Vous êtes sur la page 1sur 2

w

w
w
.
s
t
a
h
l
.
d
e
Signalling Devices 2011-01-17EK00IIIen
Sounder
Series YA90
E5/1
CS
&
Clifford &Snell
Series YA90 E5
13912E00
WebCode YA90A
> High sound output
115 dB(A) / 1 metre
> Evaluated for marine use using
Lloyds Register Type Approval
System
> 2 stage alarm, independently
selectable second stage
> 32 selectable tones meeting
international regulations
> Sound selection via
5 way DIL switch
> Dual 20 mm gland entries
as standard
> Monitoring facility (DC only)
The Yodalex alarms meet the requirements of Standards
BS EN 60529: 1992, Degree of protection IP66 and of
UL50: 4X Hosedown.
ATEX / IECEx
Class I
(NEC 505) (NEC 506) Class I Class II Class III
Zone 0 1 2 20 21 22 Zone 0 1 2 20 21 22 Division 1 2 1 2 1 2
For use in x x x x For use in x x x x For use in x x x x
Explosion Protection
Marking
IECEx
Gas explosion protection
Dust explosion protection Ex tD A21 IP66 (Ta - 60 ... + 60 C)
Europe (ATEX)
Gas explosion protection
Dust explosion protection E II D Ex tD A21 IP66 (Ta - 60 ... + 60 C)
Certificates
IECEx
Europe (ATEX)
Other certificates Canada (ULC), China (CQST Ex), Russia (CTB), USA (UL), ship approval (Llyods Register)
YA90/B versions: Ex d IIB (Ta - 60 ... + 60 C)
YA90/C versions: Ex d IIC (Ta - 60 ... + 60 C)
YA90/B versions: E II G Ex d IIB (Ta - 60 ... + 60 C)
YA90/C versions: E II G Ex d IIC (Ta - 60 ... + 60 C)
YA90/B versions: IECEx BAS 08.0062X
YA90/C versions: IECEx BAS 08.0061X
YA90/B versions: Baseefa08ATEX0191X
YA90/C versions: Baseefa08ATEX0189X
E5
E5
E5
E5
E5
E5
E5
E5
E5
E5
E5
E5
E5
E5
Sounder
Series YA90
CS
&
Clifford &Snell
Signalling Devices E5/2 2011-01-17EK00IIIen
Selection Table
Group Certification Rated operating voltage Order number Weight
kg
IIB Europe 24 V DC YA90/B/D/EU 4.500
48 V DC YA90/B/F/EU 4.500
230 V AC YA90/B/N/EU 4.500
IIC Europe 24 V DC YA90/C/D/EU 4.500
230 V AC YA90/C/N/EU 4.500
International 24 V DC YA90/C/D/IN 4.500
USA / Canada 24 V DC YA90/C/D/UL 4.500
115 V AC YA90/C/L/UL 4.500
Russia 230 V AC YA90/C/N/RU 4.500
Note Other voltages on request.
Technical Data
Electrical data
Rated operating voltage 24, 48 V DC
115 / 230 V AC
48 V DC (not available for UL listed products)
Current consumption 24 V DC, 300 mA
48 V DC, 160 mA
115 V AC, 80 mA
230 V AC, 45 mA
Acoustic data
Volume 115 dB(A) / 1 m
Tone sequences 2 tone sequences; selection via DIL switch
Ambient conditions
Operating temperature range ATEX / IECEx: - 60 ... + 60C
UL & ULC: - 60 ... + 66C
Max. relative humidity 95 % at 40 C
Mechanical data
Material
Enclosure Light weight Glass Reinforced Polyester (GRP)
Enclosure finished in red high performance paint with ABS flare assembly
Assembly parts Adjustable stainless steel ratchet bracket providing positive setting
Degree of protection IP66, 4X
Cable glands UL units fitted with 2 x M20 to 1/2 inch NPT Adaptors. All other units are supplied with ATEX
approved stopping plug and dust cover
Mounting / Installation
Assembly Stainless steel mounting bracket provided. Holes to suit M6, pitch 60 mm.
Dimensional Drawings (All Dimensions in mm / inches) - Subject to Alterations
13971E00
We reserve the right to make alterations to the technical data, weights, dimensions, designs and products available without
notice.The illustrations cannot be considered binding.
2
1
0
m
m
/
8
.
2
6

316 mm / 12.44
1
4
2
m
m
/
5
.
6

6
0
m
m
/
2
.
4

210 mm / 8.26

Vous aimerez peut-être aussi