Page 1 of 6 D A T A S H E E T 85005-0093

Not to be used for installation purposes. Issue 5


EST Catalog u EST2 Mid-Range Life Safety Systems
0
5
-
1
8
-
1
1
EST2 Audio
Control
Overview
EST2 Audio Fire Alarm is modular in design. Audio control panels
provide all the features of EST2 with the added benet of one or
two channel audio. Audio cabinets integrate both Fire Alarm con-
trol equipment and audio control equipment ensuring both func-
tionality and aesthetics. When distributed amplication is needed a
single APS power supply cabinet supports mounting of up to two
50 watt distributed ampliers in remote locations.
The EST2 audio panel provides an efcient emergency paging,
evacuation signaling and reghters telephone system in perfectly
integrated modular packages.
Standard Features
Uniform system design
One or two channel audio
Congure with or without Fireghters telephone
30 and 50 watt distributed ampliers
Integral 15 function tone generator
Page by reghters telephone with four state phones
Signature series detectors and modules supported
Class B or A Signature data circuit(s)
96 detectors and 94 modules per circuit
Two integral Class A or B notication appliance circuits
576 event history log
Page 2 of 6 D A T A S H E E T 85005-0093
Not to be used for installation purposes. Issue 5
Installation and Mounting
Application
EST2 audio suits applications requiring emergency voice paging
and evacuation signaling with or without reghters telephone.
Single channel or dual channel applications easily congure
using Signature distributed ampliers. Distributed ampliers are
available in 30 watt and 50 watt sizes. All EST2 audio ampliers
easily congure for 25Vrms or 70Vrms operation through simple
jumper selection.
EST2 with SIGA Ampliers:
Signature ampliers provide Class B or Class A wiring of audio
output circuits. Speakers connect directly to the output of the
SIGA amplier or the amplier output can run as an audio riser
to signature modules where speaker zone selection is made.
Each SIGA amplier has a built in 1kHz tone generator and
provision for a back up amplier. Should an amplier lose its input
signal the output will switch to a back up amplier. If there is no
back up amplier or the output from the back up is unavailable the
output will receive the internal 1kHz tone as the evacuation signal.
For installations requiring reghters telephone, EST2 offers a
master telephone module that allows communication with remote
telephone stations. System paging is available through the front
panel master microphone or through remote telephone stations
when congured. Six front panel switches allow the emergency
user to Page to the EVAC riser, Page to the ALERT riser or quickly
place EVAC or ALERT tones on the risers.
29.9 in
(75.94 cm)
27.13 in
(68.64 cm)
Door
Top View
Bottom View
5.33 in
(13.53cm)
4.2 in
(10.67cm)
Optional 2-DFK(R) Trim Strip
for Semi-Flush Mounting
3/4" (1.9 cm) Wide
Side
View
Front View
All conduit knockouts
1/2" or 3/4"
(1.3 cm or 1.9 cm)
Do NOT install conduit here
if batterys are to be installed
in this cabinet.
2-MCM or APS
2-MCM
Main controller
Module
2-PPS series
Power Supply
2-AAC
Audio Controller
AAxx
Audio Amplifier
or 2-MCM
AAxx
Audio Amplifier
AAxx
Audio Amplifier
AAxx
Audio Amplifier
AAxx
Audio Amplifier
2-LCX
Loop Expander Module
Do NOT install conduit here
if batterys are to be installed
in this cabinet.
Front View
Side
View
16.16 in
(42.16 cm)
5.33 in
(13.53 cm)
Optional 2-LFK(R) Trim Strip
for Semi-Flush Mounting
3/4" (1.9 cm) Wide
4.2 in
(10.67 cm)
29.9 in
(75.94 cm)
All conduit knockouts
1/2" or 3/4"
(1.3 cm or 1.9 cm)
Top View
Door
BottomView
2-MCM
Main controller Module
2-PPS series
Power Supply
2-LCX
Loop Expander Module
2-AAC
Audio Controller
AAxx
Audio Amplifier
16.2 in
(41.15 cm)
Top View
Do NOT install conduit
in this area if batteries
installed in cabinet
All conduit knockouts
for 1/2" or 3/4" conduit
(1.3 cmor 1.9 cm)
3.45 in
(8.76cm)
APS
Auxiliary Power Supply
AAxx
Audio Amplifier
AAxx
Audio Amplifier
Door
21.0 in
(53.34 cm)
Bottom View
Front View
2-WB3
2-WB7
RACCR
Page 3 of 6 D A T A S H E E T 85005-0093
Not to be used for installation purposes. Issue 5
Typical Zoned Amplier Wiring
2
Typical Speaker Circuit
25Vrms or 70Vrms
Audio Outputs
UL/ULC Listed
47KOhm EOL
UL/ULC Listed
47KOhm EOL
Typical Audio
Return (Class A Only)
UL/ULC Listed
47KOhm EOL
- +
Style Y (Class B)
Typical
Telephone
Circuit:
1
1
1 1
2
2
2
2
2
SIGA-CC1
Typical Speaker Circuit
25Vrms or 70Vrms
Audio Outputs
Typical Two Channel Audio
Panel interconnect 1vrms or
25Vrms.
PHONE
RISER OUT
To Next Device
or 47KOhm EOL
Resistor
UL/ULC Listed
47KOhm EOL
Typical Audio
Channel Return
(Class A Only)
(+)
Signature DATA OUT
To All Signature Devices
(-)
DATA OUT
To Next Device
DATA IN
(+)
(+)
(-)
(-)
From Signature Controller
or Previous Signature Device
1
2
Twisted-Shielded Pair Wire
One Twisted Pair Wire, Shield optional
AMP
APS
AMP
120VAC 50/60 Hz
or 220VAC 50/60Hz
120VAC 50/60 Hz
or 220VAC 50/60Hz
AC POWER
DISABLE
CPU FAIL TROUBLE
ALARM
SUPERVISORY GND FAULT
MONITOR TEST
RESET
DRILL
ALARM SUPVR
ACK
TRBLE MONTR
ALARM SILENCE
TROUBLE SILENCE
1
4
7
2
5
8
0
3
6
9
STATUS
ENABLE
ACTIVATE RESTORE
TEST
PROGRAM
DISABLE
REPORTS
PHONE TO EVAC
PHONE TOALERT
PAGE TO EVAC
PAGE TOALERT
EVAC
ALERT
SILENCE CALL IN
PHONE
CALL IN SILENCED
APS Series Power Supply
Page 4 of 6 D A T A S H E E T 85005-0093
Not to be used for installation purposes. Issue 5
Typical Distributed Banked Amplier Wiring
Typical Two Channel
25Vrms or 70Vrms
Audio Outputs SIGA-
CC1, CC2, or UM
SIGA-
CC1, CC2, or UM
SIGA-
CC1, CC2, or UM
UL/ULC Listed
47K EOL Ohm
Typical Audi o
Channel Return
(Class A Only)
UL/ULC Listed
47K EOL
- +
Style Y (Class B)
Typical
Te lephone
Circuit:
1
1
1 1
2
2
2
2
CC1
Typical Two Channel
25Vrms or 70Vrms
Audio Outputs
Typical Two Channel Audi o
Panel interconnect 1vrms or
25Vrms.
PHONE
RISER OUT
To Next Device
or 47K EOL
Resistor

UL/ULC Listed
47K Ohm EOL
SIGA-
CC1, CC2, or UM
SIGA-
CC1, CC2, or UM
SIGA-
CC1, CC2, or UM
Typical Audi o
Channel Return
(Class A Only)
SIGA-CC2
SIGA-CC2
SIGA-CC2
CC2
CC 2
CC 2
(+ )
Signature DATA OU T
To Al l S ignature Devices
(-)
DATA OU T
To Next Device
DATA IN
(+)
(+)
(-)
(-)
From Signature Controlle r
or Previous Signature Device
1
2
Twisted-Shielded Pair Wire
One Twisted Pair Wire, Shield optional
AC POWER
DISABLE
CP U F AI L TROUBLE
ALAR M
SUPER VISO RY GND FA ULT
MONIT OR TEST
RESE T
DRILL
ALARM SUPVR
AC K
TRBL E MONT R
ALARM SILENC E
TROUBLE SILENC E
1
4
7
2
5
8
0
3
6
9
ST AT US
ENABL E
ACTIV AT E REST OR E
TEST
PROGRAM
DISABLE
REPO RT S
PHONE TO EV AC
PHON E TO ALER T
PA GE TO EV AC
PAGE TO ALER T
EV AC
ALER T
SILENCE CALL IN
PHONE
CALL IN SILENCED
APS Series Power Supply
Page 5 of 6 D A T A S H E E T 85005-0093
Not to be used for installation purposes. Issue 5
Specications
Power Supplies 2-PPS 2-PPS/6A 2-PPS/220 2-PPS/6A-220
Notication Appliance
Power
3.5 Amps
@24 Vdc nominal
Two 3.2 Amp Taps
@24 Vdc nominal
3.5 Amps
@24 Vdc nominal
Two 3.2 Amp Taps
@24 Vdc nominal
Auxiliary Output Power 500mA Max N/A 500mA Max N/A
Line Power 120 Vac 300Watts Max, 50/60Hz 220-240 Vac 300 Watts Max, 50/60Hz
Agency Listings UL
Maximum Battery Size
Two 18 Amp Hour in 2-WB3
Two 18 Amp Hour or 11 Amp Hour batteries in 2-WB7 (See Note 1)
Note 1: For applications over 17 Amp hour and up to 24 Amp hour use BC-1.
Main Controller/Display (2-MCD)
Signature Data Circuit One Standard. Expandable to two with optional 2-LCX
Devices per SDC 96 Detectors, 94 Modules Maximum - 96 Isolators or Relay Bases
Terminal Wire Gauge 18-12 AWG (0.75-2.5 mm)
Relative Humidity 10-93% non condensing
Temperature Rating 0-49C (32 - 120F)
Wiring Styles Class A or Class B
Standard Auxiliary relays 1 Alarm Contact - 24 Vdc 1Amp; 1 Trouble Contact - 24 Vdc 1Amp; 1 Supervisory Contact - 24 Vdc 1Amp
Audio Control (2-AAC)
Agency Listings UL, ULC, FM
Standby Power 24 Vdc @ 65mA, 75mA with 2-TEL
Active Power 24 Vdc @ 110mA
Frequency Response 400Hz to 4kHz
Output Level Distortion Wiring
Conguration
Two Audio Outputs Channels 1 Vrms <1% Two Channels Class B or Class A
Auxiliary Inputs Input Impedance Input Level Two Electrically Isolated Inputs 10K Ohm 0.5 to 1.75 Vrms
Loading 15 Signature Ampliers Max.; 100 Ohm Max. 0.2F Max.
Supervision DC: 47K Ohm EOL or AC Audio Pulse
Internally Generated Tones
Slow Whoop
1kHz Steady
1kHz Morse U
Chime Hi-Lo
Horn Temporal (3-3-3)
1kHz 20 Beats per min.
Fast Whoop
1kHz March Time
Hi-Lo
Horn
Low Tone
Fast Hi-Lo Tone
4-4 Code
1kHz @ 120 Beats per min.
Microphone Dynamic, Push - to - Talk; 2-MIC mounts on inner door of 2-WB3 or 2-WB7
Fireghters Telephone Max. Five remote phones active. 2-TEL mounts on Inner door of 2-WB7
Relative Humidity 10-93% non condensing
Temperature Rating 0-49C (32 - 120F)
Wiring Styles Class A or Class B
Page 6 of 6 D A T A S H E E T 85005-0093
Not to be used for installation purposes. Issue 5
0
5
-
1
8
-
1
1
Detection & alarm since 1872
U.S.
T 888-378-2329
F 866-503-3996
Canada
Chubb Edwards
T 519 376 2430
F 519 376 7258
Southeast Asia
T : +65 6391 9300
F : +65 6391 9306

India
T : +91 80 4344 2000
F : +91 80 4344 2050

Australia
T +61 3 9239 1200
F +61 3 9239 1299
Europe
T +32 2 725 11 20
F +32 2 721 86 13
Latin America
T 305 593 4301
F 305 593 4300
utcreandsecurity.com
2010 UTC Fire & Security.
All rights reserved.
Ordering Information
Catalog
Number
Description
Ship Wt.
lb. (kg)
Electronics
2-MCD Main Control and Display (add -CC for City of Chicago) 1.5 (.7)
2-PPS 4.5 amp power supply 120VAC 2.5 (1.1)
2-PPS/220 4.5 amp power supply 220VAC 2.5 (1.1)
2-PPS/6A 6.4 amp power supply 120VAC 2.5 (1.1)
2-PPS/6A-220 6.4 amp power supply 220VAC 2.5 (1.1)
2-MIC Master Paging Microphone (add -CC for City of Chicago) 3 (1.3)
2-TEL Fireghters Master Telephone 4 (1.8)
2-AAC Audio controller (add -CC for City of Chicago) 1 (.45)
Wallboxes
2-WB3
EST2 Long Surface Wallbox - Gray nish.
For Semi-Flush mounting order trim Kit. See note 1.
20 (9)
2-WB3D Inner and outer doors for 2-WB3 wallbox. See note 1. 18 (8.2)
2-WB7
EST2 Double Wide Surface Wallbox - Gray nish.
For semi-Flush mounting order trim Kit. See note 1.
39 (17.7)
2-WB7D Inner and outer doors for 2-WB7 wallbox. See note 1. 36 (16)
RACCR Remote Audio Closet Cabinet. Red Finish 19 (8.6)
RACCDR Door for RACCR wallbox 13 (5.9)
Trim Kits
2-LFK Long Semi-Flush Trim Kit for 2-WB3 wallbox. See note 1. 4 (1.8)
2-DFK Double Wide Semi-Flush Trim Kit for 2-WB7 box. See note 1. 5 (2.3)
Note: 1. Standard nish is gray, red versions are available by adding sufx R to the catalog number e.g.
2-WB3R.
Related Equipment
SIGA-AA30 30 Watt Intelligent Audio Amplier 2 (.9)
SIGA-AA50 50 Watt Intelligent Audio Amplier 2 (.9)
APS6A 6.5 Amp Auxiliary Power Supply
26 (11.8)
APS6A/230 6.5 Amp Auxiliary Power Supply (220V)
APS10A 10 Amp Auxiliary Power Supply
APS10A/230 10 Amp Auxiliary Power Supply (220V)