16

54.7

16

54.7

26

88.8

16

54.7

26

88.8

26

88.8

36

123.0

16

54.7

26

88.8

36

123.0

For 208 volts, multiply the MBH and KW values by (208/240)^2 or 0.751.
For 208 volts, multiply the MBH and KW values by (230/240)^ 2 or 0.918.
For 460 volts, multiply the MBH and KW values by (460/480)^2 or 0.918.

TABLE 6: BLOWER MOTOR AND DRIVE DATA


Indoor
Unit
Model

Motor
HP

Blower
HP

FA090

1-1/2

690 - 920

*Motor Specifications:

Adjustable Motor Pulley

Belt

Bore,
(in.)

Pitch Diameter,
(in.)

Bore,
(in.)

Designation

Pitch Length,
(in.)

2.8 - 3.8

7/8

7.5

A36

37.3

1750 RPM

208/230/460-3-60**

1.15 service factor

solid base

56 frame

permanently lubricated
ball bearings

Fixed Blower Pulley

Pitch Diameter,
(in.)

**These motors will always be wired for a 460 volt power supply.
Refer to the wiring diagram inside the motor terminal box when
the motor leads have to be reconnected for a 208 or 230 volt
power supply.

inherently protected

TABLE 7: SUPPLY AIR BLOWER PERFORMANCE FA0901,2


7.5 HEAT PUMP BLOWER PERFORMANCE
ESP

CFM

RPM

Watts

CFM

RPM

Watts

CFM

RPM

Watts

CFM

RPM

Watts

CFM

RPM

Watts

CFM

RPM

Watts

0.2

4152

895

1877

4014

892

1844

3725

819

1378

3443

774

1201

3219

734

1015

2949

691

855

0.4

3901

900

1752

3753

897

1714

3404

823

1255

3091

777

1084

2818

736

899

2503

694

744

0.6

3617

905

1607

3478

902

1569

3000

837

1118

2671

855

943

2149

740

762

0.8

3232

911

1443

3083

907

1406

2468

831

957

2740

916

1222

2431

913

1185

0 turns
1
2

1 turn

2 turns

3 turns

4 turns

5 turns

Available static pressure in IWG to overcome the resistance of the duct system and any accessories added to the unit. Refer to the table above for
additional motor and drive data and to Table 10 for the resistance of these accessories.
Refer to Form 515.41-AD1 for blower performance curves.

Unitary Products Group

Page 33

http://www.rezine.net
036-21371-001-B-0203

TABLE 8: SUPPLY AIR PLENUM PERFORMANCE DATA


ANGLE OF DEFLECTION
VERTICAL

HORIZONTAL

LOUVERS1
INDOOR
FACE
UNIT
VELO
CFM
MODEL
CITY
FA
(FPM)

090

(PLAN
VIEW)

THROW

SPREAD

(FEET3)

(FEET)3

SPR EAD

MIN.

MAX.

MIN.

MAX

VERTICAL

LOUVERS
(ELEVATION
VIEW)

SPR EAD

18

DROP (FEET)4

2 2 -1 /2
S P R E A D

LOUVERS
(PLAN
VIEW)

THROW

SPREAD

(FEET)3

(FEET)3

MIN.

MAX

MIN.

HORIZONTAL
4 5
S P R E A D

LOUVERS
(ELEVATION
VIEW)

SPR EAD

18

MAX DROP (FEET)4

VERTICAL

HORIZONTAL

LOUVERS1
(PLAN
VIEW)

LOUVERS2
(ELEVATION
VIEW)

THROW

SPREAD

(FEET)3

(FEET)3

18

SPR EAD

MIN.

MAX.

MIN.

MAX. DROP (FEET)4

2400

615

47

74

20

29

19

34

53

23

33

17

26

39

45

65

2700

690

53

83

22

32

20

10

39

59

25

36

18

29

45

48

71

10

3000

770

59

92

24

35

21

10

42

66

27

40

19

32

50

52

78

10

3300

845

65

101

26

38

21

10

46

73

29

44

19

35

55

56

85

10

3600

920

71

110

28

41

22

11

50

79

32

47

20

10

38

60

60

91

11

Adjusting the vertical louvers will vary the throw, the spread and the drop.

Adjusting the horizontal louvers will only vary the drop.

The velocity of the air will be 125 ft./min. at the minimum distance and 80 ft./min. at the maximum distance.

The velocity of the conditioned air at the bottom of the drop will be 50 ft./min. Drafts will occur if the drop extends into the occupied level of the conditioned space.

7.5-ton Heat Pump


4400
4200
O turns

4000
1 turn

3800

CFM

3600

2 turns

3400
3 turns

3200
4 turns

3000
2800

5 turns

2600
2400
0

0.1

0.2

0.3

0.4

0.5

0.6

Static

0.7

0.8

0.9

1.1

FIGURE 3: FA090 AIRFLOW CHART

10

Unitary Products Group

Page 34

http://www.rezine.net
036-21371-001-B-0203

TABLE 9: STATIC RESISTANCES FOR UNIT ACCESSORIES (IWG)


Unit Model

CFM

Accessory

ELECTRIC HEAT

2400

2700

3000

3300

10 KW

0.01

0.01

0.01

0.02

3600
0.02

16 KW

0.01

0.02

0.02

0.03

0.04
0.07

26 KW

0.03

0.04

0.05

0.06

36 KW

0.05

0.07

0.08

0.10

0.11

Supply Air Plenum

0.03

0.03

0.04

0.05

0.06

Return Air Grille

0.02

0.03

0.04

0.05

0.06

FA090

ACCESSORIES (FIELD-INSTALLED)

the basic unit. They may have to be insulated in the field for
certain applications.

Three-Phase Electric Heaters are available in several capacities to provide maximum flexibility. The heater can be
selected to precisely meet the supplemental heating requirement of the conditioned space.
These heaters are designed for easy field-installation over
the supply air opening of the indoor unit. They have been
tested by Underwriters Laboratories and will be shipped with
a UL label. Every heater will be fully protected against excessive current and temperature by fuses and two high limit thermostats.
Units with Electric Heat will require only one power supply for
both the heating elements and the supply air blower motor,
and the power wiring can be protected by either dual element/time delay fuses or an inverse time circuit breaker.
Supply Air Plenums and Return Air Grilles (expanded metal)
are available for free-standing indoor units located in the conditioned space. Both accessories are finished to match the
exterior of the basic unit, and both can be applied with either
vertical or horizontal units. The supply air plenums are fully
insulated and have double-deflection, adjustable grilles.
Base Sections are available to raise vertical indoor units
above the floor. Outdoor air may be introduced through these
bases by cutting an access opening for the outdoor air duct
connection. These bases are finished to match the exterior of

Unitary Products Group

Decorative Coil Guards can be field installed to enhance protection of the unit.
Thermostats with either manual or automatic changeover are
available for precise control of the temperature within the
conditioned space. The manual thermostat has a four-position selector switch - COOL, OFF, HEAT, and EMERGENCY
HEAT, and three stages of control - one stage of cooling and
two stages of heating. The automatic thermostat has a threeposition selector switch - OFF, AUTOMATIC and EMERGENCY HEAT, and four stages of control - two stages of
cooling and two stages of heating.
Both thermostats have a two-position fan switch, AUTO and
ON to provide intermittent or continuous blower operation.
NOTE: The automatic changeover thermostat must be used
on units equipped with a field-supplied economizer.
The first cooling stage of the automatic thermostat
will only control the position of the reversing valve;
the system will still operate with only one stage of
cooling.
The EMERGENCY HEAT position on the selector
switch and the second stage of heating will only function on systems with an electric heat accessory.

11

Page 35

http://www.rezine.net
036-21371-001-B-0203

CENTER OF GRAVITY

CLEARANCES
Overhead (Top)1

120

Front
(Piping and Access Panels

30

Left Side

24

Right Side

24

Rear

24

Bottom2

1
2

Dim. (inches.)
Unit

Unit must be installed outdoors. Overhanging structures


or shrubs should not obstruct air discharge outlet.
Adequate snow clearance must be provided if winter
operation is expected.

EA090

70-1/8

32

29-5/8

16-1/2

All dimensions are in inches. They are


subject to change without notice. Certified
dimensions will be provided upon request.

EA090
(7-1/2 Ton)

AIR
OUT

AIR
OUT

CONTROL BOX
ACCESS

GUAGE
LINE
ACCESS

AIR
IN

39

1-3/8* OD
VAPOR LINE
5/8* OD
LIQUID LINE

14-3/4
6-3/4

2-3/4
8-3/4
5-3/8
32
7/8" KNOCKOUT
ACCESSORY WIRING
ENTRY

2-1/4

5-7/8

32-1/2
CONDENSER FAN MOTOR
ACCESS

70-1/8

6-3/4
7/8 DIA
CONTROL WIRING
ENTRY
1-3/8 DIA.
POWER WIRING
ENTRY

*AIR ON 3 SIDES

COMPRESSOR AND
CONDENSER FAN MOTOR
ACCESS

FIGURE 4: UNIT DIMENSIONS & CLEARANCES - OUTDOOR UNITS

12

Unitary Products Group

Page 36

http://www.rezine.net
036-21371-001-B-0203

MINIMUM CLEARANCES

ACCESSORIES

ELECTRIC HEATER - Add 14-1/4 to unit height when


used.
SUPPLY AIR PLENUM - Add 27-1/2 to unit height when
used.
BASE - Add 20 to unit height when used.

Side with RETURN AIR opening

24

Side with SUPPLY AIR opening

241

Side with PIPING CONNECTIONS

522

Side opposite PIPING CONNECTIONS

12

Side with access for both POWER &


CONTROL WIRING

--3

Bottom

--4

1
2
3

Overall dimension of the unit will vary if an electric heater, a


supply air plenum or a base is used.
This dimension is required for removal of the coil. Only 26 is
required for normal servicing.
Although no clearance is required for service and operation,
some clearance may be required for routing the power wiring
and the control wiring.
Allow enough clearance to trap the condensate drain line.

FIGURE 5: UNIT DIMENSIONS & CLEARANCES- INDOOR UNITS

Unitary Products Group

13

Page 37

http://www.rezine.net
036-21371-001-B-0203

Install the control wiring per basic unit instruction


Form 035-18475-000. DO NOT route any field control
wiring through the plenum.
WITHOUT ELECTRIC HEAT - Install the power and
the control wiring per basic unit instruction Form
035-18475-000. DO NOT route any wiring through the
plenum and DO NOT remove this knockout.

FIGURE 7:

ACCESSORY DIMENSIONS

Unitary Products Group

15

Page 38

http://www.rezine.net
036-21371-001-B-0203

TABLE 10: PHYSICAL DATA (OUTDOOR UNIT)


DESCRIPTION
Compressor

Fans
Fan Motors2

Coil

Refrigerant-22 (Lbs.)

UNIT MODEL - EA090

Rating - tons

7-1/2

Quantity
Diameter - inches No. of Blades
Nominal CFM
HP
RPM
Rows Deep x Rows High
Finned Length - inches
Face Area - square feet
Tube (Copper) OD - inches
Fins (Aluminum) per inch
Holding Charge

2
24/3
7800
3/4
1100
2 x 36
96
24.00
3/8
16
1.50

Operating Charge3

18.8
4

Unit Weight (Lbs.)

24.6

Pumpdown Capacity
Shipping
Operating

510
505

These compressors are fully hermetic.

These PSC motors are directly connected to the outdoor fans and have inherent protection, ball bearings and a 48 frame. Rotation
(when viewing shaft end of motor) -090 = CW.

Includes outdoor unit and matched indoor blower unit, but no piping.

Based on a 95 F ambient.

TABLE 11: PHYSICAL DATA (INDOOR UNIT)

Centrifugal Blower (Forward Curve)

DESCRIPTION
Rows Deep x Rows High
Finned Length - inches
Face Area - square feet
Tube (Copper) OD - inches
Fins (Aluminum) per inch
Diameter x Width - inches

Blower Motor1

Nominal Rating - HP

1-1/2

Filters (Throwaway)

Quantity Per Unit - 16 x 25 x 1


Total Face Area - square feet

4
11.1

Coil

Refrigerant-22 (Lbs.)
4

Unit Weight (lbs.)

UNIT MODEL - FA090


3 x 32
45.5
10.1
3/8
13
15 X 15

Holding Charge2
Pumpdown
Shipping
Operating

Capacity3

Electric Heaters
Accessory Operating Weights (Lbs.)

16.5

10 KW
16 KW
26 KW
36 KW

Supply Air Plenum


Base
Return Air Grille
Shipping Volume (Basic Unit) - cubic feet

425
385
63
66
71
74
102
60
15
45

All of these 1750 RPM motors have a solid base, a 56 frame, a 1.15 service factor, inherent protection & permanently lubricated
ball bearings. Refer to Table 7 for additional motor & drive data.

Although every indoor unit is shipped with a small holding charge, this charge will be lost during installation. Loss of all refrigerant
must be reclaimed during installation - NOT vented into the atmosphere. Refer to the above table on the OUTDOOR unit for the
system operating charge.

Based on a 80F ambient.

Refer to Installation Instruction Form 035-18475-000 for the distributed weight of these indoor units.

Refer to Table 13 for additional electric heat accessory data.

16

Unitary Products Group

Page 39

http://www.rezine.net
036-21371-001-B-0203

TABLE 12: PHYSICAL DATA - ELECTRIC HEAT ACCESSORIES


Nominal Heater Capacity

Description

10 kW

16 KW

% Nickel
Heater Elements

26 KW

36 KW

59.2

% Chromium

16.0

Coil ID - inches

9/32

Watt Density - watts/sq.in.

59

Rows Deep

Face Area - square feet

3.0

TABLE 13: ELECTRICAL DATA - OUTDOOR UNIT


Compressor

Model
EFB

090A

Power
Supply

RLA

LRA

25

200/230-3-60

25.6

190.0

46

460-3-60

12.8

95.0

Outdoor Fan Motor

0.94 @ 208V
0.84 @ 230V
0.86

Max.
Fuse
Size

208/230-1-60

3.03

38.1

60

460-1-60

1.6

19.2

30

10

Power
Supply

Size,1
AWG

Based on three, 60C insulated copper conductors in steel conduit.

TABLE 14: INDOOR UNIT - HEAT PUMP ONLY


Blower
Motor
HP

Power
Supply

1-1/2

TABLE 15: CONTROL WIRE SIZING

Max. Fuse
FLA

Size,1
AMPS

FA090

Qty.

Min.
Circuit
Amps

Min. Wire

FLA
(Each)

Power
Factor

Wire Size

Max. Total
Circuit Length, (Ft.)

#19 Solid

130

#18 Solid

170

208-3-60

5.2

15

#18 Stranded

180

230-3-60

5.0

15

#16 Stranded

270

460-3-60

2.6

15

#14 Stranded

455

#12 Stranded

730

Dual element, time delay fuses.

To determine the total circuit length, add the following distances:


1 - Outdoor Unit to Indoor Unit
________
2 - Indoor Unit to Thermostat
________
3 - Thermostat to Indoor Unit
________
4 = Indoor Unit to Outdoor Unit
________
Total Circuit Length
________

Unitary Products Group

17

Page 40

http://www.rezine.net
036-21371-001-B-0203

TABLE 16: HEAT PUMP WITH ELECTRIC HEAT1


Nominal
Heater
KW

Total Unit
Ampacity
AMPS

Max, Fuse

Min. Wire

Size,3
AMPS

Size,4
AWG

20.8

31.3

35

230-3-60

24.1

35.1

40

460-3-60

12.0

17.6

20

12

208-3-60

33.4

46.9

50

230-3-60

38.5

53.1

60

460-3-60

19.2

26.7

30

10

208-3-60

54.2

73

80

230-3-60

62.5

83.2

90

460-3-60

31.3

41.7

45

208-3-60

75.1

99

110

230-3-60

86.6

113.3

125

460-3-60

43.3

56.7

60

Power Supply

Heater
FLA

208-3-60

FA090
10

16

26

36

Unit with an electric heat accessory will always be wired for a single power supply.

Refer to the Heating Capacity table for the actual KW and MBH ratings of each heater at the different voltages.

Inverse time circuit breakers may be used in lieu of dual element, time delay fuses.

Based on three, insulated copper conductors in steel conduit: 60C wire when the total unit ampacity is below 100 amps; 75C
wire when the total unit ampacity is 100 amps and above.

18

Unitary Products Group

Page 41

http://www.rezine.net

Page 42

http://www.rezine.net

036-21363-002-B-0303

DESCRIPTION

TECHNICAL GUIDE

YORK has combined the latest concepts in modern technology


with time-proven quality standards to design a split-system heat
pump to meet the demands of the energy and quality-conscious
commercial market.
Both the outdoor and indoor units are completely piped and wired
at the factory. Only the interconnecting liquid and vapor lines are
required to complete the refrigerant circuit. Every unit is dehydrated, evacuated, leak tested and pressure tested before being
pressurized with a holding charge of Refrigerant-22 for shipment
and/or storage. The compressor, fan motors and controls are
functionally tested after the units are fabricated to assure a reliable start-up and years of dependable operation.
These units have been tested by Underwriters' Laboratories and
will be shipped with UL and CUL labels.

OUTDOOR UNIT
Every outdoor unit includes a heavy-duty compressor with a
crankcase heater, line break overload protection, a suction line
accumulator with a fusible plug, a 4-way reversing valve with a
24-volt solenoid, outdoor fan motor(s) with inherent protection,
and a copper tube/aluminum fin coil that is positioned vertically for
better drainage of the water that will condense on it during the
heating cycle.
They also include a filter-drier, an expansion valve and a distributor that are only used during the heating cycle plus a check valve
to provide the proper flow of refrigerant through the unit during
both the cooling and heating cycles.

SPLIT-SYSTEM
HEAT PUMPS
60 HZ
EA120 / FA120

To eliminate the costly cabinet deterioration problems usually


associated with outdoor equipment, all sheet metal parts are constructed of commercial grade (G90) galvanized steel. After fabrication, each part is thoroughly cleaned to remove any grease or
dirt from its surfaces. The parts that will be exposed to the
weather are then coated with a powder paint to assure a quality
finish for many years. This coating system has passed the 750
hour, salt spray test per ASTM Standard B117. To assist in servicing, the high and low pressure service connections are exterior
to the cabinet, allowing simple access.
The fan guards are vinyl-coated to provide additional rust protection. An optional decorative coil guard is available to protect the
coil on the outdoor unit.

INDOOR UNIT
Every indoor unit includes a well-insulated cabinet, a copper tube/
aluminum fin coil, 1" throwaway filters, a centrifugal blower, a
blower motor, adjustable drive components, a blower motor contactor and a small holding charge of Refrigerant-22.
They also include a filter-drier, an expansion valve and a distributor that are only used during the cooling cycle; also, a check valve
to provide the proper flow of refrigerant through the coil during
both the cooling and heating cycles.
This product was manufactured
in a plant whose quality system
is certified/registered as being
in conformity with ISO 9001.

The units are shipped in the vertical position ready for field installation. For horizontal installation, interchange the solid bottom
panel and the return air duct flange on the front of the unit.

FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE

Page 43

http://www.rezine.net
036-21363-002-B-0303

TABLE OF CONTENTS
DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
OUTDOOR UNIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
INDOOR UNIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
APPLICATION FLEXIBILITY . . . . . . . . . . . . . . . . . . . . . . 3
OUTDOOR UNITS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
VERTICAL / HORIZONTAL . . . . . . . . . . . . . . . . . . . . . . . . 3

SYSTEM FLEXIBILITY . . . . . . . . . . . . . . . . . . . . . . . . . . 5
ACCESSORIES (FIELD-INSTALLED) . . . . . . . . . . . . . 11
ACCESSORY DIMENSIONS . . . . . . . . . . . . . . . . . . . . 14

LIST OF FIGURES
Fig.#

Pg.#

LIST OF TABLES
Tbl.#

Pg.#

ARI RATINGS - COOLING, HEATING AND SOUND . 4

SYSTEM APPLICATION DATA . . . . . . . . . . . . . . . . . 5

COOLING CAPACITIES . . . . . . . . . . . . . . . . . . . . . . . 6

HEATING CAPACITIES . . . . . . . . . . . . . . . . . . . . . . . . 8

ELECTRIC HEAT ACCESSORY . . . . . . . . . . . . . . . . . 9

BLOWER MOTOR AND DRIVE DATA . . . . . . . . . . . . 9

SUPPLY AIR BLOWER PERFORMANCE . . . . . . . . . 9

SUPPLY PLENUM PERFORMANCE . . . . . . . . . . . . 10

STATIC RESISTANCES FOR UNIT


ACCESSORIES (IWG) . . . . . . . . . . . . . . . . . . . . . . . . 11

TYPICAL RIGGING . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

10 UNIT/DIMENSIONS . . . . . . . . . . . . . . . . . . . . . . . . . . 12

VERTICAL AND HORIZONTAL APPLICATION . . . . . . 4

11 CLEARANCES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

INDOOR AIRFLOW . . . . . . . . . . . . . . . . . . . . . . . . . . 10

12 PHYSICAL DATA - INDOOR UNIT . . . . . . . . . . . . . . 15

UNIT DIMENSIONS . . . . . . . . . . . . . . . . . . . . . . . . . . 12

UNIT DIMENSIONS & CLEARANCES - INDOOR


UNITS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

13 PHYSICAL DATA -ELECTRIC HEAT


ACCESSORIES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

FIELD WIRING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

15 ELECTRICAL DATA - OUTDOOR UNIT . . . . . . . . . . 16

ELECTRIC HEATER . . . . . . . . . . . . . . . . . . . . . . . . . . 14

16 INDOOR HEAT UNIT - HEAT PUMP ONLY . . . . . . . 16

SUPPLY AIR PLENUM . . . . . . . . . . . . . . . . . . . . . . . . 14

17 HEAT PUMP WITH ELECTRIC HEAT . . . . . . . . . . . . 16

RETURN AIR GRILLE . . . . . . . . . . . . . . . . . . . . . . . . 14

14 PHYSICAL DATA - OUTDOOR UNIT . . . . . . . . . . . . 15

10 BASE ACCESSORY . . . . . . . . . . . . . . . . . . . . . . . . . . 14

Unitary Products Group

Page 44

http://www.rezine.net
036-21363-002-B-0303

APPLICATION FLEXIBILITY

VERTICAL / HORIZONTAL

OUTDOOR UNITS

The FA120 unit is shipped for vertical installation with a


vertical air discharge as shown in FIG. 2; but may be
converted to other arrangements per the following
instructions:

These outdoor units are lightweight and can be


installed on almost any roof.
Units can be lifted using nylon straps with hooks at the
holes provided in the base rails, or they may be lifted
with a forklift through the slotted openings in the base
rails.
A quality appearance and low sound levels make these
units suitable for most ground level locations.
Remember that during heat and defrost cycles, condensate will drip from the underside of the unit coils.
This condensate will freeze when the temperature of
the outdoor air is below 32F. A gravel bed or some
other means of handling this condensate may have to
be provided.

1.

Remove the panels from the blower section.

2. Remove the four Phillips machine bolts that hold


the coil and blower sections together. A bolt is
located near each corner.
3. Move the blower section to the proper location.
4. Attach the blower section to the coil section with
the machine bolts removed in Step 2.
5. Before replacing the panel, see Duct Connection
and Drain Connection.
6. Replace the panels.
NOTE: See Figure -2 on next page for horizontal and
vertical application.

5 Ft. Min.

FORKLIFT
OPENINGS

FIGURE 1 - TYPICAL RIGGING

Unitary Products Group

Page 45

http://www.rezine.net
036-21363-002-B-0303

B LOWE R MOT OR
LOC AT IO N
AIR O UT
(S td. A rrangment)
R E T UR N A IR
DUC T F LANG E
B LOWE R
S E C T IO N
B LOWE R
S E C T IO N
AIR
IN

R E T UR N A IR
DUC T F LANG E

F IL T E R S

E V AP OR AT OR
C OIL

HOR IZONT AL
P OS IT IO N

C OIL
S E C T IO N

F IL T E R S

V E R T IC AL
P OS IT IO N

Alternate A ir D is charge A rrangements


S ee R everse S ide for H orizontal S us pens ion D ata
NOT E : C ertain blower pos itions a re not recommended
becaus e the blower motor s hould not be mounted
ups ide down.

FIGURE 2 - VERTICAL AND HORIZONTAL APPLICATION

TABLE 1: ARI RATINGS* - COOLING, HEATING AND SOUND


Model

Heating Capacity
Cooling Capacity
High Outdoor
Temperature (47F)

Low Outdoor Temperature (17F)

Outdoo Unit

Indoor Unit

MBH3

EER

MBH3

COP

MBH3

COP

EA-120

FA120

122

10.7

125

3.25

84

2.5

*.
.

Outdoor
Unit

Sound Rating
(bels)

EA-120

8.8

Ratings are in accordance with ARI Standard 340/360


Sound Ratings are in accordance with ARI Standard 270.

Unitary Products Group

Page 46

http://www.rezine.net
036-21363-002-B-0303

TABLE 2: SYSTEM APPLICATION DATA


Air Temperature on OUTDOOR Coil, F
Minimum

Air Temperature on INDOOR Coil, F

Maximum

Minimum

Maximum

Cool

Heat

Cool

Heat

Cool

Heat

Cool

Heat

40 db

0 db*

115 db

75 db

57 wb

50 db

72 wb

80 db

Air Flow across INDOOR Coil, CFM (Min./Max.)


FA-120
*.
.

3200/4800

Below 0F,the control circuit will ock out the compressor and allow the electric heat accessory to cycle at its standby capacity.
Operation below this temperature is permissible for a short period of time when a unit is required to heat the conditioned space up to 50F.

SYSTEM FLEXIBILITY
The coils for both the indoor and outdoor units are not only
circuited and headered for optimum heating and cooling performance, but also for ample subcooling during all modes of
operation. The sub-cooling permits the outdoor unit to be
mounted 60 feet over or under the indoor unit without any
danger of flashing liquid refrigerant during the heating or the
cooling cycle.
Refer to the REFRIGERANT PIPING table above for more
detailed information on refrigerant pipe limitations.
A = 1-3/8" OD Vapor Line
B = 1-1/8" OD Vapor Line
C = Intermediate Trap - only required when a riser exceeds
50 feet.
D = Inverted Trap - only required when the horizontal run to
the unit exceeds 25 feet.

Unitary Products Group

Page 47

http://www.rezine.net
036-21363-002-B-0303

TABLE 3: COOLING CAPACITIES


Temperature of Air Condenser Coil
85F

Air On
Evaporator Coil

CFM

3000

3750

4500

4750

5000

95F
Sensible Capacity (MBh)

Sensible Capacity (MBh)

Total
Capacity
(MBh)

Total
Input
(kW)

Total
Capacity
(MBh)

Total
Input
(kW)

86

83

80

77

74 71 68

72

134

11.4

79

70

61

53

44

86

83

80

77

74

71

121

12.2

75

66

58

49

40

67

121

11.2

96

88

79

70

62 53 45

113

12.0

93

85

76

67

59

50

42

62

110

11.1

110 105

97

57

111

11.1

111 105

97

88

79 71 62

102

11.9

102

99

91

82

74

65

57

88

80 71 63

102

11.9

102

99

91

82

74

65

72

139

11.6

90

79

57

68

58

47

129

12.4

87

76

65

54

44

67

125

11.4

110

99

88

77

66 55 45

120

12.2

108

97

86

75

64

54

43

62

114

57

115

11.2

114 112 108

97

86 75 64

108

12.1

108 107 103

92

81

70

59

11.3

115 112 108

97

86 75 64

109

12.1

109 107 103

92

81

70

72

59

144

11.8

102

88

75

62

49

136

12.6

99

86

73

60

47

67

129

11.6

123 110

97

84

71 58 44

127

12.5

122 109

96

83

70

57

44

62

118

11.4

118 118 118 105 92 79 66

114

12.4

114 114 115

102

89

75

62

57

119

11.5

119 119 119 106 92 79 66

115

12.4

115 115 115

102

89

75

62

72

148

11.9

106

78

64

50

139

12.7

103

89

75

61

47

67

134

11.7

129 115 101

87

73 59 45

130

12.5

127 113

99

85

71

57

43

62

122

11.5

122 122 122 108 94 80 66

116

12.5

116 116 117

103

89

75

61

57

123

11.6

123 123 123 109 95 81 67

117

12.4

117 117 117

103

89

75

61

72

153

11.9

111

81

66

51

141

12.8

107

77

62

48

67

138

11.8

134 119 104

89

74 59 45

132

12.6

132 117 102

87

72

57

42

62

126

11.6

126 126 126 111 96 81 66

119

12.5

119 119 119

104

89

74

59

57

127

11.6

127 127 127 112 97 82 67

119

12.5

119 119 119

105

90

75

60

WB
(F)

Return Dry Bulb (F)

92

96

Return Dry Bulb (F)

92

68

Temperature of Air Condenser Coil


105F

Air On
Evaporator Coil

CFM

3000

3750

4500

4750

5000

115F
Sensible Capacity (MBh)

Sensible Capacity (MBh)

Total
Capacity
(MBh)

Total
Input
(kW)

72

116

13.2

73

64

56

47

38

67

108

13.0

91

82

74

65

57 48 40

62

100

12.9

100

95

87

78

70 61 53

99

13.9

99

91

83

74

66

57

49

57

99

12.9

99

95

87

78

69 61 52

96

13.9

96

91

82

74

65

57

48

72

123

13.4

85

74

63

52

41

117

14.5

83

72

61

50

39

67

115

13.2

105

95

84

73

62 51 41

109

14.2

102

93

82

71

60

49

39

62

106

13.1

106 104

99

88

77 66 55

105

14.1

105

101

94

83

73

62

51

57

105

13.1

105 103

98

88

77 66 55

102

14.1

102

99

94

83

72

61

51

72

130

13.7

97

71

57

44

124

14.7

95

82

68

55

42

67

121

13.4

119 107

94

81

68 55 42

115

14.4

115

105

92

79

66

53

40

62

112

13.4

112 112 110

97

84 71 58

111

14.4

111

111

106

93

80

67

53

57

111

13.3

111

111 110

97

84 71 58

107

14.3

107

107

106

92

79

66

53

72

133

13.2

101

87

73

59

45

127

13.6

98

84

70

56

42

67

124

13.0

122 111

97

83

69 55 41

118

13.4

118

108

94

80

66

52

38

62

115

12.9

115 115 113

99

85 71 57

114

13.3

114

114

109

95

81

67

53

57

114

12.9

114 114 113

99

85 71 57

110

13.3

110

110

108

94

80

66

52

72

136

12.7

104

90

75

60

45

130

12.5

102

87

72

57

42

67

126

12.5

126 114

99

84

70 55 40

121

12.3

121

112

97

82

67

52

37

62

117

12.4

117 117 115 100 85 70 55

116

12.3

116

116

111

96

82

67

52

57

116

12.4

116 116 115 100 85 70 56

113

12.2

113

113

111

96

81

66

51

WB
(F)

Return Dry Bulb (F)


86

83

84

80

77

74 71 68
-

Total
Capacity
(MBh)

Total
Input
(kW)

111
103

Return Dry Bulb (F)


86

83

80

77

74

71

68

14.2

71

62

53

45

36

14.0

89

80

72

63

55

46

38

Unitary Products Group

Page 48

http://www.rezine.net
036-21363-002-B-0303

Temperature of Air Condenser Coil


125F

Air On
Evaporator Coil

CFM

Sensible Capacity (MBh)


Total
Capacity
(MBh)

Total
Input
(kW)

72

105

67
62
57

WB
(F)

Nominal Rating

Return Dry Bulb (F)


86

83

80

77

74 71 68

15.3

68

60

51

43

34

98

15.0

87

78

70

61

53 44 36

98

14.9

98

87

79

70

62 53 44

93

14.9

93

87

78

70

61 53 44

3000

72

111

15.5

80

70

59

48

37

67

103

15.2

99

91

80

69

58 47 37

62

103

15.1

103

98

90

79

68 58 47

57

98

15.1

98

95

90

79

68 57 46

92

1 - These capacities are gross


ratings. For net capacity, deduct
air blower motor, MBh = 3.415 x
kW. Refer to the appropriate
Blower Performance Table for
the kW of the supply air blower
motor.

3750

72

117

15.7

79

66

53

40

67

109

15.4

109 103

90

77

64 51 38

62

109

15.4

109 109 101

88

75 62 49

57

103

15.3

103 103 101

88

75 62 48

72

121

14.0

96

82

68

54

40

67

112

13.8

112 106

92

78

64 50 36

62

112

13.7

112 112 105

91

77 63 49

57

106

13.7

106 106 104

90

76 62 48

72

124

12.4

99

84

69

54

39

67

115

12.2

115 109

94

79

64 49 34

62

115

12.1

115 115 108

93

78 63 48

57

109

12.1

109 109 107

92

77 62 47

4500

4750

2 - These ratings include the


condensate fan motors (total 1
kW) and the compressor motors
but not the supply air blower
motor.

5000

1 Capacities shown are gross ratings. For net capacities, determine the KW requirement of the supply air blower motor per the SUPPLY AIR BLOWER PERFORMANCE table on page 7.

Convert KW to MBH by the following equation and deduct this equivalent heat from the gross cool ing rat ings.
Blower Motor Heat (MBH) = Blower Motor KW x 3.415
2 Apply the fol lowing correc tion factors to determine the unit performance at different CFM.
3 These rat ings include the compressor KW and the following KW for the outdoor fan motor(s).

% Nomi nal Sup ply Air CFM


To tal Ca pac ity Cor rec tion Fac tor
Sen si ble Ca pac ity Cor rec tion Fac tor
Kilo watt Cor rec tion Fac tor

80
0.963
0.935
0.981

90
0.981
0.965
0.992

100
1.000
1.000
1.000

110
1.015
1.049
1.008

120
1.030
1.098
1.019

NOTE: Sensible capacity can never exceed total capacity. A higher


corrected sensible capacity indicates a dry coil, and it should
be reduced to the corrected total capacity.

Out door Unit Size


Out door Fan Mo tor KW - 60 HZ

10 Ton
1.06

Blower motor KW is not included. Refer to the SUPPLY AIR BLOWER PERFORMANCE table for the KW rating of the supply air blower motor at the design conditions and add this power
requirement to the KW rating.

Unitary Products Group

Page 49

http://www.rezine.net
036-21363-002-B-0303

TABLE 4: HEATING CAPACITIES


HEATING APPLICATION DATA

UNIT MODEL EF-10 60 HZ


OUTDOOR TEMPERATURE (F) (72% RH)

CFM

ID DB

3000

MBH

10

20

30

40

50

60

70

13.058

35.855

58.653

81.451

104.249

127.047

149.844

172.642

60
3000

KW

2.805

4.421

6.038

7.654

9.270

10.887

12.503

14.120

3000

MBH

12.959

35.757

58.555

81.353

104.151

126.949

149.746

172.544

70
3000

KW

3.682

5.299

6.915

8.532

10.148

11.764

13.381

14.997

3000

MBH

12.312

35.110

57.908

80.706

103.503

126.301

149.099

171.897

80
3000

KW

4.697

6.313

7.930

9.546

11.162

12.779

14.395

16.012

4000

MBH

17.636

40.434

63.232

86.030

108.827

131.625

154.423

177.221

60
4000

KW

1.741

3.357

4.974

6.590

8.207

9.823

11.440

13.056

4000

MBH

17.554

40.352

63.150

85.948

108.745

131.543

154.341

177.139

70
4000

KW

2.623

4.240

5.856

7.473

9.089

10.705

12.322

13.938

4000

MBH

16.930

39.728

62.526

85.324

108.122

130.919

153.717

176.515

KW

3.645

5.261

6.877

8.494

10.110

11.727

13.343

14.960

MBH

18.690

41.488

64.285

87.083

109.881

132.679

155.477

178.274

KW

1.586

3.202

4.819

6.435

8.052

9.668

11.284

12.901

MBH

18.592

41.389

64.187

86.985

109.783

132.581

155.378

178.176

KW

2.463

4.080

5.696

7.313

8.929

10.546

12.162

13.778

MBH

17.944

40.742

63.540

86.338

109.136

131.933

154.731

177.529

KW

3.478

5.094

6.711

8.327

9.944

11.560

13.176

14.793

80
4000
5000
60
5000
5000
70
5000
5000
80
5000

THE MBH AND KW VALUES DO NOT INCLUDE THE SUPPLY AIR BLOWER MOTOR.
FOR NET CAPACITY, ADD THE SUPPLY AIR BLOWER MOTOR HEAT (MBH = 3.415 X KW)
the

1These ratings are based on an outdoor relative humidity of 72%. They include an allowance for defrost but not for the supply air blower motor heat. Refer to the BLOWER PERFORMANCE
table for the KW rating of the supply air blower motor at the design conditions. Convert this KW rating to MBH using the following equation and add this equivalent heat to the heating capacity.
Blower Motor Heat (MBH) = Blower Motor KW x (3.415 MBH/KW)
Use the following equation to determine the C.O.P. at any operating condition:
C.O.P. = Total MBH (Including Blower Motor Heat)/[Total KW (Including Blower Motor KW) x 3.415]
2Correct the MBH and KW ratings with the following factors for different supply air CFM's.
3These ratings include the compressor KW and the following KW for the outdoor fan motor(s).
Cor rec tion Fac tor
MBH
KW

80
0.96
1.030

% Nomi nal Sup ply Air CFM


90
100
110
0.98
1.00
1.02
1.015
1.000
0.985

120
1.04
0.970

NOTE: Apply these factors to the above ratings before correcting


for the supply air blower heat and power requirements.
Out door Unit Size
Out door Fan Mo tor KW - 60 HZ
Out door Fan Mo tor KW - 50 HZ

7-1/2 Ton
0.96
0.80

10 Ton
1.03
0.85

Blower motor KW is not included. Refer to the SUPPLY AIR BLOWER PERFORMANCE table for the KW rating of the supply air blower motor at the design conditions and add this power
requirement to the KW rating.

Unitary Products Group

Page 50

http://www.rezine.net
036-21363-002-B-0303

TABLE 5: ELECTRIC HEAT ACCESSORY

Heater Model

Nomi nal Volt age

2HS045016

2HS045026

2HS045036

KW

Heat ing Ca pac ity


Supplemental
MBH
KW
MBH

10

34.2

10

34.2

10

34.2

10

34.2

16

54.7

10

34.2

16

54.7

16

54.7

26

88.8

16

54.7

26

88.8

26

88.8

36

123.0

16

54.7

26

88.8

36

123.0

2401
4802
4802
2401
4802
4802
2401
4802
4802
2401
4802
4802

25A
46A
50A
25A
46A
50A
25A
46A
50A
25A
46A
50A

2HS045010

Nominal
KW
MBH

Defrost

Standby and Emer gency


KW
MBH

1For 208 volts, mul ti ply the MBH and KW val ues by (208/240)^2 or 0.751.
For 230 volts, mul ti ply the MBH and KW val ues by (230/240)^2 or 0.918.
2For 460 volts, mul ti ply the MBH and KW val ues by (460/480)^2 or 0.918.

TABLE 6: BLOWER MOTOR AND DRIVE DATA


Indoor
Unit
Model

Motor
HP*

Blower HP

FF-10

550-730

*.

Adjustable Motor Pulley

Fixed Blower Pulley

Belt

Pitch Diameter (in.)

Bore (in.)

Pitch Diameter (in.)

Bore (in.)

Designation

Pitch Length (in.)

2.8-3.8

7/8

9.5

A55

56.3

These motors will always be wired for a 460 volt power supply. Refer to the wiring diagram inside the motor terminal box when the motor
leads have to be reconnected for a 208 or 230 volt power supply.

1750 RPM

inherently protected

208/230/460-3-60**

1.15 service factor

solid base

permanently lubricated

56 frame

*Motor Specifications:

TABLE 7: SUPPLY AIR BLOWER PERFORMANCE*


ESP

CFM

RPM

Watts

CFM

RPM

Watts

CFM

RPM

Watts

CFM

RPM

Watts

CFM

RPM

Watts

CFM

RPM

Watts

0.2

5775

680

2168

5402

650

1851

4990

616

1516

4571

582

1281

4250

548

1097

0.4

5521

713

2283

5409

684

1954

4810

653

1633

4326

618

1307

3785

582

1069

3484

550

903

0.6

4864

718

2006

4736

688

1695

4098

657

1353

3411

622

1052

2635

586

826

0.8

4221

722

1695

3780

693

1393

2860

661

1019

728

1376

2625

697

1097

3223
1

0 turns

1 turn

2 turns

3 turns

4 turns

5 turns

Exceeds Amperage rating of motor.


*.
.

Available static pressure in IWG to overcome the resistance of the duct system and any accessories added to the unit. Refer to the table above for
additional motor and drive data and to Table 9 on page11 for the resistance to these accessories.
Refer to Form 515.41-AD1 for blower performance curves.

Unitary Products Group

Page 51

http://www.rezine.net
036-21363-002-B-0303

TABLE 8: SUPPLY PLENUM PERFORMANCE


Angle of Deflection

Vertical
Louvers1
(Plan View)
Indoor
Unit
Model
FF-10

CFM

0
SPREAD

Face
Velocity
(FPM

Horizontal
Lovers
(Elevation
View)

Spread
(Feet)3

Throw
(Feet)3

18

Vertical
22-1/2
Louvers
SPREAD (Plan View)

Spread
(Feet)3

Throw
(Feet)3

18

0
SPREAD

1
2
3
4

45
SPREAD

Horizontal
Lovers
(Elevation
View)

Spread
(Feet)3

Throw
(Feet)3

18

0
SPREAD

Min.

45

70

29

Max

820

63

98

25

37

3600

920

71

110

28

41

22

11

50

69

32

47

20

10

38

60

60

91

11

4000

1025

78

123

30

45

22

11

56

88

35

52

20

10

42

66

67

102

11

4400

1130

86

135

33

49

23

12

62

97

38

57

21

11

47

73

76

115

12

4800

1230

94

147

35

53

23

12

68

106

41

62

21

11

51

80

85

127

12

43

19

Min.

Max.

Min.

Max.

34

53

54

82

Drop (Feet)4

Min.

10

Max.

Max. Drop (Feet)4

Max

21

Min.

0
SPREAD

Min.
3200

120

Drop (Feet)4

Vertical Louvers
(Plan View)

Horizontal
Lovers
(Elevation
View)

10

Adjusting the vertical louvers will vary the throw, the spread and the drop.
Adjusting the horizontal louvers will only vary the drop.
The velocity of the air will be 125 ft./min. at the minimum distance and 80 ft./min. at the maximum distance.
The velocity of the conditioned air at the bottom of the drop will be 50 ft./min. occur if the drop extends into the occupied level of the conditioned
space.

FA120
7000
6500
0 turns

6000
1 turn

CFM

5500
2 turns

5000
3 turns

4500
4 turns

4000
5 turns

3500
3000
0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.1

Static
FIGURE 3 - INDOOR AIRFLOW

10

Unitary Products Group

Page 52

http://www.rezine.net
036-21363-002-B-0303

TABLE 9: STATIC RESISTANCES FOR UNIT ACCESSORIES (IWG)


UNIT MODEL

CFM

ACCESSORY

3200

3600

4000

4400

4800

10
KW

0.02

0.02

0.03

0.03

0.04

16
KW

0.03

0.04

0.05

0.06

0.07

26
KW

0.06

0.07

0.09

0.11

0.13

36
KW

0.09

0.11

0.14

0.17

0.20

SUPPLY AIR PLENUM

0.05

0.06

0.07

0.08

0.10

RETURN AIR GRILLE

0.05

0.06

0.07

0.08

0.10

ELECTRIC HEAT
FF-10

ACCESSORIES (FIELD-INSTALLED)

Three-Phase Electric Heaters are available in several


capacities to provide maximum flexibility. The heater
can be selected to precisely meet the supplemental
heating requirement of the conditioned space.
These heaters are designed for easy field-installation
over the supply air opening of the indoor unit. They
have been tested by Underwriters' Laboratories and
will be shipped with a UL label. Every heater will be
fully protected against excessive current and temperature by fuses and two high limit thermostats.
Units with Electric Heat will require only one power
supply for both the heating elements and the supply air
blower motor, and the power wiring can be protected
by either dual element/time delay fuses or an inverse
time circuit breaker.
Supply Air Plenums and Return Air Grilles (expanded
metal) are available for free-standing indoor units
located in the conditioned space. Both accessories are
finished to match the exterior of the basic unit, and both
can be applied with either vertical or horizontal units.
The supply air plenums are fully insulated and have
double-deflection, adjustable grilles.
Base Sections are available to raise vertical indoor
units above the floor. Outdoor air may be introduced
through these bases by cutting an access opening for
the outdoor air duct connection. These bases are finished to match the exterior of the basic unit. They may
have to be insulated in the field for certain applications.

Unitary Products Group

Decorative Coil Guards can be field installed to


enhance protection of the unit.
Thermostats with either manual or automatic
changeover are available for precise control of the temperature within the conditioned space. The manual
thermostat has a four-position selector switch - COOL,
OFF, HEAT, and EMERGENCY HEAT, and three
stages of control - one stage of cooling and two stages
of heating. The automatic thermostat has a three-position selector switch - OFF, AUTOMATIC and EMERGENCY HEAT, and four stages of control - two stages
of cooling and two stages of heating.
Both thermostats have a two-position fan switch,
AUTO and ON to provide intermittent or continuous
blower operation.
NOTE: The automatic changeover thermostat must be
used on units equipped with a field-supplied
economizer.
The first cooling stage of the automatic thermostat will only control the position of the
reversing valve; the system will still operate
with only one stage of cooling.
The EMERGENCY HEAT position on the selector
switch and the second stage of heating will only function on systems with an electric heat accessory.

11

Page 53

http://www.rezine.net
036-21363-002-B-0303

FIGURE 4 - UNIT DIMENSIONS

NOTE: All dimensions are in inches. They are subject


to change without notice. Certified dimensions
will be provided upon request.

TABLE 11: CLEARANCES


Overhead (Top)*

120

(Piping and Access Panels)

30

Left Side

24

Right Side

24

TABLE 10: UNIT/DIMENSIONS


Dim. (in.)
Unit
EA120

Rear

24

16

38

Bottom

*.
.

Units must be installed outdoors. Overhanging structures or


shrubs should not obstruct condenser air discharge.
Adequate snow clearance must be provided if winter operation
is expected.

12

Unitary Products Group

Page 54

http://www.rezine.net
036-21363-002-B-0303

MINIMUM CLEARANCES
Side with RETURN AIR opening

24"

Side with SUPPLY AIR opening

24"*

Side with PIPING CONNECTIONS

61

Side opposite PIPING CONNECTIONS

26

Side with access for both POWER &


CONTROL WIRING

26
**

Bottom
*.

**.

Overall dimension of the unit will


vary if an electric heater, a supply
air plenum or a base is used.
This dimension is required for
removal of the coil. Only 26 is
required for normal servicing.

Although no clearance is required


for service and operation, some
clearance may be required for
routing the power wiring and the
control wiring.
Allow enough clearance to trap
the condensate drain line.

FIGURE 5 - UNIT DIMENSIONS & CLEARANCES - INDOOR UNITS

FIGURE 6 - FIELD WIRING

Unitary Products Group

13

Page 55

http://www.rezine.net
036-21363-002-B-0303

ACCESSORY DIMENSIONS

FIGURE 7 - ELECTRIC HEATER

BASE

19-7/8

19-1/2

24

27

6-1/8
1-3/4
2-1/2
55-3/4
31

60-3/4
1-1/8

60-3/4

31-5/8

2-1/2 KNOCKOUT FOR POWER WIRING


WHEN ELECTRIC HEATER IS USED

FIGURE 10 - BASE ACCESSORY

FIGURE 8 - SUPPLY AIR PLENUM

60-3/4

31

5/8

FIGURE 9 - RETURN AIR GRILLE

14

Unitary Products Group

Page 56

http://www.rezine.net
036-21363-002-B-0303

TABLE 12: PHYSICAL DATA - INDOOR UNIT


UNIT MODEL

DESCRIPTION

FA120
Rows Deep X Rows High
Finned Length - inches
Face Area - square feet
Tube (Copper) OD - inches
Fins (Aluminum) per inch
Diameter X Width - inches
HP
RPM
Quantity per unit
Size (in)
Total Face Area - square feet
Shipping
Operating

Coil

Centrifugal Blower (Forward Curve) - Qty


Blower Motor *

Filters (Throwaway)

Unit Weight (lbs)

3 X 32
54.5
12.11
3/8
13
18 X 18 - 1
2
1750
6
20 X 20 X 1
16.7
425
435
63
66
71
74
114
20
100

10 kW
16 kW
26 kW
36 kW

Electric Heat
Accessory Operating Weight (lbs.)
Supply Air Plenum
Return Air Grille
Base
*.

Refer to Blower Motor and Drive Data table for more information

TABLE 13: PHYSICAL DATA -ELECTRIC HEAT ACCESSORIES


Nominal Heater Capacity

Description

Heater Elements

10 KW

16 KW

% Nickel

59.2

% Chromium

16.0

Coil ID - inches

9/32

Watt Density - watts/sq. in.

26 KW

36 KW

59.0

Rows Deep

Face Area - square feet

2
3.0

TABLE 14: PHYSICAL DATA - OUTDOOR UNIT


UNIT MODEL

DESCRIPTION

EA120

Compressor*

Rating - (Qty) Tons


Quantity

Fans

Blades/Pitch ()

3/30

Nominal CFM

8100

HP

3/4

RPM

1100

Rows Deep X Rows High

2 X 40

Fan Motors

Coil

Refrigerant - 22 (lbs - ozs)

Finned Length - inches

130

Face Area - square feet

36.11

Tube(Copper) OD - inches

3/8

Fins(Aluminum) per inch

18

Holding Charge (sys1/sys2)

1-0/1-0

Operating Charge

31-8

Unit Weight (lbs)


*.
.
.

10

Shipping

847

Operating

857

These compressors are fully hermetic.


The ball bearing, 48 frame, single phase condenser fan motors have internal protection and are directly connected to the condenser fans. Motor rotation is counter-clockwise when viewing the lead end, which is opposite the shaft end.
The amount of charge in the unit as shipped from the factory.

Unitary Products Group

15

Page 57

http://www.rezine.net

TABLE 15: ELECTRICAL DATA - OUTDOOR UNIT


Compressor

Outdoor Fan Motor


Power Supply

Qty.

FLA (Each)

Min.
Circuit
Amps

208/230-1-60

3.0

58.6

100

460-1-60

1.8

27.2

45

Model
Power Supply

RLA

208/230-3-60

42.0

LRA

Power Factor

Max.
Fuse
Size

Min. Wire
Size
AWG

0.95 @ 208V
2

239.0

42.0

EF-10

0.86 @ 230V
4

460-3-60

19.2

146.0

0.86

19.2

TABLE 16: INDOOR HEAT UNIT - HEAT PUMP ONLY


IN DOOR UNIT
HEAT PUMP ONLY
Blower
Motor
HP

Power
Supply

208-3-60
230-3-60
460-3-60

Max. Fuse
Size,1
AMPS

FLA
FA120
7.5
6.8
3.4

10
10
5

1Dual ele ment, time de lay fuses.


o

2Based on three 60 C, 14 AWG, in su lated cop per con duc tors

TABLE 17: HEAT PUMP WITH ELECTRIC HEAT*


NOMINAL HEATER
KW

POWER SUPPLY
208-3-60

20.8

35.4

40

10

230-3-60

23.1

37.3

40

16

26

36

*.
.
.
**.

HEATER FLA

TOTAL UNIT
AMPACITY AMPS

MAX. FUSE SIZE AMPS

MIN WIRE SIZE AWG**

460-3-60

11.5

18.7

20

12

208-3-60

33.4

51.1

60

230-3-60

36.9

54.6

60

460-3-60

18.4

27.3

30

10

208-3-60

54.2

77.1

80

230-3-60

59.9

83.4

90

460-3-60

30.0

41.7

45

208-3-60

75.1

103.2

110

230-3-60

83.3

112.2

125

460-3-60

41.5

56.1

60

Unit with an electric heat accessory will always be wired for a single power supply.
Refer to the HEATING CAPACITY table on page 5 for the actual KW and MBH ratings of each heater at the different voltages.
Inverse time circuit breakers may be used in lieu of dual element, time delay fuses.
Based on three insulated copper conductors in steel conduit:
60C wire when the total unit ampacity is below 100 amps.
75C wire when the total unit ampacity is 100 amps or above.

Subject to change without notice. Printed in U.S.A.


CD: 6-21363
Copyright by Unitary Products Group 2003. All rights reserved.
Unitary
Products
Group

5005
York
Drive

Page 58

036-21363-002-B-0303
Supersedes: 036-21363-002-A-1202
Norman
OK
73069

http://www.rezine.net

Page 59

http://www.rezine.net

Page 60

http://www.rezine.net

COMMERCIAL ZONING PACKAGE

The Facility Explorer Commercial Zoning Package is a complete, turnkey control system used to improve
occupant comfort in a building (or section of a building) that is conditioned with a packaged rooftop HVAC unit.
It accomplishes this by varying the amount of conditioned air delivered to individual zones and by intelligently
cycling the rooftop units heating and cooling stages to best satisfy all the zone demands.

Manufacturer Independent
The Facility Explorer Commercial Zoning
Package is designed to work with any
standard, packaged HVAC equipment, regardless
of manufacturer. This allows you to apply this control
package to equipment provided by a variety of
suppliers or to equipment that has already been
installed. This flexibility makes the Facility Explorer
Commercial Zoning Package perfectly suited for both
new and retrofit installations.
Affordable Intelligence
The Facility Explorer Commercial Zoning Package
utilizes the distributed application architecture of
the FX16 Master Controller. This feature allows direct
communications to occur between the FX16 and all
the zone controllers. This means that there is no
need for a traditional supervisory class controller to
manage the data sharing. This direct communication
flow allows the FX16 to monitor each zones status to
intelligently determine the proper mode of operation
for the rooftop unit.

Page 61

http://www.rezine.net

COMMERCIAL ZONING PACKAGE

Easy Installation
Several pieces of the Facility Explorer Commercial
Zoning Package can be ordered pre-assembled from
the factory to simplify installation:

Bypass Damper and Actuator Assembly

Zone Controller and Actuator Assembly (FXZAN)

FX16 Master Controller with Pre-Downloaded


Zoning Application

The FX05 Field Controller is combined with an


M9104AGA non-spring return actuator and an
electrical termination wiring block, all in one
packaged assembly

FX16 Master Controller can be ordered with the


commercial zoning application pre-downloaded
Once installed, the FX16 takes care of downloading
the corresponding parts of the zoning application to
each of the zone controllers

Perfect for retrofit installations where the zone


damper is already installed
Zone Controller, Actuator, and Damper Assembly
FXZAN Zone Controller and Actuator Assembly is
combined with a round or rectangular zone damper
Perfect for new installations or for retrofit
installations where the zone damper has not yet
been installed

2005 Johnson Controls, Inc.

A round or rectangular bypass damper is combined


with an M910xHGA non-spring return actuator

Eliminates the downloading steps from the field


installation and startup
This provides the possibility (with an onsite Medium
User Interface) to download, configure and
commission the entire system, including the
rooftop, bypass, and all zone controllers without
any software tool

P.O. Box 423, Milwaukee, WI 53201

Page 62

Printed in USA PUBL-3894

http://www.rezine.net

Page 63

http://www.rezine.net

TSS Single Duct Variable Air Volume Terminal

An integrated VAV box with direct digital controls

TSS Terminals provide Variable Air Volume (VAV) control

eliminates the coordination and difficulties

beyond the typical single duct box. They are specifically

associated with factory mounting

designed for precise air delivery throughout the entire


operating range, regardless of the installed inlet conditions.

Downloading of software, setting of parameters,

These units can be ordered with or without a Direct Digital

addressing and testing at the factory reduces

Controller (DDC), which can operate as a stand-alone unit,

startup time and lowers risk

on a Johnson Controls N2 trunk, or on a LON trunk.

Superior flow measuring provides for lower

TSS Terminals take advantage of typical benefits provided

minimum cubic feet per minute (CFM) values,

by single duct units, while performing at extremely low

which reduces energy costs and noise while

sound levels. This is critical in todays buildings where

maintaining comforts in the zone

occupants are placing more emphasis on indoor acoustics.


The TSS Terminal is manufactured and assembled with a

Installation time can be reduced with the low

multi-point, center-averaging airflow sensor, which

profile compact design and standard metal

provides a signal to the controller enabling it to quietly and

hanging straps

precisely measure airflow.

Units wired in compliance with all applicable

Bundled with the TSS Terminal is a digital controller from

National Electrical Code (NEC) requirements and

the VAV Modular Assembly (VMA) Series or the LN Series.

tested in accordance with Air Conditioning and

Each model in the VMA1400 Series and the LN Series

Refrigeration Institute (ARI) standard 880

combines a controller, pressure sensor, and actuator


housed in one pre-assembled unit.

Offers damper stall detection, starved box


detection, actuator motor duty cycle, VAV box
flow test, and other diagnostics on most
models (VMA Series)

Page 64

http://www.rezine.net

TSS Single Duct Variable Air Volume Terminal

Standard Features

Optional Features

Construction

Construction

ARI 880 certified and labeled

20-gauge galvanized steel construction

22-gauge galvanized steel casing and valve

3/4 or 1 fiberglass insulation

G90 galvanized steel

Scrim-reinforced, foil-faced insulation meeting American


Society for Testing and Materials (ASTM) C1136 for mold,
mildew, and humidity resistance

1/2, 4lb/ft3 skin, dual density fiberglass insulation, glued


and clinch-pinned in place

1/2 Elastomeric closed-cell foam insulation

Hot Water Coils

Double wall construction with 22-gauge liner

ARI 410 certified and labeled

Mounting brackets to accept all-thread hanging rods or


wire hangers

1-, 2-, 3-, 4-row coils


Tested at a minimum of 350 psig under water

Low temperature construction for use in thermal storage


applications, including a thermally isolated primary air
inlet and a composite damper shaft

Mechanically expanded copper tubes leak tested


to 350 psig air pressure
Male sweat type water connections

Hot Water Coils


Low pressure steam coils

Primary Air Valve


Embossed rigidity rings

Multi-circuit coils for reduced water pressure drop

Low-thermal conducting damper shaft with


position indicator

Opposite hand water connections


Bottom and top access plates for cleaning

Mechanical stops for open and closed position

Electrical Components

Multi-point center-averaging airflow sensor

Full unit toggle disconnect and inline motor fusing

Brass balancing tees

Primary and secondary transformer fusing

Plenum-rated sensor tubing

Electric Heat

Electrical Components

Proportional solid state relay (SSR) heater control

cETL listed for safety compliance

Mercury contactors

National Electrical Manufacturers Association (NEMA)


Type 1 wiring enclosure

Door interlocking disconnect switches


Disconnect (toggle or door interlocking)

Electric Heat
ETL listed as an assembly for safety compliance
Integral electric heat assembly
Automatic reset primary and back-up secondary
thermal limits

Pneumatic Electric (PE) switches


Mercury and magnetic contactors
Manual reset secondary limit
24 volt control transformer

Single-point power connection

Special watt densities

Hinged electrical enclosure

Finned tubular elements

Fusing per NEC

Controls

Airflow switch

Factory-provided controls

Ni-chrome elements

Direct digital controls (DDC) for N2 or LON networks

Primary/Secondary power terminations

Pneumatic controls

Wiring diagram

2005 Johnson Controls, Inc.

P.O. Box 423, Milwaukee, WI 53201


www.johnsoncontrols.com

Page 65

Printed in USA PUBL-3888

http://www.rezine.net

TSL Single Duct Low Height Variable Air Volume Terminal

An integrated VAV box with direct digital controls

TSL Terminals provide variable air volume (VAV) control

eliminates the coordination and difficulties

beyond the typical single duct box. They are specifically

associated with factory mounting

designed for precise air delivery throughout the entire


operating range and are only 10 in height, making them

Downloading of software, setting of parameters,

ideal for shallow or congested ceiling plenum applications.

addressing and testing at the factory reduces

These units can be ordered with or without a Direct Digital

startup time and lowers risk

Controller (DDC), which can operate as a stand-alone unit,


on a Johnson Controls N2 trunk, or on a LON trunk.

Superior flow measuring provides for lower


minimum cubic feet per minute (CFM) values,

TSL Terminals take advantage of typical benefits provided

which reduces energy costs and noise while

by single duct units, while performing at extremely low

maintaining comforts in the zone

sound levels. This is critical in todays buildings where


occupants are placing more emphasis on indoor acoustics.

Installation time can be reduced with the low

The TSS Terminal is manufactured and assembled with

profile compact design and standard metal

a multi-point, center-averaging airflow sensor, which

hanging straps

provides a signal to the controller enabling it to quietly and


precisely measure airflow.

Units wired in compliance with all applicable


National Electrical Code (NEC) requirements and

Bundled with the TSL Terminal is a digital controller from

tested in accordance with Air Conditioning and

the VAV Modular Assembly (VMA) Series or the LN Series.

Refrigeration Institute (ARI) standard 880

Each model in the VMA1400 Series and the LN Series


combines a controller, pressure sensor, and actuator
housed in one pre-assembled unit.

Page 66

TSL Single Duct Low Height Variable Air Volume Terminal

http://www.rezine.net

Secondary high limit

Standard Features

Airflow switch

Construction
ARI 880 certified and labeled

Single-point power connection

20-gauge, galvanized steel casing and valve

Hinged electrical enclosure door

G90 galvanized steel construction

Fusing per NEC

1/2", 4 lb/ft3 skin, dual density fiberglass insulation glued


and clinch pinned

Optional Features

Invertible unit facilitates control installation on the left- or


right-hand side

Construction

Hot Water Coils


ARI 410 certified and labeled

Scrim-reinforced, foil-faced insulation meeting American


Society for Testing and Materials (ASTM) C1136 for mold,
mildew, and humidity resistance

1-, 2-, 3-, 4-row coils

1/2 Elastomeric closed-cell foam insulation

Left- or right-hand connections

Double wall construction with a 22-gauge liner

Tested at a minimum of 450 psig under water and rated


at 300 psig working pressure at 200F

Mounting brackets to accept all thread hanging rods or


wire hangers

Aluminum fin construction with die-formed spacer collars


for uniform spacing

Discharge sound attenuator (Model TSL-SA)

Mechanically expanded copper tubes leak tested to 450


psig air pressure and rated at 300 psig working pressure
at 200F

Coil access plate for cleaning coil

Hot Water Coil


Coil circuiting options for reduced water pressure drop
Right- or left-hand water connections

Male sweat type water connections

Bottom and top access plates for cleaning

Primary Air Valve


18-gauge, G90 galvanized steel construction

Steam coils

Low thermal conductance damper shaft

Electrical Components

Position indicator on external end of damper shaft

Toggle disconnect switch

Mechanical stops for open and closed position

Primary and secondary transformer fusing

Multi-point center-averaging airflow sensor

Electric Heat

Brass balancing tees

Proportional solid state relay (SSR) heater control

Plenum-rated sensor tubing

Mercury contactors (if equipped with a mercury contactor,


the unit cannot be inverted)

Electrical Components

Door interlocking disconnect switches

cETL listed for safety compliance with Underwriters


Laboratories Inc. (UL) 1995

Disconnect (toggle or door interlocking)

National Electrical Manufacturers Association (NEMA)


Type 1 wiring enclosure

Pneumatic Electric (PE) switches

Electric Heat

Manual reset secondary limit

Invertible unit facilitates control installation on the left- or


right-hand side (not applicable if equipped with a
mercury contactor)

Controls

cETL listed as an assembly for safety compliance

Direct Digital Controls (DDC), for N2 or LON networks

Automatic reset primary and back-up secondary


thermal limits

Pneumatic controls

Mercury and magnetic contactors

Factory-provided controls

Primary auto-reset high limit

2005 Johnson Controls, Inc.

P.O. Box 423, Milwaukee, WI 53201


www.johnsoncontrols.com

Page 67

Printed in USA PUBL-3882

http://www.rezine.net

Single Duct Variable Air Volume Terminal (Model TSS)


Unit
Size
6
8
10
12
14
16
22

CFM
200
400
600
800
1100
1500
3000

Bypass
CFM
300
600
900
1200
1800
2200
5400

Dimensions
Weight
18
20
25
30
38
42
72

WxHxL
10 x 10" x 11"
12 x 10 x 11"
14 x 12.5" x 13
16 x 15" x 13
20 x 17.5" x 17.5"
24 x 17.5" x 17.5"
34 x 17.5" x 11"

A
6 1/2
6 1/2
6 1/2
6 1/2
6 1/2
6 1/2
8

I
5 7/8
7 7/8
9 7/8
11 7/8
13 7/8
15 7/8
32 1/4 x 15 7/8

X
8 3/4
10 3/4
12 3/4
14 3/4
18 3/4
22 3/4
32 3/4

Y
8 3/4
8 3/4
11 1/4
13 3/4
16 1/4
16 1/4
16 1/4

Note: All dimensions are in inches with a tolerance of +1/8. Size 22 has a rectangular inlet collar. CFM based on
1000 FPM (Bypass 1500 FPM) for low to medium pressure applications.

Clearance 24"

Page 68

http://www.rezine.net

Single Duct Variable Air Volume Terminal - Rectangular (Model TSL)

Dimensions
Unit
Bypass
Size
CFM
CFM
A
W
L
X
Weight
10
600
1200
10
15
12 1/2
13 3/4
26
12
800
1600
14
19
12 1/2
17 3/4
28
14
1200
2200
20
25
16 1/2
23 3/4
39
16
1500
3000
26
31
16 1/2
29 3/4
45
Notes: 1. For dimensional data for unit sizes 6 and 8, refer to the Single Duct Variable
Air Volume Terminal (Model TSS). All dimensions are in inches with a tolerance of +1/8.
Weights are in pounds. Weights are for the basic unit with the indicated option and
control enclosure. Actual weight varies based on project-specific requirements for unit
options, appurtenances, and controls. 2. Control enclosure is standard with factorymounted electronic controls. 3. Check all national and local codes for required
clearances.

Page 69

http://www.rezine.net

Page 70

http://www.rezine.net

Model DE Series
UVC Emitters

UVC for HVAC

TM

power needed to maintain microbial control. The UVC


Emitter, by contrast, has a 12-month service life and even
after a full year, it has 2-1/2 times greater output than
competitive devices deliver on Day 1! As a result, only SterilAire can ensure the germicidal performance you need, with no
return of microbial growth, for 3-4 times longer than the
competition.

Double-Ended, Very High


Output Germicidal Light
Source for HVAC Systems

Applications
Steril-Aire Double-Ended (DE Series) fixtures are used
for internal installation in medium to large air handling
systems in commercial, industrial, health care and institutional
buildings. They may be mounted singly, in built-up banks or in
parallel configurations in a variety of locations, including
coils, drain pans, ductwork, mixed air plenums and exhaust
systems. The DE Series is available in five lengths (18, 24,
30, 36 and 42) and four voltage options (115, 208, 230 or
277 Vac), providing installation flexibility to accommodate
virtually any system.

Benefits
Kills or inactivates surface and airborne microorganisms that
contribute to poor IAQ and/or the spread of infectious disease,
including: mold and mold spores, bacteria (including TB,
Legionella, E. coli, Listeria, salmonella, and whooping
cough); and viruses (including colds, flu, measles).
Delivers an average of 5 times the output of competitive UVC
products at HVAC operating temperatures, for 3-4 times
longer life and more reliable germicidal control.
Uses patented state-of-the-art solid-state electronic power
supply for enhanced reliability and performance.
Continuously cleans coils, drain pans, plenums and ducts,
eliminating costly cleaning programs and the use of harmful
chemicals and disinfectants.
Lowers HVAC energy costs by restoring heat transfer and net
cooling capacity.
Steril-Aires multi-patented UVC Emitter provides the
best and longest-lasting UVC performance available. As
shown in the comparison graph (above), it has been
independently tested to deliver an average of 5 times the
output of other ultraviolet devices under HVAC operating
conditions (45o F @ 550 fpm air velocity).
Competitive UVC lights must be changed every 3-4
months because they quickly lose the output or killing

Produces no ozone or other secondary contaminants will not


harm building occupants, equipment or furnishings.
Offers lowest life-cycle cost of any UVC product. Return on
investment is often less than one year.
The most widely used product for commercial UVC for
HVAC the industry standard!

Page 71

http://www.rezine.net

Model DE Specifications
The UVC EmitterTM and fixture shall be factory assembled and
tested. They shall consist of a housing, power source, reflector,
Emitter sockets and Emitter.

be available in 115-208/230 or 277 Vac, 50/60 Hertz, and single phase.


The Emitter soc kets are medium bi-pin, double click safety, twist
lock type. They shall be constructed of UVC-resistant polycarbonate.

The housing shall be constructed of 304 stainless steel to withstand


HVAC environments. The reflector shall be constructed of heavy
gauge, specular finished aluminum alloy with approximately 85%
reflectance at 254 nm wavelength. The housing shall be equipped
with 1/2" electrical conduit openings on each end to facilitate
coupling and wiring fixture-to-fixture and to power. All components
shall be in one integral assembly to maximize serviceability.

The Emitter tube shall be a very high output, hot cathode, T5


diameter, medium bi-pin type that produces broadband UVC of 250260 nm. Each tube shall produce the specified output at 2000 fpm
velocity and air temperatures of 35-170 F. It shall produce no ozone
or other secondary contaminants.

The power source shall be a Class P2, electronic, rapid start type
with a power factor greater than 0.95 and a power conversion of
greater than 75%. The power supply design shall include RF and EMI
suppression. The power supply shall be designed to maximize photon
production, irradiance and reliability in cold or moving airstreams of
35-170 F, 100% RH and up to 2000 fpm velocity. The fixture shall

Inde pendent testing: The unit shall be tested by an independent test


laboratory in accordance with the general provisions of IES Lighting
Handbook, 1981 Applications Volume, and shall be verified through
independent testing to provide output per 1" arc length of not less
than 10 W/cm2 at 1 meter in a 400 fpm airstream of 45 F.
Unit shall comply with UL Standard 1995 for use in HVAC
equipment and shall carry the "UL" and "ULC" labels.

This product may be covered by one or more of the following patents, others pending: 5,334,347/ 5,866,076/ 5,817,276/ 6,372,186/ 6,313,470/ 6,245,293/
6,267,924/ 6,280,686/ 6,423,882.

Ordering Information
Model No.

Part No.

Description

Length

DE 181 VO
DE 181 VO
DE 241 VO
DE 241 VO
DE 301 VO
DE 301 VO
DE 361 VO
DE 361 VO
DE 421 VO
DE 421 VO
GTD 16 VO
GTD 22 VO
GTD 28 VO
GTD 34 VO
GTD 40 VO

10001500
10002100
10001600
10002200
10001700
10002300
10001800
10002400
10001300
10002500
20000100
20000200
20000300
20000400
20000500

Double-Ended Fixture
Double-Ended Fixture
Double-Ended Fixture
Double-Ended Fixture
Double-Ended Fixture
Double-Ended Fixture
Double-Ended Fixture
Double-Ended Fixture
Double-Ended Fixture
Double-Ended Fixture
Replacement Emitter DE 181
Replacement Emitter DE 241
Replacement Emitter DE 301
Replacement Emitter DE 361
Replacement Emitter DE 421

18"
18"
24"
24"
30"
30"
36"
36"
42"
42"
16"
22"
28"
34"
40"

Electrical
115, 208, 230V: 70-85 watts
277V: 70-85 watts
115, 208, 230V: 70-85 watts
277V: 70-85 watts
115, 208, 230V: 70-85 watts
277V: 70-85 watts
115, 208, 230V: 70-85 watts
277V: 70-85 watts
115, 208, 230V: 70-85 watts
277V: 70-85 watts
N/A
N/A
N/A
N/A
N/A

Weight
2.3 lb.
2.3 lb.
2.7 lb.
2.7 lb.
3.3 lb.
3.3 lb.
3.7 lb.
3.7 lb.
4.1 lb.
4.1 lb.
0.15 lb.
0.15 lb.
0.20 lb.
0.25 lb.
0.25 lb.

Complies with current U.S. and Canadian UL Standards for


use in HVAC equipment.

Represented By:

Steril-Aire, Inc.
Corporate Office:
2840 N. Lima Street
Burbank, CA 91504
Telephone: 818-565-1128
Fax: 818-565-1129
Website: www.steril-aire.com
Email: sales@steril-aire.com
2003 Steril-Aire

1100-07/05

Page 72

http://www.rezine.net
036-21323-002-C-0206

GENERAL SPECIFICATIONS
OUTDOOR UNIT:
Two independent refrigerant circuits
Inherently protected fan motors
Two independent scroll compressors
V-Coil Design
Exterior service port connections
Refrigerant-22 holding charge
Five-minute compressor anti-short cycle timer
Two independent control circuits
Compressor operation to 40 F

TECHNICAL GUIDE

Field-installed Low Ambient VFD Control to 0 F


Five-year limited warranty on compressor
One-year limited warranty on all other parts

COMMERCIAL
SPLIT-SYSTEM COOLING UNITS
FOUR PIPE SYSTEM
MODELS HB 180 & HB 240
MODELS LB 180 & LB 240
15 & 20 NOMINAL TONS
9.7 EER

Simplicity Controls
Factory installed disconnect and Technicoat coils

INDOOR UNIT:
Factory-mounted expansion valve and filter-drier in both
refrigerant circuit
Adjustable TXV
s
Two-inch throwaway filters
Single point power connection
One-year limited warranty on all parts
Field installed drive packages

FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE

Page 73

http://www.rezine.net
036-21323-002-C-0206

TABLE OF CONTENTS
GENERAL SPECIFICATIONS .......................1
OUTDOOR UNIT .................................1

LIST OF TABLES
Tbl. #

Pg. #

INDOOR UNIT ...................................1


1

UNIT APPLICATION DATA. . . . . . . . . . . . . . . . . . . . . . 7

APPLICATION FLEXIBILITY OUTDOOR ..............3

ARIRATINGS - COOLING AND SOUND . . . . . . . . . . . 7

APPLICATION FLEXIBILITY INDOOR ................3

ELECTRICAL DATA COMPRESSORS . . . . . . . . . . . . 7

OUTDOOR UNIT .................................4

ELECTRICAL DATA FAN MOTORS. . . . . . . . . . . . . . . 7

ACCESSORIES (FACTORY & FIELD INSTALLED ......4

ELECTRICAL DATA, OUTDOOR MCA & MAX.


FUSE SIZE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

ACCESSORIES INDOOR UNIT (FIELD INSTALLED) ....5

OUTDOOR UNIT PHYSICAL DATA . . . . . . . . . . . . . . . 8

GUIDE SPECIFICATIONS .........................24

INDOOR UNIT PHYSICAL DATA . . . . . . . . . . . . . . . . . 8

CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

UNIT CLEARANCES. . . . . . . . . . . . . . . . . . . . . . . . . . . 9

DESCRIPTION ...................................3

INDOOR UNIT ...................................5

LIST OF FIGURES
Fig. #

Pg. #

10 HB CORNER WEIGHTS AND CENTER OF GRAVITY 9

TYPICAL INDOOR UNIT APPLICATIONS . . . . . . . . . . 3

11 PIPING AND ELECTRICAL CONNECTION SIZES . . 10

INDOOR PRODUCT NOMENCLATURE. . . . . . . . . . . . 4

12 REFRIGERANT LINE CHARGE . . . . . . . . . . . . . . . . . 11

INDOOR PRODUCT NOMENCLATURE. . . . . . . . . . . . 5

13 SUCTION LINES . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

VERTICAL ARRANGEMENTS - LB180 AND LB240 . . 6

14 LIQUID LINES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

HORIZONTAL ARRANGEMENTS - LB180


AND LB240 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

15 15 TON CAPACITY TABLE - 85 AND 95 F. . . . . . . . 13

CORNER WEIGHT . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

17 15 TON CAPACITY TABLE - 125 F . . . . . . . . . . . . . . 15

PIPING AND ELECTRICAL CONNECTION


LOCATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

18 20 TON CAPACITY TABLE - 85 AND 95 F. . . . . . . . 16

15 TON BLOWER PERFORMANCE. . . . . . . . . . . . . . 19

20 TON BLOWER PERFORMANCE. . . . . . . . . . . . . . 19

10 HORIZONTAL APPLICATION CORNER WEIGHTS. . 21


11 VERTICAL APPLICATION CORNER WEIGHTS . . . . 21
12 UNIT DIMENSIONS LB180 AND LB240 . . . . . . . . . . . 22
13 LB180 SUPPLY AIR PLENUM DIMENSIONS. . . . . . . 23
14 RETURN AIR GRILLE FOR LB180 DIMENSIONS . . . 23

16 15 TON CAPACITY TABLE - 105 AND 115 F. . . . . . 14

19 20 TON CAPACITY TABLE - 105 & 115 F . . . . . . . . 17


20 20 TON CAPACITY TABLE - 125 F . . . . . . . . . . . . . . 18
21 LB180 15 TON AIRFLOW TABLE. . . . . . . . . . . . . . . . 18
22 LB240 20 TON AIRFLOW TABLE. . . . . . . . . . . . . . . . 18
23

BLOWER DRIVE DATA . . . . . . . . . . . . . . . . . . . . . . . 20

24 BLOWER DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
25 INDOOR ELECTRICAL RATINGS . . . . . . . . . . . . . . . 20
26 INDOOR UNIT WEIGHTS AND CORNER WEIGHTS 21
27 UNIT DIMENSIONS LB180 AND LB240. . . . . . . . . . . 22

Page 74

Unitary Products Group

http://www.rezine.net
036-21323-002-C-0206

DESCRIPTION

APPLICATION FLEXIBILITY INDOOR

Both the outdoor and indoor units are completely piped and
wired at the factory and are shipped ready for immediate
installation. Only the interconnecting liquid and suction lines,
control wiring, and the main power wiring are required to
complete the installation. Every outdoor unit is dehydrated,
evacuated, leak tested and pressure tested at 450 psig
before being pressurized with a holding charge of refrigerant22 for shipment and/or storage.

B L O W E R M O T O R
L O C A T IO N
A IR O U T
(S td . A rra n g e m e n t)
R E T U R N A IR
D U C T F L A N G E
B L O W E R
S E C T IO N

B L O W E R
S E C T IO N

R E T U R N A IR
D U C T F L A N G E

To eliminate the costly cabinet deterioration problems usually


associated with outdoor equipment, all sheet metal parts are
constructed of commercial grade (G90) galvanized steel.
After fabrication, each part is thoroughly cleaned to remove
any grease or dirt from its surfaces. The parts that will be
exposed to the weather are then coated with a desert sand
powder paint to assure a quality finish for many years. This
coating system has passed the 750-hour, salt spray test per
ASTM Standard B117.

APPLICATION FLEXIBILITY OUTDOOR

E V A P O R A T O R
C O IL

A IR
IN

C O IL
S E C T IO N

F IL T E R S
V E R T IC A L
P O S IT IO N

F IL T E R S
H O R IZ O N T A L
P O S IT IO N

A L T E R N A T E A IR
D IS C H A R G E A R R A N G E M E N T S

N O T E : C E R T A IN B L O W E R P O S IT IO N S A R E N O T R E C O M M E N D E D .
B E C A U S E T H E B L O W E R M O T O R S H O U L D N O T B E M O U N T E D
U P S ID E D O W N .

FIGURE 1 - TYPICAL INDOOR UNIT


APPLICATIONS

The outdoor units are lightweight and can be installed on


almost any roof.

The indoor units are built in a single cabinet with one condensate drain pan. These units can be installed in either the vertical or horizontal position for maximum flexibility.

Units can be lifted using nylon straps with hooks at the holes
provided in the base rails, or they may be lifted with a forklift
through the slotted openings in the base rails.

NOTE: On vertical applications, the air velocity across the


indoor coil keeps the condensate from dripping off
the finned surface onto the filters.

A quality appearance and low sound levels make these units


suitable for most ground level locations.

NOTE: On horizontal applications the unit must be installed


with the condensate drain pan under the entire
indoor coil.
NOTE: The Supply Air Plenum and the Return Air Grille
accessories can be used on either arrangement.
NOTE: The Base accessory can only be used on the vertical arrangement.

CONDENSER ONLY CAPACITY


Suction
Model HB Press.&
PSIG F
61.5 35
68.5 40
240
76 45
84 50
61.5 35
68.5 40
180
76 45
84 50

65
MBH
255
275
296
319
191
207
224
241

KW*
17.2
17.6
18.1
18.7
12.7
13.0
13.3
13.7

Temperature ofAir on Condenser Coil, F


75
85
95
105
115
MBH
KW*
MBH
KW*
MBH
KW* MBH KW* MBH KW*
243
18.6
231
20.1
219
21.9 207 23.9 195 26.2
263
19.0
250
20.6
238
22.4 225 24.4 212 26.7
283
19.5
270
21.1
257
22.9 243 24.9 230 27.2
305
20.0
291
21.6
277
23.4 263 25.5 248 27.7
182
13.7
172
14.9
163
16.2 153 17.7 143 19.4
197
14.0
187
15.2
177
16.5 167 18.0 157 19.8
214
14.4
203
15.5
193
16.9 182 18.4 171 20.2
230
14.7
219
15.9
208
17.3 197 18.8 186 20.6

*Power consumption includes outdoor fans and compressors only.

Unitary Products Group

Page 75

http://www.rezine.net
036-21323-002-C-0206

FIGURE 2 - INDOOR PRODUCT NOMENCLATURE


YORK INDOOR PRODUCT NOMENCLATURE
H A 120 C 0 0 A 2 A A A 1 A
Model #

Model Number Description

Options

Product Category

H = Air Conditioner Split System

E = Heat Pump Split System

Product Identifier

A = R-22 Standard Efficiency 2-Pipe


B = R-22 Standard Efficiency 4-Pipe

120

Nominal Cooling
Capacity
MBH

090 = 7-1/2 Ton


120 =10 Ton
150 = 12-1/2 Ton
180 = 15 Ton
240 = 20 Ton

Heat Type

C = Cooling Only

00

Nominal Heating
Capacity

00 = No Heat Installed

Airflow Options

A = Standard Motor

Voltage

2 = 208/230-3-600
4 = 460-3-60

Installation Options

A = None
B = Disconnect

AA

Additional Options

AA = None
AC = Technicoat Coil

Product Generation

1 = 1st Generation

2 = 2nd Generation

Product Style

A = Style A

B = Style B

300 = 25 Ton *
360 = 30 Ton *
480 = 40 Ton *
600 = 50 Ton *

5 = 575-3-60

*NOT AVAILABLE IN HEAT PUMP

OUTDOOR UNIT
Every unit includes 2 heavy-duty scroll compressors, 2 outdoor fan motors with inherent protection, subfusing and a
copper tube/aluminum fin coil.
All controls are located in the front of the unit in the control
box and are readily accessible for maintenance, adjustment
and service. All wiring (power and control) can be made
through the front of the unit.

ACCESSORIES (FACTORY & FIELD


INSTALLED
Factory installed Non-Fused Disconnect for safety and
convenience.
Factory installed Technicoat Condenser Coils for corrosion protection.
Field Installed VFD (Variable Frequency Drive) for Low
Ambient operation down to 0 F.
Field Installed Hot Gas Bypass for low load operation.
Field installed Pump-Out Kit for applications where liquid
slugging could be an issue.

Page 76

Unitary Products Group

http://www.rezine.net
036-21323-002-C-0206

FIGURE 3 - INDOOR PRODUCT NOMENCLATURE


YORK INDOOR PRODUCT NOMENCLATURE
L A 120 C 0 0 A 2 A A A 1 A
Model #

Model Number Description

Options

Product Category

L = Air Handling Unit- Cooling

Product Identifier

A = R-22 Standard Efficiency 2-Pipe


B = R-22 Standard Efficiency 4-Pipe

Nominal Cooling Capacity MBH

090 = 7-1/2 Ton


120=10 Ton
150 = 12-1/2 Ton
180 = 15 Ton
240 = 20 Ton

Heat Type

C = Cooling Only

00

Nominal Heating Capacity

00 = No Heat Installed

Voltage

0 = None
5 = 575-3-60

Factory Options

A = None

AA

Special Options

AA = None

Generation

1 = First Generation

2 = Second Generation

Style

A = Style A

B = Style B

120

INDOOR UNIT
Every unit includes a well-insulated cabinet, copper tube/aluminum fin coil with interlaced circuiting arrangement, 2"
throwaway filters, adjustable TXV
s and centrifugal blowers.
Blower motors and drive kits are ordered separately. Power
wiring for blower motor is field supplied.
The controls include 208/230/460 or 575 volt transformer,
blower motor contactor and relay, and a low voltage terminal
block.
The units are shipped in the vertical position ready for field
installation. For horizontal installation, the blower module can
be repositioned in the field as shown on pages 3 and 6 for
maximum flexibility.

F = Air Handling Unit- Heat Pump

300 = 25 Ton *
360 = 30 Ton *
480 = 40 Ton *
600 = 50 Ton *

6= 208/230-460-3-60

(15 Ton units only) units located in the conditioned space.


Both accessories are finished to match the exterior of the
basic unit, and both can be applied with either vertical or
horizontal units. The supply air plenums are fully insulated
and have double-deflection, adjustable grilles.
Base Sections are available to raise vertical indoor units
above the floor. Outdoor air may be introduced through
these bases by cutting an access opening for the outdoor air duct connection. These bases are finished to
match the exterior of the basic unit. They may have to be
insulated in the field for certain applications.
Suspension Kit is available for indoor units installed horizontally.
Manual and electronic two stage thermostats are available for cooling applications.
Both thermostats have a two-position fan switch, AUTO
and ON to provide intermittent or continuous blower
operation.

ACCESSORIES INDOOR UNIT


(FIELD INSTALLED)
Supply Air Plenums and Return Air Grilles (expanded
metal) accessories are available for free-standing indoor

Unitary Products Group

Page 77

http://www.rezine.net
036-21323-002-C-0206

FIGURE 4 - VERTICAL ARRANGEMENTS - LB180 AND LB240

FIGURE 5 - HORIZONTAL ARRANGEMENTS - LB180 AND LB240


.

CERTAIN BLOWER POSITIONS ARE NOT


RECOMMENDED BECAUSE THE BLOWER
MOTOR SHOULD NOT BE MOUNTED UPSIDE
DOWN.

Page 78

Unitary Products Group

http://www.rezine.net
036-21323-002-C-0206

TABLE 1:UNIT APPLICATION DATA


Application Limitations

Minimum

Voltage Variation (208/230-3-60) - Volts

187

Maximum
253

Voltage Variation (460-3-60) - Volts

414

506

Voltage Variation (575-3-60) - Volts

540

630

Ambient Air on Outdoor Coil (Cooling Cycle) - F

45

115

Ambient Air on Indoor Coil (Cooling Cycle) - F

68

86

TABLE 2:ARI RATINGS - COOLING AND SOUND


Cond.Unit
Sound2

Cooling Capacity1

Model

Rated Airflow

Rated ESP
IWG

Outdoor
Unit

Indoor Unit

MBH

EER

IPLV

dB

CFM

HB180

KB180

180

9.7

10.4

89.0

6000

0.35

HB240

KB240

240

9.7

10.4

90.0

8000

0.40

1. Ratings are in accordance with ARI standard 340/360.


2. Ratings are in accordance with ARI standard 370.

TABLE 3:ELECTRICAL DATA COMPRESSORS


Compressors
Model
Number

System 1

Power
Supply

System 2

RLA

LRA

RLA

LRA

HB180

208/230-3-60

25.6

190.0

25.6

190.0

HB180

460-3-60

12.8

95.0

12.8

95.0

HB180

575-3-60

10.2

75

10.2

75

HB240

208/230-3-60

42.0

239.0

42.0

239.0

HB240

460-3-60

19.2

125.0

19.2

125.0

HB240

575-3-60

13.8

80

13.8

80

TABLE 4:ELECTRICAL DATA FAN MOTORS


Condenser Fans

Model
Number

Power
Supply

FLA
ea.

Qty.

HB180

208/230-3-60

3.7

HB180

460-3-60

1.85

HB180

575-3-60

1.7

HB240

208/230-3-60

5.8

HB240

460-3-60

2.9

HB240

575-3-60

2.2

TABLE 5:ELECTRICAL DATA,OUTDOOR MCA & MAX.FUSE SIZE


Min.Circuit
Ampacity

Max.
Fuse
Size1

Model
Number

Power
Supply

HB180

208/230-3-60

65.1

90

HB180

460-3-60

32.5

45

HB180

575-3-60

26.4

35

HB240

208/230-3-60

106.1

125

HB240

460-3-60

49.0

60

HB240

575-3-60

35.5

45

1. Maximum fuse or maximum circuit breaker (HACR type per NEC).

Unitary Products Group

Page 79

http://www.rezine.net
036-21323-002-C-0206

TABLE 6:OUTDOOR UNIT PHYSICAL DATA


Unit Model
Description
Compressor1

Rating - (Qty) Tons

Fans

HB180

HB240

2 X 7.5 = 15 Tons

2 X 10 = 20 Tons

Quantity

Diameter - inches

24

24

Blades/Pitch ( )
Nominal CFM

3/34

3/32

12,400

11,400

HP

Fan Motors2

RPM
Rows Deep X Rows High

1.5

1140

1100

2 X 30

2 X 30

60

78

Finned Length - inches each slab

Coil

Face Area - square feet (both slabs)

25

32.5

Tube(Copper) OD - inches

3/8

3/8

Fins(Aluminum) per inch

16

16

1 - 0 / 1 - 0 lbs.

1 - 0 / 1 - 0 lbs.

14.0/14.0 lbs.

17.0/17.0 lbs.

Shipping

944

1380

Operating

957

1396

Holding Charge (sys1/sys2)

Refrigerant - 22 (lbs -oz.)


Operating Charge (sys1/sys2)

Unit Weight (lbs)

1. These compressors are fully hermetic.


2. The ball bearing, 56 frame, single phase condenser fan motors have internal protection and are directly connected to the condenser fans. Motor
rotation is counterclockwise when viewing the lead end, which is opposite the shaft end.
3. The amount of charge in the unit as shipped from the factory.
4. Total operating charge for the condensing unit, matching indoor unit, and 25 feet of interconnecting pipe.

TABLE 7:INDOOR UNIT PHYSICAL DATA


Unit Model
Description
LB180

LB240

3 X 32

3 X 40

83

81

Face Area - Square Feet

18.4

22.5

Tube (Copper) OD - Inches

3/8

3/8

Fins (Aluminum) per Inch

13

16

Diameter X Width - Inches

15 X 12 - 2

18 X 18 - 2

Rows Deep X Rows High


Finned length- Inches

Coil

Centrifugal Blower
(Forward Curve - Qty)

HP

Blower Motor1

Field Installed

RPM
Quantity Per Unit

Filters
(Throwaway)

Size - Inches
Total Face Area - Square Feet

Unit Weight (lbs)

--

--

4/4

10

20 X 21 X 2 & 22 X 24 X 2

20 X 25 X2

25.8

34.7

Shipping

720

990

Operating

830

1115

3HP

47

--

5HP

120

120

Motor & Drive

Accessory Operating
Weight (lbs)

Supply Air Plenum

185

N/A

Return Air Grille

25

N/A

Base

140

210

1. Refer to Table 23 and 25 for more information.


8

Page 80

Unitary Products Group

http://www.rezine.net
036-21323-002-C-0206

All dimensions are in inches. They are


subject to change without notice. Certified dimensions will be provided upon
request.

OUTDOOR UNIT DIMENSIONS

Dimensions (In.)
Unit

TABLE 8:CONNECTIONS

15 Ton

37.5

45.75

110.5

20 Ton

37.5

45.75

128.1

TABLE 9:UNIT CLEARANCES

Connection Entry

Location

Connection Size

Overhead

Dimensions

(Top)1

120

15 Ton1

20 Ton1

Front access panels

36

Suction Line

1-1/8 ID

1-3/8 ID

Left Side

30

Liquid Line

5/8 ID

5/8 ID

Right Side

30

Power Wiring

2-1/8 KO

2-1/8 KO

Rear

24

Bottom2

Control Wiring

7/8 KO

7/8 KO
1. Units must be installed outdoors. Overhanging structures or
shrubs should not obstruct condenser air discharge.
2. Adequate snow clearance must be provided if winter operation
is expected.

1. Refer to Tables 13 and 14 for appropriate suction


and liquid line sizes.

TABLE 10:HB CORNER WEIGHTS AND CENTER OF GRAVITY


UNIT SIZE

SHIPPING
WEIGHT

OPERATING
WEIGHT

UNIT
LENGTH

UNIT
WIDTH

DIM X

DIM Y

15 Ton Outdoor

944

959

205

275

275

205

110

46

47

23

20 Ton Outdoor

1124

1141

232

339

339

232

128

46

52

23

D
CG

WIDTH

DIM Y

A
DIM X
LENGTH

FIGURE 6 - CORNER WEIGHT

Unitary Products Group

Page 81

http://www.rezine.net
036-21323-002-C-0206

FIGURE 7 - PIPING AND ELECTRICAL CONNECTION LOCATIONS

TABLE 11:PIPING AND ELECTRICAL CONNECTION SIZES


SIZE

CONNECTION ENTRY

10

SUCTION LINE SYS. #1

1-1/8 ID (15 Ton); 1-3/8 ID (20 Ton)

LIQUID LINE SYS. #1

5/8 ID

SUCTION LINE SYS. #2

1-1/8 ID (15 Ton); 1-3/8 ID (20 Ton)

LIQUID LINE SYS. #2

5/8 ID

POWER WIRING

2 KO

CONTROL WIRING

7/8 KO

Page 82

Unitary Products Group

http://www.rezine.net
036-21323-002-C-0206

REFRIGERANT PIPING
GENERAL GUIDELINES
Many service problems can be avoided by taking adequate
precautions to provide an internally clean and dry system and
by using procedures and materials that conform with established standards.
Use hard drawn copper tubing where no appreciable amount
of bending around pipes or other obstructions is necessary.
Use long radius ells wherever possible with one exception small radius elbows for the traps in all vapor risers. If soft copper is used, care should be taken to avoid sharp bends which
may cause a restriction.
Pack fiber glass insulation and a sealing material such as
permagum around refrigerant lines where they penetrate a
wall to reduce vibration and to retain some flexibility.
Support all refrigerant lines at minimum intervals with suitable
hangers, brackets or clamps.
Insulate all vapor lines with a minimum of 1/2 ARMA-FLEX
or equal. Liquid lines exposed to direct sunlight and/or high
temperatures must also be insulated.
Never solder vapor and liquid lines together. They can be
taped together for convenience and support purposes, but
they must be completely insulated from each other.

3.

Suction line velocity for oil return at part capacity, and

4.

Liquid line pressure drop due to static head.

NOTE: Never base refrigerant line sizes on the OD of the


suction and liquid connections on the unit.
Tables 13 and 14 list friction losses for both the suction and
liquid lines on the system. Table 12 shows the amount of
refrigerant charge required per foot of refrigerant line.
When the evaporator coil is below the condensing unit, the
suction line must be sized for both pressure drop and for oil
return. For certain piping arrangements, different suction line
sizes may have to be used. The velocity of the suction gas
must always be great enough to carry oil back to the compressor.
When the condensing unit is below the evaporator coil, the
liquid line must be designed for the pressure drop due to both
friction loss and vertical rise. If the total pressure drop
exceeds 40 psi, some refrigerant may flash before it reaches
the thermal expansion valve. This flashing will not only cause
erratic valve operation and poor system performance, but
could also damage the expansion valve.

TABLE 12:REFRIGERANT LINE CHARGE1


Refrigerant Line2

Line Size
O.D.(in.)

Refrigerant
Charge (lb./ft.)

LINE SIZING

Liquid

5/8

0.113

When sizing refrigerant lines for a split-system air conditioner,


check the following:

Vapor

1.

Suction line pressure drop due to friction at full capacity,

2.

Liquid line pressure drop due to friction at full capacity,

Unitary Products Group

Page 83

1-1/8
0.013
1-3/8
1. Charges are based on 40 F suction temperature and
105 F liquid temperature.
2. Type L copper tubing.

11

http://www.rezine.net
036-21323-002-C-0206

TABLE 13:SUCTION LINES1 2


Nominal
Capacity
(Tons)

Model Designation

System # 1
HL-15

Rate3(Lbs./
Min.)

7 1/2

Copper Tubing (Inches,


O.D.)

Refrigerant
Gas Velocity
(Ft./Min.)

Friction Loss4

1 1/8

2050

4.3

1 3/8

1680

1.6

1 5/8

1140

0.7

1 1/8

2050

4.3

1 3/8

1680

1.6

1 5/8

1140

0.7

1 1/8

3500

8.0

1 3/8

2280

2.8

1 5/8

1560

1.2

1 1/8

3500

8.0

1 3/8

2280

2.8

1 5/8

1560

1.2

24.6

(PSI/100 Ft.)

4-Pipe System
System # 2

System # 1
HL-20

Refrigerant
Flow

7 1/2

24.6

10

32.5

4-Pipe System
System # 2

10

32.5

1. All horizontal suction lines should be pitched at least 1 inch every 20 feet in the direction of the refrigerant flow to aid the return of
oil to the compressor.
2. Every vertical suction riser greater than 25 feet in height should have a P trap at the bottom to facilitate the return of oil to the
compressor. Use short radius fittings for these traps.
3. Based on Refrigerant-22 at the nominal capacity of the condensing unit, a saturated suction temperature of 45 F and a liquid temperature of 110 F.
4. Although suction lines should be sized for a friction loss equivalent to a 2 F change in saturation temperature (or approximately
3psi), sizing the lines for the proper return of oil is more important.
5. These friction losses do not include any allowances for valves or fittings.

TABLE 14:LIQUID LINES


Model Designation

Nominal
Capacity
(Tons)

Refrigerant

7 1/2

24.6

Flow Rate1
(Lbs./Min.)

Copper
Friction
Tubing
Loss2 3
(Inches,
(PSI/
100 Ft.)
O.D.)
1/2

System # 1
HL-15

11.0

0.5

5/8

3.5

0.5

1/2

11.0

0.5

4-Pipe System
System #2

System #1
HL-20

Vertical
Rise
(PSI/Ft.)

7 1/2

10

24.6

32.5

4-Pipe System
System # 2

10

5/8

3.5

0.5

5/8

5.8

0.5

3/4

2.3

0.5

5/8

5.8

0.5

3/4

2.3

0.5

32.5

1. Based on Refrigerant-22 at the nominal capacity of the condensing unit, a saturated suction temperature of 45 F and a liquid temperature of 110 F.
2. The total pressure drop of the liquid line for both friction and vertical rise must not exceed 40 PSI. If the pressure drop exceeds 40
PSI, the liquid refrigerant could flash before it reaches the expansion valve. This flashing will not only cause erratic valve operation and poor system performance, but could also damage the expansion valve.
3. These friction losses do not include any allowances for a strainer, filter-drier, solenoid valve, isolation valve or fittings.

12

Page 84

Unitary Products Group

http://www.rezine.net
036-21323-002-C-0206

TABLE 15: 15 TON CAPACITY TABLE - 85 AND 95 F


15 Ton Capacity Tables
HB180 Matched with LB180
AIR ON EVAPORATOR

CFM

4500

5250

6000

6750

7500

OUTDOOR AMBIENT TEMPERATURE (F):

85

W.B.

GROSS

INPUT

TEMP

CAP.

POWER

GROSS SENSIBLE CAPACITY (MBh)

(F)

(MBh)

(kW)

86

83

80

77

74

71

68

72

197.8

15.23

117.3

104.5

91.6

78.8

66.0

#N/A

#N/A

67

183.8

14.90

144.8

131.9

119.1

106.3

93.4

80.6

67.8

62

170.5

14.50

168.2

155.4

142.6

129.8

116.9

104.1

91.3

(RETURN AIR DRY BULB TEMP.- (F)

57

173.8

14.43

173.8

171.0

158.2

145.3

132.5

119.7

106.9

72

204.1

15.34

129.7

114.5

99.4

84.2

69.0

#N/A

#N/A

67

189.6

15.01

159.4

144.3

129.1

114.0

98.8

83.6

68.5

62

175.9

14.60

174.8

168.3

154.6

139.4

124.3

109.1

93.9

57

179.3

14.53

179.3

177.9

171.5

156.3

141.2

126.0

110.8

72

210.3

15.44

142.1

124.6

107.1

89.6

72.1

#N/A

#N/A

67

195.4

15.12

174.1

156.6

139.1

121.6

104.1

86.6

69.2

62

181.3

14.70

181.3

181.3

166.6

149.1

131.6

114.1

96.6

57

184.8

14.64

184.8

184.8

184.8

167.3

149.8

132.3

114.8

72

213.6

15.54

152.3

132.4

112.5

92.6

72.6

#N/A

#N/A

67

198.4

15.21

186.0

166.1

146.2

126.3

106.3

86.4

66.5

62

184.0

14.80

184.0

184.0

175.0

155.1

135.2

115.3

95.3

57

187.6

14.73

187.6

187.6

187.6

167.7

147.8

127.8

107.9

72

216.8

15.64

162.6

140.3

117.9

95.6

73.2

#N/A

#N/A

67

201.4

15.31

198.0

175.6

153.3

130.9

108.5

86.2

63.8

62

186.8

14.89

186.8

186.8

183.5

161.1

138.8

116.4

94.1

57

190.5

14.82

190.5

190.5

190.5

168.1

145.7

123.4

101.0

Indicates Nominal Capacity Rating Point.


INPUT POWER INCLUDES THE CONDENSER AND COMPRESSOR MOTORS BUT NOT THE INDOOR BLOWER MOTOR
15 Ton Capacity Tables
HB180 Matched with LB180
AIR ON EVAPORATOR
W.B.
CFM

4500

5250

6000

6750

7500

OUTDOOR AMBIENT TEMPERATURE (F):

95

GROSS

INPUT

GROSS SENSIBLE CAPACITY (MBh)

TEMP

CAP.

POWER

(F)

(MBh)

(kW)

86

83

80

77

74

71

68

72

190.9

16.89

114.1

101.3

88.5

75.7

62.8

#N/A

#N/A
65.2

(RETURN AIR DRY BULB TEMP.- (F)

67

176.8

16.51

142.2

129.4

116.5

103.7

90.9

78.0

62

162.8

16.18

162.8

153.2

140.3

127.5

114.7

101.8

89.0

57

163.2

16.11

163.2

158.1

145.2

132.4

119.6

106.7

93.9

72

196.2

16.99

126.2

111.0

95.8

80.7

65.5

#N/A

#N/A

67

181.7

16.61

156.5

141.4

126.2

111.0

95.9

80.7

65.6

62

167.4

16.27

167.4

162.5

152.0

136.8

121.6

106.5

91.3

57

167.7

16.20

167.7

165.2

157.3

142.1

127.0

111.8

96.6

72

201.5

17.09

138.2

120.7

103.2

85.7

68.2

#N/A

#N/A

67

186.6

16.71

170.9

153.4

135.9

118.4

100.9

83.4

65.9

62

171.9

16.37

171.9

171.9

163.6

146.1

128.6

111.1

93.6

57

172.3

16.30

172.3

172.3

169.3

151.8

134.4

116.9

99.4

72

205.1

17.17

148.4

128.5

108.6

88.6

68.7

#N/A

#N/A

67

190.0

16.79

182.1

162.9

143.0

123.1

103.1

83.2

63.3

62

175.0

16.45

175.0

175.0

170.9

150.9

131.0

111.1

91.2

57

175.4

16.37

175.4

175.4

173.9

154.0

134.1

114.2

94.2

72

208.8

17.25

158.7

136.3

114.0

91.6

69.2

#N/A

#N/A

67

193.4

16.86

193.4

172.4

150.1

127.7

105.4

83.0

60.7

62

178.1

16.52

178.1

178.1

178.1

155.7

133.4

111.0

88.7

57

178.5

16.45

178.5

178.5

178.5

156.2

133.8

111.4

89.1

Indicates Nominal Capacity Rating Point.


INPUT POWER INCLUDES THE CONDENSER AND COMPRESSOR MOTORS BUT NOT THE INDOOR BLOWER MOTOR

Unitary Products Group

Page 85

13

http://www.rezine.net
036-21323-002-C-0206

TABLE 16: 15 TON CAPACITY TABLE - 105 AND 115 F


15 Ton Capacity Tables
HB180 Matched with LB180
AIR ON EVAPORATOR
W.B.
CFM

4500

5250

6000

6750

7500

OUTDOOR AMBIENT TEMPERATURE (F):

GROSS

INPUT

TEMP

CAP.

POWER

(F)

(MBh)

(kW)

72

182.8

18.89

67

168.9

62

156.1

57

105

GROSS SENSIBLE CAPACITY (MBh)


86

(RETURN AIR DRY BULB TEMP.- (F)


83

80

77

74

71

68

111.9

99.1

86.2

73.4

60.6

#N/A

#N/A

18.42

139.2

126.3

113.5

100.7

87.8

75.0

62.2

18.00

156.1

150.4

137.6

124.7

111.9

99.1

86.2

157.8

17.99

157.8

152.5

139.7

126.8

114.0

101.2

88.3

72

187.6

19.03

123.6

108.5

93.3

78.1

63.0

#N/A

#N/A

67

173.4

18.56

153.1

137.9

122.8

107.6

92.4

77.3

62.1

62

160.2

18.13

160.2

157.4

148.8

133.6

118.5

103.3

88.1

57

162.0

18.13

162.0

159.3

151.1

135.9

120.7

105.6

90.4

72

192.4

19.17

135.3

117.8

100.3

82.8

65.3

#N/A

#N/A

67

177.8

18.70

167.0

149.5

132.0

114.6

97.1

79.6

62.1

62

164.3

18.27

164.3

164.3

160.0

142.5

125.0

107.5

90.1

57

166.1

18.26

166.1

166.1

162.5

145.0

127.5

110.0

92.5

72

196.1

19.23

146.1

126.2

106.2

86.3

66.4

#N/A

#N/A

67

181.2

18.76

175.9

159.8

139.8

119.9

100.0

80.1

60.1

62

167.5

18.33

167.5

167.5

165.4

145.4

125.5

105.6

85.7

57

169.3

18.32

169.3

169.3

167.5

147.6

127.7

107.7

87.8

72

199.8

19.30

156.9

134.5

112.2

89.8

67.4

#N/A

#N/A

67

184.7

18.82

184.7

170.0

147.6

125.3

102.9

80.5

58.2

62

170.7

18.39

170.7

170.7

170.7

148.3

126.0

103.6

81.3

57

172.5

18.38

172.5

172.5

172.5

150.2

127.8

105.5

83.1

Indicates Nominal Capacity Rating Point.

INPUT POWER INCLUDES THE CONDENSER AND COMPRESSOR MOTORS BUT NOT THE INDOOR BLOWER MOTOR

15 Ton Capacity Tables


HB180 Matched with LB180
AIR ON EVAPORATOR

CFM

4500

5250

6000

6750

7500

OUTDOOR AMBIENT TEMPERATURE (F):

115

W.B.

GROSS

INPUT

TEMP

CAP.

POWER

GROSS SENSIBLE CAPACITY (MBh)

(F)

(MBh)

(kW)

86

83

80

77

74

71

68

72

174.7

20.88

109.7

96.8

84.0

71.2

58.3

#N/A

#N/A

(RETURN AIR DRY BULB TEMP.- (F)

67

161.0

20.33

136.1

123.3

110.5

97.6

84.8

72.0

59.1

62

149.4

19.81

149.4

147.6

134.8

122.0

109.1

96.3

83.5

57

152.5

19.88

152.5

146.9

134.1

121.2

108.4

95.6

82.8

72

179.0

21.06

121.1

105.9

90.8

75.6

60.4

#N/A

#N/A

67

165.0

20.51

149.7

134.5

119.3

104.2

89.0

73.9

58.7

62

153.1

19.99

153.1

152.2

145.6

130.5

115.3

100.1

85.0

57

156.2

20.05

156.2

153.4

144.8

129.7

114.5

99.4

84.2

72

183.3

21.25

132.5

115.0

97.5

80.0

62.5

#N/A

#N/A

67

168.9

20.69

163.2

145.7

128.2

110.7

93.2

75.7

58.2

62

156.8

20.16

156.8

156.8

156.5

139.0

121.5

104.0

86.5

57

159.9

20.23

159.9

159.9

155.6

138.1

120.6

103.1

85.6

72

187.1

21.30

143.8

123.9

103.9

84.0

64.1

#N/A

#N/A

67

172.4

20.73

169.6

156.6

136.7

116.8

96.8

76.9

57.0

62

160.0

20.21

160.0

160.0

159.9

139.9

120.0

100.1

80.2

57

163.2

20.27

163.2

163.2

161.1

141.2

121.2

101.3

81.4

72

190.9

21.34

155.1

132.7

110.4

88.0

65.7

#N/A

#N/A

67

175.9

20.78

175.9

167.5

145.1

122.8

100.4

78.1

55.7

62

163.3

20.25

163.3

163.3

163.3

140.9

118.5

96.2

73.8

57

166.6

20.32

166.6

166.6

166.6

144.2

121.8

99.5

77.1

Indicates Nominal Capacity Rating Point.

INPUT POWER INCLUDES THE CONDENSER AND COMPRESSOR MOTORS BUT NOT THE INDOOR BLOWER MOTOR

14

Page 86

Unitary Products Group

http://www.rezine.net
036-21323-002-C-0206

TABLE 17: 15 TON CAPACITY TABLE - 125 F


15 Ton Capacity Tables
HB180 Matched with LB180
AIR ON EVAPORATOR
W.B.
CFM

4500

5250

6000

6750

7500

OUTDOOR AMBIENT TEMPERATURE (F):

GROSS

INPUT

TEMP

CAP.

POWER

(F)

(MBh)

(kW)

125

GROSS SENSIBLE CAPACITY (MBh)


(RETURN AIR DRY BULB TEMP.- (F)
86

83

80

77

74

71

68

72

166.6

22.9

107.4

94.6

81.8

68.9

56.1

#N/A

#N/A

67

153.1

22.2

133.1

120.3

107.4

94.6

81.8

68.9

56.1

62

142.7

21.6

142.7

142.7

132.0

119.2

106.4

93.5

80.7

57

147.1

21.8

147.1

141.3

128.5

115.7

102.8

90.0

77.2

72

170.4

23.1

118.5

103.4

88.2

73.1

57.9

#N/A

#N/A

67

156.6

22.5

146.2

131.1

115.9

100.8

85.6

70.4

55.3

62

146.0

21.8

146.0

146.0

142.5

127.3

112.1

97.0

81.8

57

150.4

22.0

150.4

147.6

138.6

123.5

108.3

93.1

78.0

72

174.2

23.3

129.7

112.2

94.7

77.2

59.7

#N/A

#N/A

67

160.1

22.7

159.4

141.9

124.4

106.9

89.4

71.9

54.4

62

149.2

22.1

149.2

149.2

149.2

135.4

117.9

100.4

82.9

57

153.8

22.2

153.8

153.8

148.8

131.3

113.8

96.3

78.8

72

178.0

23.4

141.5

121.5

101.6

81.7

61.8

#N/A

#N/A

67

163.6

22.7

163.3

153.5

133.5

113.6

93.7

73.8

53.8

62

152.5

22.1

152.5

152.5

152.5

134.4

114.5

94.6

74.7

57

157.2

22.2

157.2

157.2

154.7

134.7

114.8

94.9

75.0

72

181.9

23.4

153.3

130.9

108.6

86.2

63.9

#N/A

#N/A

67

167.2

22.7

167.2

165.0

142.7

120.3

98.0

75.6

53.2

62

155.8

22.1

155.8

155.8

155.8

133.5

111.1

88.8

66.4

57

160.6

22.3

160.6

160.6

160.6

138.2

115.9

93.5

71.2

Indicates Nominal Capacity Rating Point.

INPUT POWER INCLUDES THE CONDENSER AND COMPRESSOR MOTORS BUT NOT THE INDOOR BLOWER MOTOR

Unitary Products Group

Page 87

15

http://www.rezine.net
036-21323-002-C-0206

TABLE 18: 20 TON CAPACITY TABLE - 85 AND 95 F


20 Ton Capacity Tables
HB240 & LB240
AIR ON EVAPORATOR
W.B.
CFM

6000

7000

8000

8600

9200

OUTDOOR AMBIENT TEMPERATURE (F):

85

GROSS

INPUT

GROSS SENSIBLE CAPACITY (MBh)

TEMP

CAP.

POWER

(F)

(MBh)

(kW)

86

83

80

77

74

71

68

72

263.4

21.25

155.9

138.8

121.7

104.6

87.5

#N/A

#N/A

(RETURN AIR DRY BULB TEMP.- (F)

67

243.5

20.69

191.0

173.9

156.8

139.7

122.6

105.5

88.4

62

227.6

20.42

221.1

204.0

186.9

169.8

152.7

135.6

118.5

57

219.5

20.19

219.5

216.7

199.6

182.5

165.4

148.3

131.2

72

273.9

21.38

172.8

152.6

132.4

112.2

91.9

#N/A

#N/A

67

253.2

20.82

211.0

190.8

170.6

150.3

130.1

109.9

89.7

62

236.7

20.54

233.4

223.5

203.3

183.1

162.9

142.6

122.4

57

228.2

20.31

228.2

226.8

217.1

196.9

176.7

156.4

136.2

72

284.4

21.51

189.7

166.4

143.0

119.7

96.4

#N/A

#N/A

67

262.9

20.94

231.0

207.6

184.3

161.0

137.6

114.3

91.0

62

245.7

20.67

245.7

243.0

219.7

196.3

173.0

149.7

126.4

57

237.0

20.43

237.0

237.0

234.6

211.3

187.9

164.6

141.3

72

289.0

21.64

197.6

172.2

146.8

121.5

96.1

#N/A

#N/A

67

267.2

21.06

239.9

214.6

189.2

163.8

138.4

113.0

87.7

62

249.7

20.79

249.7

248.3

225.5

200.1

174.7

149.4

124.0

57

240.8

20.55

240.8

240.8

239.6

214.2

188.9

163.5

138.1

72

293.6

21.76

205.5

178.0

150.6

123.2

95.8

#N/A

#N/A

67

271.4

21.19

248.9

221.5

194.1

166.6

139.2

111.8

84.4

62

253.7

20.91

253.7

253.7

231.3

203.9

176.5

149.0

121.6

57

244.6

20.67

244.6

244.6

244.6

217.2

189.8

162.4

134.9

Indicates Nominal Capacity Rating Point.


INPUT POWER INCLUDES THE CONDENSER AND COMPRESSOR MOTORS BUT NOT THE INDOOR BLOWER MOTOR

20 Ton Capacity Tables


HB240 & LB240
AIR ON EVAPORATOR
W.B.
CFM

6000

7000

8000

8600

9200

OUTDOOR AMBIENT TEMPERATURE (F):

95

GROSS

INPUT

GROSS SENSIBLE CAPACITY (MBh)

TEMP

CAP.

POWER

(F)

(MBh)

(kW)

86

83

80

77

74

71

68

72

253.7

23.11

151.3

134.2

117.0

99.9

82.8

#N/A

#N/A

67

237.2

22.68

188.2

171.1

153.9

136.8

119.7

102.6

85.5

62

218.5

22.16

218.5

202.7

185.6

168.5

151.4

134.3

117.2

(RETURN AIR DRY BULB TEMP.- (F)

57

214.5

22.11

214.5

210.5

193.4

176.3

159.1

142.0

124.9

72

262.8

23.30

167.5

147.3

127.1

106.8

86.6

#N/A

#N/A

67

245.7

22.88

207.5

187.3

167.1

146.9

126.7

106.5

86.2

62

226.4

22.35

226.4

218.5

201.5

181.3

161.0

140.8

120.6

57

222.2

22.30

222.2

220.2

209.9

189.7

169.5

149.2

129.0

72

271.9

23.50

183.7

160.4

137.1

113.7

90.4

#N/A

#N/A

67

254.3

23.07

226.9

203.6

180.3

156.9

133.6

110.3

87.0

62

234.2

22.54

234.2

234.2

217.3

194.0

170.7

147.4

124.0

57

229.9

22.49

229.9

229.9

226.4

203.1

179.8

156.4

133.1

72

269.7

23.60

189.5

164.1

138.7

113.3

88.0

#N/A

#N/A

67

252.2

23.16

233.2

207.8

182.4

157.1

131.7

106.3

80.9

62

232.3

22.63

232.3

232.3

220.0

194.6

169.2

143.8

118.5

57

228.0

22.58

228.0

228.0

226.3

200.9

175.5

150.2

124.8

72

267.6

23.69

195.2

167.8

140.4

112.9

85.5

#N/A

#N/A

67

250.2

23.26

239.5

212.0

184.6

157.2

129.8

102.3

74.9

62

230.4

22.72

230.4

230.4

222.6

195.2

167.7

140.3

112.9

57

226.2

22.68

226.2

226.2

226.2

198.7

171.3

143.9

116.5

Indicates Nominal Capacity Rating Point.


INPUT POWER INCLUDES THE CONDENSER AND COMPRESSOR MOTORS BUT NOT THE INDOOR BLOWER MOTOR

16

Page 88

Unitary Products Group

http://www.rezine.net
036-21323-002-C-0206

TABLE 19: 20 TON CAPACITY TABLE - 105 & 115 F


20 Ton Capacity Tables
HB240 & LB240
AIR ON EVAPORATOR
W.B.
CFM

6000

OUTDOOR AMBIENT TEMPERATURE (F):

105

GROSS

INPUT

GROSS SENSIBLE CAPACITY (MBh)

TEMP

CAP.

POWER

(F)

(MBh)

(kW)

86

83

80

77

74

71

68

72

245.6

25.60

148.7

131.6

114.5

97.4

80.2

#N/A

#N/A

67

228.4

25.00

184.5

167.4

150.3

133.2

116.1

99.0

81.9

62

211.9

24.47

211.9

198.0

180.9

163.7

146.6

129.5

112.4

57

210.8

24.50

210.8

204.7

187.6

170.5

153.4

136.3

119.2

67

253.0

25.77

164.4

144.2

124.0

103.7

83.5

#N/A

#N/A

62

235.2

25.16

203.2

183.0

162.8

142.5

122.3

102.1

81.9

57

218.3

24.63

218.3

211.3

195.9

175.7

155.4

135.2

115.0

72

217.1

24.66

217.1

214.1

203.2

183.0

162.8

142.5

122.3

62

260.4

25.94

180.1

156.8

133.5

110.1

86.8

#N/A

#N/A

57

242.1

25.32

221.9

198.6

175.2

151.9

128.6

105.3

81.9

72

224.7

24.79

224.7

224.7

210.9

187.6

164.2

140.9

117.6

67

223.4

24.82

223.4

223.4

218.8

195.4

172.1

148.8

125.5

57

261.9

26.04

188.1

162.7

137.3

112.0

86.6

#N/A

#N/A

72

243.5

25.43

230.7

205.7

180.3

154.9

129.6

104.2

78.8

67

226.0

24.89

226.0

226.0

217.0

191.6

166.2

140.9

115.5

62

224.8

24.92

224.8

224.8

222.4

197.1

171.7

146.3

120.9

(RETURN AIR DRY BULB TEMP.- (F)

72
7000

8000

8600

9200

67

62

57
Indicates Nominal Capacity Rating Point.
INPUT POWER INCLUDES THE CONDENSER AND COMPRESSOR MOTORS BUT NOT THE INDOOR BLOWER MOTOR

20 Ton Capacity Tables


HB240 & LB240
AIR ON EVAPORATOR
W.B.
CFM

6000

7000

8000

8600

9200

OUTDOOR AMBIENT TEMPERATURE (F):

115

GROSS

INPUT

GROSS SENSIBLE CAPACITY (MBh)

TEMP

CAP.

POWER

(F)

(MBh)

(kW)

86

83

80

77

74

71

68

72

237.4

28.09

146.1

129.0

111.9

94.8

77.7

#N/A

#N/A

(RETURN AIR DRY BULB TEMP.- (F)

67

219.5

27.31

180.8

163.7

146.6

129.5

112.4

95.3

78.2

62

205.4

26.78

205.4

193.2

176.1

159.0

141.9

124.8

107.7

57

207.1

26.89

207.1

199.0

181.9

164.8

147.7

130.6

113.4

72

243.1

28.23

161.3

141.1

120.9

100.7

80.4

#N/A

#N/A

67

224.8

27.45

198.9

178.6

158.4

138.2

118.0

97.8

77.5

62

210.3

26.91

210.3

204.2

190.3

170.0

149.8

129.6

109.4

57

212.0

27.02

212.0

208.0

196.5

176.3

156.1

135.8

115.6

72

248.8

28.37

176.5

153.2

129.9

106.5

83.2

#N/A

#N/A

67

230.0

27.58

216.9

193.5

170.2

146.9

123.6

100.2

76.9

62

215.2

27.04

215.2

215.2

204.4

181.1

157.8

134.4

111.1

57

217.0

27.15

217.0

217.0

211.1

187.8

164.5

141.1

117.8

72

254.0

28.49

186.7

161.3

136.0

110.6

85.2

#N/A

#N/A

67

234.8

27.70

228.2

203.6

178.2

152.8

127.4

102.1

76.7

62

219.7

27.15

219.7

219.7

214.0

188.6

163.3

137.9

112.5

57

221.5

27.26

221.5

221.5

218.6

193.2

167.8

142.4

117.1

72

259.2

28.61

196.9

169.5

142.0

114.6

87.2

#N/A

#N/A

67

239.6

27.81

239.6

213.6

186.2

158.7

131.3

103.9

76.5

62

224.1

27.26

224.1

224.1

223.6

196.2

168.7

141.3

113.9

57

226.0

27.38

226.0

226.0

226.0

198.6

171.2

143.8

116.3

Indicates Nominal Capacity Rating Point.


INPUT POWER INCLUDES THE CONDENSER AND COMPRESSOR MOTORS BUT NOT THE INDOOR BLOWER MOTOR

Unitary Products Group

Page 89

17

http://www.rezine.net
036-21323-002-C-0206

TABLE 20: 20 TON CAPACITY TABLE - 125 F


20 Ton Capacity Tables
HB240 & LB240
AIR ON EVAPORATOR

OUTDOOR AMBIENT TEMPERATURE (F):

125

W.B.
GROSS
INPUT
GROSS SENSIBLE CAPACITY (MBh)
TEMP
CAP.
POWER
(RETURN AIR DRY BULB TEMP.- (F)
CFM
(F)
(MBh)
(kW)
86
83
80
77
74
71
72
229.3
30.6
143.5
126.4
109.3
92.2
75.1
#N/A
67
210.7
29.6
177.2
160.1
143.0
125.9
108.8
91.6
62
198.8
29.1
198.8
188.5
171.3
154.2
137.1
120.0
6000
57
203.4
29.3
203.4
193.2
176.1
159.0
141.9
124.8
72
233.3
30.7
158.2
138.0
117.8
97.6
77.3
#N/A
67
214.3
29.7
194.5
174.3
154.1
133.9
113.6
93.4
62
202.2
29.2
202.2
197.1
184.7
164.4
144.2
124.0
7000
57
207.0
29.4
207.0
201.9
189.8
169.6
149.4
129.2
72
237.2
30.8
172.9
149.6
126.3
102.9
79.6
#N/A
67
217.9
29.8
211.8
188.5
165.2
141.8
118.5
95.2
62
205.7
29.3
205.7
205.7
198.0
174.6
151.3
128.0
57
8000
210.5
29.5
210.5
210.5
203.5
180.1
156.8
133.5
72
246.1
30.9
185.3
160.0
134.6
109.2
83.8
#N/A
67
226.1
30.0
225.7
201.4
176.1
150.7
125.3
99.9
62
213.3
29.4
213.3
213.3
211.0
185.6
160.3
134.9
8600
57
218.2
29.6
218.2
218.2
214.7
189.3
164.0
138.6
72
255.0
31.1
197.7
170.3
142.9
115.5
88.0
#N/A
67
234.3
30.1
234.3
214.4
186.9
159.5
132.1
104.7
62
221.0
29.5
221.0
221.0
221.0
196.7
169.2
141.8
9200
57
226.0
29.7
226.0
226.0
226.0
198.5
171.1
143.7
Indicates Nominal Capacity Rating Point.
INPUT POWER INCLUDES THE CONDENSER AND COMPRESSOR MOTORS BUT NOT THE INDOOR BLOWER MOTOR

68
#N/A
74.5
102.9
107.7
#N/A
73.2
103.8
108.9
#N/A
71.9
104.6
110.2
#N/A
74.6
109.5
113.2
#N/A
77.2
114.4
116.3

TABLE 21:LB180 15 TON AIRFLOW TABLE


CFM
4400
4600
4800
5000
5200
5400
5600
5800
6000
6200
6400
6600
6800
7000
7200
7400
7600
7800

RPM

647
654
662
670
679
688
698
708
719
730

0.4 ESP
BHP
kW

1.9
2.0
2.0
2.1
2.2
2.3
2.5
2.6
2.8
3.0

1.78
1.83
1.89
1.97
2.06
2.17
2.3
2.45
2.61
2.78

RPM
660
663
667
671
676
682
688
696
704
712
722
732
742
754
766
779
792
807

0.6 ESP
BHP
1.5
1.6
1.6
1.7
1.7
1.8
1.9
2.0
2.1
2.2
2.3
2.5
2.6
2.8
3.0
3.1
3.3
3.5

kW
1.43
1.46
1.5
1.55
1.61
1.68
1.76
1.85
1.95
2.06
2.18
2.31
2.45
2.6
2.77
2.94
3.12
3.31

RPM
725
733
741
749
758
767
776
785
794
804
814
824
834
844
855
866
877
888

0.8 ESP
BHP
1.8
1.9
2.0
2.1
2.2
2.3
2.4
2.5
2.7
2.8
2.9
3.1
3.2
3.4
3.6
3.8
4.0
4.1

kW
1.69
1.77
1.85
1.94
2.03
2.13
2.24
2.36
2.48
2.61
2.74
2.89
3.03
3.19
3.35
3.52
3.7
3.88

RPM
756
775
794
811
828
844
859
873
885
897
909
919
928
936
944
950
956
960

1 ESP
BHP
2.0
2.1
2.3
2.4
2.6
2.7
2.9
3.0
3.2
3.4
3.5
3.7
3.9
4.1
4.2
4.4
4.6
4.8

kW
1.86
1.99
2.12
2.26
2.39
2.54
2.68
2.83
2.98
3.14
3.29
3.45
3.62
3.79
3.96
4.13
4.31
4.49

RPM
886
891
897
903
910
917
924
931
938
946
954
963
971
980
990
999

1.2 ESP
BHP
2.4
2.6
2.7
2.8
3.0
3.1
3.3
3.4
3.6
3.8
4.0
4.1
4.4
4.6
4.8
5.0

kW
2.29
2.4
2.52
2.64
2.77
2.91
3.05
3.2
3.36
3.53
3.7
3.88
4.07
4.27
4.47
4.68

RPM
928
937
946
955
963
972
981
990
998
1007

1.4 ESP
BHP
2.6
2.8
3.0
3.2
3.4
3.6
3.8
4.0
4.2
4.4

kW
2.4
2.59
2.78
2.98
3.17
3.36
3.56
3.75
3.94
4.14

kW
2.24
2.32
2.40
2.48
2.57
2.66
2.75
2.85
2.95
3.05
3.16
3.26
3.38
3.49
3.61
3.73
3.85
3.98
4.11
4.25

RPM
720
724
727
731
735
739
744
748
753
757
762
767
772
777
783
788
794
800
806
812

1.2 ESP
BHP
2.7
2.9
3.0
3.1
3.2
3.3
3.4
3.6
3.7
3.8
4.0
4.1
4.3
4.4
4.6
4.7
4.9
5.1
5.3
5.4

kW
2.44
2.53
2.63
2.73
2.83
2.94
3.05
3.16
3.28
3.40
3.52
3.65
3.79
3.92
4.06
4.21
4.36
4.51
4.67
4.83

RPM
763
767
771
776
781
786
791
797
803
809
816

1.4 ESP
BHP
3.1
3.2
3.3
3.4
3.6
3.7
3.9
4.1
4.2
4.4
4.6

kW
2.71
2.82
2.94
3.06
3.19
3.32
3.46
3.61
3.76
3.92
4.08

Denotes use of 5 hp motor with high static pulley kit.

Note: Airflow tables based on 2 filters, dry evaporator coil

TABLE 22:LB240 20 TON AIRFLOW TABLE


CFM
6000
6200
6400
6600
6800
7000
7200
7400
7600
7800
8000
8200
8400
8600
8800
9000
9200
9400
9600
9800
10000

RPM

0.4 ESP
BHP
kW

RPM

0.6 ESP
BHP
kW

582
2.0
590
2.1
597
2.3
603
2.4
610
2.5
617
2.7
624
2.8
630
3.0
637
3.1
577
2.0
1.80
643
3.3
584
2.3
2.08
649
3.4
591
2.6
2.34
655
3.6
598
2.9
2.59
661
3.7
605
3.2
2.81
667
3.9
Denotes use of high static pulley option.

1.74
1.87
2.00
2.13
2.26
2.40
2.53
2.66
2.79
2.92
3.06
3.19
3.32
3.46

RPM
612
617
623
629
634
640
646
651
657
662
667
673
678
683
689
694
699
704
709
714
719

0.8 ESP
BHP
2.0
2.1
2.2
2.3
2.4
2.6
2.7
2.8
2.9
3.0
3.2
3.3
3.4
3.5
3.6
3.8
3.9
4.0
4.1
4.3
4.4

kW
1.77
1.87
1.97
2.07
2.17
2.27
2.38
2.48
2.59
2.69
2.80
2.91
3.02
3.13
3.24
3.35
3.46
3.57
3.68
3.80
3.91

RPM
681
684
688
692
695
699
703
707
711
715
719
723
727
731
735
740
744
748
753
757

1 ESP
BHP
2.5
2.6
2.7
2.8
2.9
3.0
3.1
3.2
3.3
3.4
3.6
3.7
3.8
3.9
4.1
4.2
4.3
4.5
4.6
4.8

Note: Airflow tables based on 2 filters, dry evaporator coil


18

Page 90

Unitary Products Group

http://www.rezine.net
036-21323-002-C-0206

15 TON BLOWER PERFORMANCE


1.6
1.4

ESP

1.2
1
0.8
0.6
0.4
4200 4700 5200 5700 6200 6700 7200 7700
CFM
FIGURE 8 - 15 TON BLOWER PERFORMANCE

20 TON BLOWER PERFORMANCE


1.6
1.4

ESP

1.2
1
0.8
0.6
0.4
6000

6500

7000

7500

8000

8500

9000

9500

10000

CFM

FIGURE 9 - 20 TON BLOWER PERFORMANCE

Unitary Products Group

Page 91

19

http://www.rezine.net
036-21323-002-C-0206

TABLE 23: BLOWER DRIVE DATA


Drive Data
Unit Model

LB180
LB240

Model Number

Blower RPM Range

1LD0436

Adj. Motor Pulley

Fixed Blower pulley

Belts

Datum Dia. (In.)

Bore (In.)

Datum Dia. (In.)

Bore (In.)

Qty.

640-810

4.0-5.0

7/8

11

1-3/16

Designation
A57

1LD0437

800-1000

5.3-6.3

1-1/8

11

1-3/16

A55

1LD0438

580-720

4.0-5.0

1-1/8

12

1-3/16

A63

1LD0439

700-830

4.0-5.0

1-1/8

13

1-3/16

A68

TABLE 24:BLOWER DATA


Unit
Model

Blower Motor Data1


HP

Drive Data

Model Number

Frame size

Voltage (3PH-60Hz.)

Model
Number

Blower RPM
Range

2LR04603033

56

208/230/4601

1LD0436

640-810

2LR04603058

56

575

1LD0436

640-810

2LR04605023

184

208

1LD0437

800-1000

2LR04605032

184

230/460

1LD0437

800-1000

1LD0437

800-1000

1LD0439

700-830

1LD0438

580-720

1LD0439

700-830

1LD0438

580-720

1LD0439

700-830

1LD0437

800-1000

1LD0439

700-830

LB180
5
2LP04605058

184

2LR04605023

LB240

184

2LR04605032

575

208

184

2LP04605058

208/230/460

184

575

1. Three-phase motors will always be wired for 460 volt power supply. Refer to the wiring diagram inside the motor terminal box.

TABLE 25:INDOOR ELECTRICAL RATINGS


Model
Number

Blower Motor HP

Power Supply

FLA

Minimum Circuit
Ampacity

Max.Fuse Size1

208-3-60

10.6

13.3

20

230-3-60

9.6

12.0

20

208-3-60

17.5

21.9

35

230-3-60

16.7

20.9

35

460-3-60

4.8

6.0

15

575-3-60

3.6

4.5

15

460-3-60

7.6

9.5

15

5
LB180
3

LB240

575-3-60

5.2

6.5

15

208-3-60

17.5

21.9

35

230-3-60

16.7

20.9

35

460-3-60

7.6

9.5

15

575-3-60

5.2

6.5

15

1. Maximum fuse or maximum circuit breaker (HACR type per NEC).

20

Page 92

Unitary Products Group

http://www.rezine.net
036-21323-002-C-0206

TABLE 26:INDOOR UNIT WEIGHTS AND CORNER WEIGHTS


Unit Size

Position

Shipping
Weight

Operating

Unit
Length

Unit
Width

15 Ton Indoor

Horizontal

720

830

178

216

239

197

89.5

59

15 Ton Indoor

Vertical

720

830

198

224

217

191

89.5

29.5

20 Ton Indoor

Horizontal

990

1115

212

195

340

368

100

74

20 Ton Indoor

Vertical

990

1115

281

254

276

305

100

36.5

NOTE: All dimensions in inches.

C
20 Ton Motor Location

Supply Air

Return Air

15 Ton Motor Location


A

Horizontal Application Corner Weights


FIGURE 10 - HORIZONTAL APPLICATION CORNER WEIGHTS

Supply Air

20 Ton Motor
Location

15 Ton
Motor Location

Return Air

(Rear Corner) D
A
C
B

FIGURE 11 - VERTICAL APPLICATION CORNER WEIGHTS

Unitary Products Group

Page 93

21

http://www.rezine.net
036-21323-002-C-0206

7/8 KNOCKOUTS FOR POWER


AND CONTROL WIRING
AIR
OUT

5/8

AIR
OUT

5/8
L
F

K
J

G
KNOCKOUT
FOR
LIQUID
PIPING

H
C

LESS
BOTTOM
PANEL

BLOWER
SECTION

AIR
IN

KNOCKOUT
D
FOR
SUCTION
PIPING
AIR
IN

KNOCKOUT
FOR
DRAIN
PIPING

EVAPORATOR
COIL SECTION

5/8 Panel
B

LB 240
Piping
Connection
Dimensions

D
5/8 BOTTOM
PANEL

4-9/16

LB 180
Piping
Connection
Dimensions

4-5/8

1-3/4
Knockout
for Liquid
Piping

4.0

16

-3/

1-3/8
Knockout
for Liquid
Piping

10

2-7/32
19-3/32

4-5/8
12-1/4

1-3/4
Hole
for Suction
Piping

5-1/4

1-3/4
Hole
for Suction
Piping

5-25/64
3-1/2

3-1/2
3-3/8
5
3-3/8

FIGURE 12 - UNIT DIMENSIONS LB180 AND LB240

TABLE 27:UNIT DIMENSIONS LB180 AND LB240

22

MODEL

LB180
LB240

89-1/2
100-1/8

85.0
95-5/8

26.0
33-1/4

29-1/2
36-5/8

59
73-1/4

1-7/16
2-1/2

15-7/8
18-7/8

12-7/16
16-1/2

15-13/16
15-13/16

16
21-7/8

16
18

20-3/4
22-9/16

Page 94

Unitary Products Group

http://www.rezine.net
036-21323-002-C-0206

FIGURE 13 - LB180 SUPPLY AIR PLENUM DIMENSIONS1


1. Shipped knocked down for field assembly

FIGURE 14 - RETURN AIR GRILLE FOR LB180 DIMENSIONS

Unitary Products Group

Page 95

23

http://www.rezine.net

GUIDE SPECIFICATIONS
EVAPORATOR - LA300,LB180,240,360,480 & 600

covered by a 1-year limited parts warranty on the complete unit.

EACH UNIT SHALL BE:

EACH UNIT SHALL HAVE:

covered by a 1-year limited parts warranty on the complete unit.

a steel angle frame to provide the rigid support required


for shipping, rigging and years of dependable operation.

In current production with published literature available


to check performance, limitations, specifications, power
requirements, dimensions, operation and appearance,
and equipped with a V-belt drive option that will permit
the blower RPM to be adjusted to meet the exact CFM
requirement of the system.

zinc-coated steel that has been finished by a powder


paint process to provide a long-lasting, quality appearance.
removable panels for easy access to all internal components during maintenance and service.
THE DIMENSIONS OF EACH UNIT SHALL NOT EXCEED
THOSE SPECIFIED IN THE PLANS.

EACH UNIT SHALL HAVE:


a steel angle frame to provide the rigid support required
for shipping, rigging and years of dependable operation;

EACH COMPRESSOR SHALL BE:

exterior panels of 18 gauge steel, finished with baked


enamel to provide a long-lasting quality appearance;

mounted on isolators to minimize the transmission of


vibration.

removable panels to provide easy access to the internal


components for maintenance and service;and,

ALL CONDENSER COILS SHALL BE:


draw thru design.

A filter rack with 2 filters

constructed of copper tubes arranged in staggered rows


and mechanically expanded into aluminum fins.

THE DIMENSIONS OF EACH UNIT SHALL NOT EXCEED


THOSE SPECIFIED.

THE CONDENSER FAN MOTOR(S) SHALL:


THE BLOWER MOTOR SHALL:

be directly connected to the condenser fans.

be mounted within the insulated cabinet t minimize the


transmission of sound to the surrounding space, and

have permanently lubricated ball bearings.


have inherent overload protection.

Have a service factor of 1.15.

be three phase.

THE EVAPORATOR COIL SHALL:

be arranged for vertical discharge of the condenser air.

Consist of copper tubes arranged in staggered rows,


mechanically expanded into aluminum fins, be drawthrough, and

THE WIRING FOR EACH UNIT SHALL INCLUDE:


a crankcase heater (one per compressor).

include factory-mounted distributors, expansion valves


and solenoid valves for both capacity reduction and
pump down.

all 24-volt temperature control circuit.


both high and low pressure cutouts.

THE BLOWER WHEELS SHALL BE:

Solid-state or internal line break compressor motor protection.

Dynamically balanced to minimize the levels of sound and


vibration generated by the unit.

Condenser fan motor control to assure stable operation


at ambient temperature down to 40 F.
THE REFRIGERANT PIPING OF EACH SYSTEM SHALL
INCLUDE:

CONDENSER - LA300,LB180,240,360,480 & 600


EACH UNIT SHALL BE:

a filter-drier shipped separately for field installation.

ETL and cETL approved.

a liquid line, moisture-indicating, sight glass shipped


separately for field installation.

completely assembled for one-piece shipping and rigging.

liquid line and suction line valve shipped separately for


field installation.

leak pressure and functionally tested at the factory to


assure a trouble-free start-up after installation.
Subject to change without notice. Printed in U.S.A.
Copyright 2006 by Unitary Products Group. All rights reserved.
Unitary
Products
Group

5005
York
Drive

Page 96

036-21323-002-C-0206
Supersedes: 036-21323-002-B-0804
Norman
OK
73069

http://www.rezine.net

Page 97

http://www.rezine.net

Page 98

http://www.rezine.net

Controls
HVAC control just became a
whole lot smarter and easier!

Only York offers the easiest


solution to help you
take control of controls.

C
O
N
T
R
O
L

COMFORT
ONLINE ALARMING
NO HASSLE SET-UP

TOTAL HVAC
CONTROL SOLUTIONS

More control for more savings

More compatibility for more flexibility

Cut energy costs, and achieve higher levels of comfort


automatically with Simplicity Intelli-Comfort controls.

The controls are compatible with the MODBUS protocol,


and are factory-installed on 3- to 25-ton Sunline and
Predator products and Millennium HA/HB Systems.

More intelligence for more capabilities


Intelli-Comfort controls use intelligent hardware and
software to give you better monitoring, more flexibility in
control set-up, and finer control of every aspect of your
HVAC system. In addition, the more intelligent the control,
the greater savings you will realize through operational
efficiencies and conservation.

More power with less effort


Intelli-Comfort is a control thats so easy to use that
you actually benefit from the power at your fingertips.

Easier to manage
Intelli-Comfort raises the intelligence of an already
smart Simplicity control.

More control for greater comfort


The flexibility of the Simplicity Intelli-Comfort control
means comfortable, happier, and more productive
occupantsthanks to the ability to optimize temperature,
humidity, and indoor air quality simultaneously.

Put the intelligence of Simplicity Intelli-Comfort controls


to work in your building.
Simplicity Intelli-Comfort controls give you powerful capabilities without complexity. Easy to set-up, program, and use, the controls give you
everything you need to monitor and control Sunline and Predator units. And because they can be connected as your HVAC Energy
Management System you can save even more by making the intelligence of Simplicity Intelli-Comfort part of your building automation strategy.

RELIABILITY
OPEN PROTOCOL
LOW COST

New features for superior


monitoring and control
365-Day Real Time Clock with
automatic Daylight Savings Time adjustment
Occupancy Schedule allowing two different occupied
schedules per day for each of the seven days of the week
20 Holiday Schedules with a length of up to 99 days, each
with flexible start times. You can now choose the time of day
your holiday begins saving energy

Patent Pending Temperature Humidity Algorithm offsets


the operating setpoint based on high humidity in the spacewith
programmable limits to control humidity

Energy-Saving Economizer Operation with the flexibility


of using dry bulb, outside enthalpy and differential enthalpy.
Our economizer enthalpy control has setpoints for outside air
temperature, supply air temperature, small space cooling demand,
and large space cooling demand

High and Low Ambient Lockout to lockout cooling below or


heating above a programmable setpoint of outside air temperature

Outside Air CO2 Sensor to close the economizer if CO2 is present


Inside Demand Ventilation using one CO2 sensor or differential
demand ventilation using inside and outside CO2 sensors
IAQ Operation with programmable maximum outside air
damper position

Space Temperature Alarm when temperatures are outside


of program setpoints. Alarm setpoints are user programmable
Unit Monitors Airflow to detect dirty filters and insufficient airflow
Intelligent Recovery brings the space temperature to the
occupied setpoint just before or at the beginning of the first
occupied schedule each day. The control will learn and apply
the minimum runtime required to heat or cool the space to
minimize energy use

Comfort Ventilation Control tempers the ventilation air


when heating or cooling is not required, increasing comfort

2004 York International Corporation.


All rights reserved. Subject to change without notice.
Form 036-12054-001 (0105). Supersedes: Nothing. Printed in USA.

Page 99

http://www.rezine.net

Page 100

http://www.rezine.net

COMMERCIAL ZONING PACKAGE

The Facility Explorer Commercial Zoning Package is a complete, turnkey control system used to improve
occupant comfort in a building (or section of a building) that is conditioned with a packaged rooftop HVAC unit.
It accomplishes this by varying the amount of conditioned air delivered to individual zones and by intelligently
cycling the rooftop units heating and cooling stages to best satisfy all the zone demands.

Manufacturer Independent
The Facility Explorer Commercial Zoning
Package is designed to work with any
standard, packaged HVAC equipment, regardless
of manufacturer. This allows you to apply this control
package to equipment provided by a variety of
suppliers or to equipment that has already been
installed. This flexibility makes the Facility Explorer
Commercial Zoning Package perfectly suited for both
new and retrofit installations.
Affordable Intelligence
The Facility Explorer Commercial Zoning Package
utilizes the distributed application architecture of
the FX16 Master Controller. This feature allows direct
communications to occur between the FX16 and all
the zone controllers. This means that there is no
need for a traditional supervisory class controller to
manage the data sharing. This direct communication
flow allows the FX16 to monitor each zones status to
intelligently determine the proper mode of operation
for the rooftop unit.

Page 101

http://www.rezine.net

COMMERCIAL ZONING PACKAGE

Easy Installation
Several pieces of the Facility Explorer Commercial
Zoning Package can be ordered pre-assembled from
the factory to simplify installation:

Bypass Damper and Actuator Assembly

Zone Controller and Actuator Assembly (FXZAN)

FX16 Master Controller with Pre-Downloaded


Zoning Application

The FX05 Field Controller is combined with an


M9104AGA non-spring return actuator and an
electrical termination wiring block, all in one
packaged assembly

FX16 Master Controller can be ordered with the


commercial zoning application pre-downloaded

Perfect for retrofit installations where the zone


damper is already installed
Zone Controller, Actuator, and Damper Assembly
FXZAN Zone Controller and Actuator Assembly is
combined with a round or rectangular zone damper
Perfect for new installations or for retrofit
installations where the zone damper has not yet
been installed

2005 Johnson Controls, Inc.

A round or rectangular bypass damper is combined


with an M910xHGA non-spring return actuator

Once installed, the FX16 takes care of downloading


the corresponding parts of the zoning application to
each of the zone controllers
Eliminates the downloading steps from the field
installation and startup
This provides the possibility (with an onsite Medium
User Interface) to download, configure and
commission the entire system, including the
rooftop, bypass, and all zone controllers without
any software tool

P.O. Box 423, Milwaukee, WI 53201

Page 102

Printed in USA PUBL-3894

http://www.rezine.net

Page 103

http://www.rezine.net

TSS Single Duct Variable Air Volume Terminal

An integrated VAV box with direct digital controls

TSS Terminals provide Variable Air Volume (VAV) control

eliminates the coordination and difficulties

beyond the typical single duct box. They are specifically

associated with factory mounting

designed for precise air delivery throughout the entire


operating range, regardless of the installed inlet conditions.

Downloading of software, setting of parameters,

These units can be ordered with or without a Direct Digital

addressing and testing at the factory reduces

Controller (DDC), which can operate as a stand-alone unit,

startup time and lowers risk

on a Johnson Controls N2 trunk, or on a LON trunk.

Superior flow measuring provides for lower

TSS Terminals take advantage of typical benefits provided

minimum cubic feet per minute (CFM) values,

by single duct units, while performing at extremely low

which reduces energy costs and noise while

sound levels. This is critical in todays buildings where

maintaining comforts in the zone

occupants are placing more emphasis on indoor acoustics.


The TSS Terminal is manufactured and assembled with a

Installation time can be reduced with the low

multi-point, center-averaging airflow sensor, which

profile compact design and standard metal

provides a signal to the controller enabling it to quietly and

hanging straps

precisely measure airflow.

Units wired in compliance with all applicable

Bundled with the TSS Terminal is a digital controller from

National Electrical Code (NEC) requirements and

the VAV Modular Assembly (VMA) Series or the LN Series.

tested in accordance with Air Conditioning and

Each model in the VMA1400 Series and the LN Series

Refrigeration Institute (ARI) standard 880

combines a controller, pressure sensor, and actuator


housed in one pre-assembled unit.

Offers damper stall detection, starved box


detection, actuator motor duty cycle, VAV box
flow test, and other diagnostics on most
models (VMA Series)

Page 104

http://www.rezine.net

TSS Single Duct Variable Air Volume Terminal

Standard Features

Optional Features

Construction

Construction

ARI 880 certified and labeled

20-gauge galvanized steel construction

22-gauge galvanized steel casing and valve

3/4 or 1 fiberglass insulation

G90 galvanized steel

Scrim-reinforced, foil-faced insulation meeting American


Society for Testing and Materials (ASTM) C1136 for mold,
mildew, and humidity resistance

1/2, 4lb/ft3 skin, dual density fiberglass insulation, glued


and clinch-pinned in place

1/2 Elastomeric closed-cell foam insulation

Hot Water Coils

Double wall construction with 22-gauge liner

ARI 410 certified and labeled

Mounting brackets to accept all-thread hanging rods or


wire hangers

1-, 2-, 3-, 4-row coils


Tested at a minimum of 350 psig under water

Low temperature construction for use in thermal storage


applications, including a thermally isolated primary air
inlet and a composite damper shaft

Mechanically expanded copper tubes leak tested


to 350 psig air pressure
Male sweat type water connections

Hot Water Coils


Low pressure steam coils

Primary Air Valve


Embossed rigidity rings

Multi-circuit coils for reduced water pressure drop

Low-thermal conducting damper shaft with


position indicator

Opposite hand water connections


Bottom and top access plates for cleaning

Mechanical stops for open and closed position

Electrical Components

Multi-point center-averaging airflow sensor

Full unit toggle disconnect and inline motor fusing

Brass balancing tees

Primary and secondary transformer fusing

Plenum-rated sensor tubing

Electric Heat

Electrical Components

Proportional solid state relay (SSR) heater control

cETL listed for safety compliance

Mercury contactors

National Electrical Manufacturers Association (NEMA)


Type 1 wiring enclosure

Door interlocking disconnect switches


Disconnect (toggle or door interlocking)

Electric Heat
ETL listed as an assembly for safety compliance
Integral electric heat assembly
Automatic reset primary and back-up secondary
thermal limits

Pneumatic Electric (PE) switches


Mercury and magnetic contactors
Manual reset secondary limit
24 volt control transformer

Single-point power connection

Special watt densities

Hinged electrical enclosure

Finned tubular elements

Fusing per NEC

Controls

Airflow switch

Factory-provided controls

Ni-chrome elements

Direct digital controls (DDC) for N2 or LON networks

Primary/Secondary power terminations

Pneumatic controls

Wiring diagram

2005 Johnson Controls, Inc.

P.O. Box 423, Milwaukee, WI 53201


www.johnsoncontrols.com

Page 105

Printed in USA PUBL-3888

http://www.rezine.net

TSL Single Duct Low Height Variable Air Volume Terminal

An integrated VAV box with direct digital controls

TSL Terminals provide variable air volume (VAV) control

eliminates the coordination and difficulties

beyond the typical single duct box. They are specifically

associated with factory mounting

designed for precise air delivery throughout the entire


operating range and are only 10 in height, making them

Downloading of software, setting of parameters,

ideal for shallow or congested ceiling plenum applications.

addressing and testing at the factory reduces

These units can be ordered with or without a Direct Digital

startup time and lowers risk

Controller (DDC), which can operate as a stand-alone unit,


on a Johnson Controls N2 trunk, or on a LON trunk.

Superior flow measuring provides for lower


minimum cubic feet per minute (CFM) values,

TSL Terminals take advantage of typical benefits provided

which reduces energy costs and noise while

by single duct units, while performing at extremely low

maintaining comforts in the zone

sound levels. This is critical in todays buildings where


occupants are placing more emphasis on indoor acoustics.

Installation time can be reduced with the low

The TSS Terminal is manufactured and assembled with

profile compact design and standard metal

a multi-point, center-averaging airflow sensor, which

hanging straps

provides a signal to the controller enabling it to quietly and


precisely measure airflow.

Units wired in compliance with all applicable


National Electrical Code (NEC) requirements and

Bundled with the TSL Terminal is a digital controller from

tested in accordance with Air Conditioning and

the VAV Modular Assembly (VMA) Series or the LN Series.

Refrigeration Institute (ARI) standard 880

Each model in the VMA1400 Series and the LN Series


combines a controller, pressure sensor, and actuator
housed in one pre-assembled unit.

Page 106

TSL Single Duct Low Height Variable Air Volume Terminal

http://www.rezine.net

Secondary high limit

Standard Features

Airflow switch

Construction
ARI 880 certified and labeled

Single-point power connection

20-gauge, galvanized steel casing and valve

Hinged electrical enclosure door

G90 galvanized steel construction

Fusing per NEC

1/2", 4 lb/ft3 skin, dual density fiberglass insulation glued


and clinch pinned

Optional Features

Invertible unit facilitates control installation on the left- or


right-hand side

Construction

Hot Water Coils


ARI 410 certified and labeled

Scrim-reinforced, foil-faced insulation meeting American


Society for Testing and Materials (ASTM) C1136 for mold,
mildew, and humidity resistance

1-, 2-, 3-, 4-row coils

1/2 Elastomeric closed-cell foam insulation

Left- or right-hand connections

Double wall construction with a 22-gauge liner

Tested at a minimum of 450 psig under water and rated


at 300 psig working pressure at 200F

Mounting brackets to accept all thread hanging rods or


wire hangers

Aluminum fin construction with die-formed spacer collars


for uniform spacing

Discharge sound attenuator (Model TSL-SA)

Mechanically expanded copper tubes leak tested to 450


psig air pressure and rated at 300 psig working pressure
at 200F

Coil access plate for cleaning coil

Hot Water Coil


Coil circuiting options for reduced water pressure drop
Right- or left-hand water connections

Male sweat type water connections

Bottom and top access plates for cleaning

Primary Air Valve


18-gauge, G90 galvanized steel construction

Steam coils

Low thermal conductance damper shaft

Electrical Components

Position indicator on external end of damper shaft

Toggle disconnect switch

Mechanical stops for open and closed position

Primary and secondary transformer fusing

Multi-point center-averaging airflow sensor

Electric Heat

Brass balancing tees

Proportional solid state relay (SSR) heater control

Plenum-rated sensor tubing

Mercury contactors (if equipped with a mercury contactor,


the unit cannot be inverted)

Electrical Components

Door interlocking disconnect switches

cETL listed for safety compliance with Underwriters


Laboratories Inc. (UL) 1995

Disconnect (toggle or door interlocking)

National Electrical Manufacturers Association (NEMA)


Type 1 wiring enclosure

Pneumatic Electric (PE) switches

Electric Heat

Manual reset secondary limit

Invertible unit facilitates control installation on the left- or


right-hand side (not applicable if equipped with a
mercury contactor)

Controls

cETL listed as an assembly for safety compliance

Direct Digital Controls (DDC), for N2 or LON networks

Automatic reset primary and back-up secondary


thermal limits

Pneumatic controls

Mercury and magnetic contactors

Factory-provided controls

Primary auto-reset high limit

2005 Johnson Controls, Inc.

P.O. Box 423, Milwaukee, WI 53201


www.johnsoncontrols.com

Page 107

Printed in USA PUBL-3882

http://www.rezine.net

Single Duct Variable Air Volume Terminal (Model TSS)


Unit
Size
6
8
10
12
14
16
22

CFM
200
400
600
800
1100
1500
3000

Bypass
CFM
300
600
900
1200
1800
2200
5400

Dimensions
Weight
18
20
25
30
38
42
72

WxHxL
10 x 10" x 11"
12 x 10 x 11"
14 x 12.5" x 13
16 x 15" x 13
20 x 17.5" x 17.5"
24 x 17.5" x 17.5"
34 x 17.5" x 11"

A
6 1/2
6 1/2
6 1/2
6 1/2
6 1/2
6 1/2
8

I
5 7/8
7 7/8
9 7/8
11 7/8
13 7/8
15 7/8
32 1/4 x 15 7/8

X
8 3/4
10 3/4
12 3/4
14 3/4
18 3/4
22 3/4
32 3/4

Y
8 3/4
8 3/4
11 1/4
13 3/4
16 1/4
16 1/4
16 1/4

Note: All dimensions are in inches with a tolerance of +1/8. Size 22 has a rectangular inlet collar. CFM based on
1000 FPM (Bypass 1500 FPM) for low to medium pressure applications.

Clearance 24"

Page 108

http://www.rezine.net

Single Duct Variable Air Volume Terminal - Rectangular (Model TSL)

Dimensions
Unit
Bypass
Size
CFM
CFM
A
W
L
X
Weight
10
600
1200
10
15
12 1/2
13 3/4
26
12
800
1600
14
19
12 1/2
17 3/4
28
14
1200
2200
20
25
16 1/2
23 3/4
39
16
1500
3000
26
31
16 1/2
29 3/4
45
Notes: 1. For dimensional data for unit sizes 6 and 8, refer to the Single Duct Variable
Air Volume Terminal (Model TSS). All dimensions are in inches with a tolerance of +1/8.
Weights are in pounds. Weights are for the basic unit with the indicated option and
control enclosure. Actual weight varies based on project-specific requirements for unit
options, appurtenances, and controls. 2. Control enclosure is standard with factorymounted electronic controls. 3. Check all national and local codes for required
clearances.

Page 109

http://www.rezine.net

Page 110

http://www.rezine.net

Model DE Series
UVC Emitters

UVC for HVAC

TM

power needed to maintain microbial control. The UVC


Emitter, by contrast, has a 12-month service life and even
after a full year, it has 2-1/2 times greater output than
competitive devices deliver on Day 1! As a result, only SterilAire can ensure the germicidal performance you need, with no
return of microbial growth, for 3-4 times longer than the
competition.

Double-Ended, Very High


Output Germicidal Light
Source for HVAC Systems

Applications
Steril-Aire Double-Ended (DE Series) fixtures are used
for internal installation in medium to large air handling
systems in commercial, industrial, health care and institutional
buildings. They may be mounted singly, in built-up banks or in
parallel configurations in a variety of locations, including
coils, drain pans, ductwork, mixed air plenums and exhaust
systems. The DE Series is available in five lengths (18, 24,
30, 36 and 42) and four voltage options (115, 208, 230 or
277 Vac), providing installation flexibility to accommodate
virtually any system.

Benefits
Kills or inactivates surface and airborne microorganisms that
contribute to poor IAQ and/or the spread of infectious disease,
including: mold and mold spores, bacteria (including TB,
Legionella, E. coli, Listeria, salmonella, and whooping
cough); and viruses (including colds, flu, measles).
Delivers an average of 5 times the output of competitive UVC
products at HVAC operating temperatures, for 3-4 times
longer life and more reliable germicidal control.
Uses patented state-of-the-art solid-state electronic power
supply for enhanced reliability and performance.
Continuously cleans coils, drain pans, plenums and ducts,
eliminating costly cleaning programs and the use of harmful
chemicals and disinfectants.
Lowers HVAC energy costs by restoring heat transfer and net
cooling capacity.
Steril-Aires multi-patented UVC Emitter provides the
best and longest-lasting UVC performance available. As
shown in the comparison graph (above), it has been
independently tested to deliver an average of 5 times the
output of other ultraviolet devices under HVAC operating
conditions (45o F @ 550 fpm air velocity).
Competitive UVC lights must be changed every 3-4
months because they quickly lose the output or killing

Produces no ozone or other secondary contaminants will not


harm building occupants, equipment or furnishings.
Offers lowest life-cycle cost of any UVC product. Return on
investment is often less than one year.
The most widely used product for commercial UVC for
HVAC the industry standard!

Page 111

http://www.rezine.net

Model DE Specifications
The UVC EmitterTM and fixture shall be factory assembled and
tested. They shall consist of a housing, power source, reflector,
Emitter sockets and Emitter.

be available in 115-208/230 or 277 Vac, 50/60 Hertz, and single phase.


The Emitter soc kets are medium bi-pin, double click safety, twist
lock type. They shall be constructed of UVC-resistant polycarbonate.

The housing shall be constructed of 304 stainless steel to withstand


HVAC environments. The reflector shall be constructed of heavy
gauge, specular finished aluminum alloy with approximately 85%
reflectance at 254 nm wavelength. The housing shall be equipped
with 1/2" electrical conduit openings on each end to facilitate
coupling and wiring fixture-to-fixture and to power. All components
shall be in one integral assembly to maximize serviceability.
The power source shall be a Class P2, electronic, rapid start type
with a power factor greater than 0.95 and a power conversion of
greater than 75%. The power supply design shall include RF and EMI
suppression. The power supply shall be designed to maximize photon
production, irradiance and reliability in cold or moving airstreams of
35-170 F, 100% RH and up to 2000 fpm velocity. The fixture shall

The Emitter tube shall be a very high output, hot cathode, T5


diameter, medium bi-pin type that produces broadband UVC of 250260 nm. Each tube shall produce the specified output at 2000 fpm
velocity and air temperatures of 35-170 F. It shall produce no ozone
or other secondary contaminants.
Inde pendent testing: The unit shall be tested by an independent test
laboratory in accordance with the general provisions of IES Lighting
Handbook, 1981 Applications Volume, and shall be verified through
independent testing to provide output per 1" arc length of not less
than 10 W/cm2 at 1 meter in a 400 fpm airstream of 45 F.
Unit shall comply with UL Standard 1995 for use in HVAC
equipment and shall carry the "UL" and "ULC" labels.

This product may be covered by one or more of the following patents, others pending: 5,334,347/ 5,866,076/ 5,817,276/ 6,372,186/ 6,313,470/ 6,245,293/
6,267,924/ 6,280,686/ 6,423,882.

Ordering Information
Model No.

Part No.

Description

Length

DE 181 VO
DE 181 VO
DE 241 VO
DE 241 VO
DE 301 VO
DE 301 VO
DE 361 VO
DE 361 VO
DE 421 VO
DE 421 VO
GTD 16 VO
GTD 22 VO
GTD 28 VO
GTD 34 VO
GTD 40 VO

10001500
10002100
10001600
10002200
10001700
10002300
10001800
10002400
10001300
10002500
20000100
20000200
20000300
20000400
20000500

Double-Ended Fixture
Double-Ended Fixture
Double-Ended Fixture
Double-Ended Fixture
Double-Ended Fixture
Double-Ended Fixture
Double-Ended Fixture
Double-Ended Fixture
Double-Ended Fixture
Double-Ended Fixture
Replacement Emitter DE 181
Replacement Emitter DE 241
Replacement Emitter DE 301
Replacement Emitter DE 361
Replacement Emitter DE 421

18"
18"
24"
24"
30"
30"
36"
36"
42"
42"
16"
22"
28"
34"
40"

Electrical
115, 208, 230V: 70-85 watts
277V: 70-85 watts
115, 208, 230V: 70-85 watts
277V: 70-85 watts
115, 208, 230V: 70-85 watts
277V: 70-85 watts
115, 208, 230V: 70-85 watts
277V: 70-85 watts
115, 208, 230V: 70-85 watts
277V: 70-85 watts
N/A
N/A
N/A
N/A
N/A

Weight
2.3 lb.
2.3 lb.
2.7 lb.
2.7 lb.
3.3 lb.
3.3 lb.
3.7 lb.
3.7 lb.
4.1 lb.
4.1 lb.
0.15 lb.
0.15 lb.
0.20 lb.
0.25 lb.
0.25 lb.

Complies with current U.S. and Canadian UL Standards for


use in HVAC equipment.

Represented By:

Steril-Aire, Inc.
Corporate Office:
2840 N. Lima Street
Burbank, CA 91504
Telephone: 818-565-1128
Fax: 818-565-1129
Website: www.steril-aire.com
Email: sales@steril-aire.com
2003 Steril-Aire

1100-07/05

Page 112

http://www.rezine.net

036-21328-003-D-0206

DESCRIPTION
These units are completely assembled, piped and wired at the factory
to provide one-piece shipment and rigging. Each unit is pressurized
with a holding charge of Refrigerant-22 for storage and/or shipping.
The compact design, clean styling, low silhouette, and quiet operation
make these condensing units suitable for almost any outdoor location.
On rooftops . . . because they weigh much less than a single package
unit of similar capacity and are much easier to rig and support. At
ground level . . . because their ample sub-cooling capacity allows them
to be located three or more stories below the evaporator coil.

TECHNICAL GUIDE
SPLIT-SYSTEM
AIR-COOLED CONDENSING UNITS
HA300,HB360,HB480 & HB600
25 THRU 50 NOMINAL TONS

Every condenser coil is pressurized with air to 325 psig and leak
tested under water. After assembly, the unit is pressurized with a combination of Refrigerant-22 and nitrogen to 450 psig for pressure testing
and additional leak testing. During this pressure test, the operation of
the high pressure control is checked. As the unit is being evacuated
and dehydrated, the operation of the low pressure control is checked.
Every compressor, condenser fan motor, crankcase heater, and electrical control circuit is checked to assure a trouble-free start-up and
years of reliable operation.
The condenser fan guards are vinyl-coated to provide additional rust
protection and to enhance the appearance of the unit.
Compressors are mounted on rubber isolators to reduce the transmission of vibration. Vertical discharge condenser fans direct sound
upward and away from any surrounding structures.
All sheet metal parts are constructed of commercial grade (G90) galvanized steel. After fabrication, each part is thoroughly cleaned to
remove any grease or dirt from its surfaces. The external parts are
coated with a powder paint to assure a quality finish for many years.
This UL approved coating system has passed the 1000 hour, 20% salt
spray test per ASTM Standard B117.
All models include a 1-year limited warranty on the complete unit. An
additional 4-year extended compressor warranty is available as an
option on all models.
A matching line of Evaporator Blower units is also offered to meet your
precise capacity and air handling requirements.

FEATURES
Meets or exceeds ASHRAE 90.1 standards.
Scroll compressors provide both high efficiency and reliability.
Simplicity Controls
Dual refrigerant circuits on HB models.
ISO 9001
Certified Quality
Management System

Condenser coils are constructed of copper tubes and aluminum


fins for durability and long lasting efficient operation.
Crankcase heaters that will be de-energized when the compressor is operating.
Both high and low pressure controls. Since these controls are
self-contained, there are no capillary lines to be damaged.
Solid state or internal line break compressor motor protection.
Class 2, 24-volt thermostat control circuit.

Page 113

http://www.rezine.net
036-21328-003-D-0206

TABLE OF CONTENTS
DESCRIPTION ...................................1

LIST OF TABLES

FEATURES......................................1

Tbl. #

PRODUCT NOMENCLATURE.......................4

RATINGS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

PHYSICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

UNIT APPLICATION DATA. . . . . . . . . . . . . . . . . . . . . . 5

ELECTRICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

UNIT COOLING CAPACITIES AND POWER


REQUIREMENTS - CONDENSING UNIT ONLY . . . . . 6

SUCTION LINES. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

LIQUID LINES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

LIST OF FIGURES
Fig. #

Pg. #

TYPICAL FIELD WIRING FOR HA300 & LA300 . . . . . 15

TYPICAL FIELD WIRING FOR HB360, 480, 600 &


LB360, 480, 600 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

FAN ORIENTATION CONTROL BOX END . . . . . . . . 16

CORNER WEIGHTS & CENTER OF GRAVITY . . . . . 17

HA/HB UNIT DIMENSIONS. . . . . . . . . . . . . . . . . . . . . 18

25 TON PIPING CONNECTIONS . . . . . . . . . . . . . . . . 19

30 & 40 TON PIPING CONNECTIONS . . . . . . . . . . . . 20

50 TON PIPING CONNECTIONS . . . . . . . . . . . . . . . . 20

25, 30 & 40 TON POWER AND CONTROL


WIRING CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . 21

10 50 TON POWER AND CONTROL WIRING


CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
11 TYPICAL LIQUID LINE SOLENOID WIRING . . . . . . . 22

Pg. #

R-22 LINE CHARGE . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

COOLING CAPACITY 25 TON UNIT - HA300


CONDENSING UNIT MATCHED WITH LA300
EVAPORATOR UNIT . . . . . . . . . . . . . . . . . . . . . . . . . 10

10 COOLING CAPACITY 30 TON UNIT - HB360


CONDENSING UNIT MATCHED WITH LB360
EVAPORATOR UNIT . . . . . . . . . . . . . . . . . . . . . . . . . 11
11 COOLING CAPACITY 40/40 TON UNIT - HB480
CONDENSING UNIT MATCHED WITH LB480
EVAPORATOR UNIT . . . . . . . . . . . . . . . . . . . . . . . . . 12
12 COOLING CAPACITY 40 TON UNIT - HB480
CONDENSING UNIT MATCHED WITH LB600
EVAPORATOR UNIT . . . . . . . . . . . . . . . . . . . . . . . . . 13
13 COOLING CAPACITY 50 TON UNIT - HB600
CONDENSING UNIT MATCHED WITH LB600
EVAPORATOR UNIT . . . . . . . . . . . . . . . . . . . . . . . . . 14
14 CORNER WEIGHTS & CENTER OF GRAVITY
(INCHES) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
15 UNIT DIMENSIONS (INCHES) . . . . . . . . . . . . . . . . . . 18
16 UNIT CLEARANCES. . . . . . . . . . . . . . . . . . . . . . . . . . 18
17 PIPING AND ELECTRICAL CONNECTION SIZES
(25T) (INCHES) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
18 PIPING AND ELECTRICAL CONNECTION SIZES
(30/40/50T) (INCHES). . . . . . . . . . . . . . . . . . . . . . . . . 19
19 ELECTRICAL POWER KNOCKOUT SIZES
(INCHES) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

Unitary Products Group

Page 114

http://www.rezine.net
036-21328-003-D-0206

FEATURES (Continued)

Capacity staging for more economical operation and


more even temperature levels within the conditioned
space.

Optional factory installed service valves.


Optional skid for fork truck handling (requires 96 length
forks).

A lockout circuit to prevent the unit from cycling on safety


control.

A filter-drier is shipped in the unit s control box for field


installation in the liquid line near the evaporator coil. Two
are provided on all 30, 40 and 50 ton models.

Pump-out on unit startup to prevent liquid refrigerant


returning to the compressor is standard on 25 through 50
ton models.

Copper stub-outs are factory mounted on the suction


and liquid lines to simplify the field piping connections.
These stubs are provided on units equipped with or without service valves.
Multiple controls to provide stable system operation at
ambient temperatures down to 40 F with kits available
for operation to 0 F.

Unitary Products Group

Inherently protected condenser fan motors.


V-Coil Design with exterior service port connections.
Five-minute anti-short cycle timer and minimum compressor run time.
Factory installed disconnect and Technicoat coils option.
Self contained high and low pressure controls.

Page 115

http://www.rezine.net
036-21328-003-D-0206

PRODUCT NOMENCLATURE
PRODUCT NOMENCLATURE
York OUTDOOR SPLIT CONDENSING UNITS
H A 300 C 00 A 2 A AA 2
Model Number
Description

Options

Product Category

H = Air Conditioner Split System

Product Identifier

A = R-22 Standard Efficiency 2-Pipe


B = R-22 Standard Efficiency 4-Pipe

300

Nominal Cooling
Capacity
MBH

300 = 25 Ton
360 = 30 Ton
480 = 40 Ton
600 = 50 Ton

Heat Type

C = Cooling Only

00

Nominal Heating
Capacity

00 = No Heat Installed

Airflow Options

A = Standard Motor

Voltage

2 = 208/230-3-60
4 = 460-3-60

5 = 575-3-60

Installation Options

A = None
B = Disconnect

C = Service Valves
D = Service Valves + Disconnect

AA

Additional Options

AA = None
AC = Technicoated Coil

Product Generation

1 = 1st Generation

Model #

2 = 2nd Generation

TABLE 1:RATINGS*
Condensing
Unit

EER
Condensing
Unit Only

Evaporator Blower
Unit

Net System
Capacity,
MBH

System
EER

SYSTEM
IPLV

HA300
HB360
HB480
HB600

11.5
11.0
11.1
11.6

LA300
LB360
LB600
LB600

320
376
510
600

10.0
9.5
9.7
9.5

9.8
10.0
9.9
10.8

Condensing Unit
Sound Rating ,
dB
90
92
92
92

Rated in accordance with ARIStandard 340/360-2000.

Sound ratings are based on calculated valves and not in accordance with ARIStandard 370-2001.
EER = Energy Efficiency Ratio at full load - the cooling capacity in
Btu
s per hour (Btuh) divided by the power input in watts, expressed
in Btuh per watt (Btuh/watt).

IPLV - A single number cooling part-load efficiency based on equipment capacity stages and EER at these capacity stages. (ARISTD
340/360-2000)

EER;condensing unit only ratings based on 45 F SST and 95 F


entering outdoor air temperature.

LEGEND
EER = Energy Efficiency Ratio
SST = Saturated Suction Temperature
ARI= Air Conditioning and Refrigeration Institute
IPLV = Integrated Part-Load Valve

Unitary Products Group

Page 116

http://www.rezine.net
036-21328-003-D-0206

TABLE 2:PHYSICAL DATA


Condenser
Compressor*
Model
HA/HB

300

Fan (Propeller)

Fan Motor Coil (Copper Tube-Aluminum Fin)

Nominal Capacity
Pitch Nom.
Capacity Stages Qty. Dia. Deg. CFM RPM
(tons)

HP

Face
Coil Tube Fins
Area Rows Width OD per
Deep
(In.) (In.) inch
(Ft. )

Unit Weight
(Lbs.)

Shipping

Charge, R-22

Opera- Operation Holding


tion
(Lbs.-Oz.) (Lbs.)

25

24

34

23244

1.25

50

60

1608

1658

49.65

1.0

System 1

15

24

36

12690

1.25

25

60

1730

1790

30.08

1.0

System 2

15

24

36

12690

1.25

25

60

System 1

20

30

22

15414

1.50 32.5

78

System 2

20

30

22

15414

1.50 32.5

78

System 1

25

30

26

19386

1.50

52

78

System 2

25

30

26

19386

1.50

52

78

360

30.08

480
1140

3/8

16
1961

2037

37.83

1.0

37.83

600

2470

2563

46.59

1.0

46.59

All compressors are Scrolls.


One of the fan motors is controlled by a pressure switch and will not operate until system pressure reaches 280 psig and drops
below 180 psig.
The total operating charge of the condensing unit, matching indoor unit and 25 feet of interconnecting piping.

TABLE 3:UNIT APPLICATION DATA


Voltage Variation*
Min. / Max.

208/230-3-60

187/252

460-3-60

432/504

575-3-60

540/630

Ambient Air on Condenser Coil


Min. /Max.

40 F/125 F

Suction Pressure at Compressor and


57.5 psig / 92.6 psig
Corresponding Temp. at Saturation
32.0 F / 55.0 F
Min. / Max.
*

Utilization range A in accordance with ARIStandard


110.
These units can operate in an ambient temperature of
125 F providing the wet bulb temperature of the air
entering the evaporator coil does not exceed 67 F.

NOTE: Unit can operate to 0 F if equipped with a low ambient kit. See product Price Pages for correct Low
Ambient Kit.

Unitary Products Group

Page 117

http://www.rezine.net
036-21328-003-D-0206

TABLE 4:ELECTRICAL DATA


Compressor*
Unit Model
Designation

Fan Motor

Unit
Ampacity
(Amps)

Max.
Fuse
Size
(Amps)

Min.
Disconnect
Size

Power Supply

Qty.

RLA
(each)

LRA
(each)

Power Supply

HP

Qty.

FLA
(each)

208/230-3-60

47.1

350.0

208/230-3-60

1.25

4.5/4.3

124.6

150

150

460-3-60

25.0

158.0

460-3-60

1.25

2.15

64.9

80

70

575-3-60

19.9

125.0

575-3-60

1.25

1.7

51.6

70

60

380/415-3-50

25.0

158.0

380/415-3-50

1.50

2.6/2.5

66.7

90

70

208/230-3-60

32.1

195.0

208/230-3-60

1.25

4.5/4.3

154.4

175

175

460-3-60

16.4

95.0

460-3-60

1.25

2.15

78.3

90

90

575-3-60

12.1

80.0

575-3-60

1.25

1.7

58.2

70

70

380/415-3-50

16.4

95.0

380/415-3-50

1.50

2.6/2.5

80.1

90

90

208/230-3-60

42.0

239.0

208/230-3-60

1.50

5.8

201.7

225

225

460-3-60

19.2

125.0

460-3-60

1.50

2.9

93.2

110

110

575-3-60

13.8

80.0

575-3-60

1.50

2.2

67.5

80

80

380/415-3-50

19.2

125.0

380/415-3-50

1.50

2.6/2.5

92.0

110

110

208/230-3-60

47.1

350.0

208/230-3-60

1.50

5.8

224.7

250

250

460-3-60

25.0

158.0

460-3-60

1.50

2.9

117.9

125

150

575-3-60

19.9

125.0

575-3-60

1.50

2.2

93.4

110

110

380/415-3-50

25.0

158.0

380/415-3-50

1.50

2.6/2.5

116.7

125

150

HA300

HB360

HB480

HB600

Compressor quantity refers to each compressor.

TABLE 5:UNIT COOLING CAPACITIES AND POWER REQUIREMENTS - CONDENSING UNIT ONLY
Temperature of Air on Condenser Coil, qF

Suction Press. &


Corresponding
Model Temp. @ Saturation

65

75

85

95

105

115

PSIG

qF

MBH

EER

KW*

MBH

EER

KW*

MBH

EER

KW*

MBH

EER

KW*

MBH

EER

KW*

MBH

EER

KW*

HA300

61.5
68.5
76.0
84.0

35
40
45
50

308
336
366
396

14.8
15.9
16.9
17.9

20.8
21.2
21.7
22.1

295
322
350
379

13.1
14.1
15.0
15.9

22.5
22.9
23.3
23.7

282
307
333
361

11.5
12.3
13.2
14.1

24.5
24.9
25.3
25.7

268
292
317
343

10.0
10.8
11.5
12.3

26.7
27.1
27.5
28.0

255
277
300
325

9.1
9.5
10.1
10.8

28.0
29.3
29.7
30.1

241
262
284
307

7.5
8.0
8.6
9.1

32.2
32.7
33.1
33.6

HB360

61.5
68.5
76.0
84.0

35
40
45
50

377
409
442
476

14.4
15.3
16.1
16.9

26.2
26.8
27.4
28.1

358
389
422
455

12.7
13.5
14.3
15.1

28.2
28.8
29.5
30.1

340
370
401
433

11.1
11.9
12.6
13.3

30.5
31.2
31.8
32.5

321
350
380
412

9.7
10.4
11.0
11.7

33.2
33.8
34.5
35.2

302
330
360
390

8.3
9.0
9.6
10.2

36.2
36.8
37.5
38.2

283
310
339
368

7.1
7.7
8.3
8.8

39.6
40.3
41.0
41.7

HB480

61.5
68.5
76.0
84.0

35
40
45
50

502
543
585
628

14.7
15.5
16.2
16.9

34.2
35.1
36.1
37.1

479
518
559
601

13.0
13.7
14.4
15.1

36.9
37.8
38.8
39.8

456
494
533
574

11.4
12.1
12.7
13.4

40.0
40.9
41.9
42.9

432
469
507
546

9.9
10.6
11.2
11.8

43.5
44.4
45.4
46.5

409
444
481
519

8.6
9.2
9.7
10.3

47.6
48.5
49.4
50.5

385
419
455
491

7.4
7.9
8.4
8.9

52.1
53.0
54.0
55.0

HB600

61.5
68.5
76.0
84.0

35
40
45
50

609
663
719
777

15.4
16.4
17.3
18.2

39.6
40.5
41.5
42.6

583
634
687
743

13.5
14.4
15.3
16.1

43.0
44.0
45.0
46.0

556
604
655
708

11.8
12.6
13.4
14.1

47.1
48.0
49.0
50.0

529
575
623
673

10.2
10.9
11.6
12.3

51.7
52.7
53.7
54.8

503
545
590
638

8.8
9.4
10.0
10.6

56.9
58.0
59.1
60.2

476
515
558
603

7.6
8.1
8.6
9.1

62.9
64.0
65.2
66.4

*These power requirements include the following condenser fan motor KW.
Model

HA300

HB360

HB480

HB600

KW

3.4

4.3

4.3

3.8

**See Table 1 for condensing unit only EER ratings.

Unitary Products Group

Page 118

http://www.rezine.net
036-21328-003-D-0206

LINE SIZING

1.

Suction line pressure drop due to friction.

2.

Liquid line pressure drop due to friction.

3.

Suction line velocity for oil return.

Condensing Section Below Evaporator - When the condensing section is located below the evaporator blower, the
liquid line must be designed for the pressure drop due to both
friction loss and vertical rise. See Table 7. If the pressure
drop due to vertical rise and friction exceeds 40 psi, some
refrigerant will flash before it reaches the thermal expansion
valve.

4.

Liquid line pressure drop due to vertical rise.

Flash Gas:

When sizing refrigerant pipe for a split-system air conditioner,


check the following:

Tables 6 and 7 list friction losses for both the suction and liquid lines on the condensing section. For certain piping
arrangements, different sizes of suction line pipe may have to
be used. The velocity of the refrigerant vapor must always be
great enough to carry the oil back to the compressor.
Evaporator Below Condensing Section - On a split system
where the evaporator blower is located below the condensing
section, the suction line must be sized for both pressure drop
and for oil return. Oil traps may be required on this type of
application. See Table 6.

Unitary Products Group

1.

Increases the liquid line pressure loss due to friction


which in turn causes further flashing.

2.

Reduces the capacity of the refrigerant control device


which starves the evaporator.

3.

Erodes the seat of the refrigerant control device.

4.

Causes erratic control of the refrigerant entering the


evaporator. (See Installation Instructions for more detail.)

Page 119

http://www.rezine.net
036-21328-003-D-0206

TABLE 6:SUCTION LINES


Model Designation

Full Capacity
HA300

Nominal
Capacity (Tons)

Refrigerant Flow
Rate (Lbs./Min.)

25

80

System #1
Half Capacity

Full Capacity

12.5

15

40

47

System #1
Half Capacity

7.5

23.5

HB360
Full Capacity

15

47

System #2
Half Capacity

Full Capacity

7.5

20

23.5

64

System #1
Half Capacity

10

32

HB480
Full Capacity

20

64

System #2
Half Capacity

Full Capacity

10

25

32

76

System #1
Half Capacity

12.5

38

HB600
Full Capacity

25

76

System #2
Half Capacity

12.5

38

Copper Tubing
(Inches,O.D.)

Refrigerant Gas
Velocity (Ft./Min.)

Friction Loss
(PSI/100 Ft.)

2 1/8

1945

1.2

2 5/8

1500

0.6

3 1/8

1040

0.3

2 1/8

1110

0.5

2 5/8

750

0.2

3 1/8

520

0.1

1 3/8

2873

4.1

1 5/8

2030

1.8

2 1/8

1167

0.5

1 3/8

1437

1.1

1 5/8

1015

0.5

2 1/8

850

0.2

1 3/8

2873

4.1

1 5/8

2030

1.8

2 1/8

1167

0.5

1 3/8

1437

1.1

1 5/8

1015

0.5

2 1/8

850

0.2

1 5/8

3120

4.3

2 1/8

1800

1.2

2 5/8

1200

0.4

1 5/8

1560

1.2

2 1/8

900

0.3

2 5/8

600

0.1

1 5/8

3120

4.3

2 1/8

1800

1.2

2 5/8

1200

0.4

1 5/8

1560

1.2

2 1/8

1800

1.2

2 5/8

1200

0.4

1 5/8

3384

4.5

2 1/8

1945

1.2

2 5/8

1500

0.6

1 5/8

1710

1.4

2 1/8

983

0.4

2 5/8

750

0.2

1 5/8

3384

4.5

2 1/8

1945

1.2

2 5/8

1500

0.6

1 5/8

1710

1.4

2 1/8

983

0.4

2 5/8

750

0.2

Unitary Products Group

Page 120

http://www.rezine.net
036-21328-003-D-0206

TABLE 7:LIQUID LINES


Model Designation

HA300

Nominal
Refrigerant Flow
Capacity (Tons) Rate (Lbs./Min.)

System #1

Full Capacity

25

80

System #1

Full Capacity

15

47

System #2

Full Capacity

15

47

System #1

Full Capacity

20

64

System #2

Full Capacity

20

64

System #1

Full Capacity

25

76

System #2

Full Capacity

25

76

HB360

HB480

HB600

Copper Tubing
(Inches,O.D.)

Refrigerant
Liquid Velocity
(Ft./Min.)

Friction Loss
(PSI/100 Ft.)

5/8
7/8
1 1/8
5/8
7/8
1 1/8
5/8
7/8
1 1/8
5/8
7/8
1 1/8
5/8
7/8
1 1/8
5/8
7/8
1 1/8
5/8
7/8
1 1/8

500
265
156
330
159
100
330
159
100
440
212
90
440
212
90
400
265
156
400
265
156

14.2
3.4
1.0
7.9
1.4
0.8
7.9
1.4
0.8
13.2
2.3
0.6
13.2
2.3
0.6
8.5
3.4
1.0
8.5
3.4
1.0

TABLE 8:R-22 LINE CHARGE*


LINE SET, O.D.

O.D., (INCHES)

LIQUID

7/8

0.236

1 5/8

0.019

2 1/8

0.033

SUCTION
*

REFRIGERANT, LB/FT

Charges based on 40 F suction temperature and 105 F liquid temperature.


Type L copper tubing.

NOTE: Add the operating charge of the condensing unit, the evaporator coil and the refrigerant lines to determine the total refrigerant
charge of the system.

Unitary Products Group

Page 121

http://www.rezine.net
036-21328-003-D-0206

TABLE 9:COOLING CAPACITY 25 TON UNIT - HA300 CONDENSING UNIT MATCHED WITH LA300 EVAPORATOR UNIT
AIR ON
EVAP. COIL
CFM

7500

8750

10000

11250

12500

AIR ON
EVAP. COIL

TEMPERATURE OF AIR ON CONDENSER COIL 85 F

GROSS TOTAL GROSS SENSIBLE CAPACITY (MBh) RETURN DRY BULB


WB
( F)
CAPACITY INPUT
( F)
(MBH)
(Kw)
86
83
80
77
74
71
68

TEMPERATURE OF AIR ON CONDENSER COIL 95 F

GROSS TOTAL GROSS SENSIBLE CAPACITY (MBh) RETURN DRY BULB


WB
( F)
CAPACITY INPUT
( F)
(MBH)
(Kw)
86
83
80
77
74
71
68

CFM

72

348.3

25.78

218.3

194.0

169.7

145.4

121.1

#N/A

#N/A

72

335.0

28.19

213.1

188.8

164.5

140.2

115.9

#N/A

#N/A

67

326.2

25.42

266.5

242.2

217.9

193.6

169.3

145.0

120.7

67

313.6

27.83

261.1

236.8

212.5

188.2

163.9

139.6

115.3

62

294.3

27.39

294.3

287.0

262.7

238.4

214.1

189.8

165.5

57

300.7

27.59

300.7

299.4

275.1

250.8

226.5

202.2

177.9

62

305.0

25.08

305.0

291.9

267.6

243.3

219.0

194.7

170.4

57

310.4

25.24

310.4

308.4

284.1

259.8

235.5

211.2

186.9

7500

72

357.1

25.91

239.0

210.6

182.3

153.9

125.6

#N/A

#N/A

72

342.8

28.37

233.0

204.7

176.3

148.0

119.6

#N/A

#N/A

67

334.4

25.54

290.7

262.4

234.0

205.7

177.3

149.0

120.6

67

320.9

28.00

284.5

256.1

227.8

199.4

171.1

142.7

114.4

62

312.7

25.20

312.7

306.1

287.3

259.0

230.6

202.3

173.9

62

301.2

27.56

301.2

297.5

281.6

253.2

224.9

196.5

168.2

57

318.2

25.36

318.2

317.2

305.1

276.7

248.4

220.0

191.7

57

307.7

27.76

307.7

307.1

294.9

266.6

238.2

209.9

181.5

72

365.9

26.03

259.6

227.2

194.8

162.4

130.0

#N/A

#N/A

72

350.7

28.55

253.0

220.6

188.2

155.8

123.4

#N/A

#N/A

67

342.7

25.66

314.9

282.5

250.1

217.7

185.3

152.9

120.5

67

328.3

28.18

307.9

275.5

243.1

210.7

178.3

145.9

113.5

62

320.3

25.32

320.3

320.3

307.1

274.7

242.3

209.9

177.5

62

308.1

27.73

308.1

308.1

300.5

268.1

235.7

203.3

170.9

57

326.0

25.48

326.0

326.0

326.0

293.6

261.2

228.8

196.4

57

314.8

27.94

314.8

314.8

314.8

282.4

250.0

217.6

185.2

72

372.1

26.13

279.4

242.9

206.5

170.0

133.6

#N/A

#N/A

72

356.8

28.59

273.1

236.6

200.2

163.7

127.3

#N/A

#N/A

67

348.5

25.76

334.7

301.6

265.1

228.7

192.2

155.8

119.3

67

334.0

28.22

323.8

295.0

258.6

222.1

185.7

149.2

112.8

62

325.8

25.41

325.8

325.8

319.2

282.8

246.3

209.9

173.4

62

313.5

27.77

313.5

313.5

309.7

273.3

236.8

200.4

163.9

57

331.6

25.57

331.6

331.6

331.6

295.2

258.7

222.3

185.8

57

320.3

27.98

320.3

320.3

320.3

283.8

247.4

210.9

174.5

72

378.4

26.22

299.2

258.7

218.2

177.7

137.2

#N/A

#N/A

72

363.0

28.63

293.2

252.7

212.2

171.7

131.2

#N/A

#N/A

67

354.4

25.85

354.4

320.6

280.1

239.6

199.1

158.6

118.1

67

339.8

28.26

339.8

314.5

274.0

233.5

193.0

152.5

112.0

62

331.3

25.51

331.3

331.3

331.3

290.8

250.3

209.8

169.3

62

318.9

27.81

318.9

318.9

318.9

278.4

237.9

197.4

156.9

57

337.2

25.67

337.2

337.2

337.2

296.7

256.2

215.7

175.2

57

325.8

28.02

325.8

325.8

325.8

285.3

244.8

204.3

163.8

8750

10000

11250

12500

TEMPERATURE OF AIR ON CONDENSER COIL 105 F

7500

8750

10000

11250

12500

TEMPERATURE OF AIR ON CONDENSER COIL 115 F

72

319.6

31.41

206.4

182.1

157.8

133.5

109.2

#N/A

#N/A

67

300.0

30.96

254.7

230.4

206.1

181.8

157.5

133.2

108.9

72

304.2

34.63

199.8

175.5

151.2

126.9

102.6

#N/A

#N/A

67

286.4

34.09

248.4

224.1

199.8

175.5

151.2

126.9

102.6

62

285.8

30.71

285.8

280.4

256.1

231.8

207.5

183.2

158.9

57

288.9

30.73

288.9

286.4

262.1

237.8

213.5

189.2

164.9

62

277.4

34.03

277.4

273.8

249.5

225.2

200.9

176.6

152.3

57

277.1

33.87

277.1

273.5

249.2

224.9

200.6

176.3

72

327.2

31.53

226.7

198.4

170.0

141.7

113.3

#N/A

#N/A

152.0

72

311.5

34.69

220.4

192.0

163.7

135.3

107.0

#N/A

67

307.1

31.08

278.7

250.4

222.0

193.7

165.3

137.0

108.6

#N/A

67

293.3

34.15

273.0

244.7

216.3

188.0

159.6

131.3

102.9

62

292.6

30.83

292.6

289.9

275.8

247.5

219.1

190.8

162.4

57

295.7

30.85

295.7

294.5

282.3

254.0

225.6

197.3

168.9

62

284.0

34.10

284.0

282.2

270.1

241.7

213.4

185.0

156.7

57

283.7

33.93

283.7

281.9

269.7

241.4

213.0

184.7

72

334.7

31.65

247.0

214.6

182.2

149.8

117.4

#N/A

#N/A

156.3

72

318.8

34.76

241.0

208.6

176.2

143.8

111.4

#N/A

67

314.2

31.20

302.8

270.4

238.0

205.6

173.2

140.8

108.4

#N/A

67

300.1

34.22

297.6

265.2

232.8

200.4

168.0

135.6

103.2

62

299.4

30.95

299.4

299.4

295.6

263.2

230.8

198.4

166.0

57

302.6

30.97

302.6

302.6

302.6

270.2

237.8

205.4

173.0

62

290.7

34.16

290.7

290.7

290.7

258.3

225.9

193.5

161.1

57

290.3

34.00

290.3

290.3

290.3

257.9

225.5

193.1

72

339.9

31.75

268.2

231.7

195.3

158.8

122.4

#N/A

160.7

#N/A

72

323.0

34.91

263.3

226.8

190.4

153.9

117.5

#N/A

67

319.1

31.29

313.3

290.8

255.1

218.7

182.2

#N/A

145.8

109.3

67

304.1

34.36

302.9

286.7

251.6

215.2

178.7

142.3

105.8

62

304.0

31.04

304.0

304.0

302.1

265.7

57

307.2

31.06

307.2

307.2

307.2

270.8

229.2

192.8

156.3

62

294.6

34.31

294.6

294.6

294.6

258.1

221.7

185.2

148.8

234.3

197.9

161.4

57

294.2

34.14

294.2

294.2

294.2

257.7

221.3

184.8

72

345.1

31.84

289.4

248.9

208.4

148.4

167.9

127.4

#N/A

#N/A

72

327.2

35.06

285.6

245.1

204.6

164.1

123.6

#N/A

67

323.9

31.38

323.9

311.3

#N/A

272.3

231.8

191.3

150.8

110.3

67

308.1

34.51

308.1

308.1

270.5

230.0

189.5

149.0

108.5

62

308.7

31.13

308.7

57

311.9

31.15

311.9

308.7

308.7

268.2

227.7

187.2

146.7

62

298.4

34.45

298.4

298.4

298.4

257.9

217.4

176.9

136.4

311.9

311.9

271.4

230.9

190.4

149.9

57

298.0

34.29

298.0

298.0

298.0

257.5

217.0

176.5

136.0

72

288.8

37.8

193.1

168.8

144.5

120.2

95.9

#N/A

#N/A

67

272.8

37.2

242.1

217.8

193.5

169.2

144.9

120.6

96.3

62

269.0

37.4

269.0

267.2

242.9

218.6

194.3

170.0

145.7

These capacities are gross ratings. For net capacity, deduct air blower motor,
MBH - 3.415 X kW. Refer to the appropriate Blower Performance Table for the
kW of the supply air blower motor.

57

265.2

37.0

265.2

260.5

236.2

211.9

187.6

163.3

139.0

72

295.8

37.9

214.0

185.7

157.3

129.0

100.6

#N/A

#N/A

7500

8750

10000

11250

12500

TEMPERATURE OF AIR ON CONDENSER COIL 125 F

7500

8750

10000

11250

12500

67

279.4

37.2

267.3

239.0

210.6

182.3

153.9

125.6

97.2

62

275.5

37.4

275.5

274.6

264.3

236.0

207.6

179.3

150.9

57

271.7

37.0

271.7

269.3

257.2

228.8

200.5

172.1

143.8

72

302.8

37.9

234.9

202.5

170.1

137.7

105.3

#N/A

#N/A

67

286.0

37.2

286.0

260.1

227.7

195.3

162.9

130.5

98.1

62

282.0

37.4

282.0

282.0

282.0

253.4

221.0

188.6

156.2

57

278.1

37.0

278.1

278.1

278.1

245.7

213.3

180.9

148.5

72

306.1

38.1

258.4

221.9

185.5

149.0

112.6

#N/A

#N/A

67

289.1

37.4

289.1

282.5

248.2

211.7

175.3

138.8

102.4

62

285.1

37.6

285.1

285.1

285.1

250.5

214.1

177.6

141.2

57

281.1

37.2

281.1

281.1

281.1

244.7

208.2

171.8

135.3

72

309.4

38.3

281.8

241.3

200.8

160.3

119.8

#N/A

#N/A

67

292.2

37.6

292.2

292.2

268.7

228.2

187.7

147.2

106.7

62

288.2

37.8

288.2

288.2

288.2

247.7

207.2

166.7

126.2

57

284.2

37.4

284.2

284.2

284.2

243.7

203.2

162.7

122.2

These ratings include condenser fan motors and the compressor motors but not
the supply blower motor.

10

Unitary Products Group

Page 122

http://www.rezine.net
036-21328-003-D-0206

TABLE 10:COOLING CAPACITY 30 TON UNIT - HB360 CONDENSING UNIT MATCHED WITH LB360 EVAPORATOR UNIT
AIR ON
EVAP. COIL
CFM

9000

10500

12000

13500

15000

AIR ON
EVAP. COIL

TEMPERATURE OF AIR ON CONDENSER COIL 85 F

GROSS TOTAL GROSS SENSIBLE CAPACITY (MBh) RETURN DRY BULB


WB
( F)
CAPACITY INPUT
( F)
(MBH)
(Kw)
86
83
80
77
74
71
68

TEMPERATURE OF AIR ON CONDENSER COIL 95 F

GROSS TOTAL GROSS SENSIBLE CAPACITY (MBh) RETURN DRY BULB


WB
( F)
CAPACITY INPUT
( F)
(MBH)
(Kw)
86
83
80
77
74
71
68

CFM

72

417.9

32.58

261.8

232.7

203.5

174.4

145.2

#N/A

#N/A

72

401.5

35.41

256.4

227.3

198.1

169.0

139.8

#N/A

#N/A

67

391.8

31.97

321.3

292.1

262.9

233.8

204.6

175.5

146.3

67

376.3

34.84

314.8

285.7

256.5

227.3

198.2

169.0

139.9

62

366.3

31.41

366.3

352.2

323.0

293.9

264.7

235.5

206.4

62

352.9

34.26

352.9

345.5

316.3

287.1

258.0

228.8

199.7

57

377.6

31.74

377.6

376.5

347.4

318.2

289.0

259.9

230.7

57

364.2

34.57

364.2

363.3

334.1

304.9

275.8

246.6

217.5

72

428.0

32.79

285.8

251.8

217.8

183.7

149.7

#N/A

#N/A

72

410.9

35.63

280.1

246.1

212.1

178.1

144.1

#N/A

#N/A

67

401.3

32.18

349.4

315.4

281.3

247.3

213.3

179.3

145.3

67

385.1

35.06

342.6

308.6

274.6

240.6

206.6

172.5

138.5

62

375.2

31.61

375.2

368.2

345.6

311.6

277.6

243.6

209.5

62

361.1

34.48

361.1

357.4

338.6

304.6

270.6

236.5

202.5

57

386.8

31.95

386.8

386.2

371.7

337.6

303.6

269.6

235.6

57

372.7

34.79

372.7

372.2

357.7

323.6

289.6

255.6

221.6

72

438.2

33.00

309.8

270.9

232.0

193.1

154.2

#N/A

#N/A

72

420.3

35.85

303.8

264.9

226.1

187.2

148.3

#N/A

#N/A

67

410.9

32.39

377.5

338.6

299.7

260.9

222.0

183.1

144.2

67

393.9

35.27

370.4

331.6

292.7

253.8

214.9

176.0

137.2

62

384.1

31.82

384.1

384.1

368.2

329.3

290.5

251.6

212.7

62

283.1

244.3

205.4

396.0

396.0

396.0

357.1

318.2

279.3

240.4

57

369.4
381.2

322.0

32.16

34.69
35.00

360.9

396.0

369.4
381.2

369.4

57

381.2

381.2

342.3

303.5

264.6

225.7

72

445.5

33.15

333.1

289.4

245.6

201.9

158.2

#N/A

#N/A

72

427.3

36.00

327.0

283.3

239.5

195.8

152.1

#N/A

#N/A

67

417.7

32.54

401.0

361.1

317.4

273.6

229.9

186.2

142.4

67

400.4

35.42

388.7

353.9

310.1

266.4

222.6

178.9

135.2

9000

10500

12000

13500

62

390.5

31.97

390.5

390.5

382.6

338.8

295.1

251.3

207.6

62

375.5

34.83

375.5

375.5

371.3

327.5

283.8

240.1

196.3

57

402.6

32.30

402.6

402.6

402.6

358.8

315.1

271.3

227.6

57

387.6

35.15

387.6

387.6

387.6

343.8

300.1

256.3

212.6

72

452.8

33.31

356.5

307.9

259.3

210.7

162.1

#N/A

#N/A

72

434.2

36.15

350.2

301.6

253.0

204.4

155.8

#N/A

#N/A

67

424.5

32.69

424.5

383.6

335.0

286.4

237.8

189.2

140.6

67

407.0

35.57

407.0

376.2

327.6

279.0

230.4

181.8

133.2

62

396.9

32.11

396.9

396.9

396.9

348.3

299.7

251.1

202.5

62

381.7

34.98

381.7

381.7

381.7

333.1

284.5

235.9

187.3

57

409.1

32.45

409.1

409.1

409.1

360.5

311.9

263.3

214.7

57

393.9

35.29
393.9 393.9 393.9 345.3 296.7 248.1
TEMPERATURE OF AIR ON CONDENSER COIL 115 F

199.5

15000

TEMPERATURE OF AIR ON CONDENSER COIL 105 F

9000

10500

12000

13500

15000

72

384.1

39.06

249.6

220.4

191.2

162.1

132.9

#N/A

#N/A

67

359.7

38.46

307.5

278.3

249.1

220.0

190.8

161.7

132.5

62

345.0

38.07

345.0

340.8

311.6

282.5

253.3

224.2

195.0

57

350.6

38.22

350.6

349.6

320.5

291.3

262.2

233.0

203.8

72

392.7

39.27

273.0

238.9

204.9

170.9

136.9

#N/A

#N/A

67

367.8

38.66

335.0

301.0

267.0

233.0

198.9

164.9

130.9

62

352.8

38.27

352.8

350.7

334.0

299.9

265.9

231.9

197.9

57

358.5

38.42

358.5

358.0

343.4

309.4

275.4

241.4

207.3

72

401.4

39.47

296.4

257.5

218.6

179.7

140.9

#N/A

67

375.9

38.86

362.6

323.7

284.8

245.9

207.1

62

360.5

38.47

360.5

360.5

356.3

317.4

57

366.4

38.62

366.4

366.4

366.4

327.5

72

408.2

39.62

319.6

275.9

232.1

67

382.3

39.01

375.6

346.2

62

366.6

38.62

366.6

57

372.6

38.77

372.6

72

415.0

39.77

67

388.6

62
57

9000

72

366.7

42.71

242.7

213.5

184.3

155.2

126.0

#N/A

#N/A

67

343.2

42.07

300.1

270.9

241.8

212.6

183.4

154.3

125.1

62

337.2

41.88

337.2

336.1

307.0

277.8

248.7

219.5

190.3

57

337.1

41.87

337.1

336.0

306.9

277.7

248.5

219.4

190.2

72

374.6

42.90

265.8

231.8

197.8

163.7

129.7

#N/A

#N/A

67

350.5

42.26

327.4

293.4

259.4

225.3

191.3

157.3

123.3

62

344.4

42.07

344.4

343.9

329.3

295.3

261.3

227.3

193.2

57

344.3

42.06

344.3

343.8

329.2

295.2

261.1

227.1

193.1

#N/A

72

382.5

43.10

288.9

250.1

211.2

172.3

133.4

#N/A

#N/A

168.2

129.3

67

357.9

42.45

354.7

315.8

276.9

238.1

199.2

160.3

121.4

278.5

239.6

200.8

62

351.7

42.26

351.7

351.7

351.7

312.8

273.9

235.0

196.1

288.6

249.7

210.8

57

351.5

42.25

351.5

351.5

351.5

312.6

273.8

234.9

196.0

188.4

144.6

#N/A

#N/A

72

389.1

43.25

312.2

268.5

224.7

181.0

137.2

#N/A

#N/A

302.4

258.7

214.9

171.2

127.5

67

364.1

42.60

362.5

338.4

294.7

251.0

207.2

163.5

119.7

366.6

364.5

320.8

277.0

233.3

189.6

62

357.8

42.41

357.8

357.8

357.8

314.0

270.3

226.5

182.8

372.6

372.6

328.9

285.1

241.4

197.6

57

357.6

42.40

357.6

357.6

357.6

313.9

270.2

226.4

182.7

342.8

294.2

245.6

197.0

148.4

#N/A

#N/A

72

395.8

43.40

335.4

286.8

238.2

189.6

141.0

#N/A

#N/A

39.16

388.6

368.6

320.0

271.4

222.8

174.2

125.6

67

370.3

42.75

370.3

361.0

312.4

263.8

215.2

166.6

118.0

372.8

38.77

372.8

372.8

372.8

324.2

275.6

227.0

178.4

62

363.9

42.55

363.9

363.9

363.9

315.3

266.7

218.1

169.5

378.8

38.92

378.8

378.8

378.8

330.2

281.6

233.0

184.4

57

363.7

42.55

363.7

363.7

363.7

315.1

266.5

217.9

169.3

10500

12000

13500

15000

TEMPERATURE OF AIR ON CONDENSER COIL 125 F

9000

10500

12000

13500

15000

72

349.4

46.4

235.8

206.6

177.5

148.3

119.1

#N/A

#N/A

67

326.6

45.7

292.7

263.5

234.4

205.2

176.1

146.9

117.7

62

329.3

45.7

329.3

329.3

302.3

273.2

244.0

214.8

185.7

These capacities are gross ratings. For net capacity, deduct air blower motor,
MBH - 3.415 X kW. Refer to the appropriate Blower Performance Table for the
kW of the supply air blower motor.

57

323.5

45.5

323.5

322.4

293.2

264.1

234.9

205.8

176.6

72

356.5

46.5

258.6

224.6

190.6

156.6

122.6

#N/A

#N/A

67

333.3

45.9

319.8

285.8

251.7

217.7

183.7

149.7

115.7

62

336.1

45.9

336.1

336.1

324.7

290.7

256.6

222.6

188.6

57

330.1

45.7

330.1

329.5

315.0

280.9

246.9

212.9

178.9

72

363.6

46.7

281.5

242.6

203.7

164.9

126.0

#N/A

#N/A

67

339.9

46.0

339.9

308.0

269.1

230.2

191.3

152.4

113.6

62

342.8

46.0

342.8

342.8

342.8

308.2

269.3

230.4

191.5

57

336.7

45.9

336.7

336.7

336.7

297.8

258.9

220.0

181.2

72

370.0

46.9

304.8

261.0

217.3

173.6

129.8

#N/A

#N/A

67

346.0

46.2

346.0

330.7

287.0

243.2

199.5

155.8

112.0

62

348.9

46.2

348.9

348.9

348.9

307.3

263.5

219.8

176.1

57

342.7

46.0

342.7

342.7

342.7

298.9

255.2

211.4

167.7

72

376.5

47.0

328.1

279.5

230.9

182.3

133.7

#N/A

#N/A

67

352.0

46.3

352.0

352.0

304.9

256.3

207.7

159.1

110.5

62

355.0

46.3

355.0

355.0

355.0

306.4

257.8

209.2

160.6

57

348.7

46.2

348.7

348.7

348.7

300.1

251.5

202.9

154.3

Unitary Products Group

These ratings include condenser fan motors and the compressor motors but
not the supply blower motor.

11

Page 123

http://www.rezine.net
036-21328-003-D-0206

TABLE 11:COOLING CAPACITY 40/40 TON UNIT - HB480 CONDENSING UNIT MATCHED WITH LB480 EVAPORATOR UNIT
AIR ON
EVAP. COIL
CFM

12000

14000

16000

18000

20000

AIR ON
EVAP. COIL

TEMPERATURE OF AIR ON CONDENSER COIL 85 F

GROSS TOTAL GROSS SENSIBLE CAPACITY (MBh) RETURN DRY BULB


WB
( F)
CAPACITY INPUT
( F)
(Kw)
(MBH)
86
83
80
77
74
71
68

CFM

TEMPERATURE OF AIR ON CONDENSER COIL 95 F

GROSS TOTAL GROSS SENSIBLE CAPACITY (MBh) RETURN DRY BULB


WB
( F)
CAPACITY INPUT
( F)
(Kw)
(MBH)
86
83
80
77
74
71
68

72

539.6

45.22

340.2

301.3

262.4

223.5

184.6

#N/A

#N/A

72

527.0

46.63

338.3

299.4

260.5

221.6

182.7

#N/A

#N/A

67

514.1

41.84

423.9

385.0

346.1

307.2

268.3

229.5

190.6

67

494.2

45.70

415.0

376.1

337.3

298.4

259.5

220.6

181.7

62

470.8

43.24

470.8

453.4

414.5

375.6

336.7

297.9

259.0

62

483.1

45.42

483.1

480.9

442.0

403.1

364.3

325.4

286.5

57

492.1

43.78

492.1

487.3

448.5

409.6

370.7

331.8

292.9

57

482.9

45.41

482.9

480.7

441.8

402.9

364.0

325.2

286.3

72

557.3

44.33

375.3

330.0

284.6

239.2

193.9

#N/A

#N/A

72

539.4

46.94

370.0

324.7

279.3

234.0

188.6

#N/A

#N/A

67

531.0

41.01

466.1

420.7

375.4

330.0

284.7

239.3

193.9

67

505.9

46.00

452.4

407.0

361.6

316.3

270.9

225.6

180.2

62

486.2

42.39

486.2

477.5

449.6

404.2

358.9

313.5

268.1

62

494.5

45.73

494.5

493.4

474.0

428.6

383.3

337.9

292.5

57

508.2

42.91

508.2

505.8

486.4

441.0

395.7

350.3

304.9

57

494.3

45.72

494.3

493.2

473.7

428.4

383.0

337.7

292.3

72

574.9

43.43

410.5

358.6

306.8

255.0

203.1

#N/A

#N/A

72

551.9

47.26

401.8

350.0

298.2

246.3

194.5

#N/A

#N/A

67

547.8

40.18

508.3

456.5

404.7

352.8

301.0

249.1

197.3

67

517.5

46.31

489.7

437.9

386.0

334.2

282.3

230.5

178.7

62

501.6

41.53

501.6

501.6

484.6

432.8

381.0

329.1

277.3

62

505.9

46.04

505.9

505.9

505.9

454.1

402.3

350.4

298.6

57

524.3

42.04

524.3

524.3

524.3

472.5

420.6

368.8

317.0

57

505.7

46.02

505.7

505.7

505.7

453.8

402.0

350.2

298.3

72

578.9

44.86

437.5

379.2

320.8

262.5

204.2

#N/A

#N/A

72

560.8

47.46

433.7

375.4

317.1

258.8

200.4

#N/A

#N/A

67

551.6

41.51

531.9

481.5

423.2

364.9

306.5

248.2

189.9

67

526.0

46.51

512.0

468.9

410.5

352.2

293.9

235.6

177.3

12000

14000

16000

18000

62

505.1

42.90

505.1

505.1

496.6

438.3

380.0

321.6

263.3

62

514.2

46.23

514.2

514.2

514.2

455.9

397.5

339.2

280.9

57

527.9

43.43

527.9

527.9

527.9

469.6

411.3

353.0

294.7

57

513.9

46.22

513.9

513.9

513.9

455.6

397.3

339.0

280.6

72

582.9

46.30

464.5

399.7

334.9

270.1

205.3

#N/A

#N/A

72

569.8

47.66

465.6

400.8

336.0

271.2

206.4

#N/A

#N/A

67

555.4

42.84

555.4

506.5

441.7

376.9

312.1

247.3

182.5

67

534.4

46.70

534.4

499.8

435.0

370.2

305.4

240.6

175.8

62

508.6

44.27

508.6

508.6

508.6

443.8

379.0

314.2

249.4

62

522.4

46.43

522.4

522.4

522.4

457.6

392.8

328.0

263.2

57

531.6

44.82

531.6

531.6

531.6

466.8

402.0

337.2

272.4

57

522.1

46.41

522.1

522.1

522.1

457.3

392.5

327.7

262.9

20000

TEMPERATURE OF AIR ON CONDENSER COIL 105 F

12000

14000

16000

18000

20000

TEMPERATURE OF AIR ON CONDENSER COIL 115 F

72

504.2

51.33

329.0

290.1

251.2

212.3

173.5

#N/A

#N/A

67

473.3

50.38

406.1

367.2

328.3

289.4

250.6

211.7

172.8

72

481.4

56.03

319.7

280.8

242.0

203.1

164.2

#N/A

#N/A

67

452.4

55.06

397.1

358.2

319.4

280.5

241.6

202.7

163.8

62

465.3

50.16

465.3

462.2

423.3

384.5

345.6

306.7

267.8

57

465.0

50.15

465.0

461.9

423.1

384.2

345.3

306.4

267.5

62

447.6

54.90

447.6

443.5

404.7

365.8

326.9

288.0

249.1

57

447.2

54.89

447.2

443.2

404.3

365.4

326.6

287.7

72

515.8

51.62

360.8

315.4

270.1

224.7

179.4

#N/A

#N/A

248.8

72

492.2

56.30

351.6

306.2

260.8

215.5

170.1

#N/A

67

484.2

50.67

443.7

398.3

353.0

307.6

262.2

216.9

171.5

#N/A

67

462.6

55.33

435.0

389.6

344.3

298.9

253.6

208.2

162.8

62

476.1

50.45

476.1

474.5

455.1

409.7

364.4

319.0

273.7

57

475.8

50.44

475.8

474.2

454.8

409.4

364.1

318.7

273.4

62

457.7

55.17

457.7

455.7

436.2

390.9

345.5

300.1

254.8

57

457.3

55.16

457.3

455.3

435.8

390.5

345.1

299.8

72

527.5

51.91

392.6

340.8

288.9

237.1

185.3

#N/A

254.4

#N/A

72

503.1

56.57

383.4

331.6

279.7

227.9

176.0

#N/A

67

495.2

50.95

481.3

429.4

377.6

325.8

273.9

#N/A

222.1

170.2

67

472.8

55.60

472.8

421.0

369.2

317.3

265.5

213.7

161.8

62

486.9

50.74

486.9

486.9

486.9

435.0

57

486.5

50.72

486.5

486.5

486.5

434.7

383.2

331.3

279.5

62

467.8

55.44

467.8

467.8

467.8

415.9

364.1

312.3

260.4

382.9

331.0

279.2

57

467.4

55.42

467.4

467.4

467.4

415.5

363.7

311.9

72

535.9

52.12

423.7

365.4

307.0

260.0

248.7

190.4

#N/A

#N/A

72

510.9

56.79

413.6

355.3

297.0

238.7

180.3

#N/A

67

503.0

51.16

496.1

459.6

#N/A

401.3

342.9

284.6

226.3

168.0

67

480.1

55.81

480.1

450.3

392.0

333.7

275.3

217.0

158.7

62

494.6

50.94

494.6

57

494.2

50.93

494.2

494.6

494.6

436.3

377.9

319.6

261.3

62

475.0

55.65

475.0

475.0

475.0

416.7

358.3

300.0

241.7

494.2

494.2

435.9

377.6

319.3

261.0

57

474.6

55.64

474.6

474.6

474.6

416.3

357.9

299.6

72

544.2

52.33

241.3

454.7

389.9

325.1

260.3

195.5

#N/A

#N/A

72

518.6

57.01

443.9

379.1

314.3

249.5

184.7

#N/A

67

510.9

#N/A

51.37

510.9

489.7

424.9

360.1

295.3

230.5

165.7

67

487.4

56.03

487.4

479.6

414.8

350.0

285.2

220.4

155.6

62
57

502.3

51.15

502.3

502.3

502.3

437.5

372.7

307.9

243.1

62

482.2

55.87

482.2

482.2

482.2

417.4

352.6

287.8

223.0

502.0

51.13

502.0

502.0

502.0

437.2

372.4

307.6

242.8

57

481.8

55.85

481.8

481.8

481.8

417.0

352.2

287.4

222.6

12000

14000

16000

18000

20000

TEMPERATURE OF AIR ON CONDENSER COIL 125 F

12000

14000

16000

18000

20000

72

458.6

60.7

310.5

271.6

232.7

193.8

154.9

#N/A

#N/A

67

431.4

59.7

388.2

349.3

310.4

271.5

232.7

193.8

154.9

62

429.8

59.6

429.8

424.9

386.0

347.1

308.2

269.3

230.5

57

429.3

59.6

429.3

424.4

385.6

346.7

307.8

268.9

230.0

72

468.7

61.0

342.3

297.0

251.6

206.2

160.9

#N/A

#N/A

67

440.9

60.0

426.3

381.0

335.6

290.2

244.9

199.5

154.2

62

439.2

59.9

439.2

436.8

417.3

372.0

326.6

281.3

235.9

57

438.8

59.9

438.8

436.3

416.9

371.5

326.2

280.8

235.5

72

478.8

61.2

374.2

322.3

270.5

218.6

166.8

#N/A

#N/A

67

450.4

60.2

450.4

412.6

360.8

308.9

257.1

205.2

153.4

62

448.7

60.1

448.7

448.7

448.7

396.9

345.0

293.2

241.4

57

448.2

60.1

448.2

448.2

448.2

396.4

344.6

292.7

240.9

72

485.9

61.5

403.6

345.3

286.9

228.6

170.3

#N/A

#N/A

67

457.1

60.5

457.1

441.0

382.7

324.4

266.1

207.8

149.4

62

455.4

60.4

455.4

455.4

455.4

397.1

338.8

280.4

222.1

57

454.9

60.3

454.9

454.9

454.9

396.6

338.3

280.0

221.6

72

493.0

61.7

433.0

368.2

303.4

238.6

173.8

#N/A

#N/A

67

463.9

60.7

463.9

463.9

404.7

339.9

275.1

210.3

145.5

62

462.1

60.6

462.1

462.1

462.1

397.3

332.5

267.7

202.9

57

461.6

60.6

461.6

461.6

461.6

396.8

332.0

267.2

202.4

1
These capacities are gross ratings. For net capacity, deduct air blower motor,
MBH - 3.415 X kW. Refer to the appropriate Blower Performance Table for the
kW of the supply air blower motor.
2
These ratings include condenser fan motors and the compressor motors but
not the supply blower motor.

NOTE:HB480 matched with LB480 does not


meet ASHRAE 90.1-1999 minimum
EER requirements.

12

Unitary Products Group

Page 124

http://www.rezine.net
036-21328-003-D-0206

TABLE 12:COOLING CAPACITY 40 TON UNIT - HB480 CONDENSING UNIT MATCHED WITH LB600 EVAPORATOR UNIT
AIR ON
EVAP. COIL
CFM

12000

14000

16000

18000

20000

AIR ON
EVAP. COIL

TEMPERATURE OF AIR ON CONDENSER COIL 85 F

GROSS TOTAL GROSS SENSIBLE CAPACITY (MBh) RETURN DRY BULB


WB
( F)
CAPACITY INPUT
( F)
(Kw)
(MBH)
86
83
80
77
74
71
68

CFM

TEMPERATURE OF AIR ON CONDENSER COIL 95 F

GROSS TOTAL GROSS SENSIBLE CAPACITY (MBh) RETURN DRY BULB


WB
( F)
CAPACITY INPUT
( F)
(MBH)
(Kw)
86
83
80
77
74
71
68

72

560.5

43.11

351.8

312.9

274.1

235.2

196.3

#N/A

#N/A

72

538.6

46.93

343.6

304.7

265.8

226.9

188.0

#N/A

#N/A

67

527.2

42.15

431.8

392.9

354.1

315.2

276.3

237.4

198.5

67

506.8

45.97

423.3

384.4

345.5

306.7

267.8

228.9

190.0

62

493.5

41.25

493.5

474.2

435.3

396.4

357.5

318.7

279.8

57

505.5

41.69

505.5

502.0

463.1

424.2

385.3

346.4

307.6

12000

62

475.4

45.11

475.4

463.8

424.9

386.0

347.1

308.2

269.4

57

488.7

45.62

488.7

485.2

446.3

407.4

368.6

329.7

290.8

72

574.0

43.43

384.5

339.2

293.8

248.4

203.1

#N/A

#N/A

72

551.1

47.25

375.9

330.5

285.2

239.8

194.4

#N/A

#N/A

67

539.9

42.46

470.3

424.9

379.6

334.2

288.9

243.5

198.1

67

518.5

46.29

461.4

416.1

370.7

325.3

280.0

234.6

189.3

62

505.4

41.56

505.4

495.7

466.7

421.3

375.9

330.6

285.2

62

486.4

45.42

486.4

480.6

455.8

410.5

365.1

319.7

274.4

57

517.7

42.00

517.7

515.9

496.4

451.1

405.7

360.4

315.0

57

500.0

45.93

500.0

498.3

478.8

433.5

388.1

342.7

297.4

72

587.5

43.75

417.2

365.4

313.6

261.7

209.9

#N/A

#N/A

72

563.6

47.57

408.2

356.4

304.5

252.7

200.8

#N/A

#N/A

67

552.5

42.78

508.8

456.9

405.1

353.3

301.4

249.6

197.7

67

530.2

46.60

499.5

447.7

395.9

344.0

292.2

240.3

188.5

62

517.3

41.87

517.3

517.3

498.0

446.2

394.4

342.5

290.7

62

497.4

45.72

497.4

497.4

486.8

434.9

383.1

331.2

279.4

57

529.8

42.31

529.8

529.8

529.8

478.0

426.1

374.3

322.5

57

511.3

46.24

511.3

511.3

511.3

459.5

407.6

355.8

304.0

72

596.7

44.00

448.6

390.3

332.0

273.7

215.3

#N/A

#N/A

72

572.3

47.83

439.2

380.9

322.6

264.3

205.9

#N/A

#N/A

67

561.2

43.02

539.3

487.2

428.9

370.6

312.3

253.9

195.6

67

538.4

46.85

523.1

477.7

419.3

361.0

302.7

244.4

186.1

62

525.4

42.11

525.4

525.4

515.8

457.5

399.1

340.8

282.5

62

505.2

45.97

505.2

505.2

499.8

441.5

383.2

324.9

266.5

57

538.1

42.55

538.1

538.1

538.1

479.8

421.5

363.2

304.8

57

519.3

46.49

519.3

519.3

519.3

460.9

402.6

344.3

286.0

72

605.9

44.26

480.0

415.2

350.4

285.6

220.8

#N/A

#N/A

72

581.0

48.08

470.3

405.5

340.7

275.9

211.1

#N/A

#N/A

67

569.9

43.27

569.9

517.5

452.7

387.9

323.1

258.3

193.5

67

546.7

47.10

546.7

507.6

442.8

378.0

313.2

248.4

183.6

62

533.5

42.35

533.5

533.5

533.5

468.7

403.9

339.1

274.3

62

512.9

46.21

512.9

512.9

512.9

448.1

383.3

318.5

253.7

57

546.4

42.80

546.4

546.4

546.4

481.6

416.8

352.0

287.2

57

527.2

46.73

527.2

527.2

527.2

462.4

397.6

332.8

268.0

14000

16000

18000

20000

TEMPERATURE OF AIR ON CONDENSER COIL 105 F

12000

14000

16000

18000

20000

TEMPERATURE OF AIR ON CONDENSER COIL 115 F

72

268.2

51.61

179.9

160.4

129.6

90.7

51.8

#N/A

#N/A

72

491.2

56.29

314.6

275.7

236.8

197.9

159.1

#N/A

#N/A

67

252.9

50.66

217.1

197.6

171.4

132.6

93.7

54.8

15.9

67

463.3

55.36

391.7

352.8

313.9

275.0

236.2

197.3

158.4

62

245.7

50.03

245.7

235.6

214.0

175.2

136.3

97.4

58.5

62

451.5

54.96

451.5

431.3

392.5

353.6

314.7

275.8

236.9

57

246.2

50.28

246.2

236.1

214.9

176.0

137.1

98.3

59.4

57

451.4

54.95

451.4

431.2

392.4

353.5

314.6

275.7

236.8

72

403.3

51.93

289.1

253.4

212.1

166.7

121.4

#N/A

#N/A

72

502.3

56.60

351.5

306.1

260.8

215.4

170.0

#N/A

#N/A

67

380.0

50.98

353.7

318.0

279.0

233.7

188.3

142.9

97.6

67

473.7

55.67

436.4

391.0

345.6

300.3

254.9

209.6

164.2

62

365.1

50.34

365.1

360.1

346.7

301.3

255.9

210.6

165.2

62

461.6

55.26

461.6

451.6

432.1

386.8

341.4

296.0

250.7

57

368.8

50.59

368.8

363.8

353.2

307.8

262.5

217.1

171.8

57

461.5

55.26

461.5

451.5

432.0

386.7

341.3

295.9

250.6

72

538.5

52.25

398.3

346.4

294.6

242.8

190.9

#N/A

#N/A

72

513.4

56.92

388.4

336.5

284.7

232.8

181.0

#N/A

#N/A

67

507.2

51.29

490.3

438.5

386.6

334.8

282.9

231.1

179.3

67

484.2

55.98

481.1

429.2

377.4

325.5

273.7

221.9

170.0

62

484.6

50.65

484.6

484.6

479.3

427.4

375.6

323.8

271.9

62

471.8

55.57

471.8

471.8

471.8

419.9

368.1

316.3

264.4

57

491.5

50.90

491.5

491.5

491.5

439.7

387.8

336.0

284.1

57

471.7

55.56

471.7

471.7

471.7

419.8

368.0

316.2

264.3

72

546.5

52.48

428.7

370.4

312.1

253.8

195.5

#N/A

#N/A

72

520.7

57.14

418.3

359.9

301.6

243.3

185.0

#N/A

#N/A

67

514.8

51.52

506.3

467.9

409.6

351.3

292.9

234.6

176.3

67

491.1

56.19

489.5

458.1

399.8

341.5

283.2

224.9

166.5

62

491.8

50.88

491.8

491.8

489.2

430.8

372.5

314.2

255.9

62

478.5

55.78

478.5

478.5

478.5

420.2

361.9

303.6

245.2

57

498.8

51.13

498.8

498.8

498.8

440.5

382.2

323.9

265.6

57

478.4

55.78

478.4

478.4

478.4

420.1

361.8

303.4

245.1

72

554.5

52.72

459.2

394.4

329.6

264.8

200.0

#N/A

#N/A

72

528.0

57.36

448.2

383.4

318.6

253.8

189.0

#N/A

#N/A

67

522.3

51.75

522.3

497.4

432.6

367.8

303.0

238.2

173.4

67

498.0

56.40

498.0

487.1

422.3

357.5

292.7

227.9

163.1

62

499.1

51.10

499.1

499.1

499.1

434.3

369.5

304.7

239.9

62

485.3

56.00

485.3

485.3

485.3

420.5

355.7

290.9

226.1

57

506.2

51.36

506.2

506.2

506.2

441.4

376.6

311.8

247.0

57

485.1

55.99

485.1

485.1

485.1

420.3

355.5

290.7

225.9

12000

14000

16000

18000

20000

TEMPERATURE OF AIR ON CONDENSER COIL 125 F

12000

14000

16000

18000

20000

72

714.3

61.0

449.3

391.0

344.1

305.2

266.3

#N/A

#N/A

67

673.7

60.0

566.3

507.9

456.4

417.5

378.6

339.7

300.9

62

657.3

59.9

657.3

627.1

570.9

532.0

493.1

454.2

415.3

capacities are gross ratings. For net capacity, deduct air blower motor,
MBH - 3.415 X kW. Refer to the appropriate Blower Performance Table for the
kW of the supply air blower motor.

57

656.5

59.6

656.5

626.4

569.8

530.9

492.1

453.2

414.3

2These

72

601.3

61.3

413.9

358.8

309.4

264.1

218.7

#N/A

#N/A

67

567.4

60.4

519.0

464.0

412.3

366.9

321.5

276.2

230.8

62

558.1

60.2

558.1

543.0

517.6

472.2

426.9

381.5

336.1

57

554.2

59.9

554.2

539.1

510.8

465.5

420.1

374.8

329.4

72

488.2

61.6

378.5

326.6

274.8

222.9

171.1

#N/A

#N/A

67

461.1

60.7

461.1

420.0

368.1

316.3

264.5

212.6

160.8

62

459.0

60.5

459.0

459.0

459.0

412.5

360.6

308.8

256.9

57

451.8

60.2

451.8

451.8

451.8

400.0

348.2

296.3

244.5

72

494.9

61.8

407.8

349.5

291.1

232.8

174.5

#N/A

#N/A

67

467.4

60.9

467.4

448.4

390.1

331.7

273.4

215.1

156.8

62

465.2

60.7

465.2

465.2

465.2

409.6

351.2

292.9

234.6

57

458.0

60.4

458.0

458.0

458.0

399.7

341.3

283.0

224.7

72

501.5

62.0

437.1

372.3

307.5

242.7

177.9

#N/A

#N/A

67

473.7

61.1

473.7

473.7

412.0

347.2

282.4

217.6

152.8

62

471.5

60.9

471.5

471.5

471.5

406.7

341.9

277.1

212.3

57

464.1

60.6

464.1

464.1

464.1

399.3

334.5

269.7

204.9

Unitary Products Group

1These

ratings include condenser fan motors and the compressor motors but not
the supply blower motor.

13

Page 125

http://www.rezine.net
036-21328-003-D-0206

TABLE 13:COOLING CAPACITY 50 TON UNIT - HB600 CONDENSING UNIT MATCHED WITH LB600 EVAPORATOR UNIT
AIR ON
EVAP. COIL
CFM

15000

17500

20000

22500

25000

AIR ON
EVAP. COIL

TEMPERATURE OF AIR ON CONDENSER COIL 85 F

GROSS TOTAL GROSS SENSIBLE CAPACITY (MBh) RETURN DRY BULB


WB
( F)
CAPACITY INPUT
( F)
(Kw)
(MBH)
86
83
80
77
74
71
68

CFM

TEMPERATURE OF AIR ON CONDENSER COIL 95 F

GROSS TOTAL GROSS SENSIBLE CAPACITY (MBh) RETURN DRY BULB


WB
( F)
CAPACITY INPUT
( F)
(MBH)
(Kw)
86
83
80
77
74
71
68

72

728.4

42.69

453.2

404.6

356.0

307.4

258.8

#N/A

#N/A

72

649.8

55.19

415.6

367.0

318.4

269.8

221.2

#N/A

#N/A

67

633.9

49.43

526.2

477.6

429.0

380.4

331.8

283.2

234.6

67

609.1

54.35

513.9

465.3

416.7

368.1

319.5

270.9

222.3

62

592.2

48.61

592.2

578.8

530.2

481.6

433.0

384.4

335.8

62

569.9

53.61

569.9

559.3

510.7

462.1

413.5

364.9

316.3

57

617.2

49.06

617.2

617.2

570.2

521.6

473.0

424.4

375.8

57

595.3

54.16

595.3

593.3

544.7

496.1

447.5

398.9

350.3

72

745.7

42.94

493.2

436.5

379.8

323.1

266.4

#N/A

#N/A

72

665.3

55.44

454.9

398.2

341.5

284.8

228.1

#N/A

#N/A

67

648.9

49.73

571.0

514.3

457.6

400.9

344.2

287.5

230.8

67

623.7

54.60

560.3

503.6

446.9

390.2

333.5

276.8

220.1

62

606.2

48.90

606.2

599.5

565.6

508.9

452.2

395.5

338.8

62

583.5

53.86

583.5

578.2

547.8

491.1

434.4

377.7

321.0

57

631.8

49.36

631.8

631.8

608.3

551.6

494.9

438.2

381.5

57

609.6

54.41

609.6

608.6

584.3

527.6

470.9

414.2

357.5

72

762.9

43.20

533.2

468.4

403.6

338.8

274.0

#N/A

#N/A

72

680.9

55.70

494.2

429.4

364.6

299.8

235.0

#N/A

#N/A

67

663.8

50.03

615.9

551.1

486.3

421.5

356.7

291.9

227.1

67

638.3

54.86

606.8

542.0

477.2

412.4

347.6

282.8

218.0

62

620.2

49.20

620.2

620.2

601.0

536.2

471.4

406.6

341.8

62

597.1

54.11

597.1

597.1

584.9

520.1

455.3

390.5

325.7

57

646.4

49.66

646.4

646.4

646.4

581.6

516.8

452.0

387.2

57

623.8

54.66

623.8

623.8

623.8

559.0

494.2

429.4

364.6

72

775.9

43.36

574.0

501.1

428.2

355.3

282.4

#N/A

#N/A

72

692.0

55.90

532.2

459.3

386.4

313.5

240.6

#N/A

#N/A

67

675.1

50.20

651.2

588.8

515.9

443.0

370.1

297.2

224.3

67

648.7

55.05

632.9

578.6

505.7

432.8

359.9

287.0

214.1

62

630.8

49.37

630.8

630.8

621.2

548.3

475.4

402.5

329.6

62

606.9

54.30

606.9

606.9

600.7

527.8

454.9

382.0

309.1

57

657.4

49.83

657.4

657.4

657.4

584.5

511.6

438.7

365.8

57

634.0

54.86

634.0

634.0

634.0

561.1

488.2

415.3

342.4

72

788.9

43.51

614.8

533.8

452.8

371.8

290.8

#N/A

#N/A

72

703.1

56.10

570.2

489.2

408.2

327.2

246.2

#N/A

#N/A

67

686.4

50.38

686.4

626.6

545.6

464.6

383.6

302.6

221.6

67

659.1

55.25

659.1

615.3

534.3

453.3

372.3

291.3

210.3

62

641.4

49.54

641.4

641.4

641.4

560.4

479.4

398.4

317.4

62

616.6

54.49

616.6

616.6

616.6

535.6

454.6

373.6

292.6

57

668.4

50.01

668.4

668.4

668.4

587.4

506.4

425.4

344.4

57

644.2

55.05

644.2

644.2

644.2

563.2

482.2

401.2

320.2

15000

17500

20000

22500

25000

TEMPERATURE OF AIR ON CONDENSER COIL 105 F

15000

17500

20000

22500

25000

TEMPERATURE OF AIR ON CONDENSER COIL 115 F

72

622.8

61.34

405.7

357.1

308.5

259.9

211.3

#N/A

#N/A

72

595.7

67.50

395.8

347.2

298.6

250.0

201.4

#N/A

#N/A

67

583.9

60.46

503.5

454.9

406.3

357.7

309.1

260.5

211.9

67

558.6

66.57

493.1

444.5

395.9

347.3

298.7

250.1

201.5

62

562.1

59.99

562.1

556.3

507.7

459.1

410.5

361.9

313.3

62

554.4

66.37

554.4

553.2

504.6

456.0

407.4

358.8

310.2

57

574.7

60.26

574.7

573.1

524.5

475.9

427.3

378.7

330.1

57

554.0

66.35

554.0

552.9

504.3

455.7

407.1

358.5

309.9

72

636.7

61.63

444.2

387.5

330.8

274.1

217.4

#N/A

#N/A

72

608.1

67.81

433.5

376.8

320.1

263.4

206.7

#N/A

#N/A

67

596.9

60.74

548.9

492.4

435.7

379.0

322.3

265.6

208.9

67

570.1

66.88

537.4

481.1

424.4

367.7

311.0

254.3

197.6

62

574.7

60.27

574.7

571.8

544.4

487.7

431.0

374.3

317.6

62

565.9

66.68

565.9

565.3

541.0

484.3

427.6

370.9

314.2

57

587.5

60.54

587.5

586.7

562.4

505.7

449.0

392.3

335.6

57

565.5

66.66

565.5

564.9

540.6

483.9

427.2

370.5

313.8

72

650.6

61.91

482.7

417.9

353.1

288.3

223.5

#N/A

#N/A

72

620.4

68.12

471.2

406.4

341.6

276.8

212.0

#N/A

#N/A

67

610.0

61.02

594.2

529.9

465.1

400.3

335.5

270.7

205.9

67

581.7

67.18

581.7

517.8

453.0

388.2

323.4

258.6

193.8

62

587.2

60.55

587.2

587.2

581.1

516.3

451.5

386.7

321.9

62

577.3

66.98

577.3

577.3

577.3

512.5

447.7

382.9

318.1

57

600.4

60.82

600.4

600.4

600.4

535.6

470.8

406.0

341.2

57

576.9

66.97

576.9

576.9

576.9

512.1

447.3

382.5

317.7

72

661.4

62.11

520.5

447.6

374.7

301.8

228.9

#N/A

#N/A

72

630.7

68.32

508.9

436.0

363.1

290.2

217.3

#N/A

#N/A

67

620.0

61.22

612.2

566.5

493.6

420.7

347.8

274.9

202.0

67

591.4

67.38

591.4

554.4

481.5

408.6

335.7

262.8

189.9

62

596.9

60.74

596.9

596.9

593.9

521.0

448.1

375.2

302.3

62

587.0

67.18

587.0

587.0

587.0

514.1

441.2

368.3

295.4

57

610.3

61.01

610.3

610.3

610.3

537.4

464.5

391.6

318.7

57

586.5

67.16

586.5

586.5

586.5

513.6

440.7

367.8

294.9

72

672.1

62.31

558.4

477.4

396.4

315.4

234.4

#N/A

#N/A

72

641.1

68.52

546.6

465.6

384.6

303.6

222.6

#N/A

#N/A

67

630.1

61.41

630.1

603.1

522.1

441.1

360.1

279.1

198.1

67

601.1

67.58

601.1

591.0

510.0

429.0

348.0

267.0

186.0

62

606.6

60.93

606.6

606.6

606.6

525.6

444.6

363.6

282.6

62

596.6

67.37

596.6

596.6

596.6

515.6

434.6

353.6

272.6

57

620.2

61.21

620.2

620.2

620.2

539.2

458.2

377.2

296.2

57

596.1

67.36

596.1

596.1

596.1

515.1

434.1

353.1

272.1

15000

17500

20000

22500

25000

TEMPERATURE OF AIR ON CONDENSER COIL 125 F

15000

17500

20000

22500

25000

72

568.7

73.6

385.9

337.3

288.7

240.1

191.5

#N/A

#N/A

67

533.3

72.7

482.7

434.1

385.5

336.9

288.3

239.7

191.1

62

546.7

72.7

546.7

546.7

501.6

453.0

404.4

355.8

307.2

capacities are gross ratings. For net capacity, deduct air blower motor,
MBH - 3.415 X kW. Refer to the appropriate Blower Performance Table for the
kW of the supply air blower motor.

57

533.3

72.5

533.3

532.7

484.1

435.5

386.9

338.3

289.7

2These

72

579.4

74.0

422.8

366.1

309.4

252.7

196.0

#N/A

#N/A

67

543.3

73.0

525.9

469.9

413.2

356.5

299.8

243.1

186.4

62

557.1

73.1

557.1

557.1

537.6

480.9

424.2

367.5

310.8

57

543.4

72.8

543.4

543.1

518.8

462.1

405.4

348.7

292.0

72

590.1

74.3

459.7

394.9

330.1

265.3

200.5

#N/A

#N/A

67

553.4

73.3

553.4

505.7

440.9

376.1

311.3

246.5

181.7

62

567.5

73.4

567.5

567.5

567.5

508.8

444.0

379.2

314.4

57

553.5

73.1

553.5

553.5

553.5

488.7

423.9

359.1

294.3

72

600.1

74.5

497.2

424.3

351.4

278.5

205.6

#N/A

#N/A

67

562.7

73.5

562.7

542.3

469.4

396.5

323.6

250.7

177.8

62

577.0

73.6

577.0

577.0

577.0

507.2

434.3

361.4

288.5

57

562.8

73.3

562.8

562.8

562.8

489.9

417.0

344.1

271.2

72

610.0

74.7

534.8

453.8

372.8

291.8

210.8

#N/A

#N/A

67

572.0

73.7

572.0

572.0

497.9

416.9

335.9

254.9

173.9

62

586.6

73.8

586.6

586.6

586.6

505.6

424.6

343.6

262.6

57

572.1

73.5

572.1

572.1

572.1

491.1

410.1

329.1

248.1

1These

ratings include condenser fan motors and the compressor motors but not
the supply blower motor.

14

Unitary Products Group

Page 126

http://www.rezine.net
036-21328-003-D-0206

Note 1

Note 1. See page 16 and 22 for details


on wiring HA/HB models to non LA/LB
indoor models.

FIGURE 1 - TYPICAL FIELD WIRING FOR HA300 & LA300

Unitary Products Group

15

Page 127

http://www.rezine.net
036-21328-003-D-0206

Note 1

Note 1. Typical field wiring when OD unit is


matched with LA/LB air handler. When matching
condensing unit with models other than LA/LB an
additional control transformer is required on the
indoor unit. See wiring diagram page 21.

FIGURE 2 - TYPICAL FIELD WIRING FOR HB360,480,600 & LB360,480,600

CONTROL
BOX

FIGURE 3 - FAN ORIENTATION CONTROL BOX END


See Fan Operation on page 23 of Installation Instruction.

16

Unitary Products Group

Page 128

http://www.rezine.net
036-21328-003-D-0206

TABLE 14:CORNER WEIGHTS & CENTER OF GRAVITY (INCHES)


Unit Model

Unit Weight (Lbs.)


Shipping Operation

Unit Dimensions
(Inches)
Length

Width

Dim X

Dim Y

Weight
A to D

Weight
B to C

HA300

1608

1658

110.46

88.46

337

412

472

386

49.7

47.7

723.5

884.5

HB360

1730

1790

110.46

88.46

363

531

497

339

44.8

42.8

701.6

1028.4

HB480

1961

2037

128.46

88.46

393

598

585

385

51.0

43.8

778.5

1182.5

HB600

2470

2563

128.46

88.46

470

757

767

476

49.2

44.5

946.0

1524.0

FIGURE 4 - CORNER WEIGHTS & CENTER OF GRAVITY

Unitary Products Group

17

Page 129

http://www.rezine.net
036-21328-003-D-0206

REAR
B

LEFT
A

G
H
D
E
RIGHT
FRONT

FIGURE 5 - HA/HB UNIT DIMENSIONS


TABLE 15:UNIT DIMENSIONS (INCHES)
MODEL

HA300

110.5

88.5

37.5

32.8

31.0

46.1

37.1

23.6

HB360

110.5

88.5

37.5

32.8

31.0

46.1

37.1

23.6

HB480

128.5

88.5

37.5

41.8

40.0

46.1

37.1

23.6

HB600

128.5

88.5

57.7

41.8

40.0

46.1

37.1

23.6

PIPING AND ELECTRICAL CONNECTIONS


Piping connections are made from the rear of the unit.
Connections can be made directly to the suction and
liquid piping or if so equipped to the optional suction
and liquid line service valves.

6 thru 10 for piping sizes and electrical knockout


details.
TABLE 16:UNIT CLEARANCES
Location
Overhead (Top)

With the piping connections being made at the rear of


the unit, piping can be routed to the unit from the left or
right side.
Electrical connections for power and control wiring is
made from the front of the unit, left of the electrical control box access. See Tables 17, 18 and 19 and Figures

Dimensions
*

120

Front access panels

36

Left Side

30

Right Side

30

Rear

24

Bottom

Units must be installed outdoors. Overhanging structures or


shrubs should not obstruct condenser air discharge.
Adequate snow clearance must be provided if winter operation
is expected.

18

Unitary Products Group

Page 130

http://www.rezine.net
036-21328-003-D-0206

TABLE 18:PIPING AND ELECTRICAL


CONNECTION SIZES (30/40/50T)
(INCHES)

TABLE 17:PIPING AND ELECTRICAL


CONNECTION SIZES (25T) (INCHES)
CONNECTION ENTRY

SIZE

SUCTION LINE SYS #1

1-5/8 OD

LIQUID LINE SYS #1

7/8 OD

POWER WIRING KNOCKOUT

SEE TABLE 12

CONTROL WIRING

7/8 HOLE

CONNECTION ENTRY

SIZE

SUCTION LINE SYS #1

1-5/8 OD

LIQUID LINE SYS #1

7/8 OD

SUCTION LINE SYS #2

1-5/8 OD

LIQUID LINE SYS #2

7/8 OD

POWER WIRING KNOCKOUT

SEE TABLE 12

CONTROL WIRING

7/8 HOLE

TABLE 19:ELECTRICAL POWER KNOCKOUT SIZES (INCHES)


CONNECTION ENTRY
E

POWER WIRING

25T/230V

25T/460-575V

30-40-50T/230V

30-40-50T/460-575V

1-1/2

2-1/2

1-1/2

Liquid

Suction

FIGURE 6 - 25 TON PIPING CONNECTIONS

Unitary Products Group

19

Page 131

http://www.rezine.net
036-21328-003-D-0206

FIGURE 7 - 30 & 40 TON PIPING CONNECTIONS

Liquid (Sys 2)
Suction (Sys 2)
Suction (Sys 1)
Liquid (Sys 1)

FIGURE 8 - 50 TON PIPING CONNECTIONS

20

Unitary Products Group

Page 132

http://www.rezine.net
036-21328-003-D-0206

Control Wiring
Power Wiring

FIGURE 9 - 25,30 & 40 TON POWER AND CONTROL WIRING CONNECTIONS

Control Wiring
Power Wiring

FIGURE 10 - 50 TON POWER AND CONTROL WIRING CONNECTIONS

Unitary Products Group

21

Page 133

http://www.rezine.net
036-21328-003-D-0206

GUIDE SPECIFICATIONS
MODELS HA300,HB360,HB480 and HB600
CONDENSING UNITS
EACH COMPRESSOR shall be mounted on isolators to minimize the transmission of vibration.

THE INSTALLER SHALL:


Furnish York air-cooled condensing units or equivalent
in accordance with the performance schedule shown on
the plans, and
Install each unit as shown on the plans in accordance
with:
The manufacturers recommendations and

ALL CONDENSER COILS SHALL:


Be draw thru
Be constructed of copper tubes arranged in staggered
rows and mechanically expanded into aluminum fins.
THE CONDENSER FAN MOTOR(S) SHALL:

All applicable national and local codes

Be directly connected to the condenser fans.

EACH UNIT SHALL be:

Have permanently lubricated ball bearings.

ETL and cETL approved.


Completely assembled for one-piece shipping and rigging.
Leak pressure and functionally tested at the factory to
assure a trouble-free start-up after installation.
Covered by a 1-year limited parts warranty on the complete unit.
In current production with published literature available
to check performance, limitations, specifications, power
requirements, dimensions, operation and appearance.
EACH UNIT SHALL HAVE:
A steel angle frame to provide the rigid support required
for shipping, rigging and years of dependable operation.
Zinc-coated steel that has been finished by a powder
paint process to provide a long lasting, quality appearance.
Removable panels for easy access to all internal components during maintenance and service.
THE DIMENSIONS OF EACH UNIT shall not exceed those
specified on the plans.

Unitary Products Group

Have inherent overload protection.


Motors shall be three phase.
The propeller-type condenser fans shall be arranged for
vertical discharge of the condenser air.
THE WIRING FOR EACH UNIT SHALL INCLUDE:
A crankcase heater (one per compressor)
All 24-volt temperature control circuit.
Both high and low pressure cutouts.
Solid-state or internal line break compressor motor protection.
Condenser fan motor control to assure stable operation
at ambient temperatures down to 40 F.
THE REFRIGERANT PIPING of each system shall include:
A filter-drier shipped for field installation.
A liquid line, moisture-indicating, sight glass shipped for
field installation.

23

Page 134

http://www.rezine.net

246668-YTG-B-0906

DESCRIPTION

Technical Guide

These completely assembled units include a well-insulated cabinet, a


DX cooling coil with copper tubes and aluminum fins, expansion
valve(s), distributor(s), throwaway filters, a centrifugal blower, a blower
motor, an adjustable belt drive, a blower motor contactor and a small
holding charge of refrigerant-22.
The units are shipped in the vertical position ready for field installation.
They can be installed for horizontal operation by reversing the position
of the solid bottom panel with the return air duct flange on the front of
the unit.

ACCESSORIESFIELD INSTALLED
SUPPLY AIR PLENUMS

SPLIT-SYSTEM
EVAPORATOR BLOWERS
K2EU060, K4EU090, K3EU120 &
K3EU180

These fully insulated plenums are available for free standing units
located within the conditioned space, are shipped knocked-down for
easy field assembly, are finished to match the exterior of the basic
unit, and have double deflection grills that can be adjusted to vary the
throw, spread and drop of the supply air.

RETURN AIR GRILLS

5 THRU 15 NOMINAL TONS

These expanded metal grills are available for free standing units
located within the conditioned space, are finished to match the exterior
of the basic unit and are shipped in one piece for easy installation.

BASES
Bases are available to raise vertical units above the floor. Outdoor air
may be introduced through these bases by cutting an access opening
to accommodate the outdoor air duct connection. These bases are finished to match the exterior of the basic unit. They may have to be insulated in the field for certain applications.

THREE-PHASE ELECTRIC HEATERS


Electric heaters are available in several capacities to provide maximum flexibility. Both the air conditioning unit and the heater can be
selected to precisely match the cooling and heating requirements of
the conditioned space. These heaters are designed for easy field
installation over the supply air opening of the unit. They have been
tested by and will be shipped with a CSA label. Every heater will be
fully protected against excessive current and temperature by fuses
and two high limit thermostats.
Units with electric heat will require only one power supply for both the
heating elements and the supply air blower motor, and the power wiring can be protected by either dual element/time delay fuses or an
inverse time circuit breaker.

FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE

Page 135

http://www.rezine.net
246668-YTG-B-0906

TABLE OF CONTENTS
LIST OF TABLES

DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
ACCESSORIESFIELD INSTALLED . . . . . . . . . . . . . . . . 1

Tbl. #

NOMENCLATURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

UNIT SUSPENSION MOUNTING (HORIZONTAL


APPLICATION) WEIGHTS . . . . . . . . . . . . . . . . . . . . . 5

KEU OPERATING WEIGHTS (LBS.) . . . . . . . . . . . . . 5

SOUND POWER RATINGS . . . . . . . . . . . . . . . . . . . . 6

Pg. #

VERTICAL AND HORIZONTAL APPLICATION


KEU060, 090 & 120 . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

HEATING CAPACITY - ELECTRIC HEAT


ACCESSORY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

STEAM COIL CAPACITY, MBH@2 PSIG . . . . . . . . . 8

VERTICAL AND HORIZONTAL APPLICATION


KEU180 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

HOT WATER CAPACITY, MBH . . . . . . . . . . . . . . . . . 8

SUSPENSION MOUNTING (HORIZONTAL) - KEU060,


090 AND 120 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

PRESSURE DROP VS. GPM . . . . . . . . . . . . . . . . . . . 8

CAPACITY CORRECTION VS. GPM . . . . . . . . . . . . . 8

APPLICATION FLEXIBILITY . . . . . . . . . . . . . . . . . . . . . . . 4

LIST OF FIGURES
Fig. #

Pg. #

SUSPENSION ACCESSORY (HORIZONTAL) KEU180 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

SUPPLY AIR BLOWER PERFORMANCE - KEU060


(5 TON) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

UNIT DIMENSIONS KEU060 . . . . . . . . . . . . . . . . . . 16

10

UNIT DIMENSIONS KEU090 & 120 . . . . . . . . . . . . . 17

SUPPLY AIR BLOWER PERFORMANCE - KEU090


(7.5 TON) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

UNIT DIMENSIONS KEU180 . . . . . . . . . . . . . . . . . . 18

11

SUPPLY AIR BLOWER PERFORMANCE - KEU120


(10 TON) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

ACCESSORY DIMENSIONS . . . . . . . . . . . . . . . . . . 19

12

RETURN AIR GRILL . . . . . . . . . . . . . . . . . . . . . . . . . 20

SUPPLY AIR BLOWER PERFORMANCE - KEU180


(15 TON) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

10

BASE ACCESSORY . . . . . . . . . . . . . . . . . . . . . . . . . 20

13

11

STEAM COIL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

STATIC RESISTANCE FOR UNIT ACCESSORIES


(IWG) - KEU060-120 . . . . . . . . . . . . . . . . . . . . . . . . . 13

12

HOT WATER COIL . . . . . . . . . . . . . . . . . . . . . . . . . . 21

14

STATIC RESISTANCE FOR UNIT ACCESSORIES


(IWG) - KEU180 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

13

FIELD WIRING FOR POWER SUPPLY . . . . . . . . . . 24

15

SUPPLY AIR PLENUM PERFORMANCE DATA . . . 14

14

COOLING ONLY UNIT . . . . . . . . . . . . . . . . . . . . . . . 24

16

BLOWER MOTOR AND DRIVE DATA . . . . . . . . . . . 14

15

UNIT WITH STEAM OR HOT WATER COIL


ACCESSORY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

17

KEU PHYSICAL DATA . . . . . . . . . . . . . . . . . . . . . . . 15

16

FIELD WIRING FOR UNITS WITH ELECTRIC


HEAT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

18

UNIT CLEARANCES KEU060 . . . . . . . . . . . . . . . . . 16

19

UNIT CLEARANCES KEU090 & 120 . . . . . . . . . . . . 17

20

UNIT CLEARANCES KEU180 . . . . . . . . . . . . . . . . . 18

21

ELECTRIC HEATER DIMENSIONS KEU060, 090,


120 & 180 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

22

KEU ELECTRICAL DATA . . . . . . . . . . . . . . . . . . . . . 22

Unitary Products Group

Page 136

http://www.rezine.net
246668-YTG-B-0906

NOMENCLATURE

<RUN,QGRRU6SOLW6\VWHP3URGXFW1RPHQFODWXUH
.  (8  $ 
3URGXFW&DWHJRU\

9ROWDJH&RGH
 

. $LU+DQGOHU6SOLW6\VWHP$&

 

3URGXFW*HQHUDWLRQ

 

 )RXUWK*HQHUDWLRQ

3URGXFW,GHQWLILHU
+HDW7\SH 1RPLQDO+HDW&DSDFLW\

(8 56WDQG(II3LSH

$ &RROLQJ2QO\6XLWDEOHIRUILHOGLQVWDOOHGHOHFWULFKHDW

1RPLQDO&RROLQJ
&DSDFLW\0%+
 7RQ
 7RQ
 7RQ
 7RQ

ACCESSORIES-FIELD INSTALLED (CONT.)


HOT WATER COILS
These drainable coils have 2 rows of 1/2" copper tubes, 12
aluminum fins per inch, a casing that is finished to match the
exterior of the basic unit, but no water control valve. The coils
slide out of their casings for easy field installation. They
should be mounted over the return air opening on 5, 7-1/2
and 10-ton unitsbetween the unit coil and blower sections
on 15-ton units.

but no steam control valve. The coils slide out of their casings
for easy field installation and are pitched in their casings to
facilitate condensate drainage. They should be mounted over
the return air opening on 5, 7-1/2 and 10-ton unitsbetween
the unit coil and blower sections on 15-ton units.

SUSPENSION KIT
Suspension kit 1HH0451 is available for 15-ton units installed
horizontally. The accessory includes two channel iron supports and the hardware to secure them to the top of the unit.
The hanger rods must be supplied by the field.

STEAM COILS

THERMOSTATS

These non-freeze coils have 1 row of 1" copper tubes, a 5/8"


copper tube inside each 1" tube to distribute the steam evenly
across the entire length of the coil, 8 aluminum fins per inch,
a casing that is finished to match the exterior of the basic unit,

Wall-mounted thermostats and subbases (24-volt) with system and fan switches are available to control the operation of
these split system air conditioners.

Unitary Products Group

Page 137

http://www.rezine.net
246668-YTG-B-0906

APPLICATION FLEXIBILITY

$,5
287

MODELS 5, 7-1/2 & 10 TON


%/2:(5

%/2:(502725

5(7851$,5
'8&7)/$1*(

&2,/
&21'(16$7(
'5$,1
&211(&7,21

$,5
,1

&21'(16$7(
'5$,13$1

),/7(56

9(57,&$/326,7,21

These units are built in a single cabinet with two condensate


drain pans. This allows the units to be installed in either the
vertical or horizontal position for maximum flexibility.
On vertical applications, the air velocity across the cooling
coil keeps the condensate from dripping off the finned surface onto the filters.
On horizontal applications, the unit must be installed with the
condensate drain pan under the entire cooling coil.

),/7(56
5(7851
$,5'8&7
)/$1*(

&2,/
%/2:(5

$,5
,1

$,5
287

&21'(16$7(
'5$,1&211(&7,21

%/2:(502725
&21'(16$7('5$,13$1

+25,=217$/326,7,21

The Supply Air Plenum and the Return Air Grill accessories can be used on either arrangement.
The Base accessory can only be used on the vertical
arrangement.

Units installed horizontally are designed for ceiling suspension. Four 3/8"-16 weld nuts are provided in the angle supports on the front of the unit (the side with the logo).
Knockouts are provided in the exterior panels for access to
these weld nuts. The hanger rods must be supplied in the
field.

FIGURE 1 - VERTICAL AND HORIZONTAL


APPLICATION KEU060, 090 & 120

MODEL 15 TON
These units have two distinct modules . . . a blower module
and a coil module. Although the unit is always shipped in the
vertical position with a vertical air discharge as shown in illustration (a), the blower module can be repositioned in the field
as shown in illustrations (b) and (c) for maximum flexibility.

(VERTICAL POSITION)

The Supply Air Plenum, Return Air Grill and Base accessories can be applied on arrangement (a).
The Return Air Grill and Base accessories can be
applied on arrangement (b).
The Supply Air Plenum, Return Air Grill and Suspension
accessories can be applied on arrangement (c).

(HORIZONTAL POSITION)

FIGURE 2 - VERTICAL AND HORIZONTAL


APPLICATION KEU180

Unitary Products Group

Page 138

http://www.rezine.net
246668-YTG-B-0906



 
:(/'18876

 .(8
 .(8

 +%5
 +%5 

 +%5
 +%5 

'

;
&(17(5
2)*5$9,7<

&
<

!)2
).

!)2
/54

5(7851$,5*5,//+27:$7(5&2,/
$1'67($0&2,/$&&(6625,(6
,167$//('217+,6(1'2)7+(81,7

6833/<$,53/(180$1'
(/(&75,&+($7(5$&&(6625,(6
,167$//('217+,6(1'2)7+(
81,7

FIGURE 3 - SUSPENSION MOUNTING (HORIZONTAL) - KEU060, 090 AND 120


TABLE 1: UNIT SUSPENSION MOUNTING (HORIZONTAL APPLICATION) WEIGHTS
Unit Model
K*EU060
K*EU090
K*EU120
K*EU180

Shipping
Weight
(lb)
225
340
370
440

Operating
Weight
(lb)
210
235
355
425

CG (in)

4-Point Loading (lb)

22.50
26.50
26.50
26.50

15.00
24.00
24.00
24.00

47
78
86
104

51
84
92
77

58
84
92
104

53
78
86
141

TABLE 2: KEU OPERATING WEIGHTS (LBS.)


MODEL
BASIC UNIT

ACCESSORIES

(Cooling Only)
Base
Return Air Grill
Supply Air Plenum
Hot Water Coil
Steam Coil
10 KW
16 KW
Electric Heater
26 KW
36 KW
72 KW

Unitary Products Group

060
210
45
10
90
70
80

090
325
55
15
100
105
115

120
325
55
15
100
105
115

180
425
65
20
115
135
145

66
70
74
77
125

Page 139

http://www.rezine.net
246668-YTG-B-0906

 +DQJHU5RGV
)LHOG6XSSOLHG


6XVSHQVLRQ
&KDQQHOV

$,5,1
&2,/
6(&7,21

%/2:(5
6(&7,21

$,52
87

5(7851$,5*5,//(
$FFHVVRU\,QVWDOOHG
2Q7KLV(QG2I8QLW

5HIHUWR3DUW1R
IRU
LQVWDOODWLRQLQVWUXFWLRQVRQ
WKHVXVSHQVLRQDFFHVVRU\
DQGIRUWKHLQGLYLGXDOORDG
RQHDFKKDQJHUURG

6833/<$,53/(180
$QG(/(&75,&+($7(5
$FFHVVRULHV,QVWDOOHG2Q
7KLV(QG2I8QLW

FIGURE 4 - SUSPENSION ACCESSORY (HORIZONTAL) - KEU180

TABLE 3: SOUND POWER RATINGS


ESP
UNIT
MODEL

SOUND POWER (dB 10-12 WATTS)

BLOWER

OCTAVE BAND CENTERLINE FREQUENCY (HZ)


CFM
IWG

RPM

BHP

63

125

250

500

1,000

2,000

4,000

8,000

SWL dB(a)

dB(A)
@
10 FT.1

060

2,000

0.50

940

0.70

88

88

78

71

73

66

61

56

77

44

090

3,000

0.60

750

1.05

88

88

78

73

71

66

61

56

77

45

120

4,000

0.70

850

1.75

91

91

81

74

76

69

64

59

81

48

180

6,000

0.75

750

2.75

95

95

85

80

78

73

68

63

84

52

1. At a distance of 10 feet from the blower.


NOTE:

These values have been accessed using a model of sound propagation from a point source into the hemispheric free field. The dBA values provided are
for reference only. Calculation of dBA values cover matters of system design and the fan manufacturer has no way of knowing the details of each system. This constitutes an exception to any specification or guarantee requiring a dBA value or sound data in any other form than sound power level ratings.

Unitary Products Group

Page 140

http://www.rezine.net
246668-YTG-B-0906

TABLE 4: HEATING CAPACITY - ELECTRIC HEAT ACCESSORY


CAPACITY

NOMINAL RATINGS1
UNIT MODEL

HEATER MODEL

2HT045010
060

2HT045016
2HT045026

2HS045016

2HS045036

2HS045010

2HS045016

180

2HS045026

2HS045036

2HS045072

2ND STAGE

KW

MBH

KW

MBH

KW

MBH

208 / 2402

10

34.2

10

34.2

25

208 /

2402

16

54.7

10

34.2

20.5

208 /

2402

26

88.9

16

54.7

10

34.2

208 /

2402
10

34.2

10

34.2

16

54.7

10

34.2

20.5

26

88.9

16

54.7

10

34.2

36

123

16

54.7

20

68.3

10

34.2

10

34.2

16

54.7

10

34.2

20.5

26

88.9

16

54.7

10

34.2

36

123

16

54.7

20

68.3

72

246

36

123

36

123

25

46

4803

58

6004

25

208 / 2402

46

4803

58

6004

25

208 / 2402

46

4803

090, 120
2HS045026

1ST STAGE

25

25
2HS045010

VOLTAGE TEST

58

6004

25

208 / 2402

46

4803

58

600

25

208 / 2402

46

2803

58

600

25

208 / 2402

46

2803

58

6004

25

208 / 2402

46

2803
4

58

600

25

208 / 2402

46

2803

58

600

25

208 / 2402

46

2803

58

600

1. Capacity Ratings do not include the heat generated by the air blower motor.
2. For 208 volts, multiply the MBH and KW by (208/240) or 0.751.
For 230 volts, multiply the MBH and KW by (230/240) or 0.918.
3. For 460 volts, multiply the MBH and KW by (460/480) or 0.918.
4. For 575 volts, multiply the MBH and KW by (575/600) or 0.918.

Unitary Products Group

Page 141

http://www.rezine.net
246668-YTG-B-0906

TABLE 5: STEAM COIL CAPACITY1, MBH@2 PSIG2


STEAM COIL
MODEL

UNIT MODEL

DRY BULB TEMPERATURE OF AIR ENTERING COIL, F

CFM

10

30

50

70

104.0

94.0

83.9

73.9

2000

115.2

104.0

93.1

81.9

2400

124.9

113.0

100.9

89.0

2400

172.2

155.5

139.1

122.4

3000

191.2

172.6

154.3

136.0

3600

207.5

187.1

167.4

147.4

3200

196.4

177.6

158.8

140.0

4000

217.3

195.3

175.3

154.8

4800

236.1

212.9

190.4

167.8

4800

298.2

268.4

236.7

211.5

6000

329.1

297.0

265.6

234.1

7200

356.4

321.8

287.9

254.0

1600
1NF0450

060

090
1NF0451
120

1NF0452

180

1. These capacities do not include any blower motor heat.


2. Multiply these capacities by the following factors to correct for higher steam pressures.
Steam Pressure, psig
Capacity correction factor

10

15

20

25

1.05

1.12

1.19

1.25

1.30

NOTE: Steam rate (lb./hr.) = 1.025 x MBH


CAUTION: Do NOT operate a motor above its nominal HP rating when a unit is equipped with a steam coil accessory.

TABLE 6: HOT WATER CAPACITY1, MBH


WATER COIL MODEL

UNIT MODEL

1HW0450

GPM

060

CFM

10

090

15

1HW0451
120

1HW0452

15

180

20

ENTERING WATER TEMP. MINUS ENTERING AIR TEMP., F


70

90

110

130

150

1600

46.5

60.4

74.6

89.0

101.8

2000

51.7

67.2

83.0

99.2

113.4

2400

56.0

73.0

90.4

107.9

123.3

2400

78.0

101.3

124.7

148.5

169.7

3000

87.7

113.3

139.6

166.6

190.4

3600

95.5

124.0

153.0

182.1

208.1

3200

90.3

117.1

144.6

172.1

196.6

4000

100.2

130.2

160.7

191.3

218.6

4800

108.3

140.9

174.3

207.5

237.4

4800

135.5

175.1

215.8

257.4

294.1

6000

150.0

195.0

240.3

285.9

326.6

7200

162.4

210.8

260.4

309.8

354.3

1. These capacities do no include any blower motor heat.


NOTE: Water Temperature Drop, 0F = 2 x MBH
CAUTION: Do NOT operate a motor above its nominal HP rating when a unit is equipped with a hot water coil accessory.

TABLE 7: PRESSURE DROP VS. GPM


1HW0450

1HW0451

1HW0452

TABLE 8: CAPACITY CORRECTION VS. GPM

GPM

10

20

30

Pressure Drop, PSI

.10

.32

.67

GPM

15

30

45

Pressure Drop, PSI

.17

.58

1.22

GPM

20

40

60

Pressure Drop, PSI

.20

.67

1.41

1HW0450

1HW0451

1HW0452

GPM

20

30

Capacity Correction

1.12

1.16

GPM

30

45

Capacity Correction

1.11

1.15

GPM

40

60

Capacity Correction

1.12

1.17

Unitary Products Group

Page 142

http://www.rezine.net
246668-YTG-B-0906

TABLE 9: SUPPLY AIR BLOWER PERFORMANCE - KEU060 (5 TON)


EXTERNAL STATIC PRESSURE
CFM

0.2

0.4

0.6

0.8

RPM

BHP

RPM

BHP

RPM

BHP

RPM

1400

677

74

0.08

753

174

0.19

831

268

0.29

912

355

BHP
0.38

1600

725

225

0.24

801

325

0.35

879

419

0.45

959

506

0.54

1800

773

366

0.39

849

466

0.50

927

560

0.60

1008

647

0.69

2000

822

507

0.54

898

607

0.65

975

701

0.75

1056

789

0.85

2200

871

657

0.70

947

757

0.81

1025

851

0.91

1106

938

1.01

2400

922

818

0.88

997

918

0.99

1075

1012

1.09

1156

1100

1.18

2600

972

994

1.07

1048

1094

1.17

1126

1188

1.27

1207

1276

1.37

2800

1024

1187

1.27

1100

1286

1.38

1178

1380

1.48

1258

1468

1.57

3000

1076

1395

1.50

1152

1495

1.60

1230

1589

1.70

1311

1677

1.80

3200

1129

1622

1.74

1205

1721

1.85

1283

1815

1.95

----

----

----

BHP

RPM

EXTERNAL STATIC PRESSURE


CFM

1.0

1.2
W

1.4
BHP

RPM

1.6

RPM

BHP

RPM

BHP

1400

997

435

0.47

1086

507

0.54

1181

570

0.61

1282

622

0.67

1600

1044

586

0.63

1134

658

0.71

1228

721

0.77

1329

774

0.83

1800

1092

727

0.78

1182

799

0.86

1276

861

0.92

1377

914

0.98

2000

1141

869

0.93

1230

940

1.01

1325

1003

1.08

1426

1056

1.13

2200

1191

1018

1.09

1280

1090

1.17

1375

1153

1.24

1476

1205

1.29

2400

1241

1180

1.27

1330

1251

1.34

1425

1314

1.41

1526

1367

1.47

2600

1292

1356

1.45

1381

1427

1.53

1476

1490

1.60

1577

1543

1.66

2800

1343

1548

1.66

1433

1620

1.74

1527

1682

1.80

1628

1735

1.86

3000

1395

1757

1.88

1485

1828

1.96

----

----

----

----

----

----

3200

----

----

----

----

----

----

----

----

----

----

----

----

Exceeds the BHP limitation.

Unitary Products Group

Page 143

http://www.rezine.net
246668-YTG-B-0906

TABLE 10: SUPPLY AIR BLOWER PERFORMANCE - KEU090 (7.5 TON)


EXTERNAL STATIC PRESSURE
CFM

0.2

0.4

0.6

0.8

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

2200

561

281

0.30

612

400

0.43

670

530

0.57

734

661

0.71

2400

579

414

0.44

630

533

0.57

688

663

0.71

752

794

0.85

2600

599

542

0.58

649

662

0.71

707

792

0.85

771

922

0.99

2800

619

666

0.71

670

786

0.84

728

916

0.98

792

1047

1.12

3000

640

786

0.84

691

905

0.97

749

1035

1.11

813

1166

1.25

3200

662

901

0.97

713

1021

1.10

771

1151

1.23

835

1282

1.37

3400

684

1013

1.09

735

1132

1.21

793

1262

1.35

857

1393

1.49

3600

706

1120

1.20

757

1239

1.33

815

1369

1.47

879

1500

1.61

3800

728

1223

1.31

779

1342

1.44

837

1472

1.58

900

1603

1.72

4000

750

1322

1.42

800

1441

1.55

859

1571

1.69

922

1702

1.83

4200

771

1418

1.52

822

1537

1.65

880

1667

1.79

944

1798

1.93

4400

792

1510

1.62

843

1629

1.75

901

1759

1.89

965

1890

2.03

4600

813

1599

1.72

864

1718

1.84

922

1848

1.98

986

1979

2.12

EXTERNAL STATIC PRESSURE


CFM

1.0

1.2

1.4

1.6

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

2200

801

783

0.84

869

886

0.95

936

962

1.03

1000

999

1.07

2400

819

916

0.98

887

1019

1.09

954

1095

1.17

1018

1132

1.21

2600

838

1044

1.12

906

1148

1.23

973

1223

1.31

1038

1261

1.35

2800

859

1169

1.25

927

1272

1.36

994

1348

1.45

1058

1385

1.49

3000

880

1288

1.38

948

1392

1.49

1015

1467

1.57

1079

1505

1.61

3200

902

1404

1.51

970

1507

1.62

1037

1583

1.70

1101

1620

1.74

3400

924

1515

1.63

992

1618

1.74

1059

1694

1.82

1123

1731

1.86

3600

945

1622

1.74

1014

1725

1.85

1081

1801

1.93

1145

1838

1.97

3800

967

1725

1.85

1036

1828

1.96

1103

1904

2.04

1167

1941

2.08

4000

989

1824

1.96

1057

1928

2.07

1124

2003

2.15

1189

2041

2.19

4200

1011

1920

2.06

1079

2023

2.17

1146

2099

2.25

1210

2136

2.29

4400

1032

2012

2.16

1100

2116

2.27

----

----

----

----

----

----

4600

1052

2101

2.25

----

----

----

----

----

----

----

----

----

Exceeds the BHP limitation.

10

Unitary Products Group

Page 144

http://www.rezine.net
246668-YTG-B-0906

TABLE 11: SUPPLY AIR BLOWER PERFORMANCE - KEU120 (10 TON)


EXTERNAL STATIC PRESSURE
CFM

0.2

0.4

0.6

0.8

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

2800

571

122

0.13

630

332

0.36

682

489

0.52

733

618

0.66

3000

595

349

0.37

654

559

0.60

706

716

0.77

756

845

0.91

3200

619

558

0.60

678

768

0.82

730

925

0.99

780

1054

1.13

3400

643

753

0.81

702

964

1.03

754

1120

1.20

804

1249

1.34

3600

667

939

1.01

726

1149

1.23

778

1306

1.40

829

1435

1.54

3800

692

1119

1.20

751

1329

1.43

803

1485

1.59

853

1614

1.73

4000

716

1294

1.39

775

1504

1.61

827

1661

1.78

877

1790

1.92

4200

740

1468

1.57

799

1678

1.80

852

1834

1.97

902

1963

2.11

4400

765

1641

1.76

824

1851

1.99

876

2008

2.15

926

2136

2.29

4600

789

1815

1.95

848

2025

2.17

900

2182

2.34

950

2310

2.48

4800

813

1991

2.14

872

2201

2.36

924

2357

2.53

974

2486

2.67

5000

837

2169

2.33

896

2380

2.55

948

2536

2.72

998

2665

2.86

5200

861

2352

2.52

920

2562

2.75

972

2718

2.92

1022

2847

3.05

5400

884

2538

2.72

943

2748

2.95

995

2905

3.12

1045

3033

3.25

5600

907

2728

2.93

966

2939

3.15

1019

3095

3.32

1069

3224

3.46

EXTERNAL STATIC PRESSURE


CFM

1.0

1.2

1.4

1.6

RPM

BHP

RPM

BHP

RPM

BHP

RPM

2800

786

744

0.80

846

893

0.96

920

1092

1.17

1010

1364

BHP
1.46

3000

809

971

1.04

870

1121

1.20

943

1319

1.41

1034

1592

1.71

3200

833

1180

1.27

894

1329

1.43

967

1528

1.64

1057

1800

1.93

3400

857

1375

1.48

918

1525

1.64

991

1723

1.85

1082

1996

2.14

3600

882

1561

1.67

942

1711

1.84

1016

1909

2.05

1106

2182

2.34

3800

906

1741

1.87

967

1890

2.03

1040

2088

2.24

1130

2361

2.53

4000

930

1916

2.06

991

2066

2.22

1064

2264

2.43

1155

2536

2.72

4200

955

2090

2.24

1016

2239

2.40

1089

2437

2.61

1179

2710

2.91

4400

979

2263

2.43

1040

2412

2.59

1113

2610

2.80

1203

2883

3.09

4600

1003

2437

2.61

1064

2586

2.77

1137

2784

2.99

1228

3057

3.28

4800

1027

2613

2.80

1088

2762

2.96

1161

2960

3.18

1252

3233

3.47

5000

1051

2791

2.99

1112

2941

3.15

1185

3139

3.37

----

----

----

5200

1075

2973

3.19

1136

3123

3.35

----

----

----

----

----

----

5400

1098

3160

3.39

----

----

----

----

----

----

----

----

----

5600

----

----

----

----

----

----

----

----

----

----

----

----

Exceeds the BHP limitation.

Unitary Products Group

11

Page 145

http://www.rezine.net
246668-YTG-B-0906

TABLE 12: SUPPLY AIR BLOWER PERFORMANCE - KEU180 (15 TON)


EXTERNAL STATIC PRESSURE
CFM

0.2

0.4

0.6

0.8

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

4000

555

382

0.41

594

620

0.67

633

851

0.91

676

1085

1.16

4200

562

616

0.66

600

854

0.92

640

1085

1.16

683

1319

1.42

4400

569

828

0.89

608

1066

1.14

648

1297

1.39

690

1531

1.64

4600

577

1022

1.10

616

1260

1.35

656

1491

1.60

698

1725

1.85

4800

586

1202

1.29

624

1440

1.55

664

1671

1.79

707

1905

2.04

5000

595

1372

1.47

634

1610

1.73

673

1841

1.97

716

2075

2.23

5200

604

1533

1.64

643

1771

1.90

683

2002

2.15

726

2236

2.40

5400

614

1689

1.81

653

1927

2.07

693

2158

2.31

735

2392

2.57

5600

624

1841

1.97

663

2079

2.23

703

2310

2.48

745

2544

2.73

5800

635

1991

2.14

673

2228

2.39

713

2459

2.64

756

2694

2.89

6000

645

2140

2.30

684

2378

2.55

724

2609

2.80

766

2843

3.05

6200

656

2290

2.46

695

2528

2.71

735

2759

2.96

777

2993

3.21

6400

667

2442

2.62

706

2679

2.87

746

2910

3.12

788

3145

3.37

6600

679

2596

2.78

717

2833

3.04

757

3064

3.29

800

3299

3.54

6800

690

2753

2.95

729

2991

3.21

768

3222

3.46

811

3456

3.71

7000

701

2915

3.13

740

3153

3.38

780

3384

3.63

823

3618

3.88

EXTERNAL STATIC PRESSURE


CFM

1.0

1.2

1.4

1.6

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

4000

723

1333

1.43

775

1604

1.72

833

1910

2.05

900

2258

2.42

4200

729

1567

1.68

781

1839

1.97

840

2144

2.30

907

2493

2.67

4400

737

1779

1.91

789

2051

2.20

848

2356

2.53

915

2704

2.90

4600

745

1973

2.12

797

2245

2.41

856

2550

2.74

923

2899

3.11

4800

754

2153

2.31

806

2425

2.60

864

2730

2.93

931

3079

3.30

5000

763

2323

2.49

815

2594

2.78

873

2899

3.11

940

3248

3.48

5200

772

2484

2.66

824

2755

2.96

883

3061

3.28

950

3409

3.66

5400

782

2640

2.83

834

2911

3.12

893

3216

3.45

960

3565

3.82

5600

792

2792

2.99

844

3063

3.29

903

3368

3.61

970

3717

3.99

5800

802

2942

3.16

854

3213

3.45

913

3518

3.77

980

3867

4.15

6000

813

3091

3.32

865

3362

3.61

924

3667

3.93

991

4016

4.31

6200

824

3241

3.48

876

3512

3.77

935

3817

4.10

1002

4166

4.47

6400

835

3392

3.64

887

3664

3.93

946

3969

4.26

1013

4318

4.63

6600

846

3547

3.80

898

3818

4.10

957

4123

4.42

1024

4472

4.80

6800

858

3704

3.97

910

3976

4.26

968

4281

4.59

1035

4629

4.97

7000

869

3866

4.15

921

4137

4.44

980

4442

4.77

1047

4791

5.14

Exceeds the BHP limitation.

12

Unitary Products Group

Page 146

http://www.rezine.net
246668-YTG-B-0906

TABLE 13: STATIC RESISTANCE FOR UNIT ACCESSORIES (IWG) - KEU060-120


CFM
2200
2400
2600
2800
3000
3200
3400
3600
3800
4000
4200
4400
4600
4800
5000

Electric Heat KW
10

16

26

36

Supply Air
Plenum

Return
Air Grill

Hot Water
Coil

Steam
Coil

0.01
0.01
0.01
0.01
0.01
0.02
0.02
0.02
0.02
0.03
0.03
0.03
0.03
0.04
0.04

0.01
0.02
0.02
0.03
0.03
0.04
0.04
0.05
0.06
0.06
0.07
0.07
0.08
0.08
0.09

0.03
0.03
0.04
0.04
0.05
0.06
0.07
0.07
0.08
0.09
0.10
0.11
0.12
0.13
0.14

0.04
0.05
0.06
0.07
0.08
0.09
0.10
0.11
0.12
0.14
0.15
0.16
0.18
0.19
0.21

0.02
0.03
0.03
0.04
0.04
0.05
0.05
0.06
0.06
0.07
0.07
0.08
0.09
0.10
0.10

0.02
0.03
0.03
0.04
0.04
0.05
0.05
0.06
0.06
0.07
0.07
0.08
0.09
0.10
0.10

0.07
0.09
0.10
0.12
0.14
0.16
0.17
0.19
0.22
0.24
0.26
0.28
0.31
0.33
0.36

0.11
0.13
0.15
0.16
0.18
0.20
0.23
0.25
0.27
0.30
0.33
0.36
0.39
0.43
0.46

TABLE 14: STATIC RESISTANCE FOR UNIT ACCESSORIES (IWG) - KEU180


CFM
4600
4800
5000
5200
5400
5600
5800
6000
6200
6400
6600
6800
7000
7200
7400

Electric Heat KW
10

16

26

36

72

Supply Air
Plenum

Return
Air Grill

Hot Water
Coil

Steam
Coil

0.03
0.04
0.04
0.04
0.05
0.05
0.06
0.06
0.07
0.07
0.08
0.08
0.09
0.09
0.10

0.08
0.08
0.09
0.10
0.10
0.11
0.11
0.12
0.13
0.13
0.14
0.15
0.15
0.16
0.17

0.12
0.13
0.14
0.16
0.17
0.18
0.20
0.21
0.22
0.24
0.25
0.27
0.29
0.30
0.32

0.18
0.19
0.21
0.23
0.24
0.26
0.28
0.30
0.32
0.34
0.36
0.38
0.41
0.43
0.45

0.23
0.25
0.27
0.29
0.31
0.34
0.37
0.40
0.43
0.47
0.51
0.55
0.59
0.64
0.68

0.05
0.06
0.06
0.06
0.07
0.07
0.08
0.08
0.08
0.09
0.09
0.10
0.10
0.10
0.11

0.05
0.06
0.06
0.06
0.07
0.07
0.08
0.08
0.08
0.09
0.09
0.10
0.10
0.10
0.11

0.31
0.33
0.36
0.38
0.41
0.44
0.47
0.50
0.53
0.56
0.59
0.62
0.66
0.69
0.73

0.39
0.43
0.46
0.50
0.54
0.58
0.62
0.66
0.71
0.75
0.80
0.85
0.90
0.95
1.01

Unitary Products Group

13

Page 147

http://www.rezine.net
246668-YTG-B-0906

TABLE 15: SUPPLY AIR PLENUM PERFORMANCE DATA


Angle of Deflection

Model

CFM

Face
Velocity
(FPM)

0
SPREAD

Vertical

Horizontal

Louvers1
(Plan
View)

Louvers2
(Elevation
View)

Spread

Throw
(Feet)

060

090

120

180

1.
2.
3.
4.

22-1/2
SPREAD

(Feet)3
Min. Max

0
SPREAD

Throw
(Feet)

18

Drop (Feet)4

Vertical
Louvers
(Plan
View)

Spread
(Feet)

Horizontal
Louvers
(Elevation
View)

0
SPREAD

45
SPREAD

Throw
(Feet)

18

Vertical
Louvers
(Plan
View)

Horizontal
Louvers
(Elevation
View)

Spread
(Feet)

18

0
SPREAD

Min.

Max.

Min.

Max

Min.

Max.

1600

630

38

59

13

20

15

27

43

12

19

14

21

32

33

48

1800

710

43

67

14

22

16

30

48

14

22

14

23

37

35

56

2000

790

48

74

16

25

16

34

53

15

24

14

25

40

38

60

2200

870

52

81

17

27

16

37

58

17

26

15

29

44

44

66

2400

940

57

89

19

30

17

41

64

18

29

15

30

48

45

72

2400

615

47

74

20

29

19

34

53

23

33

17

26

39

45

65

2700

690

53

83

22

32

20

10

39

59

25

36

18

29

45

48

71

10

3000

770

59

92

24

35

21

10

42

66

27

40

19

32

50

52

78

10

3300

845

65

101

26

38

21

10

46

73

29

44

19

35

55

56

85

10

3600

920

71

110

28

41

22

11

50

79

32

47

20

10

38

60

60

91

11

3200

820

63

98

25

37

21

10

45

70

29

43

19

34

53

54

82

10

3600

920

71

110

28

41

22

11

50

79

32

47

20

10

38

60

60

91

11

4000

1025

78

123

30

45

22

11

56

88

35

52

20

10

42

66

67

102

11

4400

1130

86

135

33

49

23

12

62

97

38

57

21

11

47

73

76

115

12

4800

1230

94

147

35

53

23

12

68

106

41

62

21

11

51

80

85

127

12

4800

880

84

132

32

48

23

12

61

95

38

56

21

11

46

72

73

112

12

5400

1000

95

149

36

54

24

12

68

107

42

63

22

11

52

81

81

124

12

6000

1110

106

165

39

59

25

13

76

119

46

69

23

12

57

89

90

138

13

6600

1220

116

182

43

65

26

13

84

131

50

76

23

12

63

98

99

152

13

7200

1330

126

199

46

70

27

14

92

143

55

83

24

12

68

107

109

166

14

Min. Max

Drop (Feet)

Min. Max.

Drop (Feet)

Adjusting the vertical louvers will vary the throw, the spread and the drop.
Adjusting the horizontal louvers will only vary the drop.
The velocity of the air will be 125 ft./min. at the minimum distance and 80 ft./min. at the maximum distance.
The velocity of the conditioned air at the bottom of the drop will be 50 ft./min. Drafts will occur if the drop extends into the occupied
level of the conditioned space.

TABLE 16: BLOWER MOTOR AND DRIVE DATA


MOTOR

ADJUSTABLE MOTOR PULLEY

FIXED BLOWER PULLEY

BELT (NOTCHED)

BLOWER
RANGE
(RPM)

HP

FRAME

DESIGNATION

OUTSIDE
DIA.
(IN.)

PITCH
DIA.
(IN.)

BORE
(IN.)

DESIGNATION

OUTSIDE
DIA.
(IN.)

PITCH
DIA.
(IN.)

BORE
(IN.)

DESIGNATION

PITCH
LENGTH
(IN.)

QTY.

060

810/1110

3/4

56

1VL44

3.1-4.1

2.8-3.8

5/8

AL64

6.2

5.8

3/4

A32

33.3

090

655/880

1-1/2

56

1VL44

2.1-4.1

2.8-3.8

7/8

AK79

7.9

7.5

A36

37.3

120

700/950

56

1VL44

3.1-4.1

2.8-3.8

7/8

BK80

7.4

7.0

A36

37.3

180

625/810

56

1VM50

3.7-4.7

3.4-4.4

7/8

BK105

9.9

9.5

A57

58.3

MODEL

14

Unitary Products Group

Page 148

http://www.rezine.net
246668-YTG-B-0906

TABLE 17: KEU PHYSICAL DATA


Model
Component
EVAPORATOR
BLOWER1

EVAPORATOR
COIL

HOT WATER COIL

STEAM COIL

AIR FILTERS
HOLDING CHARGE

Description
060

090

120

180

Centrifugal Blower (Dia. X Wd. in.)

15 X 15

15 X 15

15 X 15

18 X 18

Fan Motor HP (Belt Drive)

3/4

1-1/2

Rows Deep

Finned Length (in.)

30

46

46

54

Fins per Inch

13

13

13

13

Face Area (ft.2)

5.0

8.6

10.2

12.1

Rows Deep

Finned Length (in.)

30

46

46

54

Fins Per Inch

12

12

12

12

Face Area (ft.2)

3.8

5.4

5.4

9.0

Inlet Connection

1 NPTE

1 NPTE

1 NPTE

1-3/8 O.D

Outlet Connection

1 NPTE

1 NPTE

1 NPTE

1-3/8 O.D

Rows Deep

Finned Length (in.)

30

46

46

54

Fins Per Inch

Face Area (ft.2)

3.8

5.4

5.4

9.0

Inlet Connection

1-1/2 NPTE

1-1/2 NPTE

1-1/2 NPTE

1-1/2 NPTE

Outlet Connection

1-1/2 NPTE

1-1/2 NPTE

1-1/2 NPTE

1-1/2 NPTE

Quantity Per Unit (16 X 25 X 1)

Quantity Per Unit (20 X 20 X 1)

Total Face Area (ft.2)

5.6

11.1

11.1

16.7

Refrigerant 22 (lbs./oz.)

0/7

0/7

0/10

0/0

1. Refer to Blower Motor and Drive Data table for additional blower and drive information.
All of these 1750 RPM motors are solid base, 56 frame with 1.15 service factor, inherent protection and permanently lubricated ball bearings.

Unitary Products Group

15

Page 149

http://www.rezine.net
246668-YTG-B-0906

(/,%7"53().'
).2%!20!.%,
&OR,OW6OLTAGE
#ONTROL0ANEL

 
 

 

 +./#+/54
2EMOVEDONLYWHEN
%LECTRIC(EAT!CCESSORY
ISUSED

!)2
/54

+./#+/54
).2%!20!.%,
&OR0OWER7IRING

 

 


 

 

 

 

 

",/7%2-/4/2
!.$$2)6%
!##%330!.%,
4HISSIDEINLY
&),4%2!##%33
0!.%,4HIS
SIDEONLY


 

 

All dimensions are in inches. They are


subject to change without notice. Certified dimensions will be provided upon
request.

(/,%7)4('2/-
-%4&/2/$
35#4)/.,).%

 
 

 

 

!)2
).

 

(/,%7)4('2/-
-%4&/2/$
,)15)$,).%





/$$2!).
#/..-USTBE
TRAPPED

FIGURE 1 - UNIT DIMENSIONS KEU060


ACCESSORIES

ELECTRIC HEATER - Add 13 to unit height when used.


SUPPLY AIR PLENUM - Add 24-1/4 to unit height when used.
BASE - Add 20 to unit height when used.

TABLE 18: UNIT CLEARANCES KEU060


MINIMUM CLEARANCES
Side with RETURN AIR opening
Side with SUPPLY AIR opening

24

Side with PIPING CONNECTIONS

24
2

Side opposite with PIPING CONNECTIONS


Side with access for both POWER & CONTROL
WIRING3,
Bottom4

060

1. Overall dimensions of the unit will vary if an electric


heater, a supply air plenum or a base is used.
2. This dimension is required for removal of the coil. Only
26 is required for normal service.
3. Although no clearance is required for service and operation, some clearance may be required for routing the
power and control wiring.
4. Allow enough clearance to trap the condensate drain
line.

36
12
-

16

Unitary Products Group

Page 150

http://www.rezine.net
246668-YTG-B-0906

 +./#+/54
&/20/7%27)2).'"ACK0ANEL
$ONOTREMOVETHISKNOCKOUTWHEN
THEUNITISEQUIPPEDWITHAN%LECTRIC
(EAT!CCESSORY2EFERTODETAILOF
THE(EATER!CCESSORYFORPOWER
WIRINGACCESSOPENING
 
 

(/,%7"53().'
&/2#/.42/,
7)2).'
"ACK0ANEL

 

 +./#+/54
2EMOVEDONLYWHEN
%LECTRIC(EAT!CCESSORY
ISUSED

!)2
/54

 
 

 



 

 

 



",/7%2-/4/2
!.$$2)6%
!##%330!.%,
4HISSIDEONLY
(/,%7)4('2/-
-%4&/2/$
,)15)$,).%
 


 

(/,%7)4('2/-
-%4&/2 /$
  35#4)/.,).%
 

 
 

 

!)2
).

 
 



All dimensions are in inches. They are


subject to change without notice. Certified dimensions will be provided upon
request.

/$$2!).
#/..-USTBE
TRAPPED

&),4%2!##%330!.%,
7HENUNITISINSTALLEDIN
AHORIZONTALPOSITION DO
NOTBLOCKTHISAREAWITH
REFRIGERANTPIPING

FIGURE 2 - UNIT DIMENSIONS KEU090 & 120


ACCESSORIES

ELECTRIC HEATER - Add 14-1/4 to unit height when used.


SUPPLY AIR PLENUM - Add 27-1/2 to unit height when used.
BASE - Add 20 to unit height when used.

TABLE 19: UNIT CLEARANCES KEU090 & 120


MINIMUM CLEARANCES
Side with RETURN AIR opening
Side with SUPPLY AIR opening

090-120
24

24
2

Side with PIPING CONNECTIONS

36

Side opposite with PIPING CONNECTIONS

12

Side with access for both POWER & CONTROL


WIRING3,
Bottom4

1. Overall dimensions of the unit will vary if an electric


heater, a supply air plenum or a base is used.
2. This dimension is required for removal of the coil. Only
26 is required for normal service.
3. Although no clearance is required for service and operation, some clearance may be required for routing the
power and control wiring.
4. Allow enough clearance to trap the condensate drain
line.

Unitary Products Group

17

Page 151

http://www.rezine.net
246668-YTG-B-0906

B L
(A
L o
s e

O
lw
c
c

W
a y
a te
tio n

E R
s o
d o
h a

M O
n th
n o
s b

T O
e w
p p o
e e n

R A N D D
ir in g c o n n
s ite s id e O
ro ta te d 1

R IV E A C C
e c tio n s id
N L Y w h e
8 0 fro m p

E S S
e o f u
n th e
o s itio

1 -2 3 /3 2 " K N O C K O U T
R e m o v e o n ly w h e n E le c tr ic
H e a t A c c e s s o r y is u s e d .

P A N E L
n it)
b lo w e r
n s h o w n .

7 /8
D o
H e
w ir

" K N O
n o t re
a t A c c
in g a c

6 0 -3 /4
2 1 -7 /8

1 9 -3 /8

C K O U T F
m o v e th is
e s s o ry . R
c e s s o p e n
7 /8 " K N O
C O N T R O

W E R W IR IN G
u t w h e n th e u n it is e q u ip p e d w ith a n E le c tr ic
d e ta il o f th e H e a te r A c c e s s o r y fo r p o w e r
T F O R
IN G
A L T E R N A T E
2 -5 /8 " K N O C K O U T *

A IR
O U T

5 -7 /8
2 -1 /8

5 -1 /2
7 /8

7 -1 /4

O R P O
k n o c k o
e fe r to
in g
C K O U
L W IR

1 8 -7 /8
3 2 -3 /8
6

1 6 -1 /2
B L O W E R
S E C T IO N

3 -1 /8

2 -5
K N
O U
1 -5
S U
C O

1 9

1 0
2 7 -5 /8

6 -1 /4

6 2 -5 /8
3 -1 /8

A IR

IN

1 -1
F O
C O
(M

2 -3 /1 6
5 6 -3 /8
1

3 1 -5 /8

2 -3 /1 6

K O R
O D
IO N
.*

3 -1 /8

C O IL
S E C T .

2 -3 /8

/8 "
O C
T F
/8 "
C T
N N

F IL T
F ilte
th ro
th e

/4 " K N
7 /8 "
N N E C
u s t b e
R

O C
O D
T IO
tra p

All dimensions are in inches. They are


subject to change without notice. Certified dimensions will be provided upon
request.

K O U T
D R A IN
N *
p e d )

E R A C C E S S P A N E L
rs c a n b e re m o v e d
u g h e ith e r s id e o f
u n it.

1 -1 /4 " K N O C K O U T F O R
5 /8 " O D L IQ U ID C O N N E C T IO N *

* R e fe r to IN S T A L L IN G R E F R IG E R A N T M A IN S in in s ta lla tio n in s tr u c tio n


w h e n p ip in g th r o u g h th e o p p o s ite s id e o f th e u n it.

FIGURE 3 - UNIT DIMENSIONS KEU180


ACCESSORIES

ELECTRIC HEATER - Add 14-1/4 to unit height when using 10,


16, 26, or 36 KW heater
SUPPLY AIR PLENUM - Add 27 to unit height when used.
BASE - Add 24 to unit height when used.
HOT WATER OR STEAM COIL - Add 6 to unit depth when used.

TABLE 20: UNIT CLEARANCES KEU180


MINIMUM CLEARANCES
Side Air with RETURN AIR opening
Side with SUPPLY AIR opening

24

Bottom

61

Side opposite PIPING CONNECTIONS


4

24

Side with PIPING CONNECTIONS

180

1. Overall dimension of the unit will vary if an electric


heater, a supply air plenum or a base is used.
2. This dimension is required for removal of the DX coil.
Only 26 is required for normal servicing.
3. If the coil has to be removed, this dimension is required
to loosen screws that secure the coil to the unit frame.
This dimension will also be required for blower motor
access if the piping connections are made on the opposite side of the unit.
4. Allow enough clearance to trap the condensate drain
lines.

26
-

18

Unitary Products Group

Page 152

http://www.rezine.net
246668-YTG-B-0906

6833/<$,53/(180
*

.





&

)
/

63

+
63

'

.12&.2876)2532:(5 &21752/:,5,1*

WITH ELECTRIC HEAT - Remove this 2-1/2 knockout and one of the 7/8
knockouts from the rear panel of the plenum. Remove the 1-23/32 knockout
and one of the 7/8 knockouts from the top panel of the basic unit. Install a 1/
2 squeeze connector in both of the 7/8 openings.

6+,33('.12&.(''2:1
)25),(/'$66(0%/<

.12&.287)2532:(5:,5,1*

WITH ELECTRIC HEAT - Remove this 2-1/2 knockout from the


rear panel of the plenum. Route the power wiring conduit through
this opening and connect it to the field-supplied fitting on the electric heat accessory. Connect the power wiring to the fuse block in
the heater control box.

Route the power wiring conduit through the 2-1/2 opening and connect it
to the field-supplied fitting on the electric heat accessory. Connect the
power wiring to the fuse block in the heater control box.
Route the control wires through the 7/8 openings and connect them to
the terminals on block TB1. Secure them with the 1/2 squeeze connectors.

Install the control wiring per basic unit Installation Manual.


DO NOT route any field control wiring through the plenum.
Electric Heaters are NOT CSA approved for installation
within a supply air plenum.

Electric Heaters are NOT CSA approved for installation


within a supply air plenum.

WITHOUT ELECTRIC HEAT - Install the power and the control wiring
per basic unit Installation Manual. DO NOT route any wiring through
the plenum and DO NOT remove this knockout.

WITHOUT ELECTRIC HEAT - Remove both 7/8 knockouts from the rear
panel of the plenum and both 7/8 knockouts from the top panel of the
basic unit. Install a 1/2 squeeze connector in one of the plenum openings and both of the unit openings. Install a 1/2 conduit fitting in the other
opening of the plenum.

Plenum Unit
Model Model

Connect the power wiring conduit to the fitting on the plenum. Route the
power wiring through the conduit, one of the squeeze connectors on the
unit, and the field-supplied squeeze connector on the blower motor contactor box. Connect the power wiring to the blower motor contactor.

Plenum Dimensions (inches)


A
36

25-1/2 34-2/8 31-3/4 15-3/4 7-5/8 7/8 2-1/8 11-1/4

1SP0450

060

1SP0451

090
120

52-1/8 28-1/4 27-1/2 49-3/8 17-7/8 8-3/4 7/8 1-1/8 15-1/4 1-3/4

1SP0452

180

60-3/4

31

27

Route the control wires through the remaining plenum and unit openings and connect them to the terminals on block TB1. Secure them
with the 1/2 squeeze connectors.

55-3/4 19-7/8 6-1/8 1- 2-1/2 19-1/2 1-3/4

'

(
)
0
*

&

+($7(5
(/(0(17
&+$0%(5

+
.


%
$

:,5,1*+$51(66/2&$7,21
7KLVRSHQLQJLQWKHERWWRPRIWKHKHDWHU
FRQWUROER[LVXVHGIRUWKHZLULQJKDUQHVV
WKDWFRQQHFWVWKHKHDWHUDFFHVVRU\WRWKH
EDVLFXQLW,WLVSURYLGHGZLWKDVTXHH]H
FRQQHFWRUIRUVHFXULQJWKHZLULQJKDUQHVV
DQGLWVORFDWLRQFRUUHVSRQGVWRWKHORFD
WLRQRIWKHNQRFNRXWLQWKHWRS
SDQHORIWKHEDVLFXQLW

$&&(6623(1,1*)2532:(56833/<:,5,1*
.:7+58.:$GGDFRQGXLWILWWLQJ
WRWKHKROHIRUZLUHVL]HVXSWKURXJK
$:*5HPRYHWKHNQRFNRXWULQJDQGDGGD
FRQGXLWILWWLQJWRWKHKROHIRU
ZLUHVL]HVXSWKURXJK$:*
.:7+58.:$GGDFRQGXLWILWWLQJ
WRWKHKROHIRUZLUHVL]HVXSWKURXJK
$:*5HPRYHWKHNQRFNRXWULQJDQGDGGD
 FRQGXLWILWWLQJWRWKH KROHIRUZLUHVL]HV
XSWKURXJK

$:*

&21752/%2;
$&&(663$1(/

FIGURE 5 - ACCESSORY DIMENSIONS

Unitary Products Group

19

Page 153

http://www.rezine.net
246668-YTG-B-0906

TABLE 21: ELECTRIC HEATER DIMENSIONS KEU060, 090, 120 & 180
Heater Dimensions (inches)

Heater
Model

Nom.
kW

Unit
Model

2HT045010251
2HT045016251
2HT045026251

10
16
26

060

25-1/8

22-1/2

13

7/8

1/2

5-1/4

1-11/16

1-3/4

20-1/8

16-7/8

2HS04501025, 46, 58
2HS04501625, 46, 58
2HS04502625, 46, 58
2HS04503625, 46, 58

10
16
26
36

090
120
180

27-1/4

25-1/4

14-1/4

1/2

5-1/2

1-1/2

1-1/2

22-1/4

19-1/4

2HS04507225, 46, 58

72

180

29-7/8

26-3/8

21-3/4

2-3/8

5-1/4

3/4

6-3/8

2-1/4

2-1/2

22-1/4

19-1/4

1. The 2HT heaters are not CSA approved for 060 units mounted horizontally.

RETURN AIR GRILLE

* ) 5 -

FIGURE 7 - BASE ACCESSORY

FIGURE 6 - RETURN AIR GRILL


Grill Dimensions (Inches)
Grill Model

B
A

5/8

Unit Model
A

Grill Dimensions (Inches)


Grill Model

Unit Model
A

1RG0450

060

36

22

1BS0450

060

36

22

20

1RG0451

090
120

52

25

1BS0451

090
120

52

25-1/8

20

1RG0452

180

60-3/4

31

1BS0452

180

60-3/4

31-5/8

24

20

Unitary Products Group

Page 154

http://www.rezine.net
246668-YTG-B-0906

C
1-1/2" NPTE
CONNS.

F
E

Steam Coil Dimensions (inches)

Coil
Model

Unit
Model

1NF04501

060

36

21-7/8

2-1/2

2-5/8

10-5/8

1NF04511

090

52

25

2-1/2

2-5/8

13-5/8

1NF0451

120

52

25

2-1/2

2-5/8

13-5/8

1NF04522

180

60-3/4

32-1/4

3-5/16

3-1/2

17-1/2

1. Installs over the return air opening of the unit-before the filters.
2. Installs between the coil and blower section of the unit.

D
2

FIGURE 8 - STEAM COIL

&
%

Coil
Model

*


137(
&2116

Unit
Model

Hot Water Coil Dimensions (inches)


A

060

36

1HW04511

090

52

25

1HW04511

120

52

25

1HW04522

180

1HW0450

3-3/8

1
NPTE

5 1-11/16 2-3/4 5-7/8

3-3/8

1
NPTE

5 1-11/16 2-3/4 5-7/8

3-3/8

1
NPTE

21-7/8 5 1-11/16 2-3/4 6-1/4

60-3/4 32-1/4 6

2-5/32 3-5/16 6-9/16 3-27/32

1-3/8
NPTE

1. Installs over the return air opening of the unit-before the filters.
2. Installs between the coil and blower section of the unit.

'


FIGURE 9 - HOT WATER COIL

Unitary Products Group

21

Page 155

http://www.rezine.net
246668-YTG-B-0906

TABLE 22: KEU ELECTRICAL DATA


Model
(TONS)

Power
Supply
Voltage

Indoor
Motor
FLA

208

7.6

240

6.9

208

6.6

240

6.0

460

3.0

575

2.4

208

7.5

240

6.8

460

3.4

575

2.7

0603
(5)

090
(7.5)

120
(10)

Heater
Model
Number

Nominal
Heater
KW

Applied
Heater KW

Electric
Heat Amps

Min.
Circuit
Ampacity
(AMPS)

Max. Fuse1 /
HACR
Breaker2
(AMPS)

None
2HT04501025
2HT04501625
2HT04502625
None
2HT04501025
2HT04501625
2HT04502625
None
2HS04501025
2HS04501625
2HS04502625
2HS04503625
None
2HS04501025
2HS04501625
2HS04502625
2HS04503625
None
2HS04501046
2HS04501646
2HS04502646
2HS04503646
None
2HS04501058
2HS04501658
2HS04502658
2HS04503658
None
2HS04501025
2HS04501625
2HS04502625
2HS04503625
None
2HS04501025
2HS04501625
2HS04502625
2HS04503625
None
2HS04501046
2HS04501646
2HS04502646
2HS04503646
None
2HS04501058
2HS04501658
2HS04502658
2HS04503658

-10
16
26
-10
16
26
-10
16
26
36
-10
16
26
36
-10
16
26
36
-10
16
26
36
-10
16
26
36
-10
16
26
36
-10
16
26
36
-10
16
26
36

-7.5
12.0
19.5
-10.0
16.0
26.0
-7.5
12.0
19.5
27.0
-10.0
16.0
26.0
36.0
-10.0
16.0
26.0
36.0
-10.0
16.0
26.0
36.0
-7.5
12.0
19.5
27.0
-10.0
16.0
26.0
36.0
-10.0
16.0
26.0
36.0
-10.0
16.0
26.0
36.0

-20.8
33.4
54.2
-24.1
38.5
62.5
-20.8
33.4
54.2
75.1
-24.1
38.5
62.5
86.6
-12.0
19.2
31.3
43.3
-9.6
15.4
25.0
34.6
-20.8
33.4
54.2
75.1
-24.1
38.5
62.5
86.6
-12.0
19.2
31.3
43.3
-9.6
15.4
25.0
34.6

9.5
35.6
51.2
77.3
8.6
38.7
56.7
86.8
8.3
34.3
49.9
76.0
102.1
7.5
37.6
55.6
85.7
115.8
3.8
18.8
27.8
42.8
57.9
3.0
15.0
22.2
34.3
46.3
9.4
35.4
51.1
77.1
103.2
8.5
38.6
56.6
86.7
116.8
4.3
19.3
28.3
43.3
58.4
3.4
15.4
22.6
34.6
46.7

15
40
60
80
15
40
60
90
15
35
50
80
110
15
40
60
90
125
15
20
30
45
60
15
20
25
35
50
15
40
60
80
110
15
40
60
90
125
15
20
30
45
60
15
20
25
35
50

22

Unitary Products Group

Page 156

http://www.rezine.net
246668-YTG-B-0906

TABLE 22: KEU ELECTRICAL DATA (CONTINUED)


Model
(TONS)

Power
Supply
Voltage

Indoor
Motor
FLA

208

10.6

240

9.6

460

4.8

575

3.9

180
(15)

Heater
Model
Number

Nominal
Heater
KW

Applied
Heater KW

Electric
Heat Amps

Min.
Circuit
Ampacity
(AMPS)

Max. Fuse1 /
HACR
Breaker2
(AMPS)

None
2HS04501025
2HS04501625
2HS04502625
2HS04503625
2HS04507225
None
2HS04501025
2HS04501625
2HS04502625
2HS04503625
2HS04507225
None
2HS04501046
2HS04501646
2HS04502646
2HS04503646
2HS04507246
None
2HS04501058
2HS04501658
2HS04502658
2HS04503658
2HS04507258

-10
16
26
36
72
-10
16
26
36
72
-10
16
26
36
72
-10
16
26
36
72

-7.5
12.0
19.5
27.0
54.1
-10.0
16.0
26.0
36.0
72.0
-10.0
16.0
26.0
36.0
72.0
-10.0
16.0
26.0
36.0
72.0

-20.8
33.4
54.2
75.1
150.1
-24.1
38.5
62.5
86.6
173.2
-12.0
19.2
31.3
43.3
86.6
-9.6
15.4
25.0
34.6
69.3

13.3
39.3
54.9
81.0
107.1
200.9
12.0
42.1
60.1
90.2
120.3
228.5
6.0
21.0
30.1
45.1
60.1
114.3
4.9
16.9
24.1
36.1
48.2
91.5

20
40
60
90
110
225
15
45
70
100
125
250
15
25
35
50
70
125
15
20
25
40
50
100

1. Dual element time delay.


2. HACR type per NEC.
3. The K*EU060 indoor motor is single phase. The electrical heaters MUST be supplied with 3-phase voltage only.

Unitary Products Group

23

Page 157

http://www.rezine.net

Page 158

http://www.rezine.net
036-21096-001-C-0206

SPLIT-SYSTEM
EVAPORATOR BLOWER
L4EU240
20 NOMINAL TONS

DESCRIPTION
This 20 ton evaporator blower is designed with two distinct
modules to provide maximum application flexibility. The units
are shipped as single packages with the blower module
mounted on top of the coil module, but the blower module can
be repositioned in the field to meet almost any installation
requirement.
The blower module includes the blower wheels and room for a
field-mounted motor and drive. The coil module includes direct
expansion coils, one-inch throwaway filters, 1 liquid line
solenoid valve for 50% capacity reduction, thermal expansion
valves, distributors and a condensate drain pan.

FEATURES

Each evaporator coil is pressurized with air to 325 psig and leak
tested under water. After the headers are brazed onto the coil
and the coil is installed in the unit, the coil will be pressurized
with a combination of refrigerant-22 and nitrogen to 150 psig for
pressure testing and additional leak testing. After the coil is
evacuated and dehydrated, it will be pressurized with a holding
charge of refrigerant-22 for storage and/or shipping.

APPLICATION FLEXIBILITY - This evaporator blower can be


arranged for a variety of air discharge patterns in either the
horizontal or the vertical position.

A supply air plenum, return air grille, steam coil, hot water coil,
base section, suspension hardware, blower motors and drive
accessories are available for field-installation to provide
additional application flexibility.

The unit can be bottom-supported or ceiling-suspended and


can be arranged to meet almost any space or duct
requirements. Each unit is available with a choice of blower
motors, drive packages plus other accessories to make them
suitable for most applications.

This evaporator blower, applied with a matching condensing


unit, will provide years of quiet, efficient and dependable
operation.

Unitary Products Group

The following illustration shows three of the more common


installation arrangements. Refer to the unit installation
instruction for other possibilities.

PART LOAD OPERATION - The unit requires no field


modifications for part load operation. Capacity reduction not
only provides economical operation but also maintains more
even temperature and humidity levels in the conditioned
space.

Page 159

http://www.rezine.net
036-21096-001-C-0206

ACCESSORIES

PHYSICAL DATA - Unit and Accessories

RETURN AIR GRILLE - This decorative, expanded metal grille


will enhance the appearance of any unit that has no return air
ductwork and is especially recommended for units located
within the conditioned space.

Evaporator Coil

SUPPLY AIR PLENUM - This decorative, horizontal discharge


plenum will enhance the appearance and performance of any
unit that does not have supply air ductwork. It has the same
durable finish as the evaporator blower, is fully insulated, is
shipped ready for mounting on horizontal or vertical units and
has grilles which may be adjusted to meet the throw and spread
requirements of the conditioned space.

Centrifugal Blowers

SUSPENSION PACKAGE - This accessory can be used to


suspend horizontal units from above without interfering with
access to the unit. It can also be used for elevating a floormounted unit (either horizontal or vertical) to provide additional
height for the installation of a trap at the condensate drain
connection. A suspension package can be used with vibration
isolators.

STEAM COIL - A steam coil is available for field installation


between the blower and coil modules of both horizontal and
vertical units. Since their casings match the dimensions and
the finish of the basic units, they become an integral part of the
unit after installation. The coil slides out of its casing for easy
installation and is pitched in its casing to facilitate condensate
drainage. The coil has copper tubes that have been
mechanically expanded into aluminum fins. Both headers are
located on the same end of the coil. Each coil is leak-tested at
325 psig and dried before their connections are capped for
storage and shipping.
BLOWER MOTORS - Different HP motors are available to
meet almost any air delivery requirement. All motors are UL
approved, have inherent protection, permanently lubricated
ball bearings and get field-mounted within the insulated cabinet
of the unit to minimize the transmission of sound to the
surrounding space. Power wiring for the blower motor is
field supplied.

3
32
82.7
13
3/8
18.4
15 x 12

(8)
20 x 22 x 1
Face Area (Sq.Ft.)
24.1
Operating Charge (Refrigerant-22) Lbs.-Oz.
7.4
Rows Deep
2
Fins / Inch
8
Drainable,
Tube OD (in.)
1/2
Hot Water Coil
Accessory
Face Area (Sq.Ft.)
14.5
Supply/Return (Copper) OD (in.)
1-3/8
Rows Deep
1
8
Non-Freeze, Steam Fins / Inch
Tube OD x ID (in.)
1 x 5/8
Distributing Coil
Accessory
Face Area (Sq.Ft.)
13.5
Inlet/Outlet (Brass) NPTE (in.)
1-1/2
Shipping*
690
Weight (Lbs.)
Operating
800
3 HP
90
Motor & Drive
5 HP
120
Supply Air Plenum
150
Accessory
120
Operating Weight, Base
(Lbs.)
Return Air Grille
15
Steam Coil
150
Hot Water Coil
150
Filters (Throwaway)

BASE SECTION - The base section can be used to elevate


units off the floor. If desired, outdoor air may be introduced thru
these sections by cutting an access opening to accommodate
the outdoor air duct connection. The base has a durable finish
to match the evaporator blower unit. It may have to be insulated
for certain applications.

HOT WATER COIL - A drainable water coil is available for field


installation between the blower and the coil modules of both
horizontal and vertical units. Since their casings match the
dimensions and the finish of the basic units, they become an
integral part of the unit after installation. The coil slides out of its
casing for easy installation. The coil has copper tubes that have
been mechanically expanded into aluminum fins. Both headers
are located on the same end of the coil. Each coil is leak-tested
at 325 psig under water and dried before their connections are
capped for storage and shipping.

Rows Deep
Rows High
Finned Length (in.)
Fins / Inch
Tube OD (in.)
Face Area (Sq. Ft.)
Wheel Dia. x Width (in.)
(2 Per Unit)
Quan. & Size (in.)

*Less Motor and Drive.

ELECTRICAL DATA
Motor
Rating1

3 HP

5 HP

Power
Supply
208-3-60
230-3-60
460-3-60
208-3-60
230-3-60
460-3-60

Locked
Nameplate
Rotor
Amps
Amps
10.6
9.2
4.6
13.6
13.4
6.7

70.4
61.2
30.6
86.0
85.0
42.5

Min.
Max.
Max.
Wire
Fuse
Wire
2
3
Size, Length, Size,4
(AWG)
(Ft.)
(Amps)
14
105
20
14
140
15
14
550
8
12
135
25
12
150
25
14
385
12

For additional motor data, refer to blower motor and drive data table.
Based on three, 60C insulated copper conductors in steel conduit.

Based on an 80% power factor and a 3% voltage drop.

"

Dual element, time delay fuses.

DRIVE PACKAGES - Different size pulleys and belts are


available to provide a blower RPM range to meet almost any air
delivery requirement. Variable pitch motor pulleys can be
adjusted to provide the proper blower RPM. All drive packages
are rated at least 25% above the nominal HP rating of the
blower motor. Two-groove pulleys and two belts are provided
on every drive package rated at 5 HP.

Unitary Products Group

Page 160

http://www.rezine.net
036-21096-001-C-0206

SUPPLY AIR BLOWER PERFORMANCE*


CFM
RPM

6400

7200

8000

8800

9600

ESP

BHP

KW

ESP

BHP

KW

ESP

BHP

KW

ESP

BHP

KW

ESP

BHP

KW

600

0.15

1.49

1.42

650

0.31

1.71

1.63

0.14

2.00

1.90

700

0.49

1.95

1.86

0.32

2.27

2.16

0.12

2.63

2.50

750

0.67

2.21

2.10

0.51

2.56

2.44

0.32

2.92

2.78

0.10

3.35

3.19

800

0.85

2.50

2.38

0.70

2.85

2.71

0.52

3.25

3.09

0.31

3.70

3.52

0.07

4.20

4.00

850

1.05

2.80

2.66

0.91

3.19

3.04

0.74

3.61

3.44

0.53

4.07

3.87

0.29

4.62

4.40

900

1.25

3.11

2.96

1.12

3.55

3.38

0.96

3.99

3.80

0.76

4.51

4.29

0.53

5.07

4.82

950

1.46

3.46

3.29

1.34

3.92

3.73

1.18

4.43

4.22

1.00

4.97

4.73

0.78

5.53

5.26

1000

1.67

3.82

3.64

1.56

4.33

4.12

1.42

4.88

4.64

1.24

5.44

5.18

LEU 240 AIR FLOW PERFORMANCE

WC"

Total External Static Pressure

2
1.8
1000RPM

1.6
1.4

950RPM

1.2

900RPM

850RPM

0.8

800RPM

0.6

750RPM

0.4

700RPM

5 HP

4 HP

3 HP

0.2

600RPM

0
6400

650RPM

2 HP

7200

8000

8800

9600

Cubic Feet Per Minute (CFM)


*When determining required brake horsepower, select nearest HP to the right of selected CFM.
Horsepower ratings on the Airflow Chart are approximate values. To assure correct BHP, please refer to Supply
Air Blower Performance Chart at the top of the page.

Unitary Products Group

Page 161

http://www.rezine.net
036-21096-001-C-0206

BLOWER MOTOR AND DRIVE DATA


Drive
Accessory
Model No.
1LD0404

Motor

Blower Pulley

RPM Range

HP

Frame

Shaft Size

Mfgs. No.

Size

Mfgs. No.

Size

600 - 775

56

7/8

A55

AK104

10 X 1-3/16

1VM50

1LD0406

775 - 970

184

1-1/8

A512

2AK94

9 X 1-3/16

2VP56

3.4-4.4 x 7/8
4.0-5.0 x 11/8

Belt

Motor Pulley

All motors are 1750 RPM and have a 1.15 service factor.

Two matched belts.

HEATING COIL CAPACITIES


HOT WATER COIL CAPACITY*, Mbh
Hot Water Coil
Accessory

Unit Model

1HW0405

LEU240

GPM

CFM

35

6,400
8,000
9,600

70
179
199
220

*These capacities do not include any blower motor heat.


NOTE: Water Temperature Drop (

F) =

Entering Water Temp. Minus Entering Air Temp., F


90
110
130
229
280
331
255
312
369
282
344
407

150
382
425
469

CAPACITY CORRECTION AND PRESSURE DROP VS GPM

2 x MBH
GPM

CAUTION:
Do NOT operate the supply air blower motor above its
nominal HP rating when a unit is equipped with a hot
water coil accessory.

Hot Water Coil


Accessory

GPM

1HW0405

15
35
55
75

Pressure Drop+
PSI
0.2
0.8
1.5
2.5

Capacity Correction
Factor
0.74
1.00
1.04
1.06

For pressure drop in feet (water), multiply these values by 2.31.

Do NOT use steam in these hot water coils.

STEAM COIL CAPACITY1, Mbh @ 2 psig2


Steam Coil
Accessory

Unit Model

CFM

LEU240

6,400
8,000
9,600

1NF0453

10
402
464
481

Dry Bulb Temperature of Air Entering Coil,


30
50
364
325
419
374
435
388

70
286
330
342

These capacities do not include any blower motor heat.

Multiply these capacities by the following factors to correct for higher steam pressures.

Steam pressure, psig


Capacity correction factor

5
1.05

10
1.12

15
1.19

20
1.25

25
1.30

CAUTION:
Do NOT operate the supply air blower motor above its nominal HP rating when a unit is equipped with a steam coil accessory.

NOTE: Steam rate (lbs./hr.) = 1.025 x MBH.

Although these coils are suitable for much higher pressures,


steam above 25 psig will provide too much heat and could
damage the blower motor.

ACCESSORY STATIC RESISTANCES (IWG)


CFM
6400
7200
8000
8800
9600

Supply
Air
Plenum
.03
.03
.04
.05
.06

Return
Air
Grille
.04
.05
.06
.07
.08

NonFreeze
Steam Coil
.14
.17
.21
.25
.29

Hot
Water
Coil
.07
.08
.10
.12
.14

Unitary Products Group

PLENUM PERFORMANCE
CFM
6400
8000
9600

Throw, Feet
Minimum
Maximum
80
145
98
165
115
185

Page 162

http://www.rezine.net
036-21096-001-C-0206

UNIT DIMENSIONS

All dimensions are in inches. They


are subject to change without notice.
Certified dimensions will be provided
upon request.

ACCESSORIES

Heating Coil - Add 6 inches to overall unit


height when used.

Plenum - Add 24-5/8 inches to overall unit

height when used.


Base - Add 23-3/8 inches to overall unit
height when used.

CLEARANCES

24 inches on one side for piping connection


and access to blower motor.

One-inch on opposite side.


One-inch on rear.

A
89-1/2

B
85

C
D
26-1/8 29-1/2

E
59

F
G
H
J
2-7/16 15-7/8 12-7/16 20-3/4

K
16

L
16

M
20-3/4

N
1

P
1-5/8

Unitary Products Group

Page 163

http://www.rezine.net
036-21096-001-C-0206

ACCESSORY DIMENSIONS
SUPPLY AIR PLENUM - Model 1SP0405

SHIPPED KNOCKED DOWN


FOR FIELD ASSEMBLY

RETURN AIR GRILLE - Model 1RG0405

BASE SECTION* - Model 1BS0405

SHIPPED KNOCKED DOWN


FOR FIELD ASSEMBLY

*Ventilation air can be brought into the unit


through the base section providing the
base section is fully insulated in the field.

Unitary Products Group

Page 164

http://www.rezine.net
036-21096-001-C-0206

ACCESSORY DIMENSIONS (Cont'd.)


HOT WATER COIL* - Model 1HW0405

*Coil is field-installed between the


evaporator coil and the blower
section of the unit.

STEAM COIL* - Model 1NF0453

*Coil is field-installed between the


evaporator coil and the blower
section of the unit.

SUSPENSION KIT - Model 1HH0451

BASIC UNIT SUSPENSION WEIGHTS (Lbs.)


Suspension Point
w/3 HP Motor*
A
142
B
132
C
152
D
162
E
132
F
127
Total Weight
847
*Motor location at suspension point F.

Unitary Products Group


5005 York Drive, Norman, Oklahoma 73069
Subject to change without notice. Printed in U.S.A.
Copyright by York International Corporation 2006. All Rights Reserved.

Page 165

036-21096-001-C-0206
Supersedes: 036-21096-001-B-0901

http://www.rezine.net

Page 166

http://www.rezine.net

Page 167

http://www.rezine.net

Controls
HVAC control just became a
whole lot smarter and easier!

Only York offers the easiest


solution to help you
take control of controls.

C
O
N
T
R
O
L

COMFORT
ONLINE ALARMING
NO HASSLE SET-UP

TOTAL HVAC
CONTROL SOLUTIONS

More control for more savings

More compatibility for more flexibility

Cut energy costs, and achieve higher levels of comfort


automatically with Simplicity Intelli-Comfort controls.

The controls are compatible with the MODBUS protocol,


and are factory-installed on 3- to 25-ton Sunline and
Predator products and Millennium HA/HB Systems.

More intelligence for more capabilities


Intelli-Comfort controls use intelligent hardware and
software to give you better monitoring, more flexibility in
control set-up, and finer control of every aspect of your
HVAC system. In addition, the more intelligent the control,
the greater savings you will realize through operational
efficiencies and conservation.

More power with less effort


Intelli-Comfort is a control thats so easy to use that
you actually benefit from the power at your fingertips.

Easier to manage
Intelli-Comfort raises the intelligence of an already
smart Simplicity control.

More control for greater comfort


The flexibility of the Simplicity Intelli-Comfort control
means comfortable, happier, and more productive
occupantsthanks to the ability to optimize temperature,
humidity, and indoor air quality simultaneously.

Put the intelligence of Simplicity Intelli-Comfort controls


to work in your building.
Simplicity Intelli-Comfort controls give you powerful capabilities without complexity. Easy to set-up, program, and use, the controls give you
everything you need to monitor and control Sunline and Predator units. And because they can be connected as your HVAC Energy
Management System you can save even more by making the intelligence of Simplicity Intelli-Comfort part of your building automation strategy.

RELIABILITY
OPEN PROTOCOL
LOW COST

New features for superior


monitoring and control
365-Day Real Time Clock with
automatic Daylight Savings Time adjustment
Occupancy Schedule allowing two different occupied
schedules per day for each of the seven days of the week
20 Holiday Schedules with a length of up to 99 days, each
with flexible start times. You can now choose the time of day
your holiday begins saving energy

Patent Pending Temperature Humidity Algorithm offsets


the operating setpoint based on high humidity in the spacewith
programmable limits to control humidity

Energy-Saving Economizer Operation with the flexibility


of using dry bulb, outside enthalpy and differential enthalpy.
Our economizer enthalpy control has setpoints for outside air
temperature, supply air temperature, small space cooling demand,
and large space cooling demand

High and Low Ambient Lockout to lockout cooling below or


heating above a programmable setpoint of outside air temperature

Outside Air CO2 Sensor to close the economizer if CO2 is present


Inside Demand Ventilation using one CO2 sensor or differential
demand ventilation using inside and outside CO2 sensors
IAQ Operation with programmable maximum outside air
damper position

Space Temperature Alarm when temperatures are outside


of program setpoints. Alarm setpoints are user programmable
Unit Monitors Airflow to detect dirty filters and insufficient airflow
Intelligent Recovery brings the space temperature to the
occupied setpoint just before or at the beginning of the first
occupied schedule each day. The control will learn and apply
the minimum runtime required to heat or cool the space to
minimize energy use

Comfort Ventilation Control tempers the ventilation air


when heating or cooling is not required, increasing comfort

2004 York International Corporation.


All rights reserved. Subject to change without notice.
Form 036-12054-001 (0105). Supersedes: Nothing. Printed in USA.

Page 168

http://www.rezine.net

Page 169

http://www.rezine.net

COMMERCIAL ZONING PACKAGE

The Facility Explorer Commercial Zoning Package is a complete, turnkey control system used to improve
occupant comfort in a building (or section of a building) that is conditioned with a packaged rooftop HVAC unit.
It accomplishes this by varying the amount of conditioned air delivered to individual zones and by intelligently
cycling the rooftop units heating and cooling stages to best satisfy all the zone demands.

Manufacturer Independent
The Facility Explorer Commercial Zoning
Package is designed to work with any
standard, packaged HVAC equipment, regardless
of manufacturer. This allows you to apply this control
package to equipment provided by a variety of
suppliers or to equipment that has already been
installed. This flexibility makes the Facility Explorer
Commercial Zoning Package perfectly suited for both
new and retrofit installations.
Affordable Intelligence
The Facility Explorer Commercial Zoning Package
utilizes the distributed application architecture of
the FX16 Master Controller. This feature allows direct
communications to occur between the FX16 and all
the zone controllers. This means that there is no
need for a traditional supervisory class controller to
manage the data sharing. This direct communication
flow allows the FX16 to monitor each zones status to
intelligently determine the proper mode of operation
for the rooftop unit.

Page 170

http://www.rezine.net

COMMERCIAL ZONING PACKAGE

Easy Installation
Several pieces of the Facility Explorer Commercial
Zoning Package can be ordered pre-assembled from
the factory to simplify installation:

Bypass Damper and Actuator Assembly

Zone Controller and Actuator Assembly (FXZAN)

FX16 Master Controller with Pre-Downloaded


Zoning Application

The FX05 Field Controller is combined with an


M9104AGA non-spring return actuator and an
electrical termination wiring block, all in one
packaged assembly

FX16 Master Controller can be ordered with the


commercial zoning application pre-downloaded

Perfect for retrofit installations where the zone


damper is already installed
Zone Controller, Actuator, and Damper Assembly
FXZAN Zone Controller and Actuator Assembly is
combined with a round or rectangular zone damper
Perfect for new installations or for retrofit
installations where the zone damper has not yet
been installed

2005 Johnson Controls, Inc.

A round or rectangular bypass damper is combined


with an M910xHGA non-spring return actuator

Once installed, the FX16 takes care of downloading


the corresponding parts of the zoning application to
each of the zone controllers
Eliminates the downloading steps from the field
installation and startup
This provides the possibility (with an onsite Medium
User Interface) to download, configure and
commission the entire system, including the
rooftop, bypass, and all zone controllers without
any software tool

P.O. Box 423, Milwaukee, WI 53201

Page 171

Printed in USA PUBL-3894

http://www.rezine.net

Page 172

http://www.rezine.net

TSS Single Duct Variable Air Volume Terminal

An integrated VAV box with direct digital controls

TSS Terminals provide Variable Air Volume (VAV) control

eliminates the coordination and difficulties

beyond the typical single duct box. They are specifically

associated with factory mounting

designed for precise air delivery throughout the entire


operating range, regardless of the installed inlet conditions.

Downloading of software, setting of parameters,

These units can be ordered with or without a Direct Digital

addressing and testing at the factory reduces

Controller (DDC), which can operate as a stand-alone unit,

startup time and lowers risk

on a Johnson Controls N2 trunk, or on a LON trunk.

Superior flow measuring provides for lower

TSS Terminals take advantage of typical benefits provided

minimum cubic feet per minute (CFM) values,

by single duct units, while performing at extremely low

which reduces energy costs and noise while

sound levels. This is critical in todays buildings where

maintaining comforts in the zone

occupants are placing more emphasis on indoor acoustics.


The TSS Terminal is manufactured and assembled with a

Installation time can be reduced with the low

multi-point, center-averaging airflow sensor, which

profile compact design and standard metal

provides a signal to the controller enabling it to quietly and

hanging straps

precisely measure airflow.

Units wired in compliance with all applicable

Bundled with the TSS Terminal is a digital controller from

National Electrical Code (NEC) requirements and

the VAV Modular Assembly (VMA) Series or the LN Series.

tested in accordance with Air Conditioning and

Each model in the VMA1400 Series and the LN Series

Refrigeration Institute (ARI) standard 880

combines a controller, pressure sensor, and actuator


housed in one pre-assembled unit.

Offers damper stall detection, starved box


detection, actuator motor duty cycle, VAV box
flow test, and other diagnostics on most
models (VMA Series)

Page 173

http://www.rezine.net

TSS Single Duct Variable Air Volume Terminal

Standard Features

Optional Features

Construction

Construction

ARI 880 certified and labeled

20-gauge galvanized steel construction

22-gauge galvanized steel casing and valve

3/4 or 1 fiberglass insulation

G90 galvanized steel

Scrim-reinforced, foil-faced insulation meeting American


Society for Testing and Materials (ASTM) C1136 for mold,
mildew, and humidity resistance

1/2, 4lb/ft3 skin, dual density fiberglass insulation, glued


and clinch-pinned in place

1/2 Elastomeric closed-cell foam insulation

Hot Water Coils

Double wall construction with 22-gauge liner

ARI 410 certified and labeled

Mounting brackets to accept all-thread hanging rods or


wire hangers

1-, 2-, 3-, 4-row coils


Tested at a minimum of 350 psig under water

Low temperature construction for use in thermal storage


applications, including a thermally isolated primary air
inlet and a composite damper shaft

Mechanically expanded copper tubes leak tested


to 350 psig air pressure
Male sweat type water connections

Hot Water Coils


Low pressure steam coils

Primary Air Valve


Embossed rigidity rings

Multi-circuit coils for reduced water pressure drop

Low-thermal conducting damper shaft with


position indicator

Opposite hand water connections


Bottom and top access plates for cleaning

Mechanical stops for open and closed position

Electrical Components

Multi-point center-averaging airflow sensor

Full unit toggle disconnect and inline motor fusing

Brass balancing tees

Primary and secondary transformer fusing

Plenum-rated sensor tubing

Electric Heat

Electrical Components

Proportional solid state relay (SSR) heater control

cETL listed for safety compliance

Mercury contactors

National Electrical Manufacturers Association (NEMA)


Type 1 wiring enclosure

Door interlocking disconnect switches


Disconnect (toggle or door interlocking)

Electric Heat
ETL listed as an assembly for safety compliance
Integral electric heat assembly
Automatic reset primary and back-up secondary
thermal limits

Pneumatic Electric (PE) switches


Mercury and magnetic contactors
Manual reset secondary limit
24 volt control transformer

Single-point power connection

Special watt densities

Hinged electrical enclosure

Finned tubular elements

Fusing per NEC

Controls

Airflow switch

Factory-provided controls

Ni-chrome elements

Direct digital controls (DDC) for N2 or LON networks

Primary/Secondary power terminations

Pneumatic controls

Wiring diagram

2005 Johnson Controls, Inc.

P.O. Box 423, Milwaukee, WI 53201


www.johnsoncontrols.com

Page 174

Printed in USA PUBL-3888

http://www.rezine.net

TSL Single Duct Low Height Variable Air Volume Terminal

An integrated VAV box with direct digital controls

TSL Terminals provide variable air volume (VAV) control

eliminates the coordination and difficulties

beyond the typical single duct box. They are specifically

associated with factory mounting

designed for precise air delivery throughout the entire


operating range and are only 10 in height, making them

Downloading of software, setting of parameters,

ideal for shallow or congested ceiling plenum applications.

addressing and testing at the factory reduces

These units can be ordered with or without a Direct Digital

startup time and lowers risk

Controller (DDC), which can operate as a stand-alone unit,


on a Johnson Controls N2 trunk, or on a LON trunk.

Superior flow measuring provides for lower


minimum cubic feet per minute (CFM) values,

TSL Terminals take advantage of typical benefits provided

which reduces energy costs and noise while

by single duct units, while performing at extremely low

maintaining comforts in the zone

sound levels. This is critical in todays buildings where


occupants are placing more emphasis on indoor acoustics.

Installation time can be reduced with the low

The TSS Terminal is manufactured and assembled with

profile compact design and standard metal

a multi-point, center-averaging airflow sensor, which

hanging straps

provides a signal to the controller enabling it to quietly and


precisely measure airflow.

Units wired in compliance with all applicable


National Electrical Code (NEC) requirements and

Bundled with the TSL Terminal is a digital controller from

tested in accordance with Air Conditioning and

the VAV Modular Assembly (VMA) Series or the LN Series.

Refrigeration Institute (ARI) standard 880

Each model in the VMA1400 Series and the LN Series


combines a controller, pressure sensor, and actuator
housed in one pre-assembled unit.

Page 175

TSL Single Duct Low Height Variable Air Volume Terminal

http://www.rezine.net

Secondary high limit

Standard Features

Airflow switch

Construction
ARI 880 certified and labeled

Single-point power connection

20-gauge, galvanized steel casing and valve

Hinged electrical enclosure door

G90 galvanized steel construction

Fusing per NEC

1/2", 4 lb/ft3 skin, dual density fiberglass insulation glued


and clinch pinned

Optional Features

Invertible unit facilitates control installation on the left- or


right-hand side

Construction

Hot Water Coils


ARI 410 certified and labeled

Scrim-reinforced, foil-faced insulation meeting American


Society for Testing and Materials (ASTM) C1136 for mold,
mildew, and humidity resistance

1-, 2-, 3-, 4-row coils

1/2 Elastomeric closed-cell foam insulation

Left- or right-hand connections

Double wall construction with a 22-gauge liner

Tested at a minimum of 450 psig under water and rated


at 300 psig working pressure at 200F

Mounting brackets to accept all thread hanging rods or


wire hangers

Aluminum fin construction with die-formed spacer collars


for uniform spacing

Discharge sound attenuator (Model TSL-SA)

Mechanically expanded copper tubes leak tested to 450


psig air pressure and rated at 300 psig working pressure
at 200F

Coil access plate for cleaning coil

Hot Water Coil


Coil circuiting options for reduced water pressure drop
Right- or left-hand water connections

Male sweat type water connections

Bottom and top access plates for cleaning

Primary Air Valve


18-gauge, G90 galvanized steel construction

Steam coils

Low thermal conductance damper shaft

Electrical Components

Position indicator on external end of damper shaft

Toggle disconnect switch

Mechanical stops for open and closed position

Primary and secondary transformer fusing

Multi-point center-averaging airflow sensor

Electric Heat

Brass balancing tees

Proportional solid state relay (SSR) heater control

Plenum-rated sensor tubing

Mercury contactors (if equipped with a mercury contactor,


the unit cannot be inverted)

Electrical Components

Door interlocking disconnect switches

cETL listed for safety compliance with Underwriters


Laboratories Inc. (UL) 1995

Disconnect (toggle or door interlocking)

National Electrical Manufacturers Association (NEMA)


Type 1 wiring enclosure

Pneumatic Electric (PE) switches

Electric Heat

Manual reset secondary limit

Invertible unit facilitates control installation on the left- or


right-hand side (not applicable if equipped with a
mercury contactor)

Controls

cETL listed as an assembly for safety compliance

Direct Digital Controls (DDC), for N2 or LON networks

Automatic reset primary and back-up secondary


thermal limits

Pneumatic controls

Mercury and magnetic contactors

Factory-provided controls

Primary auto-reset high limit

2005 Johnson Controls, Inc.

P.O. Box 423, Milwaukee, WI 53201


www.johnsoncontrols.com

Page 176

Printed in USA PUBL-3882

http://www.rezine.net

Single Duct Variable Air Volume Terminal (Model TSS)


Unit
Size
6
8
10
12
14
16
22

CFM
200
400
600
800
1100
1500
3000

Bypass
CFM
300
600
900
1200
1800
2200
5400

Dimensions
Weight
18
20
25
30
38
42
72

WxHxL
10 x 10" x 11"
12 x 10 x 11"
14 x 12.5" x 13
16 x 15" x 13
20 x 17.5" x 17.5"
24 x 17.5" x 17.5"
34 x 17.5" x 11"

A
6 1/2
6 1/2
6 1/2
6 1/2
6 1/2
6 1/2
8

I
5 7/8
7 7/8
9 7/8
11 7/8
13 7/8
15 7/8
32 1/4 x 15 7/8

X
8 3/4
10 3/4
12 3/4
14 3/4
18 3/4
22 3/4
32 3/4

Y
8 3/4
8 3/4
11 1/4
13 3/4
16 1/4
16 1/4
16 1/4

Note: All dimensions are in inches with a tolerance of +1/8. Size 22 has a rectangular inlet collar. CFM based on
1000 FPM (Bypass 1500 FPM) for low to medium pressure applications.

Clearance 24"

Page 177

http://www.rezine.net

Single Duct Variable Air Volume Terminal - Rectangular (Model TSL)

Dimensions
Unit
Bypass
Size
CFM
CFM
A
W
L
X
Weight
10
600
1200
10
15
12 1/2
13 3/4
26
12
800
1600
14
19
12 1/2
17 3/4
28
14
1200
2200
20
25
16 1/2
23 3/4
39
16
1500
3000
26
31
16 1/2
29 3/4
45
Notes: 1. For dimensional data for unit sizes 6 and 8, refer to the Single Duct Variable
Air Volume Terminal (Model TSS). All dimensions are in inches with a tolerance of +1/8.
Weights are in pounds. Weights are for the basic unit with the indicated option and
control enclosure. Actual weight varies based on project-specific requirements for unit
options, appurtenances, and controls. 2. Control enclosure is standard with factorymounted electronic controls. 3. Check all national and local codes for required
clearances.

Page 178

http://www.rezine.net

Page 179

http://www.rezine.net

Model DE Series
UVC Emitters

UVC for HVAC

TM

power needed to maintain microbial control. The UVC


Emitter, by contrast, has a 12-month service life and even
after a full year, it has 2-1/2 times greater output than
competitive devices deliver on Day 1! As a result, only SterilAire can ensure the germicidal performance you need, with no
return of microbial growth, for 3-4 times longer than the
competition.

Double-Ended, Very High


Output Germicidal Light
Source for HVAC Systems

Applications
Steril-Aire Double-Ended (DE Series) fixtures are used
for internal installation in medium to large air handling
systems in commercial, industrial, health care and institutional
buildings. They may be mounted singly, in built-up banks or in
parallel configurations in a variety of locations, including
coils, drain pans, ductwork, mixed air plenums and exhaust
systems. The DE Series is available in five lengths (18, 24,
30, 36 and 42) and four voltage options (115, 208, 230 or
277 Vac), providing installation flexibility to accommodate
virtually any system.

Benefits
Kills or inactivates surface and airborne microorganisms that
contribute to poor IAQ and/or the spread of infectious disease,
including: mold and mold spores, bacteria (including TB,
Legionella, E. coli, Listeria, salmonella, and whooping
cough); and viruses (including colds, flu, measles).
Delivers an average of 5 times the output of competitive UVC
products at HVAC operating temperatures, for 3-4 times
longer life and more reliable germicidal control.
Uses patented state-of-the-art solid-state electronic power
supply for enhanced reliability and performance.
Continuously cleans coils, drain pans, plenums and ducts,
eliminating costly cleaning programs and the use of harmful
chemicals and disinfectants.
Lowers HVAC energy costs by restoring heat transfer and net
cooling capacity.
Steril-Aires multi-patented UVC Emitter provides the
best and longest-lasting UVC performance available. As
shown in the comparison graph (above), it has been
independently tested to deliver an average of 5 times the
output of other ultraviolet devices under HVAC operating
conditions (45o F @ 550 fpm air velocity).
Competitive UVC lights must be changed every 3-4
months because they quickly lose the output or killing

Produces no ozone or other secondary contaminants will not


harm building occupants, equipment or furnishings.
Offers lowest life-cycle cost of any UVC product. Return on
investment is often less than one year.
The most widely used product for commercial UVC for
HVAC the industry standard!

Page 180

http://www.rezine.net

Model DE Specifications
The UVC EmitterTM and fixture shall be factory assembled and
tested. They shall consist of a housing, power source, reflector,
Emitter sockets and Emitter.

be available in 115-208/230 or 277 Vac, 50/60 Hertz, and single phase.


The Emitter soc kets are medium bi-pin, double click safety, twist
lock type. They shall be constructed of UVC-resistant polycarbonate.

The housing shall be constructed of 304 stainless steel to withstand


HVAC environments. The reflector shall be constructed of heavy
gauge, specular finished aluminum alloy with approximately 85%
reflectance at 254 nm wavelength. The housing shall be equipped
with 1/2" electrical conduit openings on each end to facilitate
coupling and wiring fixture-to-fixture and to power. All components
shall be in one integral assembly to maximize serviceability.
The power source shall be a Class P2, electronic, rapid start type
with a power factor greater than 0.95 and a power conversion of
greater than 75%. The power supply design shall include RF and EMI
suppression. The power supply shall be designed to maximize photon
production, irradiance and reliability in cold or moving airstreams of
35-170 F, 100% RH and up to 2000 fpm velocity. The fixture shall

The Emitter tube shall be a very high output, hot cathode, T5


diameter, medium bi-pin type that produces broadband UVC of 250260 nm. Each tube shall produce the specified output at 2000 fpm
velocity and air temperatures of 35-170 F. It shall produce no ozone
or other secondary contaminants.
Inde pendent testing: The unit shall be tested by an independent test
laboratory in accordance with the general provisions of IES Lighting
Handbook, 1981 Applications Volume, and shall be verified through
independent testing to provide output per 1" arc length of not less
than 10 W/cm2 at 1 meter in a 400 fpm airstream of 45 F.
Unit shall comply with UL Standard 1995 for use in HVAC
equipment and shall carry the "UL" and "ULC" labels.

This product may be covered by one or more of the following patents, others pending: 5,334,347/ 5,866,076/ 5,817,276/ 6,372,186/ 6,313,470/ 6,245,293/
6,267,924/ 6,280,686/ 6,423,882.

Ordering Information
Model No.

Part No.

Description

Length

DE 181 VO
DE 181 VO
DE 241 VO
DE 241 VO
DE 301 VO
DE 301 VO
DE 361 VO
DE 361 VO
DE 421 VO
DE 421 VO
GTD 16 VO
GTD 22 VO
GTD 28 VO
GTD 34 VO
GTD 40 VO

10001500
10002100
10001600
10002200
10001700
10002300
10001800
10002400
10001300
10002500
20000100
20000200
20000300
20000400
20000500

Double-Ended Fixture
Double-Ended Fixture
Double-Ended Fixture
Double-Ended Fixture
Double-Ended Fixture
Double-Ended Fixture
Double-Ended Fixture
Double-Ended Fixture
Double-Ended Fixture
Double-Ended Fixture
Replacement Emitter DE 181
Replacement Emitter DE 241
Replacement Emitter DE 301
Replacement Emitter DE 361
Replacement Emitter DE 421

18"
18"
24"
24"
30"
30"
36"
36"
42"
42"
16"
22"
28"
34"
40"

Electrical
115, 208, 230V: 70-85 watts
277V: 70-85 watts
115, 208, 230V: 70-85 watts
277V: 70-85 watts
115, 208, 230V: 70-85 watts
277V: 70-85 watts
115, 208, 230V: 70-85 watts
277V: 70-85 watts
115, 208, 230V: 70-85 watts
277V: 70-85 watts
N/A
N/A
N/A
N/A
N/A

Weight
2.3 lb.
2.3 lb.
2.7 lb.
2.7 lb.
3.3 lb.
3.3 lb.
3.7 lb.
3.7 lb.
4.1 lb.
4.1 lb.
0.15 lb.
0.15 lb.
0.20 lb.
0.25 lb.
0.25 lb.

Complies with current U.S. and Canadian UL Standards for


use in HVAC equipment.

Represented By:

Steril-Aire, Inc.
Corporate Office:
2840 N. Lima Street
Burbank, CA 91504
Telephone: 818-565-1128
Fax: 818-565-1129
Website: www.steril-aire.com
Email: sales@steril-aire.com
2003 Steril-Aire

1100-07/05

Page 181

http://www.rezine.net

Page 182

http://www.rezine.net
036-21335-003-B-0206

TECHNICAL GUIDE

PROVEN PERFORMANCE

SPLIT-SYSTEM AIR-COOLED

GENERAL

EVAPORATOR BLOWER
25,30,40 & 50 TON
LA300,LB360,480 & 600

The LA/LB line is a flexible performer. LA300, LB360 & 480


can be positioned in up to 12 different positions and suspended in various positions. The LB600 can be positioned in
up to 7 different arrangements and suspended also. The LA/
LB line will give you the power to condition large amounts of
building space and the ability to conform to almost any situation.

FEATURING
EASE OF SERVICE
PUMP-OUT ON START-UP
BASE SECTIONS (25, 30 & 40 Ton only)
SUSPENSION PACKAGES
HOT WATER COILS
STEAM COILS (LA300 & LB360 only)
WIDE RANGE OF BLOWER MOTORS
A VARIETY OF DRIVE PACKAGES
CONTROL BOX WITH LOW VOLTAGE TRANSFORMER AND MOTOR STARTER (motor, motor drive
kit and motor overloads sold separately).

FOR DISTRIBUTION USE ONLY -Page


NOT TO183
BE USED AT POINT OF RETAIL SALE

http://www.rezine.net
036-21335-003-B-0206

TABLE OF CONTENTS

LIST OF TABLES

DESCRIPTION ..............................4
MODULAR DESIGN .........................4
FACTORY-MOUNTED COMPONENTS ..........4
ACCESSORIES .............................4
GUIDE SPECIFICATIONS ....................23

LIST OF FIGURES
Fig.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18

Pg.
PRODUCT NOMENCLATURE . . . . . . . . . . . . . . . . . 3
UNIT INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . 4
DETAILS FOR SECURING BOTTOM MOUNTING
SUPPORTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
LA300/LB360 WEIGHT DISTRIBUTION. . . . . . . . . . 6
UNIT DIMENSIONS - LA300, LB360 & LB480 . . . . 11
25 TON LIQUID LINE SOLENOID WIRING. . . . . . . 11
30, 40 & 50 TON LIQUID LINE
SOLENOID WIRING . . . . . . . . . . . . . . . . . . . . . . . . 11
LA300 PIPING CONNECTIONS . . . . . . . . . . . . . . . 12
LB360 PIPING CONNECTIONS . . . . . . . . . . . . . . . 12
LB480 PIPING CONNECTIONS . . . . . . . . . . . . . . . 12
UNIT DIMENSIONS - LB600 . . . . . . . . . . . . . . . . . . 13
LB600 PIPING CONNECTIONS END PANEL DETAIL. . . . . . . . . . . . . . . . . . . . . . . . 13
HOT WATER COIL DIMENSIONS. . . . . . . . . . . . . . 14
STEAM COIL DIMENSIONS . . . . . . . . . . . . . . . . . . 14
BASE SECTION DIMENSIONS . . . . . . . . . . . . . . . . 14
BLOWER CURVE LA300 & LB360 . . . . . . . . . . . . . 19
BLOWER CURVE LB480. . . . . . . . . . . . . . . . . . . . . 21
BLOWER CURVE LB600. . . . . . . . . . . . . . . . . . . . . 22

Tbl.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22

Pg.
STATIC RESISTANCES FOR UNIT ACCESSORIES . 5
UNIT MOUNTING DIMENSIONS . . . . . . . . . . . . . . . . . 5
CORNER WEIGHTS . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
ACCESSORY OPERATING WEIGHT
DISTRIBUTION (LBS). . . . . . . . . . . . . . . . . . . . . . . . . . 7
UNIT BLOWER MOTOR DATA . . . . . . . . . . . . . . . . . . 7
UNIT DRIVE DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
MOTOR OVERLOAD ELEMENTS . . . . . . . . . . . . . . . . 8
HOT WATER COIL CAPACITIES . . . . . . . . . . . . . . . . . 9
HOT WATER COIL CAPACITY CORRECTION
AND PRESSURE DROP VS GPM . . . . . . . . . . . . . . . . 9
STEAM COIL CAPACITIES, MBH @ 2 PSIG . . . . . . . 10
CORRECTION FACTORS FOR HIGH STEAM . . . . . 10
UNIT DIMENSIONS - LA300, LB360, LB480 . . . . . . . 11
UNIT CONNECTION SIZES . . . . . . . . . . . . . . . . . . . . 12
HOT WATER COIL DIMENSIONS . . . . . . . . . . . . . . . 14
STEAM COIL DIMENSIONS. . . . . . . . . . . . . . . . . . . . 14
BASE SECTIONS DIMENSIONS . . . . . . . . . . . . . . . . 14
PHYSICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
ELECTRICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . 17
FAN PERFORMANCE DATA - 25 TON . . . . . . . . . . . 18
FAN PERFORMANCE DATA - 30 TON . . . . . . . . . . . 18
FAN PERFORMANCE DATA - 40 TON . . . . . . . . . . . 20
FAN PERFORMANCE DATA - 50 TON . . . . . . . . . . . 20

Unitary Products Group

Page 184

http://www.rezine.net
036-21335-003-B-0206

YORK SPLIT INDOOR PRODUCT NOMENCLATURE


L A 300 C 00 A 6 A AA 1 A
Model Number
Description

Options

Product Category

L = Air Handling Unit - Cooling F = Air Handling Unit - Heat Pump

Product Identifier

A = R-22 Standard Efficiency 2-Pipe


B = R-22 Standard Efficiency 4-Pipe

300

Nominal Cooling
Capacity
MBH

300 = 25 Ton
360 = 30 Ton
480 = 40 Ton
600 = 50 Ton

Heat Type

C = Cooling Only

00

Nominal Heating
Capacity

00 = No Heat Installed

Airflow Options

A = None

Voltage

0 = None
5 = 575-3-60

Factory Options

A = None

AA

Special Options

AA = None

Product Generation

1 = First Generation

Model #

FIGURE 1 -

6 = 208/230-460-3-60

2 = Second Generation

PRODUCT NOMENCLATURE

NOTE: LB600 matches with both HB480 and HB600


Outdoor Condensing Units for maximum efficiency.

Unitary Products Group

NOTE:LB480 Indoor and HB480 Outdoor Units do


match up, but do not meet ASHRAE 90.1 standards for efficiency.

Page 185

http://www.rezine.net
036-21335-003-B-0206

DESCRIPTION
Evaporator blower units are designed with two distinct modules to provide maximum application flexibility. The 25, 30
and 40 ton units are shipped as single packages with the
blower module mounted on top of the coil module, The
blower module can be repositioned in the field to meet almost
any installation requirement. Blower and coil modules for the
50 ton units are shipped separately to simplify handling.
These modules can be connected in the field with the same
flexibility as the smaller units.

Figure 2 shows three of the common installation arrangements. Refer to the unit installation instructions for other possibilities.
Units may be bottom-supported or ceiling-suspended and
can be arranged to meet almost any space or duct requirements. Each unit is available with a choice of blower motors,
drive packages and other accessories to make them suitable
for most applications.

FACTORY-MOUNTED COMPONENTS

The blower module includes the blower wheels and room for
a field-mounted motor and drive. The coil module includes
direct expansion coils, 2 in. throwaway filters, liquid line solenoid valves for both capacity reduction and pumpdown, thermal expansion valves, distributors and a condensate drain
pan.

PART LOAD OPERATION These evaporator blowers have


multiple coils with pre-piped distributors, expansion valves
and solenoid valves. Field modifications are not required for
part load operations. Capacity reduction not only provides
economical operation, but also maintains more even temperature and humidity levels in the conditioned space.

Every evaporator coil is pressurized with air to 325 psig and


leak tested under water. After the headers are brazed onto
the coil and the coil is installed in the unit, the coil is pressurized with a combination of Refrigerant-22 and nitrogen to 150
psig for pressure testing and additional leak testing. After the
coil is evacuated and dehydrated, it is pressurized with a
holding charge of Refrigerant-22 for storage and/or shipping.

EASY SERVICE Serviceable expansion valves are provided


on every unit. These superior valves are factory-installed to
provide many years of trouble-free operation. If service is
required, it is not necessary to unbraze any joints.

Steam coils, hot water coils, base sections, suspension hardware, blower motors and drive packages are available as
field-installed accessories to provide additional application
flexibility.
These evaporator blowers, combined with condensing units,
provide years of quiet, efficient and dependable operation.
These units are manufactured under ISO 9001 Quality System Certification.
For Indoor Unit Installation details, please see document 03518496-000.

MODULAR DESIGN
These evaporator blowers can be arranged for a variety of air
discharge patterns in either the horizontal or vertical position.

FIGURE 2 -

UNIT INSTALLATION

PUMP-OUT Evaporator blowers include a solenoid valve for


non-recycling pump-out. When a cooling requirement in the
conditioned space is needed, the refrigerant is pumped into
the high side of the system before unit start-up.

ACCESSORIES
BASE SECTIONS (25, 30 and 40 ton only: Base sections can
be used to elevate units above the floor. If desired, outdoor
air may be introduced through these sections by cutting an
access opening to accommodate the outdoor air duct connection. These bases have a durable finish to match the
evaporator blower unit. They may have to be insulated for
certain applications.
SUSPENSION PACKAGES: These accessories can be used
to suspend horizontal units from above without interfering
with access to the unit. They can also be used for elevating a
floor-mounted unit (either horizontal or vertical) to provide
additional height for the installation of a trap at the condensate drain connection. All suspension packages can be used
with vibration isolators.
HOT WATER COILS: Drainable water coils are available for
field installation between the blower and the coil modules of
both horizontal and vertical units. Since their casings match
the dimensions and the finish of the basic units, they become
an integral part of the unit after installation. The coils slide out
of their casings for easy installation. Coils have copper tubes
that have been mechanically expanded into aluminum fins.
Both headers are located on the same end of the coil. Coils
are leak-tested at 325 psig under water and dried before their
connections are capped for storage and shipping.

Unitary Products Group

Page 186

http://www.rezine.net
036-21335-003-B-0206

STEAM COILS (LA300 & LB360 only): A steam coil is available on the 25 & 30 Ton for installation between the blower
and coil modules of both horizontal and vertical units. Since
the casing matches the dimensions and the finish of the basic
unit, it becomes an integral part of the unit after installation.
The coil slides out of the casings for easy installation and is
pitched in the casings to facilitate condensate drainage. The
coil has copper tubes that have been mechanically expanded
into aluminum fins. Both headers are located on the same
end of the coil. The coil is leak-tested at 325 psig and dried
before the connections are capped for storage and shipping.

rounding space. 5 HP motors are inherently protected. 7.5


HP - 15 HP require motor overload protection. Power wiring
for blower motor is field supplied.
DRIVE PACKAGES: Different size pulleys and belts are available for each unit to provide a blower RPM range to meet
almost any air delivery requirement. Variable pitch motor pulleys can be adjusted to provide the proper blower RPM. All
drive packages are rated at least 25% above the nominal HP
rating of the blower motor. Two-groove pulleys and two belts
are provided on every drive package rated at 5 HP and
above.

BLOWER MOTORS: Different HP motors are available for


each unit to meet almost any air delivery requirement. All
motors are UL approved, have permanently lubricated ball
bearings and are field-mounted within the insulated cabinet of
the units to minimize the transmission of sound to the sur-

STARTERS AND HEATER ELEMENTS (7.5 - 15 HP): The


blower motors that are available for the units do not have
inherent protection and require external motor overload protection. See details in Table 7.

TABLE 1:STATIC RESISTANCES FOR UNIT ACCESSORIES


UNIT MODEL

LA300

LB360

ACCESSORY

CFM
8,000

9,000

10,000

11,000

12,000

Hot Water Coil

0.06

0.07

0.08

0.09

0.10

Steam Coil

0.11

0.14

0.17

0.20

0.23

10,000

11,000

12,000

13,000

14,000

Hot Water Coil

0.08

0.09

0.10

0.12

0.14

Steam Coil

0.17

0.20

0.23

0.27

0.31

12,800

14,400

16,000

17,600

19,200

0.11

0.13

0.15

0.17

0.20

16,000

18,000

20,000

22,000

24,000

0.15

0.18

0.21

0.24

0.28

LB480
Hot Water Coil
LB600
Hot Water Coil

TABLE 2:UNIT MOUNTING DIMENSIONS1


LA/LB
UNIT

DIMENSIONS,INCHES

300

AX
69-1/4

BX
49-1/16

CX
26-5/8

360

69-1/4

49-1/16

26-5/8

480

84

50-9/16

34

1.

See Figure 4 for dimensions AX, BX and CX.

Unitary Products Group

Page 187

http://www.rezine.net
036-21335-003-B-0206

NOTE: The following illustration shows how the channels


should be secured to the unit using the hardware
provided with the suspension accessory.

(2) 9/16 HOLES FOR 1/2


HANGER RODS
SUSPENSION
CHANNEL

5/16 NUT,
LOCKWASHER,
FLATWASHER

5/16 NUT,
FLATWASHER

3/8 NUT (USED


AS SPACER)
UNIT PANEL
5/16 BOLT,
FLAT-WASHER
SIDE
PANEL

UNIT ANGLE

FIGURE 3 : DETAILS FOR SECURING BOTTOM MOUNTING SUPPORTS

AX

BX

VERTICAL LA300, LB360, LB480


UNIT SUPPORTED FROM BELOW
BX

A
3

C
B LOWE R
S E C TIO N

1-1/2

HOR IZONTAL
LE U360 O R 480
UNIT S US P E NDE D
F R OM A B OVE 3

E VAP . C OIL
S E C TIO N

B LOWE R
S E C TIO N

E VAP .
C OIL
S E C TIO N
HE ATING C OIL 2

CX

S US P E NS IO N
ANG LE S 1

BX
D
1

The s ame channels can be used in either position. W hen used to


support at vertical unit, these channels s hould be cut to match the
bottom dimension of the e vaporator coil s ection.

The s uspension channels have two s ets of mounting holes to


accommodate horizontal units with or without a heating coil. O n
a horizontal unit without a heating coil, th e s uspension channels
will extend 3" beyond both e nds of the unit.

The s ame channels can be used to s upport a horizontal, fl oormounted unit from below.

After these bottom channels a re cut per N ote 1, a new h ole will have
to be drilled a t the cut end if the unit is to be mounted on isolators.

BX

FIGURE 4 : LA300/LB360 WEIGHT DISTRIBUTION

Unitary Products Group

Page 188

http://www.rezine.net
036-21335-003-B-0206

TABLE 3:CORNER WEIGHTS


Unit Weight

UNITMODEL

Shipping

Operation

LA300

1180

1125

LB360

1180

1146

LB480

1510

1426

LB600

1572

1640

Configuration
HORIZONTAL
VERTICAL
HORIZONTAL
VERTICAL
HORIZONTAL
VERTICAL
HORIZONTAL
VERTICAL

A
276
262
281
266
348
292
451
484

B
317
301
323
307
414
348
386
414

C
285
301
290
307
361
427
370
342

D
247
262
252
266
303
359
433
400

TABLE 4:ACCESSORY OPERATING WEIGHT DISTRIBUTION (LBS)1


ACCESSORY

LA300

LB360

LB480

LB600

BASE2

25

25

30

45

HOT WATER COIL

35

35

45

35

STEAM COIL 1 ROW

30

30

35

50

1.

These weights should be added to each point load in table 3.

2.

This accessory can only be applied on units installed in the vertical position.

TABLE 5:UNIT BLOWER MOTOR DATA


UNIT MODEL

HP

MOTOR KIT
MODEL NUMBER

FRAMESIZE

2LR04605032
5
LA300

2LR04605023

230/460
184

2LP04605158

230/460
213

2LP04607158

575

2LR04605032

230/460

2LR04605023

184

2LR04605158
LB360

208
575

2LP04607133
7.5

VOLTAGE
(3PH-60HZ)

575

2LP04607133
7.5

208

208/230/460
213

2LP04607158

575

2LP04610133
10

208/230/460
215

2LP04610158

575

2LP04607133
7.5

208/230/460
213

2LP04607158

575

LB480
2LP04610133
10

208/230/460
215

2LP04610158

575

2LP04610133
10

208/230/460
215

2LP04610158

575

LB600
2LP04615133
15

208/230/460
254

2LP04615158

Unitary Products Group

575

Page 189

http://www.rezine.net
036-21335-003-B-0206

TABLE 6:UNIT DRIVE DATA


ADJUSTABLE MOTOR PULLEY
UNIT
MODEL

LA300

LB360

LB480

LB600

FIXED BLOWER PULLEY

DRIVE KIT
MODEL
NUMBER

BLOWER
RPM
RANGE

PITCH DIA.
(IN.)

BORE
(IN.)

PITCH DIA.
(IN.)

BORE
(IN.)

1LD0440

600 - 750

4.0 - 5.0

1 1/8

12.0

1LD0407

700 - 850

4.2 - 5.2

1 3/8

1LD0442

780 - 940

5.3 - 6.3

1LD0415

636 - 795

1LD0407

BELTS

QTY.

PITCH
LENGTH
(IN.)

DESIGNATION

1 3/16

63.3

A62

11.0

1 3/16

63.3

A62

1 3/8

12.0

1 3/16

63.3

A62

4.0 - 5.0

1 1/8

11.0

1 3/16

63.3

A62

668 - 827

4.2 - 5.2

1 3/8

11.0

1 3/16

63.3

A62

1LD0408

827 - 986

5.3 - 6.3

1 3/8

11.0

1 3/16

59.7

A59

1LD0409

607 - 776

4.3 - 5.5

1 3/8

12.4

1 3/16

85.1

B84

1LD0410

776 - 917

5.4 - 6.6

1 3/8

12.4

1 3/16

86.8

B85

1LD0411

692 - 833

4.8 - 6.0

1 3/8

12.4

1 3/16

78.6

B78

1LD0412

762 - 931

5.4 - 6.6

1 5/8

12.4

1 3/16

76.8

B75

TABLE 7:MOTOR OVERLOAD ELEMENTS1


MOTOR HP

VOLTAGE

MODEL NUMBER

208

2MP04704600

230

2MP04704600

460

2MP04704900

575

2MP04705000

208

2MP04703700

230

2MP04704500

460

2MP04704300

575

2MP04704000

208

2MP04701600

230

2MP04704100

460

2MP04704200

575

2MP04704300

208

2MP04704400

230

2MP04701700

460

2MP04704500

575

2MP04704600

Do not operate the supply air blower motor above


its nominal HP rating when a unit is equipped with
a hot water coil accessory. Do not use steam in hot
water coils.

7.5

10

Do not operate the supply air blower above its


nominal HP rating when a unit is equipped with a
steam coil accessory.
Although these coils are suitable for a much higher
pressure, steam above 25 psig provides too much
heat that could damage the blower motor.

15

1.

These units are equipped from the factory with a correctly sized motor starter;overload elements are not
factory supplied.

Note: Three elements required per unit.

Unitary Products Group

Page 190

http://www.rezine.net
036-21335-003-B-0206

TABLE 8:HOT WATER COIL CAPACITIES1


UNIT
MODEL

HOT WATER
COIL MODEL

ENTERING WATER TEMPERATURE MINUS ENTRY AIR TEMPERATURE F.


GPM

LA300

CFM
70

90

110

130

150

6,000

204

263

325

384

443

8,000

236

304

372

440

508

10,000

265

341

416

492

568

12,000

291

374

457

540

623

8,000

236

304

372

440

508

10,000

265

341

416

492

568

12,000

291

374

457

540

623

14,000

315

405

495

585

675

12,800

348

447

547

646

746

16,000

389

500

611

722

833

19,200

425

547

668

790

911

16,000

389

500

611

722

833

20,000

436

561

686

810

935

24,000

473

610

746

882

1,019

50

1HW0406

LB360

50

LB480

75
1HW0407

LB600

75

1.

These capacities do not include any blower motor heat.


NOTE: Temperature Water Drop ( F) = (2 X MBH) / GPM.

TABLE 9:HOT WATER COIL CAPACITY CORRECTION AND PRESSURE DROP VS GPM1
HOT WATER COIL MODEL

GPM

PRESSURE DROP
PSI

CAPACITY CORRECTION
FACTOR

25

0.4

0.79

50

1.0

1.00

75

1.8

1.04

100

3.4

1.07

50

1.0

0.95

75

1.5

1.00

100

2.4

1.03

125

3.5

1.05

1HW0406

1HW0407

1.

For pressure drop in feet (water), multiply these values by 2.31.

Unitary Products Group

Page 191

http://www.rezine.net
036-21335-003-B-0206

TABLE 10:STEAM COIL CAPACITIES1,MBH @ 2 PSIG2


UNIT
MODEL

STEAM COIL
MODEL

DRY BULB TEMPERATURE OF AIR ENTERING COIL ( F)


CFM
10

30

50

70

6,000

471

424

380

330

8,000

535

483

432

380

10,000

592

535

478

422

12,000

642

580

518

456

8,000

535

483

432

380

10,000

592

535

478

422

12,000

642

580

518

456

14,000

687

621

555

489

LA300

1NF0454

LB360

1.

These capacities do not include any blower motor heat.

2.

Multiply these capacities by the factors in Table 11 to correct for higher steam pressure.

TABLE 11:CORRECTION FACTORS FOR HIGH STEAM


STEAM PRESSURE (PSIG)

10

15

20

25

CAPACITY CORRECTION FACTOR

1.05

1.12

1.19

1.25

1.30

NOTE: Steam Rate = (lbs/Hr.) = 1.025 x MBH

10

Unitary Products Group

Page 192

http://www.rezine.net
036-21335-003-B-0206

7/8 KNOCKOUTS FOR POWER


AND CONTROL WIRING
AIR
OUT

AIR
OUT

5/8
5/8

L
K
J

LESS
BOTTOM
PANEL

C
BLOWER
SECTION

AIR
IN

AIR
IN

EVAPORATOR
SECTION
EVAPORATOR
COIL SECTION

5/8 PANEL

See detailed drawings for piping


and drain connections
on following pages.

D
5/8 BOTTOM
PANEL

FIGURE 5 -

UNIT DIMENSIONS - LA300,LB360 & LB480

TABLE 12:UNIT DIMENSIONS - LA300,LB360,LB480


MODEL

LA300

100-1/8

95-5/8

33-1/4

36-5/8

74

2-1/2

18-7/8

16-1/2

15-13/16

21-7/8

18

22-9/16

LB360

100-1/8

95-5/8

33-1/4

36-5/8

74

2-1/2

18-7/8

16-1/2

15-13/16

21-7/8

18

22-9/16

LB480

103-1/8

95-5/8

40-5/8

44

88-5/8

2-1/2

18-7/8

23-7/8

20-11/16

21-7/8

18

22-11/16

FIGURE 6 -

25 TON LIQUID LINE SOLENOID


WIRING

Unitary Products Group

FIGURE 7 -

30,40 & 50 TON LIQUID LINE


SOLENOID WIRING
11

Page 193

http://www.rezine.net
036-21335-003-B-0206

LIQUID
SYS. #1

LIQUID
LIQUID
SYS. #2

SUCTION

SYS. #1

SYS. # 2

SUCTION

FIGURE 10 - LB480 PIPING CONNECTIONS


FIGURE 8 -

LA300 PIPING CONNECTIONS


TABLE 13:UNIT CONNECTION SIZES
Connection Entry

Connection Size
LA300 LB360 LB480 LB600 + M2CX600

Suction Line Sys # 1

2 1/8

1-1/8

1-3/8

2-1/8

Suction Line Sys # 2

N/A

1-1/8

1-3/8

2-1/8

Liquid Line Sys # 1

7/8

7/8

7/8

7/8

Liquid Line Sys # 2

N/A

7/8

7/8

7/8

Power Wiring

7/8 (2) 7/8 (2) 7/8 (2)

1-3/8

Control Wiring

7/8 (2) 7/8 (2) 7/8 (2)

7/8 (2)

LIQUID (SYS. #1)

LIQUID (SYS. #2)

SUCTION
(SYS. #1)

SUCTION
(SYS. #2)

FIGURE 9 -

LB360 PIPING CONNECTIONS

12

Unitary Products Group

Page 194

http://www.rezine.net
036-21335-003-B-0206

FIGURE 11 - UNIT DIMENSIONS - LB600

4.7"

13.5"

Liquid
Line
Sys. #1
4.0"

10.1"
Liquid
Line
Sys. #2

3.8"
24.0"

Suction
Line
Sys. #2
3.0"
23.86"

2.1"

6.0"

Condensate
Drain

13.5"
Suction
Line
Sys. #1
3.0"

6.7"

FIGURE 12 - LB600 PIPING CONNECTIONS - END PANEL DETAIL


Unitary Products Group

13

Page 195

http://www.rezine.net
036-21335-003-B-0206

FIGURE 13 - HOT WATER COIL DIMENSIONS


TABLE 14:HOT WATER COIL DIMENSIONS
COIL
MODEL

UNIT
MODEL

DIMENSIONS
A

1HW0406

LA300
LB360

100-1/8

37-7/8

6-3/4

3-7/8

1-3/8

1-3/8

1HW0407

LB480
LB600

103-1/8

45-1/4

6-1/2

1-5/8

1-5/8

FIGURE 14 - STEAM COIL DIMENSIONS


TABLE 15:STEAM COIL DIMENSIONS1
COIL
MODEL

UNIT
MODEL

1NF0454

LA300
LB360

1.

DIMENSIONS
A

100-1/8

37-7/8

4-3/8

18-3/8

1-1/2

2-1/2

Coils are field-installed between the evaporator coil and the blower section of the unit.

TABLE 16:BASE SECTIONS DIMENSIONS1


BASE
MODEL

UNIT
MODEL

DIMENSIONS
A

1BS0406

LA300
LB360

100-1/8

37-7/8

1BS0407

LB480

103-1/8

45-1/4

1.

Ventilation air can be brought into the unit through the


base section providing the base section is fully insulated in the field.

FIGURE 15 - BASE SECTION DIMENSIONS


14

Unitary Products Group

Page 196

http://www.rezine.net
036-21335-003-B-0206

TABLE 17:PHYSICAL DATA


MODEL
DESCRIPTION
LA300

LB360

LB480

LB600

4 x 40

4 x 40

4 x 50

4 x 62

93

93

96

96

Face Area, Feet2

25.8

25.8

33.3

41.3

Tube (copper) OD, Inches

3/8

3/8

3/8

3/8

Fins (Aluminum) per 1 inch

16

16

16

16

7/8

7/8

7/8

7/8

2 1/8

1 1/8

1 3/8

2 1/8

Rows Deep X Rows High


Finned Length, Inches

EVAPORATOR
COIL

Piping Connections,
Inches
CENTRIFUGAL
BLOWERS (2 PER UNIT)

FILTERS (THROWAWAY)

Liquid, Inches
Suction, Inches

Diameter X Width, Inches (Forward Curved)

Size and Quantity Per


Model, Inches

18 x 18

16 x 20 x 2

20 x 20 x 2

20 x 22 x 2

16 x 25 x 2

20 x 25 x 2

10

25 x 25 x 2

34.7

42.6

53.1

Total Face Area / feet2


OPERATING CHARGE
(LBS R-22)

System 1

49.65

30.08

37.83

46.59

System 2

30.08

37.83

46.59

1/2

1/2

1/2

Rows Deep

Fins (Aluminum) per 1 inch

12

12

21.2

27.2

27.2

Tube (copper) OD, Inches

DRAINABLE HOT WATER


COIL ACCESSORY

Face Area, Feet2


Connections (Supply & Return), Inches
Tube (copper) OD, inches

NON-FREEZE,STEAM
DISTRIBUTING COIL
ACCESSORY

20 x 18

1 3/8 OD (Copper)
1 (Outside) 5/8 (Inside)

Rows Deep

Fins (Aluminum) per 1 inch

8
N/A

Face Area, feet2


Connection, (Brass)
Inches (NPTE)

1 5/8 OD (Copper)

18.2
Inlet
Outlet

Unitary Products Group

2
1-1/2

15

Page 197

http://www.rezine.net
036-21335-003-B-0206

TABLE 17:PHYSICAL DATA


MODEL
DESCRIPTION

COMPONENT WEIGHT

LA300

LB360

LB480

LB600

Basic Unit (Less Motor & Drive)

980

980

1260

1474

Shipping Weight (lbs)

1180

1180

1510

1572

Operating Weight (lbs)

1125

1146

1426

1640

Hot Water Coil

150

150

190

190

Steam Coil

160

160

117 (5hp)

117 (5hp)

120 (7.5hp)

120 (7.5hp)

120 (7.5hp)

141 (10hp)

141 (10hp)

141 (10hp)

217 (15hp)

Accessories

Blower Motor (1750 RPM)

16

Unitary Products Group

Page 198

http://www.rezine.net
036-21335-003-B-0206

TABLE 18:ELECTRICAL DATA


UNIT MODEL

HP

FLA

VOLTAGE
(3PH-60HZ)

MIN.CIRCUIT AMPACITY

MAX.FUSE SIZE
(Amps)

16.7

208

21

35

15.2

230

19

30

7.6

460

10

15

6.1

575

15

24.2

208

30

50

22

230

28

45

11

460

14

20

575

11

20

16.7

208

21

35

15.2

230

19

30

7.6

460

10

15

6.1

575

15

24.2

208

30

50

22

230

28

45

11

460

14

20

575

11

20

30.8

208

39

60

28

230

35

60

14

460

18

30

11

575

14

20

24.2

208

30

50

22

230

28

45

11

460

14

20

575

11

20

30.8

208

39

60

28

230

35

60

14

460

18

30

11

575

14

20

30.8

208

39

60

28

230

35

60

14

460

18

30

11

575

14

20

46.2

208

58

100

42

230

53

90

21

460

26

45

17

575

21

35

LA300

7.5

5.0

LB360

7.5

10

7.5

LB480

10

10

LB600

15

Unitary Products Group

17

Page 199

http://www.rezine.net
036-21335-003-B-0206

TABLE 19:FAN PERFORMANCE DATA - 25 TON1


CFM
8,000

RPM

9,000

10,000

11,000

12,000

SP2

BHP3

KW

SP2

BHP3

KW

SP2

BHP3

KW

SP2

BHP3

KW

SP2

BHP3

KW

600

0.30

2.5

2.3

0.20

3.1

2.9

0.02

3.6

3.4

635

0.56

2.4

2.3

0.43

2.7

2.6

0.31

3.3

3.1

0.13

3.8

3.5

700

0.80

3.0

2.8

0.68

3.3

3.1

0.54

3.7

3.5

0.38

4.2

3.9

0.20

4.8

4.5

775

1.12

3.7

3.4

1.00

4.0

3.7

0.85

4.4

4.1

0.70

4.8

4.5

0.54

5.3

5.0

800

1.23

3.9

3.7

1.11

4.3

4.0

0.97

4.7

4.4

0.82

5.1

4.8

0.66

5.6

5.2

875

1.60

4.8

4.5

1.48

5.1

4.8

1.34

5.6

5.2

1.19

6.0

5.7

1.04

6.6

6.2

900

1.73

5.1

4.8

1.61

5.5

5.1

1.47

5.9

5.5

1.33

6.4

6.0

1.17

7.0

6.5

940

1.95

5.6

5.2

1.82

6.0

5.6

1.70

6.5

6.1

1.

Unit resistance is based on a dry evaporator coil and clean filters.

2.

Available static pressure in IWG to overcome the resistance of the duct system and any accessories added to the unit. Refer to
the blower motor and drive table and the accessory static resistance table for additional information.

3.

Motors can be selected to operate into the service factor because they are located in the moving air stream, upstream of any heating device. units with steam or hot water coils are the only exception. On these units, the BHP must not exceed the nominal HP
rating of the motor.

TABLE 20:FAN PERFORMANCE DATA - 30 TON1


CFM
10,000

RPM

11,000

12,000

13,000

14,000

SP2

BHP3

KW

SP2

BHP3

KW

SP2

BHP3

KW

SP2

BHP3

KW

SP2

BHP3

KW

600

0.20

3.1

2.9

0.02

3.6

3.4

635

0.31

3.3

3.1

0.13

3.8

3.5

700

0.54

3.7

3.5

0.38

4.2

3.9

0.20

4.8

4.5

0.03

5.3

5.0

775

0.85

4.4

4.1

0.70

4.8

4.5

0.54

5.3

5.0

0.39

5.8

5.5

0.20

6.4

6.0

800

0.97

4.7

4.4

0.82

5.1

4.8

0.66

5.6

5.2

0.52

6.1

5.7

0.35

6.7

6.3

875

1.34

5.6

5.2

1.19

6.0

5.7

1.04

6.6

6.2

0.93

7.1

6.6

0.77

7.7

7.2

900

1.47

5.9

5.5

1.33

6.4

6.0

1.17

7.0

6.5

1.07

7.5

7.0

0.90

8.2

7.6

940

1.70

6.5

6.1

1.55

7.0

6.6

1.40

7.7

7.2

1.31

8.3

7.8

1.09

9.0

8.4

1.

Unit resistance is based on a dry evaporator coil and clean filters.

2.

Available static pressure in IWG to overcome the resistance of the duct system and any accessories added to the unit. Refer to
the blower motor and drive table and the accessory static resistance table for additional information.

3.

Motors can be selected to operate into the service factor because they are located in the moving air stream, upstream of any heating device. units with steam or hot water coils are the only exception. On these units, the BHP must not exceed the nominal HP
rating of the motor.

18

Unitary Products Group

Page 200

http://www.rezine.net
036-21335-003-B-0206

LA300 & LB360


3.2
10
00

3.0

RP
M

2.8
10

90
0R
PM

2.4

8
P
BH

2.2
2.0

80
0R
PM

700

1.4

P
BH

P
BH

1.2

RPM

P
BH

P
BH

1.6

1.8

600 RPM

1.0

2
P
BH

TOTAL STATIC PRESSURE, IWG

P
BH

2.6

0.8

500 RPM

0.6
0.4
0.2
0
0

10

20

30

40

50

60 70

80

90 100 110 120 130 140 150 160 170 180 190 200 210 220 230
CFM (X 100)

Available external static pressure for unit accessories and


the duct system.

Internal unit resistance based


on a dry coil plus 2"
throwaway filters.

FIGURE 16 - BLOWER CURVE LA300 & LB360

Unitary Products Group

19

Page 201

http://www.rezine.net
036-21335-003-B-0206

TABLE 21:FAN PERFORMANCE DATA - 40 TON1


CFM
12,800

RPM

14,400

16,000

17,600

19,200

SP2

BHP

KW

SP2

BHP

KW

SP2

BHP

KW

SP2

BHP

KW

SP2

BHP

KW

600

0.20

4.3

3.7

640

0.38

4.8

4.1

0.19

5.6

4.8

700

0.65

5.5

4.7

0.47

6.4

5.5

0.28

7.2

6.2

775

0.99

6.5

5.6

0.84

7.4

6.4

0.66

8.4

7.2

0.46

9.4

8.1

0.23

10.4

9.0

800

1.11

6.8

5.9

0.96

7.8

6.7

0.79

8.8

7.6

0.59

9.8

8.4

0.36

10.8

9.3

900

1.65

8.1

7.0

1.52

9.3

8.0

1.36

10.5

9.0

915

1.73

8.3

7.2

1.60

9.5

8.2

1.44

10.7

9.2

1.

Unit resistance is based on a dry evaporator coil and clean filters.

2.

Available static pressure in IWG to overcome the resistance of the duct system and any accessories added to the unit. Refer to
the blower motor and drive table and the accessory static resistance table for additional information.

TABLE 22:FAN PERFORMANCE DATA - 50 TON1


CFM
16,000

RPM

18,000

20,000

22,000

24,000

SP2

BHP

KW

SP2

BHP

KW

SP2

BHP

KW

SP2

BHP

KW

SP2

BHP

KW

600

0.82

6.0

5.2

0.59

7.2

6.2

0.35

8.4

7.2

0.08

9.7

8.4

660

1.17

7.3

6.3

0.96

8.5

7.3

0.73

9.8

8.5

0.45

11.2

9.7

0.14

12.7

11.0

700

1.40

8.2

7.1

1.21

9.4

8.1

0.98

10.7

9.2

0.70

12.2

10.5

0.40

13.7

11.8

760

1.76

9.5

8.2

1.59

10.8

9.3

1.38

12.3

10.6

1.11

13.8

11.9

0.81

15.6

13.5

800

2.00

10.4

9.0

1.85

11.8

10.2

1.64

13.3

11.5

1.38

14.9

12.9

1.09

16.9

14.6

900

2.60

12.8

11.0

2.49

14.5

12.5

2.35

16.0

13.8

930

2.78

13.5

11.6

2.68

15.3

13.2

1.

Unit resistance is based on a dry evaporator coil and clean filters.

2.

Available static pressure in IWG to overcome the resistance of the duct system and any accessories added to the unit. Refer to
the blower motor and drive table and the accessory static resistance table for additional information.

20

Unitary Products Group

Page 202

http://www.rezine.net
036-21335-003-B-0206

LB480
3.2

15

100

P
BH

3.0

0R

2.8

PM
HP
2B
-1/

12

2.6

900

RPM

10

P
BH

2.2

BH
P

2.0
1.8

PM

800 R

BH

1.6

BH

TOTAL STATIC PRESSURE, IWG

2.4

1.4

700 RPM

1.2
600 RPM

1.0
0.8

500 RPM
0.6
0.4
0.2
0
0

10

20

30

40

50

60

70

80

90

100

110

120

130

140

150

160

170

180

190 200

CFM (X 100)
Internal unit resistance based
on a dry coil plus 2"
throwaway filters.

Available external static pressure for unit accessories and


the duct system.

FIGURE 17 - BLOWER CURVE LB480

Unitary Products Group

21

Page 203

http://www.rezine.net
036-21335-003-B-0206

LB600
3.2

90

RP

3.0
2.8
2.6
80

0R

PM

BH
P

HP

1.6
1.4

HP

RPM

10

1.8

700

BH

P
BH

2.0

16 B

14

12

2.2

8B

600 RPM

1.2
HP

6B

TOTAL STATIC PRESSURE, IWG

2.4

PM

1.0

500 R

0.8
0.6
0.4
0.2
0
0

20

40

60

80

100

120

140

160

180

200

220

240

260

280

300

320

340

360

CFM (X 100)
AvaIlable external static pressure for unit accessories and
the duct system.

Internal unit resistance based


on a dry coil plus 1"
throwaway filters.

FIGURE 18 - BLOWER CURVE LB600

22

Unitary Products Group

Page 204

http://www.rezine.net
036-21335-003-B-0206

GUIDE SPECIFICATIONS
EACH UNIT SHALL BE:

THE DIMENSIONS OF EACH UNIT SHALL NOT


EXCEED THOSE SPECIFIED.

Covered by a 1-year limited parts warranty on the complete unit.


In current production with published literature available
to check performance, limitations, specifications, power
requirements, dimensions, operation and appearance;
also equipped with a V-belt drive option that:
a.

Will permit the blower RPM to be adjusted to meet


the exact CFM requirement of the system.

THE BLOWER MOTOR SHALL:


Be mounted within the insulated cabinet to minimize the
transmission of sound to the surrounding space, and
Have a service factor of 1.15.

THE EVAPORATOR COIL SHALL:


Consist of copper tubes arranged in staggered rows,
mechanically expanded into aluminum fins,

EACH UNIT ENCLOSURE SHALL HAVE:


A steel angle frame to provide the rigid support required
for shipping, rigging and years of dependable operation.
Exterior panels of 18 gauge steel, finished with baked
enamel to provide a long lasting quality appearance
Removable panels to provide easy access to the internal
components for maintenance and service, and,

Be draw-through, and
Include factory-mounted distributors, expansion valves
and solenoid valves for both capacity reduction and
pumpdown.

THE BLOWER WHEELS SHALL:


Be dynamically balanced to minimize the levels of sound
and vibration generated by the unit.

A filter rack with 2 filters.

Unitary Products Group

23

Page 205

http://www.rezine.net

Page 206

http://www.rezine.net

Page 207

http://www.rezine.net

Controls
HVAC control just became a
whole lot smarter and easier!

Only York offers the easiest


solution to help you
take control of controls.

C
O
N
T
R
O
L

COMFORT
ONLINE ALARMING
NO HASSLE SET-UP

TOTAL HVAC
CONTROL SOLUTIONS

More control for more savings

More compatibility for more flexibility

Cut energy costs, and achieve higher levels of comfort


automatically with Simplicity Intelli-Comfort controls.

The controls are compatible with the MODBUS protocol,


and are factory-installed on 3- to 25-ton Sunline and
Predator products and Millennium HA/HB Systems.

More intelligence for more capabilities


Intelli-Comfort controls use intelligent hardware and
software to give you better monitoring, more flexibility in
control set-up, and finer control of every aspect of your
HVAC system. In addition, the more intelligent the control,
the greater savings you will realize through operational
efficiencies and conservation.

More power with less effort


Intelli-Comfort is a control thats so easy to use that
you actually benefit from the power at your fingertips.

Easier to manage
Intelli-Comfort raises the intelligence of an already
smart Simplicity control.

More control for greater comfort


The flexibility of the Simplicity Intelli-Comfort control
means comfortable, happier, and more productive
occupantsthanks to the ability to optimize temperature,
humidity, and indoor air quality simultaneously.

Put the intelligence of Simplicity Intelli-Comfort controls


to work in your building.
Simplicity Intelli-Comfort controls give you powerful capabilities without complexity. Easy to set-up, program, and use, the controls give you
everything you need to monitor and control Sunline and Predator units. And because they can be connected as your HVAC Energy
Management System you can save even more by making the intelligence of Simplicity Intelli-Comfort part of your building automation strategy.

RELIABILITY
OPEN PROTOCOL
LOW COST

New features for superior


monitoring and control
365-Day Real Time Clock with
automatic Daylight Savings Time adjustment
Occupancy Schedule allowing two different occupied
schedules per day for each of the seven days of the week
20 Holiday Schedules with a length of up to 99 days, each
with flexible start times. You can now choose the time of day
your holiday begins saving energy

Patent Pending Temperature Humidity Algorithm offsets


the operating setpoint based on high humidity in the spacewith
programmable limits to control humidity

Energy-Saving Economizer Operation with the flexibility


of using dry bulb, outside enthalpy and differential enthalpy.
Our economizer enthalpy control has setpoints for outside air
temperature, supply air temperature, small space cooling demand,
and large space cooling demand

High and Low Ambient Lockout to lockout cooling below or


heating above a programmable setpoint of outside air temperature

Outside Air CO2 Sensor to close the economizer if CO2 is present


Inside Demand Ventilation using one CO2 sensor or differential
demand ventilation using inside and outside CO2 sensors
IAQ Operation with programmable maximum outside air
damper position

Space Temperature Alarm when temperatures are outside


of program setpoints. Alarm setpoints are user programmable
Unit Monitors Airflow to detect dirty filters and insufficient airflow
Intelligent Recovery brings the space temperature to the
occupied setpoint just before or at the beginning of the first
occupied schedule each day. The control will learn and apply
the minimum runtime required to heat or cool the space to
minimize energy use

Comfort Ventilation Control tempers the ventilation air


when heating or cooling is not required, increasing comfort

2004 York International Corporation.


All rights reserved. Subject to change without notice.
Form 036-12054-001 (0105). Supersedes: Nothing. Printed in USA.

Page 208

http://www.rezine.net

Page 209

http://www.rezine.net

COMMERCIAL ZONING PACKAGE

The Facility Explorer Commercial Zoning Package is a complete, turnkey control system used to improve
occupant comfort in a building (or section of a building) that is conditioned with a packaged rooftop HVAC unit.
It accomplishes this by varying the amount of conditioned air delivered to individual zones and by intelligently
cycling the rooftop units heating and cooling stages to best satisfy all the zone demands.

Manufacturer Independent
The Facility Explorer Commercial Zoning
Package is designed to work with any
standard, packaged HVAC equipment, regardless
of manufacturer. This allows you to apply this control
package to equipment provided by a variety of
suppliers or to equipment that has already been
installed. This flexibility makes the Facility Explorer
Commercial Zoning Package perfectly suited for both
new and retrofit installations.
Affordable Intelligence
The Facility Explorer Commercial Zoning Package
utilizes the distributed application architecture of
the FX16 Master Controller. This feature allows direct
communications to occur between the FX16 and all
the zone controllers. This means that there is no
need for a traditional supervisory class controller to
manage the data sharing. This direct communication
flow allows the FX16 to monitor each zones status to
intelligently determine the proper mode of operation
for the rooftop unit.

Page 210

http://www.rezine.net

COMMERCIAL ZONING PACKAGE

Easy Installation
Several pieces of the Facility Explorer Commercial
Zoning Package can be ordered pre-assembled from
the factory to simplify installation:

Bypass Damper and Actuator Assembly

Zone Controller and Actuator Assembly (FXZAN)

FX16 Master Controller with Pre-Downloaded


Zoning Application

The FX05 Field Controller is combined with an


M9104AGA non-spring return actuator and an
electrical termination wiring block, all in one
packaged assembly

FX16 Master Controller can be ordered with the


commercial zoning application pre-downloaded

Perfect for retrofit installations where the zone


damper is already installed
Zone Controller, Actuator, and Damper Assembly
FXZAN Zone Controller and Actuator Assembly is
combined with a round or rectangular zone damper
Perfect for new installations or for retrofit
installations where the zone damper has not yet
been installed

2005 Johnson Controls, Inc.

A round or rectangular bypass damper is combined


with an M910xHGA non-spring return actuator

Once installed, the FX16 takes care of downloading


the corresponding parts of the zoning application to
each of the zone controllers
Eliminates the downloading steps from the field
installation and startup
This provides the possibility (with an onsite Medium
User Interface) to download, configure and
commission the entire system, including the
rooftop, bypass, and all zone controllers without
any software tool

P.O. Box 423, Milwaukee, WI 53201

Page 211

Printed in USA PUBL-3894

http://www.rezine.net

Page 212

http://www.rezine.net

TSS Single Duct Variable Air Volume Terminal

An integrated VAV box with direct digital controls

TSS Terminals provide Variable Air Volume (VAV) control

eliminates the coordination and difficulties

beyond the typical single duct box. They are specifically

associated with factory mounting

designed for precise air delivery throughout the entire


operating range, regardless of the installed inlet conditions.

Downloading of software, setting of parameters,

These units can be ordered with or without a Direct Digital

addressing and testing at the factory reduces

Controller (DDC), which can operate as a stand-alone unit,

startup time and lowers risk

on a Johnson Controls N2 trunk, or on a LON trunk.

Superior flow measuring provides for lower

TSS Terminals take advantage of typical benefits provided

minimum cubic feet per minute (CFM) values,

by single duct units, while performing at extremely low

which reduces energy costs and noise while

sound levels. This is critical in todays buildings where

maintaining comforts in the zone

occupants are placing more emphasis on indoor acoustics.


The TSS Terminal is manufactured and assembled with a

Installation time can be reduced with the low

multi-point, center-averaging airflow sensor, which

profile compact design and standard metal

provides a signal to the controller enabling it to quietly and

hanging straps

precisely measure airflow.

Units wired in compliance with all applicable

Bundled with the TSS Terminal is a digital controller from

National Electrical Code (NEC) requirements and

the VAV Modular Assembly (VMA) Series or the LN Series.

tested in accordance with Air Conditioning and

Each model in the VMA1400 Series and the LN Series

Refrigeration Institute (ARI) standard 880

combines a controller, pressure sensor, and actuator


housed in one pre-assembled unit.

Offers damper stall detection, starved box


detection, actuator motor duty cycle, VAV box
flow test, and other diagnostics on most
models (VMA Series)

Page 213

http://www.rezine.net

TSS Single Duct Variable Air Volume Terminal

Standard Features

Optional Features

Construction

Construction

ARI 880 certified and labeled

20-gauge galvanized steel construction

22-gauge galvanized steel casing and valve

3/4 or 1 fiberglass insulation

G90 galvanized steel

Scrim-reinforced, foil-faced insulation meeting American


Society for Testing and Materials (ASTM) C1136 for mold,
mildew, and humidity resistance

1/2, 4lb/ft3 skin, dual density fiberglass insulation, glued


and clinch-pinned in place

1/2 Elastomeric closed-cell foam insulation

Hot Water Coils

Double wall construction with 22-gauge liner

ARI 410 certified and labeled

Mounting brackets to accept all-thread hanging rods or


wire hangers

1-, 2-, 3-, 4-row coils


Tested at a minimum of 350 psig under water

Low temperature construction for use in thermal storage


applications, including a thermally isolated primary air
inlet and a composite damper shaft

Mechanically expanded copper tubes leak tested


to 350 psig air pressure
Male sweat type water connections

Hot Water Coils


Low pressure steam coils

Primary Air Valve


Embossed rigidity rings

Multi-circuit coils for reduced water pressure drop

Low-thermal conducting damper shaft with


position indicator

Opposite hand water connections


Bottom and top access plates for cleaning

Mechanical stops for open and closed position

Electrical Components

Multi-point center-averaging airflow sensor

Full unit toggle disconnect and inline motor fusing

Brass balancing tees

Primary and secondary transformer fusing

Plenum-rated sensor tubing

Electric Heat

Electrical Components

Proportional solid state relay (SSR) heater control

cETL listed for safety compliance

Mercury contactors

National Electrical Manufacturers Association (NEMA)


Type 1 wiring enclosure

Door interlocking disconnect switches


Disconnect (toggle or door interlocking)

Electric Heat
ETL listed as an assembly for safety compliance
Integral electric heat assembly
Automatic reset primary and back-up secondary
thermal limits

Pneumatic Electric (PE) switches


Mercury and magnetic contactors
Manual reset secondary limit
24 volt control transformer

Single-point power connection

Special watt densities

Hinged electrical enclosure

Finned tubular elements

Fusing per NEC

Controls

Airflow switch

Factory-provided controls

Ni-chrome elements

Direct digital controls (DDC) for N2 or LON networks

Primary/Secondary power terminations

Pneumatic controls

Wiring diagram

2005 Johnson Controls, Inc.

P.O. Box 423, Milwaukee, WI 53201


www.johnsoncontrols.com

Page 214

Printed in USA PUBL-3888

http://www.rezine.net

TSL Single Duct Low Height Variable Air Volume Terminal

An integrated VAV box with direct digital controls

TSL Terminals provide variable air volume (VAV) control

eliminates the coordination and difficulties

beyond the typical single duct box. They are specifically

associated with factory mounting

designed for precise air delivery throughout the entire


operating range and are only 10 in height, making them

Downloading of software, setting of parameters,

ideal for shallow or congested ceiling plenum applications.

addressing and testing at the factory reduces

These units can be ordered with or without a Direct Digital

startup time and lowers risk

Controller (DDC), which can operate as a stand-alone unit,


on a Johnson Controls N2 trunk, or on a LON trunk.

Superior flow measuring provides for lower


minimum cubic feet per minute (CFM) values,

TSL Terminals take advantage of typical benefits provided

which reduces energy costs and noise while

by single duct units, while performing at extremely low

maintaining comforts in the zone

sound levels. This is critical in todays buildings where


occupants are placing more emphasis on indoor acoustics.

Installation time can be reduced with the low

The TSS Terminal is manufactured and assembled with

profile compact design and standard metal

a multi-point, center-averaging airflow sensor, which

hanging straps

provides a signal to the controller enabling it to quietly and


precisely measure airflow.

Units wired in compliance with all applicable


National Electrical Code (NEC) requirements and

Bundled with the TSL Terminal is a digital controller from

tested in accordance with Air Conditioning and

the VAV Modular Assembly (VMA) Series or the LN Series.

Refrigeration Institute (ARI) standard 880

Each model in the VMA1400 Series and the LN Series


combines a controller, pressure sensor, and actuator
housed in one pre-assembled unit.

Page 215

TSL Single Duct Low Height Variable Air Volume Terminal

http://www.rezine.net

Secondary high limit

Standard Features

Airflow switch

Construction
ARI 880 certified and labeled

Single-point power connection

20-gauge, galvanized steel casing and valve

Hinged electrical enclosure door

G90 galvanized steel construction

Fusing per NEC

1/2", 4 lb/ft3 skin, dual density fiberglass insulation glued


and clinch pinned

Optional Features

Invertible unit facilitates control installation on the left- or


right-hand side

Construction

Hot Water Coils


ARI 410 certified and labeled

Scrim-reinforced, foil-faced insulation meeting American


Society for Testing and Materials (ASTM) C1136 for mold,
mildew, and humidity resistance

1-, 2-, 3-, 4-row coils

1/2 Elastomeric closed-cell foam insulation

Left- or right-hand connections

Double wall construction with a 22-gauge liner

Tested at a minimum of 450 psig under water and rated


at 300 psig working pressure at 200F

Mounting brackets to accept all thread hanging rods or


wire hangers

Aluminum fin construction with die-formed spacer collars


for uniform spacing

Discharge sound attenuator (Model TSL-SA)

Mechanically expanded copper tubes leak tested to 450


psig air pressure and rated at 300 psig working pressure
at 200F

Coil access plate for cleaning coil

Hot Water Coil


Coil circuiting options for reduced water pressure drop
Right- or left-hand water connections

Male sweat type water connections

Bottom and top access plates for cleaning

Primary Air Valve


18-gauge, G90 galvanized steel construction

Steam coils

Low thermal conductance damper shaft

Electrical Components

Position indicator on external end of damper shaft

Toggle disconnect switch

Mechanical stops for open and closed position

Primary and secondary transformer fusing

Multi-point center-averaging airflow sensor

Electric Heat

Brass balancing tees

Proportional solid state relay (SSR) heater control

Plenum-rated sensor tubing

Mercury contactors (if equipped with a mercury contactor,


the unit cannot be inverted)

Electrical Components

Door interlocking disconnect switches

cETL listed for safety compliance with Underwriters


Laboratories Inc. (UL) 1995

Disconnect (toggle or door interlocking)

National Electrical Manufacturers Association (NEMA)


Type 1 wiring enclosure

Pneumatic Electric (PE) switches

Electric Heat

Manual reset secondary limit

Invertible unit facilitates control installation on the left- or


right-hand side (not applicable if equipped with a
mercury contactor)

Controls

cETL listed as an assembly for safety compliance

Direct Digital Controls (DDC), for N2 or LON networks

Automatic reset primary and back-up secondary


thermal limits

Pneumatic controls

Mercury and magnetic contactors

Factory-provided controls

Primary auto-reset high limit

2005 Johnson Controls, Inc.

P.O. Box 423, Milwaukee, WI 53201


www.johnsoncontrols.com

Page 216

Printed in USA PUBL-3882

http://www.rezine.net

Single Duct Variable Air Volume Terminal (Model TSS)


Unit
Size
6
8
10
12
14
16
22

CFM
200
400
600
800
1100
1500
3000

Bypass
CFM
300
600
900
1200
1800
2200
5400

Dimensions
Weight
18
20
25
30
38
42
72

WxHxL
10 x 10" x 11"
12 x 10 x 11"
14 x 12.5" x 13
16 x 15" x 13
20 x 17.5" x 17.5"
24 x 17.5" x 17.5"
34 x 17.5" x 11"

A
6 1/2
6 1/2
6 1/2
6 1/2
6 1/2
6 1/2
8

I
5 7/8
7 7/8
9 7/8
11 7/8
13 7/8
15 7/8
32 1/4 x 15 7/8

X
8 3/4
10 3/4
12 3/4
14 3/4
18 3/4
22 3/4
32 3/4

Y
8 3/4
8 3/4
11 1/4
13 3/4
16 1/4
16 1/4
16 1/4

Note: All dimensions are in inches with a tolerance of +1/8. Size 22 has a rectangular inlet collar. CFM based on
1000 FPM (Bypass 1500 FPM) for low to medium pressure applications.

Clearance 24"

Page 217

http://www.rezine.net

Single Duct Variable Air Volume Terminal - Rectangular (Model TSL)

Dimensions
Unit
Bypass
Size
CFM
CFM
A
W
L
X
Weight
10
600
1200
10
15
12 1/2
13 3/4
26
12
800
1600
14
19
12 1/2
17 3/4
28
14
1200
2200
20
25
16 1/2
23 3/4
39
16
1500
3000
26
31
16 1/2
29 3/4
45
Notes: 1. For dimensional data for unit sizes 6 and 8, refer to the Single Duct Variable
Air Volume Terminal (Model TSS). All dimensions are in inches with a tolerance of +1/8.
Weights are in pounds. Weights are for the basic unit with the indicated option and
control enclosure. Actual weight varies based on project-specific requirements for unit
options, appurtenances, and controls. 2. Control enclosure is standard with factorymounted electronic controls. 3. Check all national and local codes for required
clearances.

Page 218

http://www.rezine.net

Page 219

http://www.rezine.net

Model DE Series
UVC Emitters

UVC for HVAC

TM

power needed to maintain microbial control. The UVC


Emitter, by contrast, has a 12-month service life and even
after a full year, it has 2-1/2 times greater output than
competitive devices deliver on Day 1! As a result, only SterilAire can ensure the germicidal performance you need, with no
return of microbial growth, for 3-4 times longer than the
competition.

Double-Ended, Very High


Output Germicidal Light
Source for HVAC Systems

Applications
Steril-Aire Double-Ended (DE Series) fixtures are used
for internal installation in medium to large air handling
systems in commercial, industrial, health care and institutional
buildings. They may be mounted singly, in built-up banks or in
parallel configurations in a variety of locations, including
coils, drain pans, ductwork, mixed air plenums and exhaust
systems. The DE Series is available in five lengths (18, 24,
30, 36 and 42) and four voltage options (115, 208, 230 or
277 Vac), providing installation flexibility to accommodate
virtually any system.

Benefits
Kills or inactivates surface and airborne microorganisms that
contribute to poor IAQ and/or the spread of infectious disease,
including: mold and mold spores, bacteria (including TB,
Legionella, E. coli, Listeria, salmonella, and whooping
cough); and viruses (including colds, flu, measles).
Delivers an average of 5 times the output of competitive UVC
products at HVAC operating temperatures, for 3-4 times
longer life and more reliable germicidal control.
Uses patented state-of-the-art solid-state electronic power
supply for enhanced reliability and performance.
Continuously cleans coils, drain pans, plenums and ducts,
eliminating costly cleaning programs and the use of harmful
chemicals and disinfectants.
Lowers HVAC energy costs by restoring heat transfer and net
cooling capacity.
Steril-Aires multi-patented UVC Emitter provides the
best and longest-lasting UVC performance available. As
shown in the comparison graph (above), it has been
independently tested to deliver an average of 5 times the
output of other ultraviolet devices under HVAC operating
conditions (45o F @ 550 fpm air velocity).
Competitive UVC lights must be changed every 3-4
months because they quickly lose the output or killing

Produces no ozone or other secondary contaminants will not


harm building occupants, equipment or furnishings.
Offers lowest life-cycle cost of any UVC product. Return on
investment is often less than one year.
The most widely used product for commercial UVC for
HVAC the industry standard!

Page 220

http://www.rezine.net

Model DE Specifications
The UVC EmitterTM and fixture shall be factory assembled and
tested. They shall consist of a housing, power source, reflector,
Emitter sockets and Emitter.

be available in 115-208/230 or 277 Vac, 50/60 Hertz, and single phase.


The Emitter soc kets are medium bi-pin, double click safety, twist
lock type. They shall be constructed of UVC-resistant polycarbonate.

The housing shall be constructed of 304 stainless steel to withstand


HVAC environments. The reflector shall be constructed of heavy
gauge, specular finished aluminum alloy with approximately 85%
reflectance at 254 nm wavelength. The housing shall be equipped
with 1/2" electrical conduit openings on each end to facilitate
coupling and wiring fixture-to-fixture and to power. All components
shall be in one integral assembly to maximize serviceability.
The power source shall be a Class P2, electronic, rapid start type
with a power factor greater than 0.95 and a power conversion of
greater than 75%. The power supply design shall include RF and EMI
suppression. The power supply shall be designed to maximize photon
production, irradiance and reliability in cold or moving airstreams of
35-170 F, 100% RH and up to 2000 fpm velocity. The fixture shall

The Emitter tube shall be a very high output, hot cathode, T5


diameter, medium bi-pin type that produces broadband UVC of 250260 nm. Each tube shall produce the specified output at 2000 fpm
velocity and air temperatures of 35-170 F. It shall produce no ozone
or other secondary contaminants.
Inde pendent testing: The unit shall be tested by an independent test
laboratory in accordance with the general provisions of IES Lighting
Handbook, 1981 Applications Volume, and shall be verified through
independent testing to provide output per 1" arc length of not less
than 10 W/cm2 at 1 meter in a 400 fpm airstream of 45 F.
Unit shall comply with UL Standard 1995 for use in HVAC
equipment and shall carry the "UL" and "ULC" labels.

This product may be covered by one or more of the following patents, others pending: 5,334,347/ 5,866,076/ 5,817,276/ 6,372,186/ 6,313,470/ 6,245,293/
6,267,924/ 6,280,686/ 6,423,882.

Ordering Information
Model No.

Part No.

Description

Length

DE 181 VO
DE 181 VO
DE 241 VO
DE 241 VO
DE 301 VO
DE 301 VO
DE 361 VO
DE 361 VO
DE 421 VO
DE 421 VO
GTD 16 VO
GTD 22 VO
GTD 28 VO
GTD 34 VO
GTD 40 VO

10001500
10002100
10001600
10002200
10001700
10002300
10001800
10002400
10001300
10002500
20000100
20000200
20000300
20000400
20000500

Double-Ended Fixture
Double-Ended Fixture
Double-Ended Fixture
Double-Ended Fixture
Double-Ended Fixture
Double-Ended Fixture
Double-Ended Fixture
Double-Ended Fixture
Double-Ended Fixture
Double-Ended Fixture
Replacement Emitter DE 181
Replacement Emitter DE 241
Replacement Emitter DE 301
Replacement Emitter DE 361
Replacement Emitter DE 421

18"
18"
24"
24"
30"
30"
36"
36"
42"
42"
16"
22"
28"
34"
40"

Electrical
115, 208, 230V: 70-85 watts
277V: 70-85 watts
115, 208, 230V: 70-85 watts
277V: 70-85 watts
115, 208, 230V: 70-85 watts
277V: 70-85 watts
115, 208, 230V: 70-85 watts
277V: 70-85 watts
115, 208, 230V: 70-85 watts
277V: 70-85 watts
N/A
N/A
N/A
N/A
N/A

Weight
2.3 lb.
2.3 lb.
2.7 lb.
2.7 lb.
3.3 lb.
3.3 lb.
3.7 lb.
3.7 lb.
4.1 lb.
4.1 lb.
0.15 lb.
0.15 lb.
0.20 lb.
0.25 lb.
0.25 lb.

Complies with current U.S. and Canadian UL Standards for


use in HVAC equipment.

Represented By:

Steril-Aire, Inc.
Corporate Office:
2840 N. Lima Street
Burbank, CA 91504
Telephone: 818-565-1128
Fax: 818-565-1129
Website: www.steril-aire.com
Email: sales@steril-aire.com
2003 Steril-Aire

1100-07/05

Page 221

http://www.rezine.net

Page 222