lire and smoke dampers lire valves

PL-16 PL-17
PL-15 PL-18-1, PL-18-2
DOL-3-1 DOL-3-2
PL-12
PPV-K90
DOL-1R DOL-1RK
PL-13 PL-14
DPL-7
PL-18-3, PL-18-4
FIRE DAMPERS
Fire dampers are installed in rectangular or
circular ventilation ducts, at passages of fire
compartments. In case of fire, fire dampers close
automatically, thus preventing fire from spreading
through the ventilation ducts. Fire resistance is
30, 60, 90 or 120 minutes.
Types according to the release mechanism type:
basic type with fusible link release
motorized type with electric actuator
FIRE PROTECTION VALVES
Fire protection valves are used to prevent fire from
spreading from bathrooms, kitchens. They are
installed at the beginning of ventilating ducts,
directly into the walls or ceilings. Release
mechanism triggers at 70 C.
Fire protection valves have two functions:
they are the part of fire protection wall with fire
resistance 90 min,
they are used for aeration (both, air supply and
exhaust) with a possibility of air flow regulation.
SMOKE DAMPERS
Smoke dampers open automatically in case of fire
and thus enable the exhaust of smoke and heat.
Fire resistance is 30, 60, 90 or 120 minutes.
Types according to the release mechanism type:
basic mechanical type with fusible link
solenoid type
motorized type with electric actuator
Rectangular fire dampers
FIRE DAMPERS, FIRE PROTECTION VALVES, SMOKE DAMPERS
Circular fire dampers
Fire protection valves
Smoke dampers
FIRE PROTECTION TECHNIQUE
Fire dampers, Fire protection valves, Smoke dampers
Fire dampers Page
Rectangular fire dampers (PL-12) and Circular fire dampers (PL-13, PL-14) ......................................................................................................................344
Types.................................................................................................................................................................................................................................345
Installation.........................................................................................................................................................................................................................347
Technical data....................................................................................................................................................................................................................350
Ordering key......................................................................................................................................................................................................................353
Rectangular fire dampers (PL-15) and Circular fire dampers (PL-16, PL-17) ......................................................................................................................354
Types.................................................................................................................................................................................................................................355
Installation.........................................................................................................................................................................................................................359
Technical data....................................................................................................................................................................................................................362
Ordering key......................................................................................................................................................................................................................363
Rectangular fire dampers (PL-18-1 and PL-18-2) and Circular fire dampers (PL-13R-K90) ...............................................................................................364
Types.................................................................................................................................................................................................................................366
Installation.........................................................................................................................................................................................................................369
Technical data....................................................................................................................................................................................................................371
Ordering key......................................................................................................................................................................................................................373
Electric actuators for fire dampers....................................................................................................................................................................................374
Fire protection valves
Fire protection valve PPV-K90...............................................................................................................................................................................................378
Smoke dampers
Smoke damper DOL-1R.........................................................................................................................................................................................................381
Smoke damper DOL-1RK (duct version)................................................................................................................................................................................383
Smoke damper DPL-7 ...........................................................................................................................................................................................................385
Smoke dampers DOL-3-1 .....................................................................................................................................................................................................389
Smoke dampers DOL-3-2 .....................................................................................................................................................................................................393
Smoke dampers PL-18-3 and PL-18-4 ................................................................................................................................................................................397
Electric actuators for smoke dampers..............................................................................................................................................................................400
Certificates..................................................................................................................................................................................................................................406
344
PL-12
PL-13
PL-14
FIRE DAMPERS PL-12, PL-13 AND PL-14
FIRE DAMPERS PL-12, PL-13 and PL-14
Application
Fire dampers prevent fire from spreading in air conditioning and ventilation
installations. They are installed at crossings of ventilating ducts through
partition walls and ceilings which divide a building into fire compartments.
Description
Fire dampers consist of housing made of galvanized sheet metal, damper blade
made of special insulation material, thermal release mechanism with melting
point at 70C or 120C, manual lever for moving the damper blade into
opened or closed position, springs, bearings and other parts.
Fire resistance and classification
Fire dampers have the fire resistance of K60 or K90.
They have been attested according to the following standards:
NORM B 3800 , part 1
NORM B 3800 , part 2
NORM M 7625
Types
PL-12: rectangular fire dampers
PL-13: circular fire dampers - with flange
PL-14: circular fire dampers - for spiral ducts
Types according to the release mechanism type:
basic type with fusible link release (designation A, A2 or A7)
with electric actuator (designations E5 to E19)
Note: check ordering key for specific type, not all combinations are applicable.
Nominal sizes of rectangular dampers PL-12
When ordering, it is necessary beside dimensions BxH, to indicate also the
length L.
Upon request, it is possible to produce fire dampers PL-12 of special
dimensions within the following range:
B = from 150 to 1500 mm, H = from 150 to 800 mm, L = from 160 to 700 mm
Standard length for PL-12:
Standard length for PL-12 is 325mm.
Nominal sizes of dampers PL-13, PL-14
Standard lengths (L) for circular fire dampers PL-13, PL-14:
PL-13 from 315 to 800, L = 400
(when ordering, it is not necessary to specify the length)
PL-14 from 100 to 500, L = 300
(when ordering, it is not necessary to specify the length)
Special dimensions:
Upon request, it is possible to produce fire dampers PL-13 and PL-14 of
custom dimensions within the range of standard dimensions.
PL-13
PL-14
BxH= from 200 x 150 mm to 1500 x 800 mm (table at page 350)
FIRE DAMPERS PL-12, PL-13 AND PL-14 TYPES
345
Types:
PL-13-K90/A
Basic type
1. Housing made of galvanised steel sheet
2. Blade made of special fire-resistant material
with intumescent seal
3. Thermal release link (melting point 70 C or
120C)
4. Inspection opening
5. Handle
6. Spring
Operating principle:
During the normal operation damper remains
open. In case of fire, the thermal release link
melts at 70C or 120C, respectively, thus
enabling the spring to close the damper's blade.
400

D
n
D
n
+65
1 4
5
6
2

D
z
3
250
PL-12-K60 or K90/A2/T12
Basic type with limit switches:
7. Limit switch T1 is used to control the
damper's closed position. By activating the
limit switch a corresponding signal light
or an acoustic signal in the central control
panels is switched on. When the damper is
returned to the open position, the signal is
switched off.
8. Limit switch T2 is used to control the
damper's open position. When the damper is
returned to the closed position, the signal in the
central control panel is switched off.
Version with position indicator
12. Position indicator
In principle, construction is the same as basic
type, with incorporated position indicator, used
to indicate the positions OPEN or CLOSED.
This function is not possible when fire damper
is equipped with electric actuator.
7
2
5
12
7
5
2
12
PL-14-K90/A/T1/K
346
FIRE DAMPERS WITH ELECTRIC ACTUATOR PL-12, PL-13 AND PL-14

In case of circular fire dampers, the range of
applicability of BLF actuators is from 100 to 500.
The range of applicability for BLF actuators (designations: E15, E16, E19)
Fire dampers with electric actuators:
10. Electric actuator
11. Junction box
Besides triggering by thermal fuse,
damper may be additionally triggered by a signal
from a smoke detector or control panel switch.
When the damper is opened, electric actuator is
under electrical power all the time, when power is
cut off, the built in spring automatically closes the
damper. Under normal circumstances i.e. when
there is no fire and thermal fuse has not been
triggered, the damper returns to the open position
automatically when the power returns. Both limit
switches to indicate the positions CLOSED
and OPEN are incorporated in the electric
actuator and need not to be ordered separately.
FIRE DAMPERS PL-12, PL-13 AND PL-14 INSTALLATION
347
View of the left and the right type fire
damper
Right damper "D":
As seen in the direction of the arrow.
If the order does not specify the direction of drive
D or L, the right type D will be supplied. See
the ordering key.
Left damper "L":
As seen in the direction of the arrow.
Installation
The fire dampers are installed so as to place the
release device and inspection opening at the
accessible side of wall or ceiling. In this way
the thermal release link and the inside of the
damper can be controlled. The dampers may
be installed into any position. They are installed
directly into a wall or a ceiling which has the same
fire resistance as the damper. Installed damper
housing must not be statically stressed by
building's construction.
348
FIRE DAMPERS PL-12, PL-13 AND PL-14 INSTALLATION
Duct openings
The minimum allowable distance of the openings
in the duct (e.g. grilles) from the damper is 1.5
times the larger dimension of the connecting duct.
1.5D 1.5D
250

D
n
+
1
2
0
150

D
n
+
8
0
Warning
Standard type fire dampers are not allowed to be
installed in the explosion hazardous spaces. It is
also not allowed to install standard type fire
dampers in ventilating devices which lead away
the mixture of air and explosion gasses.
Maintenance
Dirty and humid air is likely to influence the
functional capability of the dampers. Therefore, the
dampers have to be checked regularly as follows:
All types of dampers should be completely
checked twice a year. If two successive tests
show no defects, it is sufficient to perform
further tests only once a year.
Dampers equipped with electrical actuators,
triggered by the button or switch in the control
room are to be checked four times a year.
PL-14-K90/A PL-13-K90/A
349
Fire damper installation in lightweight flexible walls
FIRE DAMPERS PL-12, PL-13 AND PL-14 INSTALLATION






















205
Section C-C
Main view is shown clipped without insulation filling and wall forming
plasterboards. Visible are plasterboard plates around the damper, which serve
to fill in the gap.
Legend:
W111 Partition wall with single supporting metal construction, both sides single layer plated
W112 Partition wall with single supporting metal construction, both sides double layer plated
W113 Partition wall with single supporting metal construction, both sides triple layer plated
W115 Partition wall with double supporting metal construction, both sides double layer plated
W115* Partition wall between apartments, with double supporting metal construction, both sides single layer plated plus single layer plate in the middle
W116 Installation wall with double supporting metal construction, both sides double layer plated
W118 Safety wall with single supporting metal construction, both sides triple layer plated plus two layers of sheet metal
1. PL-12W(...)-K90/A2/T1
2. UA profile
3. UA profile
4. L joint for UA profiles
5. Insulation layer (mineral wool)
6. Plasterboard (gypsum) plate
7. Plasterboard (gypsum) plate-filler
8. Supporting- protective profile H/B
9. Universal screw
L = length of fire damper
L = 600 is non standard length for fire damper
B,H - nominal dimensions of fire damper B (width),
H (height)
Fire dampers must be installed in partitions with
fire resistance being equal or higher than the
damper.
Wall type Wall width
B
Fire damper length
L
350
FIRE DAMPERS PL-12 TECHNICAL DATA
PL-12-K90
BxH 150 200 250 300 350 400 450 500 550 600 650 700 750 800
200 0.024 0.034 0.044 0.054 0.064 0.074 0.084 0.093 0.103 0.113 0.123 0.133 0.143 0.153
250 0.031 0.043 0.056 0.068 0.080 0.093 0.105 0.117 0.130 0.142 0.154 0.167 0.179 0.191
300 0.037 0.052 0.067 0.082 0.097 0.112 0.126 0.141 0.156 0.171 0.186 0.201 0.215 0.230
350 0.044 0.061 0.078 0.096 0.113 0.130 0.148 0.165 0.182 0.200 0.217 0.235 0.252 0.269
400 0.050 0.070 0.090 0.110 0.129 0.149 0.169 0.189 0.209 0.229 0.249 0.268 0.288 0.308
450 0.056 0.079 0.101 0.124 0.146 0.168 0.191 0.213 0.235 0.258 0.280 0.302 0.325 0.347
500 0.063 0.088 0.113 0.137 0.162 0.187 0.212 0.237 0.262 0.287 0.311 0.336 0.361 0.386
550 0.069 0.097 0.124 0.151 0.179 0.206 0.233 0.261 0.288 0.315 0.343 0.370 0.397 0.425
600 0.076 0.106 0.135 0.165 0.195 0.225 0.255 0.285 0.314 0.344 0.374 0.404 0.434 0.464
650 0.082 0.114 0.147 0.179 0.211 0.244 0.276 0.309 0.341 0.373 0.406 0.438 0.470 0.503
700 0.088 0.123 0.158 0.193 0.228 0.263 0.298 0.332 0.367 0.402 0.437 0.472 0.507 0.542
750 0.095 0.132 0.170 0.207 0.244 0.282 0.319 0.356 0.394 0.431 0.468 0.506 0.543 0.580
800 0.101 0.141 0.181 0.221 0.261 0.301 0.340 0.380 0.420 0.460 0.500 0.540 0.579 0.619
850 0.108 0.150 0.192 0.235 0.277 0.319 0.362 0.404 0.446 0.489 0.531 0.574 0.616 0.658
900 0.114 0.159 0.204 0.249 0.293 0.338 0.383 0.428 0.473 0.518 0.563 0.607 0.652 0.697
950 0.120 0.168 0.215 0.263 0.310 0.357 0.405 0.452 0.499 0.547 0.594 0.641 0.689 0.736
1000 0.127 0.177 0.227 0.276 0.326 0.376 0.426 0.476 0.526 0.576 0.625 0.675 0.725 0.775
1050 0.133 0.186 0.238 0.290 0.343 0.395 0.447 0.500 0.552 0.604 0.657 0.709 0.761 0.814
1100 0.140 0.195 0.249 0.304 0.359 0.414 0.469 0.524 0.578 0.633 0.688 0.743 0.798 0.853
1150 0.146 0.203 0.261 0.318 0.375 0.433 0.490 0.548 0.605 0.662 0.720 0.777 0.834 0.892
1200 0.152 0.212 0.272 0.332 0.392 0.452 0.512 0.571 0.631 0.691 0.751 0.811 0.871 0.931
1250 0.159 0.221 0.284 0.346 0.408 0.471 0.533 0.595 0.658 0.720 0.782 0.845 0.907 0.969
1300 0.165 0.230 0.295 0.360 0.425 0.490 0.554 0.619 0.684 0.749 0.814 0.879 0.943 1.008
1350 0.172 0.239 0.306 0.374 0.441 0.508 0.576 0.643 0.710 0.778 0.845 0.913 0.980 1.047
1400 0.178 0.248 0.318 0.388 0.457 0.527 0.597 0.667 0.737 0.807 0.877 0.946 1.016 1.086
1450 0.184 0.257 0.329 0.402 0.474 0.546 0.619 0.691 0.763 0.836 0.908 0.980 1.053 1.125
1500 0.191 0.266 0.341 0.415 0.490 0.565 0.640 0.715 0.790 0.865 0.939 1.014 1.089 1.164
Table of nominal dimensions with effective sections A
ef
(m
2
)
351
FIRE DAMPERS PL-12 TECHNICAL DATA
2 3 4 5 10 20 30 40 50 60 70
p
t
(Pa)
6 7 8 9
3
4
5
6
7
8
9
10
v
(
m
/
s
)
1.0 0.8 0.6 0.4 0.2

35 dB
40
45
50
55 60
L W
A
0.02
0.03
0.04
0.05
0.1
0.2
0.3
0.4
0.5
1.0
1000 2000 32000
Q(m
3
/h)
400 3000 6000 12000
A
(
m

2
)
4
m
/
s
5
6
7
8
9
1
0
Table of effective cross-sections A
ef
(m
2
) and resistance quotients () for PL-12
Pressure drop and sound power level diagram for PL-12
H
B/H 200 300 400 500 600 700 800
200 0,034 0,054 0,074 0,093 0,113 0,133 0,153 A
ef
1,00 0,82 0,73 0,68 0,64 0,62 0,61
300 0,052 0,082 0,112 0,141 0,171 0,201 0,230 A
ef
0,98 0,70 0,63 0,62 0,55 0,51 0,49
400 0,070 0,110 0,149 0,189 0,229 0,268 0,308 A
ef
0,95 0,69 0,61 0,52 0,48 0,43 0,41
500 0,088 0,137 0,187 0,237 0,287 0,336 0,386 A
ef
0,93 0,65 0,55 0,48 0,41 0,39 0,38
600 0,106 0,165 0,225 0,285 0,344 0,404 0,464 A
ef
0,90 0,62 0,52 0,43 0,40 0,37 0,35
700 0,123 0,193 0,263 0,332 0,402 0,472 0,542 A
ef
0,88 0,60 0,50 0,42 0,38 0,35 0,30
800 0,141 0,221 0,301 0,380 0,460 0,540 0,619 A
ef
0,86 0,60 0,49 0,40 0,37 0,32 0,30
900 0,159 0,249 0,338 0,428 0,518 0,607 0,697 A
ef
0,84 0,59 0,48 0,40 0,35 0,31 0,29
1000 0,177 0,276 0,376 0,476 0,576 0,675 0,775 A
ef
0,82 0,58 0,47 0,39 0,34 0,30 0,27
1100 0,195 0,304 0,414 0,524 0,633 0,743 0,853 A
ef
0,80 0,57 0,45 0,38 0,35 0,30 0,27
1200 0,212 0,332 0,452 0,571 0,691 0,811 0,931 A
ef
0,78 0,56 0,46 0,37 0,32 0,29 0,25
1300 0,230 0,360 0,490 0,619 0,749 0,879 1,008 A
ef
0,76 0,55 0,45 0,35 0,30 0,27 0,24
1400 0,248 0,388 0,527 0,667 0,807 0,946 1,086 A
ef
0,74 0,54 0,43 0,34 0,30 0,28 0,23
1500 0,266 0,415 0,565 0,715 0,865 1,014 1,164 A
ef
0,72 0,54 0,42 0,34 0,30 0,27 0,23
352
Pressure drop and sound power level diagram for PL-13 and PL-14
Table of effective cross-sections A
ef
(m
2
) for PL-13 and PL-14
PL-13-K 90
L=400
Nominal size A
ef
(m
2
)
315 0.076
400 0.121
500 0.193
630 0.309
710 0.390
800 0.490
PL-14-K 90
L=300
Nominal size A
ef
(m
2
)
100 0.006
125 0.010
150 0.015
160 0.017
180 0.022
200 0.028
224 0.036
250 0.045
280 0.057
300 0.065
315 0.072
350 0.092
355 0.094
400 0.121
500 0.190
FIRE DAMPERS PL-13 AND PL-14 TECHNICAL DATA
0.4
0.6
1
2
4
6
8
10
20
40
60
80
100
200 500 1000 2000 4000 6000 10000 15000
2
0
0
3
1
5
4
0
0
5
0
0
6
3
0
7
1
0
8
0
0
2
0
2
5
3
0
3
5
4
0
4
5
5
0
5
5
Q (m
3
/h)

p
t
(
P
a
)
L W
A
1
8
0
1
6
0
1
5
0
1
2
5
2
8
0
2
5
0
2
2
4
s
i
z
e

1
0
0
353
PL - 12 - K90 / A / T1 / K / L B x H
L
D
K
T1
T2
T12
D0
A
A2
A7
E5
E6
E9
E15
E16
E19
PL-12-K60
PL-12-K90
PL-13-K90
PL-14-K90
Left
Right=standard (need not to be stated by ordering)
Position indicator
Limit switch closed
Limit switch open
Limit switch closed, open
Junction box (possible with electric actuators, types E)
Basic type with manual handling - fusible link release (PL-13, PL-14)
Basic type with manual handling - fusible link release (PL-12)
Simplified type with manual handling - fusible link release (PL-12)
Electric actuator BF 24-T*
Electric actuator BF 230-T*
Electric actuator BF 24-T-st + BKN 230-24*
Electric actuator BLF-24 T*
Electric actuator BLF-230 T*
Electric actuator BLF 24-T-st + BKN 230-24*
Rectangular fire damper (60 min)
Rectangular fire damper (90 min)
Circular fire damper (with flange)
Circular fire dampers (for spiral ducts)
* See page 349
** In electric actuator variants, the motor is fitted with limit switches. An electric actuator variant with extra limit switches (T1, T2, T12) is not available.
*** Not necessary to order with electric actuator variants.
Ordering key:
FIRE DAMPERS PL-12, PL-13 AND PL-14 ORDERING KEY
Fire dampers for lightweight walls
(80) width of the wall
(111) lightweight wall type

















354
FIRE DAMPERS PL-15, PL-16 AND PL-17
FIRE DAMPERS PL-15, PL-16 and PL-17
Application:
Fire dampers prevent fire from spreading through air-conditioning and
ventilation installations. They are designed for installation in the ventilation
duct passages through partition walls and ceilings dividing the building into
fire compartments.
Description:
Fire dampers consist of a three-section housing made of galvanised steel
sheet, with the mid section made of a special insulation material, a blade made
of a special insulation material, and a thermal release mechanism with the
release temperature 70C or 120C.
Fire resistance and classification:
Fire dampers fire resistance is EI 120-S.
Fire dampers are type tested according to EN 1366-2.
Types
PL-15: square fire damper
PL-16: circular fire damper with flange
PL-17: circular fire damper for installation in spiral-ducts
Types according to the release mechanism:
basic type with fusible link release (designation A, A2 or A7)
with electric actuator (designations E1 to E19)
Nominal dimensions PL-15
B x H = from 250 x 250 to 1500 x 800 mm.
It is possible to make fire damper dimension 250 x 250 reduced to 150 x 150.
For detailed description see page 358.
Upon request fire damper PL-15 of custom dimensions within the range:
B = from 250 to 1500, H = from 250 to 800 can be produced.
Standard length for PL-15:
Standard length for PL-15 is 400mm.
Nominal sizes of dampers PL-16, PL-17
Standard length for circular fire dampers PL-16 and PL-17:
Standard length for PL-16 and PL-17 is 400mm.
It is possible to make fire damper PL-17 of nominal dimension less than 150
reduced to 100. For detailed description see page 358.
Upon request fire dampers PL-16 and PL-17 of custom dimensions within the
range of standard dimensions can be produced.
Connection flanges on PL-16 are made according to standards DIN 24154
Reihe 1 teil I (edition 06/90) and EN12220 respectively.
PL-16 315 400 500 630 710 800
PL-17 150 160 180 200 224 250 280 300 315
350 355 400 500
PL-15
PL-17
355
FIRE DAMPERS PL-15, PL-16 AND PL-17 TYPES
Types
PL-15 EI 120-S/A7
1 6 5 2 3 4
4
77 400
4
0
4
0
H
40 40 59 H
PL-17 EI 120-S/A
p+45 400
20

z
4 1 5 6 2 3
PL-15 EI 120-S/A7/T12
400 77 40 40 B
4
0
4
0
H
59
1 6 5 2 3 4
4
PL-17 EI 120-S/A/T12
4 1 5 6 2 3
p+45

p
8
4
400
20

z
Basic type
1. Housing made of galvanised steel sheet
2. Blade made of special fire-resistant material
3. Thermal release link (melting point 70C or
120C)
4. Inspection opening
5. Handle
6. Spring
Operating principle:
During the normal operation damper remains
open. In case of fire, the thermal release link
melts at 70C or 120C, respectively, thus
enabling the spring to close the damper's blade.
Basic type with limit switches:
7. Limit switch T1 is used to control the
damper's closed position. By activating the
limit switch a corresponding signal light
or an acoustic signal in the central control panel
s is switched on. When the damper is returned
to the open position, the signal is switched off.
8. Limit switch T2 is used to control the
damper's open position. When the damper is
returned to the closed position, the signal in the
central control panel is switched off.
356
FIRE DAMPERS PL-15, PL-16 AND PL-17 TYPES
Types
PL-15 EI 120-S/A2
H
4
0
4
0
H 40 71
77 400
40
3 4
4
2 6 1 5
PL-15 EI 120-S/A2/T12
3 4 2
4
8 6 1 7 5
H
4
0
4
0
H 40 71 40 400 77
PL-15 EI 120-S/E5, E6/D
10 1 11
4
4
3 2
H
4
0
4
0
H 40 68 40
400
PL-16 EI 120-S/E.../D
11
1 10 4 12 3
Dp+70 400
D
p
D
n
Version with electric actuators:
10. Electric actuator
11. Junction box
Besides triggering by thermal fuse,
damper may be additionally triggered by a signal
from a smoke detector or control panel switch.
When the damper is opened, electric actuator is
under electrical power all the time, when power is
cut off the built in spring automatically closes the
damper. Under normal circumstances i.e. when
there is no fire and thermal fuse has not been
triggered, the damper returns to the open position
automatically when the power returns.
Both limit switches to indicate the
positions CLOSED and OPEN are
incorporated in the electric actuator and
need not to be ordered separately.
Basic type with limit switches:
7. Limit switch T1 is used to control the damper's
closed position. By activating the limit switch a
corresponding signal light or an acoustic signal
in the central control panel s is switched on.
When the damper is returned to the open
position, the signal is switched off.
8. Limit switch T2 is used to control the damper's
open position. When the damper is returned to
the closed position, the signal in the central
control panel is switched off.
Basic type
1. Housing made of galvanised steel sheet
2. Blade made of special fire-resistant material
3. Thermal release link (melting point 70C or 120C)
4. Inspection opening
5. Handle
6. Spring
Operating principle:
During the normal operation damper remains
open. In case of fire, the thermal release link
melts at 70C or 120C, respectively, thus
enabling the spring to close the damper's blade.
357
FIRE DAMPERS PL-15, PL-16 AND PL-17 TYPES
Definition of the left and right type fire
damper
Closing
direction
Left
damper "L"
Closing
direction
Right
damper "D"
550 500 450 400 350 300 250 200 150
1000
950
900
850
800
750
700
650
600
550
500
450
400
350
300
250
200
BxH
The range of applicability for BLF actuators
(designations: E15, E16, E19)
PL-17 EI 120-S/K

z
12
PL-15 EI 120-S/A7/K
12
In case of circular fire dampers, the range of
applicability for BLF actuators is from 100 to 500.
Version with position indicator
12. Position indicator
In principle, construction is the same as basic
type, with incorporated position indicator, used
to indicate the positions OPEN or CLOSED.
This function is not possible when fire damper
is equipped with electric actuator.
358
FIRE DAMPERS PL-15, PL-16 AND PL-17 TYPES
View of the left and right type fire damper
Left type we only produce in basic A7 manual
version.
Right damper "D"
As seen in the direction of the handle.
If the order does not specify the direction of drive
D or L, the right type D will be supplied. See
the ordering key.
Left damper "L"
As seen in the direction of the handle.
Application
When the right fire damper is installed under the
ceiling in the corner (see picture), it can happen,
that the thermal release (pos.3) is not accessible
through revision opening (pos.4), because of the
blade being in the way. In such case we use left
fire damper.
FIRE DAMPERS WITH REDUCERS
PL-15
1. Fire damper PL-15
2. Reducer
The smallest producible damper is BxH= 250 x 250 mm.
For such it is possible to make reducers which enable
connection of a duct with dimensions less than
250 x 250 mm.
Table - dimensions of reducers:
* Check before ordering
PL-17
1. Fire damper PL-17
2. Reducer
The smallest producible damper is 150.
For such it is possible to make reducers which
enable connection of a duct with dimensions less
than 150.
Table - dimensions of reducers:
Desna"D"
Leva"L"
Desna"D"
3 4 3 4
3 4
50
400
330
40 40 b
4
0
3
3
0
4
0
b
400 - 600 *
50
2 1 2
Application of the left and right type fire damper
PL-15 with reducers
Dp+45
D
p
50
D
r
50
400
2
1 2
D
z
PL-17 with reducers
Dr
100
125
b (mm) 150 200
h (mm) 150 200
Right D Right D
Left L
359
FIRE DAMPERS PL-15, PL-16 AND PL-17 INSTALLATION
13 14 13
14
151
77 400
w 18 18
1
8
1
8
4
0
H
1
9
7
.
5
H
+
2
2
0
4
0
40 40 B
B+220
59
13
14
4
0
0
7
7
13
14
18 18
1
8
1
8
4
0
B
B
+
2
2
0
5
9
4
0
40 H
H+220
197.5
40
PL-15 Installation
Dampers must be installed so, that the inspection
opening and release mechanism are on accessible
side of the wall or ceiling. In this way it is possible
to control the thermal release link and the inner
side of the damper.
Dampers PL-15 can be installed positioned as
shown on the picture.
Wall limit is defined by bracket pos.14.
Fire dampers must be installed in partitions with
fire resistance being equal or higher than the
damper.
Allowed installations are in masonry, concrete,
aerated concrete or lightweight flexible walls of
proper fire resistance.
Minimum allowed wall thickness for masonry,
concrete or aerated concrete walls or ceilings is
W = 10cm.
Fire damper PL-15 installation in concrete or
aerated concrete ceiling.
The build-in damper housing should not be
statically stressed by buildings structure.
We recommend the use of wooden supports
during the installation (see picture).
Before installation the anchors (pos.13) must be
placed as shown on the sketch.
Sketch is representative for all PL-15 types.
Warning:
Standard type fire dampers are not allowed to be
installed in the explosion hazardous spaces. It is
also not allowed to install standard type fire
dampers in ventilating devices which lead away
the mixture of air and explosion gasses.
Standard type fire dampers are not allowed to be
installed outdoors or at places exposed to weather
conditions (rain, snow).
Other instructions for installation are available in "
Installation instructions for safe use, maintenance,
testing and installation of fire dampers".
Maintenance:
Dirty and humid air is likely to influence the
functional capability of the dampers. Therefore, the
dampers have to be checked regularly as follows:
All types of dampers should be completely
checked twice a year. If two successive tests
show no defects, it is sufficient to perform
further tests only once a year.
Dampers equipped with electrical actuators,
triggered by the button or switch in the control
room are to be checked four times a year.
Fire damper PL-15 installation in masonry, concrete or aerated concrete wall
Installation of fire damper PL-15 into concrete or areated concrete ceiling
Use of wooden supports during the installation
Allowed positions for fire dampers installations
0 90 180 270
360
FIRE DAMPERS PL-15, PL-16 AND PL-17 INSTALLATION
1. PL-15 EI 120-S/W*/A2
2. UA profile
3. Insulation layer (mineral wool)
4. Plasterboard (gypsum) plate
5. Universal screw
6. Fixing bracket
Wall type Wall width
D (mm)
W 111 100
125
W112 100
125
150
W113 125
150
175
W115 155
205
255
W115* 215
W116 220
270
320
W118 177
Fire damper installation in lightweight flexible walls
Legend:
W111 Partition wall with single supporting metal construction, both sides single layer plated
W112 Partition wall with single supporting metal construction, both sides double layer plated
W113 Partition wall with single supporting metal construction, both sides triple layer plated
W115 Partition wall with double supporting metal construction, both sides double layer plated
W115* Partition wall between apartments, with double supporting metal construction, both sides single layer plated plus single layer plate in the middle
W116 Installation wall with double supporting metal construction, both sides double layer plated
W118 Safety wall with single supporting metal construction, both sides triple layer plated plus two layers of sheet metal
3
1
4 5
6
2
40
400 77
40 B 40 40
4
0
4
0
H
1
9
7
4
0
15 15 <150 150 150
150 w
<150
1
5
1
5
<
1
5
0
1
5
0
1
5
0
<
1
5
0
4
0
71
361
FIRE DAMPERS PL-15, PL-16 AND PL-17 INSTALLATION
PL-16, PL-17 Installation
Dampers must be installed so, that the inspection
opening and release mechanism are on accessible
side of the wall or ceiling. In this way it is possible to
control the thermal release link and the inner side of
the damper.
Dampers PL-16, PL-17 can be installed positioned
as shown on the picture.
Wall limit is defined by label pos.14.
Fire dampers must be installed in partitions with fire
resistance being equal or higher than the damper.
Allowed installations are in masonry, concrete,
aerated concrete or lightweight flexible walls of
proper fire resistance.
Minimum allowed wall thickness for masonry,
concrete or aerated concrete walls or ceilings is
W= 10cm.
Fire damper PL-15 installation in concrete or aerated
concrete ceiling.
The build-in damper housing should not be statically
stressed by buildings structure. We recommend the
use of wooden supports during the installation (see
picture).
Before installation the anchors (pos.13) must be
placed as shown on the sketch.
Sketch is representative for all PL-16, PL-17 types.
Warning:
Standard type fire dampers are not allowed to be
installed in the explosion hazardous spaces. It is
also not allowed to install standard type fire
dampers in ventilating devices which lead away
the mixture of air and explosion gasses.
Standard type fire dampers are not allowed to be
installed outdoors or at places exposed to weather
conditions (rain, snow).
Other instructions for installation are available in "
Installation instructions for safe use, maintenance,
testing and installation of fire dampers".
Maintenance
Dirty and humid air is likely to influence the
functional capability of the dampers. Therefore, the
dampers have to be checked regularly as follows:
All types of dampers should be completely
checked twice a year. If two successive tests
show no defects, it is sufficient to perform
further tests only once a year.
Dampers equipped with electrical actuators,
triggered by the button or switch in the control
room are to be checked four times a year.
Fire damper PL-16, PL-17 installation in masonry, concrete or aerated concrete wall
Use of wooden supports during the installation
Allowed positions for fire dampers installations
p+45 400
20
150 w

p
z

p
+
2
4
0
13 13
14
0 90 180 270
362
FIRE DAMPERS PL-15, PL-16 AND PL-17 TECHNICAL DATA
H
B/H 250 300 350 400 450 500 550 600 650 700 750 800
250 0,038 0,047 0,057 0,066 0,076 0,085 0,095 0,104 0,114 0,123 0,133 0,142 A
ef
0,99 0,90 0,81 0,75 0,71 0,68 0,66 0,65 0,64 0,62 0,61 0,60
300 0,048 0,060 0,072 0,084 0,096 0,108 0,120 0,132 0,144 0,156 0,168 0,180 A
ef
0,96 0,85 0,77 0,72 0,68 0,65 0,63 0,61 0,60 0,59 0,57 0,55
350 0,059 0,073 0,088 0,102 0,117 0,131 0,146 0,160 0,175 0,189 0,204 0,218 A
ef
0,92 0,81 0,73 0,68 0,65 0,62 0,60 0,58 0,56 0,54 0,53 0,51
400 0,069 0,086 0,103 0,120 0,137 0,154 0,171 0,188 0,205 0,222 0,239 0,256 Aef
0,89 0,77 0,70 0,65 0,62 0,59 0,57 0,54 0,52 0,51 0,49 0,48
450 0,080 0,099 0,119 0,138 0,158 0,177 0,197 0,216 0,236 0,255 0,275 0,294 A
ef
0,85 0,74 0,66 0,62 0,59 0,56 0,54 0,52 0,50 0,48 0,47 0,45
500 0,09 0,112 0,134 0,156 0,178 0,2 0,222 0,244 0,266 0,288 0,31 0,332 A
ef
0,81 0,71 0,64 0,59 0,56 0,53 0,51 0,49 0,48 0,47 0,45 0,44
550 0,101 0,125 0,150 0,174 0,199 0,223 0,248 0,272 0,297 0,321 0,346 0,370 A
ef
0,78 0,68 0,61 0,57 0,54 0,51 0,49 0,48 0,47 0,46 0,44 0,43
600 0,111 0,138 0,165 0,192 0,219 0,246 0,273 0,3 0,327 0,354 0,381 0,408 A
ef
0,74 0,65 0,59 0,55 0,52 0,49 0,48 0,47 0,46 0,45 0,44 0,43
650 0,122 0,151 0,181 0,210 0,240 0,269 0,299 0,328 0,358 0,387 0,417 0,446 A
ef
0,71 0,62 0,58 0,54 0,50 0,48 0,47 0,46 0,45 0,44 0,43 0,42
700 0,132 0,164 0,196 0,228 0,260 0,292 0,324 0,356 0,388 0,420 0,452 0,484 A
ef
0,69 0,60 0,56 0,52 0,49 0,47 0,45 0,45 0,44 0,43 0,42 0,41
750 0,143 0,177 0,212 0,246 0,281 0,315 0,350 0,384 0,419 0,453 0,488 0,522 A
ef
0,66 0,59 0,54 0,50 0,47 0,45 0,44 0,44 0,43 0,42 0,41 0,40
800 0,153 0,190 0,227 0,264 0,301 0,338 0,375 0,412 0,449 0,486 0,523 0,560 A
ef
0,65 0,57 0,53 0,49 0,46 0,44 0,43 0,42 0,42 0,41 0,40 0,39
850 0,164 0,203 0,243 0,282 0,322 0,361 0,401 0,440 0,480 0,519 0,559 0,598 A
ef
0,63 0,55 0,51 0,48 0,44 0,43 0,42 0,41 0,41 0,40 0,39 0,38
900 0,174 0,216 0,258 0,300 0,342 0,384 0,426 0,468 0,510 0,552 0,594 0,636 A
ef
0,62 0,54 0,51 0,47 0,43 0,42 0,41 0,40 0,39 0,39 0,38 0,37
950 0,1845 0,229 0,2735 0,318 0,3625 0,407 0,4515 0,496 0,5405 0,585 0,6295 0,674 A
ef
0,61 0,53 0,49 0,45 0,42 0,41 0,40 0,39 0,38 0,38 0,36 0,35
1000 0,195 0,242 0,289 0,336 0,383 0,430 0,477 0,524 0,571 0,618 0,665 0,712 A
ef
0,60 0,52 0,48 0,44 0,41 0,40 0,39 0,38 0,37 0,36 0,35 0,34
1050 0,206 0,255 0,305 0,354 0,404 0,453 0,503 0,552 0,602 0,651 0,701 0,750 A
ef
0,59 0,51 0,47 0,43 0,40 0,39 0,38 0,38 0,37 0,35 0,33 0,32
1100 0,216 0,268 0,32 0,372 0,424 0,476 0,528 0,58 0,632 0,684 0,736 0,788 A
ef
0,58 0,50 0,46 0,42 0,39 0,39 0,38 0,37 0,35 0,34 0,32 0,30
1150 0,227 0,281 0,336 0,390 0,445 0,499 0,554 0,608 0,663 0,717 0,772 0,826 A
ef
0,57 0,49 0,45 0,41 0,39 0,38 0,37 0,36 0,34 0,33 0,31 0,29
1200 0,237 0,294 0,351 0,408 0,465 0,522 0,579 0,636 0,693 0,750 0,807 0,864 A
ef
0,56 0,48 0,43 0,40 0,39 0,38 0,37 0,35 0,33 0,31 0,30 0,28
1250 0,248 0,307 0,367 0,426 0,486 0,545 0,605 0,664 0,724 0,783 0,843 0,902 A
ef
0,55 0,47 0,42 0,39 0,38 0,37 0,36 0,34 0,32 0,30 0,28 0,27
1300 0,258 0,320 0,382 0,444 0,506 0,568 0,630 0,692 0,754 0,816 0,878 0,940 A
ef
0,54 0,45 0,41 0,38 0,37 0,36 0,34 0,33 0,31 0,29 0,28 0,26
1350 0,269 0,333 0,398 0,462 0,527 0,591 0,656 0,720 0,785 0,849 0,914 0,978 A
ef
0,53 0,44 0,40 0,37 0,36 0,35 0,34 0,32 0,30 0,28 0,27 0,25
1400 0,279 0,346 0,413 0,48 0,547 0,614 0,681 0,748 0,815 0,882 0,949 1,016 A
ef
0,53 0,44 0,40 0,37 0,35 0,35 0,33 0,32 0,30 0,28 0,27 0,25
1450 0,290 0,359 0,429 0,498 0,568 0,637 0,707 0,776 0,846 0,915 0,985 1,054 A
ef
0,52 0,43 0,39 0,36 0,35 0,35 0,33 0,31 0,29 0,28 0,26 0,25
1500 0,300 0,372 0,444 0,516 0,588 0,660 0,732 0,804 0,876 0,948 1,020 1,092 A
ef
0,52 0,43 0,39 0,36 0,35 0,34 0,33 0,31 0,29 0,27 0,26 0,25
Table of effective cross-sections A
ef
(m
2
) and resistance coefficients () for PL-15
363
FIRE DAMPERS PL-15, PL-16 AND PL-17 ORDERING KEY
PL - 15 EI 120-S / A / T1 / K / L B x H
L
D
K
T1
T2
T12
D0
A
A2
A7
E5
E6
E9
E15
E16
E19
PL 15 EI 120-S
PL 16 EI 120-S
PL 17 EI 120-S
PL-15 EI 120-S/W111 (100)
PL-15 EI 120-S/W111 (125)
PL-15 EI 120-S/W112 (100)
PL-15 EI 120-S/W112 (125)
PL-15 EI 120-S/W112 (150)
PL-15 EI 120-S/W113 (125)
PL-15 EI 120-S/W113 (150)
PL-15 EI 120-S/W113 (175)
PL-15 EI 120-S/W115 (155)
PL-15 EI 120-S/W115 (205)
PL-15 EI 120-S/W115 (255)
PL-15 EI 120-S/W115*(215)
PL-15 EI 120-S/W116 (220)
PL-15 EI 120-S/W116 (270)
PL-15 EI 120-S/W116 (320)
PL-15 EI 120-S/W118 (177)
Left
Right=standard (need not to be stated by ordering)
Position indicator
Limit switch closed
Limit switch open
Limit switch closed,open
Junction box (possible with electric actuators, types E)
Basic type with manual handling - fusible link release (PL-16, PL-17)
Basic type with manual handling - fusible link release (PL-15)
Simplified type with manual handling - fusible link release (PL-15)
Electric actuator BF 24-T*
Electric actuator BF 230-T*
Electric actuator BF 24-T-st + BKN 230-24*
Electric actuator BLF-24 T*
Electric actuator BLF-230 T*
Electric actuator BLF 24-T-st + BKN 230-24*
rectangular fire damper
circular fire damper with flange
circular fire damper for installation in spiral-ducts
Fire dampers for lightweight walls
* In electric actuator variants, the motor is fitted with limit switches. An elactric actuator variant with extra limit switches (T1, T2, T12) is not available.
Ordering key:
364
FIRE DAMPERS PL-18-1-EI 30, PL-18-2-EI 120; PL-13R-K90
PL-18-2-EI 120/A2/T1
PL-18-2-EI 120/E16
PL-13R-K90/F/A/T1
PL-13R-K90/S/E16
Fire dampers PL-18-1, PL-18-2, PL-13R
Application:
Fire dampers prevent fire from spreading in air conditioning and ventilation
installations. They are installed at crossings of ventilating ducts through
partition walls and ceilings which divide a building into fire compartments.
Description:
Fire dampers consist of housing made of galvanized sheet metal, damper
blade made of special insulation material, thermal release mechanism with
melting point at 70C or 120C, manual lever for moving the damper blade
into opened or closed position, springs, bearings and other parts.
Fire resistance and classification:
Fire dampers have fire resistance EI 30, EI 90, EI 120.
They have been a-tested according to Russian standards in compliance
with certificate NPB 241-97.
Types
PL-18-1-EI 30: rectangular fire dampers
PL-18-2-EI 120: rectangular fire dampers
PL-13R-K90/F: circular fire dampers - with flange
PL-13R-K90/S: circular fire dampers - for spiral ducts
Types according to the release mechanism:
basic type with fusible link release (designation A, A2 or A7)
with electric actuator (designations E5 to E19)
365
FIRE DAMPERS PL-18-1-EI 30, PL-18-2-EI 120; PL-13R-K90 DIMENSIONS
Nominal dimensions of fire dampers PL-13R-K90/F, PL-13R-K90/S
PL-13R-K90/F 315 400 500 630 710 800
PL-13R-K90/S 100 125 150 160 180 200 224 250 280 300 315 350 355 400 500
Standard lengths for circular fire
dampers
PL-13R-K90/F from 315 to 800, L=400
(when ordering, it is not necessary to specify
the length)
PL-13R-K90/S from 100 to 500, L=300
(when ordering, it is not necessary to specify
the length)
Upon request, it is possible to produce fire
dampers PL-13R-K90/F and PL-13R-K90/S of
custom dimensions within the range of
standard dimensions.
PL-13R-K90/S
D
n
100 125 150 160 180 200 224 250 280 300 315 350 355 400 500
D
z
99 124 149 159 179 199 223 249 279 299 314 349 354 399 499
PL-13R-K90/F
D
n
315 400 500 630 710 800
D
z
322 404 507 638 715 801
D
f
386 468 571 712 789 875
Flange dimensions are made according to
standard DIN 24154 Reihe 2 Blatt 2 (edition
07/66)
D
n
- Nominal dimension
D
z
- Outer damper housing diameter
D
f
- Outer flange diameter
Nominal dimensions of fire dampers PL-18-1, PL-18-2
BxH
150
200
250
300
350
400
450
500
550
600
650
700
750
800
850
900
950
1000
1050
1100
1150
1200
1250
1300
1350
1400
1450
1500
150 200 250 300 350 400 450 500 550 600 650 700 750 800 850 900 950 1000
Nominal dimensions of fire dampers PL-13R-K90/F, PL-13R-K90/S
366
FIRE DAMPERS PL-18-1-EI 30, PL-18-2-EI 120; PL-13R-K90 TYPES
Basic type
1. Housing made of galvanised steel sheet
2. Blade made of special fire-resistant material with
intumescent seal
3. Thermal release link (melting point 70C or
120C)
4. Inspection opening
5. Handle
6. Spring
7. Limit switch T1 is used to control the
damper's closed position. By activating the
limit switch a corresponding signal light
or an acoustic signal in the central control
panel is switched on. When the damper is
returned to the open position, the signal is
switched off.
8. Limit switch T2 is used to control the
damper's open position. When the damper is
returned to the closed position, the signal in the
central control panel is switched off.
Operating principle:
During the normal operation damper remains
open. In case of fire, the thermal release link
melts at 70C or 120C, respectively, thus
enabling the spring to close the damper's blade.
Types:
PL-18-1-EI 30/A2/T12
PL-18-2-EI 120/A2/T12
4
6
8
7 1 2
5 3
325 B
H
32.5 32.5
8
3
2
.
5
3
2
.
5
4
6
8
7 1 2
5 3
325 B
H
32.5 32.5
8
3
2
.
5
3
2
.
5
4
6
8
7 1 2
5 3
325 B
H
32.5 32.5
8
3
2
.
5
3
2
.
5
PL-18-1-EI 30/A7/T12
367
FIRE DAMPERS PL-18-1-EI 30, PL-18-2-EI 120; PL-13R-K90 TYPES
PL-18-2-EI 120/A7/T12
PL-13R-K90/S/A
5
6
2
3 1 4
2 5
D
z
300
PL-13R-K90/F/A
5
6
2
3
400
D
f
1 4
D
z
A
A
A - A
4
6
8
7 1 2
5 3
325 B
H
32.5 32.5
8
3
2
.
5
3
2
.
5
368
FIRE DAMPERS WITH ELECTRIC ACTUATOR PL-18-1-EI 30, PL-18-2-EI 120; PL-13R-K90
BxH 150 200 250 300 350 400 450 500 550
200
250
300
350
400
450
500
550
600
650
700
750
800
850
900
950
1000
The range of applicability for BLF actuators (designations: E15, E16, E19)
In case of circular fire dampers, the range of
applicability for BLF actuators is from
100 to 500.
D L
View of the left and right type fire
damper
Right damper "D": as seen in the direction of
the arrow.
If the order does not specify the direction of
drive D or L, the right type D will be
supplied. See the ordering key.
Left damper "L": as seen in the direction of the
arrow.
Installation
The fire dampers must be installed so, that the
release device and inspection opening are at the
accessible side of wall or ceiling. In this way
the thermal release link and the inside of the
damper can be controlled. The dampers may
be installed in any position. They must be
installed directly into the wall or ceiling of the
same fire resistance as the damper.
Installed damper housing should not be
statically stressed by building's construction.
369
FIRE DAMPERS PL-18-1-EI 30, PL-18-2-EI 120; PL-13R-K90 INSTALLATION
PL- 18-1-EI 30/E6
B+190
B
1
3
5
H
107
H
+
1
2
0
32.5 32.5 L
205 W
40
B+190
B L
205 W
1
1
5
H
115
H
+
1
2
0
32.5 32.5
250
400
A
A
D
z
+
8
5
Dz+140
G
15
A - A
W
PL- 18-2-EI 120/A2
PL-13R-K90/F/A
Fire damper with nominal diameter 315,
dimension G=50mm.
Fire dampers with nominal diameter from 400 to
800, dimension G=70mm.
370
FIRE DAMPERS PL-18-1-EI 30, PL-18-2-EI 120; PL-13R-K90 INSTALLATION
Warning
Standard type fire dampers are not allowed to be
installed in the explosion hazardous spaces. It is
also not allowed to install standard type fire
dampers in ventilating devices which lead away
the mixture of air and explosion gasses.
Standard type fire dampers are not allowed to be
installed outdoors or at places exposed to
weather conditions (rain, snow).
Other instructions for installation are available in
"Installation instructions for safe use,
maintenance, testing and installation of fire
dampers".
Maintenance
Dirty and humid air is likely to influence the
functional capability of the dampers. Therefore,
the dampers have to be checked regularly as
follows:
All types of dampers should be completely
checked twice a year. If two successive tests
show no defects, it is sufficient to perform
further tests only once a year.
Dampers equipped with electrical actuators,
triggered by the button or switch in the
control room are to be checked four times a
year.
D
z
+
7
5
Dz+125
G
15
150
300
W
250
400
A
A
W
D
z
+
8
5
Dz+180
1
1
5
15
A - A
150
300
W
D
z
+
8
5
Dz+180
1
1
5
15
PL-13R-K90/F/E5
PL- 13R-K90/S/A
PL-13R-K90/S/E15
Fire dampers with nominal diameter from 100 to
315, dimension G=50mm.
Fire dampers with nominal diameter from 350 to
500, dimension G=70mm.
371
FIRE DAMPERS PL-18-1-EI 30, PL-18-2-EI 120 TECHNICAL DATA
H
B/H 150 200 250 300 350 400 450 500 550 600 650 700 750 800 850 900 950 1000
150 0,011 0,017 0,023 0,029 0,035 0,041 0,048 0,054 0,060 0,066 0,072 0,078 0,084 0,090 0,096 0,102 0,108 0,114 A
ef
1,02 1,01 1,00 1,00 0,99 0,98 0,96 0,85 0,80 0,78 0,77 0,73 0,70 0,69 0,68 0,69 0,69 0,63
200 0,016 0,025 0,033 0,042 0,050 0,059 0,067 0,076 0,085 0,093 0,102 0,110 0,119 0,127 0,136 0,144 0,153 0,161 A
ef
1,01 1,00 1,00 0,98 0,97 0,82 0,79 0,73 0,70 0,68 0,69 0,64 0,63 0,63 0,62 0,62 0,61 0,59
250 0,021 0,032 0,043 0,054 0,065 0,076 0,087 0,098 0,109 0,121 0,132 0,143 0,154 0,165 0,176 0,187 0,198 0,209 A
ef
1,00 0,99 0,98 0,82 0,88 0,73 0,69 0,68 0,69 0,63 0,62 0,62 0,61 0,58 0,55 0,52 0,51 0,50
300 0,026 0,040 0,053 0,067 0,080 0,094 0,107 0,121 0,134 0,148 0,162 0,175 0,189 0,202 0,216 0,229 0,243 0,256 A
ef
1,00 0,99 0,82 0,88 0,72 0,68 0,69 0,63 0,62 0,62 0,59 0,55 0,52 0,50 0,49 0,48 0,49 0,50
350 0,031 0,047 0,063 0,079 0,095 0,111 0,127 0,143 0,159 0,175 0,191 0,207 0,224 0,240 0,256 0,272 0,288 0,304 A
ef
0,99 0,98 0,79 0,72 0,68 0,69 0,63 0,62 0,61 0,55 0,51 0,50 0,48 0,49 0,50 0,57 0,58 0,57
400 0,036 0,055 0,073 0,092 0,110 0,129 0,147 0,166 0,184 0,203 0,221 0,240 0,258 0,277 0,296 0,314 0,333 0,351 A
ef
0,98 0,85 0,72 0,68 0,69 0,63 0,62 0,58 0,52 0,50 0,48 0,49 0,50 0,57 0,56 0,43 0,48 0,55
450 0,041 0,062 0,083 0,104 0,125 0,146 0,167 0,188 0,209 0,230 0,251 0,272 0,293 0,314 0,335 0,357 0,378 0,399 A
ef
0,98 0,77 0,70 0,69 0,63 0,62 0,59 0,52 0,50 0,48 0,50 0,57 0,56 0,43 0,48 0,53 0,54 0,52
500 0,046 0,069 0,093 0,116 0,140 0,164 0,187 0,211 0,234 0,258 0,281 0,305 0,328 0,352 0,375 0,399 0,423 0,446 A
ef
0,98 0,76 0,68 0,65 0,62 0,58 0,52 0,49 0,49 0,50 0,56 0,57 0,44 0,53 0,54 0,52 0,53 0,41
550 0,051 0,077 0,103 0,129 0,155 0,181 0,207 0,233 0,259 0,285 0,311 0,337 0,363 0,389 0,415 0,441 0,467 0,493 A
ef
0,82 0,73 0,69 0,63 0,61 0,52 0,50 0,48 0,50 0,57 0,48 0,48 0,55 0,54 0,45 0,43 0,41 0,40
600 0,056 0,084 0,113 0,141 0,170 0,198 0,227 0,256 0,284 0,313 0,341 0,370 0,398 0,427 0,455 0,484 0,512 0,541 A
ef
0,82 0,71 0,63 0,62 0,58 0,51 0,48 0,50 0,57 0,48 0,50 0,55 0,52 0,53 0,44 0,40 0,39 0,41
650 0,061 0,092 0,123 0,154 0,185 0,216 0,247 0,278 0,309 0,340 0,371 0,402 0,433 0,464 0,495 0,526 0,557 0,588 A
ef
0,83 0,68 0,63 0,61 0,52 0,49 0,73 0,57 0,48 0,50 0,54 0,52 0,43 0,41 0,40 0,38 0,41 0,39
700 0,066 0,099 0,133 0,166 0,200 0,233 0,267 0,300 0,334 0,367 0,401 0,435 0,468 0,502 0,535 0,569 0,602 0,636 A
ef
0,77 0,68 0,62 0,58 0,50 0,48 0,44 0,57 0,50 0,54 0,52 0,43 0,41 0,40 0,43 0,42 0,38 0,35
750 0,071 0,107 0,143 0,179 0,215 0,251 0,287 0,323 0,359 0,395 0,431 0,467 0,503 0,539 0,575 0,611 0,647 0,683 A
ef
0,94 0,69 0,62 0,55 0,50 0,74 0,58 0,43 0,50 0,49 0,48 0,47 0,41 0,43 0,40 0,37 0,35 0,34
800 0,076 0,114 0,153 0,191 0,230 0,268 0,307 0,345 0,384 0,422 0,461 0,499 0,538 0,577 0,615 0,654 0,692 0,731 A
ef
0,73 0,63 0,61 0,52 0,48 0,71 0,57 0,50 0,54 0,53 0,45 0,40 0,43 0,40 0,37 0,35 0,34 0,32
850 0,080 0,121 0,163 0,204 0,245 0,286 0,327 0,368 0,409 0,450 0,491 0,532 0,573 0,614 0,655 0,696 0,737 0,778 A
ef
0,72 0,63 0,58 0,50 0,73 0,57 0,43 0,55 0,52 0,52 0,44 0,43 0,40 0,37 0,35 0,34 0,33 0,30
900 0,085 0,129 0,172 0,216 0,260 0,303 0,347 0,390 0,434 0,477 0,521 0,564 0,608 0,651 0,695 0,738 0,782 0,826 A
ef
0,70 0,63 0,55 0,49 0,50 0,57 0,54 0,54 0,43 0,41 0,38 0,42 0,35 0,34 0,34 0,31 0,29 0,28
950 0,090 0,136 0,182 0,228 0,274 0,321 0,367 0,413 0,459 0,505 0,551 0,597 0,643 0,689 0,735 0,781 0,827 0,873 A
ef
0,68 0,62 0,52 0,48 0,57 0,43 0,55 0,54 0,44 0,40 0,41 0,38 0,35 0,34 0,31 0,29 0,28 0,27
1000 0,095 0,144 0,192 0,241 0,289 0,338 0,387 0,435 0,484 0,532 0,581 0,629 0,678 0,726 0,775 0,823 0,872 0,920 A
ef
0,68 0,62 0,51 0,49 0,57 0,50 0,54 0,43 0,40 0,43 0,40 0,35 0,33 0,32 0,31 0,29 0,28 0,27
1050 0,100 0,151 0,202 0,253 0,304 0,355 0,406 0,457 0,509 0,560 0,611 0,662 0,713 0,764 0,815 0,866 0,917 A
ef
0,69 0,61 0,50 0,74 0,57 0,50 0,52 0,44 0,41 0,41 0,38 0,34 0,33 0,29 0,28 0,28 0,27
1100 0,105 0,159 0,212 0,266 0,319 0,373 0,426 0,480 0,533 0,587 0,641 0,694 0,748 0,801 0,855 0,908 0,962 A
ef
0,68 0,61 0,50 0,44 0,48 0,54 0,53 0,40 0,43 0,39 0,35 0,34 0,30 0,28 0,27 0,27 0,26
1150 0,110 0,166 0,222 0,278 0,334 0,390 0,446 0,502 0,558 0,614 0,670 0,727 0,783 0,839 0,895 0,951 1,007 A
ef
0,69 0,58 0,48 0,57 0,50 0,54 0,52 0,41 0,41 0,38 0,34 0,32 0,29 0,28 0,29 0,28 0,27
1200 0,115 0,174 0,232 0,291 0,349 0,408 0,466 0,525 0,583 0,642 0,700 0,759 0,818 0,876 0,935 0,993 A
ef
0,69 0,55 0,49 0,56 0,50 0,52 0,41 0,38 0,40 0,35 0,34 0,28 0,29 0,29 0,28 0,27
1250 0,120 0,181 0,242 0,303 0,364 0,425 0,486 0,547 0,608 0,669 0,730 0,791 0,852 0,913 0,975 1,036 A
ef
0,63 0,52 0,49 0,57 0,34 0,53 0,40 0,42 0,39 0,34 0,32 0,28 0,27 0,29 0,28 0,27
1300 0,125 0,188 0,252 0,316 0,379 0,443 0,506 0,570 0,633 0,697 0,760 0,824 0,887 0,951 1,014 1,078 A
ef
0,63 0,52 0,74 0,48 0,54 0,52 0,41 0,42 0,35 0,34 0,28 0,29 0,28 0,28 0,27 0,26
1350 0,130 0,196 0,262 0,328 0,394 0,460 0,526 0,592 0,658 0,724 0,790 0,856 0,922 0,988 1,054 A
ef
0,63 0,51 0,71 0,44 0,53 0,44 0,38 0,36 0,35 0,33 0,28 0,27 0,27 0,28 0,26
1400 0,135 0,203 0,272 0,340 0,409 0,477 0,546 0,615 0,683 0,752 0,820 0,889 0,957 1,026 1,094 A
ef
0,62 0,50 0,57 0,50 0,52 0,41 0,41 0,37 0,35 0,29 0,29 0,28 0,28 0,27 0,25
1450 0,140 0,211 0,282 0,353 0,424 0,495 0,566 0,637 0,708 0,779 0,850 0,921 0,992 1,063 A
ef
0,62 0,50 0,55 0,53 0,52 0,44 0,41 0,35 0,34 0,30 0,27 0,27 0,27 0,26
1500 0,145 0,218 0,292 0,365 0,439 0,512 0,586 0,659 0,733 0,807 0,880 0,954 1,027 1,101 A
ef
0,62 0,50 0,56 0,54 0,43 0,41 0,39 0,36 0,34 0,29 0,28 0,27 0,26 0,25
Table of effective cross-sections A
ef
(m
2
) and resistance coefficients () for PL-18-1, PL-18-2
372
FIRE DAMPERS PL-18-1-EI 30, PL-18-2-EI 120; PL-13R-K90 TECHNICAL DATA
Pressure drop and sound power level diagram for PL-13R-K90/S and PL-13R-K90/F
Table of effective cross-sections A
ef
(m
2
) for PL-13R-K90/S and PL-13R-K90/F
PL-13R-K90/F
L=400
Nominal dimension A
ef
(m
2
)
315 0,076
400 0,121
500 0,193
630 0,309
710 0,390
800 0,490
PL-13R-K90/S
L=300
Nominal dimension A
ef
(m
2
)
100 0,006
125 0,010
150 0,015
160 0,017
180 0,022
200 0,028
224 0,036
250 0,045
280 0,057
300 0,065
315 0,072
350 0,092
355 0,094
400 0,121
500 0,190
2
3
4
5
6
7
8
9
10
20
30
40
50
60
70
80
90
100
d (mm)
8
0
0
7
1
0
6
3
0
5
6
0
5
0
0
4
5
0
4
0
0
3
1
5
3
5
5
2
0
0
2
5
0

p

(
P
a
)
Q (m
3
/h)
2
0
0
3
0
0
4
0
0
5
0
0
6
0
0
7
0
0
8
0
0
9
0
0
1
0
0
0
3
0
0
0
4
0
0
0
5
0
0
0
6
0
0
0
7
0
0
0
8
0
0
0
9
0
0
0
1
0
0
0
0
2
0
0
0
0
2
0
0
0
30
35
40
45
50
55
60
65
400
0.02
0.03
0.04
0.05
0.1
0.2
0.3
0.4
0.5
1.0
1000 2000 3000 6000 12000 32000
Q (m
3
/h)
A

(
m
(
m
/
s
)
4
5
6
7
9
1
0
2
)8
Pressure drop and sound power level diagram for PL-18-1, PL-18-2
3
4
5
6
7
8
9
10

1
,0
0
,2
0
,6
0
,4
0
,8


v

(
m
/
s
)
p (Pa)
35
40
45
50
55 60

(
d
B
(
L
W
A
A
)
)
373
FIRE DAMPERS PL-18-1-EI 30, PL-18-2-EI 120; PL-13R-K90 ORDERING KEY
PL - 18 - 1 - EI 30 / A2 / T1 / L B x H
L
D
T1
T2
T12
A
A2
A7
E5
E6
E9
E15
E16
E19
PL-18-1-EI 30
PL-18-2-EI 120
PL-13R-K90/F
PL-13R-K90/S
Left
Right=standard (need not to be stated by ordering)
Limit switch closed
Limit switch open
Limit switch closed, open
Basic type with manual handling - fusible link release (PL-13R-K90)
Basic type with manual handling - fusible link release (PL-18-1-EI 30, PL-18-2-EI 120)
Simplified type with manual handling - fusible link release (PL-18-1-EI 30, PL-18-2-EI 120)
Electric actuator BF 24-T*
Electric actuator BF 230-T*
Electric actuator BF 24-T-st + BKN 230-24*
Electric actuator BLF-24 T*
Electric actuator BLF-230 T*
Electric actuator BLF 24-T-st + BKN 230-24*
rectangular fire damper
circular fire damper with flange
circular fire damper for installation with flange
circular fire damper for installation in spiral-ducts
Ordering key:
* In electric actuator variants, the motor is fitted with limit switches. An electric actuator variant with extra limit switches (T1, T2, T12) is not available.
374
ACTUATORS BF 24-T, BF 230-T,
SPRING RETURN ACTUATORS 90C
Application
Type BF -T spring return actuators are
intended for driving fire dampers in
ventilation and air conditioning systems.
Mode of operation
BF -T actuator moves the damper to its
normal working position while tensioning the
return spring at the same time. If the power supply
is interrupted, the energy stored in the spring
moves the damper back to its safe position.
Thermal fuse Tf1 operates if the ambient
temperature exceeds 72C. Replaceable thermal
fuses Tf2/Tf3 operate if the temperature inside the
duct exceeds 72C. Tf1, Tf2 or Tf3 fuses cause the
power supply to be interrupted permanently so that
it cannot be restored.
Signalling
Two micro switches with fixed settings are installed
in the actuator for indicating the damper end
positions. The position of the damper blade can be
read off on a mechanical position indicator.
Manual operation
The damper can be operated manually and fixed in
any required position. Release of the locking
mechanism can be achieved manually or
automatically by applying the supply voltage.
Wiring Diagram
Note BF 24-T Supply via safety
isolation transformer
Parallel connection of several actuators possible.
Power consumption must be observed!
Note BF 230-T Caution: Main power supply
voltage! A device that disconnects the pole
conductors (minimum contact gap 3 mm)
is required for isolation from the power supply.
S1 S2 S3 S4 S5 S6
<5 <80
2 1
BAE72B-S
Tf1 Tf2 Tf3 LED
Technical data BF 24-T BF 230-T
Nominal voltage 24V AC 50/60 Hz 230 V AC 50/60 Hz
24V DC
Trigger temperature Tf1: duct outside temperature 72C Tf1: duct outside temperature 72C
Thermal fuse Tf2 and Tf3: duct inside temperature 72C Tf2 and Tf3: duct inside temperature 72C
Power consumption
Motoring 7 W 8 W
Holding 2 W 3 W
Power consumption for wire sizing 10VA(Imax 5,8A@5ms) 12,5VA(Imax 500mA@5ms)
Protection class III II
Degree of protection IP 54 IP 54
Auxiliary switch 2 x EPU 6 (3) A, AC 250 V & 2 x EPU 6 (3) A, AC 250 V &
Switching points 5, 80 5, 80
Connecting cable motor 1 m, 2 x 0,75 mm
2
motor 1 m, 2 x 0,75 mm
2
aux. switches 1 m, 6 x 0,75 mm
2
aux. switches 1 m, 6 x 0,75 mm
2
Angle of rotation Max. 95 (incl. 5 spring pretensioning) Max. 95 (incl. 5 spring pretensioning)
Damper connection-mechanical Form-fit 12 mm (10 mm with adapter supplied) Form-fit 12 mm (10 mm with adapter supplied)
Torque motor min. 18 Nm motor min. 18 Nm
spring-return min. 12 Nm spring-return min. 12 Nm
Running time motor 140 s motor 140 s
spring-return 16 s (@t
amb
= 20C) spring-return 16 s (@t
amb
= 20C)
Direction of rotation Selected by mounting L/R Selected by mounting L/R
Position indication Mechanical with pointer Mechanical with pointer
Ambient temperature range - 30 ... + 50C - 30 ... + 50C
Non-operating temperature - 40 ... + 50C - 40 ... + 50C
Ambient humidity According to EN 60730-1 According to EN 60730-1
EMC low-voltage directive CE according to 89/336/EEC and 92/31/EEC, 93/68/ EEC CE according to 89/336/EEC and 92/31/EEC, 93/68/ EEC
Sound power level Motor max. 45 dB (A); spring 62 dB (A) Motor max. 45 dB (A); spring 62 dB (A)
Service life Min. 60.000 safe positions Min. 60.000 safe positions
Maintenance Maintenance - free Maintenance - free
Weight 2800 g 3100 g
ACTUATORS BF 24-T, BF 230-T, SPRING RETURN ACTUATORS 90C
375
ACTUATORS BLF 24-T, BLF 230-T,
SPRING RETURN ACTUATORS 90C
Application
Type BLF -T spring return actuators are
intended for driving fire dampers in
ventilation and air conditioning systems.
Mode of operation
BLF -T actuator moves the damper to its
normal working position while tensioning the
return spring at the same time. If the power supply
is interrupted, the energy stored in the spring
moves the damper back to its safe position.
Thermal fuse Tf1 operates if the ambient
temperature exceeds 72C. Replaceable thermal
fuses Tf2/Tf3 operate if the temperature inside the
duct exceeds 72C. Tf1, Tf2 or Tf3 fuses cause the
power supply to be interrupted permanently so that
it cannot be restored.
Signalling
Two micro switches with fixed settings are
installed in the actuator for indicating the damper
end positions.
The position of the damper blade can be read off
on a mechanical position indicator.
Manual operation
The damper can be operated manually and fixed in
any required position. Release of the locking
mechanism can be achieved manually or
automatically by applying the supply voltage.
BLF 24-T, BLF 230-T
Wiring Diagram
Note BF 24-T Supply via safety
isolation transformer
Parallel connection of several actuators possible.
Power consumption must be observed!
Note BF 230-T Caution: Main power supply
voltage! A device that disconnects the pole
conductors (minimum contact gap 3 mm)
is required for isolation from the power supply.
S1 S2 S3 S4 S5 S6
<5 <80
2 1
BAE72B-S
Tf1 Tf2 Tf3 LED
Technical data BLF 24-T BLF 230-T
Nominal voltage 24V AC 50/60 Hz 230V AC 50/60 Hz
24V DC
Trigger temperature Tf1: duct outside temperature 72C Tf1: duct outside temperature 72C
Thermal fuse Tf2 and Tf3: duct inside temperature 72C Tf2 and Tf3: duct inside temperature 72C
Power consumption
Motoring 5 W 6 W
Holding 2.5 W 3 W
Power consumption for wire sizing 7 VA (lmax 5,8 A @ 5 ms) 7 VA (lmax 150 A @ 10 ms)
Protection class III II
Degree of protection IP 54 IP 54
Auxiliary switches 2 x EPU 6 (1,5) A, AC 250 V & 2 x EPU 6 (1,5) A, AC 250 V &
Switching points 5, 80 5, 80
Connecting cable motor 1 m, 2 x 0,75 mm
2
motor 1 m, 2 x 0,75 mm
2
aux. switches 1 m, 6 x 0,75 mm
2
aux. switches 1 m, 6 x 0,75 mm
2
Angle of rotation Max. 95 (incl. 5 spring pretensioning) Max. 95 (incl. 5 spring pretensioning)
Damper connection-mechanical Form-fit 12 mm (10 mm with adapter supplied) Form-fit 12 mm (10 mm with adapter supplied)
Torque motor min. 6 Nm motor min. 6 Nm
spring-return min. 4 Nm spring-return min. 4 Nm
Running time motor 40 - 75 s (0 ... 6 Nm) motor 40 - 75 s (0 ... 6 Nm)
spring-return 20 s (@t
amb
= 20C) spring-return 20 s (@t
amb
= 20C)
Direction of rotation Selected by mounting L/R Selected by mounting L/R
Position indication Mechanical with pointer Mechanical with pointer
Ambient temperature range - 30 ... + 50C - 30 ... + 50C
Non-operating temperature - 40 ... + 50C - 40 ... + 50C
Ambient humidity According to EN 60730-1 According to EN 60730-1
EMC CE according to 89/336/EEC and 92/31/EEC, 93/68 EEC CE according to 89/336/EEC and 92/31/EEC, 93/68 EEC
Sound power level Motor max. 45 dB (A); spring 62 dB (A) Motor max. 45 dB (A); spring 62 dB (A)
Service life Min. 60.000 safe positions Min. 60.000 safe positions
Maintenance Maintenance - free Maintenance - free
Weight 1630 g 1730 g
ACTUATOR BLF 24-T, BLF 230-T, SPRING RETURN ACTUATORS 90C
COMMUNICATION AND POWER SUPPLY UNIT
BKN 230-24
Application
The BKN 230-24 communication and power supply
unit is intended for use with spring return actuators
BLF24(-T)-ST or BF24(-T)-ST for motorizing fire
dampers. It simplifies the electrical work of installing
the dampers and also facilities onsite testing as well
as allowing local or central control and monitoring
of the fire damper over a simple 2 wire conductor.
Mode of operation
The BKN230-24 also functions as a distribution
power unit for supplying the spring-return actuators
that are connected to it. Another of its functions is to
signal the NORMAL and SAFE positions of the
damper (from the switches in the spring-return
actuators) to the central control panel over a 2-wire
conductor. The same conductor is used for
transmitting the ON/OFF control command from the
control panel to the damper actuator via the
BKN230-24.
Installation and connections
To simplify installation and connection, the spring-
return actuator is fitted with connectors which plug
directly into the BKN230-24 unit. BKN230-24 is
connected to the mains with enclosed cable and
mains Euro-plug, so the unit can be connected to
ordinary socket. The 2-wire conductor is connected
to the terminals 6 and 7. The terminals 1 and 2 are
for the direct connection of thermal trigger or smoke
detectors.
Functional testing
If it is proposed to test the actuator without the
BKS24... unit connected, it can be switched to
NORMAL mode by fitting a jumper between
terminals 3 and 4. The SAFE damper position can
be checked either by pressing the pushbutton
on the BAE72-S unit or by interrupting the power
supply.
Parallel connection
If we must use more than one actuator to drive
oversized fire damper, we can use single 2-wire
conductor so, that we connect two BKN230-24
units in parallel. To do so we use terminal 4 and 5
on first unit (master) and wire it with terminal 6
and 7 on second slave unit.
Note: It is recommended to use BKN 230-24
communication and power supply unit in
conjunction with Control Unit BKS24-9A
Dimensions:
Wiring Diagram
1. Jumper factory-fitted. Can be removed if necessary to be replaced by a thermoelectric trigger.
(The safety function will be triggered if terminals 1 and 2 are not linked).
2. Jumper only used for commissioning purposes and without BKS24-... !
BKN230-24
1
2
3
4
5
6
7
a
b
1)
2)
BF(G)24-T-ST, BF..24-ST
M
Power supply
AC 230 V
2-wire conductor
BAE72-S
Technical Data BKN 230-24
Voltage 230 V AC 50/60 Hz (range 198264 V)
Cable with Euro-plug type 26 0.9 m
For wire sizing 11 VA (incl. spring-return actuator)
Power consumption (NORMAL position) 3.5 W
Ambient temperature range 20... + 50 C
Protection class II (all insulated)
Degree of protection IP 42
Screw terminals (7 pole) 2 x1.5 mm
2
Weight 550 g
5
4
COMMUNICATION AND POWER SUPPLY UNIT BKN 230-24
376
Wiring Diagram
Connection via
safety transformer !
Control
ON (NORMAL) / OFF (SAFE)
Programming-Input
for auxiliary contact K2
Fault K1
group alarm FD 1...9
Common input
Note: Relay contacts K1 and K2 are shown without power applied
Function Contact K1 Programming Auxiliary Contact K2
Alarm
Situation Status
Contact K2 closed, when
all Dampers OPEN (NORMAL)
Contact K2 closed, when
Damper Nr.1 OPEN (NORMAL)
Contact K2 closed, when
all Dampers CLOSED (SAFE)
NO Alarm
Wiring
left open
Function
Auxiliary contact K2
function to be programmed
by appropriate wiring
of terminal 14
377
BELIMO COMMUNICATION AND CONTROL
UNIT BKS24-9A
Control and monitoring of up to 9 motorized fire
dampers in combination with the Communication
and Power Supply Units BKN230-24
Application
The BKS24-9A has been designed for panel
mounting. It signals the operating positions and any
faults from the fire dampers to which it is connected.
A variety of functions are possible with the built-in
auxiliary contacts. e.g. signalling of damper
positions, fault alarm and fan enabling.
Mode of operation
The BKS24-9A unit receives position signals from
the BKN230-24 units and transmits control
commands to them over the 2-wire conductors.
Correct operation of the dampers is indicated by the
2 LEDs:
Control ON = NORMAL Position
Control OFF = SAFE Position
Fault
If the damper does not reach the required position
within the preset time, the appropriate on-board
FAULT LED flashes and, at the same time, the FAULT
contact K1 is activated. This contact is overridden as
soon the defective damper reaches the required
position. The on-board FAULT LED remains on, until
the fault is reset.
Auxiliary contact K2
An auxiliary contact is provided for signalling the
positions of dampers to a higher-level system. The
function of the auxiliary contact can be programmed
via terminal 14 according to the instructions beside.
Installation and connections
The BKS24-9A unit can be clipped directly onto a
35mm DIN mounting rail and external wiring is
connected by two 9-pin terminal connectors.
Functional testing
Functional testing can be performed by pressing the
TEST pushbutton. While this button is held
depressed, the dampers run to the SAFE position.
Any malfunctions are indicated by the internal
FAULT LEDs.
Fire compartments
The required fire compartments must be taken into
account when making the groupings and when
wiring the BKS24-9A unit.
Dimensions
Technical Data BKS 24-9A
Nominal voltage 24 V AC 50/60Hz
Nominal voltage range 21.6...28.8 V AC
For wire sizing 5.5 VA (Imax. 6.4 A @2.5ms)
Power consumption 3.5 W
Electrical connection Terminals for 2 x 1.5 mm2
Lengths of conductors
2-wire-conductors a/b max. 600 m (wire size 0.75 mm2)
control input 13 max. 600 m (wire size 0.75 mm2)
Auxiliary contact AC 24 V @0.5 A
Protection class III safety extra-low voltage
Degree of protection IP 20
Ambient temperature 0...+ 50 C
EMC CE according 89/336/EEC
Mode of operation Type 1 (EN 60730-1)
Maintenance maintenance free
Weight 160 g
BELIMO COMMUNICATION AND CONTROL UNIT BKS24-9A
378
D+90 D+90

D
+
9
0
The fire protection valve is installed directly in a
wall or ceiling. All positions are possible under
condition that the thickness of a concrete wall is
minimum 100 mm or 120 mm for masonry wall
respectively.
Installation
150

D
1

D
2

D
4 3
1 3 2
x
Fire protection valve PPV-K90
Application:
Fire protection valves PPV are used for preventing
the fire from spreading in air conditioning and
ventilating systems. They are installed at crossings
of ventilating ducts through partition walls and
ceilings which divide a building into fire
compartments. When installed in a fire partition
wall, the fire resistance is 90 min, otherwise 60 min
only. It is used for air-in-and outlet. The air flow
quantity can be regulated by a special regulating
system. A thermo link device activates the valve
at 70C and springs shut the air flow and fire
spread through the ventilating ducts is stopped. The
operation of the thermo release device and of the
fire valve can be controlled by pulling out the
central part of the valve. The fire protection valve
has been approved by ZAG Institute (Ljubljana,
Slovenia), by IBS (Institut fr Brandschutztechnik
Linz, Austria) and by LTM (Zagreb, Croatia).
Description:
The fire protection valve PPV consists of an
installation frame (1) and a special inner part (2).
The central part can be pulled out by a special
bayonet pin or the distance can be set towards
housing and thus the air flow quantity can be
adjusted. The size of opening is 10 or 20 mm. The
installation frame and the guiding tube are made of
steel profile (painted in white colour). A shut-off
plate is made of special fire resisting material in
white colour. All inner parts are galvanized and
hence non-corrosive.
Assembly parts
1. Installation frame
2. Inside shut-off part
3. Seal
4. Thermo link device 70 C
Sizes and dimensions
Size D D1 D2
100 98 164 158
125 123 189 183
160 158 224 218
200 198 264 258
FIRE PROTECTION VALVE PPV-K90
379
The minimum fire resistance of the partition wall
should be 90 min. When installing, you should
follow instructions.
Components
1. PPV-K90
2. Insulation
3. Fire resistant gypsum board
4. Self-tapping screws
5. Profile 50x30x1.5 mm
Note:
Only item 1 is supplied.
When installing drill the holes for self-tapping
screws.
Installation in light partition walls:
FIRE PROTECTION VALVE PPV-K90 INSTALLATION
Application in the kitchen Application in toilets
380
300
115+250
30
min.115
3 2 1
Q (m
3
/h)
V
L
(m/s)
p (Pa)
L
wA
(dB)
L (m)
x (mm)
PPV-K90
125
15
FIRE PROTECTION VALVE PPV-K90 TECHNICAL DATA
Adjustment
It is possible to order extension tube, in case
when the wall is thicker than normal.
1. Installation frame
2. Valve
3. Duct
L W
A

(
d
B
)
100
150
200
500 400 300 200 150 100 50
1
2
5
1
2
5
2
50
10
15
20
30
40
30
60
1
0
0
1
0
0
1
40
2
0
0
1
6
0
50
1
6
0
2 1 1
2
0
0
2 2 1
P
r
e
s
s
u
r
e

d
r
o
p

p
t
(
P
a
)
Air flow Q (m
3
/h)

p
t
20

p
t
20
Pressure drop diagram
L(m) L(m)
Q(m
3
/h)
v
L
(m/s)
Inlet charackteristics
500 400 300 200 150 100 50
5
1
2
3
4
6
10
15
20
100
125
160
200
100
125
160
200
T
h
r
o
w

d
i
s
t
a
n
c
e

L

(
m
)
Air flow Q (m
3
/h)
v
L
=0.25 m/s
X=20
X
X=10
Air flow
Maximal velocity O,5 m/s at distance L
Total pressure drop
Sound power level
Throw distance
Width of the opening
Ordering example:
Fire protection valve:
Size:
Pcs:
381
H
B
B+110 40
85
150
H
+
1
3
5
9
0

1 7 9 5 2
Smoke dampers DOL-1R
Application:
Smoke dampers DOL-1R are used in single
compartment configuration to remove smoke and
heat in case of fire. In normal position, the damper
is closed. In case of fire, the smoke damper is
triggered by a signal from fire alarm control panel
or smoke detector that opens the blade, thus
enabling exhaust of smoke and heat. Optional
versions are also release mechanism with thermal
link only or combination of remotely triggered
solenoid plus thermal link. Fire resistance is 90
minutes.
Description:
Smoke damper consists of housing made of
galvanised sheet metal, brass bearings, blade
made of fire resistant material, special seal that
prevents spread of smoke and protection frame
with grille pained in red.
Components:
1. Housing made of galvanised sheet steel
2. Blade made of fire resistant material with special
seal
5. Handle
7. Limit-switch T
9. Solenoid release mechanism-pull type (W)
Fire resistance
90 min certified by ZAG Ljubljana, Slovenia
Dimensions
B 252 318 400 503 634 797 1003 1262
H 252 318 400 503 634 797
SMOKE DAMPERS DOL-1R
N
9
7
230/220V, 50Hz F
Switch in the fire control
central unit
Solenoid
Limit switch T1
on damper
Control lamp
Solenoid- technical data
Nominal voltage: 230/220V/50Hz
Pull type, max. pulse ON time 8 sec
Duty cycle: ED 10%
Max. inrush current: 5A
Min. wire size: 0,75 mm
2
The control lamp may alternatvely be connected to a separate power supply (230V or 24V).
382
H
174
B
B+110
B+170
40
H
+
1
3
5
H
+
1
9
0
9
0

150
85
DOL-1R-W/T B X H
T
W
A
WA
Limit switch
Pull solenoid
Thermo link 70C
Combination- pull solenoid and thermo link
Ordering key:
Basic version:
DOL-1R-A is equipped with the fusible link that
releases at 70C and opens the smoke damper.
Optional limit switch T that signals the blade
position can be added.
Solenoid version:
DOL-1R-W/T operating principle; in case of fire
the smoke damper opens by means of electric
impulse transmitted from the fire alarm control
panel, smoke alarm, etc. It is important that the
electric impulse duration does not exceed 8
seconds, to prevent the burn out of the solenoid
coil. Limit switch has, besides signalising, also
the function of breaking-off the electric impulse in
the moment when damper opens. In normal
position the damper is not under voltage. Closing
of the damper is always manual.
Versions:
DOL-1R-W-T
SMOKE DAMPERS DOL-1R
383
B
63.5
H
H
+
8
0
B+80
3 1 2 4
250
175
6 5
Smoke damper DOL - 1 RK
Application:
Smoke dampers DOL-1RK are used in single
compartment configuration to remove smoke and
heat in case of fire. In normal position, the damper
is closed. In case of fire, the smoke damper is
triggered by a signal from fire alarm control panel
or smoke detector that opens the blade, thus
enabling exhaust of smoke and heat.
Fire resistance is 90 minutes.
Description:
Smoke damper consists of housing made of
galvanised sheet metal, brass bearings, blade
made of fire resistant material, special seal that
prevents spread of smoke.
Components:
1. Housing
2. Blade
3. Electric actuator
4. Linkage mechanism
5. Seal
6. Inspection opening
Fire resistance
90 min certified by ZAG Ljubljana, Slovenia
Dimensions:
B 200 250 300 350 400 450 550 600 650 700 750 800 850 900 950 1000 1050 1100 1150 1200 1250 1300 1350 1400 1450 1500
H 250 300 350 400 450 500 550 600 650 700 750 800
SMOKE DAMPERS DOL-1RK
384
B
B+140
40 40
4
0
H
4
0
H
+
1
4
0
18 L 125 18 125 125
1
8
L

1
2
5
1
8
1
2
5
1
2
5
L

1
2
5
L 125
DOL-1R K / E1/ D
250
175 W
D
E1
E2
K
Junction box
Electric actuator BF 24
Electric actuator BF 230
Duct version
Ordering key:
Installation
The smoke dampers must be installed so, that the
electrical actuator and inspection opening are at
the accessible side of wall or ceiling. In this way
the actuating mechanism and the inside of the
damper can be controlled. The dampers may
be installed in any position. The dampers must be
installed directly into the wall or ceiling of the
same fire resistance as the damper.
Installed damper housing should not be statically
stressed by building's construction.
Mode of operation
Electric actuator moves the blade of smoke damper
to its normal working position "closed", while
tensioning the return spring at the same time.
Damper is triggered by power interruption form fire
alarm control panel or from properly wired smoke
detector. When the damper is in working position
"closed", electric actuator is under electrical power
all the time, when power is cut off the built in
spring automatically moves the damper to safe
position "open". Under normal circumstances i.e.
when there is no fire the damper returns to the
close position automatically when the power
returns. Both limit switches to indicate the
positions CLOSEDand OPEN are incorporated
in the electric actuator and need not to be ordered
separately.
Maintenance
Dirty and humid air is likely to influence the
functional capability of the dampers. Therefore, the
dampers have to be checked twice a year.
DOL-1RK
SMOKE DAMPERS DOL-1RK
385
1 5 2 6 4
7
8
3
40
4
0
4
0
300 B 40
4
0
0
2
9
9
H
260
B+300
Smoke damper DPL-7
Application:
Smoke dampers DPL-7 are used in multi-
compartment configuration to remove smoke and
heat in case of fire. During fire, the smoke damper
can be controllably moved to close or open position,
thus enabling exhaust of smoke and heat.
Regulation must be done via fire alarm control panel
with redundant power supply.
Description:
Smoke dampers DPL-7 consist of housing made of
galvanised sheet metal, blade made of fire resistant
material, brass bearings, insulation cover box for
electric actuator and other parts. As for drive,
electric actuators Belimo (type BE or BLE) are
used.
Mode of operation:
Electric actuators used for smoke dampers DPL-7
operate according to "open"/"closed" principle.
Manufacturer guarantees, that smoke dampers can
be controllably opened or closed within 30 minutes
after the fire outburst.
Fire resistance and classification
Smoke damper DPL-7 has fire resistance K-90
(NORM M 7625).
Certified according to Austrian standard NORM
H 6029:
In Slovenia certified by ZAG Ljubljana.
Components
1. Housing
2. Blade
3. Bearing
4. Motor cover
5. Electric actuator BE..
6. Electric cable E30 (not supplied with damper)
7. BKNE 230-24
8. Junction box
Nominal dimensions:
B 200 250 300 350 400 450 550 600 650 700 750 800 850 900 950 1000 1050 1100 1150 1200 1250 1300 1350 1400 1450 1500
H 250 300 350 400 450 500 550 600 650 700 750 800
SMOKE DAMPERS DPL-7
Length L= 300
DPL-7 actuators BE..(E21, E22, E23)
386
SMOKE DAMPERS DPL-7
B+300
300
B
B+65
265
H
H
+
6
5
2
2
0
3
0
0
2 3 1 5 4 7 6
8
2
2
0
8
0
200
550 500 450 400 350 300 250 200 150
1000
950
900
850
800
750
700
650
600
550
500
450
400
350
300
250
200
BxH
DPL-7 actuators BLE..(E25, E26, E27)
The range of applicability for BLE actuators (designations: E25, E26, E27)
Components
1. Housing
2. Blade
3. Bearing
4. Motor cover
5. Electric actuator BLE..
6. Electric cable E30 (not supplied with damper)
7. BKNE 230-24
8. Junction box
387
SMOKE DAMPERS DPL-7
B+145
B+380
275
40
H
+
1
4
5
4
0
4
4
0
40
B+380
H
+
1
4
5
4
0
4
4
0
345
H
+
6
5
H
B+300
B+65
B
235
1
0
0
3
0
0
4
0
0
1
0
0
3
0
0
4
0
0
B+300
B+65
B
235
H
+
6
5
H
3
4
0
1
4
0
B+145
B+380
275
40
H
+
1
4
5
4
0
3
4
0
40
B+380
H
+
1
4
5
4
0
3
4
0
345
H
+
6
5
H
B+300
B+65
B
235
8
0
2
2
0
3
0
0
8
0
2
2
0
3
0
0
B+300
B+65
B
235
H
+
6
5
H
3
0
0
1
2
0
DPL-7 installation-actuators BE...(E21,E22,E23)
DPL-7 installation-actuators BLE...(E25,E26,E27)
Smoke dampers DPL-7 must be installed directly
into the wall or ceiling of the same fire resistance
as the damper. Installed damper housing should
not be statically stressed by building's
construction. The electric power cable leading from
the motor cover into the room shall have fire
resistance E30. The hole for E30 cable is to be
drilled through the cover at the time of installation.
Warning
Standard type smoke dampers are not allowed to
be installed in the explosion hazardous spaces. It
is also not allowed to install the standard type
smoke dampers in ventilating devices which lead
away the mixture of air and explosion gasses.
Other instructions for installation are available in
"Installation instructions for safe use, maintenance,
testing and installation of dampers".
Maintenance
Dirty and humid air is likely to influence the
functional capability of the dampers. Therefore, the
dampers have to be checked regularly as follows:
All types of dampers should be completely
checked twice a year. If two successive tests
show no defects, it is sufficient to perform
further tests only once a year.
Dampers equipped with electrical actuators,
triggered by the button or switch in the control
room are to be checked four times a year.
120 W
388
DPL-7 / E21 / DO B x H
DO
E21
E22
E23
E25
E26
E27
DPL-7
Junction box
Electric actuator Belimo BE 24-12-ST+BKNE 230-24
Electric actuator Belimo BE 24-12
Electric actuator Belimo BE 230-12
Electric actuator Belimo BLE 24-12-ST+BKNE 230-24
Electric actuator Belimo BLE 24-12
Electric actuator Belimo BLE 230-12
Smoke damper type
Ordering key:
SMOKE DAMPERS DPL-7
389
SMOKE DAMPERS DOL-3-1
Smoke dampers DOL-3-1
Application:
Smoke dampers DOL-3-1 are used in single
compartment configuration to remove smoke and
heat in case of fire. In normal position, the damper
is closed. In case of fire, the smoke damper is
triggered by a signal from fire alarm control panel
or smoke detector that opens the blade, thus
enabling exhaust of smoke and heat.
Fire resistance of smoke dampers DOL-3-1 is E120.
Description:
Smoke damper consists of housing made of
galvanised sheet metal, brass bearings, blade
made of galvanised sheet metal, special seal that
prevents spread of smoke and protection frame
with grille pained in RAL 9010 white colour.
Components
1. Housing made of galvanised sheet metal
2. Blade made of galvanised sheet metal with
special sealing
5. Handle
6. Seal
7. Limit-switch T
8. Solenoid release mechanism-pull type (W)
9. Grille
Fire resistance
E 120 attested by VNIPO, Moscow
Solenoid- technical data
Nominal voltage: 230/220V/50Hz
Pull type, max. pulse ON time 8 sec
Duty cycle: ED 10%
Max. inrush current: 5A
Min. wire size: 0,75 mm2
Versions
DOL 3-1 W/T
A-A
165 30
H

+

1
3
7
9 2 5
A
A
B
B + 90
H
H

+

9
0
1 7 8 6
Limit switch T1
on damper
Switch in the fire control
central unit
Solenoid Control lamp
230/220 V, 50Hz F
View shown without grille
The control lamp may alternatively be connected
to a separate power supply (230V or 24 V).
390
SMOKE DAMPERS DOL-3-1
Solenoid version:
DOL-3-1 operating principle; in case of fire the
smoke damper opens by means of electric impulse
transmitted from the fire alarm control panel,
smoke alarm, etc. It is important that the electric
impulse duration does not exceed 8 seconds, to
prevent the burn out of the solenoid coil. Limit
switch has, besides signalising, also the function
of breaking-off the electric impulse in the moment
when damper opens. In normal position the
damper is not under voltage. Closing of the
damper is always manual.
Versions
DOL 3-1 W/T
Table of nominal dimensions DOL-3-1 W/T
B + 190
165 30
B + 90
B
H

+

1
9
0
H

+

9
0
H
H

+

1
3
7
BxH 200 250 300 350 400 450 500 550 600 650 700 750 800 850 900 950 1000
150
200
250
300
350
400
450
500
550
600
650
700
750
800
850
900
950
1000
1050
1100
1150
1200
1250
1300
1350
1400
1450
1500
391
SMOKE DAMPERS DOL-3-1
A-A
9
H

+

1
3
7
165 30
2
H H

+

9
0
B
B + 90
A
A
1 3 4 6
Components
1. Housing made of galvanised sheet metal
2. Blade made of galvanised sheet metal with
special sealing
3. Electric actuator
4. Linkage mechanism
6. Seal
9. Grille
Fire resistance
E 120 attested by VNIPO, Moscow
Installation
The smoke dampers must be installed so, that the
electrical actuator and inspection opening are at
the accessible side of wall or ceiling. In this way
the actuating mechanism and the inside of the
damper can be controlled. The dampers may be
installed in any position. The dampers must be
installed directly into the wall or ceiling of the
same fire resistance as the damper.
Installed damper housing should not be statically
stressed by building's construction.
Mode of operation
Electric actuator moves the blade of smoke damper
to its normal working position "closed", while
tensioning the return spring at the same time.
Damper is triggered by power interruption form
fire alarm control panel or from properly wired
smoke detector. When the damper is in working
position "closed", electric actuator is under
electrical power all the time, when power is cut off
the built in spring automatically moves the damper
to safe position "open". Under normal
circumstances i.e. when there is no fire the damper
returns to the close position automatically when
the power returns. Both limit switches to indicate
the positions CLOSEDand OPEN are
incorporated in the electric actuator and need not
to be ordered separately.
Versions
DOL 3-1 E..
H

+

1
3
7
165 30
H
H

+

9
0
B
B + 90
H

+

1
9
0
B + 190
392
SMOKE DAMPERS DOL-3-1
Dimensional range for electric actuator BF (E1, E2)
Dimensional range for electric actuator BLF (E11, E12)
Table of nominal dimensions DOL-3-1 E..
BxH 300 350 400 450 500 550 600 650 700 750 800 850 900 950 1000
300
350
400
450
500
550
600
650
700
750
800
850
900
950
1000
1050
1100
1150
1200
1250
1300
1350
1400
1450
1500
DOL 3-1 W/T B x H
T
W
E1
E2
E11
E12
Limit switch
Pull solenoid 230/220V, 50Hz
Electric actuator BF 24*
Electric actuator BF 230*
Electric actuator BLF 24*
Electric actuator BLF 230*
Ordering key:
* In electric actuator variants, the motor is fitted with limit switches. An electric actuator variant with extra limit switches (T1, T2, T12) is not available.
393
SMOKE DAMPERS DOL-3-2
Smoke dampers DOL-3-2
Application:
Smoke dampers DOL-3-2 are used in single
compartment configuration to remove smoke and
heat in case of fire. In normal position, the damper
is closed. In case of fire, the smoke damper is
triggered by a signal from fire alarm control panel
or smoke detector that opens the blade, thus
enabling exhaust of smoke and heat.
Fire resistance of smoke dampers DOL-3-2 is E120.
Description:
Smoke damper consists of housing made of
galvanised sheet metal, brass bearings, blade
made of galvanised sheet metal and special seal
that prevents spread of smoke.
Components
1. Housing made of galvanised sheet metal
2. Blade made of galvanised sheet metal with
special sealing
5. Handle
6. Seal
7. Limit-switch T
8. Solenoid release mechanism-pull type (W)
Fire resistance
E 120 attested by VNIPO, Moscow
Solenoid- technical data
Nominal voltage: 230/220V/50Hz
Pull type, max. pulse ON time 8 sec
Duty cycle: ED 10%
Max. inrush current: 5A
Min. wire size: 0,75 mm
2
DOL 3-2
Versions
DOL 3-2 W/T
A-A
H

+

6
5
2 5
A
A
B
B + 65
H
H

+

6
5
1 7 8 6
200
Limit switch T1
on damper
Switch in the fire control
central unit
Solenoid Control lamp
230/220 V, 50Hz F
The control lamp may alternatively be connected
to a separate power supply (230V or 24 V).
394
SMOKE DAMPERS DOL-3-2
Solenoid version:
DOL-3-2 operating principle; in case of fire, the
smoke damper opens by means of electric impulse
transmitted from the fire alarm control panel,
smoke alarm, etc. It is important that the electric
impulse duration does not exceed 8 seconds, to
prevent the burn out of the solenoid coil. Limit
switch has, besides signalising, also the function
of breaking-off the electric impulse in the moment
when damper opens. In normal position the
damper is not under voltage. Closing of the
damper is always manual.
Versions
DOL 3-2 W/T
Table of nominal dimensions DOL-3-2 W/T
W
200
H
H
+
6
5
B
B+65
H
+
1
4
0
B+140
BxH 200 250 300 350 400 450 500 550 600 650 700 750 800 850 900 950 1000
150
200
250
300
350
400
450
500
550
600
650
700
750
800
850
900
950
1000
1050
1100
1150
1200
1250
1300
1350
1400
1450
1500
395
SMOKE DAMPERS DOL-3-2
H
H

+

6
5
A
A
B
B + 65
1 3 4
A-A
200
2 6
Components
1. Housing made of galvanised sheet metal
2. Blade made of galvanised sheet metal with
special sealing
3. Electric actuator
4. Linkage mechanism
6. Seal
Fire resistance
E 120 attested by VNIPO, Moscow
Installation
The smoke dampers must be installed so, that the
electrical actuator and inspection opening are at
the accessible side of wall or ceiling. In this way
the actuating mechanism and the inside of the
damper can be controlled. The dampers may be
installed in any position. The dampers must be
installed directly into the wall or ceiling of the
same fire resistance as the damper.
Installed damper housing should not be statically
stressed by building's construction.
Mode of operation
Electric actuator moves the blade of smoke damper
to its normal working position "closed", while
tensioning the return spring at the same time.
Damper is triggered by power interruption form
fire alarm control panel or from properly wired
smoke detector. When the damper is in working
position "closed", electric actuator is under
electrical power all the time, when power is cut off
the built in spring automatically moves the damper
to safe position "open". Under normal
circumstances i.e. when there is no fire the damper
returns to the close position automatically when
the power returns. Both limit switches to indicate
the positions CLOSEDand OPEN are
incorporated in the electric actuator and need not
to be ordered separately.
Versions
DOL 3-2 E..
W
200
H
H

+

6
5
B
B + 65
H

+

1
4
0
B + 140
W
(mm)
= + 40 mm
Wall thickness (mm)
2
396
SMOKE DAMPERS DOL-3-2
Dimensional range for electric actuator BF (E1, E2)
Dimensional range for electric actuator BLF (E11, E12)
Table of nominal dimensions DOL-3-2 E..
BxH 300 350 400 450 500 550 600 650 700 750 800 850 900 950 1000
300
350
400
450
500
550
600
650
700
750
800
850
900
950
1000
1050
1100
1150
1200
1250
1300
1350
1400
1450
1500
DOL 3-2 W/T B x H
T
W
E1
E2
E11
E12
Limit switch
Pull solenoid 230/220V, 50Hz
Electric actuator BF 24*
Electric actuator BF 230*
Electric actuator BLF 24*
Electric actuator BLF 230*
Ordering key:
* In electric actuator variants, the motor is fitted with limit switches. An electric actuator variant with extra limit switches (T1, T2, T12) is not available.
397
SMOKE DAMPERS PL-18-3-EI 30, E 120; PL-18-4-EI 120, E 120
Smoke dampers PL-18-3, PL-18-4
duct versions
Application:
Smoke dampers PL-18-3, PL-18-4 are used in
single compartment configuration to remove
smoke and heat in case of fire. In normal
position, the damper is closed. In case of fire,
the smoke damper is triggered by a signal from
fire alarm control panel or smoke detector that
opens the blade, thus enabling exhaust of
smoke and heat.
Description:
Smoke damper consists of housing made of
galvanised sheet metal, brass bearings, blade
made of fire resistant material and special seal
that prevents spread of smoke.
Nominal dimensions smoke dampers PL-18-3, PL-18-4
BxH
150
200
250
300
350
400
450
500
550
600
650
700
750
800
850
900
950
1000
1050
1100
1150
1200
1250
1300
1350
1400
1450
1500
150 200 250 300 350 400 450 500 550 600 650 700 750 800 850 900 950 1000
398
SMOKE DAMPERS PL-18-3-EI 30, E 120; PL-18-4-EI 120, E 120
PL-18-3-EI 30, E 120/E11
PL-18-4-EI 120,E 120/E2
Components:
1. Housing made of galvanised sheet metal
2. Blade made of fire resistant material with
special sealing
4. Inspection opening
9. Electric actuator
Fire resistance:
EI 30, E 120 attested by VNIPO, Moscow
EI 120, E 120 attested by VNIPO, Moscow
325
1 2
9
325
1 2
9
B
1
1
5
115
32.5 32.5
4
H
3
2
.
5
3
2
.
5
9
9
H
3
2
.
5
3
2
.
5
B
1
1
5
115
32.5 32.5
4
399
SMOKE DAMPERS PL-18-3-EI 30, E 120; PL-18-4-EI 120, E 120
PL-18-3-EI 30 / E1 / L BxH
L
D
E1
E2
E11
E12
PL-18-3-EI 30, E 120
PL-18-4-EI 120, E 120
L
205 W
B+190
B
1
1
5
H
1 15
H
+
1
2
0
32.5 32.5
BxH 150 200 250 300 350 400 450 500 550
200
250
300
350
400
450
500
550
600
650
700
750
800
850
900
950
1000
Left
Right=standard (need not to be stated by ordering)
Electric actuator BF 24*
Electric actuator BF 230*
Electric actuator BLF 24*
Electric actuator BLF 230*
Rectangular smoke dampers
Rectangular smoke dampers
Ordering key:
Installation
The smoke dampers must be installed so, that
the electrical actuator and inspection opening
are at the accessible side of wall or ceiling. In
this way the actuating mechanism and the inside
of the damper can be controlled. The dampers
may be installed in any position. The dampers
must be installed directly into the wall or ceiling
of the same fire resistance as the damper.
Installed damper housing should not be
statically stressed by building's construction.
Mode of operation
Electric actuator moves the blade of smoke damper
to its normal working position "closed", while
tensioning the return spring at the same time.
Damper is triggered by power interruption form
fire alarm control panel or from properly wired
smoke detector. When the damper is in working
position "closed", electric actuator is under
electrical power all the time, when power is cut off
the built in spring automatically moves the damper
to safe position "open". Under normal
circumstances i.e. when there is no fire the damper
returns to the close position automatically when
the power returns. Both limit switches to indicate
the positions CLOSEDand OPEN are
incorporated in the electric actuator and need not
to be ordered separately.
Maintenance
Dirty and humid air is likely to influence the
functional capability of the dampers. Therefore,
the dampers have to be checked twice a year.
PL-18-3-EI 30, E 120/E11
The range of applicability for BLF actuators (designations E11, E12)
400
ACTUATORS BF 24, BF 230, SPRING RETURN ACTUATORS 90C
ACTUACTORS BF 24, BF 230,
SPRING RETURN ACTUATORS 90C
Application
Type BF spring return actuators are intended
for driving smoke dampers in single compartment
exhaust ventilation systems.
Mode of operation
BLF -T actuator moves the damper to its
normal working position while tensioning the
return spring at the same time. If the power supply
is interrupted, the energy stored in the spring
moves the damper back to its safe position.
Signalling
Two micro switches with fixed settings are
installed in the actuator for indicating the damper
end positions.
The position of the damper blade can be read off
on a mechanical position indicator.
Manual operation
The damper can be operated manually and fixed in
any required position. Release of the locking
mechanism can be achieved manually or
automatically by applying the supply voltage.
Electrical accessories for BF 24
BAE72 B(-S) Thermoelectric Triggering Device
(with test button).
BF 24, BF 230
Wiring Diagram
Note BF 24-T Supply via safety
isolation transformer
Parallel connection of several actuators possible.
Power consumption must be observed!
Optional
Note BF 230-T Caution: Main power supply
voltage! A device that disconnects the pole
conductors (minimum contact gap 3 mm)
is required for isolation from the power supply.
S1 S2 S3 S4 S5 S6
<5 <80
2 1
BAE72B-S
Tf1 Tf2 Tf3 LED
Technical data BF 24 BF 230
Nominal voltage 24V AC 50/60 Hz 230V AC 50/60 Hz
24V DC
Power consumption
Motoring 7 W 8 W
Holding 2 W 3 W
Power consumption for wire sizing 10VA(Imax 8,3A@5ms) 12,5VA(Imax 500mA@5ms)
Protection class III II
Degree of protection IP 54 IP 54
Auxiliary switch 2 x EPU 6 (3) A, 250 V & 2 x EPU 6 (3) A, 250 V &
Switching points 5, 80 5, 80
Connecting cable motor 1 m, 2 x 0,75 mm
2
motor 1 m, 2 x 0,75 mm
2
aux. switches 1 m, 6 x 0,75 mm
2
aux. switches 1 m, 6 x 0,75 mm
2
Angle of rotation Max. 95 (incl. 5 spring pretensioning) Max. 95 (incl. 5 spring pretensioning)
Damper connection-mechanical Form-fit 12 mm (10 mm with adapter supplied) Form-fit 12 mm (10 mm with adapter supplied)
Torque motor Min. 18 Nm motor Min. 18 Nm
spring - return Min. 12 Nm spring - return Min. 12 Nm
Running time motor 140 s motor 140 s
spring - return 16 s (@t
amb
= 20C) spring - return 16 s (@t
amb
= 20C)
Direction of rotation Selected by mounting L/R Selected by mounting L/R
Position indication Mechanical with pointer Mechanical with pointer
Ambient temperature range - 30 ... + 50C - 30 ... + 50C
Non-operating temperature - 40 ... + 50C - 40 ... + 50C
Ambient humidity According to EN 60730-1 According to EN 60730-1
EMC CE according to 89/336/EEC and 92/31/EEC, 93/68/ EEC CE according to 89/336/EEC and 92/31/EEC, 93/68/ EEC
Sound power level Motor max. 45 dB (A); spring 62 dB (A) Motor max. 45 dB (A); spring 62 dB (A)
Service life Min. 60.000 safe positions Min. 60.000 safe positions
Maintenance Maintenance free Maintenance free
Weight 2800 g 3100 g
401
ACTUATORS BLF 24, BLF 230, SPRING RETURN ACTUATORS 90C
BF 24, BF 230
Wiring Diagram
Note BF 24-T Supply via safety
isolation transformer
Parallel connection of several actuators possible.
Power consumption must be observed!
Optional
Note BF 230-T Caution: Main power supply
voltage! A device that disconnects the pole
conductors (minimum contact gap 3 mm)
is required for isolation from the power supply.
S1 S2 S3 S4 S5 S6
<5 <80
2 1
BAE72B-S
Tf1 Tf2 Tf3 LED
Technical data BLF 24 BLF 230
Nominal voltage 24V AC 50/60 Hz 230V AC 50/60 Hz
24V DC
Power consumption
Motoring 5 W 6 W
Holding 2,5 W 3 W
Power consumption for wire sizing 7 VA (lmax 5,8 A @ 5 ms) 7 VA (lmax 150 mA @ 5 ms)
Protection class III II
Degree of protection IP 54 IP 54
Auxiliary switch 2 x EPU 6 (1,5) A, AC 250 V & 2 x EPU 6 (1,5) A, AC 250 V &
Switching points 5, 80 5, 80
Connecting cable motor 1 m, 2 x 0,75 mm
2
motor 1 m, 2 x 0,75 mm
2
aux. switches 1 m, 6 x 0,75 mm
2
aux. switches 1 m, 6 x 0,75 mm
2
Angle of rotation Max. 95 (incl. 5 spring pretensioning) Max. 95 (incl. 5 spring pretensioning)
Damper connection-mechanical Form-fit 12 mm (10 mm with adapter supplied) Form-fit 12 mm (10 mm with adapter supplied)
Torque motor min. 6 Nm motor min. 6 Nm
spring-return min. 4 Nm spring-return min. 4 Nm
Running time motor 40 - 75 s (0 ... 6 Nm) motor 40 - 75 s (0 ... 6 Nm)
spring-return 20 s (@t
amb
= 20C) spring-return 20 s (@t
amb
= 20C)
Direction of rotation Selected by mounting L/R Selected by mounting L/R
Position indication Mechanical with pointer Mechanical with pointer
Ambient temperature range - 30 ... + 50C - 30 ... + 50C
Non-operating temperature - 40 ... + 50C - 40 ... + 50C
Ambient humidity According to EN 60730-1 According to EN 60730-1
EMC CE according to 89/336/EEC and 92/31/EEC, 93/68 EEC CE according to 89/336/EEC and 92/31/EEC, 93/68 EEC
Sound power level Motor max. 45 dB (A); spring 62 dB (A) Motor max. 45 dB (A); spring 62 dB (A)
Service life Min. 60.000 safe positions Min. 60.000 safe positions
Maintenance Maintenance - free Maintenance - free
Weight 1540 g 1730 g
ACTUATORS BLF 24, BLF 230,
SPRING RETURN ACTUATORS 90C
Application
Type BLF spring return actuators are intended
for driving smoke dampers in single compartment
exhaust ventilation systems.
Mode of operation
BLF .. actuator moves the damper to its normal
working position while tensioning the return
spring at the same time. If the power supply is
interrupted, the energy stored in the spring moves
the damper back to its safe position.
Signalling
Two micro switches with fixed settings are
installed in the actuator for indicating the damper
end positions.
The position of the damper blade can be read off
on a mechanical position indicator.
Manual operation
The damper can be operated manually and fixed in
any required position. Release of the locking
mechanism can be achieved manually or
automatically by applying the supply voltage.
Electrical accessories for BLF 24
BAE72 B(-S) Thermoelectric Triggering Device (with
test button).
402
Note BE 24-Supply via safety
isolation transformer
2 - wire system
Wiring diagram
Note BE 230 Caution: Main power supply voltage!
A device that disconnects the pole conductors
(minimum contact gap 3 mm) is required for isolation
from the power supply.
Parallel connection of several actuators possible.
Power consumption must be observed!
ELECTRIC ACTUATORS FOR SMOKE DAMPERS BE 24-12, BE 230-12
ELECTRIC ACTUATORS FOR SMOKE
DAMPERS BE 24-12, BE 230-12
Application
Actuators are intended for driving multi-
compartment smoke dampers in smoke exhaust
systems.
Mode of operation
Open/Close control is effected by means of a 2-
wire system. The actuator is overload-proof and
therefore remains energized while stationary at the
end-stops.
Signalling
Two micro switches with fixed settings are
installed in the actuator for indicating the damper
end positions.
The position of the damper blade can be read off
on a mechanical position indicator.
Manual operation
With enclosed wrench.
Standards and specifications
The design of the actuator is based on the following
standards and specifications:
Draft DIN 18232, Part 6, Sept. 1992
Preliminary standard NORM H 6029, May 1997
Ventilation systems
Fire smoke extraction systems
Extracts from:
CEN/TC191, 1996
prEN12101-8
Technical data BE 24-12 BE 230-12
Nominal voltage 24V AC 50/60 Hz 230 V AC50/60 Hz
24V DC
Nominal voltage range AC 19.2 ... 28.8 V / DC 21.6 ... 28.8 V AC 198 ... 264 V
Power consumption for wire sizing 18VA(Imax 8,2A @ 5ms) 15 VA(Imax 7,9 @ @5ms)
Power consumption
Motoring 12W 8W
Holding 0,5W 0,5W
Connecting cable motor 1 m, 2 x 0,75 mm2 motor 1 m, 2 x 0,75 mm2
aux. switches 1 m, 6 x 0,75 mm
2
aux. switches 1 m, 6 x 0,75 mm
2
Auxiliary switches 2 x EPU 6 (3) A, AC250 V 2 x EPU 6 (3) A, AC250 V
Switching points 3, 87 3, 87
Angle of rotation Max. 100 Max. 100
Damper connection-mechanical Form-fit 12 mm Form-fit 12 mm
Torque 40 Nm 40 Nm
Direction of rotation Selected by mounting L/R Selected by mounting L/R
Running time <60 s for 90 <60 s for 90
Position indication Mechanical with pointer Mechanical with pointer
Protection class III II
Degree of protection IP 54 IP 54
Ambient temperature range - 30 ... + 50C - 30 ... + 50C
Non-operating temperature - 40 ... + 50C - 40 ... + 50C
Ambient humidity According to EN 60730-1 According to EN 60730-1
EMC low-voltage directive CE according to 89/336/EEC and 92/31/EEC, 93/68 EEC CE according to 89/336/EEC and 92/31/EEC, 93/68 EEC
Weight 2700 g 2700 g
403
ELECTRIC ACTUATORS FOR SMOKE DAMPERS BLE 24-12, BLE 230-12
Note BE 24-Supply via safety
isolation transformer
2 - wire system
Wiring diagram
Note BE 230 Caution: Main power supply voltage!
A device that disconnects the pole conductors
(minimum contact gap 3 mm) is required for isolation
from the power supply.
Parallel connection of several actuators possible.
Power consumption must be observed!
BLE230, BLE24
ELECTRIC ACTUATORS FOR SMOKE
DAMPERS BLE 24-12, BLE 230-12
Application
Actuators are intended for driving multi-
compartment smoke dampers in smoke exhaust
systems.
Mode of operation
Open/Close control is effected by means of a 2-
wire system. The actuator is overload-proof and
therefore remains energized while stationary at the
end-stops.
Signalling
Two micro switches with fixed settings are
installed in the actuator for indicating the damper
end positions.
The position of the damper blade can be read off
on a mechanical position indicator.
Manual operation
With enclosed wrench.
Standards and specifications
The design of the actuator is based on the following
standards and specifications:
Draft DIN 18232, Part 6, Sept. 1992
Preliminary standard NORM H 6029, May 1997
Ventilation systems
Fire smoke extraction systems
Extracts from:
prEN1366-10
prEN12101-8
Technical data BE 24-12 BE 230-12
Nominal voltage 24V AC 50/60 Hz 230 V AC50/60 Hz
24V DC
Nominal voltage range AC 19.2 ... 28.8 V / DC 21.6 ... 28.8 V AC 198 ... 264 V
Power consumption for wire sizing 9VA(Imax 2,7A @ 5ms) 12 VA(Imax 6A @ 5ms)
Power consumption
Motoring 7,5W 5W
Holding 0,5W 0,5W
Connecting cable motor 1 m, 2 x 0,75 mm2 motor 1 m, 2 x 0,75 mm2
aux. switches 1 m, 6 x 0,75 mm
2
aux. switches 1 m, 6 x 0,75 mm
2
Auxiliary switches 2 x EPU 6 (3) A, AC250 V 2 x EPU (3) A, AC250 V
Switching points 3, 87 3, 87
Angle of rotation Max. 105 Max. 105
Damper connection-mechanical Form-fit 12 mm Form-fit 12 mm
Torque 15 Nm 15 Nm
Direction of rotation Selected by mounting L/R Selected by mounting L/R
Running time <30 s for 90 <30 s for 90
Position indication Mechanical with pointer Mechanical with pointer
Protection class III II
Degree of protection IP 54 IP 54
Ambient temperature range - 30 ... + 50C - 30 ... + 50C
Non-operating temperature - 40 ... + 50C - 40 ... + 50C
Ambient humidity According to EN 60730-1 According to EN 60730-1
EMC low-voltage directive CE according to 89/336/EEC and 92/31/EEC, 93/68 EEC CE according to 89/336/EEC and 92/31/EEC, 93/68 EEC
Weight 1680 g 1680 g
404
Wiring diagram
LED Status Function
yellow
yellow
yellow

yellow
green
green
flashing light damper moving to OPEN
flashing at double frequency fault
dark power failure
steady light damper open
flashing light damper moving to CLOSED
steady light damper closed
or green
+ green


AC 230 V
7
1
2
3
4
5
6
BE(G)24-ST, BE24-12-ST
b
a
Nothing must
be assigned
to terminals
1 to 5
The device contains no
parts which can be
replaced or repaired by
the user.
2-wire conductor to BKSE24-6
BKNE230-24
M
COMMUNICATION AND POWER SUPPLY UNIT BKNE230-24
4
.
5
4
3
153
5
140
130
8
8
5
4
4
5
Temperature(C)
100
50
0
-10 0 10 20 30
Time (min.)
Dimensions
COMMUNICATION AND POWER SUPPLY UNIT
BKNE230-24
Description
The BKNE230-24 is a separate power supply unit
for BE24-ST BLE24-ST smoke extraction damper
actuators. It also serves as a communications
interface between the actuators and BKSE24-6
control and monitoring unit.
Communication / Command memory
The BKNE230-24 signals the damper position OPEN
/ CLOSED (from switches on the actuator) and any
fault alarms to the BKSE24-6 unit. It also receives
positioning commands from the control unit and
triggers the actuator to the required position. The
last control command is retained throughout
temporary power failures. (The factory setting is
Close damper command stored in the memory).
Monitoring
The BKNE230-24 unit monitors the positions
of the switches on the actuator, its running time
and the exchange of data with the control and
monitoring unit. It also monitors the actuator
current and the power supply.
Signalling
The power supply unit incorporates two LEDs
to signal its functional status.
Installation and connection
In order to make installation as simple as possible
the smoke extraction damper actuators
...-ST are fitted with plug connectors that can
be inserted directly into the BKNE230-24 unit.
The 2-wire conductor must be connected to
screw terminals 6 and 7.
Note
It is recommended that a fire alarm
signal cable suitable for the application be
used for the 2-wire conductor. It is essential
to ensure the correct polarity.
Safety function
The safety function is guaranteed within the
temperature range shown in the diagram
below which is based on standard NORM
H 6029 and DIN 18232.
Measurements at actuator (protected by thermal
insulation)
Technical data BKNE230-24
Voltage 230 V AC 50/60 Hz
Nominal voltage range 198...264 V AC
For wire sizing 19 VA (with actuator)
Power consumption 10 W (with actuator)
Connections
mains lead 1 m long (halogen free, without plug)
actuator 6-pin plug, 3-pin plug
*2-wire connector screw terminals for wire 2 x 1.5 mm
2
Recommended cable JE-H (St) Bd FE180/E30-E90
Protection class II (all-insulated)
normal operation 30...+50C
storage 40...+80C
EMC CE according to 89/336/EEC
Low Voltage Directive CE according to 73/23/EEC
Mode of operation type 1 (EN 60730-1)
Software class A (EN 60730-1)
Maintenance maintenance-free
Weight 680 g
405
Wiring diagram
Delay 0 s (Fan)
COM
Delay 60 s (Fan)
OPEN
SMOKE EXTRACTION
AUTO
CEASE
SMOKE EXTRACTION
CLOSED
* Fault (Error)
* Inverted output: fault = contact open
Connect through
safety transformer
Input 1 Input 2
(isolated)
COMMUNICATION AND CONTROL UNIT BKSE24-6
COMMUNICATION AND CONTROL UNIT
BKSE24-6
Application
The BKSE24-6 unit is designed for mounting in
equipment cabinets and indicates operating status
and fault signals for the smoke extraction dampers
that are linked to it. The auxiliary contacts that are
incorporated also allow functions to be signalled
or passed on to higher level control systems.
Mode of operation
The signals from the BKNE230-24 unit are received
by the BKSE24-6 unit and evaluated individually. All
BKNE230-24 units are triggered simultaneously.
Communication is via the 2-wire conductor. Correct
operation of the dampers is indicated by means of
two LEDs. Faults are also indicated by the same LED
and the corresponding fault LED.
Control
There are two control options for the BKSE24-6 unit:
Input 1 (terminal 10) controlled through a switch or
pushbutton. The commands for SMOKE
EXTRACTION (terminals 10/12) or CEASE SMOKE
EXTRACTION (terminals 10/11) are handled with
This option is Priority 1 and is intended for direct
control with main fire switch.
Input 2 (terminals 8/9) controlled through a higher-
level system.
The command for SMOKE EXTRACTION is handled
with Priority 2 and is only implemented when Input 1
is positioned to AUTO (terminal 10 open).
Command memory
The last control command is retained throughout
temporary power failures.
INIT
In the event of a fault, a self-test can be initiated by
pressing the SET/INIT pushbutton. be connected to
screw terminals 6 and 7.
Fault memory
Faults remain stored in the BKSE24-6 unit until the
dampers have performed a complete trouble-free
cycle.
Factory settings
The BKSE24-6 unit is programmed at the factory for
6 smoke extraction dampers. The control command
CEASE SMOKE EXTRACTION is also stored in the
memory.
Installation and connection
The BKSE24-6 unit can be clipped directly to a 35
mm DIN mounting rail and connected by means of
two 9-pole plug-in terminals. It is recommended that
a fire alarm signal cable suitable for the application
be used for the 2- wire conductor.
Smoke extraction zoning
The zoning arrangements required for the smoke
extraction system can be set up by forming
groups and by wiring the BKSE24-6 unit
appropriately.
Dimensions
Technical data BKSE230-24
Voltage AC 24 V 50/60 Hz
Nominal voltage range AC 19.2...28.8 V
For wire sizing 5.5 VA (Imax. 6.4 A @2.5 ms)
Power consumption 3.5 W
Input 1 (Priority 1)
- extract smoke link terminals 10-12
- cease smoke extraction link terminals 10-11
- Auto input open (basic position)
- signal duration tmin = 1 s
- input impedance R(terminals10-11) = 66 k_; R(terminals10-12) = 66 k_
Input 2 (Priority 2) terminals 8 + 9 (isolated from input 1)
- input level DC U(high) = DC 18...30 V; U(low) < DC 12 V
- input current DC I = 5 0.5 mA
- input level AC U(high) = AC 16...30 V; U(low) < AC 8 V
- input current AC I = 2.5 0.5 mA
- signal duration tmin = 0.5 s
Connections terminals for wire 2 x 1.5 mm
2
Conductor lengths
2-wire conductor a/b max. 600 m (wire 0.75 mm
2
)
control input max. 600 m (wire 0.75 mm
2
)
Recommended cable Type Fire alarm signal cable 2 x 0.8 mm
2
JE-H (St) Bd FE180/E30-E90
Recommended cable JE-H (St) Bd FE180/E30-E90
Auxiliary contacts AC 24 V, 0.5 A
Protection class III Safety extra-low voltage
Degree of protection IP20
Mode of operation type 1 (EN 60730-1)
Software class A (EN 60730-1)
EMC CE according to 89/336/EEC
Maintenance maintenance-free
Weight 160 g
406
CERTIFICATES
Fire Certificate of
Description Type resistance (min) Classification Endorsed countries authorized organisation
Slovenia, Austria, Croatia, ZAG, IBS, LTM,
Rectangular fire damper PL-12 60 ali 90 K60 ali K90 Serbia, Romania, Hungary IMS, CTPC, EMI
Rectangular fire damper PL-15 120 EI 120 S Slovenia, Poland, Ukraine, Romania ZAG, ITB, MOE, CTPC
Rectangular fire damper PL-18-1 30 EI 30 Russia VNIPO
Rectangular fire damper PL-18-1* 120 EI 120 Serbia IMS
Rectangular fire damper PL-18H 120 K120 Croatia LTM
Rectangular fire damper PL-18-2 120 EI 120 Russia VNIPO
Slovenia, Austria, Croatia, ZAG, IBS, LTM, IMS,
Circular fire damper PL13 90 K90 Serbia, Romania, Hungary CTPC, EMI
Slovenia, Austria, Croatia, ZAG, IBS, LTM, IMS,
Circular fire damper PL-14 90 K90 Serbia, Romania, Hungary CTPC, EMI
Circular fire damper PL13R 90 EI 90 Russia VNIPO
Slovenia, Poland, ZAG, ITB, MOE, CTPC
Circular fire damper PL-16 120 EI 120 S Ukraine, Romania
Circular fire damper PL-17 120 EI 120 S Slovenia, Poland, Romania ZAG, ITB, CTPC
Fire valve PPV-K90 90 K90 Slovenia, Austria, Croatia ZAG, IBS, LTM
Smoke damper- single compartment DOL-1R 90 K 90 Slovenia ZAG
Smoke damper- single compartment DOL-1RK 90 K90 Slovenia, Serbia ZAG, IMS
Slovenia, Austria, ZAG, IBS, CTPC, EMI
Smoke damper- multi compartment DPL-7 90 K90 Romania, Hungary
Smoke damper- single compartment PL-18-3 30, 120 EI 30, E 120 Russia, Serbia VNIPO, IMS
Smoke damper- single compartment PL-18-4 120 EI 120, E 120 Russia VNIPO
Smoke damper- single compartment DOL-3-1 120 E 120 Russia VNIPO
Smoke damper- single compartment DOL-3-2 120 E 120 Russia VNIPO
* Special model, not included in main catalogue, request for special information.
Products in Ex version are also available, for further information, contact our sales department.
Note: only part of all certificates is shown, for detailed information contact our sales department.
Tested and certified fire resistance of all components.
The right for technical changes reserved.