Technical Information Sheet SL10-xxx

Novaris Pty Ltd ABN: 33 065 427 232


72 Browns Road, Kingston, TAS. 7050 TEL: +61 3 6229 7233
AUSTRALIA FAX: +61 3 6229 9245
Copyright 2003 Novaris E-mail: sales@novaris.com.au

SIGNAL LINE PROTECTORS - Panel Mount


Si gnal Li ne Prot ect i on
Novaris SL12 signal line protectors are designed for the
effective protection against lightning induced overvoltages
on process control, telemetry, PLC, telecommunications
and information technology systems. Protection is provided
for up to 12 signal lines.

Operat i on

Multistage transient protection is utilised in every unit,
guaranteeing low-let-through performance and a long
operating life.

High-energy gas discharge tubes provide the first stage of
protection and absorb the majority of the surge.

Fine protection consisting of the secondary and tertiary
stages absorbs residual energy downstream from the gas
arrester. Fast-acting metal oxide varistors and a diode-
clamping network serve to clamp let-through voltage spikes
to a known and predictable level.

These three stages of protection eliminate component stress
by balancing energy absorption between each stage, as well
as significantly improving performance.

Protection is provided for both common mode and
transverse mode disturbances with options for isolated
earth incorporating earth-clamping components.

Mounting
Novaris SL12 signal line protectors are supplied ready for
direct panel mounting with provision for four M4 fasteners.
For applications where DIN rail mounting is required, refer
to Technical Information Sheet SL1DIN-7V5.
Speci f i cat i ons

Description: Signal line multistage over
voltage protector.
Clamping voltage: 7.5, 18, 36, 68 or 200V.
Lines protected: 12 lines / 6 pairs.
Protection modes: Transverse and common
modes.
Protection stages: Gas arrester, MOV and TVS
stages, energy absorbtion
balanced for improved
performance and long life.
Surge withstand: IEEE C62.41 cat. A, B, C.
AS1768-1991 cat. A, B, C.
Surge rating - 8/20s: 20kA per line.
Maximum current: 350mA or 2A.
Line resistance: 8.2 for 350mA models.
<1 for 2A models.
-3dB cut-off frequency: >1.5MHz for 350mA models.
>1.0MHz for 2A models
Dimensions: 80H x 128W x 42D


Options
Cat No. Description
SL12-xxx/yy 12-line signal protector

xxx specifies clamping voltages:
7V5 (7.5), 18, 36, 68 or 200.

yy specifies maximum current rating:
Blank for 350mA, /2A for 2A versions.