Installation calculation report

New_project

Page 2/26

Content

Project description.................................................................................................................. 3
1.1

Project general settings................................................................................................................... 3

1.2

Settings for wiring device calculation............................................................................................ 3

1.3

List of loads...................................................................................................................................... 3

Installation general design.....................................................................................................5


2.1

Single line diagram of the installation............................................................................................ 5

2.2

List of devices.................................................................................................................................. 6

Calculation notes...................................................................................................................11
3.1

Source circuits................................................................................................................................ 11

3.2

Generator circuits........................................................................................................................... 11

3.3

LV Source circuits.......................................................................................................................... 11

3.4

Capacitor bank circuits.................................................................................................................. 11

3.5

Feeder circuits................................................................................................................................ 12

3.6

LV Transformer circuits................................................................................................................. 12

3.7

Generic load circuits...................................................................................................................... 13

3.8

Lighting load circuits..................................................................................................................... 14

3.9

Power socket load circuits............................................................................................................ 14

3.10

Motor starter combination........................................................................................................ 14

3.11

Busbar circuits.......................................................................................................................... 15

3.12

Busbar truncking system circuits...........................................................................................15

3.13

Lighting Busbar truncking system circuits............................................................................15

Project: New_project

24/10/2014

Page 3/26

1 Project description
1.1 Project general settings
Installation standard

IEC60364

Calculation standard
Circuit breaker standard
Frequency

TR50480
IEC 60947-2
50 Hz

1.2 Settings for wiring device calculation


Maximal CSA

240 mm

1.3 List of loads


Name
AA 3
AA 8

Name
EA 10

Name
MA 9

1.3.1 Generic loads


Sr (kVA)
Pr (kW) Ir (A)
250
200
361
111
100
160

Cos
0.8
0.9

Nbr
1
1

1.3.2 Lighting distribution


Type of lamp P Lamp (W)
P ballast (W)
Fluorescent
18
4.5
with
ferromagnetic
ballast
1.3.3 Motor loads
Sr (kVA)
Pr (kW) Ir (A)
67.2
58.5
97

Project: New_project

Cos
0.87

Nbr
1

Polarity
3Ph+N
3Ph+N

Non linear load THDi 3 (%)


No
0
No
0

Nb of lamp/light
1

Polarity
3Ph

Nb of light
10

Non linear load THDi 3 (%)


No
0

24/10/2014

Page 4/26

2 Installation general design


2.1 Single line diagram of the installation

Project: New_project

24/10/2014

Page 5/26

Project: New_project

24/10/2014

Page 6/26

2.2 List of devices


2.2.1 MV/LV transformer
Nbr Range
Insulation

Name

My bin p 1

Trihal

Dry-type

Sr (kVA)

ukrT (%) Connection U2 (V) SEA

400

2.2.2 LV switchboards and busbar


Switchboard name
Range
UC 2
No preference
UC 7
No preference
Busbar name

Switchboard
name
UC 2
UC 7

WC 1
WC 6
2.2.3
Nbr

Name
My ct
ngun

My ct ti 1 1
QA 4

My ct ti 2 1
My ct ti
C

My ct ti
n

Name
QB 4

Circuit breaker
Range Rating (A)
Designation
Compact
630
NSX NSX630F
Compact
400
NSX NSX400F
Compact
250
NSX NSX250B
Compact
250
NSX NSX250B
Compact
160
NSX NSX160F
Acti9 iC60 - 0.5
iC60N

Rating (A)
0.00
0.00

IP
Undefined
Undefined

Polarity

SEA

Equipotential bounding

1
1

3Ph+N
3Ph+N

TN-S
TN-S

With
Without

Poles

Trip unit/Curve

4P4d

Micrologic 5.3 A

4P4d

Micrologic 2.3

4P4d

Micrologic 2.2

4P4d

Micrologic 2.2

3P3d

MA

4P4d

RCD

RCD

RCD class

RCD class

Cable schedule

Name Nbr Incomer


Dy
1
My ct
ni ti
ti 1
1
WD 8 1
My ct
ti 2
WD 10 1
My ct
ti n
Project: New_project

TN-S

Ks

2.2.4 Switch
Nbr Range Rating (A) Poles
1
Interpact 250
4P
INS250_
100-630

2.2.5

420

Rb
(m)
10000

Feeder Type
AA 3
Multi-core

Insulation L (m)
XLPE
60

L1/L2/L3
1x150
Copper

N
1x150
Copper

PE/PEN
1x75
Copper

AA 8

Single-core

XLPE

50

EA 10

Multi-core

XLPE

25

1x50
Copper
1x1.5
Copper

1x50
Copper
1x1.5
Copper

1x25
Copper
1x4 Copper
24/10/2014

Page 7/26

WD 9

Dy
ni
WD 4

1
1

My ct
ti C
My
bin p
QA 4

Project: New_project

MA 9

Multi-core

XLPE

25

My ct Multi-core
ngun
QB 4
Multi-core

XLPE

15

XLPE

10

1x16
Copper
2x120
Copper
1x70
Copper

2x120
Copper
1x70
Copper

1x16
Copper
1x120
Copper
1x35
Copper

24/10/2014

Page 8/26

3 Calculation notes
3.1 Source circuits
3.1.1 Circuit Source 0
MV power supply
W0
Max. upstream short circuit power 500 MVA
Min. upstream short circuit power 250 MVA
MV/LV transformer
Range
Technology
Rated power
ukrT
Type of losses
PkrT
System earthing arrangement
MV Connection
LV Connection
No load secondary voltage Ur0
Ur LV
Rb (neutral grounding)
Ra (mass grounding)
Cable
Parameters
Length
Installation method

My bin p
Trihal
Dry-type
400 kVA
6%
Normal
4800 W
TN-S
D
yn
420V
400V
NA
NA
Dy ni

15 m
31
E
multi-core cables on horizontal
perforated tray
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
XLPE
Ambient temperature
30 C
Level of third harmonic THDI
0%
Ib
577 A
Sizing constraint
Iz
Sizing Information
Correction factors
Temperature factor
Standard table reference
Soil thermal resistivity factor
Standard table reference
Loaded neutral factor
Standard table reference
Touching conductor factor
Standard table reference
Fuse coefficient factor
Project: New_project

1
A-52-14
1
A-52-16
1
D-52-1
0.88
E
1
24/10/2014

Page 9/26

1
0.88

User correction factor


Overall factor

Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

2x120 mm
Copper
609 A
2x120 mm
Copper
609 A
1x120 mm
Copper

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 9.48
8.21

9.48

6.77

7.55

0.00 0.00

Synthesis for all operating mode


(kA) 9.48
8.21
9.48

6.77

7.55

0.00 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Circuit breaker
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr
Short delay settings
Isd current
Tsd
Instantaneous tripping
Ii current

Design current
IL1

IL2

Operating mode Normal


(A)
533.531
533.457
Project: New_project

My ct ngun
Compact NSX
NSX630F
630 A
36 kA
NA
NA
NA
4P4d
Micrologic 5.3 A
630 A
578 A
16 s
5780 A
0s
6930 A

IL3
533.457

IN
0.075
24/10/2014

Page 10/26

Synthesis for all operating mode


(A)
533.531
533.457

533.457

0.075

Voltage drop
Cumulated from upstream
Operating mode Normal
0.392
U3L (%)
0.453
UL1L2 (%)
0.453
UL2L3 (%)
0.453
UL3L1 (%)
0.392
UL1N (%)
0.392
UL2N (%)
0.392
UL3N (%)

Project: New_project

Circuit
0.392
0.453
0.453
0.453
0.392
0.392
0.392

24/10/2014

Page 11/26

3.2 Feeder circuits


3.2.1 Circuit My ct nhnh 2
Circuit breaker
QA 4
Range
Compact NSX
Designation
NSX250B
Circuit breaker rating
250 A
Breaking capacity
25 kA
TNS One pole breaking capacity NA
IT One pole breaking capacity NA
Reinforced breaking capacity
NA
Pole & protected pole
4P4d
Trip unit designation
Micrologic 2.2
Trip unit rating
250 A
Long delay settings
Ir
232 A
Tr
16 s
Short delay settings
Isd current
2325 A
Tsd
0.02 s
Instantaneous tripping
Ii current
3000 A

Cable
Parameters
Length
Installation method

WD 4

10 m
31
E
multi-core cables on horizontal
perforated tray
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
XLPE
Ambient temperature
30 C
Level of third harmonic THDI
0%
Ib
232 A
Sizing constraint
Iz
Sizing Information
Correction factors
Temperature factor
Standard table reference
Soil thermal resistivity factor
Standard table reference
Loaded neutral factor
Standard table reference
Touching conductor factor
Standard table reference
Project: New_project

1
A-52-14
1
A-52-16
1
D-52-1
1
E
24/10/2014

Page 12/26

1
1
1

Fuse coefficient factor


User correction factor
Overall factor

Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

1x70 mm
Copper
246 A
1x70 mm
Copper
246 A
1x35 mm
Copper

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 9.19
7.96

8.91

6.37

6.63

6.56 0.00

Synthesis for all operating mode


(kA) 9.19
7.96
8.91

6.37

6.63

6.56 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Switch
QB 4
Range
Interpact INS250_100-630
Designation
INS250
Rating
250 A
Icm (making capacity)
30 kA
Icw
8.5 kA - 1 s.
Cascading with upstream circuit No
breaker
Reinforced short circuit
NA
withstand
Pole
4
Design current
IL1

IL2

IL3

IN

Operating mode Normal


(A)
231.969
231.886

231.886

0.083

Synthesis for all operating mode


(A)
231.969
231.886

231.886

0.083

Voltage drop
Cumulated from upstream
Operating mode Normal
0.731
U3L (%)
Project: New_project

Circuit
0.339
24/10/2014

Page 13/26

UL1L2 (%)
UL2L3 (%)
UL3L1 (%)
UL1N (%)
UL2N (%)
UL3N (%)

Project: New_project

0.844
0.844
0.844
0.731
0.731
0.731

0.391
0.391
0.391
0.339
0.339
0.339

24/10/2014

Page 14/26

3.3 Generic load circuits


3.3.1 Circuit MCH NG LC 1
Circuit breaker
My ct ti 1
Range
Compact NSX
Designation
NSX400F
Circuit breaker rating
400 A
Breaking capacity
36 kA
TNS One pole breaking capacity NA
IT One pole breaking capacity NA
Reinforced breaking capacity
NA
Pole & protected pole
4P4d
Trip unit designation
Micrologic 2.3
Trip unit rating
400 A
Long delay settings
Ir
368 A
Tr
16 s
Short delay settings
Isd current
2944 A
Tsd
0.02 s
Instantaneous tripping
Ii current
4800 A

Cable
Parameters
Length
Installation method

Dy ni ti 1

60 m
31
E
multi-core cables on horizontal
perforated tray
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
XLPE
Ambient temperature
30 C
Level of third harmonic THDI
0%
Ib
361 A
Sizing constraint
Iz
Sizing Information
Correction factors
Temperature factor
Standard table reference
Soil thermal resistivity factor
Standard table reference
Loaded neutral factor
Standard table reference
Touching conductor factor
Project: New_project

1
A-52-14
1
A-52-16
1
D-52-1
1
24/10/2014

Page 15/26

E
1
1
1

Standard table reference


Fuse coefficient factor
User correction factor
Overall factor

Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

1x150 mm
Copper
399 A
1x150 mm
Copper
399 A
1x95 mm
Copper

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 9.19
7.96

8.91

5.29

4.74

4.54 0.00

Synthesis for all operating mode


(kA) 9.19
7.96
8.91

5.29

4.74

4.54 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Charge
U
S
P
I
cos
Polarity
Phase connection
Number of circuit
Ku (Normal)
Harmonic generator
THDI3
Design current
IL1

AA 3
400 V
250 kVA
200 kW
361 A
0.8
3Ph+N
1
1
No
0%
IL2

IL3

IN

Operating mode Normal


(A)
360.844
360.844

360.844

Synthesis for all operating mode


(A)
360.844
360.844

360.844

Voltage drop
Cumulated from upstream
Project: New_project

Circuit
24/10/2014

Page 16/26

Operating mode Normal


2.027
U3L (%)
2.340
UL1L2 (%)
2.340
UL2L3 (%)
2.340
UL3L1 (%)
2.027
UL1N (%)
2.027
UL2N (%)
2.027
UL3N (%)

1.635
1.888
1.888
1.888
1.635
1.635
1.635

Synthesis for all operating mode


2.027
U3L (%)
2.340
UL1L2 (%)
2.340
UL2L3 (%)
2.340
UL3L1 (%)
2.027
UL1N (%)
2.027
UL2N (%)
2.027
UL3N (%)

Project: New_project

24/10/2014

Page 17/26

3.3.2 Circuit MCH NG LC 2


Circuit breaker
My ct ti 2
Range
Compact NSX
Designation
NSX250B
Circuit breaker rating
250 A
Breaking capacity
25 kA
TNS One pole breaking capacity NA
IT One pole breaking capacity NA
Reinforced breaking capacity
NA
Pole & protected pole
4P4d
Trip unit designation
Micrologic 2.2
Trip unit rating
250 A
Long delay settings
Ir
161 A
Tr
16 s
Short delay settings
Isd current
1288 A
Tsd
0.02 s
Instantaneous tripping
Ii current
3000 A

Cable
Parameters
Length
Installation method

WD 8

Sizing Information

The CSA of cable WD 8 has been


increased from 35 to 50 to comply with
the voltage drop in the circuit.

50 m
31
F
single-core cables on horizontal
perforated tray
Type of cable
Single-core
Nb of additional touching circuits 0
Insulation
XLPE
Ambient temperature
30 C
Level of third harmonic THDI
0%
Ib
160 A
Sizing constraint
Voltage drop

Correction factors
Temperature factor
Standard table reference
Soil thermal resistivity factor
Standard table reference
Loaded neutral factor
Standard table reference
Touching conductor factor
Standard table reference
Fuse coefficient factor
User correction factor
Project: New_project

1
A-52-14
1
A-52-16
1
D-52-1
0.98
F
1
1
24/10/2014

Page 18/26

0.98

Overall factor

Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

1x50 mm
Copper
212 A
1x50 mm
Copper
212 A
1x25 mm
Copper

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 8.72
7.55

7.98

4.04

2.99

2.05 0.00

Synthesis for all operating mode


(kA) 8.72
7.55
7.98

4.04

2.99

2.05 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Charge
U
S
P
I
cos
Polarity
Phase connection
Number of circuit
Ku (Normal)
Harmonic generator
THDI3
Design current
IL1

AA 8
400 V
111 kVA
100 kW
160 A
0.9
3Ph+N
1
1
No
0%
IL2

IL3

IN

Operating mode Normal


(A)
160.375
160.375

160.375

Synthesis for all operating mode


(A)
160.375
160.375

160.375

Voltage drop
Cumulated from upstream
Operating mode Normal
2.348
U3L (%)
2.711
UL1L2 (%)
2.711
UL2L3 (%)
Project: New_project

Circuit
1.617
1.867
1.867
24/10/2014

Page 19/26

UL3L1 (%)
UL1N (%)
UL2N (%)
UL3N (%)

2.711
2.348
2.348
2.348

1.867
1.617
1.617
1.617

Synthesis for all operating mode


2.348
U3L (%)
2.711
UL1L2 (%)
2.711
UL2L3 (%)
2.711
UL3L1 (%)
2.348
UL1N (%)
2.348
UL2N (%)
2.348
UL3N (%)

Project: New_project

24/10/2014

Page 20/26

3.4 Lighting load circuits


3.4.1 Circuit TI CHIU SNG
Circuit breaker
My ct ti n
Range
Acti9 iC60
Designation
iC60N
Circuit breaker rating
0.5 A
Breaking capacity
50 kA
TNS One pole breaking capacity NA
IT One pole breaking capacity NA
Reinforced breaking capacity
NA
Pole & protected pole
4P4d
Trip unit designation
C
Trip unit rating
0.5 A
Long delay settings
Ir
0.5 A
Tr
NA
Short delay settings
Isd current
4.25 A
Tsd
NA
Instantaneous tripping
Ii current
NA

Cable
Parameters
Length
Installation method

WD 10

25 m
31
E
multi-core cables on horizontal
perforated tray
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
XLPE
Ambient temperature
30 C
Level of third harmonic THDI
0%
Ib
0A
Sizing constraint
Iz
Sizing Information
Correction factors
Temperature factor
Standard table reference
Soil thermal resistivity factor
Standard table reference
Loaded neutral factor
Standard table reference
Touching conductor factor
Project: New_project

1
A-52-14
1
A-52-16
1
D-52-1
1
24/10/2014

Page 21/26

Standard table reference


Fuse coefficient factor
User correction factor
Overall factor

Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

E
1
1
1

1x1.5 mm
Copper
23 A
1x1.5 mm
Copper
23 A
1x4 mm
Copper

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 8.72
7.55

7.98

0.47

0.27

0.39 0.00

Synthesis for all operating mode


(kA) 8.72
7.55
7.98

0.47

0.27

0.39 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Charge
U
S
P
I
cos
Ku (Normal)
Number of circuit
Polarity
Phase connection
Type of luminaries
Nb of luminaries
Nb of lights/luminaries
Lights power
Ballast power
Ia
Harmonic generator
THDI3
Design current
IL1

EA 10
400 V
0.3 kVA
0.225 kW
0.433 A
0.9
0.85
1
3Ph+N
Fluorescent with ferromagnetic ballast
1
10
18 W
4.5 W
0.433 A
No
0%
IL2

Operating mode Normal


(A)
0.368
0.276

Project: New_project

IL3
0.276

IN
0.092

24/10/2014

Page 22/26

Synthesis for all operating mode


(A)
0.368
0.276

0.276

0.092

Voltage drop
Cumulated from upstream
Operating mode Normal
0.788
U3L (%)
0.901
UL1L2 (%)
0.893
UL2L3 (%)
0.901
UL3L1 (%)
0.802
UL1N (%)
0.788
UL2N (%)
0.788
UL3N (%)

Circuit
0.057
0.057
0.049
0.057
0.071
0.057
0.057

Synthesis for all operating mode


0.788
U3L (%)
0.901
UL1L2 (%)
0.893
UL2L3 (%)
0.901
UL3L1 (%)
0.802
UL1N (%)
0.788
UL2N (%)
0.788
UL3N (%)

Project: New_project

24/10/2014

Page 23/26

3.5 Motor starter combination


3.5.1 Circuit TI NG C
Circuit breaker
My ct ti C
Range
Compact NSX
Designation
NSX160F
Circuit breaker rating
160 A
Breaking capacity
36 kA
TNS One pole breaking capacity NA
IT One pole breaking capacity NA
Reinforced breaking capacity
NA
Pole & protected pole
3P3d
Trip unit designation
MA
Trip unit rating
100 A
Long delay settings
Ir
100 A
Tr
NA
Short delay settings
Isd current
1400 A
Tsd
NA
Instantaneous tripping
Ii current
NA
Contactor
Designation
Type of coordination

LC1D115
LC1D115
T1

Thermal relay
Designation
Ir

LRD4367
LRD4367
97

Cable
Parameters
Length
Installation method

WD 9

25 m
31
E
multi-core cables on horizontal
perforated tray
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
XLPE
Ambient temperature
30 C
Level of third harmonic THDI
0%
Ib
97 A
Sizing constraint
Iz
Sizing Information
Correction factors
Temperature factor
Standard table reference
Project: New_project

1
A-52-14
24/10/2014

Page 24/26

1
A-52-16
1
D-52-1
1
E
1
1
1

Soil thermal resistivity factor


Standard table reference
Loaded neutral factor
Standard table reference
Touching conductor factor
Standard table reference
Fuse coefficient factor
User correction factor
Overall factor

Selected phase
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

1x16 mm
Copper
100 A
1x16 mm
Copper

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 8.72
7.55

0.00

3.39

0.00

2.27 0.00

Synthesis for all operating mode


(kA) 8.72
7.55
0.00

3.39

0.00

2.27 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Asynchronous LV Motor
Startup type
U
Mechanical power
Startup current Id/Ir
Transient current Id/Ir
Ir for sizing
Sr for sizing
Pr for sizing
cos
Polarity
Number of circuit
Ku (mode Normal)
Harmonic generator
THDI3
Design current
IL1

MA 9
Direct on line
400 V
55 kW
7.2
<=19
97 A
67.2 kVA
58.5 kW
0.87
3Ph
1
1
No
0%

IL2

Operating mode Normal


(A)
97.000
97.000

IL3
97.000

IN
0

Synthesis for all operating mode


Project: New_project

24/10/2014

Page 25/26

(A)

97.000

97.000

97.000

Voltage drop
Cumulated from upstream

Circuit

Operating mode Normal


2.125
U3L (%)
2.454
UL1L2 (%)
2.454
UL2L3 (%)
2.454
UL3L1 (%)
0.731
UL1N (%)
0.731
UL2N (%)
0.731
UL3N (%)
Startup Voltage drop
UStartUp

1.394
1.610
1.610
1.610
0.000
0.000
0.000

9.729

3.6 Busbar circuits


3.6.1 Circuit WC 1
Busbar
WC 1
Parameters
Switchboard Name
UC 2
Switchboard Range
No preference
Rating (A)
0
IP
Undefined
Feeder
Circuit name
Protection name

Protection type

MCH NG LC 1

My ct ti 1

NSX400F

My ct nhnh 2

QA 4

NSX250B

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 9.19
7.96

8.91

6.77

7.55

7.81 0.00

Synthesis for all operating mode


(kA) 9.19
7.96
8.91

6.77

7.55

7.81 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

3.6.2
Busbar
Project: New_project

Circuit WC 6
WC 6
24/10/2014

Page 26/26

Parameters
Switchboard Name
Switchboard Range
Rating (A)
IP
Feeder
Circuit name

Protection name

Protection type

MCH NG LC 2

My ct ti 2

NSX250B

TI NG C

My ct ti C

NSX160F

TI CHIU SNG

My ct ti n

iC60N

UC 7
No preference
0
Undefined

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 8.72
7.55

7.98

6.37

6.63

6.56 0.00

Synthesis for all operating mode


(kA) 8.72
7.55
7.98

6.37

6.63

6.56 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.