Vous êtes sur la page 1sur 9

Sand Trap Louvers

air master
Copyright reserved. Specifications subject to change without notice.
ISO 9002 certified company
Chapter1 3
A.Sand trap louvers
1. Sand trap louver...............................: ASTL..............13.1
2. Sand trap louver with filter. .................: ASTL+F...........13.2
3. Sand trap louver with damper...............: ASTL+D..........13.3
4. Sand trap louver with filter and damper...: ASTL+F+D.......13.4
5. Flush mounted sand trap louver. ...........: AFSTL............13.5
Standard sizes.......................................................13.6
Fixing details........................................................13.6
How to order.........................................................13.6
B.Performance Data
1. Sand rejection efficiency ..........................................13.7
2. %Efficiency Vs Face velocity. .....................................13.7
3. Face velocity Vs Total pressure drop......: Tab: 13.1.........13.8
4. Effective pressure area in square meters.: Tab: 13.2.........13.8
INDEX
Sand Trap Louvers
Construction:
Frame and blades: 1.5 mm and 1.2 mm thick
high quality extruded aluminium profiles.
Bird screen: 12 mm x 12 mm x 1.5 mm dia alu-
minium wire mesh as standard.
12 mm x 12 mm x 1 mm dia G.I wire mesh as
optional.
Drain: 20 mm dia self drain holes at the bottom
of the louver.
Description:
The frame and blades are of high quality extrud-
ed aluminium profiled construction with the
advantages of corrosion resistance and rigidity.
Composed two sets of inverted U channels
mounted vertically on two opposite rows.
Drain holes of diameter 20mm are provided in
two rows at the bottom of the louver for emptying
filtered sand and dust.
Can be manufactured from galvanized steel
sheets as option.
Designed to separate sand and dust from the air
stream.
Sand trap louver wih bird screen
Model: ASTL
air master
13.1
Copyright reserved. Specifications subject to change without notice.
ISO 9002 certified company
Generally used for ventilation applications and at
inlet duct of air handling unit.
Standard finishes:
Natural aluminium anodized finish.
Finish as per RAL colour codes.
Flexibility of finishing available on option.
Construction:
Frame and blades: 1.5 mm and 1.2 mm thick
high quality extruded aluminium profiles.
Bird screen: 12 mm x 12 mm x 1.5 mm dia alu-
minium wire mesh as standard.
12 mm x 12 mm x 1 mm dia G.I wire mesh as
optional.
Drain: 20 mm dia self drain holes at the bottom
of the louver.
Filter frame: 20 gauge aluminium sheet.
Filter media: Expanded Aluminium media.
Description:
The frame and blades are of high quality extrud-
ed aluminium profiled construction with the
advantages of corrosion resistance and rigidity.
Composed two sets of inverted U channels
mounted vertically on two opposite rows.
Drain holes of diameter 20mm are provided in
two rows at the bottom of the louver for emptying
filtered sand and dust.
Fixed with a removable washable extruded alu-
minium filter with aluminium mesh as the filter
media.
Filters are available at 12, 25, 40 and 50 mm
thickness as required.
air master
13.2
Copyright reserved. Specifications subject to change without notice.
Sand Trap Louvers
Sand trap louver with filter
Model: ASTL+F
Total assembly is designed to operate at medium
and high velocities with high dust holding capac-
ity at low resistance to air flow.
Can be manufactured from galvanized steel
sheets as option.
Design to separate sand and dust from the air
stream. Generally used for ventilation applica-
tions and at inlet duct of air handling unit.
Standard finishes:
Natural aluminium anodized finish.
Finish as per RAL colour codes.
Flexibility of finishing available as option.
Construction:
Frame and blades: 1.5 mm and 1.2 mm thick
high quality extruded aluminium profiles.
Bird screen: 12 mm x 12 mm x 1.5 mm dia alu-
minium wire mesh as standard.
12 mm x 12 mm x 1 mm dia G.I wire mesh as
optional.
Drain: 20 mm dia self drain holes at the bottom
of the louver.
Damper: Galvanized steel sheet construction.
Damper blades: High quality extruded alumini-
um profiles.
Description:
Manufactured from high quality extruded alu-
minium profiles with the advantages of corrosion
resistance and rigidity.
Composed two sets of inverted U - channels
mounted vertically on two opposite rows.
Drain holes of diameter 20 mm are provided in
two rows at the bottom of the louver for emptying
filtered sand and dust.
Fixed with a removable volume control damper to
ensures positive control over the fresh air stream.
air master
13.3
Copyright reserved. Specifications subject to change without notice.
Sand Trap Louvers
Sand trap louver with damper
Model: ASTL+D
Damper can be operated manually from the back
of the louver or can be motor operated.
Designed to separate sand and dust from the air
stream. Generally used for ventilation applica-
tions and at inlet duct of air handling unit.
Standard finishes:
Natural aluminium anodized finish.
Finish as per RAL colour codes.
Flexibility of finishing available as option.
Construction:
Frame and blades: 1.5 mm and 1.2 mm thick
high quality extruded aluminium profiles.
Bird screen: 12 mm x 12 mm x 1.5 mm dia alu-
minium wire mesh as standard.
12 mm x 12 mm x 1 mm dia G.I wire mesh as
optional.
Drain: 20 mm dia self drain holes at the bottom
of the louver.
Damper: Galvanized steel sheet construction.
Damper blades: High quality extruded alumini-
um profiles.
Filter frame: 20 gauge aluminium sheet.
Filter media: Aluminium mesh.
Description:
The frame and blades are of high quality extrud-
ed aluminium profiled construction with the
advantages of corrosion resistance and rigidity.
Composed two sets of inverted U channels
mounted vertically on two opposite rows.
Drain holes of diameter 20 mm are provided in
two rows at the bottom of the louver for emptying
filtered sand and dust.
Fixed with a removable filter and volume control
damper which ensures positive control over the
fresh air stream.
air master
13.4
Copyright reserved. Specifications subject to change without notice.
Sand Trap Louvers
Sand trap louver with damper and filter
Model: ASTL+D+F
Dampter can be operated manually by a project-
ed lever or can be motor operated.
Aluminium filters with washable expanded alu-
minium media, as the filter media are available in
12, 25, 40 and 50 mm thickness as required.
Designed to separate sand and dust from the air
stream. Generally used for ventilation applica-
tions and at inlet duct of air handling unit.
Standard finishes:
Natural aluminium anodized finish.
Finish as per RAL colour codes.
Flexibility of finishing available as option.
High Efficiency Sand Trap Louver
Model: ASTL-HE
Copyright reserved. Specifications subject to change without notice.
2003 Rev. 1
ISO 9002 certified company
Sand Trap Louvers
13.4a
Construction:
Frame: 2mm thick extruded aluminium formed sheets.
Blades: 6063 high grade aluminium blade 2mm thick.
Sand Chute: 1.5mm thick aluminium sheet.
Description:
Designed to filter sand particles at high intake velocities, as
high as 4m/sec with high efficiency which is more than 90%
and lesser pressure drop.
It has the advantage of more free area so that sizes of usual
sand trap louvers can be reduced to 25% of the normal sizes.
Composed of a row of blades mountred vertically inside the
frame.
Designed to seperate sand and dust from the air stream.
The filtered sand will be drained through a sand chute fixed at
the bottom of the louver.
Generally used for ventilation applications and at inlet duct of
air handling unit.
Standard finishes:
Natural anodized aluminium finish.
Powder coated color finish as per RAL color codes.
Flexibility of finish available as option.
Pressure loss vs Face velocity
% Retained vs Face velocity
A - 25mm blade spacing / 200-700 micron sand
B - 25mm blade spacing / 20-200 micron sand
C - 40mm blade spacing / 200-700 micron sand
D - 40mm blade spacing / 20-200 micron sand
Construction:
Frame and blades: 1.5 mm and 1.2 mm thick
high quality extruded aluminium profiles.
Bird screen: 12 mm x 12 mm x 1.5 mm dia alu-
minium wire mesh as standard.
12 mm x 12 mm x 1 mm dia G.I wire mesh as
optional.
Sand chute: Aluminium sheet tray of 1.2 mm
thick.
Description:
The frame and blades are of high quality extrud-
ed aluminium profiled construction with the
advantages of corrosion resistance and rigidity.
Composed two sets of inverted U channels
mounted vertically on two opposite rows.
Surface of the louver is fixed flush on the plane of
the wall. The filtered sand will be drained through
a sand chute.
Sand chute is an inclined tray fixed at the bottom
of the louver for sand drain.
Designed to separate sand and dust from the air
stream.
Generally used for ventilation applications and at
inlet duct of air handling unit.
air master
13.5
Copyright reserved. Specifications subject to change without notice.
Sand Trap Louvers
Flush mouned sand trap louver
Model: AFSTL
Standard finishes:
Natural aluminium anodized finish.
Finish as per RAL colour codes.
Flexibility of finishing available as option.
13.6
Copyright reserved. Specifications subject to change without notice.
air master
Sand Trap Louvers
Standard Sizes:
Available in square and rectangular sizes.
All combinations of width x height.
Non Standard sizes are available.
Fixing details:
Concealed screw fixing as per the site conditions.
Ordering example:
To select sand trap louver, damper and filter assembly, of size 1200 x 900 mm, quantity : 75 nos, wih
aluminium anodized finish..
Order as : ASTL+F+D-1200 x900 - 75 - A.
Width in mm 150 300 450 600 750 900 1050 1200 1350 1500
Height in mm 150 300 450 600 750 900 1050 1200 1350 1500
How to order:
Model
ASTL
AFSTL
A c c e s s o r i e s
F = filter
D = damper
D+F = damper and filter
Finish
A = Aluminium anodized finish.
B = RAL - 9010
C = Other RAL colours.
Size
Specify listed size
Width x Height
in mm x mm
Quantity
Specify in
numbers
13.7
Copyright reserved. Specifications subject to change without notice.
air master
Sand Trap Louvers
Performance data:
1. Sand rejection efficiency:
Tests conducted on sim ilar equipm ent as
M odel A STL indicate a typical efficiency of
90 percent on 200 to 700 microns
80 percent on 20 to 200 microns
50 percent on 1 to 70 microns
Better efficiency can be achieved by sand trap lou-
vers with washable aluminium filters.
% Efficiency Vs Face velocity in m/sec.
Model : ASTL
Pressure loss vs Face velocity
Model : ASTL & ASTL+F