PROJ ECT NAME : PROVISION OF DETAILED DESIGN SERVICES

FOR THAI BINH DEVELOPMENT PROJECT,


BLOCKS 102 & 106, OFFSHORE VIETNAM
DOCUMENT TITLE : DATASHEET FOR AIR-CONDITIONER
DOCUMENT NO.

CONTRACT NO.

CTR NO.
:

:
:
TBDP-A-E-DS-0104

PCV/TBDP- A/2011/702

D-EL-400











REV CODE
ISSUE
DATE
DOC
STATUS
CONTRACTOR
COMPANY
ACCEPTANCE
AUTHOR CHECKER APPROVER
NAME NAME NAME NAME DATE
A 21-01-14 IFR HNT Quang NM Thao Andrew Hoang
0 17-03-14 AFC HNT Quang NM Thao Andrew Hoang



Document Class: B - Confidential (Should only be shared with staff or contractors who have a need-to-know)
Client Name: PETRONAS Carigali Overseas Sdn Bhd (PCOSB)
Datasheet No. : TBDP-A-E-DS-0104
Revision No. : 0
Specification No:
Proj ect: Page No. : 1 of 10
Equipment Name: Fan coil Unit
Equipment Tag No.: FCU-01A/01B
Location: Thai Binh Drilling Wellhead Platform, i.e. TBDP-A, Offshore Vietnam
1
Quantity 2 (1 duty, 1standby)
2
Description Fan coil unit+Built-in thermostat
3
Service Instrument room
4
Manufacturer / Model No. *
5
Unit Type Wall mounted type
6
Cabinet Material Manufacturer's Standard
7
Overall Dimensions (L x W x H mm) 940 x 275 x 199/*
8
Weight (Kg) 10/*
9
Total Supply Air (L/S) , minimum 223
10 Cooling Capacity :
11
Sensible heat (kWR), minimum *
12 Total heat (kWR), minimum
13 Area Classification Safe area
14
Base Frame Material Manufacturer's Standard
15
Noise Level (dBA) @ 1 m (low/high) 44/47
16
Capacity (L/s), minimum *
17
External Discharge Pressure (Pa) *
18
Volume Control Device *
19
RPM (Max. 1450) 1300/*
20 Mounting *
21 Electrical Characteristic 230V/1Pha/50Hz
22 Fan Motor Absorbed Power (W) 30/*
23
Fan Motor Rating (W) *
24 Material Manufacturer's Standard
PROVISION OF DETAILED DESIGN SERVICES FOR
THAI BINH DEVELOPMENT PROJECT, BLOCKS 102 & 106,
OFFSHORE VIETNAM
5.3
25
EVAPORATOR COIL
26
Air On-Coil C DB/WB *
27
Air Off-Coil C DB/WB *
28
Coil Face Velocity (m/s) 2.5 MAX.
29
No. of Rows 3/*
30 No. Fins per inch (FPI) *
31 FILTER
32 Manufacturer / Model No. *
33 Type / Material Washable / *
34
Filter Size *
35
Filter Efficiency 85% min
36
Filter Face Velocity (m/s) 2.5 MAX.
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53 * VENDOR TO COMPLETE
54
55
56
57
58
0 17-03-14 AFC HNT Quang NMThao Andrew Hoang
A 21-01-14 IFR HNT Quang NMThao Andrew Hoang
0
COMPANY ACCEPTANCE ACCEPTANCE DATE
CONTRACTOR
REV ISSUE DATE DOC. STATUS
AUTHOR CHECKER APPROVER
Client Name: PETRONAS Carigali Overseas Sdn Bhd (PCOSB)
Datasheet No. : TBDP-A-E-DS-0104
Revision No. : 0
Specification No:
Proj ect: Page No. : 2 of 10
Equipment Name: Fan coil Unit
Equipment Tag No.: FCU-02A/02B
Location: Thai Binh Drilling Wellhead Platform, i.e. TBDP-A, Offshore Vietnam
1
Quantity 2 (1 duty, 1standby)
2
Description Fan coil unit+Built-in thermostat
3
Service Electrical room
4
Manufacturer / Model No. *
5
Unit Type Wall mounted type
6
Cabinet Material Manufacturer's Standard
7
Overall Dimensions (L x W x H mm) 940 x 275 x 199/*
8
Weight (Kg) 10/*
9
Total Supply Air (L/S) , minimum 223
10 Cooling Capacity :
11
Sensible heat (kWR), minimum *
12 Total heat (kWR), minimum
13 Area Classification Safe area
14
Base Frame Material Manufacturer's Standard
15
Noise Level (dBA) @ 1 m (low/high) 44/47
16
Capacity (L/s), minimum *
17
External Discharge Pressure (Pa) *
18
Volume Control Device *
19
RPM (Max. 1450) 1300/*
20 Mounting *
21 Electrical Characteristic 230V/1Pha/50Hz
22 Fan Motor Absorbed Power (W) 30/*
23
Fan Motor Rating (W) *
24 Material Manufacturer's Standard
5.3
PROVISION OF DETAILED DESIGN SERVICES FOR
THAI BINH DEVELOPMENT PROJECT, BLOCKS 102 & 106,
OFFSHORE VIETNAM
0
0
25
EVAPORATOR COIL
26
Air On-Coil C DB/WB *
27
Air Off-Coil C DB/WB *
28
Coil Face Velocity (m/s) 2.5 MAX.
29
No. of Rows 3/*
30 No. Fins per inch (FPI) *
31 FILTER
32 Manufacturer / Model No. *
33 Type / Material Washable / *
34
Filter Size *
35
Filter Efficiency 85% min
36
Filter Face Velocity (m/s) 2.5 MAX.
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53 * VENDOR TO COMPLETE
54
55
56
57
58
A 21-01-14 IFR HNT Quang NMThao Andrew Hoang
0 17-03-14 AFC HNT Quang NMThao Andrew Hoang
APPROVER
COMPANY ACCEPTANCE ACCEPTANCE DATE
CONTRACTOR
REV ISSUE DATE DOC. STATUS
AUTHOR CHECKER
Client Name: PETRONAS Carigali Overseas Sdn Bhd (PCOSB)
Datasheet No. : TBDP-A-E-DS-0104
Revision No. : 0
Specification No:
Proj ect: Page No. : 3 of 10
Equipment Name: Fan Coil Unit
Equipment Tag No.: FCU-03A/03B
Location: Thai Binh Drilling Wellhead Platform, i.e. TBDP-A, Offshore Vietnam
1
Quantity 2 (1 duty, 1standby)
2
Description Fan coil unit+Built-in thermostat
3
Service Battery room
4
Manufacturer / Model No. *
5
Unit Type Wall mounted type
6
Cabinet Material Manufacturer's Standard
7
Overall Dimensions (L x W x H mm) 790 x 275 x 195/*
8
Weight (Kg) 8.4/*
9
Total Supply Air (L/S) , minimum 162
10 Cooling Capacity :
11
Sensible heat (kWR), minimum *
12 Total heat (kWR), minimum
13 Area Classification Zone 1, Group IIC, T3
14
Base Frame Material Manufacturer's Standard
15
Noise Level (dBA) @ 1 m (low/high) 44/47
16
Capacity (L/s), minimum *
17
External Discharge Pressure (Pa) *
18
Volume Control Device *
19
RPM (Max. 1450) 1300/*
20 Mounting *
21 Electrical Characteristic 230V/1Pha/50Hz
22 Fan Motor Absorbed Power (W) 30/*
23
Fan Motor Rating (W) *
24 Material Manufacturer's Standard
PROVISION OF DETAILED DESIGN SERVICES FOR
THAI BINH DEVELOPMENT PROJECT, BLOCKS 102 & 106,
OFFSHORE VIETNAM
3.70
0
25
EVAPORATOR COIL
26
Air On-Coil C DB/WB *
27
Air Off-Coil C DB/WB *
28
Coil Face Velocity (m/s) 2.5 MAX.
29
No. of Rows 3/*
30 No. Fins per inch (FPI) *
31 FILTER
32 Manufacturer / Model No. *
33 Type / Material Washable / *
34
Filter Size *
35
Filter Efficiency 85% min
36
Filter Face Velocity (m/s) 2.5 MAX.
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53 * VENDOR TO COMPLETE
54
55
56
57
58
A 21-01-14 IFR HNT Quang NMThao Andrew Hoang
0 Andrew Hoang 17-03-14 AFC HNT Quang NMThao
REV ISSUE DATE DOC. STATUS
AUTHOR CHECKER APPROVER
COMPANY ACCEPTANCE ACCEPTANCE DATE
CONTRACTOR
Client Name: PETRONAS Carigali Overseas Sdn Bhd (PCOSB)
Datasheet No. : TBDP-A-E-DS-0104
Revision No. : 0
Specification No:
Proj ect: Page No. : 4 of 10
Equipment Name: Fan Coil Unit
Equipment Tag No.: FCU-04
Location: Thai Binh Drilling Wellhead Platform, i.e. TBDP-A, Offshore Vietnam
1
Quantity 1
2
Description Fan coil unit+Built-in thermostat
3
Service Shelter room
4
Manufacturer / Model No. *
5
Unit Type Wall mounted type
6
Cabinet Material Manufacturer's Standard
7
Overall Dimensions (L x W x H mm) 790 x 275 x 195/*
8
Weight (Kg) 8.4/*
9
Total Supply Air (L/S) , minimum 162
10 Cooling Capacity :
11
Sensible heat (kWR), minimum *
12 Total heat (kWR), minimum
13 Area Classification Safe zone
14
Base Frame Material Manufacturer's Standard
15
Noise Level (dBA) @ 1 m (low/high) 44/47
16
Capacity (L/s), minimum *
17
External Discharge Pressure (Pa) *
18
Volume Control Device *
19
RPM (Max. 1450) 1300/*
20 Mounting *
21 Electrical Characteristic 230V/1Pha/50Hz
22 Fan Motor Absorbed Power (W) 30/*
23
Fan Motor Rating (W) *
24 Material Manufacturer's Standard
3.70
PROVISION OF DETAILED DESIGN SERVICES FOR
THAI BINH DEVELOPMENT PROJECT, BLOCKS 102 & 106,
OFFSHORE VIETNAM
25
EVAPORATOR COIL
26
Air On-Coil C DB/WB *
27
Air Off-Coil C DB/WB *
28
Coil Face Velocity (m/s) 2.5 MAX.
29
No. of Rows 3/*
30 No. Fins per inch (FPI) *
31 FILTER
32 Manufacturer / Model No. *
33 Type / Material Washable / *
34
Filter Size *
35
Filter Efficiency 85% min
36
Filter Face Velocity (m/s) 2.5 MAX.
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53 * VENDOR TO COMPLETE
54
55
56
57
58
A 21-01-14 IFR HNT Quang NMThao Andrew Hoang
0 17-03-14 AFC HNT Quang NMThao Andrew Hoang
0
APPROVER
COMPANY ACCEPTANCE ACCEPTANCE DATE
CONTRACTOR
REV ISSUE DATE DOC. STATUS
AUTHOR CHECKER
Client Name: PETRONAS Carigali Overseas Sdn Bhd (PCOSB)
Datasheet No. : TBDP-A-E-DS-0104
Revision No. : 0
Specification No:
Proj ect: Page No. : 5 of 10
Equipment Name: Air Cooled Condenser Unit
Equipment Tag No.: ACCU-01A/01B
Location: Thai Binh Drilling Wellhead Platform, i.e. TBDP-A, Offshore Vietnam
1 Quantity 2 (1 duty, 1 standby)
2
Description Air Cooled Condenser Unit
3
Service Instrument room
4
Manufacturer/Model No. *
5
Type Direct Expansion Air Cooled
6
Casing Material SS 316L
7
Overall Dimensions (L x W x H mm) 780 x 540 x 250/*
8
Dry Weight (Kg)
35/*
9
Operating Weight (Kg)
*
10 Total Cooling Capacity (KwR) 5.3
11
Unit Classification Safe zone
12 Casing Thickness ( mm ) 1.5
13 Noise Level ( dBA ) @ 1 M 58
14
Refrigerant Receiver NOTE ( 2 )
15
COMPRESSOR
16
Type *
17
Manufacturer/Model No. *
18
No. off Compressor
1
19
Refrigerant Type (CFC free type) R407C or equivalent
20 Operating Charge Refrigerant (Kg) *
21 Lubricating Oil (L) *
22 Saturated Suction Temp (C) *
23
Saturated Discharge Temp (C) *
24 No. of Cycle *
PROVISION OF DETAILED DESIGN SERVICES FOR
THAI BINH DEVELOPMENT PROJECT, BLOCKS 102 & 106,
OFFSHORE VIETNAM
25
Capacity Reduction Method *
26
Capacity Reduction (%) *
27
Net Refrigeration Capacity (Kw) *
28
Total Absorbed Power (Kw) 1.5/*
29
Total Rated Power (Kw) *
30 Electrical Characteristic (V/Phase/H) 230V/ 1Phase/50Hz
31 Mounting ( NOTE 3) / *
32 COIL
33 Manufacturer/Model No. *
34
Coil / Fin Material Copper / Cooper (Treated with anti-corrosion coating)
35
No. of Rows
2
36
No. of Fins per inch (FPI) *
37
Condensing Temp (C) *
38 Air Inlet Temp (C) 36/*
39 Total Heat Rejection (Kw) *
40 Coil Design Pressure ( Pa ) *
41 CONDENSING FANS
42 Type of Fan Permanent split capacitor
43 No. & Size of Fans 2/*
44 Air Volume (L/S) *
45 Fan Motor Absorbed Power (w) *
46 Fan Motor Rating (w) *
47 Impeller Material Polyamide Glass Reinforced (PAGAS)
48 Cowl Material *
49 Mounting 95% Anti vib mounts
50
51
52
53 * VENDOR TO COMPLETE
54 NOTE ( 1 ) : VENDOR SHALL FURNISH EQUIPMENT NOISE DATA & COMPLY TO REQUIREMENTS AS PER SPECS
55 NOTE ( 2 ) : VENDOR SHALL BE RESPONSIBLE TO SIZE & PROVIDE RECIEVER TO STORE ALL REFRIGERANT IN THE SYSTEM DURING
56 PIPING PUMP DOWN CYCLE.
57 NOTE ( 3 ) : VIBRATION ISOLATORS SHALL PROVIDE 95% ANTI VIBRATION ISOLATION AT COMPRESSOR RUNNING SPEED.
58
A 21-01-14 IFR HNT Quang NMThao Andrew Hoang
0 17-03-14 AFC HNT Quang NMThao Andrew Hoang
0
APPROVER
COMPANY ACCEPTANCE ACCEPTANCE DATE
CONTRACTOR
REV ISSUE DATE DOC. STATUS
AUTHOR CHECKER
Client Name: PETRONAS Carigali Overseas Sdn Bhd (PCOSB)
Datasheet No. : TBDP-A-E-DS-0104
Revision No. : 0
Specification No:
Proj ect: Page No. : 6 of 10
Equipment Name: Air Cooled Condenser Unit
Equipment Tag No.: ACCU-02A/02B
Location: Thai Binh Drilling Wellhead Platform, i.e. TBDP-A, Offshore Vietnam
1 Quantity 2 (1 duty, 1 standby)
2
Description Air Cooled Condenser Unit
3
Service Electrical room
4
Manufacturer/Model No. *
5
Type Direct Expansion Air Cooled
6
Casing Material SS 316L
7
Overall Dimensions (L x W x H mm) 780 x 540 x 250/*
8
Dry Weight (Kg)
35/*
9
Operating Weight (Kg)
*
10 Total Cooling Capacity (KwR) 5.3
11
Unit Classification Safe zone
12 Casing Thickness ( mm ) 1.5
13 Noise Level ( dBA ) @ 1 M 58
14
Refrigerant Receiver NOTE ( 2 )
15
COMPRESSOR
16
Type *
17
Manufacturer/Model No. *
18
No. off Compressor
1
19
Refrigerant Type (CFC free type) R407C or equivalent
20 Operating Charge Refrigerant (Kg) *
21 Lubricating Oil (L) *
22 Saturated Suction Temp (C) *
23
Saturated Discharge Temp (C) *
24 No. of Cycle *
PROVISION OF DETAILED DESIGN SERVICES FOR
THAI BINH DEVELOPMENT PROJECT, BLOCKS 102 & 106,
OFFSHORE VIETNAM
25
Capacity Reduction Method *
26
Capacity Reduction (%) *
27
Net Refrigeration Capacity (Kw) *
28
Total Absorbed Power (Kw) 1.5/*
29
Total Rated Power (Kw) *
30 Electrical Characteristic (V/Phase/H) 230V/ 1Phase/50Hz
31 Mounting ( NOTE 3) / *
32 COIL
33 Manufacturer/Model No. *
34
Coil / Fin Material Copper / Cooper (Treated with anti-corrosion coating)
35
No. of Rows
2
36
No. of Fins per inch (FPI) *
37
Condensing Temp (C) *
38 Air Inlet Temp (C) 36/*
39 Total Heat Rejection (Kw) *
40 Coil Design Pressure ( Pa ) *
41 CONDENSING FANS
42 Type of Fan Permanent split capacitor
43 No. & Size of Fans 2/*
44 Air Volume (L/S) *
45 Fan Motor Absorbed Power (w) *
46 Fan Motor Rating (w) *
47 Impeller Material Polyamide Glass Reinforced (PAGAS)
48 Cowl Material *
49 Mounting 95% Anti vib mounts
50
51
52
53 * VENDOR TO COMPLETE
54 NOTE ( 1 ) : VENDOR SHALL FURNISH EQUIPMENT NOISE DATA & COMPLY TO REQUIREMENTS AS PER SPECS
55 NOTE ( 2 ) : VENDOR SHALL BE RESPONSIBLE TO SIZE & PROVIDE RECIEVER TO STORE ALL REFRIGERANT IN THE SYSTEM DURING
56 PIPING PUMP DOWN CYCLE.
57 NOTE ( 3 ) : VIBRATION ISOLATORS SHALL PROVIDE 95% ANTI VIBRATION ISOLATION AT COMPRESSOR RUNNING SPEED.
58
NMThao
NMThao
AFC
HNT Quang
HNT Quang
Andrew Hoang
Andrew Hoang 17-03-14
21-01-14 IFR A
0
0
0
CONTRACTOR
AUTHOR CHECKER APPROVER
COMPANY ACCEPTANCE ACCEPTANCE DATE REV DOC. STATUS ISSUE DATE
Client Name: PETRONAS Carigali Overseas Sdn Bhd (PCOSB)
Datasheet No. : TBDP-A-E-DS-0104
Revision No. : 0
Specification No:
Proj ect: Page No. : 7 of 10
Equipment Name: Air Cooled Condenser Unit
Equipment Tag No.: ACCU-03A/03B
Location: Thai Binh Drilling Wellhead Platform, i.e. TBDP-A, Offshore Vietnam
1 Quantity 2 (1 duty, 1 standby)
2
Description Air Cooled Condenser Unit
3
Service Battery room
4
Manufacturer/Model No. *
5
Type Direct Expansion Air Cooled
6
Casing Material SS 316L
7
Overall Dimensions (L x W x H mm) 700 x 540 x 250/*
8
Dry Weight (Kg)
28/*
9
Operating Weight (Kg)
*
10 Total Cooling Capacity (KwR) 3.7
11
Unit Classification Safe zone
12 Casing Thickness ( mm ) 1.5
13 Noise Level ( dBA ) @ 1 M 58
14
Refrigerant Receiver NOTE ( 2 )
15
COMPRESSOR
16
Type *
17
Manufacturer/Model No. *
18
No. off Compressor
1
19
Refrigerant Type (CFC free type) R407C or equivalent
20 Operating Charge Refrigerant (Kg) *
21 Lubricating Oil (L) *
22 Saturated Suction Temp (C) *
23
Saturated Discharge Temp (C) *
24 No. of Cycle *
PROVISION OF DETAILED DESIGN SERVICES FOR
THAI BINH DEVELOPMENT PROJECT, BLOCKS 102 & 106,
OFFSHORE VIETNAM
25
Capacity Reduction Method *
26
Capacity Reduction (%) *
27
Net Refrigeration Capacity (Kw) *
28
Total Absorbed Power (Kw) 1.5/*
29
Total Rated Power (Kw) *
30 Electrical Characteristic (V/Phase/H) 230V/ 1Phase/50Hz
31 Mounting ( NOTE 3) / *
32 COIL
33 Manufacturer/Model No. *
34
Coil / Fin Material Copper / Cooper (Treated with anti-corrosion coating)
35
No. of Rows
2
36
No. of Fins per inch (FPI) *
37
Condensing Temp (C) *
38 Air Inlet Temp (C) 36/*
39 Total Heat Rejection (Kw) *
40 Coil Design Pressure ( Pa ) *
41 CONDENSING FANS
42 Type of Fan Permanent split capacitor
43 No. & Size of Fans 2/*
44 Air Volume (L/S) *
45 Fan Motor Absorbed Power (w) *
46 Fan Motor Rating (w) *
47 Impeller Material Polyamide Glass Reinforced (PAGAS)
48 Cowl Material *
49 Mounting 95% Anti vib mounts
50
51
52
53 * VENDOR TO COMPLETE
54 NOTE ( 1 ) : VENDOR SHALL FURNISH EQUIPMENT NOISE DATA & COMPLY TO REQUIREMENTS AS PER SPECS
55 NOTE ( 2 ) : VENDOR SHALL BE RESPONSIBLE TO SIZE & PROVIDE RECIEVER TO STORE ALL REFRIGERANT IN THE SYSTEM DURING
56 PIPING PUMP DOWN CYCLE.
57 NOTE ( 3 ) : VIBRATION ISOLATORS SHALL PROVIDE 95% ANTI VIBRATION ISOLATION AT COMPRESSOR RUNNING SPEED.
58
A 21-01-14 IFR HNT Quang NMThao Andrew Hoang
0 Andrew Hoang 17-03-14 AFC HNT Quang NMThao
0
0
REV ISSUE DATE DOC. STATUS
AUTHOR CHECKER APPROVER
COMPANY ACCEPTANCE ACCEPTANCE DATE
CONTRACTOR
Client Name: PETRONAS Carigali Overseas Sdn Bhd (PCOSB)
Datasheet No. : TBDP-A-E-DS-0104
Revision No. : 0
Specification No:
Proj ect: Page No. : 8 of 10
Equipment Name: Air Cooled Condenser Unit
Equipment Tag No.: ACCU-04
Location: Thai Binh Drilling Wellhead Platform, i.e. TBDP-A, Offshore Vietnam
1 Quantity 1
2
Description Air Cooled Condenser Unit
3
Service Shelter room
4
Manufacturer/Model No. *
5
Type Direct Expansion Air Cooled
6
Casing Material SS 316L
7
Overall Dimensions (L x W x H mm) 700 x 540 x 250/*
8
Dry Weight (Kg)
28/*
9
Operating Weight (Kg)
*
10 Total Cooling Capacity (KwR) 3.7
11
Unit Classification Safe zone
12 Casing Thickness ( mm ) 1.5
13 Noise Level ( dBA ) @ 1 M 58
14
Refrigerant Receiver NOTE ( 2 )
15
COMPRESSOR
16
Type *
17
Manufacturer/Model No. *
18
No. off Compressor
1
19
Refrigerant Type (CFC free type) R407C or equivalent
20 Operating Charge Refrigerant (Kg) *
21 Lubricating Oil (L) *
22 Saturated Suction Temp (C) *
23
Saturated Discharge Temp (C) *
24 No. of Cycle *
PROVISION OF DETAILED DESIGN SERVICES FOR
THAI BINH DEVELOPMENT PROJECT, BLOCKS 102 & 106,
OFFSHORE VIETNAM
25
Capacity Reduction Method *
26
Capacity Reduction (%) *
27
Net Refrigeration Capacity (Kw) *
28
Total Absorbed Power (Kw) 1.5/*
29
Total Rated Power (Kw) *
30 Electrical Characteristic (V/Phase/H) 230V/ 1Phase/50Hz
31 Mounting ( NOTE 3) / *
32 COIL
33 Manufacturer/Model No. *
34
Coil / Fin Material Copper / Cooper (Treated with anti-corrosion coating)
35
No. of Rows
2
36
No. of Fins per inch (FPI) *
37
Condensing Temp (C) *
38 Air Inlet Temp (C) 36/*
39 Total Heat Rejection (Kw) *
40 Coil Design Pressure ( Pa ) *
41 CONDENSING FANS
42 Type of Fan Permanent split capacitor
43 No. & Size of Fans 2/*
44 Air Volume (L/S) *
45 Fan Motor Absorbed Power (w) *
46 Fan Motor Rating (w) *
47 Impeller Material Polyamide Glass Reinforced (PAGAS)
48 Cowl Material *
49 Mounting 95% Anti vib mounts
50
51
52
53 * VENDOR TO COMPLETE
54 NOTE ( 1 ) : VENDOR SHALL FURNISH EQUIPMENT NOISE DATA & COMPLY TO REQUIREMENTS AS PER SPECS
55 NOTE ( 2 ) : VENDOR SHALL BE RESPONSIBLE TO SIZE & PROVIDE RECIEVER TO STORE ALL REFRIGERANT IN THE SYSTEM DURING
56 PIPING PUMP DOWN CYCLE.
57 NOTE ( 3 ) : VIBRATION ISOLATORS SHALL PROVIDE 95% ANTI VIBRATION ISOLATION AT COMPRESSOR RUNNING SPEED.
58
A 21-01-14 IFR HNT Quang NMThao Andrew Hoang
0 17-03-14 AFC HNT Quang NMThao Andrew Hoang
0
APPROVER
COMPANY ACCEPTANCE ACCEPTANCE DATE
CONTRACTOR
REV ISSUE DATE DOC. STATUS
AUTHOR CHECKER
Client Name: PETRONAS Carigali Overseas Sdn Bhd (PCOSB)
Datasheet No. : TBDP-A-E-DS-0104
Revision No. : 0
Specification No:
Proj ect: Page No. : 9 of 10
Equipment Name: Exhaust Fan
Equipment Tag No.: EF-01A/01B
Location: Thai Binh Drilling Wellhead Platform, i.e. TBDP-A, Offshore Vietnam
1
Quantity
2 (1 duty, 1 standby)
2
Description Exhaust Air Fan
3
Service Battery room
4
Manufacturer/Model No. *
5
Type/Drive Wall mounted type
6
Material Manufacturer's Standard
7
Capacity (L/S) 90
8
Ext. Static Pressure (Pa) 50/*
9
Volume Control Device *
10 RPM (max 1450) 900/*
11
Mounting *
12 Anti Spark Design *
13 Electrical Characteristic 230V/ 1Phase/50Hz
14
Fan Motor Rating (Kw) *
15
Fan Motor Absorbed Power (Kw)
16
Area Classification Zone 1, Group IIC, T3
17
Insulation class F
18
Operating Temp class B
19
20
21
22
23
24
PROVISION OF DETAILED DESIGN SERVICES FOR
THAI BINH DEVELOPMENT PROJECT, BLOCKS 102 & 106,
OFFSHORE VIETNAM
0.15/*
0
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53 * VENDOR TO COMPLETE
54
55
56
57
58
A 21-01-14 IFR HNT Quang NMThao Andrew Hoang
0 Andrew Hoang 17-03-14 AFC HNT Quang NMThao
REV ISSUE DATE DOC. STATUS
AUTHOR CHECKER APPROVER
COMPANY ACCEPTANCE ACCEPTANCE DATE
CONTRACTOR
Client Name: PETRONAS Carigali Overseas Sdn Bhd (PCOSB)
Datasheet No. : TBDP-A-E-DS-0104
Revision No. : 0
Specification No:
Proj ect: Page No. : 10 of 10
Equipment Name: Exhaust Fan
Equipment Tag No.: EF-02
Location: Thai Binh Drilling Wellhead Platform, i.e. TBDP-A, Offshore Vietnam
1
Quantity
1
2
Description Exhaust Air Fan
3
Service Shelter room
4
Manufacturer/Model No. *
5
Type/Drive Wall mounted type
6
Material Manufacturer's Standard
7
Capacity (L/S) 90
8
Ext. Static Pressure (Pa) 50/*
9
Volume Control Device *
10 RPM (max 1450) 900/*
11
Mounting *
12 Anti Spark Design *
13 Electrical Characteristic 230V/ 1Phase/50Hz
14
Fan Motor Rating (Kw) *
15
Fan Motor Absorbed Power (Kw)
16
Area Classification Safe zone
17
Insulation class F
18
Operating Temp class B
19
20
21
22
23
24
0.15/*
PROVISION OF DETAILED DESIGN SERVICES FOR
THAI BINH DEVELOPMENT PROJECT, BLOCKS 102 & 106,
OFFSHORE VIETNAM
0
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53 * VENDOR TO COMPLETE
54
55
56
57
58
A 21-01-14 IFR HNT Quang NMThao Andrew Hoang
0 17-03-14 AFC HNT Quang NMThao Andrew Hoang
APPROVER
COMPANY ACCEPTANCE ACCEPTANCE DATE
CONTRACTOR
REV ISSUE DATE DOC. STATUS
AUTHOR CHECKER