Vous êtes sur la page 1sur 16

SEC-COA

PROTECTION REQUIREMENTS
FOR
THE INSTALLATION OF 33KV MRMU FOR ISOLATION OF DISTRIBUTION
FEEDER FROM GENERATION BUS BAR AT S/S 8780

CONTENTS
1.0

Introduction

2.0

Standard and Specification

3.0

Protection Requirements at S/S 8780 (Control Room)

3.1

33KV UG Cable Protection

3.2

33KV BBP Modification at S/S 8780

4.0

Protection Requirements at MRMU

4.1

33KV UG Cable Protection

4.2

33KV OHL Feeder Protection 15-2-1(F3)

4.3

V.T Supply

5.0

DC Power Supplies

6.0

ADDITIONAL REQUIREMENTS

A.

AC/DC System at MRMU Control Room

B.

Alarm and Indications

C.

Control and Protection Secondary wiring

7.0

GENERAL REQUIREMENTS
(Instruction to Contractor/Supplier)
A.

Submittal & Drawings

B.

Control & Protection Supplies

C.

Isolation, Earthing & Shorting of CTS & VTS

D.

Aux. Supply Supervision

E.

Miscellaneous

F.

Ferruling

G.

Commissioning of Protection Relays


PR- For Isolation of GEN.
& Dist. Boundary.

1/15

PROTECTION REQUIREMENTS
FOR
THE INSTALLATION OF 33KV MRMU FOR ISOLATION OF DISTRIBUTION
FEEDER FROM GENERATION BUS BAR AT S/S 8780
1.0 INTRODUCTION
As per the management decision the control of the out going 33KV distribution
feeders shall be shifted from generation control room (S/S 8780) to distribution
control room out side generation premises by installing additional 33KV MRMUs.
The MRMUs shall be connected with the existing controlling 33KV C.Bs at
generation control room through 33KV XLPE cables.
The 33KV out going feeders shall be connected with the 33KV MRMUs.
The existing protection at the 33KV bus of the S/S 8780 is very old AEG make
obsolete and require complete replacement more so MRMU shall be installed in the
independent Distribution room constructed out side the premises of the generation
bounderies. Hence two independent protection shall be required.
1) Cable connecting S/S 8780 C.B with MRMU.
2) Out going feeder protection.
Out going feeder protection of MRMU shall operate only through MRMU while UG
Cable protection shall operate through 8780 CB and MRMU and block any auto
recloser on the circuit.
This document details the protection requirement for the proposed modifications at
S/S 8780 and the proposed modification at distribution Metered Ring Main Units.
All material used and workmanship shall be of high quality with good engineering
practice. Notwithstanding any special requirements, all system shall operate
satisfactorily. Detailed protection requirements are listed in the following paragraph.
2.0 STANDARDS AND SPECIFICATIONS.
The following SEC (COA) standard and specifications together with additional
information contained with this section give the SEC-COA requirements for the
protection equipment at substation 8780 and the proposed R.M.Units.
BS 142
IEC 6068
IEC 60255
IEC 60529
IEC 61850
PR- For Isolation of GEN.
& Dist. Boundary.

2/15

Specifications:
15-0-1(Rev. C)

Nomenclature of Protection Relays

15-0-2 (Rev. 0)
Circuits.

Testing & Commissioning of Control Alarms and Protection

15-0-9

Switchgear Interlocking.

15-0-10

Alarms Organization and Indications

15.2.4

33KV Bus Bar Protection

15-2-1(F3)

33KV OHL protection (Interconnector)

15-2-1

33KV UG Feeder protection

TCP-4/3 (Rev.10)

Use of Protection Equipment

TCS-P-105

(T-Pre-Com.1000-Rev.0) Transmission Pre- Commissioning


Test Procedure

10/1(Rev.C)

DC Power Supplies (48V DC)

10/2(Rev.C)

DC Power Supplies (125V DC)

15-0-6

Intertripping

The following Transmission Material standard Specifications (TMSS) shall also be


applicable for this project.
1.
2.
3.

38 - TMSS-05
01-TMSS-01
32-TMSS-01

Alarms Organization and Indications.


General Requirement for All Equipment/Material
13.8KV & 33KV Metal clad switchgear Up to 3000A

4.
5.
6.
7.
8.
9.
10.
11.
12.

50-TMSS-01
50-TMSS-03
TESP-119-06
TESP-119-30
TES-P-119.33
SEEDS II
48-TMMS-03
38-TMMS-03
31-TMMS-02

Current Transformers 11KV through 380KV


Potential Transformers 33KV through 380KV
Surge Protection
Auxiliary Power System (AC/DC)
Substation General Diagram
Engineering Drawing Standards.
Pilot Cable Termination Box
Remote Terminal Unit (RTU)
Aux. AC/DC Panels

rating.

All relays shall comply with the appropriate parts of IEC Publication # 60068, 60255,
60529 & 61000 and ANSI C-37.90. SEC-COA code of practice, TCP-4/3 Rev.10
Use of protection equipment.
The relays shall be IEC 61850 compatible.
3/15
PR- For Isolation of GEN.
& Dist. Boundary.

Commissioning of relays & other protection equipment shall be made in accordance


with SEC-COA spec.15-0-2 & TCS-P-105 (T-Pre-com.-1000-Rev.0) Precommissioing Procedure.
Fully wired commissioning and maintenance and test facility shall be provided for
each protection individually. Relay manufacturers prescribed test procedure shall be
taken into account. The contractor shall provide serial ports for testing through
computer.
3.0 PROTECTION REQUIREMENTS AT S/S 8780(CONTROL ROOM)
3.1 33KV UG CABLE PROTECTION (15-2-1).
The existing OHL panels having protections like distance relay type SD 135 A, auto
recloser type SKU 500 and back up O/C & E/F relay type SIT 852 shall be
dismantled
/removed and panels shall be modified as detailed below; All new relays shall be
from
TCP- 4/3 Rev.10.
For XLPE cable between 33KV switchgear panels at the S/S 8780 and MRMU the
contractor shall install Pilot wire cable differential protection as per SEC-COA
Specification 15-2-1.
It comprises cable differential module (MBCI01) current check module (MCRI01),
Pilot
supervision relay (MRTP02) and test block (2RMMLG02) at S/S 8780.
The existing CTs (CT- T1, Core 3 - Ratio; 1200 -800-600-400-200/5/5/5 A, 5P15,
15VA) at S/S 8780 previously connected with distance protection can be used for
Pilot wire cable differential protection.
(The contractor shall submit Calculations proving adequacy of the CTs
otherwise
CTs shall be replaced with adequate one).
A pilot cable box which shall meet SEC-COA specification shall be provided for the
termination and connection of pilot cable for the proposed U/G cable circuits at S/S
8780.
Pilot wire cable dedicated for protection shall be installed along the route of the
power cable.
Trip lock out relay shall be provided for cable differential protection so that the
feeder shall not be closed on fault from ECC.
Substation 8780 end shall be provided as receiving end (supervised).
3.2 33KV BBP MODIFICATION
33KV Bus bar Protection scheme at S/S 8780 shall be modified to trip the
respective MRMU C.Bs for 33kv BB faults. If 33KV BBP trip relays spare contacts
are not available than the contractor shall install additional trip relays in parallel for
tripping the 33KV RMU C.Bs. In any case 20 % spare auxiliary contacts in trip lock
PR- For Isolation of GEN.
& Dist. Boundary.

out relays shall be maintained for future/emergency use.


4/15

Existing CTs in the 33KV switchgear panels at S/S 8780 is as under;


CT-T1, Core1 - Ratio; 1200-800-600-400-200/5/5/5 A, 1M5, 15VA
(Metering)
CT-T1, Core2 - Ratio; 1200-800-600-400-200/5/5/5 A, 5P15, 15VA
(Back up O/C & E/F)
CT- T1, Core3 - Ratio; 1200-800-600-400-200/5/5/5 A, 5P15, 15VA
(Distance Protection)
CT-T2, Core1 - Ratio; 2500/5/5 Class 5P15, Burden 30 VA
CT-T2, Core2 - Ratio; 2500/5/5 Class 5P15, Burden 30 VA
( Bus bar Protection)
New protection with the CTs shall be connected as detailed below;
CT-T1, Core1 - Ratio; 1200-800-600-400-200/5/5/5 A, 1M5, 15VA
(Existing Metering)
CT-T1, Core2 - Ratio; 1200-800-600-400-200/5/5/5 A, 5P15, 15VA
(Spare)
CT- T1, Core3 - Ratio; 1200-800-600-400-200/5/5/5 A, 5P15, 15VA
(Pilot wire Cable differential Prot.)
CT-T2, Core1 - Ratio; 2500/5/5 Class 5P15, Burden 30 VA
CT-T2, Core2 - Ratio; 2500/5/5 Class 5P15, Burden 30 VA
(Existing Bus bar Protection)
The above CTs must be confirmed at site and shall be utilized as mentioned
above.
The available DC Supply for the substation 8780 is 125 volts. However it shall be
confirmed from site.

5/15

PR- For Isolation of GEN.


& Dist. Boundary.

4.0

PROTECTION REQUIREMNT AT METERED RING MAIN UNITS

4.1

33KV UG CABLE PROTECTION (15-2-1).

For XLPE cable between 33KV switchgear panels at the MRMU and S/S 8780
The contractor shall install Pilot wire cable differential protection as per SEC-COA
Specification 15-2-1.
It comprises cable differential module (MBCI01) current check module (MCRI01),
Pilot
supervision relay (MRTP01) and test block (2RMMLG02) at MRMU.
It requires one set of additional CT identical to CT at 33KV switchgear used for pilot
wire protection. The CT shall be installed on cable connected from MRMU to out
going
feeder. (The CTs shall be of ratio 1200 -800-400/5 A).
(The contractor shall submit Calculations proving adequacy of the CTs)
A pilot cable box which shall meet SEC-COA specification shall be provided for the
termination and connection of pilot cable for the proposed U/G cable circuits at
MRMU.
Pilot wire cable dedicated for protection shall be installed along the route of the
power cable.
Trip lock out relay shall be provided for cable differential protection so that the
feeder shall not be closed on fault from ECC.
MRMU Room substation end shall be provided with sending end pilot supervision
facility.
4.2 33KV OHL FEEDER PROTECTION. 15-2-1 (F3)
The 33KV Ring Main Units shall be used for OHL feeders and shall be equipped
with protection in accordance with SEC-COA Spec.15-2-1(F3) 33KV OHL Feeder
(Interconnector). The relays shall be from TCP- 4/3. However the protection shall
be
as follows;
The main protection shall be of modern multifunction numerical type and shall
have Distance+DEF+IDMT O/C & E/F + VT Supervision+Auto recloser. And shall
be connected with the existing CTs Ratio 200-400/5-5, 5P10, 15VA.
The existing Over current and earth fault relay type MIFII (GE) shall be used as
back up O/C & E/F protection. SEF relay shall be added for radial feeder.
The existing O/C & E/F Protection (MIF II) and new SEF Protection relay shall be
connected with new ring type CTs (200-400/5 A,5P10, 15 VA) to be installed on
the cable connecting with the OHL as detailed bellow;
PR- For Isolation of GEN.
& Dist. Boundary.

6/15

Existing CTs in the 5Nos.33KV MRMUs are as under;


CT-T1-3, Core 1, Ratio; 200-400/5-5A, Class 5P10 Burden 15 VA,
(O/C & E/F Prot.)
CT-T1-3, Core2, Ratio; 200-400/5-5A, Class 0.5M, Burden 10 VA
(Metering)
Following additional CTs shall be installed on cable termination in cable
compartment
of MRMU.
New protection with the additional and existing CTs in MRMU shall be
connected as detailed below;
CT-T1-3, Core1, Ratio; 200-400/5-5A, Class 5P10 Burden 15 VA, (EXISTING)
(Distance Prot. + DEF+IDMT O/C & E/F+VT supervision+ A/R)
CT-T1-3, Core2, Ratio; 200-400/5-5A, Class 0.5M, Burden 10 VA (EXISTING)
(Existing Metering)
CT-4, Ratio; 200-400/5 A, Class 5P10, Burden 15 VA
(NEW)
(Existing Back up O/C & E/F + New SEF)
CT-5, Ratio; 1200-800-400/5 A

(NEW)
(Pilot wire Cable differential Prot.)
Identical to CT as stated at Sec.3.1

4.3 V.T SUPPLY


V.T signal for distance and DEF relays at MRMU shall be taken from the
33KV Bus bar of S/S 8780.The size of the cable shall be adequate.

Notes:
1. Testing & commissioning of protection relays and other protection
equipment shall be made in accordance with SEC- COA Spec.TCS-P105.
Transmission Commissioning test Procedure.
2.

All protection relays shall be from TCP-4/3 (Rev.10)

3. Relay Settings calculations with complete data shall be submitted at least


one month before the date of starting the testing.
4.

All dismantled material shall be handed over to SEC-COA staff in good


packing.
PR- For Isolation of GEN.
& Dist. Boundary.

7/15

5.

The existing drawings shall be modified and updated. The poor quality
drawing shall be reproduced.

6. The MRMU C.Bs shall be equipped with complete trip circuit supervision
and shall be provided as per SEC-COA spec.15-2-1(F3). Each radialy fed
DC supply shall be supervised at the end of the loop.
5.0 DC POWER SUPPLY (48V)
The DC Power Supply shall follow specification 10/1.
6.
A.

ADDITIONAL REQUIREMENTS.
AC/DC SYSTEM AT MRMU CONTROL ROOM
The existing DC supply with MRMUs is not reliable. Hence there shall be

two
independent battery systems along with battery chargers as per Sec.COA
latest spec. 10/1. DC load of the substation shall be equally distributed on
DC
system 1 and DC system 2.
However, each DC system shall be capable of taking full load of th e
MRMUnits
AC DB shall be designed as per SEC-COA Drawing # SC/P/A3/530-1 and
DC
DB shall be designed as per SEC-COA Drawing # SC/P/A3/530-7.
Each DC supply shall be individually supervised at the end of the loop.
The AC auxiliary supply shall be taken from the substation auxiliary service
transformer connected through 33KV UG Cable to existing MRMU. AC and
DC DB shall be installed as per SEC-COA Spec.10/1 Rev.C.
B.

Alarms and Indications


Alarms and indications shall be in accordance with the appropriciate parts
of SEC-COA Spec.15-0-10 (38-TMMS-05) Alarms & indications shall be
modified and upgraded at S/S 8780 as detailed above.
If additional annunciator units required shall be provided.
At distribution MRMUs complete alarm indications shall be provided as per
SEC-COA Spec 15-0-10.
The grouping of alarms/indications shall be wired to RTU then to ECC via
SCADA.
The contractor shall install one RTU Compatible with SEC existing SCADA
system, with adequate no. of points for alarm indication and control from
ECC as per SEC standards.
PR- For Isolation of GEN.
& Dist. Boundary.

8/15

C.

Control and Protection Secondary wiring


Control and protection wiring shall be in accordance with appropriate parts
of SEC-COA Spec.4/7 and as per attached instructions.

7.0 GENERAL REQUIREMENTS


General requirements are as per attached instruction.

INSTRUCTIONS TO CONTRACTOR/SUPPLIER
FOR CONTROL & PROTECTION SECONDARY WIRING,
TERMINALS & TERMINATIONS
1.

All secondary wiring in associated equipment shall use high-quality material and shall
be installed in such a way to maximize the integrity and reliability.

2.

The arrangement and layout of all secondary wiring shall be neat and tidy whether it
is exposed in the panel or enclosed within some form of trunking. Wiring shall be so
fixed and arranged to facilitate access to apparatus without damage to the wiring.
Adequate means of protection shall be provided to prevent damage to wiring where it
passes from one compartment to another and from a fixed compartment onto a hinged
panel where additional means shall be incorporated to avoid damage of conductors at
the hinged joint.

3.

No wire shall be joined or tapped between terminal blocks.

4.

Where a panel contains equipment for more than one primary circuit, the wiring
associated with each circuit shall be segregated and common wiring shall also be
segregated where possible.

5.

Each wire conductor shall be PVC insulated to at least 600V, multi-stranded or singlecore copper and of adequate cross-sectional area to carry continuously the maximum
current appropriate to the circuit in which it is used without excessive temperature
rise. Notwithstanding the foregoing, the exposed secondary wiring shall have a
conductor cross-sectional area of 4.0 mm2 for current and not under 1.5mm2 for
voltage circuits.
6. For insulation of all secondary wiring, colored wiring which is specified below, shall
be used as standard:

PR- For Isolation of GEN.


& Dist. Boundary.

9/15

Red
Yellow
Blue

These colors shall be used respectively for phases 1, 2 & 3;


A, B & C; R, S & T; U, V & W or Red, Yellow and Blue of current.
transformer or voltage transformer circuits.

Black

A.C. neutral connections and single-phase A.C. wiring.

Red
Black

These colors shall be used respectively for positive and negative D.C.
supply wiring and on battery systems.

Green/Yellow Earth connections.


Grey

D.C. control and protection connections.

7.

Each secondary wire external to relays and other devices shall be ferruled at each end
with an identification number which is unique within each panel and which shall
appear on all associated schematic and wiring diagrams. The numbering system
used shall be to ICE Publication 391, Fig.14d. All numbers shall be read from the
terminal outwards and the number of the local end terminal shall be placed next to the
conductor termination.

8.

Ferrules shall be non-removable without-re-terminating the wire and they shall not be
free to easily slide along the wire insulation.
Ferrules shall normally be white with clearly legible black lettering, but red ferrules
with black lettering shall be accepted for use in tripping circuits provided they are
clearly legible.

9.

10. The finish of all ferrules shall be such that the colors do not change considerably with
age and they shall be resistant to the accumulation of dust.
11. Wiring between the switchgear and remote control panels shall be via PVC/SWA (not
tap armoured) multi-core cables which shall be glanded with suitable earth for the
armour at both ends and shall have identification tap every 10 meter.
12. Comprehensive wiring or connection diagrams shall be provided which shall clearly
show the connection and routing of each wire along with the insulation color, the
unique wire number, terminal number, terminal block number and the unique cable
number. Test facilities incorporated in the terminal blocks shall also be clearly shown.
13. All secondary wiring and associated equipment shall be fire-resistant to IEC
Publication 331.
14. When terminating wires, a sufficient length shall be left to allow each connection to be
removed from the terminal block and replaced easily. Terminations shall be grouped
to adjacent terminals by function or by cable as appropriate.
15. At least 10% spare cable cores shall be provided and terminated at the terminal
blocks farthest from the cable entry and also not less than 20% spare unused
PR- For Isolation of GEN.
& Dist. Boundary.

terminals shall be provided at the bottom of every block, in each category.


10/15

16. Not more than 2 terminations shall be connected to one side of a terminal block and
external wiring shall be connected to the opposite side of a terminal block.
17. Terminations shall be of the highest quality, suitable for the conductors and terminal
blocks with which they are used and properly crimped using the correct crimping tool
recommended by the manufacturer.
18. Terminal blocks used for secondary wiring shall be of the highest quality and the body
shall be manufactured from insulating material which is dimensionally stable, resistant
to
cracking and not subject to moisture absorption. The comparative tracking index
CTI) shall be at least 500 when tested to IEC Publication No. 112. The design shall
be
such that the accumulation of dust and moisture is minimized, but the creepage
distance between poles or to earth shall be at least 8 mm.
Where necessary to achieve adequate isolation, insulating barriers shall be
incorporated between groups of terminals.
19. Terminals shall be clearly and consecutively numbered up to two digits in each
terminal block. Each terminal block shall be labeled and uniquely identified within
each panel. Metallic parts shall be manufactured from phosphor bronze or other
suitable materials having due regard to the ambient conditions and the strength
necessary to achieve adequate tightness of the connections.
20. Insertion clamp-type terminal blocks shall incorporate serrated pressure plates and
shall not rely on screw pressure bearing directly on a wire conductor or termination.
21. In order to increase the integrity of connections, particularly those associated with
circuit breaker tripping, spring compression of the serrated pressure plates and the
use of hook-type terminations shall be preferred. Although, such spring compression
shall give reliable pullout values for the hook-type terminations, these terminal blocks
shall also incorporate screws to apply further pressure to the serrated pressure plates
and allow full tightening.
22. Shrouds shall be fitted to all terminal blocks used for circuits which may be subject to
high voltages such as current transformer, voltage transformer and protection pilot
circuits.
23. All instruments and equipment located on the panel shall be wired fully to the
terminals on the panel board at the manufacturer's Works.
GENERAL REQUIREMENTS
Minimum drawing submittal shall be as, but not limited to the following.
A.

SUBMITTAL OF DRAWINGS:
1.

Drawing index shall be available at the beginning of each set of drawing


describing the subject of each sheet or group of sheets and its issue number.
PR- For Isolation of GEN.
& Dist. Boundary.

11/15

2.
drawings

A full detailed legend describing the equipment type and how to read the
shall be given.

3. Each sheet of drawing shall be marked as For Approval, Approved and Final
As-Built, as the case may be.
4.

Drawings shall be submitted in A3 size in a proper binder with no sheets folded.

5.
The feeder/bay name/number shall be available on each sheet with the following
sheet number.
6.
Proper inter-reference shall be added for each primary and secondary
equipment and these inter-references shall include all the necessary guidance,
such as drawing number, reference.
7.

Each sheet shall be titled as per the function, such as Tripping Relay-1, DC
Distribution, etc.

8.

At the beginning of each set of drawing an equipment list shall be added and
this
shall furnish full information about each device in respect of type, rating,
make, the
number of NO & NC contacts, the Sheet #, grid location on the sheet
containing
the device and ordering information, etc.

9.

Inter-references for contacts are to follow contacts location and not the coil
location.

10.
new
B.

For modification work the existing drawings shall be modified incorporating the
equipment/wiring added and indicating wiring/equipment deleted.
CONTROL & PROTECTION SUPPLIES:

For SF6 type CBs The SF6 Low alarm shall be available in service and test
position
for Local and ECC and should block the CB operation.
The supply connections shall be made point to point with supply terminals
covered
with plastic cover and proper supply supervision relays shall be provided.
Each switchgear feeder cubicle should be equipped with 3 DC MCBs and One
AC
MCB of 6A rating for the following circuits.
i)

Protection and tripping supply.

ii)

Local indication supply.


PR- For Isolation of GEN.
& Dist. Boundary.

iii)

Control supply closing of CB, spring motor charging and ESM.

iv)

AC supply for lighting, plug sockets and space heater .

12/15

The indication lamps should be with series built in resistance to reduce the
applied
voltages to increase the operating time. All indication lamps should be
provided with
testing facility. Common ON/OFF should also be provided; one for all indication
lamps such that supply can be kept in OFF position when indications are not
required. The rating of all indication lamps should be of 125% of the rated
auxiliary
voltage at the substation.
The supply for each type of protection, tripping circuit and alarm shall be derived
directly from the main DC distribution board independently for each bay internal
looping of such supplies shall not be acceptable either in control or protection
panels
and MCB shall be equipped with an alarm contact covering both automatic and
manual operation.
The supply connections shall be made point to point with supply terminals
covered
with plastic cover and proper supply supervision relays shall be
provided.
C.
1.

ISOLATION OF VTS, SHORTING, ISOLATION & EARTHING OF CTs:


Proper CT shorting and isolating arrangement shall be provided for each CT circuit
and 11 terminals arrangement shall invariably be used to allow isolation of neutral
and earth connections.

2.

The CT star point shall never be made directly on the CT secondary terminals.

3.
CT terminals shall be covered with a caution label as Caution, CT Circuit, and
Short
before Isolation The label shall describe the shorting and isolation
process briefly.
4.
5.
cover.
6.

Plug-in type connection shall never be used in CT circuitry.


Each VT circuit shall be equipped with isolating link, covered in a labeled plastic
Color coded cables shall be used for VT circuit.

7.
Supply to any cubicle shall be through a labeled terminal block with the cable
supply
on one side and the internal connection on the other wires shall be
terminated by
insulated lug.
8.

Each equipment inside a panel shall be properly labeled in its function on metallic
PR- For Isolation of GEN.
& Dist. Boundary.

sheet.
9.

Each trip isolation link shall be labeled with red sleeve.

10

Each relay shall be associated with separate test block.

13/15

D.

Auxiliary Supply Supervision


1) Supervision of Protection Supplies
Each branch of DC protection supply shall be supervised by means of an undervoltage relay. The relay shall be connected such that the maximum amount of
wiring is supervised. Operation shall occur if the supervised supply voltage is
reduced below 80% of nominal value with acceptable delay on drop off.
2) Supervision of Circuit Breaker Tripping Circuits
Supervision of circuit breaker trip circuit should be with pre-closing and after
closing supervision with suitable fixed time delay.

E.

FERRULING:
Ferruling of both internal and external secondary wiring shall follow IEC-391

Fig.14d.
F.

MISCELLANEOUS:
1.
Consistency throughout the substation in numbering, designation, ferruling,
labeling,
etc., shall be maintained.

2. For each relay and device the detailed catalogues covering working principle,
precommissioning tests, operation and maintenance, setting procedures shall be
provided in original documents and not photo copies.
3.

Measuring transducers for SCADA shall be located on SCADA panel.

4.

CT shorting and isolating facilities also shall be provided in SCADA panels.

G.

COMMISSIONING OF PROTECTION RELAYS.

1.

Commissioning of relays and other protection measurements shall be made in


accordance with SEC-COA Spec.15-0-2 and TCS-P-105 Transmission precommissioning test procedure fully wired commissioning and maintenance test
facility
PR- For Isolation of GEN.
& Dist. Boundary.

shall be provided for each protection individually. Relay manufacturers prescribed


test
procedure shall be taken in account.
2.
All relays supplied must be in accordance with SEC-COA technical code of
practice #
TCP-4/3 Use of protection equipment preference shall be given to
modern numerical
relays from TCP-4/3.

14/15

3. The contractor shall prepare and submit all protection relay settings, including
complete details of settings calculation at least two month before the day of
commissioning the project.

REVISED
PR- Modification in MRMU & S/S 8780
04109001/ZR/PR-S/S8780-MRMU
04-04-2010G (19-04-1431H)

ZR/10

PR- For Isolation of GEN.


& Dist. Boundary.

15/15

PR- For Isolation of GEN.


& Dist. Boundary.

Vous aimerez peut-être aussi