PROJECT : PAGE :

CLIENT : DESIGN BY :
JOB NO. : DATE : REVIEW BY :
INPUT DATA
Exposure category (B, C or D, ASCE 7-10 26.7.3) C
Importance factor (ASCE 7-10 Table 1.5-2)
I
w
= 1.00 for all Category
V = 136 mph
K
zt
= 1 Flat
Building height (IBC/CBC, 1609.6.1.1) h = 75 ft
Building length L = 100 ft
Building width (IBC/CBC, 1609.6.1.1) B = 50 ft
A = 28 ft
2
DESIGN SUMMARY
Max building horizontal force normal to building length, L, face = 373.7 kips
Max overturning moment at wind normal to building length, L, face = 19211.5 ft - kips
Max building horizontal force normal to building length, B, face = 155.5 kips
Max overturning moment at wind normal to building length, B, face = 13800.2 ft - kips
Max building upward force = 277.5 kips
Max building torsion force = 4203.9 ft - kips
ANALYSIS
Velocity pressure
q
s
= 0.00256 V
2
= 47.35 psf
where: q
s
= wind velocity pressure at atandard height of 33 feet (ASCE 7-10 26.5.1, IBC/CBC Figure 1609)
Design pressures for MWFRS
P
net
= q
s
K
z
C
net
[ I K
zt
] (IBC/CBC, Equation 16-35)
where: P = pressure in appropriate zone. P
min
= 16 psf (ASCE 7-10 28.4.4)
K
z
= velocity pressure exposure coefficient evaluated at height, h, (Tab. 28.3-1 & Tab. 27.3-1) = 1.19
C
net
= K
d
[(G C
pf
)-(G C
pi
)] , (IBC/CBC, 1609.6.2 / Table 1609.6.2. The equation used on following calcs.)
K
d
= wind directionality factor. (Tab. 26.6-1, for building, page 250) = 0.85
G C
p f
= product of gust effect factor and external pressure coefficient, see table below. (Fig. 28.4-1, page 300 & 301)
G C
p i
= product of gust effect factor and internal pressure coefficient.(Tab. 26.11-1, Enclosed Building, page 258)
= 0.18 or -0.18
Surface z (ft) GC
Pi
- GC
Pi
Surface z (ft) GC
Pi
- GC
Pi
0 - 15 15.28 32.52 Side Wall All -37.90 -20.66
20 16.69 33.93
25 17.81 35.05
30 18.94 36.18
40 20.62 37.87 Surface z (ft) GC
Pi
- GC
Pi
Surface z (ft) GC
Pi
- GC
Pi
50 22.03 39.27 Leeward All -29.54 -12.29 Leeward All -21.17 -3.93
60 23.16 40.40
70 24.28 41.52
75 24.84 42.09
Surface Dist. (ft) GC
Pi
- GC
Pi
Surface Dist. (ft) GC
Pi
- GC
Pi
0 - 37.5 -52.12 -34.88 0 - 37.5 -49.20 -31.95
50 -37.90 -20.66 75 -42.09 -24.84
100 -33.72 -16.48
Figure 27.4-8, page 271
Normal to B Face
Roof
P (psf) with


Wind Analysis for Alternate All-Heights Method, Based on ASCE 7-2010
P (psf) with
Basic wind speed (ASCE 7-10 26.5.1 or 2012 IBC)
Topographic factor (ASCE 7-10 26.8 & Table 26.8-1)
Effective area of components (or Solar Panel area)
P (psf) with P (psf) with
W
i
n
d
w
a
r
d

W
a
l
l
Normal to L Face P (psf) with
Roof
Normal to L Face
Normal to B Face P (psf) with
cont'd
Case 1 Case 2 Case 1 Case 2 Case 3 Case 4
V
Base
(kips) 374 280 155 117 397 228
M
Base
(ft - kips) 19212 14409 13800 10350 24759 13317 Fig. 27.4-8
M
T
(ft - kips) 0 4204 0 874 0 3812 Page 271
F
Upward
(kips) 200 150 170 128 277 148
V
min
(kips) 120 120 60 60 135 134 Min. wind
F
Up,min
(kips) 80 80 80 80 80 80 Sec. 6.1.4.1
Design pressures for components and cladding
a = width of edge strips, Fig 28.4-1, note 9, page 301, MAX[ MIN(0.1B, 0.1L, 0.4h), MIN(0.04B, 0.04L), 3] = 5.00 ft
Effective
Area (ft
2
) GC
P
- GC
P
GC
P
- GC
P
GC
P
- GC
P
GC
P
- GC
P
GC
P
- GC
P
Comp. 28 0.26 -0.96 0.26 -1.49 0.26 -2.04 0.83 -0.92 0.83 -1.12
(Walls reduced 10 %, Fig. 6-11A note 5.)
Positive Negative Positive Negative Positive Negative Positive Negative Positive Negative
20.85 -54.37 20.85 -79.84 20.85 -106.32 48.32 -52.63 48.32 -62.16
Zone 5
Comp. & Cladding
Zone 1 Zone 2 Zone 3 Zone 4 Zone 5
Zone 1 Zone 2 Zone 3 Zone 4
Pressure
( psf )
Base Forces
Normal to L Face
ASCE-7
Normal to B Face Wind with Angle