Vous êtes sur la page 1sur 37

WFRA Report No 2208900

Issue Number 2208900a.1


Page 1 of 37

CONSULTANCY • TESTING

TEST DESCRIPTION

FIRE RESISTANCE TEST OF TWO


SINGLE LEAF DOORSETS IN GENERAL
ACCORDANCE WITH BS 476:
PARTS 20 & 22: 1987

TEST APPLICANT

Danube Group
Jebel Ali
UNITED ARAB EMIRATES

TEST DATE
26th October 2007

TESTING AUTHORITY © 2007 Warrington Fire Research Aust Pty Ltd.


Unit 2, 409 - 411 Hammond Road, Dandenong, Victoria 3175, P.O. Box 4282, Dandenong South, Victoria 3164, Australia.
Tel: Int+61 (0)3 9767 1066 Fax: Int+61 (0)3 9767 1001 or (0)3 9767 1051 Email: testing@wfra.com.au,
Home Page: www.wfra.com.au A.B.N. 81 050 241 524

Warrington Fire Research • Australia • New Zealand • United Kingdom • Singapore • China
WFRA Report No 2208900
Issue Number 2208900a.1
Page 2 of 37

DOCUMENT REVISION STATUS

Date Issued Issue No Description

7th November 2007 2208900a.1 Initial Issue

SIGNATORIES
Prepared by: Reviewed by:

A. F. Rayner K. G. Nicholls

On behalf of Warrington Fire Research (Aust) Pty Ltd

GENERAL CONDITIONS OF USE


This report may only be reproduced in full without modifications by the
report applicant only. Copies, extracts or abridgments of this report in any
form shall not be made distributed or published by other organisations
or individuals without the permission in writing from a Director of
Warrington Fire Research (Aust) Pty Ltd.

C ON SU L T AN C Y • TESTING
WFRA Report No 2208900
Issue Number 2208900a.1
Page 3 of 37

CONTENTS

1 CONSTRUCTION DETAILS 4
Test Assembly 4
Test Specimen 4
Assembly and Installation Methods 4
Orientation 4
2 SCHEDULE OF COMPONENTS 5
3 TEST PROCEDURE 8
Statement of compliance 8
Variations from test standards 8
Pre-test conditioning 8
Sampling / Specimen Selection 8
Ambient Temperature 8
Test Duration 9
Instrumentation and Equipment 9
4 TEST MEASUREMENTS 10
Furnace Temperature and Pressure Measurements 10
Specimen Temperatures 10
Deflection Measurements 10
Heat flux Measurement 10
Observations 10
5 TEST RESULTS 11
6 APPLICATION OF TEST RESULTS 12
Test Limitations 12
Variations from the Tested Specimens 12
Uncertainty of measurement 12
APPENDIX 1 DRAWINGS OF TEST ASSEMBLY 13
APPENDIX 2 TEST OBSERVATIONS 19
APPENDIX 3 INSTRUMENTATION POSITIONS 22
APPENDIX 4 TEST DATA 26
A 4.1 Furnace Temperature 26
A 4.2 Furnace Pressure 26
A 4.3 Specimen Temperatures 27
A 4.4 Deflection Measurements 33
A 4.5 Heat Flux Measurement 34
APPENDIX 5 PHOTOGRAPHS 35

C ON SU L T AN C Y • TESTING
WFRA Report No 2208900
Issue Number 2208900a.1
Page 4 of 37

1 CONSTRUCTION DETAILS

TEST ASSEMBLY
The test assembly comprised a nominal 3200mm x 3200mm x 110mm thick
cored concrete block wall incorporating two single leaf particle board core
doorsets.

TEST SPECIMEN
The test specimens comprised two single leaf particle board core doorsets
referred to as Door A and Door B for the purposes of this test report. Further
details are provided in Figures A1.1 to A1.6 and the schedule of components
Section 2.

ASSEMBLY AND INSTALLATION METHODS


The cored concrete block wall was built into a steel restraint frame, incorporating
openings for the doorsets, by a building contractor at WFRA Melbourne
commencing on the 19th October 2007 and under the supervision of a WFRA
representative. The test applicant supplied and installed the single leaf doorsets
(including leafs, frames and all door hardware) commencing on the
24th October 2007 and under the supervision of a WFRA representative.

ORIENTATION
The specimen was installed with Door A swinging towards the furnace and
Door B swinging away from the furnace.

C ON SU L T AN C Y • TESTING
WFRA Report No 2208900
Issue Number 2208900a.1
Page 5 of 37

2 SCHEDULE OF COMPONENTS
ITEM DESCRIPTION
DOOR A
Leaf Size 2350mm high x 1000mm wide x 44mm (nominal) thick door leaf.
Leaf Core The leaf core was stated by the test sponsor to be nominally 44mm thick
and designated as DANUBE “KINGSA” Core supplied by DANUBE.
KINGSA, as stated by the test sponsor, is a particleboard material and
has a nominal dry density of 580kg/m3.
Leaf edging 8mm thick (nominal) beech hardwood.
Reinforcement Nil.
plates
Leaf Facing Nil.
Leaf Seals Lorient IS8010si threshold seal was rebated into the centre of the door
leaf bottom edge.
Hinges 100mm x 75mm x 3mm hinges with 4-off screw fixings through each
plate to the door leaf and door frame. The hinges were fitted to the left
hand side of the door leaf (looking from the unexposed side) with the
door swinging towards the furnace. Hinge areas were additionally
protected with Lorient Intumescent Hinge Protection Kit, refer Figure
A1.6.
Hinge Locations There were 3 hinges positioned at 975mm centres with the lowest hinge
positioned 210mm from the sill to the centre of the hinge.
Frame The solid timber door frame was 90mm wide x 45mm thick with a door
seat rebate of 20mm deep x 46mm wide. The frame was made from
European beech hardwood of a nominal density of 600 kg/m3. The
frames were joined with a mitred and tennon joint that was glued and
screwed into position.
Frame Seals Lorient LP1504DS (Type 617) Intumescent Fire and Smoke Seals, as
stated by the test sponsor, were rebated within the perimeter of the frame
and extended past hinges.
Fixings The timber frame was secured to the opening in the masonry wall with
11-off (5-off per vertical side and 1-off in the head) No 10 x 100mm long
socket head screws into plastic plugs, as stated by the test sponsor, at
maximum spacing 765mm and 125mm from either end.
Lockset Dorma 515 Mortice lock (cylinder mortice lock) with striker centrally
located nominally 1035mm from the sill and a backset of nominally
60mm. The lever handles (Gainsborough generic) were to the
unexposed and exposed sides. The latch throw was nominally 10mm.
Mortice lockset was additionally protected with Lorient Intumescent Lock
Protection Kit, refer Figure A1.6.
Closer DORMA TS73V fitted to exposed side of the doorset.

C ON SU L T AN C Y • TESTING
WFRA Report No 2208900
Issue Number 2208900a.1
Page 6 of 37

ITEM DESCRIPTION

DOOR B
Leaf Size 2350mm high x 1000mm wide x 44mm (nominal) thick door leaf.
Leaf Core The leaf core was stated by the test sponsor to be nominally 44mm thick
and designated as DANUBE “KINGSA” Core supplied by DANUBE.
KINGSA, as stated by the test sponsor, is a particleboard material and
has a nominal dry density of 580kg/m3.
Leaf edging 8mm thick (nominal) beech hardwood.
Reinforcement Nil.
plates
Leaf Facing Nil.
Leaf Seals Lorient IS8010si threshold seal was rebated into the centre of the door
leaf bottom edge.
Hinges 100mm x 75mm x 3mm hinges with 4-off screw fixings through each
plate to the door leaf and door frame. The hinges were fitted to the left
hand side of the door leaf (looking from the unexposed side) with the
door swinging away from the furnace. Hinge areas were additionally
protected with Lorient Intumescent Hinge Protection Kits, refer Figure
A1.6.
Hinge Locations There were 3 hinges positioned at 975mm centres with the lowest hinge
positioned 210mm from the sill to the centre of the hinge.
Frame The solid timber door frame was 90mm wide x 45mm thick with a door
seat rebate of 46mm wide x 20mm deep. The frame was made from
European beech hardwood of a nominal density of 600 kg/m3. The
frames were joined with a mitred and tennon joint that was glued and
screwed into position.
Frame Seals Lorient LP1504DS (Type 617) Intumescent Fire and Smoke Seals, as
stated by the test sponsor, were rebated within the perimeter of the frame
and extended past hinges.
Fixings The timber frame was secured to the opening in the masonry wall with
11-off (5-off per vertical side and 1-off in the head) No 10 x 100mm long
socket head screws into plastic plugs, as stated by the test sponsor, at
maximum spacing 765mm and 125mm from either end.
Lockset Dorma 515 Mortice lock (cylinder mortice lock) with striker centrally
located nominally 1035mm from the sill and a backset of nominally
60mm. The lever handles (Gainsborough generic) were to the
unexposed and exposed sides. The latch throw was nominally 10mm.
Mortice lockset was additionally protected with Lorient Intumescent Lock
Protection Kit, refer Figure A1.6.
Closer DORMA TS73V fitted to unexposed side of the doorset.

C ON SU L T AN C Y • TESTING
WFRA Report No 2208900
Issue Number 2208900a.1
Page 7 of 37

ITEM DESCRIPTION

Supporting Construction
Description 110mm thick cored concrete block wall.
Door Sill One course of solid concrete blocks 10.31s 390mm x 190mm x 90mm
with three courses of concrete bricks 230mm x 110mm x 75mm above
with the top course laid perpendicular to the wall to form a sill for the
doorsets.
Blocks above sill Twelve courses of cored concrete blocks were laid on the sill to form the
openings and an additional three courses were laid above the openings
including one lintel beam course which included a single D16
reinforcement rod with premixed concrete filling the void.
Sealant Lorient intumescent mastic was used to seal the gap (backed by
Rockwool on the RH side and top as gap between 15-20mm) between
the edge of the door frames and the opening in the concrete block wall
on both sides.

C ON SU L T AN C Y • TESTING
WFRA Report No 2208900
Issue Number 2208900a.1
Page 8 of 37

3 TEST PROCEDURE

STATEMENT OF COMPLIANCE
The test was performed in general accordance with the requirements of
BS 476: Part 20: 1987 and BS 476: Part 22: 1987 Part 6 as appropriate for
insulated doorsets, other than the variations stated below.

VARIATIONS FROM TEST STANDARDS


The furnace temperature was measured by 6-off mineral insulated metal
sheathed Type K thermocouples with wire diameters not greater than 1mm and
overall diameter of 3mm with the measuring junction insulated from the sheath.
The thermocouples protruded a minimum of 25mm from steel supporting tubes.
BS 476: Part 20: 1987 specifies the furnace temperature to be measured by 6-off
Nickel chromium/nickel aluminium wire contained within a mineral insulation and
in a heat resisting steel sheet of diameter 1.5mm, the hot junctions being
electrically insulated from the sheath. The thermocouple hot junction shall
project 25mm from a porcelain insulator.
This variation, is considered to make the test slightly more onerous, however
would not have significantly affected the results of the fire-resistance test.

The furnace pressure varied more than as prescribed by BS 476: Part 22: 1987
during the period of 5-15 minutes test duration but was above that prescribed
(maximum pressure level variation +2 Pa). It is considered that the test pressure
has created a more severe exposure than if tested in full accordance
BS 476: Part 22: 1987.

PRE-TEST CONDITIONING
The specimen was stored in the test laboratory prior to testing and was subjected
to indoor ambient normal laboratory conditions for approximately two days (after
wall completion) prior to testing.

SAMPLING / SPECIMEN SELECTION


The laboratory was not involved in the selection of the test specimen for test.

AMBIENT TEMPERATURE
The ambient temperature at the start of the test was 20°C and remained at this
until the end of the test.

C ON SU L T AN C Y • TESTING
WFRA Report No 2208900
Issue Number 2208900a.1
Page 9 of 37

TEST DURATION
The test was terminated after approximately 42 minutes at the request of the test
sponsor.

INSTRUMENTATION AND EQUIPMENT


The instrumentation was provided in accordance with BS 476: Part 22: 1987
except for the furnace control thermocouples as mentioned above.
The furnace temperature was measured by 6-off mineral insulated metal
sheathed Type K thermocouples with wire diameters not greater than 1mm and
overall diameter of 3mm with the measuring junction insulated from the sheath.
The thermocouples protruded a minimum of 25mm from steel supporting tubes.
The non fire side specimen temperatures were measured by Type K
thermocouples with wire diameters less than 0.5mm diameter soldered to 12mm
diameter × 0.2mm thick copper discs covered by a 30mm × 30mm × 2.0 mm
inorganic insulating pads. The thermocouples positions are described in Table
A3.1, and are shown on Figure A3.1 in Appendix 3. A roving thermocouple was
available to measure temperatures at positions that appear hotter than the
positions monitored by fixed thermocouples.
Deflection measurements were taken from calibrated tapes, fixed to the test
specimen, using a Telescope Levelling Instrument (Dumpy Level) Model 200B, at
the positions shown on Figure A3.2 in Appendix 3.
The furnace pressure was measured approximately 1000mm above sill level.
Cotton pads and gap gauges were available during the test to assess the
performance under the criteria for integrity up to unexposed face temperatures of
300°C for both Doorsets. After that time gap gauges only were available to
assess the performance under the criteria for integrity.

C ON SU L T AN C Y • TESTING
WFRA Report No 2208900
Issue Number 2208900a.1
Page 10 of 37

4 TEST MEASUREMENTS

FURNACE TEMPERATURE AND PRESSURE MEASUREMENTS


Furnace temperature and pressure data are provided in A4.1 and A4.2 in
Appendix 4.1.

SPECIMEN TEMPERATURES
Specimen temperature data is provided in A4.3 and Table A4.1 in Appendix 4.

DEFLECTION MEASUREMENTS
Deflection measurement data is provided in A4.4 in Appendix 4.

HEAT FLUX MEASUREMENT


Heat Flux measurements are provided in A4.5 in Appendix 4.

OBSERVATIONS
A table that includes observations of the significant behaviour of the specimen
and details of the occurrence of the various performance criteria specified in
BS 476: Part 22: 1987 is provided in Appendix 2. Photographs of the specimen
are included in Appendix 5.

C ON SU L T AN C Y • TESTING
WFRA Report No 2208900
Issue Number 2208900a.1
Page 11 of 37

5 TEST RESULTS
The specimen achieved the following performance when tested in general
accordance with BS 476: Part 22: 1987 Section 6 as appropriate.

DOOR A

Loadbearing Capacity Not applicable


36 minutes
Integrity Failure by sustained flaming by virtue of flames
on unexposed side at bottom RH corner of door.
36 minutes
Insulation Insulation failure deemed to occur at time of
integrity failure.

DOOR B

Loadbearing Capacity Not applicable


41 minutes
Integrity Failure by sustained flaming by virtue of flames
on unexposed side at bottom of door.
41 minutes
Insulation Insulation failure deemed to occur at time of
integrity failure.

C ON SU L T AN C Y • TESTING
WFRA Report No 2208900
Issue Number 2208900a.1
Page 12 of 37

6 APPLICATION OF TEST RESULTS

TEST LIMITATIONS
The results of this fire test may be used to directly assess fire hazard, but it
should be recognized that a single test method will not provide a full assessment
of fire hazard under all fire conditions. The results only relate to the behaviour of
the specimen of the element of the construction under the particular conditions of
the test; they are not intended to be the sole criteria for assessing the potential
fire performance of the element in use nor do they necessarily reflect the actual
behaviour in fires.

VARIATIONS FROM THE TESTED SPECIMENS


This report details the methods of construction, the test conditions and the results
obtained when the specific element of construction described herein was tested
following the procedure outlined in BS 476: Parts 20 & 22: 1987. Any significant
variation with respect to size, constructional details, loads, stresses, edge or end
conditions, other than those allowed under the field of direct application in the
relevant test method, is not addressed by this report. It is recommended that any
proposed variation to the tested configuration should be referred to the test
sponsor in the first instance to obtain appropriate documentary evidence of
compliance from Warrington Fire Research or another Registered Testing
Authority.

UNCERTAINTY OF MEASUREMENT
Because of the nature of fire resistance testing and the consequent difficulty in
quantifying the uncertainty of measurement of fire resistance, it is not possible to
provide a stated degree of accuracy of the result.

C ON SU L T AN C Y • TESTING
WFRA Report No 2208900
Issue Number 2208900a.1
Page 13 of 37

APPENDIX 1 DRAWINGS OF TEST ASSEMBLY

UNEXPOSED FACE ELEVATION


OPENINGS FOR DOORSETS WITHIN MASONRY WALL

Figure A1.1: Test Assembly Drawing

C ON SU L T AN C Y • TESTING
WFRA Report No 2208900
Issue Number 2208900a.1
Page 14 of 37

UNEXPOSED FACE ELEVATION


DOORSET INSTALLATION

Figure A1.2: Door Frame Fixing Locations

C ON SU L T AN C Y • TESTING
WFRA Report No 2208900
Issue Number 2208900a.1
Page 15 of 37

Figure A1.3: Doorset Constructional Drawing (Provided By Client)

C ON SU L T AN C Y • TESTING
WFRA Report No 2208900
Issue Number 2208900a.1
Page 16 of 37

Figure A1.4: Doorset Frame & Leaf Sectional Drawing (Provided By Client)

C ON SU L T AN C Y • TESTING
WFRA Report No 2208900
Issue Number 2208900a.1
Page 17 of 37

Figure A1.5: Doorset bottom Sectional Drawing (Provided By Client)

C ON SU L T AN C Y • TESTING
WFRA Report No 2208900
Issue Number 2208900a.1
Page 18 of 37

Figure A1.6: Lorient Intumescent Kit (Provided By Client)

C ON SU L T AN C Y • TESTING
WFRA Report No 2208900
Issue Number 2208900a.1
Page 19 of 37

APPENDIX 2 TEST OBSERVATIONS


Time
Observation
Min Sec

DOOR A
0 00 Fire Resistance Test was commenced and ambient air temperature
was approximately 20°C.
2 03 Smoke emission was evident from the latchset of the doorset.
2 15 Smoke emission had ceased.
3 45 Smoke emission was evident from all edges of the doorset.
4 38 Smoke emission was evident from all edges of the doorset.
3 52 Smoke emission from the doorset had ceased.
7 09 Smoke emission had reduced with emission evident from the top half
of the hinge side.
10 47 Smoke emission was evident from the top RH corner of the doorset
and middle hinge location.
13 40 Smoke emission was evident from the perimeter of the doorset.
13 58 Small amount of smoke emission evident from perimeter with some
smoke emission from wall door jamb interface.
15 10 Puffs of smoke were evident from under each doorset, stopped
almost immediately.
22 00 Small amount of smoke emission evident from wall door jamb
interface.
30 00 Doorset continued to maintain integrity in accordance with
BS 476: Part 22: 1987.
30 34 Small amount of smoke emission evident from top LH corner of
doorset.
35 06 Intermittent flaming evident on bottom edge of doorset.
36 25 Flaming of unexposed face of doorset was initiated at bottom RH
corner of door leaf.
Sustained flaming of specimen continued for a period of not
36 35 less than 10 seconds. Integrity failure of Door A in accordance
with BS 476: Part 22: 1987. Flaming was extinguished.
38 04 Sustained flaming of specimen continued for a period of not less
than 10 seconds at latchset. Flaming was extinguished.
38 57 Sustained flaming of specimen continued for a period of not less
than 10 seconds at latchset. Flaming was extinguished.
42 24 Fire resistance test was terminated at the request of the test
sponsor.

C ON SU L T AN C Y • TESTING
WFRA Report No 2208900
Issue Number 2208900a.1
Page 20 of 37

Time
Observation
Min Sec

DOOR B
0 00 Fire Resistance Test was commenced and ambient air temperature
was approximately 19°C.
1 41 Smoke emission was evident from the top RH corner of the doorset.
3 25 There was an increase in the amount of smoke emission.
3 45 Smoke emission was evident from all edges of the doorset.
4 09 Smoke emission was evident only from the top RH corner of the
doorset.
5 45 Smoke emission had dramatically reduced with emission evident
from the top of the doorset only.
6 21 Cotton pad was applied to the top RH corner of the doorset for a
period of approximately 15 seconds and no discolouration was
evident.
10 12 Smoke emission was evident from top RH corner of doorset and
below top hinge.
There was a reduction in the amount of smoke emission from the top
13 19
RH corner of the doorset.
Smoke emission was evident from top RH corner of doorset, below
14 50
top hinge and around middle hinge.
There was a slight increase in the amount of smoke emission from
18 32
the top hinge and top RH corner of doorset.
20 05 Smoke emission evident from middle hinge location.
25 19 Possible charring of door jamb near top hinge location was evident.
Cotton pad was applied to the top hinge location of the doorset for a
26 19 period of approximately 15 seconds and no discolouration was
evident.
28 04 Discolouration of door jamb near middle hinge location was evident.
30 00 Doorset continued to maintain integrity in accordance with
BS 476: Part 22: 1987.
Intermittent flaming on unexposed side evident at bottom LH side of
31 09
doorset.
Cotton pad was applied to the top RH corner of the doorset for a
31 31 period of approximately 15 seconds and no discolouration was
evident.
Glowing of frame behind leaf was evident at bottom RH corner of
32 13
doorset.
Cotton pad was applied to the bottom RH corner of the doorset for a
32 47 period of approximately 15 seconds and no discolouration was
evident.

C ON SU L T AN C Y • TESTING
WFRA Report No 2208900
Issue Number 2208900a.1
Page 21 of 37

Time
Observation
Min Sec
Intermittent flaming on unexposed side evident at bottom LH side of
33 30
doorset.
Intermittent flaming on unexposed side evident at bottom LH side of
34 15
doorset.
34 20 Intermittent flaming on exposed side evident at bottom of doorset.
Cotton pad was applied to the top RH corner of the doorset for a
35 47 period of approximately 15 seconds and no discolouration was
evident.
40 25 Glowing of bottom timber edge strip was evident
41 07 Glowing embers had fallen from doorset.
Flaming of unexposed face of doorset was initiated at bottom RH
41 19
corner of door leaf.
Sustained flaming of specimen continued for a period of not
41 29 less than 10 seconds. Integrity failure of Door A in accordance
with BS 476: Part 22: 1987. Flaming was extinguished.
42 24 Fire resistance test was terminated at the request of the test
sponsor.

The above observations include observations of the significant behaviour of the specimen.

C ON SU L T AN C Y • TESTING
WFRA Report No 2208900
Issue Number 2208900a.1
Page 22 of 37

APPENDIX 3 INSTRUMENTATION POSITIONS

C11
A11
B11 B6 C6
A12

B1 B2
C1 C2

B3 B12 C10 C3 C12


B9 C9
B10 B8
C8
B5 C5
B4 C4

B7 C7

Figure A3.1: Thermocouple Locations


Table A3.1: Thermocouple Locations
Leaf A Leaf B
Location Location
T/C Description T/C Description
X y x y
B1 287 1775 Upper west quarter point. C1 280 1770 Upper west quarter point.
B2 770 1775 Upper east quarter point. C2 780 1770 Upper east quarter point.
B3 528 1170 Midpoint. C3 530 1180 Midpoint.
B4 287 585 Lower west quarter point. C4 280 590 Lower west quarter point.
B5 770 585 Lower east quarter point. C5 780 590 Lower east quarter point.
B6 960 2287 Top east corner 50mm C6 980 2302 Top east corner 50mm
from edges of leaf. from edges of leaf.
B7 960 50 Bottom east corner C7 980 50
Bottom east corner 50mm
50mm from edges of
from edges of leaf.
leaf.
B8 895 1005 50mm west of latch. C8 895 1005 50mm west of latch.
B9 970 1080 50mm above latch. C9 970 1080 50mm above latch.
A11 100 2302 Behind closer
A12 262 2232 50mm below closer
Door frame A Door frame B
B10 22 1190 West midpoint C10 22 1190 West midpoint
B11 530 2360 Top midpoint C11 530 2360 Top midpoint
B12 1038 1190 East midpoint C12 1038 1190 East midpoint

C ON SU L T AN C Y • TESTING
WFRA Report No 2208900
Issue Number 2208900a.1
Page 23 of 37

DA1 DAF1

DBF1
DB1

DAC DBC

DA2 DBF2
DAF2
DB2

Figure A3.2: Deflection measurement Locations

Table A3.2: Deflection Locations


Doorset A Doorset B
Location Location
T/C Description T/C Description
X y x y
DA1 945 2272 Upper east corner of DB1 960 1967 Upper east corner of
leaf. leaf.
DAF1 1038 2207 Upper east corner of DBF1 1038 2017 Upper east corner of
frame. frame.
DAC 528 1190 Midpoint. DBC 528 1190 Midpoint.
DA2 945 100 Lower east corner of DB2 960 70 Lower east corner of
leaf. leaf.
DAF2 1038 70 Lower east corner of DBF2 1038 110 Lower east corner of
frame. frame.

C ON SU L T AN C Y • TESTING
WFRA Report No 2208900
Issue Number 2208900a.1
Page 24 of 37

DOOR A EXPOSED FACE ELEVATION

Figure A3.3: Doorset A Clearance measurements

C ON SU L T AN C Y • TESTING
WFRA Report No 2208900
Issue Number 2208900a.1
Page 25 of 37

DOOR B UNEXPOSED FACE ELEVATION

Figure A3.4: Doorset B Clearance measurements

C ON SU L T AN C Y • TESTING
WFRA Report No 2208900
Issue Number 2208900a.1
Page 26 of 37

APPENDIX 4 TEST DATA


A 4.1 FURNACE TEMPERATURE

1200

1000
Temperature (°C)

800

600

400

200

0
0 5 10 15 20 25 30 35 40 45
Time (Minutes)
BS 476: Part 20: 1987 Mean Furn Max Furn Min Furn

Figure A4.1: Furnace Temperatures vs. Time.

A 4.2 FURNACE PRESSURE

Time Pressure (Pa) Time Pressure (Pa)


(mins) Average (mins) Average
5-10 5 25-30 -1
10-15 5 30-35 -1
15-20 3 35-40 0
20-25 2 40-45 0

Note: Furnace pressure was measured at a position approximately 1000mm


above sill level.

C ON SU L T AN C Y • TESTING
WFRA Report No 2208900
Issue Number 2208900a.1
Page 27 of 37

A 4.3 SPECIMEN TEMPERATURES

200
180
160
Temperature (°C)

140
120
100
80
60
40
20
0
0 5 10 15 20 25 30 35 40 45
Time (Minutes)

B1 B2 B3 B4 B5 Integrity Limit

Figure A4.2: Door A Quarter point Temperatures vs. Time

200
180
160
Temperature (°C)

140
120
100
80
60
40
20
0
0 5 10 15 20 25 30 35 40 45
Time (Minutes)

Average Integrity Limit

Figure A4.3: Average of Door A Quarter point Temperatures


(B1 up to and including B5) vs. Time

C ON SU L T AN C Y • TESTING
WFRA Report No 2208900
Issue Number 2208900a.1
Page 28 of 37

200
180
160
Temperature (°C)

140
120
100
80
60
40
20
0
0 5 10 15 20 25 30 35 40 45
Time (Minutes)

B6 B7 B8 B9 Integrity Limit

Figure A4.4: Door A Miscellaneous Temperatures vs. Time

200
180
160
Temperature (°C)

140
120
100
80
60
40
20
0
0 5 10 15 20 25 30 35 40 45
Time (Minutes)

B10 B11 B12 Integrity Limit

Figure A4.5: Door A Doorframe Temperatures vs. Time

C ON SU L T AN C Y • TESTING
WFRA Report No 2208900
Issue Number 2208900a.1
Page 29 of 37

200
180
160
Temperature (°C)

140
120
100
80
60
40
20
0
0 5 10 15 20 25 30 35 40 45
Time (Minutes)

C1 C2 C3 C4 C5 Integrity Limit

Figure A4.6: Door B Quarter point Temperatures vs. Time

200
180
160
Temperature (°C)

140
120
100
80
60
40
20
0
0 5 10 15 20 25 30 35 40 45
Time (Minutes)

Average Integrity Limit

Figure A4.7: Average of Door B Quarter point Temperatures


(C1 up to and including C5) vs. Time

C ON SU L T AN C Y • TESTING
WFRA Report No 2208900
Issue Number 2208900a.1
Page 30 of 37

200
180
160
Temperature (°C)

140
120
100
80
60
40
20
0
0 5 10 15 20 25 30 35 40 45
Time (Minutes)
A11 A12 C6 C7
C8 C9 Integrity Limit
Figure A4.8: Door B Miscellaneous Temperatures vs. Time

200
180
160
Temperature (°C)

140
120
100
80
60
40
20
0
0 5 10 15 20 25 30 35 40 45
Time (Minutes)

B10 B11 B12 Integrity Limit

Figure A4.9: Door B Doorframe Temperatures vs. Time

C ON SU L T AN C Y • TESTING
WFRA Report No 2208900
Issue Number 2208900a.1
Page 31 of 37

Table A4.1: Test Specimen Temperatures

Temp (°C) at t (minutes) Limit1,2


3
Element T/C No. Description
t=0 t=15 t=30 t=36 (Mins)

Doorset A (Eastern Doorset)


B1 Top west 23 41 63 64 -
(1/4 & mid)

B2 Top east 23 39 62 64 -
Doorset

B3 Centre 23 38 60 62 -
B4 Bottom west 23 35 56 60 -
B5 Bottom east 23 35 57 61 -
B6 Top RH corner 23 39 69 75 -
B7 Bottom RH corner 22 32 67 81 -
Misc.

B8 LH side of latch 23 38 58 59 -
B9 Above latch 23 453 69 80 -
B10 West mid point 21 21 26 29 -
Frame

B11 Top mid point 21 23 30 36 -


B12 East mid point 21 21 32 35 -

1
Notes: Limit time is the time to the nearest whole minute, rounded down to the nearest minute, at which
the temperature recorded by the thermocouple does not rise by more than 180K above the initial
temperature.
2
Limit time is the time to the nearest whole minute, rounded down to the nearest minute, at which
the average temperature recorded by the thermocouples (quarter points) does not rise by more
than 140K above the initial average temperature.
3
Refer to Appendix 3 for locations of thermocouples as only a generic description is included in
the table.
‘-’ Under limit column indicates the temperature limit was not exceeded during the test period or up
until the time of integrity failure if a failure occurred.
# Indicates thermocouple fault.

C ON SU L T AN C Y • TESTING
WFRA Report No 2208900
Issue Number 2208900a.1
Page 32 of 37

Table A4.1: Test Specimen Temperatures (continued…)


Temp (°C) at t (minutes) Limit1,2
Element T/C No. Description3
t=0 t=15 t=30 t=41 (Mins)

Doorset B (Eastern Doorset)


C1 Top west 23 37 60 67 -
(1/4 & mid)

C2 Top east 23 38 60 65 -
Doorset

C3 Centre 23 37 60 65 -
C4 Bottom west 23 36 58 66 -
C5 Bottom east 23 35 57 63 -
A11 LH side of closer 23 33 60 70 -
Miscellaneous

A12 Below closer 23 40 63 71 -


C6 Top RH corner 22 30 58 67 -
C7 Bottom RH corner 21 26 49 69 -
C8 LH side of latch 22 34 62 66 -
C9 Above latch 22 32 59 69 -
C10 West mid point 22 27 48 75 -
Frame

C11 Top mid point 22 23 46 53 -


C12 East mid point 21 25 33 50 -

1
Notes: Limit time is the time to the nearest whole minute, rounded down to the nearest minute, at which
the temperature recorded by the thermocouple does not rise by more than 180K above the initial
temperature.
2
Limit time is the time to the nearest whole minute, rounded down to the nearest minute, at which
the average temperature recorded by the thermocouples (quarter points) does not rise by more
than 140K above the initial average temperature.
3
Refer to Appendix 3 for locations of thermocouples as only a generic description is included in the
table.
4
These thermocouples were close to the glazing feature therefore not used to measure the
insulation performance of the doorset in accordance with BS476: Part 22: 1987.
‘-’ Under limit column indicates the temperature limit was not exceeded during the test period or up
until the time of integrity failure if a failure occurred.
# Indicates thermocouple fault.

C ON SU L T AN C Y • TESTING
WFRA Report No 2208900
Issue Number 2208900a.1
Page 33 of 37

A 4.4 DEFLECTION MEASUREMENTS

25
20
15
10
Deflection (mm)

5
0
-5
-10
-15
-20
-25
-30
-35
-40
0 5 10 15 20 25 30 35 40 45
Time (Minutes)
DA1 DAF1 DAC DA2 DAF2

Figure A4.10: Out-of-Plane Deflection vs. Time of Doorset A


Positive measurements show movement of leaf towards furnace and negative
measurements show movement of leaf away from furnace.

25
20
15
10
Deflection (mm)

5
0
-5
-10
-15
-20
-25
-30
-35
-40
0 5 10 15 20 25 30 35 40 45
Time (Minutes)
DB1 DBF1 DBC DB2 DBF2

Figure A4.11: Out-of-Plane Deflection vs. Time of Doorset B


Positive measurements show movement of frame towards furnace and negative
measurements show movement of frame away from furnace.

C ON SU L T AN C Y • TESTING
WFRA Report No 2208900
Issue Number 2208900a.1
Page 34 of 37

A 4.5 HEAT FLUX MEASUREMENT

4
Irradiance (kW/m²)

0
0 5 10 15 20 25 30 35 40 45
Time (Minutes)

Recorded Radiation Emitted Radiation Integrity Limit

Figure A4.12: Heat flux emitted from Doorset A Vs Time


Radiometer located central to the door leaf at 1000mm away from the specimen.
Recorded radiation is radiation level at radiometer position and emitted radiation is
radiation level (calculated) emitted from face of door leaf

4
Irradiance (kW/m²)

0
0 5 10 15 20 25 30 35 40 45
Time (Minutes)

Recorded Radiation Emitted Radiation Integrity Limit

Figure A4.13: Heat flux emitted from Doorset B Vs Time


Radiometer located central to the door leaf at 1000mm away from the specimen.
Recorded radiation is radiation level at radiometer position and emitted radiation is
radiation level (calculated) emitted from face of door leaf

C ON SU L T AN C Y • TESTING
WFRA Report No 2208900
Issue Number 2208900a.1
Page 35 of 37

APPENDIX 5 PHOTOGRAPHS

Figure A5.1: Exposed face of test specimen prior to commencement of test

Figure A5.2: Unexposed face of test specimen prior to commencement of test

C ON SU L T AN C Y • TESTING
WFRA Report No 2208900
Issue Number 2208900a.1
Page 36 of 37

Figure A5.3: Sustained flaming evident at Figure A5.4: Sustained flaming evident at
bottom RH corner of Doorset A at 36’00” bottom of Doorset B at 41’00” test duration.
test duration. Integrity failure in accordance Integrity failure in accordance with
with BS476: Part 22: 1987 BS476: Part 22: 1987

Figure A5.5: Unexposed face of test specimen after completion of fire-resistance test

C ON SU L T AN C Y • TESTING
WFRA Report No 2208900
Issue Number 2208900a.1
Page 37 of 37

Figure A5.6: Exposed face after completion of fire-resistance test

C ON SU L T AN C Y • TESTING

Vous aimerez peut-être aussi