sirius
ENGINEERING
Selection and
ordering data
Circuit-breakers
Contactors
Overload relays
The advantages of the modular SIRIUS system at a glance:
Overload Load
relays
feeders
Modular design
Accessories
Design
Assembly
Communications
Maintenance
Approvals
Mounting
Screwed or snapped-on for permanent, reliable mounting over its service life
Spring-loaded terminals
Service
Short delivery times also for spare parts through a global logistics network
Environment
Environmentally compatible production and materials, can be recycled, low power loss devices
Optical design
Simple, ergonomic and has been awarded the IF product design award
AC 400 V
AC 500 V
Selection tables
Selection tables
Contents
General information
Circuit-breaker + contactor
10
13
3RV circuit-breaker + 3RT contactor + 3RB12 electronic overload relay / SIMOCODE-DP 3UF5
19
22
23
Circuit-breaker + contactor
25
28
30
3RV circuit-breaker + 3RT contactor + 3RB12 electronic overload relay / SIMOCODE-DP 3UF5
34
37
38
AC 690 V
Selection tables
40
Circuit-breaker + contactor
41
43
45
46
48
General information
various devices
any time.
Coordination type 1 or 2
120
100
min
Tripping time
20
10
5
2
1
50
CLASS 30
25
20
20
15
10
10
CLASS 5
5
2
1
2
5
10x I e
0.6
Tripping current (average values)
50
NSB0_00298
current.
sions.
tion type 1.
Tests
All of the specified combinations
are tested in compliance with IEC
60947-4-1.
Q1
I>
I>
I>
ly signaled. Instead of the overload relay, the 3RV1921-1M signaling block can be alternatively
used for the SIRIUS 3RV circuitbreaker. This signaling block also
L1
L2
L3
K1
N
135
K2
246
W1
W2
V1 M V2
U1 3~ U2
breaker.
246
F1
135
K3
circuit
after 10 seconds.
simultaneously tripped.
Circuit-breaker + contactor
CLASS 10, coordination type 1, Iq = 50 kA
AC 400 V
Standard three-phase motor
4-pole at 400 V AC 1
Rated
Motor current
power
(nominal value)
Setting range
Circuitbreaker
Circuit-breaker
Contactor
Order No.
Order No.
Size
Short-circuit
breaking
capacity
overload
release
kW
Iq
kA
0.06
0.2
0.140.2
3RV1011-0BA10
3RT1015-1AP01
S00
50
0.06
0.2
0.180.25
3RV1011-0CA10
3RT1015-1AP01
S00
50
0.09
0.3
0.220.32
3RV1011-0DA10
3RT1015-1AP01
S00
50
0.09
0.3
0.280.4
3RV1011-0EA10
3RT1015-1AP01
S00
50
0.12
0.4
0.350.5
3RV1011-0FA10
3RT1015-1AP01
S00
50
0.18
0.6
0.450.63
3RV1011-0GA10
3RT1015-1AP01
S00
50
0.25
0.85
0.550.8
3RV1011-0HA10
3RT1015-1AP01
S00
50
0.25
0.85
0.71
3RV1011-0JA10
3RT1015-1AP01
S00
50
0.37
1.1
0.91.25
3RV1011-0KA10
3RT1015-1AP01
S00
50
0.55
1.5
1.11.6
3RV1011-1AA10
3RT1015-1AP01
S00
50
0.75
1.9
1.42
3RV1011-1BA10
3RT1015-1AP01
S00
50
0.75
1.9
1.82.5
3RV1011-1CA10
3RT1015-1AP01
S00
50
1.1
2.7
2.23.2
3RV1011-1DA10
3RT1015-1AP01
S00
50
1.5
3.6
2.84
3RV1011-1EA10
3RT1015-1AP01
S00
50
1.5
3.6
3.55
3RV1011-1FA10
3RT1015-1AP01
S00
50
2.2
5.0
4.56.3
3RV1011-1GA10
3RT1015-1AP01
S00
50
6.5
5.58
3RV1011-1HA10
3RT1015-1AP01
S00
50
8.5
710
3RV1011-1JA10
3RT1016-1AP01
S00
50
5.5
11.5
912
3RV1011-1KA10
3RT1017-1AP01
S00
50
7.5
15.5
1116
3RV1021-4AA10
3RT1025-1AP00
S0
50
7.5
15.5
1420
3RV1021-4BA10
3RT1025-1AP00
S0
50
11
22
1722
3RV1021-4CA10
3RT1026-1AP00
S0
50
11
22
2025
3RV1021-4DA10
3RT1026-1AP00
S0
50
15
29
2232
3RV1031-4EA10
3RT1034-1AP00
S2
50
18.5
35
2840
3RV1031-4FA10
3RT1035-1AP00
S2
50
22
41
3645
3RV1031-4GA10
3RT1036-1AP00
S2
50
22
41
4050
3RV1031-4HA10
3RT1036-1AP00
S2
50
30
55
4563
3RV1041-4JA10
3RT1044-1AP00
S3
50
37
66
5775
3RV1041-4KA10
3RT1045-1AP00
S3
50
45
80
7090
3RV1041-4LA10
3RT1046-1AP00
S3
50
45
80
80100
3RV1041-4MA10
3RT1046-1AP00
S3
50
55
97
40100
3VL2710-2AP33
75
132
64160
3VL2716-2AP33
90
160
80200
3VL3720-2AP36 3 3RT1056-6AP36
S6
50
110
195
80200
3VL3720-2AP36 4 3RT1064-6AP36
S10
50
3RT1054-1AP36
S6
50
3RT1055-6AP36
S6
50
110
195
80200
3VL3720-2AP36 4 3RT1264-6AP56
S10V
50
132
230
100250
3VL3725-2AP36 5 3RT1065-6AP36
S10
50
132
230
100250
3VL3725-2AP36 5 3RT1265-6AP36
S10V
50
160
280
125315
3VL4731-2AP36
S10
50
3RT1066-6AP36
160
280
125315
3VL4731-2AP36
3RT1266-6AP36
S10V
50
200
350
200500
3VL5750-2AP36
3RT1075-6AP36
S12
50
200
350
200500
3VL5750-2AP36
3RT1275-6AP36
S12V
50
250
430
200500
3VL5750-2AP36
3RT1076-6AP36
S12
50
250
430
200500
3VL5750-2AP36
3RT1276-6AP36
S12V
50
1
2
3
Nominal value at 400 V AC, 50 Hz for 4-pole standard motors. The specific starting and rated data of the motor to be protected are decisive when selecting devices.
Rated control supply voltage 230 V, 50 Hz. Other control voltages are also possible.
Alternatively, 3VL2716-2AP33 is possible.
Circuit-breaker + contactor
CLASS 10, coordination type 2, Iq = 50 kA
AC 400 V
Standard three-phase motor
4-pole at 400 V AC 1
Rated
Motor current
power
(nominal value)
P
I
Setting range
Circuitbreaker
overload
kW
Circuit-breaker
Contactor
Order No.
Order No.
Size
release
Short-circuit
breaking
capacity
Iq
kA
0.06
0.2
0.140.2
3RV1011-0BA10
3RT1015-1AP01
S00
50
0.06
0.2
0.180.25
3RV1011-0CA10
3RT1015-1AP01
S00
50
0.09
0.3
0.220.32
3RV1011-0DA10
3RT1015-1AP01
S00
50
0.09
0.3
0.280.4
3RV1011-0EA10
3RT1015-1AP01
S00
50
0.12
0.4
0.350.5
3RV1011-0FA10
3RT1015-1AP01
S00
50
0.18
0.6
0.450.63
3RV1011-0GA10
3RT1015-1AP01
S00
50
0.25
0.85
0.550.8
3RV1011-0HA10
3RT1015-1AP01
S00
50
0.25
0.85
0.71
3RV1011-0JA10
3RT1015-1AP01
S00
50
0.37
1.1
0.91.25
3RV1011-0KA10
3RT1015-1AP01
S00
50
0.55
1.5
1.11.6
3RV1011-1AA10
3RT1015-1AP01
S00
50
50
0.75
1.9
1.42
3RV1011-1BA10
3RT1015-1AP01
S00
0.75
1.9
1.82.5
3RV1021-1CA10
3RT1024-1AP00
S0
50
1.1
2.7
2.23.2
3RV1021-1DA10
3RT1024-1AP00
S0
50
1.5
3.6
2.84
3RV1021-1EA10
3RT1024-1AP00
S0
50
1.5
3.6
3.55
3RV1021-1FA10
3RT1024-1AP00
S0
50
2.2
5.0
4.56.3
3RV1021-1GA10
3RT1024-1AP00
S0
50
6.5
5.58
3RV1021-1HA10
3RT1024-1AP00
S0
50
8.5
710
3RV1021-1JA10
3RT1026-1AP00
S0
50
5.5
11.5
912.5
3RV1021-1KA10
3RT1026-1AP00
S0
50
7.5
15.5
1116
3RV1021-4AA10
3RT1026-1AP00
S0
50
7.5
15.5
1420
3RV1021-4BA10
3RT1026-1AP00
S0
50
11
22
1825
3RV1031-4DA10
3RT1034-1AP00
S2
50
15
29
2232
3RV1031-4EA10
3RT1034-1AP00
S2
50
18.5
35
2840
3RV1031-4FA10
3RT1035-1AP00
S2
50
22
41
3645
3RV1031-4GA10
3RT1036-1AP00
S2
50
22
41
4050
3RV1031-4HA10
3RT1036-1AP00
S2
50
50
30
55
4563
3RV1041-4JA10
3RT1044-1AP00
S3
37
66
5775
3RV1041-4KA10
3RT1045-1AP00
S3
50
45
80
7090
3RV1041-4LA10
3RT1046-1AP00
S3
50
45
80
80100
3RV1041-4MA10
3RT1046-1AP00
S3
50
55
97
40100
3VL2710-2AP33 3 3RT1054-1AP36
S6
50
75
132
64160
3VL2716-2AP33
3RT1055-6AP36
S6
50
90
160
80200
3VL3720-2AP36 3 3RT1056-6AP36
S6
50
110
195
80200
3VL3720-2AP36 4 3RT1064-6AP36
S10
50
110
195
80200
3VL3720-2AP36 4 3RT1264-6AP56
S10V
50
132
230
100250
3VL3725-2AP36 5 3RT1065-6AP36
S10
50
132
230
100250
3VL3725-2AP36 5 3RT1265-6AP36
S10V
50
160
280
125315
3VL4731-2AP36
3RT1066-6AP36
S10
50
160
280
125315
3VL4731-2AP36
3RT1266-6AP36
S10V
50
200
350
200500
3VL5750-2AP36
3RT1075-6AP36
S12
50
200
350
200500
3VL5750-2AP36
3RT1275-6AP36
S12V
50
250
430
200500
3VL5750-2AP36
3RT1076-6AP36
S12
50
250
430
200500
3VL5750-2AP36
3RT1276-6AP36
S12V
50
4
5
Circuit-breaker + contactor
CLASS 10, coordination type 2, Iq 100 kA
AC 400 V
Standard three-phase motor
4-pole at 400 V AC 1
Rated
Motor current
power
(nominal value)
P
I
kW
A
Setting range
Circuitbreaker
overload
release
A
Circuit-breaker
Contactor
Order No.
Order No.
0.04
0.06
0.06
0.09
0.09
0.12
0.18
0.18
0.25
0.37
0.55
0.75
0.04
0.06
0.06
0.09
0.09
0.12
0.18
0.18
0.25
0.37
0.55
0.75
0.75
1.1
1.5
1.5
2.2
3
4
5.5
7.5
7.5
11
15
18.5
22
22
30
37
45
45
0.110.16
0.140.2
0.180.25
0.220.32
0.280.4
0.350.5
0.450.63
0.550.8
0.71
0.91.25
1.11.6
1.42
0.110.16
0.140.2
0.180.25
0.220.32
0.280.4
0.350.5
0.450.63
0.550.8
0.71
0.91.25
1.11.6
1.42
1.82.5
2.23.2
2.84
3.55
4.56.3
5.58
710
912.5
1116
1420
1825
2232
2840
3645
4050
4563
5775
7090
80100
3RV1011-0AA10
3RV1011-0BA10
3RV1011-0CA10
3RV1011-0DA10
3RV1011-0EA10
3RV1011-0FA10
3RV1011-0GA10
3RV1011-0HA10
3RV1011-0JA10
3RV1011-0KA10
3RV1011-1AA10
3RV1011-1BA10
3RV1021-0AA10
3RV1021-0BA10
3RV1021-0CA10
3RV1021-0DA10
3RV1021-0EA10
3RV1021-0FA10
3RV1021-0GA10
3RV1021-0HA10
3RV1021-0JA10
3RV1021-0KA10
3RV1021-1AA10
3RV1021-1BA10
3RV1021-1CA10
3RV1021-1DA10
3RV1021-1EA10
3RV1021-1FA10
3RV1021-1GA10
3RV1021-1HA10
3RV1021-1JA10
3RV1021-1KA10
3RV1021-4AA10
3RV1021-4BA10
3RV1031-4DA10
3RV1031-4EA10
3RV1031-4FA10
3RV1031-4GA10
3RV1031-4HA10
3RV1042-4JA10
3RV1042-4KA10
3RV1042-4LA10
3RV1042-4MA10
3RT1015-1AP01
3RT1015-1AP01
3RT1015-1AP01
3RT1015-1AP01
3RT1015-1AP01
3RT1015-1AP01
3RT1015-1AP01
3RT1015-1AP01
3RT1015-1AP01
3RT1015-1AP01
3RT1015-1AP01
3RT1015-1AP01
3RT1024-1AP00
3RT1024-1AP00
3RT1024-1AP00
3RT1024-1AP00
3RT1024-1AP00
3RT1024-1AP00
3RT1024-1AP00
3RT1024-1AP00
3RT1024-1AP00
3RT1024-1AP00
3RT1024-1AP00
3RT1024-1AP00
3RT1024-1AP00
3RT1024-1AP00
3RT1024-1AP00
3RT1024-1AP00
3RT1024-1AP00
3RT1024-1AP00
3RT1026-1AP00
3RT1026-1AP00
3RT1026-1AP00
3RT1026-1AP00
3RT1034-1AP00
3RT1034-1AP00
3RT1035-1AP00
3RT1036-1AP00
3RT1036-1AP00
3RT1054-1AP36
3RT1054-1AP36
3RT1054-1AP36
3RT1054-1AP36
S00
S00
S00
S00
S00
S00
S00
S00
S00
S00
S00
S00
S0
S0
S0
S0
S0
S0
S0
S0
S0
S0
S0
S0
S0
S0
S0
S0
S0
S0
S0
S0
S0
S0
S2
S2
S2
S2
S2
S3/S6
S3/S6
S3/S6
S3/S6
130
130
130
130
130
130
130
130
130
130
130
130
130
130
130
130
130
130
130
130
130
130
130
130
130
130
130
130
130
130
130
130
100
100
100
100
100
100
100
100
100
100
100
3RV1042-4JA10
3RV1042-4KA10
3RV1042-4LA10
3RV1042-4MA10
3RT1044-1AP00
3RT1045-1AP00
3RT1046-1AP00
3RT1046-1AP00
S3
S3
S3
S3
80
80
80
80
0.16
0.2
0.2
0.3
0.3
0.4
0.6
0.6
0.85
1.1
1.5
1.9
0.16
0.2
0.2
0.3
0.3
0.4
0.6
0.6
0.85
1.1
1.5
1.9
1.9
2.7
3.6
3.6
5
6.5
8.5
11.5
15.5
15.5
22
29
35
41
41
55
66
80
80
Size
Short-circuit
breaking
capacity
Iq
kA
8
1
2
Nominal value at 400 V AC, 50 Hz for 4-pole standard motors. The specific starting and rated data of the motor to be protected are decisive when selecting.
Rated control supply voltage 230 V, 50 Hz. Other control voltages are also possible.
Circuit-breaker + contactor
CLASS 20, coordination type 2, Iq = 50 kA
AC 400 V
Standard three-phase motor
4-pole at 400 V AC 1
Rated
Motor current
power
(nominal value)
P
I
kW
A
Setting range
Circuitbreaker
overload
release
A
Circuitbreaker
Contactor
Order No.
Order No.
5.5
7.5
11
11
15
18.5
18.5
22
30
30
37
45
45
55
75
90
90
110
110
132
160
160
200
200
250
1116
1420
1825
2232
2840
2840
3650
3650
4563
5775
5775
7090
80100
40100
64160
80200
80200
80200
80200
100250
125315
125315
200500
200500
200500
3RV1031-4AB10
3RV1031-4BB10
3RV1031-4DB10
3RV1031-4EB10
3RV1042-4FB10
3RV1042-4FB10
3RV1042-4HB10
3RV1042-4HB10
3RV1042-4JB10
3RV1042-4KB10
3RV1042-4KB10
3RV1042-4LB10
3RV1042-4MB10
3VL2710-2AS33 3
3VL2716-2AS33
3VL3720-2AS36 3
3VL3720-2AS36 3
3VL3720-2AS36 4
3VL3720-2AS36 4
3VL3725-2AS36 5
3VL4731-2AS36
3VL4731-2AS36
3VL5750-2AS36
3VL5750-2AS36
3VL5750-2AS36
3RT1034-1AP00
3RT1034-1AP00
3RT1035-1AP00
3RT1035-1AP00
3RT1044-1AP00
3RT1044-1AP00
3RT1044-1AP00
3RT1044-1AP00
3RT1046-1AP00
3RT1046-1AP00
3RT1046-1AP00
3RT1054-1AP36
3RT1054-1AP36
3RT1055-6AP36
3RT1056-6AP36
3RT1064-6AP36
3RT1065-6AP36
3RT1066-6AP36
3RT1264-6AP36
3RT1265-6AP36
3RT1266-6AP36
3RT1075-6AP36
3RT1076-6AP36
3RT1275-6AP36
3RT1276-6AP36
1
2
3
4
5
11.5
15.5
22
22
29
35
35
41
55
55
66
80
80
97
132
160
160
195
195
230
280
280
350
350
430
Size
Short-circuit
breaking
capacity
Iq
kA
S2
S2
S2
S2
S3
S3
S3
S3
S3
S3
S3
S3/S6
S3/S6
S6
S6
S10
S10
S10
S10V
S10V
S10V
S12
S12
S12V
S12V
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
Nominal value at 400 V AC, 50 Hz for 4-pole standard motors. The specific starting and rated data of the motor to be protected are decisive when selecting devices.
Rated control supply voltage 230 V, 50 Hz. Other control voltages are also possible.
Alternatively, 3VL2716-2AS33 is possible.
Alternatively, 3VL3725-2AS36 is possible.
Alternatively, 3VL4731-2AS36 is possible.
AC 400 V
Standard three-phase motor
4-pole at 400 V AC 1
Rated
Motor current
power
(nominal value)
P
I
kW
A
Setting range
Circuitbreaker
overload
release
A
Circuit-breaker
Contactor
Order No.
Order No.
0.06
without
3RV1321-0BC10
3RT1015-1AP01
0.2
Size
Overload relay
Setting range
Overload relay
overload release
Order No.
Short-circuit
breaking
capacity
Iq
S0/S00 3RU1116-0BB0
0.140.2
50
0.06
0.2
without
3RV1321-0CC10
3RT1015-1AP01
S0/S00 3RU1116-0CB0
0.180.25
50
0.09
0.3
without
3RV1321-0DC10
3RT1015-1AP01
S0/S00 3RU1116-0DB0
0.220.32
50
0.09
0.3
without
3RV1321-0EC10
3RT1015-1AP01
S0/S00 3RU1116-0EB0
0.280.4
50
0.12
0.4
without
3RV1321-0FC10
3RT1015-1AP01
S0/S00 3RU1116-0FB0
0.350.5
50
0.18
0.6
without
3RV1321-0GC10
3RT1015-1AP01
S0/S00 3RU1116-0GB0
0.450.63
50
0.25
0.85
without
3RV1321-0HC10
3RT1015-1AP01
S0/S00 3RU1116-0HB0
0.550.8
50
0.25
0.85
without
3RV1321-0JC10
3RT1015-1AP01
S0/S00 3RU1116-0JB0
0.71
50
0.37
1.1
without
3RV1321-0KC10
3RT1015-1AP01
S0/S00 3RU1116-0KB0
0.91.25
50
0.55
1.5
without
3RV1321-1AC10
3RT1015-1AP01
S0/S00 3RU1116-1AB0
1.11.6
50
0.75
1.9
without
3RV1321-1BC10
3RT1015-1AP01
S0/S00 3RU1116-1BB0
1.42
50
1.1
2.7
without
3RV1321-1DC10
3RT1015-1AP01
S0/S00 3RU1116-1DB0
2.23.2
50
1.5
3.6
without
3RV1321-1EC10
3RT1015-1AP01
S0/S00 3RU1116-1EB0
2.84
50
1.5
3.6
without
3RV1321-1FC10
3RT1015-1AP01
S0/S00 3RU1116-1FB0
3.55
50
2.2
5.0
without
3RV1321-1GC10
3RT1015-1AP01
S0/S00 3RU1116-1GB0
4.56.3
50
6.5
without
3RV1321-1HC10
3RT1015-1AP01
S0/S00 3RU1116-1HB0
5.58
50
8.5
without
3RV1321-1JC10
3RT1016-1AP01
S0/S00 3RU1116-1JB0
710
50
5.5
11.5
without
3RV1321-1KC10
3RT1017-1AP01
S0/S00 3RU1116-1KB0
912
50
7.5
15.5
without
3RV1321-4AC10
3RT1024-1AP00
S0
1116
50
3RU1126-4AB0
7.5
15.5
without
3RV1321-4BC10
3RT1025-1AP00
S0
3RU1126-4BB0
1420
50
11
22
without
3RV1321-4CC10
3RT1026-1AP00
S0
3RU1126-4CB0
1722
50
11
22
without
3RV1321-4DC10
3RT1026-1AP00
S0
3RU1126-4DB0
2025
50
15
29
without
3RV1331-4EC10
3RT1034-1AP00
S2
3RU1136-4EB0
2232
50
18.5
35
without
3RV1331-4FC10
3RT1035-1AP00
S2
3RU1136-4FB0
2840
50
22
41
without
3RV1331-4GC10
3RT1036-1AP00
S2
3RU1136-4GB0
3645
50
22
41
without
3RV1331-4HC10
3RT1036-1AP00
S2
3RU1136-4HB0
4050
50
30
55
without
3RV1341-4JC10
3RT1044-1AP00
S3
3RU1146-4JB0
4563
50
37
66
without
3RV1341-4KC10
3RT1045-1AP00
S3
3RU1146-4KB0
5775
50
45
80
without
3RV1341-4LC10
3RT1046-1AP00
S3
3RU1146-4LB0
7090
50
45
80
without
3RV1341-4MC10 3RT1046-1AP00
S3
3RU1146-4MB0
80100
50
10
1
2
Nominal value at 400 V AC, 50 Hz for 4-pole standard motors. The specific starting and rated data of the motor to be protected are decisive when selecting devices.
Rated control supply voltage 230 V, 50 Hz. Other control voltages are also possible.
AC 400 V
V
t
Setting range
Circuitbreaker
overload
release
A
Circuit-breaker
Contactor
Order No.
Order No.
0.06
without
3RV1321-0BC10
3RT1015-1AP01
0.2
Size
Overload relay
Setting range
Overload relay
overload release
Short-circuit
breaking
capacity
Order No.
Iq
kA
0.140.2
50
S0/S00 3RU1116-0BB0
0.06
0.2
without
3RV1321-0CC10
3RT1015-1AP01
S0/S00 3RU1116-0CB0
0.180.25
50
0.09
0.3
without
3RV1321-0DC10
3RT1015-1AP01
S0/S00 3RU1116-0DB0
0.220.32
50
0.09
0.3
without
3RV1321-0EC10
3RT1015-1AP01
S0/S00 3RU1116-0EB0
0.280.4
50
0.12
0.4
without
3RV1321-0FC10
3RT1015-1AP01
S0/S00 3RU1116-0FB0
0.350.5
50
0.18
0.6
without
3RV1321-0GC10
3RT1015-1AP01
S0/S00 3RU1116-0GB0
0.450.63
50
0.25
0.85
without
3RV1321-0HC10
3RT1015-1AP01
S0/S00 3RU1116-0HB0
0.550.8
50
0.25
0.85
without
3RV1321-0JC10
3RT1015-1AP01
S0/S00 3RU1116-0JB0
0.71
50
0.37
1.1
without
3RV1321-0KC10
3RT1015-1AP01
S0/S00 3RU1116-0KB0
0.91.25
50
0.55
1.5
without
3RV1321-1AC10
3RT1015-1AP01
S0/S00 3RU1116-1AB0
1.11.6
50
0.75
1.9
without
3RV1321-1BC10
3RT1015-1AP01
S0/S00 3RU1116-1BB0
1.42
50
0.75
1.9
without
3RV1321-1CC10
3RT1024-1AP00
S0
1.82.5
50
3RU1126-1CB0
1.1
2.7
without
3RV1321-1DC10
3RT1024-1AP00
S0
3RU1126-1DB0
2.23.2
50
1.5
3.6
without
3RV1321-1EC10
3RT1024-1AP00
S0
3RU1126-1EB0
2.84
50
1.5
3.6
without
3RV1321-1FC10
3RT1024-1AP00
S0
3RU1126-1FB0
3.55
50
2.2
5.0
without
3RV1321-1GC10
3RT1024-1AP00
S0
3RU1126-1GB0
4.56.3
50
6.5
without
3RV1321-1HC10
3RT1024-1AP00
S0
3RU1126-1HB0
5.58
50
8.5
without
3RV1321-1JC10
3RT1026-1AP00
S0
3RU1126-1JB0
710
50
5.5
11.5
without
3RV1321-1KC10
3RT1026-1AP00
S0
3RU1126-1KB0
912.5
50
7.5
15.5
without
3RV1321-4AC10
3RT1026-1AP00
S0
3RU1126-4AB0
1116
50
7.5
15.5
without
3RV1321-4BC10
3RT1026-1AP00
S0
3RU1126-4BB0
1420
50
11
22
without
3RV1331-4DC10
3RT1034-1AP00
S2
3RU1136-4DB0
1825
50
15
29
without
3RV1331-4EC10
3RT1034-1AP00
S2
3RU1136-4EB0
2232
50
18.5
35
without
3RV1331-4FC10
3RT1035-1AP00
S2
3RU1136-4FB0
2840
50
22
41
without
3RV1331-4GC10
3RT1036-1AP00
S2
3RU1136-4GB0
3645
50
22
41
without
3RV1331-4HC10
3RT1036-1AP00
S2
3RU1136-4HB0
4050
50
30
55
without
3RV1341-4JC10
3RT1044-1AP00
S3
3RU1146-4JB0
4563
50
37
66
without
3RV1341-4KC10
3RT1045-1AP00
S3
3RU1146-4KB0
5775
50
45
80
without
3RV1341-4LC10
3RT1046-1AP00
S3
3RU1146-4LB0
7090
50
45
80
without
3RV1341-4MC10 3RT1046-1AP00
S3
3RU1146-4MB0
80100
50
11
1
2
Nominal value at 400 V AC, 50 Hz for 4-pole standard motors. The specific starting and rated data of the motor to be protected are decisive when selecting devices.
Rated control supply voltage 230 V, 50 Hz. Other control voltages are also possible.
AC 400 V
Standard three-phase motor
4-pole at 400 V AC 1
Rated
Motor current
power
(nominal value)
P
I
kW
A
Setting range
Circuitbreaker
overload
release
A
Circuit-breaker
Contactor
Overload relay
Setting range
Overload relay
overload release
Short-circuit
breaking
capacity
Order No.
Order No.
Order No.
Iq
kA
Size
0.04
0.16
without
3RV1321-0AC10
3RT1015-1AP01 S0/S00
3RU1116-0AB0
0.110.16
130
0.06
0.2
without
3RV1321-0BC10
3RT1015-1AP01 S0/S00
3RU1116-0BB0
0.140.2
130
0.06
0.2
without
3RV1321-0CC10
3RT1015-1AP01 S0/S00
3RU1116-0CB0
0.180.25
130
0.09
0.3
without
3RV1321-0DC10
3RT1015-1AP01 S0/S00
3RU1116-0DB0
0.220.32
130
0.09
0.3
without
3RV1321-0EC10
3RT1015-1AP01 S0/S00
3RU1116-0EB0
0.280.4
130
0.12
0.4
without
3RV1321-0FC10
3RT1015-1AP01 S0/S00
3RU1116-0FB0
0.350.5
130
0.18
0.6
without
3RV1321-0GC10
3RT1015-1AP01 S0/S00
3RU1116-0GB0
0.450.63
130
0.18
0.6
without
3RV1321-0HC10
3RT1015-1AP01 S0/S00
3RU1116-0HB0
0.550.8
130
0.25
0.85
without
3RV1321-0JC10
3RT1015-1AP01 S0/S00
3RU1116-0JB0
0.71
130
0.37
1.1
without
3RV1321-0KC10
3RT1015-1AP01 S0/S00
3RU1116-0KB0
0.91.25
130
0.55
1.5
without
3RV1321-1AC10
3RT1015-1AP01 S0/S00
3RU1116-1AB0
1.11.6
130
0.75
1.9
without
3RV1321-1BC10
3RT1015-1AP01 S0/S00
3RU1116-1BB0
1.42
130
0.75
1.9
without
3RV1321-1CC10
3RT1024-1AP00 S0
3RU1126-1CB0
1.82.5
130
1.1
2.7
without
3RV1321-1DA10
3RT1024-1AP00 S0
3RU1126-1DB0
2.23.2
130
1.5
3.6
without
3RV1321-1EA10
3RT1024-1AP00 S0
3RU1126-1EB0
2.84
130
1.5
3.6
without
3RV1321-1FA10
3RT1024-1AP00 S0
3RU1126-1FB0
3.55
130
2.2
without
3RV1321-1GC10
3RT1024-1AP00 S0
3RU1126-1GB0
4.56.3
130
6.5
without
3RV1321-1HC10
3RT1024-1AP00 S0
3RU1126-1HB0
5.58
130
8.5
without
3RV1321-1JC10
3RT1026-1AP00 S0
3RU1126-1JB0
710
130
5.5
11.5
without
3RV1321-1KC10
3RT1026-1AP00 S0
3RU1126-1KB0
912.5
130
7.5
15.5
without
3RV1321-4AC10
3RT1026-1AP00 S0
3RU1126-4AB0
1116
100
7.5
15.5
without
3RV1321-4BC10
3RT1026-1AP00 S0
3RU1126-4BB0
1420
100
11
22
without
3RV1331-4DC10
3RT1034-1AP00 S2
3RU1136-4DB0
1825
100
15
29
without
3RV1331-4EC10
3RT1034-1AP00 S2
3RU1136-4EB0
2232
100
18.5
35
without
3RV1331-4FC10
3RT1035-1AP00 S2
3RU1136-4FB0
2840
100
22
41
without
3RV1331-4GC10
3RT1036-1AP00 S2
3RU1136-4GB0
3645
100
22
41
without
3RV1331-4HC10
3RT1036-1AP00 S2
3RU1136-4HB0
4050
100
Coordination type 1
30
55
without
3RV1342-4JC10
3RT1044-1AP00 S3
3RU1146-4JB0
4563
80
37
66
without
3RV1342-4KC10
3RT1045-1AP00 S3
3RU1146-4KB0
5775
80
45
80
without
3RV1342-4LC10
3RT1046-1AP00 S3
3RU1146-4LB0
7090
80
45
80
without
3RV1342-4MC10
3RT1046-1AP00 S3
3RU1146-4MB0
80100
80
12
1
2
Nominal value at 400 V AC, 50 Hz for 4-pole standard motors. The specific starting and rated data of the motor to be protected are decisive when selecting devices.
Rated control supply voltage 230 V, 50 Hz. Other control voltages are also possible.
V
t
AC 400 V
Standard three-phase motor
4-pole at 400 V AC 1
Rated
Motor current
power
(nominal value)
P
I
kW
A
Setting range
Circuitbreaker
overload
release 2
A
Circuit-breaker
Contactor
Order No.
Order No.
0.06
0.09
0.12
0.18
0.25
0.55
0.75
1.1
1.1
1.5
2.2
3
0.06
0.09
0.12
0.18
0.25
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
110
132
132
160
160
200
200
250
250
0.220.32
0.280.4
1.11.6
1.11.6
1.11.6
1.42
2.23.2
2.23.2
2.84
3.55
4.56.3
5.58
0.280.4
0.450.63
0.450.63
1.11.6
1.11.6
1.11.6
1.42
2.23.2
2.84
3.55
4.56.3
5.58
912.5
1420
1420
2232
2840
4563
4563
5775
5775
80100
without
without
without
without
without
without
without
without
without
without
without
without
without
3RV1011-0DA10
3RV1011-0EA10
3RV1011-1AA10
3RV1011-1AA10
3RV1011-1AA10
3RV1011-1BA10
3RV1011-1DA10
3RV1011-1DA10
3RV1011-1EA10
3RV1011-1FA10
3RV1011-1GA10
3RV1011-1HA10
3RV1021-0EA10
3RV1021-0GA10
3RV1021-0GA10
3RV1021-1AA10
3RV1021-1AA10
3RV1021-1AA10
3RV1021-1BA10
3RV1021-1DA10
3RV1021-1EA10
3RV1021-1FA10
3RV1021-1GA10
3RV1021-1HA10
3RV1021-1KA10
3RV1021-4BA10
3RV1021-4BA10
3RV1031-4EA10
3RV1031-4FA10
3RV1041-4JA10
3RV1041-4JA10
3RV1041-4KA10
3RV1041-4KA10
3RV1041-4MA10
3VL2710-2DK33 3
3VL2716-2DK33
3VL3725-2DK36 3
3VL3725-2DK36 4
3VL3725-2DK36 4
3VL4725-2DK36 5
3VL4725-2DK36 5
3VL4731-2DK36 5
3VL4731-2DK36
3VL5750-2DK36
3VL5750-2DK36
3VL5750-2DK36
3VL5750-2DK36
3RT1015-1AP01
3RT1015-1AP01
3RT1015-1AP01
3RT1015-1AP01
3RT1015-1AP01
3RT1015-1AP01
3RT1015-1AP01
3RT1015-1AP01
3RT1015-1AP01
3RT1015-1AP01
3RT1015-1AP01
3RT1015-1AP01
3RT1024-1AP00
3RT1024-1AP00
3RT1024-1AP00
3RT1024-1AP00
3RT1024-1AP00
3RT1024-1AP00
3RT1024-1AP00
3RT1024-1AP00
3RT1024-1AP00
3RT1024-1AP00
3RT1024-1AP00
3RT1024-1AP00
3RT1025-1AP00
3RT1025-1AP00
3RT1025-1AP00
3RT1034-1AP00
3RT1035-1AP00
3RT1044-1AP00
3RT1044-1AP00
3RT1045-1AP00
3RT1045-1AP00
3RT1046-1AP00
3RT1054-1AP36
3RT1055-6AP36
3RT1056-6AP36
3RT1064-6AP36
3RT1264-6AP36
3RT1065-6AP36
3RT1265-6AP36
3RT1066-6AP36
3RT1266-6AP36
3RT1075-6AP36
3RT1275-6AP36
3RT1076-6AP36
3RT1276-6AP36
1
2
3
4
5
6
7
0.2
0.3
0.4
0.6
0.85
1.5
1.9
2.7
2.7
3.6
5
6.5
0.2
0.35
0.4
0.6
0.85
1.1
1.5
1.9
2.7
3.6
5
6.5
8.5
11.5
15.5
22
29
35
41
55
66
80
97
132
160
195
195
230
230
280
280
350
350
430
430
Size
S00
S00
S00
S00
S00
S00
S00
S00
S00
S00
S00
S00
S0
S0
S0
S0
S0
S0
S0
S0
S0
S0
S0
S0
S0
S0
S0
S2
S2
S3
S3
S3
S3
S3
S6
S6
S6
S10
S10V
S10
S10V
S10
S10V
S12
S12V
S12
S12V
Overload relay
Setting range
Overload relay
overload release
Short-circuit
breaking
capacity
Order No.
Iq
kA
3RB1016-1RB0
3RB1016-1RB0
3RB1016-1NB0
3RB1016-1NB0
3RB1016-1NB0
3RB1016-1NB0
3RB1016-1PB0
3RB1016-1PB0
3RB1016-1PB0
3RB1016-1PB0
3RB1016-1PB0
3RB1016-1SB0
3RB1026-1RB0
3RB1026-1RB0
3RB1026-1RB0
3RB1026-1NB0
3RB1026-1NB0
3RB1026-1NB0
3RB1026-1NB0
3RB1026-1PB0
3RB1026-1PB0
3RB1026-1PB0
3RB1026-1PB0
3RB1026-1SB0
3RB1026-1SB0
3RB1026-1QB0
3RB1026-1QB0
3RB1036-1QB0
3RB1036-1UB0
3RB1046-1UB0
3RB1046-1UB0
3RB1046-1EB0
3RB1046-1EB0
3RB1046-1EB0
3RB1056-1FG0
3RB1056-1FG0
3RB1056-1FG0
3RB1056-1FG0
3RB1056-1FG0
3RB1066-1GG0
3RB1066-1GG0
3RB1066-1KG0
3RB1066-1KG0
3RB1066-1KG0
3RB1066-1KG0
3RB1066-1KG0
3RB1066-1KG0
0.10.4
0.10.4
0.41.6
0.41.6
0.41.6
0.41.6
1.56.0
1.56.0
1.56.0
1.56.0
1.56.0
312
0.10.4
0.10.4
0.10.4
0.41.6
0.41.6
0.41.6
0.41.6
1.56.0
1.56.0
1.56.0
1.56.0
312
312
625
625
625
1350
1350
1350
25100
25100
25100
50200
50200
50200
50200
50200
55250
55250
200540
200540
200540
200540
200540
200540
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
6
6
7
7
Nominal value at 400 V AC, 50 Hz for 4-pole standard motors. The specific starting and rated data of the motor to be protected are decisive when selecting devices.
The circuit-breaker should be set to the maximum current value.
Alternatively, 3VL2716-2DK33 is possible.
Alternatively, 3VL3725-2DK36 is possible.
Alternatively, 3VL4731-2DK36 is possible.
Alternatively, 3RB1066-1GG0 is possible.
Alternatively, 3RB1066-1KG0 is possible.
13
AC 400 V
Standard three-phase motor
4-pole at 400 V AC 1
Rated
Motor current
power
(nominal value)
P
I
kW
A
Setting range
Circuitbreaker
overload
release 2
A
Circuit-breaker
Contactor
Order No.
Order No.
0.06
0.09
0.12
0.18
0.25
0.37
0.55
0.06
0.09
0.12
0.18
0.25
0.37
0.55
0.75
1.1
1.5
2.2
3
3
4
4
5.5
7.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
110
132
132
160
160
200
200
250
250
0.220.32
0.280.4
1.11.6
1.11.6
1.11.6
1.11.6
1.42
0.280.4
0.450.63
0.450.63
1.11.6
1.11.6
1.11.6
1.42
2.23.2
2.84
3.55
4.56.3
5.58
710
912.5
1116
1420
1420
1825
2232
2840
4563
4563
5775
5775
80100
without
without
without
without
without
without
without
without
without
without
without
without
without
3RV1011-0DA10
3RV1011-0EA10
3RV1011-1AA10
3RV1011-1AA10
3RV1011-1AA10
3RV1011-1AA10
3RV1011-1BA10
3RV1021-0EA10
3RV1021-0GA10
3RV1021-0GA10
3RV1021-1AA10
3RV1021-1AA10
3RV1021-1AA10
3RV1021-1BA10
3RV1021-1DA10
3RV1021-1EA10
3RV1021-1FA10
3RV1021-1GA10
3RV1021-1HA10
3RV1021-1JA10
3RV1021-1KA10
3RV1021-4AA10
3RV1021-4BA10
3RV1021-4BA10
3RV1031-4DA10
3RV1031-4EA10
3RV1031-4FA10
3RV1041-4JA10
3RV1041-4JA10
3RV1041-4KA10
3RV1041-4KA10
3RV1041-4MA10
3VL2710-2DK33
3VL2716-2DK33
3VL3725-2DK36
3VL3725-2DK36
3VL3725-2DK36
3VL4725-2DK36
3VL4725-2DK36
3VL4731-2DK36
3VL4731-2DK36
3VL5750-2DK36
3VL5750-2DK36
3VL5750-2DK36
3VL5750-2DK36
3RT1015-1AP01
3RT1015-1AP01
3RT1015-1AP01
3RT1015-1AP01
3RT1015-1AP01
3RT1015-1AP01
3RT1015-1AP01
3RT1024-1AP00
3RT1024-1AP00
3RT1024-1AP00
3RT1024-1AP00
3RT1024-1AP00
3RT1024-1AP00
3RT1024-1AP00
3RT1024-1AP00
3RT1024-1AP00
3RT1024-1AP00
3RT1024-1AP00
3RT1024-1AP00
3RT1026-1AP00
3RT1026-1AP00
3RT1026-1AP00
3RT1026-1AP00
3RT1026-1AP00
3RT1034-1AP00
3RT1034-1AP00
3RT1035-1AP00
3RT1044-1AP00
3RT1044-1AP00
3RT1045-1AP00
3RT1045-1AP00
3RT1046-1AP00
3RT1054-1AP36
3RT1055-6AP36
3RT1056-6AP36
3RT1064-6AP36
3RT1264-6AP36
3RT1065-6AP36
3RT1265-6AP36
3RT1066-6AP36
3RT1266-6AP36
3RT1075-6AP36
3RT1275-6AP36
3RT1076-6AP36
3RT1276-6AP36
1
2
3
4
14
5
6
7
0.2
0.3
0.4
0.6
0.85
1.1
1.5
0.2
0.35
0.4
0.6
0.85
1.1
1.5
1.9
2.7
3.6
5
6.5
6.5
8.5
8.5
11.5
15.5
15.5
22
29
35
41
55
66
80
97
132
160
195
195
230
230
280
280
350
350
430
430
3
4
4
5
5
5
Size
S00
S00
S00
S00
S00
S00
S00
S0
S0
S0
S0
S0
S0
S0
S0
S0
S0
S0
S0
S0
S0
S0
S0
S0
S2
S2
S2
S3
S3
S3
S3
S3
S6
S6
S6
S10
S10V
S10
S10V
S10
S10V
S12
S12V
S12
S12V
Overload relay
Setting range
Overload relay
overload release
Short-circuit
breaking
capacity
Order No.
Iq
kA
3RB1016-1RB0
3RB1016-1RB0
3RB1016-1NB0
3RB1016-1NB0
3RB1016-1NB0
3RB1016-1NB0
3RB1016-1NB0
3RB1026-1RB0
3RB1026-1RB0
3RB1026-1RB0
3RB1026-1NB0
3RB1026-1NB0
3RB1026-1NB0
3RB1026-1NB0
3RB1026-1PB0
3RB1026-1PB0
3RB1026-1PB0
3RB1026-1PB0
3RB1026-1SB0
3RB1026-1SB0
3RB1026-1SB0
3RB1026-1QB0
3RB1026-1QB0
3RB1026-1QB0
3RB1036-1QB0
3RB1036-1QB0
3RB1036-1UB0
3RB1046-1UB0
3RB1046-1UB0
3RB1046-1EB0
3RB1046-1EB0
3RB1046-1EB0
3RB1056-1FG0
3RB1056-1FG0
3RB1056-1FG0
3RB1056-1FG0
3RB1056-1FG0
3RB1066-1GG0
3RB1066-1GG0
3RB1066-1KG0
3RB1066-1KG0
3RB1066-1KG0
3RB1066-1KG0
3RB1066-1KG0
3RB1066-1KG0
0.10.4
0.10.4
0.41.6
0.41.6
0.41.6
0.41.6
0.41.6
0.10.4
0.10.4
0.10.4
0.41.6
0.41.6
0.41.6
0.41.6
1.56.0
1.56.0
1.56.0
1.56.0
312
312
312
625
625
625
625
625
1350
1350
1350
25100
25100
25100
50200
50200
50200
50200
50200
55250
55250
200540
200540
200540
200540
200540
200540
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
6
6
7
7
Nominal value at 400 V AC, 50 Hz for 4-pole standard motors. The specific starting and rated data of the motor to be protected are decisive when selecting devices.
The circuit-breaker should be set to the maximum current value.
Alternatively, 3VL2716-2DK33 is possible.
Alternatively, 3VL3725-2DK36 is possible.
Alternatively, 3VL4731-2DK36 is possible.
Alternatively, 3RB1066-1GG0 is possible.
Alternatively, 3RB1066-1KG0 is possible.
AC 400 V
V
t
Setting range
Circuitbreaker
overload
release 2
A
Circuit-breaker
Contactor
Order No.
Order No.
0.06
0.09
0.12
0.18
0.25
0.37
0.55
0.06
0.09
0.12
0.18
0.25
0.37
0.55
0.75
1.1
1.5
2.2
3
3
4
5.5
7.5
7.5
11
15
18.5
22
30
37
45
0.220.32
0.280.4
1.11.6
1.11.6
1.11.6
1.11.6
1.42
0.280.4
0.450.63
0.450.63
1.11.6
1.11.6
1.11.6
1.42
2.23.2
2.84
3.55
4.56.3
5.58
710
912.5
1420
1420
1825
2232
2840
4563
4563
5775
5775
80100
3RV1011-0DA10
3RV1011-0EA10
3RV1011-1AA10
3RV1011-1AA10
3RV1011-1AA10
3RV1011-1AA10
3RV1011-1BA10
3RV1021-0EA10
3RV1021-0GA10
3RV1021-0GA10
3RV1021-1AA10
3RV1021-1AA10
3RV1021-1AA10
3RV1021-1BA10
3RV1021-1DA10
3RV1021-1EA10
3RV1021-1FA10
3RV1021-1GA10
3RV1021-1HA10
3RV1021-1JA10
3RV1021-1KA10
3RV1021-4BA10
3RV1021-4BA10
3RV1031-4DA10
3RV1031-4EA10
3RV1031-4FA10
3RV1042-4JA10
3RV1042-4JA10
3RV1042-4KA10
3RV1042-4KA10
3RV1042-4MA10
3RT1015-1AP01
3RT1015-1AP01
3RT1015-1AP01
3RT1015-1AP01
3RT1015-1AP01
3RT1015-1AP01
3RT1015-1AP01
3RT1024-1AP00
3RT1024-1AP00
3RT1024-1AP00
3RT1024-1AP00
3RT1024-1AP00
3RT1024-1AP00
3RT1024-1AP00
3RT1024-1AP00
3RT1024-1AP00
3RT1024-1AP00
3RT1024-1AP00
3RT1024-1AP00
3RT1026-1AP00
3RT1026-1AP00
3RT1026-1AP00
3RT1026-1AP00
3RT1034-1AP00
3RT1034-1AP00
3RT1035-1AP00
3RT1054-1AP36
3RT1054-1AP36
3RT1054-1AP36
3RT1054-1AP36
3RT1054-1AP36
3RV1042-4JA10
3RV1042-4JA10
3RV1042-4KA10
3RV1042-4KA10
3RV1042-4LA10
3RV1042-4MA10
3RT1044-1AP00
3RT1044-1AP00
3RT1044-1AP00
3RT1045-1AP00
3RT1046-1AP00
3RT1046-1AP00
0.2
0.3
0.4
0.6
0.85
1.1
1.5
0.2
0.3
0.4
0.6
0.85
1.1
1.5
1.9
2.7
3.6
5
6.5
6.5
8.5
11.5
15.5
15.5
22
29
35
41
55
66
80
1
2
3
4
Size
Overload relay
Setting range
Overload relay
overload release
Short-circuit
breaking
capacity
Order No.
Iq
kA
S00
S00
S00
S00
S00
S00
S00
S0
S0
S0
S0
S0
S0
S0
S0
S0
S0
S0
S0
S0
S0
S0
S0
S2
S2
S2
S3/S6
S3/S6
S3/S6
S3/S6
S3/S6
3RB1016-1RB0
3RB1016-1RB0
3RB1016-1NB0
3RB1016-1NB0
3RB1016-1NB0
3RB1016-1NB0
3RB1016-1NB0
3RB1026-1RB0
3RB1026-1RB0
3RB1026-1RB0
3RB1026-1NB0
3RB1026-1NB0
3RB1026-1NB0
3RB1026-1NB0
3RB1026-1PB0
3RB1026-1PB0
3RB1026-1PB0
3RB1026-1PB0
3RB1026-1SB0
3RB1026-1SB0
3RB1026-1SB0
3RB1026-1QB0
3RB1026-1QB0
3RB1036-1QB0
3RB1036-1QB0
3RB1036-1UB0
3RB1046-1UB0
3RB1046-1UB0
3RB1056-1FG0
3RB1056-1FG0
3RB1056-1FG0
0.10.4
0.10.4
0.41.6
0.41.6
0.41.6
0.41.6
0.41.6
0.10.4
0.10.4
0.10.4
0.41.6
0.41.6
0.41.6
0.41.6
1.56.0
1.56.0
1.56.0
1.56.0
312
312
312
625
625
625
625
1350
1350
1350
50200
50200
50200
130
130
130
130
130
130
130
130
130
130
130
130
130
130
130
130
130
130
130
130
130
100
100
100
100
100
100
100
100
100
100
S3
S3
S3
S3
S3
S3
3RB1046-1UB0
3RB1046-1UB0
3RB1046-1EB0
3RB1046-1EB0
3RB1046-1EB0
3RB1046-1EB0
1350
1350
25100
25100
25100
25100
80
80
80
80
80
80
4
4
Nominal value at 400 V AC, 50 Hz for 4-pole standard motors. The specific starting and rated data of the motor to be protected are decisive when selecting devices.
The circuit-breaker should be set to the maximum current value.
Rated control supply voltage 230 V, 50 Hz. Other control voltages are also possible.
Stand-alone mounting.
15
AC 400 V
Standard three-phase motor
4-pole at 400 V AC 1
Rated
Motor current
power
(nominal value)
P
I
kW
A
0.06
0.2
0.12
0.4
0.18
0.6
0.25
0.85
0.37
1.1
0.55
1.5
0.75
1.9
1.1
2.7
1.5
3.6
2.2
5
3
6.5
0.06
0.2
0.09
0.3
0.12
0.4
0.18
0.6
0.25
0.85
0.37
1.1
0.55
1.5
0.75
1.9
1.1
2.7
1.5
3.6
2.2
5
3
6.5
4
8.5
5.5
11.5
7.5
15.5
11
22
15
29
18.5
35
22
41
30
55
37
66
45
80
55
97
75
132
90
160
90
160
110
195
110
195
132
230
160
280
160
280
200
350
200
350
250
430
1
2
3
4
5
16
6
7
8
Setting range
Circuitbreaker
overload
release 2
A
0.280.4
1.11.6
1.11.6
1.11.6
1.42
1.82.5
2.23.2
2.84
4.56.3
5.58
912
0.280.4
0.450.63
0.550.8
1.11.6
1.11.6
1.42
1.82.5
2.23.2
2.84
4.56.3
5.58
912.5
1420
1420
2232
2840
4563
4563
4563
5775
80100
without
without
without
without
without
without
without
without
without
without
without
without
without
Circuit-breaker
Contactor
Order No.
3RV1011-0EA10
3RV1011-1AA10
3RV1011-1AA10
3RV1011-1AA10
3RV1011-1BA10
3RV1011-1CA10
3RV1011-1DA10
3RV1011-1EA10
3RV1011-1GA10
3RV1011-1HA10
3RV1011-1KA10
3RV1021-0EA10
3RV1021-0GA10
3RV1021-0HA10
3RV1021-1AA10
3RV1021-1AA10
3RV1021-1BA10
3RV1021-1CA10
3RV1021-1DA10
3RV1021-1EA10
3RV1021-1GA10
3RV1021-1HA10
3RV1021-1KA10
3RV1021-4BA10
3RV1021-4BA10
3RV1031-4EA10
3RV1031-4FA10
3RV1041-4JA10
3RV1041-4JA10
3RV1041-4JA10
3RV1041-4KA10
3RV1041-4MA10
3VL2710-2DK33
3VL2710-2DK33 4
3VL2716-2DK33
3VL2716-2DK33 5
3VL3725-2DK36
3VL3725-2DK36
3VL3725-2DK36
3VL3725-2DK36 6
3VL4731-2DK36
3VL4731-2DK36
3VL5750-2DK36
3VL5750-2DK36
3VL5750-2DK36
Order No.
3RT1015-1AP01
3RT1015-1AP01
3RT1015-1AP01
3RT1015-1AP01
3RT1015-1AP01
3RT1015-1AP01
3RT1015-1AP01
3RT1015-1AP01
3RT1015-1AP01
3RT1015-1AP01
3RT1017-1AP01
3RT1024-1AP00
3RT1024-1AP00
3RT1024-1AP00
3RT1024-1AP00
3RT1024-1AP00
3RT1024-1AP00
3RT1024-1AP00
3RT1024-1AP00
3RT1024-1AP00
3RT1024-1AP00
3RT1024-1AP00
3RT1025-1AP00
3RT1025-1AP00
3RT1025-1AP00
3RT1034-1AP00
3RT1035-1AP00
3RT1044-1AP00
3RT1044-1AP00
3RT1044-1AP00
3RT1045-1AP00
3RT1046-1AP00
3RT1054-1AP36
3RT1055-6AP36
3RT1056-6AP36
3RT1064-6AP36
3RT1065-6AP36
3RT1066-6AP36
3RT1264-6AP36
3RT1265-6AP36
3RT1266-6AP36
3RT1075-6AP36
3RT1076-6AP36
3RT1275-6AP36
3RT1276-6AP36
Size
Overload relay
Setting range
Overload relay
overload release
Short-circuit
breaking
capacity
S00
S00
S00
S00
S00
S00
S00
S00
S00
S00
S00
S0
S0
S0
S0
S0
S0
S0
S0
S0
S0
S0
S0
S0
S0
S2
S2
S3
S3
S3
S3
S3
S6
S6
S6
S10
S10
S10
S10V
S10V
S10V
S12
S12
S12V
S12V
Order No.
3RB1016-2RB0
3RB1016-2NB0
3RB1016-2NB0
3RB1016-2NB0
3RB1016-2NB0
3RB1016-2NB0
3RB1016-2PB0
3RB1016-2PB0
3RB1016-2PB0
3RB1016-2SB0
3RB1016-2SB0
3RB1026-2RB0
3RB1026-2RB0
3RB1026-2RB0
3RB1026-2NB0
3RB1026-2NB0
3RB1026-2NB0
3RB1026-2NB0
3RB1026-2PB0
3RB1026-2PB0
3RB1026-2PB0
3RB1026-2SB0
3RB1026-2SB0
3RB1026-2QB0
3RB1026-2QB0
3RB1036-2QB0
3RB1036-2UB0
3RB1046-2UB0
3RB1046-2UB0
3RB1046-2UB0
3RB1046-2EB0
3RB1046-2EB0
3RB1056-2FG0
3RB1056-2FG0
3RB1056-2FG0
3RB1056-2FG0
3RB1056-2FG0
3RB1056-2FG0
3RB1056-2FG0
3RB1066-2GG0
3RB1066-2KG0
3RB1066-2KG0
3RB1066-2KG0
3RB1066-2KG0
3RB1066-2KG0
A
0.10.4
0.41.6
0.41.6
0.41.6
0.41.6
0.41.6
1.56.0
1.56.0
1.56.0
312
312
0.10.4
0.10.4
0.10.4
0.41.6
0.41.6
0.41.6
0.41.6
1.56.0
1.56.0
1.56.0
312
312
625
625
625
1350
1350
1350
1350
25100
25100
50200
50200
50200
50200
50200
50200
50200
55250
200540
200540
200540
200540
200540
Iq
kA
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
7
7
8
Nominal value at 400 V AC, 50 Hz for 4-pole standard motors. The specific starting and rated data of the motor to be protected are decisive when selecting devices.
The circuit-breaker should be set to the maximum current value.
Rated control supply voltage 230 V, 50 Hz. Other control voltages are also possible.
Alternatively, 3VL2716-2DK33 is possible.
Alternatively, 3VL3725-2DK36 is possible.
Alternatively, 3VL4731-2DK36 is possible.
Alternatively, 3RB1066-2GG0 is possible.
Alternatively, 3RB1066-2KG0 is possible.
V
it
AC 400 V
Standard three-phase motor
4-pole at 400 V AC 1
Rated
Motor current
power
(nominal value)
P
I
kW
A
Setting range
Circuitbreaker
overload
release 2
A
Circuit-breaker
Contactor
Overload relay
Setting range
Overload relay
overload release
Short-circuit
breaking
capacity
Order No.
Order No.
Order No.
Iq
kA
0.06
0.2
0.280.4
0.12
0.4
1.11.6
3RV1011-0EA10
3RT1015-1AP01 S00
3RB1016-2RB0
0.10.4
50
3RV1011-1AA10
3RT1015-1AP01 S00
3RB1016-2NB0
0.41.6
0.18
0.6
50
1.11.6
3RV1011-1AA10
3RT1015-1AP01 S00
3RB1016-2NB0
0.41.6
0.25
50
0.85
1.11.6
3RV1011-1AA10
3RT1015-1AP01 S00
3RB1016-2NB0
0.41.6
50
0.37
1.1
1.42
3RV1011-1BA10
3RT1015-1AP01 S00
3RB1016-2NB0
0.41.6
50
0.06
0.2
0.280.4
3RV1021-0EA10
3RT1024-1AP00 S0
3RB1026-2RB0
0.10.4
50
0.09
0.3
0.450.63
3RV1021-0GA10
3RT1024-1AP00 S0
3RB1026-2RB0
0.10.4
50
0.12
0.4
0.550.8
3RV1021-0HA10
3RT1024-1AP00 S0
3RB1026-2RB0
0.10.4
50
0.18
0.6
1.11.6
3RV1021-1AA10
3RT1024-1AP00 S0
3RB1026-2NB0
0.41.6
50
0.25
0.85
1.11.6
3RV1021-1AA10
3RT1024-1AP00 S0
3RB1026-2NB0
0.41.6
50
0.37
1.1
1.42
3RV1021-1BA10
3RT1024-1AP00 S0
3RB1026-2NB0
0.41.6
50
0.55
1.5
1.82.5
3RV1021-1CA10
3RT1024-1AP00 S0
3RB1026-2NB0
0.41.6
50
0.75
1.9
2.23.2
3RV1021-1DA10
3RT1024-1AP00 S0
3RB1026-2PB0
1.56.0
50
1.1
2.7
2.84
3RV1021-1EA10
3RT1024-1AP00 S0
3RB1026-2PB0
1.56.0
50
1.5
3.6
4.56.3
3RV1021-1GA10
3RT1024-1AP00 S0
3RB1026-2PB0
1.56.0
50
2.2
5.58
3RV1021-1HA10
3RT1024-1AP00 S0
3RB1026-2SB0
312
50
6.5
912.5
3RV1021-1KA10
3RT1026-1AP00 S0
3RB1026-2SB0
312
50
8.5
1420
3RV1021-4BA10
3RT1026-1AP00 S0
3RB1026-2QB0
625
50
5.5
11.5
1420
3RV1021-4BA10
3RT1026-1AP00 S0
3RB1026-2QB0
625
50
7.5
15.5
2232
3RV1031-4EA10
3RT1034-1AP00 S2
3RB1036-2QB0
625
50
11
22
2840
3RV1031-4FA10
3RT1035-1AP00 S2
3RB1036-2UB0
1350
50
Size
15
29
4563
3RV1041-4JA10
3RT1044-1AP00 S3
3RB1046-2UB0
1350
50
18.5
35
4563
3RV1041-4JA10
3RT1044-1AP00 S3
3RB1046-2UB0
1350
50
22
41
4563
3RV1041-4JA10
3RT1044-1AP00 S3
3RB1046-2UB0
1350
50
30
55
7090
3RV1041-4LA10
3RT1046-1AP00 S3
3RB1046-2EB0
25100
50
45
80
without
3VL2710-2DK33
3RT1054-1AP36 S6
3RB1056-2FG0
50200
50
55
97
without
3VL2710-2DK33
3RT1055-6AP36 S6
3RB1056-2FG0
50200
50
75
132
without
3VL2716-2DK33
3RT1056-6AP36 S6
3RB1056-2FG0
50200
50
90
160
without
3VL2716-2DK33
3RT1064-6AP36 S10
3RB1056-2FG0
50200
50
90
160
without
3VL3725-2DK36
3RT1065-6AP36 S10
3RB1056-2FG0
50200
50
110
195
without
3VL3725-2DK36
3RT1066-6AP36 S10
3RB1056-2FG0
50200
50
110
195
without
3VL3725-2DK36
3RT1264-6AP36 S10V
3RB1056-2FG0
50200
50
132
230
without
3VL3725-2DK36
3RT1265-6AP36 S10V
3RB1066-2GG0
55250
50
160
280
without
3VL4731-2DK36
3RT1266-6AP36 S10V
3RB1066-2KG0
200540
50
160
280
without
3VL4731-2DK36
3RT1075-6AP36 S12
3RB1066-2KG0
200540
50
200
350
without
3VL5750-2DK36
3RT1076-6AP36 S12
3RB1066-2KG0
200540
50
200
350
without
3VL5750-2DK36
3RT1275-6AP36 S12V
3RB1066-2KG0
200540
50
250
430
without
3VL5750-2DK36
3RT1276-6AP36 S12V
3RB1066-2KG0
200540
50
1
2
3
4
5
6
7
8
Nominal value at 400 V AC, 50 Hz for 4-pole standard motors. The specific starting and rated data of the motor to be protected are decisive when selecting devices.
The circuit-breaker should be set to the maximum current value.
Rated control supply voltage 230 V, 50 Hz. Other control voltages are also possible.
Alternatively, 3VL2716-2DK33 is possible.
Alternatively, 3VL3725-2DK36 is possible.
Alternatively, 3VL4731-2DK36 is possible.
Alternatively, 3RB1066-2GG0 is possible.
Alternatively, 3RB1066-2KG0 is possible.
17
AC 400 V
Standard three-phase motor
4-pole at 400 V AC 1
Rated
Motor current
power
(nominal value)
P
I
kW
A
Setting range
Circuitbreaker
overload
release 2
A
Circuit-breaker
Contactor
Overload relay
Setting range
Overload relay
overload release
Short-circuit
breaking
capacity
Order No.
Order No.
Order No.
Iq
kA
0.06
0.2
0.280.4
0.12
0.4
1.11.6
3RV1011-0EA10
3RT1015-1AP01 S00
3RB1016-2RB0
0.10.4
130
3RV1011-1AA10
3RT1015-1AP01 S00
3RB1016-2NB0
0.41.6
0.18
0.6
130
1.11.6
3RV1011-1AA10
3RT1015-1AP01 S00
3RB1016-2NB0
0.41.6
0.25
130
0.85
1.11.6
3RV1011-1AA10
3RT1015-1AP01 S00
3RB1016-2NB0
0.41.6
130
0.37
1.1
1.42
3RV1011-1BA10
3RT1015-1AP01 S00
3RB1016-2NB0
0.41.6
130
0.06
0.2
0.280.4
3RV1021-0EA10
3RT1024-1AP00 S0
3RB1026-2RB0
0.10.4
130
0.09
0.3
0.450.63
3RV1021-0GA10
3RT1024-1AP00 S0
3RB1026-2RB0
0.10.4
130
0.12
0.4
0.550.8
3RV1021-0HA10
3RT1024-1AP00 S0
3RB1026-2RB0
0.10.4
130
0.18
0.6
1.11.6
3RV1021-1AA10
3RT1024-1AP00 S0
3RB1026-2NB0
0.41.6
130
0.25
0.85
1.11.6
3RV1021-1AA10
3RT1024-1AP00 S0
3RB1026-2NB0
0.41.6
130
0.37
1.1
1.42
3RV1021-1BA10
3RT1024-1AP00 S0
3RB1026-2NB0
0.41.6
130
0.55
1.5
1.82.5
3RV1021-1CA10
3RT1024-1AP00 S0
3RB1026-2NB0
0.41.6
130
0.75
1.9
2.23.2
3RV1021-1DA10
3RT1024-1AP00 S0
3RB1026-2PB0
1.56.0
130
1.1
2.7
2.84
3RV1021-1EA10
3RT1024-1AP00 S0
3RB1026-2PB0
1.56.0
130
1.5
3.6
4.56.3
3RV1021-1GA10
3RT1024-1AP00 S0
3RB1026-2PB0
1.56.0
130
2.2
5.58
3RV1021-1HA10
3RT1024-1AP00 S0
3RB1026-2SB0
312
130
6.5
912.5
3RV1021-1KA10
3RT1026-1AP00 S0
3RB1026-2SB0
312
130
8.5
1420
3RV1021-4BA10
3RT1026-1AP00 S0
3RB1026-2QB0
625
100
5.5
11.5
1420
3RV1021-4BA10
3RT1026-1AP00 S0
3RB1026-2QB0
625
100
7.5
15.5
2232
3RV1031-4EA10
3RT1034-1AP00 S2
3RB1036-2QB0
625
100
11
22
2840
3RV1031-4FA10
3RT1035-1AP00 S2
3RB1036-2UB0
1350
100
15
29
4563
3RV1042-4JA10
3RT1054-1AP36 S3/S6
3RB1046-2UB0
1350
100
18.5
35
4563
3RV1042-4JA10
3RT1054-1AP36 S3/S6
3RB1046-2UB0
1350
100
22
41
4563
3RV1042-4JA10
3RT1054-1AP36 S3/S6
3RB1046-2UB0
1350
100
30
55
5775
3RV1042-4KA10
3RT1054-1AP36 S3/S6
3RB1056-2FG0
50200
100
37
66
80100
3RV1042-4MA10
3RT1054-1AP36 S3/S6
3RB1056-2FG0
50200
100
Size
29
4563
3RV1042-4JA10
3RT1044-1AP00 S3
3RB1046-2UB0
1350
80
18.5
35
4563
3RV1042-4JA10
3RT1044-1AP00 S3
3RB1046-2UB0
1350
80
22
41
4563
3RV1042-4JA10
3RT1044-1AP00 S3
3RB1046-2UB0
1350
80
30
55
5775
3RV1042-4KA10
3RT1045-1AP00 S3
3RB1046-2EB0
25100
80
37
66
80100
3RV1042-4MA10
3RT1046-1AP00 S3
3RB1046-2EB0
25100
80
18
2
3
4
Nominal value at 400 V AC, 50 Hz for 4-pole standard motors. The specific starting and rated data of the motor to be protected are decisive when selecting devices.
The circuit-breaker should be set to the maximum current value.
Rated control supply voltage 230 V, 50 Hz. Other control voltages are also possible.
Stand-alone mounting.
Circuit-breaker + contactor +
3RB12 electronic overload relay / SIMOCODE-DP 3UF5
CLASS 10, coordination type 2, Iq 50/100 kA
AC 400 V
V
t
Setting range
Circuitbreaker
overload
release
A
Circuit-breaker
Contactor
Order No.
Order No.
Size
Overload relay
Setting range
Overload relay
overload
release
Order No.
A
1.256.3
No. of
primary
windings
Shortcircuit
breaking
capacity
Iq
kA
130
0.09
0.3
without
3RV1321-0HC10 3RT1024-1AP00 S0
3RB1246-1PM00
0.12
0.4
without
3RV1321-0HC10 3RT1024-1AP00 S0
or
130
0.18
0.6
without
3RV1321-0JC10
3RT1024-1AP00 S0
3UF5001-3AN00-1
130
0.25
0.85
without
3RV1321-0KC10
3RT1024-1AP00 S0
130
0.37
1.1
without
3RV1321-1AC10 3RT1024-1AP00 S0
130
0.55
1.5
without
3RV1321-1AC10 3RT1024-1AP00 S0
130
0.75
1.9
without
3RV1321-1BC10
3RT1024-1AP00 S0
130
1.1
2.7
without
3RV1321-1DC10 3RT1024-1AP00 S0
130
1.5
3.5
without
3RV1321-1EC10
3RT1024-1AP00 S0
130
2.2
without
3RV1321-1GC10 3RT1024-1AP00 S0
130
6.5
without
3RV1321-1HC10 3RT1024-1AP00 S0
3RB1246-1QM00
130
8.5
without
3RV1321-1JC10
3RT1026-1AP00 S0
or
6.325
130
5.5
11.5
without
3RV1321-1KC10
3RT1026-1AP00 S0
3UF5011-3AN00-1
130
7.5
15.5
without
3RV1331-4EC10
3RT1034-1AP00 S2
100
11
22
2232
3RV1031-4EA10 3RT1034-1AP00 S2
100
15
29
4050
3RV1031-4HA10 3RT1036-1AP00 S2
3RB1246-1EM00
100
18.5
35
without
3RV1341-4JC10
3RT1044-1AP00 S3
or
50
22
41
without
3RV1341-4JC10
3RT1044-1AP00 S3
3UF5021-3AN00-1
50
30
55
without
3RV1341-4JC10
3RT1044-1AP00 S3
50
37
66
without
3RV1341-4KC10
3RT1045-1AP00 S3
50
45
80
without
3RV1341-4LC10
3RT1046-1AP00 S3
50
55
97
without
3VL2710-2DK33 4 3RT1054-1AP36 S6
3RB1253-0FM00
50
75
132
without
3VL2716-2DK33
or
90
160
without
3VL3725-2DK36 4 3RT1056-6AP36 S6
3UF5031-3AN00-1
3RT1055-6AP36 S6
25100
50205
50
50
50
50
110
195
without
3RB1257-0KM00
110
195
without
or
132
230
without
3VL4725-2DK36
3UF5041-3AN00-1
50
132
230
without
50
160
280
without
3VL4731-2DK36
3RT1066-6AP36 S10
50
160
280
without
3VL4731-2DK36
3RT1266-6AP36 S10V
50
200
350
without
3VL5750-2DK36
3RT1075-6AP36 S12
50
200
350
without
3VL5750-2DK36
3RT1275-6AP36 S12V
50
250
430
without
3VL5750-2DK36
3RT1076-6AP36 S12
50
250
430
without
3VL5750-2DK36
3RT1276-6AP36 S12V
50
1
2
3
4
5
6
7
3RT1065-6AP36 S10
125500
Nominal value at 400 V AC, 50 Hz for 4-pole standard motors. The specific starting and rated data of the motor to be protected are decisive when selecting devices.
The circuit-breaker should be set to the maximum current value.
Rated control supply voltage 230 V, 50 Hz. Other control voltages are also possible.
Alternatively, 3VL2716-2DK33 is possible.
Alternatively, 3VL2725-2DK36 is possible.
Alternatively, 3VL4731-2DK36 is possible.
Alternatively, 3RB1257-0KM00 or 3UF5041-3AN00-1 is possible.
19
Circuit-breaker + contactor +
3RB12 electronic overload relay / SIMOCODE-DP 3UF5
CLASS 20, coordination type 2, Iq 50/100 kA
AC 400 V
Standard three-phase motor
4-pole at 400 V AC 1
Rated
Motor current
power
(nominal value)
P
I
kW
A
Circuit-breaker
Contactor
Order No.
Order No.
Size
Overload relay
Setting range
Overload relay
overload
release
Order No.
A
1.256.3
No. of
primary
windings
Shortcircuit
breaking
capacity
Iq
kA
0.09
0.3
without
3RV1321-0HC10 3RT1024-1AP00 S0
3RB1246-1PM00
130
0.12
0.4
without
3RV1321-0HC10 3RT1024-1AP00 S0
or
130
0.18
0.6
without
3RV1321-0HC10 3RT1024-1AP00 S0
3UF5001-3AN00-1
130
0.25
0.85
without
3RV1321-0KC10
3RT1024-1AP00 S0
130
0.37
1.1
without
3RV1321-1AC10 3RT1024-1AP00 S0
130
0.55
1.5
without
3RV1321-1CC10
3RT1024-1AP00 S0
130
0.75
1.9
without
3RV1321-1DC10 3RT1024-1AP00 S0
130
1.1
2.7
without
3RV1321-1EC10
3RT1024-1AP00 S0
130
1.5
3.5
without
3RV1321-1GC10 3RT1024-1AP00 S0
130
2.2
without
3RV1321-1HC10 3RT1024-1AP00 S0
130
6.5
without
3RV1321-1JC10
3RT1026-1AP00 S0
3RB1246-1QM00
130
8.5
without
3RV1331-4BC10
3RT1034-1AP00 S2
or
100
5.5
11.5
2232
3RV1031-4EA10 3RT1034-1AP00 S2
3UF5011-3AN00-1
100
7.5
15.5
2232
3RV1031-4EA10 3RT1034-1AP00 S2
100
11
22
4050
3RV1031-4HA10 3RT1036-1AP00 S2
100
6.325
15
29
without
3RV1341-4JC10
3RT1044-1AP00 S3
3RB1246-1EM00
50
18.5
35
without
3RV1341-4JC10
3RT1044-1AP00 S3
or
50
22
41
5775
3RV1041-4KA10 3RT1044-1AP00 S3
3UF5021-3AN00-1
50
30
55
80100
45
80
55
97
25100
3RV1041-4MA10 3RT1046-1AP00 S3
50
without
3VL2710-2DK33
50
without
3VL2710-2DK33
50
50
3RT1054-1AP36 S6
4
3RT1055-1AP36 S6
3RB1253-0FM00
3RT1056-6AP36 S6
or
3RT1064-6AP36 S10
3UF5031-3AN00-1
50
50
50205
75
132
without
3VL2716-2DK33
90
160
without
3VL2716-2DK33
90
160
without
110
195
without
3VL3725-2DK36
3RT1066-6AP36 S10
50
110
195
without
3VL3725-2DK36
3RT1264-6AP36 S10V
50
132
230
without
3VL3725-2DK36
3RT1265-6AP36 S10V
50
160
280
without
or
50
160
280
without
3VL4731-2DK36
3RT1075-6AP36 S12
3UF5041-3AN00-1
50
200
350
without
3VL5750-2DK36
3RT1076-6AP36 S12
50
200
350
without
3VL5750-2DK36
3RT1275-6AP36 S12V
50
250
430
without
3VL5750-2DK36
3RT1276-6AP36 S12V
50
1
2
3
4
20
Setting range
Circuitbreaker
overload
release
A
5
6
7
3RB1257-0KM00
125500
Nominal value at 400 V AC, 50 Hz for 4-pole standard motors. The specific starting and rated data of the motor to be protected are decisive when selecting devices.
The circuit-breaker should be set to the maximum current value.
Rated control supply voltage 230 V, 50 Hz. Other control voltages are also possible.
Alternatively, 3VL2716-2DK33 is possible.
Alternatively, 3VL3725-2DK36 is possible.
Alternatively, 3VL4731-2DK36 is possible.
Alternatively, 3RB1257-0KM00 or 3UF5041-3AN00-1 is possible.
Circuit-breaker + contactor +
3RB12 electronic overload relay / SIMOCODE-DP 3UF5
CLASS 30, coordination type 2, Iq 50/100 kA
V
g
AC 400 V
Standard three-phase motor
4-pole at 400 V AC 1
Rated
Motor current
power
(nominal value)
P
I
kW
A
Setting range
Circuitbreaker
overload
release 2
A
Circuit-breaker
Contactor
Overload relay
Setting range
Overload relay
overload
release
Order No.
Order No.
Order No.
A
1.256.3
Size
No. of
primary
windings
Shortcircuit
breaking
capacity
Iq
kA
0.12
0.4
1.11.6
3RV1021-1AA10
3RT1024-1AP00 S0
3RB1246-1PM00
130
0.18
0.6
1.42.0
3RV1021-1BA10
3RT1024-1AP00 S0
or
130
0.25
0.85
1.82.5
3RV1021-1CA10
3RT1024-1AP00 S0
3UF5001-3AN00-1
130
0.37
1.1
2.23.2
3RV1021-1DA10
3RT1024-1AP00 S0
130
0.55
1.5
2.84
3RV1021-1EA10
3RT1024-1AP00 S0
130
0.75
1.9
3.55
3RV1021-1FA10
3RT1026-1AP00 S0
130
1.1
2.7
4.56.3
3RV1021-1GA10
3RT1026-1AP00 S0
130
1.5
3.5
710
3RV1021-1JA10
3RT1026-1AP00 S0
130
2.2
912.5
3RV1021-1KA10
3RT1026-1AP00 S0
130
6.5
1116
3RV1031-4AA10
3RT1034-1AP00 S2
3RB1246-1QM00
100
6.325
8.5
1420
3RV1031-4BA10
3RT1034-1AP00 S2
or
100
5.5
11.5
2232
3RV1031-4EA10
3RT1034-1AP00 S2
3UF5011-3AN00-1
100
7.5
15.5
2840
3RV1031-4FA10
3RT1035-1AP00 S2
100
11
22
4050
3RV1031-4HA10
3RT1036-1AP00 S2
100
15
29
5775
3RV1041-4KA10
3RT1044-1AP00 S3
3RB1246-1EM00
50
18.5
35
7090
3RV1041-4LA10
3RT1045-1AP00 S3
or
50
22
41
80100
3RV1041-4MA10 3RT1046-1AP00 S3
3UF5021-3AN00-1
50
30
66
without
3VL2710-2DK33
3RT1054-1AP36 S6
37
66
without
3VL2710-2DK33
3RT1054-1AP36 S6
45
80
without
3VL2710-2DK33
3RT1055-6AP36 S6
55
97
without
3VL2710-2DK33 4 3RT1056-6AP36 S6
3RB1253-0FM00
75
132
without
3VL2716-2DK33
90
160
without
90
160
without
110
195
without
3VL3725-2DK36
132
230
without
3RT1064-6AP36 S10
3RT1265-6AP36 S10V
5
25100
25100
50
50
50
50
or
50
3UF5031-3AN00-1
50
50
50
50
50205
3RB1253-0FM00 6
3RB1257-0KM00
125500
132
230
without
3VL3725-2DK36
3RT1075-6AP36 S12
or
50
160
280
without
3VL4731-2DK36
3RT1076-6AP36 S12
3UF5041-3AN00-1
50
160
280
without
3VL4731-2DK36
3RT1275-6AP36 S12
50
200
350
without
3VL5750-2DK36
3RT1276-6AP36 S12
50
1
2
3
4
5
6
Nominal value at 400 V AC, 50 Hz for 4-pole standard motors. The specific starting and rated data of the motor to be protected are decisive when selecting devices.
The circuit-breaker should be set to the maximum current value.
Rated control supply voltage 230 V, 50 Hz. Other control voltages are also possible.
Alternatively, 3VL2716-2DK33 is possible.
Alternatively, 3VL4731-2DK36 is possible.
Alternatively, 3RB1257-0KM00 or 3UF5041-3AN00-1 is possible.
21
AC 400 V
Standard three-phase motor
4-pole at 400 V AC 1
Rated
Motor current
power
(nominal value)
P
In
Setting range
Circuitbreaker
overload
release
Circuit-breaker
kW
Order No.
Order No.
Order No.
5.5
11.5
912
3RV1011-1KA10
3RU1116-1HB0 5.58
7.5
15.5
without
3RV1321-4BC10
Contactors
Size
Line contactor
+ delta
contactor
Overload relay
Star contactor
Setting
range
Overload
relay
overload
release
A
710
Iq
kA
50
50
11
22
without
3RV1321-4DC10
3RT1024-1AP00 3RT1024-1AP00 S0
3RU1126-4AB0 1116
50
15
29
without
3RV1331-4FC10
3RU1126-4BB0
1420
50
18.5
35
without
3RV1331-4FC10
3RU1126-4DB0 2025
50
22
41
without
3RV1331-4GC10
3RU1136-4EB0
2232
50
30
55
without
3RV1341-4JC10
2840
50
37
66
without
3RV1341-4KC10
3RU1136-4GB0 3645
50
45
80
without
3RV1341-4LC10
3RU1136-4HB0 4050
50
22
Short-circuit
breaking
capacity
Setting range
Circuitbreaker
overload
release
Circuit-breaker
kW
Order No.
AC 400 V
Contactors
Size
Line contactor
+ delta
contactor
Overload relay
Star contactor
Order No.
Order No.
Setting
range
Overload
relay
overload
release
A
Short-circuit
breaking
capacity
Iq
kA
5.5
11.5
without
3RV1321-4AC10
3RT1026-1AP00 3RT1024-1AP00 S0
3RU1126-1HB0 5.58
50
7.5
15.5
without
3RV1321-4BC10
3RT1026-1AP00 3RT1024-1AP00 S0
3RU1126-1JB0
50
11
22
without
3RV1331-4DC10
3RU1136-4AB0 1116
710
50
15
29
without
3RV1331-4FC10
3RU1136-4BB0
1420
50
18.5
35
without
3RV1331-4FC10
3RU1136-4DB0 1825
50
22
41
without
3RV1331-4GC10
3RU1136-4EB0
2232
50
30
55
without
3RV1341-4JC10
3RU1146-4FB0
2840
50
37
66
without
3RV1341-4KC10
3RU1146-4HB0 3650
50
45
80
without
3RV1341-4LC10
3RU1146-4JB0
50
1
2
3
4563
Nominal value at 400 V AC, 50 Hz for 4-pole standard motors. The specific starting and rated data of the motor to be protected are decisive when selecting devices.
The circuit-breaker should be set to the maximum current value.
Rated control supply voltage 230 V, 50 Hz. Other control voltages are also possible.
AC 400 V
V
t
Setting range
Circuitbreaker
overload
release
Circuit-breaker
Contactors
Size
kW
Order No.
Order No.
5.5
11.5
1420
3RV1021-4BA10
3RT1024-1AP00 3RT1024-1AP00 S0
Line contactor
+ delta
contactor
Overload relay
Short-circuit
breaking
capacity
Order No.
Setting
range
Overload
relay
overload
release
A
3RB1026-1QB0
625
50
Star contactor
Iq
kA
7.5
15.5
1420
3RV1021-4BA10
3RT1024-1AP00 3RT1024-1AP00 S0
11
22
2232
3RV1031-4EA10
3RB1036-1QB0
625
50
15
29
2840
3RV1031-1FA10
3RB1036-1UB0
1350
50
18.5
35
4563
3RV1041-4JA10
3RB1046-1UB0
1350
50
3RB1046-1EB0
25100
22
41
4563
3RV1041-4JA10
30
55
5775
3RV1041-4KA10
37
66
5775
3RV1041-4KA10
45
80
80100
55
97
without
75
132
without
3VL2716-2DK33
90
160
without
3VL2716-2DK33
50
50
50
50
50
3RB1056-1FG0
50200
50
50
50
110
195
without
3VL3725-2DK36
132
230
without
50
160
280
without
3VL4731-2DK36
50
200
350
without
3VL5750-2DK36
250
430
without
3VL5750-2DK36
50
50
200540
50
1
2
3
4
5
6
Nominal value at 500 V AC, 50 Hz for 4-pole standard motors. The specific starting and rated data of the motor to be protected are decisive when selecting devices.
Rated control supply voltage 230 V, 50 Hz. Other control voltages are also possible.
The circuit-breaker should be set to the maximum current value.
Alternatively, 3VL2716-2DK33 is possible.
Alternatively, 3VL3725-2DK36 is possible.
Alternatively, 3VL4731-2DK36 is possible.
23
AC 400 V
Standard three-phase motor
4-pole at 400 V AC 1
Rated
Motor current
power
(nominal value)
P
In
Setting range
Circuitbreaker
overload
release
Circuit-breaker
kW
Order No.
Order No.
Order No.
5.5
11.5
without
3RV1321-1KC10
3RT1026-1AP00 3RT1024-1AP00 S0
3RB1246-1QM00 6.325
50
7.5
15.5
without
50
11
22
15
29
18.5
35
without
Size
Line contactor
+ delta
contactor
Overload relay
Star contactor
Setting
range
Overload
relay
overload
release
A
Short-circuit
breaking
capacity
Iq
kA
3RV1331-4EC10
or
2232
3RV1031-4EA10
3UF5011-3AN00-1
4050
3RV1031-4HA10
50
3RV1341-4JC10
50
50
22
41
without
3RV1341-4JC10
30
55
without
3RV1341-4JC10
3RB1246-1EM00 25100
50
37
66
without
3RV1341-4KC10
or
50
45
80
without
3RV1341-4LC10
3UF5021-3AN00-1
50
55
97
without
3VL2710-2DK33
75
132
without
3VL2716-2DK33
90
160
without
110
195
without
3VL3725-2DK36
132
230
without
50
160
280
without
3VL4731-2DK36
50
200
350
without
3VL5750-2DK36
50
250
430
without
3VL5750-2DK36
50
1
2
3
24
Contactors
4
5
6
50
3RB1253-0FM00 50205
50
or
50
3UF5031-3AN00-1
50
50
Nominal value at 500 V AC, 50 Hz for 4-pole standard motors. The specific starting and rated data of the motor to be protected are decisive when selecting devices.
Rated control supply voltage 230 V, 50 Hz. Other control voltages are also possible.
The circuit-breaker should be set to the maximum current value.
Alternatively, 3VL2716-2DK33 is possible.
Alternatively, 3VL3725-2DK36 is possible.
Alternatively, 3VL4731-2DK36 is possible.
Circuit-breaker + contactor
CLASS 10, coordination type 1, Iq = 50 kA
AC 500 V
V
t
Setting range
Circuitbreaker
overload
release
Circuit-breaker
kW
Order No.
Order No.
0.06
0.09
0.12
0.12
0.18
0.18
0.25
0.37
0.55
0.75
0.75
1.1
1.5
2.2
3
4
5.5
7.5
7.5
11
15
18.5
22
30
30
37
45
55
75
90
110
132
132
160
160
200
200
250
250
315
315
355
355
0.16
0.24
0.32
0.32
0.48
0.48
0.68
0.88
1.2
1.5
1.5
2.2
2.9
4.0
5.2
6.8
9.2
12.4
12.4
17.6
23
28
33
44
44
53
64
78
106
128
156
184
184
224
224
280
280
344
344
432
432
488
488
0.140.2
0.180.25
0.220.32
0.280.4
0.350.5
0.450.63
0.550.8
0.71
0.91.25
1.11.6
1.42
1.82.5
2.23.2
3.55
4.56.3
5.58
710
912.5
1116
1420
1825
2232
2840
3645
4050
4563
5775
7090
64160
64160
64160
80200
80200
100250
100250
125315
125315
200500
200500
200500
200500
200500
200500
3RV1011-0BA10
3RV1011-0CA10
3RV1011-0DA10
3RV1011-0EA10
3RV1011-0FA10
3RV1011-0GA10
3RV1011-0HA10
3RV1011-0JA10
3RV1011-0KA10
3RV1011-1AA10
3RV1011-1BA10
3RV1011-1CA10
3RV1011-1DA10
3RV1011-1FA10
3RV1011-1GA10
3RV1011-1HA10
3RV1011-1JA10
3RV1021-1KA10
3RV1021-4AA10
3RV1021-4BA10
3RV1031-4DA10
3RV1031-4EA10
3RV1031-4FA10
3RV1031-4GA10
3RV1031-4HA10
3RV1041-4JA10
3RV1041-4KA10
3RV1041-4LA10
3VL2716-2AP33
3VL2716-2AP33
3VL2716-2AP33 3
3VL3720-2AP36 4
3VL3720-2AP36 4
3VL3725-2AP36 5
3VL3725-2AP36 5
3VL4731-2AP36
3VL4731-2AP36
3VL5750-2AP36
3VL5750-2AP36
3VL5750-2AP36
3VL5750-2AP36
3VL5750-2AP36
3VL5750-2AP36
3RT1015-1AP01
3RT1015-1AP01
3RT1015-1AP01
3RT1015-1AP01
3RT1015-1AP01
3RT1015-1AP01
3RT1015-1AP01
3RT1015-1AP01
3RT1015-1AP01
3RT1015-1AP01
3RT1015-1AP01
3RT1015-1AP01
3RT1015-1AP01
3RT1015-1AP01
3RT1015-1AP01
3RT1016-1AP01
3RT1017-1AP01
3RT1025-1AP00
3RT1025-1AP00
3RT1026-1AP00
3RT1034-1AP00
3RT1034-1AP00
3RT1035-1AP00
3RT1036-1AP00
3RT1036-1AP00
3RT1044-1AP00
3RT1044-1AP00
3RT1045-1AP00
3RT1054-6AP36
3RT1055-6AP36
3RT1056-6AP36
3RT1064-6AP36
3RT1264-6AP36
3RT1065-6AP36
3RT1265-6AP36
3RT1066-6AP36
3RT1266-6AP36
3RT1075-6AP36
3RT1275-6AP36
3RT1076-6AP36
3RT1276-6AP36
3RT1076-6AP36
3RT1276-6AP36
1
2
3
4
5
Contactors
Iq
kA
S00
S00
S00
S00
S00
S00
S00
S00
S00
S00
S00
S00
S00
S00
S00
S00
S00
S0
S0
S0
S2
S2
S2
S2
S2
S3
S3
S3
S6
S6
S6
S10
S10V
S10
S10V
S10
S10V
S12
S12V
S12
S12V
S12
S12V
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
Nominal value at 500 V AC, 50 Hz for 4-pole standard motors. The specific starting and rated data of the motor to be protected are decisive when selecting devices.
Rated control supply voltage 230 V, 50 Hz. Other control voltages are also possible.
Alternatively, 3VL3720-2AP36 is possible.
Alternatively, 3VL3725-2AP36 is possible.
Alternatively, 3VL4731-2AP36 is possible.
25
Circuit-breaker + contactor
CLASS 10, coordination type 2, Iq = 50 kA
AC 500 V
Standard three-phase motor
4-pole at 500 V AC 1
Rated
Motor current
power
(nominal value)
P
In
Setting range
Circuitbreaker
overload
release
Circuit-breaker
kW
Order No.
Order No.
0.06
0.09
0.12
0.12
0.18
0.18
0.25
0.37
0.55
0.75
0.75
1.1
1.5
2.2
3
4
5.5
7.5
7.5
11
15
18.5
22
30
30
37
45
55
75
90
110
132
132
160
160
200
200
250
250
315
315
355
355
0.16
0.24
0.32
0.32
0.48
0.48
0.68
0.88
1.2
1.5
1.5
2.2
2.9
4.0
5.2
6.8
9.2
12.4
12.4
17.6
23
28
33
44
44
53
64
78
106
128
156
184
184
224
224
280
280
344
344
432
432
488
488
0.140.2
0.180.25
0.220.32
0.280.4
0.350.5
0.450.63
0.550.8
0.71
0.91.25
1.11.6
1.42
1.82.5
2.23.2
3.55
4.56.3
5.58
710
912.5
1116
1420
1825
2232
2840
3645
4050
4563
5775
7090
64160
64160
64160
80200
80200
100250
100250
125315
125315
200500
200500
200500
200500
200500
200500
3RV1011-0BA10
3RV1011-0CA10
3RV1011-0DA10
3RV1011-0EA10
3RV1011-0FA10
3RV1011-0GA10
3RV1011-0HA10
3RV1011-0JA10
3RV1011-0KA10
3RV1011-1AA10
3RV1021-1BA10
3RV1021-1CA10
3RV1021-1DA10
3RV1021-1FA10
3RV1021-1GA10
3RV1021-1HA10
3RV1021-1JA10
3RV1021-1KA10
3RV1031-4AA10
3RV1031-4BA10
3RV1031-4DA10
3RV1031-4EA10
3RV1031-4FA10
3RV1031-4GA10
3RV1031-4HA10
3RV1041-4JA10
3RV1041-4KA10
3RV1041-4LA10
3VL2716-2AP33
3VL2716-2AP33 3
3VL2716-2AP33 4
3VL3720-2AP36 4
3VL3720-2AP36 5
3VL3725-2AP36 5
3VL3725-2AP36
3VL4731-2AP36
3VL4731-2AP36
3VL5750-2AP36
3VL5750-2AP36
3VL5750-2AP36
3VL5750-2AP36
3VL5750-2AP36
3VL5750-2AP36
3RT1015-1AP01
3RT1015-1AP01
3RT1015-1AP01
3RT1015-1AP01
3RT1015-1AP01
3RT1015-1AP01
3RT1015-1AP01
3RT1015-1AP01
3RT1015-1AP01
3RT1015-1AP01
3RT1024-1AP00
3RT1026-1AP00
3RT1034-1AP00
3RT1034-1AP00
3RT1034-1AP00
3RT1034-1AP00
3RT1034-1AP00
3RT1034-1AP00
3RT1034-1AP00
3RT1034-1AP00
3RT1034-1AP00
3RT1034-1AP00
3RT1035-1AP00
3RT1036-1AP00
3RT1036-1AP00
3RT1044-1AP00
3RT1044-1AP00
3RT1045-1AP00
3RT1054-1AP36
3RT1055-6AP36
3RT1056-6AP36
3RT1064-6AP36
3RT1264-6AP36
3RT1065-6AP36
3RT1265-6AP36
3RT1066-6AP36
3RT1266-6AP36
3RT1075-6AP36
3RT1276-6AP36
3RT1076-6AP36
3RT1276-6AP36
3RT1076-6AP36
3RT1276-6AP36
1
2
26
3
4
5
Contactors
Size
Overload relay
breaking
capacity
Iq
kA
S00
S00
S00
S00
S00
S00
S00
S00
S00
S00
S0
S0
S0/S2
S0/S2
S0/S2
S0/S2
S0/S2
S0/S2
S2
S2
S2
S2
S2
S2
S2
S3
S3
S3
S6
S6
S6
S10
S10V
S10
S10V
S10
S10V
S12
S12V
S12
S12V
S12
S12V
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
Nominal value at 500 V AC, 50 Hz for 4-pole standard motors. The specific starting and rated data of the motor to be protected are decisive when selecting devices.
Rated control supply voltage 230 V, 50 Hz. Other control voltages are also possible.
Alternatively, 3VL3720-2AS36 is possible.
Alternatively, 3VL3725-2AS36 is possible.
Alternatively, 3VL4731-2AS36 is possible.
Circuit-breaker + contactor
CLASS 20, coordination type 2, Iq = 50 kA
AC 500 V
Standard three-phase motor
4-pole at 500 V AC 1
Rated
Motor current
power
(nominal value)
Setting range
Circuitbreaker
Circuit-breaker
Contactor
P
kW
I
A
release
A
Order No.
Order No.
7.5
12.4
1116
3RV1031-4AB10
3RT1034-1AP00
S2
50
11
17.6
1420
3RV1031-4BB10
3RT1034-1AP00
S2
50
11
17.6
1825
3RV1031-4DB10
3RT1034-1AP00
S2
50
15
23
2232
3RV1031-4EB10
3RT1035-1AP00
S2
50
18.5
28
2232
3RV1031-4EB10
3RT1044-1AP00
S2/S3
50
18.5
28
2840
3RV1042-4FB10
3RT1044-1AP00
S3
50
22
33
2840
3RV1042-4FB10
3RT1044-1AP00
S3
50
30
44
3650
3RV1042-4HB10
3RT1044-1AP00
S3
50
30
44
4563
3RV1042-4JB10
3RT1044-1AP00
S3
50
37
53
4563
3RV1042-4JB10
3RT1045-1AP00
S3
50
37
53
5775
3RV1042-4KB10
3RT1045-1AP00
S3
50
45
64
5775
3RV1042-4KB10
3RT1054-1AP36
S3/S6
50
55
79
7090
3RV1042-4LB10
3RT1054-1AP36
S3/S6
50
75
106
64160
3VL2716-2AS33
3RT1055-6AP36
S6
50
90
128
64160
3VL2716-2AS33
3RT1056-6AP36
S6
50
110
156
64160
3VL2716-2AS33 3 3RT1064-6AP36
S10
50
132
184
80200
3VL3720-2AS36 4 3RT1065-6AP36
S10
50
Size
Short-circuit
breaking
capacity
overload
132
184
80200
3VL3720-2AS36 4
S10
50
132
184
80200
3VL3720-2AS36 4 3RT1264-6AP36
S10V
50
160
224
100250
3VL3725-2AS36 5 3RT1265-6AP36
S10V
50
200
280
125315
3VL4731-2AS36
3RT1266-6AP36
S10V
50
200
280
125315
3VL4731-2AS36
3RT1075-6AP36
S12
50
250
344
200500
3VL5750-2AS36
3RT1076-6AP36
S12
50
250
344
200500
3VL5750-2AS36
3RT1275-6AP36
S12V
50
315
432
200500
3VL5750-2AS36
3RT1276-6AP36
S12V
50
255
488
200500
3VL5750-2AS36
3RT1276-6AP36
S12V
50
1
2
3
4
5
3RT1066-6AP36
Iq
kA
Nominal value at 500 V AC, 50 Hz for 4-pole standard motors. The specific starting and rated data of the motor to be protected are decisive when selecting devices.
Rated control supply voltage 230 V, 50 Hz. Other control voltages are also possible.
Alternatively, 3VL3720-2AS36 is possible.
Alternatively, 3VL3725-2AS36 is possible.
Alternatively, 3VL4731-2AS36 is possible.
27
AC 500 V
Standard three-phase motor
4-pole at 500 V AC 1
Rated
Motor current
power
(nominal value)
P
I
kW
A
Setting range
Circuitbreaker
overload
release
A
Circuit-breaker
Contactor
Order No.
Order No.
0.06
without
3RV1321-0BC10
3RT1015-1AP01
0.16
Size
Overload relay
Setting range
Overload relay
overload release
Short-circuit
breaking
capacity
Order No.
Iq
kA
0.140.2
50
S0/S00 3RU1116-0BB0
0.09
0.24
without
3RV1321-0CC10
3RT1015-1AP01
S0/S00 3RU1116-0CB0
0.180.25
50
0.12
0.32
without
3RV1321-0DC10
3RT1015-1AP01
S0/S00 3RU1116-0DB0
0.220.32
50
0.12
0.32
without
3RV1321-0EC10
3RT1015-1AP01
S0/S00 3RU1116-0EB0
0.280.4
50
0.18
0.48
without
3RV1321-0FC10
3RT1015-1AP01
S0/S00 3RU1116-0FB0
0.350.5
50
0.18
0.48
without
3RV1321-0GC10
3RT1015-1AP01
S0/S00 3RU1116-0GB0
0.450.63
50
0.25
0.68
without
3RV1321-0HC10
3RT1015-1AP01
S0/S00 3RU1116-0HB0
0.550.8
50
0.37
0.88
without
3RV1321-0JC10
3RT1015-1AP01
S0/S00 3RU1116-0JB0
0.71
50
0.55
1.2
without
3RV1321-0KC10
3RT1015-1AP01
S0/S00 3RU1116-0KB0
0.91.25
50
0.75
1.5
without
3RV1321-1AC10
3RT1015-1AP01
S0/S00 3RU1116-1AB0
1.11.6
50
0.75
1.5
without
3RV1321-1BC10
3RT1015-1AP01
S0/S00 3RU1116-1BB0
1.42
50
1.1
2.2
without
3RV1321-1CC10
3RT1015-1AP01
S0/S00 3RU1116-1CB0
1.82.5
50
1.5
2.9
without
3RV1321-1DC10
3RT1015-1AP01
S0/S00 3RU1116-1DB0
2.23.2
50
2.2
4.0
without
3RV1321-1FC10
3RT1015-1AP01
S0/S00 3RU1116-1FB0
3.55
50
5.2
without
3RV1321-1GC10
3RT1015-1AP01
S0/S00 3RU1116-1GB0
4.56.3
50
6.8
without
3RV1321-1HC10
3RT1016-1AP01
S0/S00 3RU1116-1HB0
5.58
50
5.5
9.2
without
3RV1321-1JC10
3RT1017-1AP01
S0/S00 3RU1116-1JB0
710
50
7.5
12.4
without
3RV1321-1KC10
3RT1025-1AP00
S0
3RU1126-1KB0
912.5
50
7.5
12.4
without
3RV1321-4AC10
3RT1025-1AP00
S0
3RU1126-4AB0
1116
50
11
17.6
without
3RV1321-4BC10
3RT1026-1AP00
S0
3RU1126-4BB0
1420
50
15
23
without
3RV1331-4DC10
3RT1034-1AP00
S2
3RU1136-4DB0
1825
50
18.5
28
without
3RV1331-4EC10
3RT1034-1AP00
S2
3RU1136-4EB0
2232
50
22
33
without
3RV1331-4FC10
3RT1035-1AP00
S2
3RU1136-4FB0
2840
50
30
44
without
3RV1331-4GC10
3RT1036-1AP00
S2
3RU1136-4GB0
3645
50
30
44
without
3RV1331-4HC10
3RT1036-1AP00
S2
3RU1136-4HB0
4050
50
37
53
without
3RV1341-4JC10
3RT1044-1AP00
S3
3RU1146-4JB0
4563
50
45
64
without
3RV1341-4KC10
3RT1044-1AP00
S3
3RU1146-4KB0
5775
50
55
78
without
3RV1341-4LC10
3RT1045-1AP00
S3
3RU1146-4LB0
7090
50
28
1
2
Nominal value at 500 V AC, 50 Hz for 4-pole standard motors. The specific starting and rated data of the motor to be protected are decisive when selecting devices.
Rated control supply voltage 230 V, 50 Hz. Other control voltages are also possible.
AC 500 V
V
t
Setting range
Circuitbreaker
overload
release
A
Circuit-breaker
Contactor
Order No.
Order No.
0.06
0.16
without
3RV1321-0BC10
3RT1015-1AP01
0.09
0.24
without
3RV1321-0CC10
3RT1015-1AP01
Size
Overload relay
Setting range
Overload relay
overload release
Short-circuit
breaking
capacity
Order No.
Iq
kA
S0/S00 3RU1116-0BB0
0.140.2
50
S0/S00 3RU1116-0CB0
0.180.25
50
0.12
0.32
without
3RV1321-0DC10
3RT1015-1AP01
S0/S00 3RU1116-0DB0
0.220.32
50
0.12
0.32
without
3RV1321-0EC10
3RT1015-1AP01
S0/S00 3RU1116-0EB0
0.280.4
50
0.18
0.48
without
3RV1321-0FC10
3RT1015-1AP01
S0/S00 3RU1116-0FB0
0.350.5
50
0.18
0.48
without
3RV1321-0GC10
3RT1015-1AP01
S0/S00 3RU1116-0GB0
0.450.63
50
0.25
0.68
without
3RV1321-0HC10
3RT1015-1AP01
S0/S00 3RU1116-0HB0
0.550.8
50
0.37
0.88
without
3RV1321-0JC10
3RT1015-1AP01
S0/S00 3RU1116-0JB0
0.71
50
0.55
1.2
without
3RV1321-0KC10
3RT1015-1AP01
S0/S00 3RU1116-0KB0
0.91.25
50
0.75
1.5
without
3RV1321-1AC10
3RT1015-1AP01
S0/S00 3RU1116-1AB0
1.11.6
50
0.75
1.5
without
3RV1321-1BC10
3RT1024-1AP00
S0
3RU1116-1BB0
1.42
50
1.1
2.2
without
3RV1321-1CC10
3RT1026-1AP00
S0
3RU1126-1CB0
1.82.5
50
1.5
2.9
without
3RV1321-1DC10
3RT1034-1AP00
S0/S2
3RU1126-1DB0
2.23.2
50
2.2
4.0
without
3RV1321-1FC10
3RT1034-1AP00
S0/S2
3RU1126-1FB0
3.55
50
5.2
without
3RV1321-1GC10
3RT1034-1AP00
S0/S2
3RU1126-1GB0
4.56.3
50
6.8
without
3RV1321-1HC10
3RT1034-1AP00
S0/S2
3RU1136-1HB0
5.58
50
5.5
9.2
without
3RV1321-1JC10
3RT1034-1AP00
S0/S2
3RU1136-1JB0
710
50
7.5
12.4
without
3RV1321-1KC10
3RT1034-1AP00
S0/S2
3RU1136-1KB0
912.5
50
11
17.6
without
3RV1331-4BC10
3RT1034-1AP00
S2
3RU1136-4BB0
1420
50
15
23
without
3RV1331-4DC10
3RT1034-1AP00
S2
3RU1136-4DB0
1825
50
18.5
28
without
3RV1331-4EC10
3RT1034-1AP00
S2
3RU1136-4EB0
2232
50
22
33
without
3RV1331-4FC10
3RT1035-1AP00
S2
3RU1136-4FB0
2840
50
30
44
without
3RV1331-4GC10
3RT1036-1AP00
S2
3RU1136-4GB0
3645
50
30
44
without
3RV1331-4HC10
3RT1036-1AP00
S2
3RU1136-4HB0
4050
50
37
53
without
3RV1341-4JC10
3RT1044-1AP00
S3
3RU1146-4JB0
4563
50
45
64
without
3RV1341-4KC10
3RT1044-1AP00
S3
3RU1146-4KB0
5775
50
55
78
without
3RV1341-4LC10
3RT1045-1AP00
S3
3RU1146-4LB0
7090
50
1
2
3
Nominal value at 500 V AC, 50 Hz for 4-pole standard motors. The specific starting and rated data of the motor to be protected are decisive when selecting devices.
Rated control supply voltage 230 V, 50 Hz. Other control voltages are also possible.
Stand-alone mounting.
29
AC 500 V
Standard three-phase motor
4-pole at 500 V AC 1
Rated
Motor current
power
(nominal value)
P
I
kW
A
Setting range
Circuitbreaker
overload
release 2
A
Circuit-breaker
Contactor
Order No.
Order No.
0.06
0.09
0.12
0.18
0.25
0.37
0.55
0.75
1.1
1.5
2.2
3
4
0.06
0.09
0.12
0.18
0.25
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
132
132
160
160
200
200
250
250
315
315
355
355
0.140.2
0.280.4
0.280.4
1.11.6
1.11.6
1.11.6
1.11.6
1.82.5
2.23.2
3.55
3.55
4.56.3
710
0.350.5
0.350.5
0.450.63
0.91.25
0.91.25
0.91.25
1.42
1.42
2.84
2.84
4.56.3
4.56.3
912.5
1420
1420
2232
2232
2840
4563
4563
5775
5775
without
without
without
without
without
without
without
without
without
without
without
without
without
without
without
without
3RV1011-0BA10
3RV1011-0EA10
3RV1011-0EA10
3RV1011-1AA10
3RV1011-1AA10
3RV1011-1AA10
3RV1011-1AA10
3RV1011-1CA10
3RV1011-1DA10
3RV1011-1FA10
3RV1011-1FA10
3RV1011-1GA10
3RV1011-1JA10
3RV1021-0FA10
3RV1021-0FA10
3RV1021-0GA10
3RV1021-0KA10
3RV1021-0KA10
3RV1021-0KA10
3RV1021-1BA10
3RV1021-1BA10
3RV1021-1EA10
3RV1021-1EA10
3RV1021-1GA10
3RV1021-1GA10
3RV1021-1KA10
3RV1021-4BA10
3RV1021-4BA10
3RV1031-4EA10
3RV1031-4EA10
3RV1031-4FA10
3RV1041-4JA10
3RV1041-4JA10
3RV1041-4KA10
3RV1041-4KA10
3VL2710-2DK33
3VL2716-2DK33
3VL2716-2DK33
3VL2716-2DK33
3VL3725-2DK36
3VL3725-2DK36
3VL3725-2DK36
3VL3725-2DK36
3VL4731-2DK36
3VL4731-2DK36
3VL5750-2DK36
3VL5750-2DK36
3VL5750-2DK36
3VL5750-2DK36
3VL5750-2DK36
3VL5750-2DK36
3RT1015-1AP01
3RT1015-1AP01
3RT1015-1AP01
3RT1015-1AP01
3RT1015-1AP01
3RT1015-1AP01
3RT1015-1AP01
3RT1015-1AP01
3RT1015-1AP01
3RT1015-1AP01
3RT1015-1AP01
3RT1016-1AP01
3RT1017-1AP01
3RT1024-1AP00
3RT1024-1AP00
3RT1024-1AP00
3RT1024-1AP00
3RT1024-1AP00
3RT1024-1AP00
3RT1024-1AP00
3RT1024-1AP00
3RT1025-1AP00
3RT1025-1AP00
3RT1025-1AP00
3RT1025-1AP00
3RT1025-1AP00
3RT1026-1AP00
3RT1026-1AP00
3RT1034-1AP00
3RT1034-1AP00
3RT1035-1AP00
3RT1044-1AP00
3RT1044-1AP00
3RT1045-1AP00
3RT1045-1AP00
3RT1054-1AP36
3RT1054-1AP36
3RT1055-6AP36
3RT1056-6AP36
3RT1064-6AP36
3RT1264-6AP36
3RT1065-6AP36
3RT1265-6AP36
3RT1066-6AP36
3RT1266-6AP36
3RT1075-6AP36
3RT1275-6AP36
3RT1076-6AP36
3RT1276-6AP36
3RT1076-6AP36
3RT1276-6AP36
1
2
3
30
4
5
6
0.16
0.24
0.32
0.48
0.68
0.88
1.2
1.5
2.2
2.9
4
5.2
6.8
0.16
0.24
0.32
0.48
0.68
0.88
1.2
1.5
2.2
2.9
4
5.2
6.8
9.2
12.4
17.6
23
28
33
44
53
64
78
106
128
156
184
184
224
224
280
280
344
344
432
432
488
488
5
5
Size
S00
S00
S00
S00
S00
S00
S00
S00
S00
S00
S00
S00
S00
S0
S0
S0
S0
S0
S0
S0
S0
S0
S0
S0
S0
S0
S0
S0
S2
S2
S2
S3
S3
S3
S3
S6
S6
S6
S6
S10
S10V
S10
S10V
S10
S10V
S12
S12V
S12
S12V
S12
S12V
Overload relay
Setting range
Overload relay
overload release
Short-circuit
breaking
capacity
Order No.
Iq
kA
3RB1016-1RB0
3RB1016-1RB0
3RB1016-1RB0
3RB1016-1NB0
3RB1016-1NB0
3RB1016-1NB0
3RB1016-1NB0
3RB1016-1NB0
3RB1016-1PB0
3RB1016-1PB0
3RB1016-1PB0
3RB1016-1PB0
3RB1016-1SB0
3RB1026-1RB0
3RB1026-1RB0
3RB1026-1RB0
3RB1026-1NB0
3RB1026-1NB0
3RB1026-1NB0
3RB1026-1NB0
3RB1026-1NB0
3RB1026-1PB0
3RB1026-1PB0
3RB1026-1PB0
3RB1026-1PB0
3RB1026-1SB0
3RB1036-1QB0
3RB1036-1QB0
3RB1036-1QB0
3RB1036-1QB0
3RB1036-1UB0
3RB1046-1UB0
3RB1046-1UB0
3RB1046-1EB0
3RB1046-1EB0
3RB1056-1FG0
3RB1056-1FG0
3RB1056-1FG0
3RB1056-1FG0
3RB1056-1FG0
3RB1056-1FG0
3RB1066-1GG0
3RB1066-1GG0
3RB1066-1KG0
3RB1066-1KG0
3RB1066-1KG0
3RB1066-1KG0
3RB1066-1KG0
3RB1066-1KG0
3RB1066-1KG0
3RB1066-1KG0
0.10.4
0.10.4
0.10.4
0.41.6
0.41.6
0.41.6
0.41.6
0.41.6
1.56.0
1.56.0
1.56.0
1.56.0
312
0.10.4
0.10.4
0.10.4
0.41.6
0.41.6
0.41.6
0.41.6
0.41.6
1.56.0
1.56.0
1.56.0
1.56.0
312
625
625
625
625
1350
1350
1350
25100
25100
50200
6
6
55250
200540
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
Nominal value at 500 V AC, 50 Hz for 4-pole standard motors. The specific starting and rated data of the motor to be protected are decisive when selecting devices.
The circuit-breaker should be set to the maximum current value.
Rated control supply voltage 230 V, 50 Hz. Other control voltages are also possible.
Alternatively, 3VL3725-2DK36 is possible.
Alternatively, 3VL4731-2DK36 is possible.
Alternatively, 3RB1066-1GG0 is possible.
AC 500 V
V
t
1
2
3
4
5
6
Setting range
Circuitbreaker
overload
release 2
A
Circuit-breaker
Contactor
Order No.
Order No.
0.06
0.09
0.12
0.18
0.25
0.37
0.55
0.06
0.09
0.12
0.18
0.25
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
132
132
160
160
200
200
250
250
315
315
355
355
0.140.2
0.280.4
0.280.4
0.71.0
0.71.0
0.91.25
1.11.6
0.280.4
0.280.4
0.350.5
1.11.6
1.11.6
1.11.6
1.11.6
1.42
2.23.2
3.55
3.55
4.56.3
710
1116
1116
2232
2232
2840
4563
4563
5775
5775
without
without
without
without
without
without
without
without
without
without
without
without
without
without
without
without
3RV1011-0BA10
3RV1011-0EA10
3RV1011-0EA10
3RV1011-0JA10
3RV1011-0JA10
3RV1011-0KA10
3RV1011-1AA10
3RV1021-0EA10
3RV1021-0EA10
3RV1021-0FA10
3RV1021-1AA10
3RV1021-1AA10
3RV1021-1AA10
3RV1021-1AA10
3RV1021-1BA10
3RV1021-1DA10
3RV1021-1FA10
3RV1021-1FA10
3RV1021-1GA10
3RV1021-1JA10
3RV1031-4AA10
3RV1031-4AA10
3RV1031-4EA10
3RV1031-4EA10
3RV1031-4FA10
3RV1041-4JA10
3RV1041-4JA10
3RV1041-4KA10
3RV1041-4KA10
3VL2710-2DK33
3VL2716-2DK33
3VL2716-2DK33
3VL2716-2DK33 4
3VL3725-2DK36
3VL3725-2DK36
3VL3725-2DK36 5
3VL3725-2DK36 5
3VL4731-2DK36
3VL4731-2DK36
3VL5750-2DK36
3VL5750-2DK36
3VL5750-2DK36
3VL5750-2DK36
3VL5750-2DK36
3VL5750-2DK36
3RT1015-1AP01
3RT1015-1AP01
3RT1015-1AP01
3RT1015-1AP01
3RT1015-1AP01
3RT1015-1AP01
3RT1015-1AP01
3RT1024-1AP00
3RT1024-1AP00
3RT1024-1AP00
3RT1024-1AP00
3RT1024-1AP00
3RT1024-1AP00
3RT1024-1AP00
3RT1024-1AP00
3RT1034-1AP00
3RT1034-1AP00
3RT1034-1AP00
3RT1034-1AP00
3RT1034-1AP00
3RT1034-1AP00
3RT1034-1AP00
3RT1034-1AP00
3RT1034-1AP00
3RT1035-1AP00
3RT1044-1AP00
3RT1044-1AP00
3RT1045-1AP00
3RT1045-1AP00
3RT1054-1AP36
3RT1054-1AP36
3RT1055-6AP36
3RT1056-6AP36
3RT1064-6AP36
3RT1264-6AP36
3RT1065-6AP36
3RT1265-6AP36
3RT1066-6AP36
3RT1266-6AP36
3RT1075-6AP36
3RT1275-6AP36
3RT1076-6AP36
3RT1276-6AP36
3RT1076-6AP36
3RT1276-6AP36
0.16
0.24
0.32
0.48
0.68
0.88
1.2
0.16
0.24
0.32
0.48
0.68
0.88
1.2
1.5
2.2
2.9
4
5.2
6.8
9.2
12.4
17.6
23
28
33
44
53
64
78
106
128
156
184
184
224
224
280
280
344
344
432
432
488
488
Size
S00
S00
S00
S00
S00
S00
S00
S0
S0
S0
S0
S0
S0
S0
S0
S0/S2
S0/S2
S0/S2
S0/S2
S0/S2
S2
S2
S2
S2
S2
S3
S3
S3
S3
S6
S6
S6
S6
S10
S10V
S10
S10V
S10
S10V
S12
S12V
S12
S12V
S12
S12V
Overload relay
Setting range
Overload relay
overload release
Short-circuit
breaking
capacity
Order No.
Iq
kA
3RB1016-1RB0
3RB1016-1RB0
3RB1016-1RB0
3RB1016-1NB0
3RB1016-1NB0
3RB1016-1NB0
3RB1016-1NB0
3RB1026-1RB0
3RB1026-1RB0
3RB1026-1RB0
3RB1026-1NB0
3RB1026-1NB0
3RB1026-1NB0
3RB1026-1NB0
3RB1026-1NB0
3RB1026-1PB0
3RB1026-1PB0
3RB1026-1PB0
3RB1026-1PB0
3RB1036-1QB0
3RB1036-1QB0
3RB1036-1QB0
3RB1036-1QB0
3RB1036-1QB0
3RB1036-1UB0
3RB1046-1UB0
3RB1046-1UB0
3RB1046-1EB0
3RB1046-1EB0
3RB1056-1FG0
3RB1056-1FG0
3RB1056-1FG0
3RB1056-1FG0
3RB1056-1FG0
3RB1056-1FG0
3RB1066-1GG0
3RB1066-1GG0
3RB1066-1KG0
3RB1066-1KG0
3RB1066-1KG0
3RB1066-1KG0
3RB1066-1KG0
3RB1066-1KG0
3RB1066-1KG0
3RB1066-1KG0
0.10.4
0.10.4
0.10.4
0.41.6
0.41.6
0.41.6
0.41.6
0.10.4
0.10.4
0.10.4
0.41.6
0.41.6
0.41.6
0.41.6
0.41.6
1.56.0
1.56.0
1.56.0
1.56.0
625
625
625
625
625
1350
1350
1350
25100
25100
50200
6
6
55250
200540
Nominal value at 500 V AC, 50 Hz for 4-pole standard motors. The specific starting and rated data of the motor to be protected are decisive when selecting devices.
The circuit-breaker should be set to the maximum current value.
Rated control supply voltage 230 V, 50 Hz. Other control voltages are also possible.
Alternatively, 3VL3725-2DK36 is possible.
Alternatively, 3VL4731-2DK36 is possible.
Alternatively, 3RB1066-1GG0 is possible.
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
31
AC 500 V
Standard three-phase motor
4-pole at 500 V AC 1
Rated
Motor current
power
(nominal value)
P
I
kW
A
Setting range
Circuitbreaker
overload
release 2
A
Circuit-breaker
Contactor
Order No.
Order No.
0.06
0.09
0.12
0.18
0.25
0.37
0.75
0.75
1.1
2.2
3
0.06
0.09
0.12
0.18
0.25
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
132
132
160
200
200
250
250
315
355
0.220.32
0.280.4
0.450.63
1.11.6
1.11.6
1.11.6
1.82.5
2.23.2
2.84
4.56.3
5.58
0.350.5
0.450.63
0.450.63
0.91.25
0.91.25
1.42
1.42
2.84
2.84
4.56.3
4.56.3
5.58
912.5
1420
1420
2232
2840
4563
4563
5775
5775
without
without
without
without
without
without
without
without
without
without
without
without
without
without
3RV1011-0DA10
3RV1011-0EA10
3RV1011-0GA10
3RV1011-1AA10
3RV1011-1AA10
3RV1011-1AA10
3RV1011-1CA10
3RV1011-1DA10
3RV1011-1EA10
3RV1011-1GA10
3RV1011-1HA10
3RV1021-0FA10
3RV1021-0GA10
3RV1021-0GA10
3RV1021-0KA10
3RV1021-0KA10
3RV1021-1BA10
3RV1021-1BA10
3RV1021-1EA10
3RV1021-1EA10
3RV1021-1GA10
3RV1021-1GA10
3RV1021-1HA10
3RV1021-1KA10
3RV1021-4BA10
3RV1021-4BA10
3RV1031-4EA10
3RV1031-4FA10
3RV1041-4JA10
3RV1041-4JA10
3RV1041-4KA10
3RV1041-4KA10
3VL2710-2DK33
3VL2710-2DK33
3VL2716-2DK33
3VL2716-2DK33 4
3VL2716-2DK33
3VL3725-2DK36
3VL3725-2DK36 5
3VL3725-2DK36
3VL4731-2DK36
3VL4731-2DK36
3VL5750-2DK36
3VL5750-2DK36
3VL5750-2DK36
3VL5750-2DK36
3RT1015-1AP01
3RT1015-1AP01
3RT1015-1AP01
3RT1015-1AP01
3RT1015-1AP01
3RT1015-1AP01
3RT1015-1AP01
3RT1015-1AP01
3RT1015-1AP01
3RT1016-1AP01
3RT1016-1AP01
3RT1024-1AP00
3RT1024-1AP00
3RT1024-1AP00
3RT1024-1AP00
3RT1024-1AP00
3RT1024-1AP00
3RT1024-1AP00
3RT1025-1AP00
3RT1025-1AP00
3RT1025-1AP00
3RT1025-1AP00
3RT1025-1AP00
3RT1025-1AP00
3RT1026-1AP00
3RT1026-1AP00
3RT1034-1AP00
3RT1035-1AP00
3RT1044-1AP00
3RT1044-1AP00
3RT1044-1AP00
3RT1045-1AP00
3RT1054-1AP36
3RT1054-1AP36
3RT1055-6AP36
3RT1056-6AP36
3RT1064-6AP36
3RT1066-6AP36
3RT1264-6AP36
3RT1265-6AP36
3RT1266-6AP36
3RT1075-6AP36
3RT1076-6AP36
3RT1275-6AP36
3RT1276-6AP36
3RT1276-6AP36
1
2
3
4
32
5
6
7
0.16
0.24
0.32
0.48
0.68
0.88
1.5
1.5
2.2
4
5.2
0.16
0.24
0.32
0.48
0.68
0.88
1.2
1.5
2.2
2.9
4
5.2
6.8
9.2
12.4
17.6
23
28
33
44
53
78
78
106
128
156
184
184
224
280
280
344
344
432
488
Size
S00
S00
S00
S00
S00
S00
S00
S00
S00
S00
S00
S0
S0
S0
S0
S0
S0
S0
S0
S0
S0
S0
S0
S0
S0/S2
S0/S2
S2
S2
S3
S3
S3
S3
S6
S6
S6
S6
S10
S10
S10V
S10V
S10V
S12
S12
S12V
S12V
S12V
Overload relay
Setting range
Overload relay
overload release
Short-circuit
breaking
capacity
Order No.
Iq
kA
3RB1016-2RB0
3RB1016-2RB0
3RB1016-2RB0
3RB1016-2NB0
3RB1016-2NB0
3RB1016-2NB0
3RB1016-2NB0
3RB1016-2PB0
3RB1016-2PB0
3RB1016-2PB0
3RB1016-2SB0
3RB1026-2RB0
3RB1026-2RB0
3RB1026-2RB0
3RB1026-2NB0
3RB1026-2NB0
3RB1026-2NB0
3RB1026-2NB0
3RB1026-2NB0
3RB1026-2PB0
3RB1026-2PB0
3RB1026-2PB0
3RB1026-2SB0
3RB1026-2SB0
3RB1036-2QB0
3RB1036-2QB0
3RB1036-2QB0
3RB1036-2UB0
3RB1046-2UB0
3RB1046-2UB0
3RB1046-2UB0
3RB1046-2EB0
3RB1056-2FG0
3RB1056-2FG0
3RB1056-2FG0
3RB1056-2FG0
3RB1056-2FG0
3RB1056-2FG0
3RB1056-2FG0
3RB1066-2GG0
3RB1066-2KG0
3RB1066-2KG0
3RB1066-2KG0
3RB1066-2KG0
3RB1066-2KG0
3RB1066-2KG0
0.10.4
0.10.4
0.10.4
0.41.6
0.41.6
0.41.6
0.41.6
1.56.0
1.56.0
1.56.0
312
0.10.4
0.10.4
0.10.4
0.41.6
0.41.6
0.41.6
0.41.6
0.41.6
1.56.0
1.56.0
1.56.0
312
312
625
625
625
1350
1350
1350
1350
25100
50200
50200
50200
50200
50200
50200
50200
55250
200-540
200540
200540
200540
200540
200540
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
6
6
7
Nominal value at 500 V AC, 50 Hz for 4-pole standard motors. The specific starting and rated data of the motor to be protected are decisive when selecting devices.
The circuit-breaker should be set to the maximum current value.
Rated control supply voltage 230 V, 50 Hz. Other control voltages are also possible.
Alternatively, 3VL3725-2DK36 is possible.
Alternatively, 3VL4731-2DK36 is possible.
Alternatively, 3RB1066-2GG0 is possible.
Alternatively, 3RB1066-2KG0 is possible.
AC 500 V
V
t
Setting range
Circuitbreaker
overload
release 2
A
0.220.32
Circuit-breaker
Contactor
Overload relay
Setting range
Overload relay
overload release
Short-circuit
breaking
capacity
Order No.
3RV1011-0DA10
Order No.
3RT1015-1AP01 S00
Order No.
3RB1016-2RB0
A
0.10.4
Iq
kA
50
0.09
0.24
0.280.4
0.12
0.32
0.450.63
3RV1011-0EA10
3RT1015-1AP01 S00
3RB1016-2RB0
0.10.4
50
3RV1011-0GA10
3RT1015-1AP01 S00
3RB1016-2RB0
0.10.4
0.18
0.48
50
0.71.0
3RV1011-0JA10
3RT1015-1AP01 S00
3RB1016-2NB0
0.41.6
0.25
50
0.68
0.91.25
3RV1011-0KA10
3RT1015-1AP01 S00
3RB1016-2NB0
0.41.6
50
0.37
0.88
1.11.6
3RV1011-1AA10
3RT1015-1AP01 S00
3RB1016-2NB0
0.41.6
50
0.06
0.16
0.280.4
3RV1021-0EA10
3RT1024-1AP00 S0
3RB1026-2RB0
0.10.4
50
0.09
0.24
0.450.63
3RV1021-0GA10
3RT1024-1AP00 S0
3RB1026-2RB0
0.10.4
50
Size
0.12
0.32
0.450.63
3RV1021-0GA10
3RT1024-1AP00 S0
3RB1026-2RB0
0.10.4
50
0.18
0.48
1.11.6
3RV1021-1AA10
3RT1024-1AP00 S0
3RB1026-2NB0
0.41.6
50
0.25
0.68
1.11.6
3RV1021-1AA10
3RT1024-1AP00 S0
3RB1026-2NB0
0.41.6
50
0.37
0.88
1.11.6
3RV1021-1AA10
3RT1024-1AP00 S0
3RB1026-2NB0
0.41.6
50
0.55
1.2
1.42
3RV1021-1BA10
3RT1024-1AP00 S0
3RB1026-2NB0
0.41.6
50
0.75
1.5
1.82.5
3RV1021-1CA10
3RT1026-1AP00 S0
3RB1026-2NB0
0.41.6
50
1.1
2.2
2.84
3RV1021-1EA10
3RT1034-1AP00 S0/S2
3RB1026-2PB0
1.56.0
50
2.2
4.56.3
3RV1021-1GA10
3RT1034-1AP00 S0/S2
3RB1026-2PB0
1.56.0
50
5.2
5.58
3RV1021-1HA10
3RT1034-1AP00 S0/S2
3RB1026-2SB0
312
50
6.8
912.5
3RV1021-1KA10
3RT1034-1AP00 S0/S2
3RB1036-2QB0
625
50
5.5
9.2
1116
3RV1031-4AA10
3RT1034-1AP00 S2
3RB1036-2QB0
625
50
7.5
12.4
1420
3RV1031-4BA10
3RT1034-1AP00 S2
3RB1036-2QB0
625
50
11
17.6
2232
3RV1031-4EA10
3RT1034-1AP00 S2
3RB1036-2QB0
625
50
15
23
2840
3RV1031-4FA10
3RT1035-1AP00 S2
3RB1036-2UB0
1350
50
18.5
28
4563
3RV1041-4JA10
3RT1044-1AP00 S3
3RB1046-2UB0
1350
50
22
33
4563
3RV1041-4JA10
3RT1044-1AP00 S3
3RB1046-2UB0
1350
50
30
44
5775
3RV1041-4KA10
3RT1044-1AP00 S3
3RB1046-2UB0
1350
50
37
53
5775
3RV1041-4KA10
3RT1045-1AP00 S3
3RB1046-2EB0
25100
50
45
78
without
3VL2710-2DK33
3RT1054-1AP36 S6
3RB1056-2FG0
50200
50
55
78
without
3VL2710-2DK33
3RT1054-1AP36 S6
3RB1056-2FG0
50200
50
75
106
without
3VL2716-2DK33
3RT1055-6AP36 S6
3RB1056-2FG0
50200
50
90
128
without
3VL2716-2DK33
3RT1056-6AP36 S6
3RB1056-2FG0
50200
50
110
156
without
3RB1056-2FG0
50200
50
132
184
without
3VL3725-2DK36
3RT1066-6AP36 S10
3RB1056-2FG0 6 50200
50
132
184
without
3VL3725-2DK36
3RT1264-6AP36 S10V
3RB1056-2FG0 6 50200
50
160
224
without
3RB1066-2GG0 7 55250
50
200
280
without
3VL4731-2DK36
3RT1266-6AP36 S10V
3RB1066-2KG0
200-540
50
200
280
without
3VL4731-2DK36
3RT1075-6AP36 S12
3RB1066-2KG0
200540
50
250
344
without
3VL5750-2DK36
3RT1076-6AP36 S12
3RB1066-2KG0
200540
50
250
344
without
3VL5750-2DK36
3RT1275-6AP36 S12V
3RB1066-2KG0
200540
50
315
432
without
3VL5750-2DK36
3RT1276-6AP36 S12V
3RB1066-2KG0
200540
50
355
488
without
3VL5750-2DK36
3RT1276-6AP36 S12V
3RB1066-2KG0
200540
50
1
2
3
4
5
6
7
Nominal value at 500 V AC, 50 Hz for 4-pole standard motors. The specific starting and rated data of the motor to be protected are decisive when selecting devices.
The circuit-breaker should be set to the maximum current value.
Rated control supply voltage 230 V, 50 Hz. Other control voltages are also possible.
Alternatively, 3VL3725-2DK36 is possible.
Alternatively, 3VL4731-2DK36 is possible.
Alternatively, 3RB1066-2GG0 is possible.
Alternatively. 3RB1066-2KG0 is possible.
33
Circuit-breaker + contactor +
3RB12 electronic overload relay / SIMOCODE-DP 3UF5
CLASS 10, coordination type 2, Iq = 50 kA
AC 500 V
Standard three-phase motor
4-pole at 500 V AC 1
Rated
Motor current
power
(nominal value)
P
I
kW
A
Setting range
Circuitbreaker
overload
release
A
Circuit-breaker
Contactor
Overload relay
Order No.
Order No.
Order No.
0.12
0.32
without
0.18
0.48
without
3RV1321-0HC10
3RT1024-1AP00 S0
3RB1246-1PM00
1.256.3
50
3RV1321-0HC10
3RT1024-1AP00 S0
or
0.25
0.68
50
without
3RV1321-0JC10
3RT1024-1AP00 S0
3UF5001-3AN00-1
0.37
50
0.88
without
3RV1321-0KC10
3RT1024-1AP00 S0
50
0.55
1.2
without
3RV1321-0KC10
3RT1024-1AP00 S0
50
0.75
1.5
without
3RV1321-1BC10
3RT1024-1AP00 S0
50
1.1
2.2
without
3RV1321-1CC10
3RT1026-1AP00 S0
50
1.5
2.9
without
3RV1321-1DC10
3RT1034-1AP00 S0/S2
50
2.2
without
3RV1321-1EC10
3RT1034-1AP00 S0/S2
50
5.2
without
3RV1321-1GC10
3RT1034-1AP00 S0/S2
50
Size
6.325
Shortcircuit
breaking
capacity
Iq
kA
6.8
without
3RV1321-1HC10
3RT1034-1AP00 S0/S2
3RB1246-1QM00
50
5.5
9.2
without
3RV1321-1JC10
3RT1034-1AP00 S0/S2
or
50
7.5
12.4
without
3RV1321-1KC10
3RT1034-1AP00 S0/S2
3UF5011-3AN00-1
50
11
17.6
without
3RV1331-4EC10
3RT1034-1AP00 S2
50
15
23
2232
3RV1031-4EA10
3RT1034-1AP00 S2
50
50
50
15
23
without
3RV1331-4HC10
3RT1036-1AP00 S2
18.5
28
without
3RV1331-4HC10
3RT1036-1AP00 S2
3RB1246-1EM00
22
33
4050
3RV1031-4HA10
3RT1036-1AP00 S2
or
50
30
44
without
3RV1341-4JC10
3RT1044-1AP00 S3
3UF5021-3AN00-1
50
37
53
without
3RV1341-4JC10
3RT1044-1AP00 S3
50
45
64
without
3RV1341-4KC10
3RT1044-1AP00 S3
50
55
78
without
3RV1341-4LC10
3RT1045-1AP00 S3
50
75
106
without
3VL2716-2DK33
3RT1054-1AP36 S6
3RB1253-0FM00
50
90
128
without
3VL2716-2DK33
3RT1055-6AP36 S6
or
50
110
156
without
3VL2716-2DK33
3RT1056-6AP36 S6
3UF5031-3AN00-1
50
132
184
without
3VL3725-2DK36
3RT1064-6AP36 S10
3RB1253-0FM00 /
50
132
184
without
3VL3725-2DK36
3RT1264-6AP36 S10V
3UF5031-3AN00-1
50
160
224
without
3VL3725-2DK36
3RT1065-6AP36 S10
3RB1257-0KM00
50
160
224
without
3VL3725-2DK36
3RT1265-6AP36 S10V
or
50
200
280
without
3VL4731-2DK36
3RT1066-6AP36 S10
3UF5041-3AN00-1
50
200
280
without
3VL4731-2DK36
3RT1266-6AP36 S10V
50
250
344
without
3VL5750-2DK36
3RT1075-6AP36 S12
50
250
344
without
3VL5750-2DK36
3RT1275-6AP36 S12V
50
315
432
without
3VL5750-2DK36
3RT1076-6AP36 S12
50
315
432
without
3VL5750-2DK36
3RT1276-6AP36 S12V
50
355
488
without
3VL5750-2DK36
3RT1076-6AP36 S12
50
355
488
without
3VL5750-2DK36
3RT1276-6AP36 S12V
50
1
2
3
34
4
5
6
25100
50205
125500
Nominal value at 500 V AC, 50 Hz for 4-pole standard motors. The specific starting and rated data of the motor to be protected are decisive when selecting devices.
The circuit-breaker should be set to the maximum current value.
Rated control supply voltage 230 V, 50 Hz. Other control voltages are also possible.
Alternatively, 3VL3725-2DK36 is possible.
Alternatively, 3VL4731-2DK36 is possible.
Alternatively, 3RB1257-0KM00 or 3UF5041-3AN00-1 is possible.
Circuit-breaker + contactor +
3RB12 electronic overload relay / SIMOCODE-DP 3UF5
CLASS 20, coordination type 2, Iq = 50 kA
AC 500 V
V
Standard three-phase motor
4-pole at 500 V AC 1
Rated
Motor current
power
(nominal value)
P
I
kW
A
Setting range
Circuitbreaker
overload
release
A
Circuit-breaker
Contactor
Overload relay
Order No.
Order No.
Order No.
A
1.256.3
Size
Shortcircuit
breaking
capacity
Iq
kA
0.12
0.32
without
3RV1321-0JC10
3RT1024-1AP00 S0
3RB1246-1PM00
50
0.18
0.48
without
3RV1321-0KC10
3RT1024-1AP00 S0
or
50
0.25
0.68
without
3RV1321-0KC10
3RT1024-1AP00 S0
3UF5001-3AN00-1
50
0.37
0.88
without
3RV1321-1AC10 3RT1024-1AP00 S0
50
0.55
1.2
without
3RV1321-1BC10
3RT1024-1AP00 S0
50
0.75
1.5
without
3RV1321-1CC10
3RT1026-1AP00 S0
50
1.1
2.2
without
50
1.5
2.9
without
3RV1321-1EC10
3RT1034-1AP00 S0/S2
50
2.2
without
50
5.2
without
50
6.8
without
3RV1321-1JC10
3RT1034-1AP00 S0/S2
3RB1246-1QM00
50
5.5
9.2
without
3RV1331-4BC10
3RT1034-1AP00 S2
or
6.325
50
7.5
12.4
2232
3RV1031-4EA10 3RT1034-1AP00 S2
3UF5011-3AN00-1
50
11
17.6
2840
3RV1031-4FA10
3RT1035-1AP00 S2
50
15
23
without
3RV1341-4JC10
3RT1044-1AP00 S3
50
18.5
28
without
3RV1341-4JC10
3RT1044-1AP00 S3
3RB1246-1EM00
50
22
33
without
3RV1341-4JC10
3RT1044-1AP00 S3
or
25100
50
30
44
5775
3RV1041-4KA10 3RT1044-1AP00 S3
3UF5021-3AN00-1
37
53
7090
3RV1041-4LA10
45
78
55
78
50
3RT1045-1AP00 S3
50
without
3VL2710-2DK33 3RT1054-1AP36 S6
50
without
3VL2710-2DK33 3RT1054-1AP36 S6
50
75
106
without
3VL2716-2DK33 3RT1055-6AP36 S6
3RB1253-0FM00
50
90
128
without
3VL2716-2DK33 3RT1056-6AP36 S6
or
50
110
156
without
3UF5031-3AN00-1
50
132
184
without
3VL3725-2DK36
3RT1065-6AP36 S10
50
132
184
without
3VL3725-2DK36
3RT1066-6AP36 S10
50
132
184
without
3VL3725-2DK36
3RT1264-6AP36 S10V
50
160
224
without
3RB1257-0KM00
200
280
without
3VL4731-2DK36
3RT1266-6AP36 S10V
200
280
without
3VL4731-2DK36
3RT1075-6AP36 S12
250
344
without
3VL5750-2DK36
3RT1076-6AP36 S12
250
344
without
3VL5750-2DK36
315
432
without
3VL5750-2DK36
355
488
without
3VL5750-2DK36
1
2
3
4
5
50205
125500
50
or
50
3UF5041-3AN00-1
50
50
3RT1275-6AP36 S12V
50
3RT1276-6AP36 S12V
50
3RT1276-6AP36 S12V
50
Nominal value at 500 V AC, 50 Hz for 4-pole standard motors. The specific starting and rated data of the motor to be protected are decisive when selecting devices.
The circuit-breaker should be set to the maximum current value.
Rated control supply voltage 230 V, 50 Hz. Other control voltages are also possible.
Alternatively, 3VL3725-2DK36 is possible.
Alternatively, 3VL4731-2DK36 is possible.
35
Circuit-breaker + contactor +
3RB12 electronic overload relay / SIMOCODE-DP 3UF5
CLASS 30, coordination type 2, Iq = 50 kA
AC 500 V
Standard three-phase motor Setting range
4-pole at 500 V AC
Circuit-breaker
Contactor
Size
Overload relay
Setting range
Circuit-
No. of
Short-
Rated
overload
power
release
windings breaking
capacity
release
P
kW
Iq
A
Order No.
Order No.
Order No.
A
1.256.3
kA
0.12
0.32
without
3RV1321-1AC10 3RT1024-1AP00 S0
3RB1246-1PM00
50
0.18
0.48
without
3RV1321-1BC10
3RT1024-1AP00 S0
or
50
0.25
0.68
without
3RV1321-1BC10
3RT1024-1AP00 S0
3UF5001-3AN00-1
50
0.37
0.88
1.82.5
3RV1021-1CA10 3RT1026-1AP00 S0
50
0.55
1.2
2.23.2
50
0.75
1.5
2.84
50
1.1
2.2
3.55
3RV1021-1FA10
50
3RT1034-1AP00 S0/S2
1.5
2.9
710
3RV1021-1JA10
3RT1034-1AP00 S0/S2
50
2.2
710
3RV1021-1JA10
3RT1034-1AP00 S0/S2
50
5.2
912.5
50
6.8
1116
3RV1031-4AA10 3RT1034-1AP00 S2
3RB1246-1QM00
50
5.5
9.2
1420
3RV1031-4BA10 3RT1034-1AP00 S2
or
6.325
50
7.5
12.4
2232
3RV1031-4EA10 3RT1034-1AP00 S2
3UF5011-3AN00-1
50
11
17.6
2840
3RV1031-4FA10
50
50
50
50
3RT1035-1AP00 S2
15
22
4050
3RV1031-4HA10 3RT1036-1AP00 S2
18.5
28
5775
3RV1041-4KA10 3RT1044-1AP00 S3
3RB1246-1EM00
22
33
7090
3RV1041-4LA10
3RT1045-1AP00 S3
or
30
44
7090
3RV1041-4LA10
3RT1045-1AP00 S3
3UF5021-3AN00-1
50
37
64
without
50
25100
3VL2710-2DK33 3RT1054-1AP36 S6
45
64
without
3VL2710-2DK33 3RT1054-1AP36 S6
50
55
78
without
3VL2710-2DK33 3RT1055-6AP36 S6
50
75
106
without
3VL2716-2DK33 3RT1056-6AP36 S6
3RB1253-0FM00
50
90
128
without
3VL2716-2DK33
or
50
110
156
without
3UF5031-3AN00-1
50
110
156
without
50
110
156
without
3VL2716-2DK33
50
132
184
without
3VL3725-2DK36
50
3RT1064-6AP36 S10
50205
3RT1264-6AP36 S10V
4
3RT1265-6AP36 S10V
3RB1253-0FM00 /
3UF5031-3AN00-1
160
224
without
3RB1257-0KM00
160
224
without
or
200
280
without
3VL4731-2DK36
3RT1076-6AP36 S12
3UF5041-3AN00-1
50
200
280
without
3VL4731-2DK36
3RT1275-6AP36 S12V
50
250
344
without
3VL5750-2DK36
3RT1276-6AP36 S12V
50
1
2
3
36
4
5
6
125500
50
50
Nominal value at 500 V AC, 50 Hz for 4-pole standard motors. The specific starting and rated data of the motor to be protected are decisive when selecting devices.
The circuit-breaker should be set to the maximum current value.
Rated control supply voltage 230 V, 50 Hz. Other control voltages are also possible.
Alternatively, 3VL3725-2DK36 is possible.
Alternatively, 3VL4731-2DK36 is possible.
Alternatively, 3RB1257-0KM00 or 3UF5041-3AN00-1 is possible.
AC 500 V
V
Standard three-phase motor
4-pole at 500 V AC 1
Setting range
Circuit-
Circuit-breaker
Contactor
Size
Line contactor
+ delta
contactor
Overload relay
Star contactor
Setting
range
Shortcircuit
Rated
power
P
kW
I
A
Order No.
7.5
12.4
without
3RV1321-4AC10
710
50
11
17.6
without
3RV1321-4BC10
3RT1024-1AP00 3RT1024-1AP00 S0
3RU1126-1KB0
912.5
50
15
22
without
3RV1321-4DC10
3RT1024-1AP00 3RT1024-1AP00 S0
3RU1126-4AB0 1116
50
18.5
29
without
3RV1331-4EC10
3RU1126-4BB0
1420
50
22
34
without
3RV1331-4FC10
3RU1136-4DB0 1825
50
30
46
without
3RV1331-4HC10
3RU1136-4EB0
2232
50
37
53
without
3RV1341-4JC10
3RU1136-4FB0
2840
50
45
65
without
3RV1341-4KC10
3RU1136-4GB0 3645
50
55
79
without
3RV1341-4LC10
3RU1136-4HB0 4050
50
Order No.
Order No.
Overload breaking
relay
capacity
overload
release
Iq
A
kA
Setting range
Circuit-
Circuit-breaker
AC 500 V
Contactor
Size
Line contactor
+ delta
contactor
Overload relay
Star contactor
Setting
range
Shortcircuit
Rated
power
P
kW
I
A
Order No.
Order No.
7.5
12.4
without
3RV1331-4AC10
710
50
11
17.6
without
3RV1331-4BC10
912.5
50
Order No.
Overload breaking
relay
capacity
overload
release
Iq
A
kA
15
22
without
3RV1331-4DC10
50
18.5
29
without
3RV1331-4EC10
1420
50
22
34
without
3RV1331-4FC10
50
30
46
without
3RV1331-4HC10
2232
50
37
53
without
3RV1341-4JC10
2840
50
45
65
without
3RV1341-4KC10
50
55
79
without
3RV1341-4LC10
50
37
1
2
Nominal value at 500 V AC, 50 Hz for 4-pole standard motors. The specific starting and rated data of the motor to be protected are decisive when selecting devices.
Rated control supply voltage 230 V, 50 Hz. Other control voltages are also possible.
AC 500 V
Standard three-phase motor
4-pole at 500 V AC 1
Circuit-breaker
Contactor
Size
Line contactor
+ delta
contactor
Setting
P
kW
I
A
7.5
12.4
1116
3RV1021-4BA10
11
17.6
2232
3RV1031-4EA10
50
15
22
2232
3RV1031-4EA10
50
18.5
29
2840
3RV1031-4FA10
Order No.
Overload
relay
overload
release
Shortcircuit
Order No.
Star contactor
Overload relay
range
Rated
power
Order No.
breaking
capacity
3RB1036-1QB0 625
3RB1036-1UB0 1350
Iq
kA
50
50
22
34
4563
3RV1041-4JA10
50
30
46
4563
3RV1041-4JA10
50
37
53
5775
3RV1041-4KA10
3RV1041-4KA10
50
3RV1041-4LA10
50
3VL2716-2DK33
45
65
5775
55
79
7090
75
106
without
3RB1046-1EB0
3RB1056-1FG0
25100
50200
50
50
90
128
without
3VL2716-2DK33
50
110
156
without
50
132
184
without
3VL3725-2DK36
50
160
224
without
50
200
280
without
3VL4731-2DK36
50
250
344
without
3VL5750-2DK36
50
315
432
without
3VL5750-2DK36
355
488
without
3VL5750-2DK36
1
2
3
38
Setting range
Circuit-
4
5
6
200540 50
50
Nominal value at 690 V AC, 50 Hz for 4-pole standard motors. The specific starting and rated data of the motor to be protected are decisive when selecting devices.
Rated control supply voltage 230 V, 50 Hz. Other control voltages are also possible.
The circuit-breaker should be set to the maximum current value.
Alternatively, 3VL3725-2DK36 is possible.
Alternatively, 3VL4731-2DK36 is possible.
3RB1056-1FG0 stand-alone mounting 3RB1066-1G0 is also possible for direct mounting.
AC 500 V
Standard three-phase motor
4-pole at 500 V AC 1
Setting range
Circuit-
Rated
power
P
kW
I
A
7.5
12.4
1116
11
17.6
15
22
18.5
Circuit-breaker
Contactor
Size
Line contactor
+ delta
contactor
Star contactor
Overload relay
range
Setting
Overload
relay
overload
release
Order No.
Shortcircuit
breaking
capacity
Iq
kA
625
50
Order No.
Order No.
3RV1031-4AA10
2232
3RV1031-4EA10
50
2232
3RV1031-4EA10
50
29
2840
3RV1031-4FA10
22
34
4563
3RV1041-4JA10
50
30
46
4563
3RV1041-4JA10
50
37
53
5775
3RV1041-4KA10
45
65
5775
3RV1041-4KA10
55
79
7090
3RV1041-4LA10
75
106
without
3VL2716-2DK33
90
128
without
3VL2716-2DK33
50
50
110
156
without
3VL2716-2DK33 2
132
184
without
3VL3725-2DK36
160
224
without
200
280
without
3VL4731-2DK36
250
344
without
3VL5750-2DK36
432
without
3VL5750-2DK36
355
488
without
3VL5750-2DK36
2
3
4
5
6
25100
50
50
50
50
50200
50
50
55250
315
1350
50
50
50
200540
Nominal value at 690 V AC, 50 Hz for 4-pole standard motors. The specific starting and rated data of the motor to be protected are decisive when selecting devices.
Rated control supply voltage 230 V, 50 Hz. Other control voltages are also possible.
The circuit-breaker should be set to the maximum current value.
Alternatively, 3VL3725-2DK36 is possible.
Alternatively 3VL4731-2DK36 is possible.
3RB1056-1FG0 stand-alone mounting 3RB1066-1GG is also possible for direct mounting.
50
50
39
AC 500 V
Standard three-phase motor
4-pole at 500 V AC 1
Rated
power
P
kW
I
A
Circuit-breaker
Contactor
Line contactor
+ delta
contactor
Order No.
Size
Star contactor
Overload relay
range
Setting
Overload
relay
overload
release
Shortcircuit
breaking
capacity
Order No.
Order No.
Iq
kA
6.325
50
7.5
12.4
without
3RV1321-1KC10
3RB1246-1QM00
11
17.6
without
3RV1331-4EC10
oder
50
15
22
without
3RV1331-4HC10
3UF5011-3AN00-1
50
18.5
29
without
3RV1331-4HC10
22
34
4050
3RV1031-4HA10
30
46
without
3RV1341-4JC10
3RB1246-1EM00
37
53
without
3RV1341-4JC10
oder
3UF5021-3AN00-1
50
50
45
65
without
3RV1341-4KC10
55
79
without
3RV1341-4LC10
75
106
without
3VL2716-2DK33
3RB1253-0FM00
90
128
without
3VL2716-2DK33
oder
3UF5031-3AN00-1
25100
50
50
50
50
110
156
without
3VL2716-2DK33 4
132
184
without
3VL3725-2DK36
160
224
without
50205
50
50
50
50
125500 50
200
280
without
3VL4731-2DK36
50
250
344
without
3VL5750-2DK36
50
315
432
without
3VL5750-2DK36
50
355
488
without
3VL5750-2DK36
50
1
2
40
Setting range
Circuit-
3
4
5
Nominal value at 690 V AC, 50 Hz for 4-pole standard motors. The specific starting and rated data of the motor to be protected are decisive when selecting devices.
Rated control supply voltage 230 V, 50 Hz. Other control voltages are also possible.
The circuit-breaker should be set to the maximum current value.
Alternatively, 3VL3725-2DK36 is possible.
Alternatively, 3VL4731-2DK36 is possible.
Circuit-breaker + contactor
CLASS 10, coordination type 2, Iq = 50 kA
AC 690 V
Standard three-phase motor
4-pole at 690 V AC 1
Rated
Motor current
power
(nominal value)
P
I
kW
A
Setting range
Circuitbreaker
overload
release
A
Standard
circuitbreaker
with limiter
function
type
Circuit-breaker
Contactor
Order No.
Order No.
Size
Short-circuit
breaking
capacity
Iq
kA
0.09
0.17
0.140.2
not required
3RV1021-0BA10
3RT1024-1AP00
S0
50
0.12
0.23
0.180.25
not required
3RV1021-0CA10
3RT1024-1AP00
S0
50
0.12
0.23
0.220.32
not required
3RV1021-0DA10
3RT1024-1AP00
S0
50
0.18
0.35
0.280.4
not required
3RV1021-0EA10
3RT1024-1AP00
S0
50
0.18
0.35
0.350.5
not required
3RV1021-0FA10
3RT1024-1AP00
S0
50
0.25
0.49
0.450.63
not required
3RV1021-0GA10
3RT1024-1AP00
S0
50
0.37
0.64
0.550.8
not required
3RV1021-0HA10
3RT1024-1AP00
S0
50
0.55
0.87
0.71
not required
3RV1021-0JA10
3RT1024-1AP00
S0
50
0.75
1.1
0.91.25
not required
3RV1021-0KA10
3RT1024-1AP00
S0
50
0.75
1.1
1.11.6
not required
3RV1021-1AA10
3RT1024-1AP00
S0
50
1.1
1.6
1.42
3RV1321-4DC10
3RV1021-1BA10
3RT1024-1AP00
S0
50
50
1.5
2.1
1.82.5
Size S0
3RV1021-1CA10
3RT1024-1AP00
S0
2.2
2.8
2.23.2
In = 25 A
3RV1021-1DA10
3RT1024-1AP00
S0
50
3.0
3.8
3.55
3RV1021-1FA10
3RT1024-1AP00
S0
50
4.0
4.9
4.56.3
3RV1021-1GA10
3RT1024-1AP00
S0
50
5.5
6.7
5.58
3RV1331-4HC10
3RV1021-1HA10
3RT1024-1AP00
S0
50
7.5
8.9
710
Size S2
3RV1021-1JA10
3RT1024-1AP00
S0
50
11
12.8
1116
In = 50 A
3RV1021-4AA10
3RT1025-1AP00
S0
50
11
12.8
1116
3RV1331-4HC10
3RV1031-4AA10
3RT1034-1AP00
S2
50
15
17
1420
Size S2
3RV1031-4BA10
3RT1034-1AP00
S2
50
18.5
21
1825
In = 50 A
22
24
2232
30
32
2840
3RV1031-4DA10
3RT1035-1AP00
S2
50
3RV1031-4EA10
3RT1035-1AP00
S2
50
3RV1331-4HC10
3RV1031-4FA10
3RT1044-1AP00
S2/S3
50
S2/S3
50
S2/S3
50
S6
50
37
39
3645
Size S2
3RV1031-4GA10
3RT1044-1AP00
45
47
4050
In = 50 A
3RV1031-4HA10
3RT1045-1AP00
55
57
40100
not required
3VU2032-0AL60
3RT1055-6AP36
75
77
40100
not required
3VU2032-0AL60
3RT1055-6AP36
S6
50
90
93
64160
not required
3VU2032-0CL60
3RT1055-6AP36
S6
50
110
113
64160
not required
3VU2032-0CL60
3RT1055-6AP36
S6
50
132
134
64160
not required
3VU2032-0CL60
3RT1055-6AP36
S6
50
160
162
80200
not required
3VU2032-0DL60
3RT1056-6AP36
S6
50
200
203
128320
not required
3VU2042-0FL60
3RT1264-6AP36
S10V
50
250
250
128320
not required
3VU2042-0FL60
3RT1265-6AP36
S10V
50
315
316
160400
not required
3VU2052-0FL60
3RT1275-6AP36
S12V
50
355
354
252630
not required
3VU2052-0HL60
3RT1275-6AP36
S12V
50
400
400
252630
not required
3VU2052-0HL60
3RT1275-6AP36
S12V
50
500
493
252630
not required
3VU2052-0HL60
3RT1276-6AP36
S12V
50
1
2
3
Nominal value at 690 V AC, 50 Hz for 4-pole standard motors. The specific starting and rated data of the motor to be protected are decisive when selecting devices.
Rated control supply voltage 230 V, 50 Hz. Other control voltages are also possible.
There must be a minimum clearance of 10 cm between the circuit-breaker and the contactor.
41
Circuit-breaker + contactor
CLASS 20, coordination type 2, Iq = 50 kA
AC 690 V
Standard three-phase motor
4-pole at 690 V AC 1
Rated
Motor current
power
(nominal value)
Setting range
Circuitbreaker
overload
Circuit-breaker
Contactor
Size
Short-circuit
breaking
capacity
release
kW
Order No.
Order No.
kA
55
57
40100
3VU2032-0AL60
3RT1055-6AP36 S6
50
75
77
64160
3VU2032-0CL60
3RT1055-6AP36 S6
50
90
93
64160
3VU2032-0CL60
3RT1055-6AP36 S6
50
Iq
110
113
80200
3VU2032-0DL60
3RT1056-6AP36 S6
50
132
133
128320
3VU2042-0FL60
3RT1264-6AP36 S10V
50
160
162
128320
3VU2042-0FL60
3RT1264-6AP36 S10V
50
200
204
128320
3VU2042-0FL60
3RT1264-6AP36 S10V
50
250
249
128320
3VU2042-0FL60
3RT1265-6AP36 S10V
50
315
316
160400
3VU2052-0FL60
3RT1275-6AP36 S12V
50
355
354
252630
3VU2052-0HL60
3RT1275-6AP36 S12V
50
400
400
252630
3VU2052-0HL60
3RT1275-6AP36 S12V
50
500
493
252630
3VU2052-0HL60
3RT1276-6AP36 S12V
50
Circuit-breaker
Contactor
Short-circuit
breaking
capacity
Circuit-breaker + contactor
CLASS 30, coordination type 2, Iq = 50 kA
AC 690 V
Standard three-phase motor
4-pole at 690 V AC 1
Rated
Motor current
power
(nominal value)
Setting range
Circuitbreaker
P
kW
I
A
release
A
Order No.
Order No.
55
57
40100
3VU2032-0AL60
3RT1055-6AP36
S6
50
Size
overload
Iq
kA
75
77
64160
3VU2032-0CL60
3RT1055-6AP36
S6
50
90
93
80200
3VU2032-0DL60
3RT1056-6AP36
S6
50
110
113
128320
3VU2042-0FL60
3RT1264-6AP36
S10V
50
132
133
128320
3VU2042-0FL60
3RT1264-6AP36
S10V
50
160
162
128320
3VU2042-0FL60
3RT1264-6AP36
S10V
50
200
204
128320
3VU2042-0FL60
3RT1265-6AP36
S10V
50
250
249
160400
3VU2052-0FL60
3RT1275-6AP36
S12V
50
315
316
252630
3VU2052-0HL60
3RT1276-6AP36
S12V
50
355
354
252630
3VU2052-0HL60
3RT1276-6AP36
S12V
50
42
1
2
Nominal value at 690 V AC, 50 Hz for 4-pole standard motors. The specific starting and rated data of the motor to be protected are decisive when selecting devices.
Rated control supply voltage 230 V, 50 Hz. Other control voltages are also possible.
AC 690 V
Standard three-phase motor Setting range
4-pole at 690 V AC
Circuit-breaker
Contactor
Size
Overload relay
Circuit-
Rated
power
release
kW
Order No.
Order No.
75
90
110
132
160
200
250
77
93
113
134
162
203
250
without
without
without
without
without
without
without
3VU23 12-0BC60
3VU23 12-0BC60
3VU23 22-0CC60
3VU23 22-0CC60
3VU23 22-0DC60
3VU23 32-0EC60
3VU23 42-0FC60
3RT1054-1AP36
3RT1054-1AP36
3RT1054-1AP36
3RT1055-6AP36
3RT1056-6AP36
3RT1064-6AP36
3RT1265-6AP36
S6
S6
S6
S6
S6
S10
S10V
315
355
400
500
316
354
400
493
without
without
without
without
3VU23 42-0GC60
3VU23 52-0HC60
3VU23 52-0HC60
3VU23 52-0HC60
3RT1275-6AP36
3RT1275-6AP36
3RT1275-6AP36
3RT1276-6AP36
S12V
S12V
S12V
S12V
Setting range
Short-circuit
Overload relay
breaking
overload release
capacity
Iq
Order No.
kA
3RB1056-1FG0
50200
3RB1066-1GG0
oder
3RB1066-1KG0
3RB1066-1KG0
oder
3RB1066-1LG0
55250
oder
200540
200540
oder
300630
50
50
50
50
50
50
50
50
50
50
50
50
AC 690 V
Standard three-phase motor Setting range
4-pole at 690 V AC
Circuit-breaker
Contactor
Size
Overload relay
Circuit-
Rated
power
release
kW
Order No.
Order No.
55
75
90
110
132
160
200
250
315
355
400
500
57
77
93
113
133
162
203
250
316
354
400
493
without
without
without
without
without
without
without
without
without
without
without
without
3VU23 12-0AC60
3VU23 12-0AC60
3VU23 22-0CC60
3VU23 22-0DC60
3VU23 32-0EC60
3VU23 32-0EC60
3VU23 32-0EC60
3VU23 42-0FC60
3VU23 42-0GC60
3VU23 52-0HC60
3VU23 52-0HC60
3VU23 52-0HC60
3RT1054-1AP36
3RT1054-1AP36
3RT1055-6AP36
3RT1056-6AP36
3RT1064-6AP36
3RT1065-6AP36
3RT1066-6AP36
3RT1265-6AP36
3RT1275-6AP36
3RT1275-6AP36
3RT1275-6AP36
3RT1276-6AP36
Setting range
Short-circuit
Overload relay
breaking
overload release
capacity
Iq
S6
S6
S6
S6
S10
S10
S10
S10V
S12V
S12V
S12V
S12V
Order No.
kA
3RB1056-2FG0
50200
3RB1066-2GG0
oder
3RB1066-2KG0
55250
oder
200540
3RB1066-2KG0
oder
3RB1066-2LG0
200540
oder
300630
50
50
50
50
50
50
50
50
50
50
50
50
43
1
2
Nominal value at 690 V AC, 50 Hz for 4-pole standard motors. The specific starting and rated data of the motor to be protected are decisive when selecting devices.
Rated control supply voltage 230 V, 50 Hz. Other control voltages are also possible.
Circuit-breaker + contactor +
3RB12 electronic overload relay / SIMOCODE-DP 3UF5
CLASS 30, coordination type 2, Iq = 50 kA
AC 690 V
Standard three-phase motor Setting range
4-pole at 690 V AC
Circuit-breaker
Contactor
Size
Overload relay
Circuit-
Rated
power
release
kW
Order No.
Order No.
55
75
90
110
132
160
200
250
315
355
57
77
93
113
133
162
203
249
316
354
without
without
without
without
without
without
without
without
without
without
3VU23 12-0AC60
3VU23 22-0CC60
3VU23 22-0DC60
3VU23 32-0EC60
3VU23 32-0EC60
3VU23 32-0EC60
3VU23 42-0FC60
3VU23 42-0GC60
3VU23 52-0HC60
3VU23 52-0HC60
3RT1054-1AP36
3RT1055-6AP36
3RT1056-6AP36
3RT1064-6AP36
3RT1064-6AP36
3RT1066-6AP36
3RT1265-6AP36
3RT1275-6AP36
3RT1275-6AP36
3RT1276-6AP36
Setting range
Short-circuit
Overload relay
breaking
overload release
capacity
Iq
S6
S6
S6
S10
S10
S10
S10V
S12V
S12V
S12V
Order No.
kA
3RB1253-0FM00
oder
3UF5031-3AN00-1
50205
3RB1257-0KM00
oder
3UF5041-3AN00-1
125500
50
50
50
50
50
50
50
50
50
50
AC 690 V
Standard three-phase motor
4-pole at AC 690 V 1
Setting range
Circuit-
Circuit-breaker
Contactor
Rated
Motor current
breaker
Line contactor
power
(nominal value)
overload
release
+ delta
contactor
Size
Star contactor
relay
overload
release
kW
Order No.
Order No.
90
93
without
3VU2312-0BC60
3RT1054-1AP36
3RT1035-1AP00
S6/S2
110
113
without
3VU2322-0CC60
3RT1054-1AP36
3RT1035-1AP00
S6/S2
132
134
without
3VU2322-0CC60
3RT1055-6AP36
3RT1044-1AP00
S6/S3
160
162
without
3VU2322-0DC60
3RT1056-6AP36
3RT1044-1AP00
S6/S3
200
203
without
3VU2332-0EC60
3RT1064-6AP36
3RT1054-1AP36
S10/S6
250
250
without
3VU2342-0EC60
3RT1265-6AP36
3RT1264-6AP36
S10V/S10V
315
316
without
3VU2342-0GC60
3RT1275-6AP36
3RT1264-6AP36
S12V/S10V
355
354
without
3VU2352-0HC60
3RT1275-6AP36
3RT1264-6AP36
S12V/S10V
400
400
without
3VU2352-0HC60
3RT1275-6AP36
3RT1264-6AP36
S12V/S10V
500
493
without
3VU2352-0HC60
3RT1276-6AP36
3RT1264-6AP36
S12V/S10V
44
1
2
Setting
range
Overload
Overload relay
Nominal value at 690 V AC, 50 Hz for 4-pole standard motors. The specific starting and rated data of the motor to be protected are decisive when selecting devices.
Rated control supply voltage 230 V, 50 Hz. Other control voltages are also possible.
Order No.
3RB1056-1FG0
50200
3RB1066-1GG0
55250
3RB1066-1KG0
200540
V
t
AC 690 V
Standard three-phase motor
4-pole at AC 500 V 1
Setting range
Circuit-
Circuit-breaker
Contactor
Size
Rated
Line contactor
power
+ delta
contactor
kW
Order No.
Order No.
90
93
without
3VU2312-0BC60
110
113
without
132
134
without
160
162
200
203
250
Star contactor
Shortcircurit
Overload relay
range
Setting
breaking Overload
capacity
relay
overload
release
50
3RB1253-0FM00 50205
3VU2322-0CC60
50
or
3VU2322-0CC60
50
3UF5031-3AN00-1
without
3VU2322-0DC60
50
without
3VU2332-0EC60
50
250
without
3VU2342-0FC60
315
316
without
or
355
354
without
3UF5041-3AN00-1
Order No.
400
400
without
500
493
without
3RB1257-0KM00 125500
45
1
2
Nominal value at 690 V AC, 50 Hz for 4-pole standard motors. The specific starting and rated data of the motor to be protected are decisive when selecting devices.
Rated control supply voltage 230 V, 50 Hz. Other control voltages are also possible.
Circuit-breaker
X2
3RV1.1
3RT101
400/500 V
20
10
3RV1.2
3RT101
3RT102
3RT103
400/500 V
400/500 V
400/500 V
30
30
30
10
10
10
9
9
9
3RV1.3
3RT102
3RT103
3RT104
400/500 V
400/500 V
400/500 V
50
50
50
10
10
10
10
10
10
3RT104
3RT104
400 V
500 V
90
220
10
10
12
20
3RV1.4
1
1L1
3L2 5L3
3RV1...
2T1
4T2 6T3
1L1
3L2 5L3
3RV1...
X2
3RT1...
3RT1...
Minimum clearance to the contactor at the front. For circuit-breakers, a minimum clearance at the front is not required.
2T1
4T2 6T3
Rated operating
voltage
Ue
A1)
3VL2/3
400525 V
50
25
25
87
3VL4/5
400525 V
50
25
25
106,5
B
1
2
D
C
46
Clearance to grounded parts and components for 3RT10/3RT12 contactors (sizes S6/S10/S12)
Contactor
Rated operating
voltage
3RT105
3RT106
3RT107
3RT126
3RT127
400/500/690 V
400/500/690 V
400/500/690 V
400/500/690 V
400/500/690 V
Clearance to
grounded or
live parts and
components (mm)
G
H
I
40
10
20
20
10
20
20
10
20
20
10
20
20
10
20
H
I
3RT105
3RT106
3RT107
3RT126
3RT127
400/500/690 V
400/500/690 V
400/500/690 V
400/500/690 V
400/500/690 V
Clearance to
grounded or
live parts and
components (mm)
40
20
20
20
20
10
10
10
10
10
20
20
20
20
20
20
20
20
20
20
H
I
47
2 circuit-breakers
combined with contactors
Circuit-breaker
Contactor
3RV1.2 with
3RV1.3 with
3RT102
3RT103
3RT104
Clearance to grounded or
live parts and components (mm)
Rated operating
voltage
690 V
690 V
690 V
3-phase busbars:
Size S0: 3RV19 15-1AB
Size S2: 3RV19 35-1A
Y2
mm
10
10
10
Y3
mm
95
120
120
X1
mm
20
10
10
2
1L1
3L2 5L3
1L1
3L2 5L3
X1
3RV1...
2T1
4T2 6T3
X2
mm
14
32
40
Z
mm
20
10
10
Z
Y1
Y1
mm
80
50
50
3RV1...
3RV1...
2T1
4T2 6T3
1L1
3L2 5L3
X2
3RT1...
Y2
Y3
3RT1...
Size S0
Mounted on an insulated base
plate. When screws are used to
retain the device, these screws
may not be grounded.
The mounting rail adapter can
be alternatively used without
any restrictions.
3-phase busbar
1L1
3L2 5L3
1L1
3RV1...
2T1
4T2 6T3
3L2 5L3
3RV1...
2T1
4T2 6T3
1L1
3L2 5L3
Size S0:
3RV19 15-1AB
Supply side
1L1
Size S2:
3RV19 35-1A
Supply side
3L2 5L3
1L1
3RV1...
2T1
Size S2/S3
Mounting on an insulated base
plate.
A mounting rail adapter can be
alternatively used.
Mounting for
size S0 from 7.5 to 11 kW
4T2 6T3
3L2 5L3
3RV1...
2T1
4T2 6T3
1L1
3L2 5L3
3RT1...
3RT1...
2T1
4T2 6T3
Load side
Load side
48
Rated operating
voltage
Clearance to grounded or
live parts and components (mm)
A
B
C
D 1
E
3VU2.1
690 V
100
25
30
35
107
3VU2.2
690 V
100
25
30
35
107
3VU2.3
690 V
100
25
30
35
107
3VU2.4
690 V
125
30
30
107
3VU2.5
690 V
125
30
30
107
Contactor
D*
Refer to the mounting regulations for 400/500 V AC for the clearances to grounded parts
and components for 3RT10/3RT12 contactors (sizes S6/S10/S12)
Refer to the mounting regulations for 400/500 V AC for the clearances to grounded parts
and components for 3RT10/3RT12 contactors (sizes S6/S10/S12) with mounted
3RB10/3RB12/3UF5 overload relays
49
Notes
50
51
SIRIUS SC Solid-State
Switching Devices
Siemens AG 2005
SIRIUS Switching
SIRIUS Commanding
and Signaling
Name
Telephone/Fax
SIRIUS AND
MORE
Street/Postal Code/City
Company/department
ENGINEERING SUPPLYING
SIRIUS Supplying
DISPO 27601
SIRIUS
Detecting
SIRIUS Product
Overview
SIRIUS Infeed
System
SIRIUS
Starting
Printed in Germany
SIRIUS
Protecting
ECOFAST
AS-Interface
COMMANDING DETECTING
AND SIGNALING
MONITORING
STARTING
AND CONTROLLING